MAKING MODERN LIVING POSSIBLE © Danfoss A/S (MWA), 2015-02 DKRCI.PD.GH0.A7.02 / 520H0764 1 Technical brochure Liquid level regulating valves PMFL / PMFH and SV Features Applicable to HCFC, HFC and R717 (Ammonia). PMFL/PMFH are based on PM valve family housings Same flange programme as for PM valve series Valve housing in low temperature cast iron (spherical) - EN GJS 400-18-LT Manual operation possible Position indicator available For modulating liquid level control in refrigeration, freezing and air conditioning plant, a system comprising a liquid level regulating valve type PMFL or PMFH, controlled by a pilot float valve type SV, is used. PMFL and SV systems are used on the evaporator side. PMFH and SV systems are used on the condenser side. The system is suitable for use with ammonia or fluorinated refrigerants. The PMFL and PMFH can be used in liquid lines to or from • evaporators • separators • intermediate coolers • condensers • receivers Modulating liquid level regulation provides liquid injection that is proportional to the actual capacity. This gives a constant amount of flashgas, thus ensuring stable regulation and economic operation because variations in pressure and temperature are held to a minimum. Pressure gauge connection to monitor inlet pressure Simple installation Main valve top cover can be located in any position without affecting the function Pressure Equipment Directive (PED) The PMFL / PMFH valves are approved and CE marked in accordance with Pressure Equipment Directive - 97/23/EC. For further details / restrictions - see Installation Instruction. * CE is only applicable to the EN GJS 400-18-LT PMFL/PMFH-valves* Nominal bore DN25 (1 in.) DN 32-125 mm (1 1 / 4 - 5 in.) DN 150 mm (6 in.) Classified for Fluid group I Catagory Article 3, paragraph 3 II III Approvals

Upload: volien

Post on 02-Apr-2018

227 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

MAKING MODERN LIVING POSSIBLE

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GH0.A7.02 / 520H0764 1

Technical brochure

Liquid level regulating valvesPMFL / PMFH and SV

Features Applicable to HCFC, HFC and R717 (Ammonia). PMFL/PMFH are based on PM valve family housingsSame flange programme as for PM valve seriesValve housing in low temperature cast iron (spherical) - EN GJS 400-18-LTManual operation possiblePosition indicator available

For modulating liquid level control in refrigeration, freezing and air conditioning plant, a system comprising a liquid level regulating valve type PMFL or PMFH, controlled by a pilot float valve type SV, is used.

PMFL and SV systems are used on the evaporator side. PMFH and SV systems are used on the condenser side.The system is suitable for use with ammonia orfluorinated refrigerants. The PMFL and PMFH can be used in liquid lines to or from• evaporators• separators• intermediate coolers• condensers• receivers

Modulating liquid level regulation provides liquid injection that is proportional to the actual capacity. This gives a constant amount of flashgas, thus ensuring stable regulation and economic operation because variations inpressure and temperature are held to a minimum.

Pressure gauge connection to monitor inlet pressureSimple installationMain valve top cover can be located in any position without affecting the function

Pressure Equipment Directive (PED)The PMFL / PMFH valves are approved and CEmarked in accordance with Pressure Equipment

Directive - 97/23/EC.For further details / restrictions - see InstallationInstruction.

* CE is only applicable to the EN GJS 400-18-LT

PMFL/PMFH-valves*

Nominal bore DN≤ 25 (1 in.) DN 32-125 mm (11/4 - 5 in.) DN 150 mm (6 in.)

Classified for Fluid group I

Catagory Article 3, paragraph 3 II III

Approvals

Page 2: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

2 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

Technical data RefrigerantsApplicable to HCFC, HFC and R717 (Ammonia).

Max. working pressurePMFL / H: MWP = 28 barSV: MWP = 28 bar

Max. test pressurePMFL / H: Max. test pressure = 42 barSV: Max. test pressure = 42 bar

Temperature of media: –60°C to +120°C.

Note: Max. working pressure is limited toMWP = 21 bar when media temperatures are:below –20°C for valves made of GGG-40.3 andbelow –10°C for valves made of GG-25.

Page 3: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GE0.C7.02 / 520H3489 3

Liquid level regulating valves, types PMFL / PMFH and SV

Design/Function

PMFL

6. Seal plug10. Valve spindle12. Valve seat19. Valve body19a. Channel in valve body20. Bottom cover23. Main spring24. Servo piston24a. Channel in servo piston30. Top cover30a.b.c. Channels in top cover31. Valve cone43. Supplementary spring44. Manometer connection53. Spindle cap60. Setting spindle73. Pilot connection

When the liquid level inside the float drops, the float orifice opens. This relieves the higher pressure, ps, acting on the servo piston to the low pressure side causing the PMFL to open. Variations in liquid level will result in variations

The setting spindle, pos. 60, has not been set from factory. It is imperative that the setting spindle is adjusted before the valve is put into operation. The outer spring, pos. 23, is preset and the inner spring, pos. 43, is adjusted when

in pressure over the piston and variation in the amount of liquid injected. It is important to choose the correct spring set when designing the plant. The spring set should be selected from the table below:

turning the spindle. The following tables shows the adjustment of the inner spring in number of turns of the spindle as a function of valve size, spring type and pressure difference:

PMFL

→ To SV float

SubcoolingPressure difference over main valve

bar psi bar psi

K F 4 - 15 58 - 218 1.2 - 4.0 17 - 58

0 - 8 0 - 14 Normal spring set Weak spring set

8 - 40 14 - 72 Strong spring set

PMFL

C/w normal (factory mounted) spring set, subcooling 0-8 K ~ 0-14 F

Pressure difference (Dp) over PMFL in bar or psi

< 5 bar 5 - 8 bar 8 - 10 bar 10 - 12 bar > 12 bar

< 72 psi 72 - 116 psi 116 - 145 psi 145 - 174 psi > 174 psi

80 No tension 2 - 3 3 - 4.5 4.5 - 6 ca. 7

125 No tension 3 - 5 5 - 7 7 - 9 ca. 10

200 No tension 3 - 5 5 - 7 7 - 9 ca. 10

300 No tension 4 - 6 6 - 9 9 - 12 ca. 14

PMFL

C/w strong spring set, subcooling 8-40 K ~ 14-72 F

Pressure difference (Dp) over PMFL in bar or psi

6 - 9 bar > 9 bar

87 - 131 psi > 131 psi

80 4 Max. tension

125 6 Max. tension

PMFL C/w stong spring set, subcooling 8-40 K ~ 14-72 F

Pressure difference (Dp) over PMFL in bar or psi

6 - 16 bar

87 - 232 psi

200Spring must always be set to max. tension

300

PMFL

C/w weak spring set, low pressure plants

Pressure difference (Dp) over PMFL in bar or psi

1.2 - 1.8 bar 1.8 - 2.5 bar 2.5 - 3 bar 3 - 4 bar

17 - 26 psi 26 - 36 psi 36 - 43 psi 43 - 58 psi

80 No tension 3 - 4 4 - 6 Max. tension

125 No tension 4 - 6 6 - 8 Max. tension

200 No tension 4 - 6 6 - 8 Max. tension

300 No tension 5 - 7 5 - 7 Max. tension

Page 4: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

4 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

Design/Function(continued)

The values for spindle turns are an indication foran initial setting only. If a position indicator is used, a more precise modulation can be achieved when fine tuning the valve setting. If the PMFL is not opening fully, the spring tension must be reduced. If the PMFL is operating in a ON/OFF function, the spring tension should be increased. The condenser pressure will have an effect on the fine tuning and large variations in condensing pressure might call for readjustment.The subcooling is measured just before the PMFLand the pressure difference is for the valve onlyexcluding piping and armatures.

The PMFL can be used together with SV 4 as a pilot valve.

The final choice of orifice may vary depending onrefrigerant and pressure levels. Smaller pressurelevels needs a bigger orifice. Pressure differencelevels below 3 bar (43 psi) need SV 4-6with Ø3 mm orifice.

PMFL function example

Low pressure float system(for explanatory purposes only)

SV 4 can be used for PMFL low pressure control system. The float must be connected as shown. Note: Only one inlet connection possible for SV 4.

SV floats for PMFL

The orifices determines the kv (Cv) value of the pilot and the following table can be used as an initial selection guide:

PMFLSV 4-6

Ø 2.5 Ø 3 (SV 4)

80 X

125 X

200 X

300 X

Inlet to SV 4 from PMFL

From compressor

To compressorFrom evaporator

Condenser Alarm Alarmfloat switch

Through type receiver

Liquid level

Overflowvalve

Filter

Oil drain valve

To evaporator

Page 5: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GE0.C7.02 / 520H3489 5

Liquid level regulating valves, types PMFL / PMFH and SV

SV 3 (1)

Design/Function(Continued)

PMFH

If the liquid level inside the SV float rises, the floatorifice opens and relieves pressure through thepilot line to the top of the PMFH, increasing thepressure, ps, moving the pushrod downwards and opening the PMFH. The pilot line is connected in the topcover at SI. Override of the pilot signal can be made by using an EVM valve at SII. It is important to choose the correct spring set when designing the plant. The spring set should be selected from the table below:

PMFH

PMFH function example

From low stagecompressor(s)

To high stagecompressor(s)

From high stagecompressor(s)

To low stageseparator

Condenser

Alarmfloatswitch

Intermediatepressurevessel

Liquid trapreceiver

Filter

Tocompressorcooling

High pressure float system(for explanatory purposes only)

Alarm

3. Manometer connection6. Seal plug10. Valve spindle19. Valve body19a. Channel in valve body20. Bottom cover21a. Channel in servo piston23. Main spring24. Servo piston30. Top cover30a.b.c. Channels in top cover31. Valve cone53. Spindle cap60. Manual opening73. Pilot connection

The PMFH can be used together with either SV 1or 3 with the SV mounted with the bleed valvedownwards, refer to the drawing below. Thisreverses the opening so that rising float opens the orifice.

Pressure difference over main valve

bar psi bar psi

0 - 4.5 0 - 65 > 4.5 > 65

Weak spring set Normal spring set

S-connection

P-connection

Page 6: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

6 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

SV 1-3 float has 2 different pilot connections: S-port (series connection with PMFH) or P-port (parallel connection with the PMFH).

P-port:When using the P-port, it is possible to force openthe PMFH valve to a fully open position. This ispractical for service purposes or to confirm if thefloat has sufficient capacity for the PMFH and theoperating conditions. However, when P-portconnection is used it is possible to overfill a system due to constant bleeding or unautorised tampering. In this case, it is advisable to introduce a shut off when the liquid level reaches

a preset point. Shut off can be done via an electrical switch if an EVM valve is mounted in the SII port in the top of the PMFH. It is only advisable to use the P-port at low pressure difference.

S-port:The S-port offers the advantage of a preorificewhich divides the pressure drop and any wearpossibility due to cavitation. S-port connection must be used at high pressure differences, dp > 10 bar (145 psi). The kv (Cv) value of the SV is higher using P-port than using S-port. A higher P-band can thus be obtained.

Design/Function(Continued)

SV 1-3

Sizing Sizing example for PMFL

RefrigerantR 717 (NH3)

Evaporator capacityQe = 600 kW

Evaporating temperaturete = −10°C (∼ pe = 2.9 bar abs.)

Condensing temperaturetc = +30°C (∼ pc = 11.9 bar abs.)

Liquid temperature ahead of valvetl = +20°C at max. capacity

Subcooling∆tsub = tc − tl = 30°C − 20°C = 10 KCalculations do not take into account pressureloss in pipelines.

Pressure drop across valve∆p = pc − pe = 11.9 bar − 2.9 bar = 9 bar

Correction factor for 10 K subcooling0.98

Corrected capacity600 kW × 0.98 = 588 kW

The corrected capacity can be found in thecapacity table. It will be seen from the table thatvalve type PMFL 80-4 should be chosen.Refering to “ordering table”, code number027F0053 can be found.For details of flanges, accessories and pilot valve,see the ordering table.

Since ∆p = 9 bar and ∆tsub = 10 K, it will beseen from the “C/w strong spring set” for PMFLthat a “STRONG” spring set must be used. Thepilot line is connected to SV at connection S. In the ordering table the code number for the spring set can be found: 027F0118.Sizing example for PMFH

RefrigerantR 717 (NH3)

Evaporator capacityQe = 2200 kW

Evaporating temperaturete = −10°C (∼ pe = 2.9 bar abs.)

Condensing temperaturetc = +30°C (∼ 11.9 bar abs.)

Liquid temperature ahead of valvetl = +20°C

Subcooling∆tsub = tc − tl = 30°C − 20°C = 10 KCalculations do not take into account pressureloss in pipelines.

Pressure drop across valve∆p = pc − pe = 11.9 bar − 2.9 bar = 9 bar

Correction factor for 10 K subcooling0.98

Corrected capacity2200 kW × 0.98 = 2156 kW

The corrected capacity can be found in thecapacity table. It will be seen from the table thatvalve type PMFH 80-7 should be chosen.In the ordering table the code number for thevalve can be found: 027F3060 for CE-approvedvalve.

For details of flanges, accessories and pilotvalve, see the ordering table.

Correction factorsWhen dimensioning, multiply the evaporatorcapacity by a correction factor k dependent on

the subcooling ∆tsub just ahead of the valve.The corrected capacity can then be found in the capacity table.

R 717 (NH3)∆t K 2 4 10 15 20 25 30 35 40 45 50

k 1.01 1.00 0.98 0.96 0.94 0.92 0.91 0.89 0.87 0.86 0.85

R 22∆t K 2 4 10 15 20 25 30 35 40 45 50

k 1.01 1.00 0.96 0.93 0.90 0.87 0.85 0.83 0.80 0.78 0.77

Page 7: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GE0.C7.02 / 520H3489 7

Liquid level regulating valves, types PMFL / PMFH and SV

Capacity in kWType Evaporating

temperature te

°C

Rated capacity in kWat pressure drop across valve Dp bar

Type Evaporatingtemperature te

°C

Rated capacity in kWat pressure drop across valve Dp bar

0.8 1.2 1.6 2.0 4.0 8.0 12.0 16.0

R 717 (NH3) R 717 (NH3)PMFL 80-1 +10

0−10−20−30−40−50

50515354555656

60626465666767

69717374757975

76798182838682

PMFL 80-1 +100

−10−20−30−40−50

104107110111111111109

140142143143143142140

161165166166165162160

176178179179177175

PMFL 80-2 +100

−10−20−30−40−50

80838586888990

97101103105106107106

111115118119120120119

123127130132133132131

PMFL 80-2PMFH 80-2

+100

−10−20−30−40−50

167172176177177175173

224227228238227225222

257264265264262258253

281284285284281277

PMFL 80-3 +100

−10−20−30−40−50

127131134137139140139

154159163164167166164

176182186188188187184

194201205207207205201

PMFL 80-3PMFH 80-3

+100

−10−20−30−40−50

264271276278276272267

353356357356353349343

404414416413407400393

440444445443438431

PMFL 80-4 +100

−10-20−30−40−50

206214219222224223219

250259264267267263257

286295301303301295288

316327333334330323315

PMFL 80-4PMFH 80-4

+100

−10-20−30−40−50

427438444445439429420

571573572568561552543

651664665657647635624

704709709704696685

PMFL 80-5 +100

−10−20−30−40−50

325336344347345338327

394406413414407396383

449463470468458444429

496511518514502486470

PMFL 80-5PMFH 80-5

+100

−10−20−30−40−50

667679685680666649632

887883874864852837823

1010102010201000984966948

108010801080107010601040

PMFL 80-6 +100

−10−20−30−40−50

565584591587571546520

682700705692666636608

773792795777746712684

851869871850816781751

P MFL 80-6PMFH 80-6

+100

−10−20−30−40−50

1130113011301110108010501020

1490146014301410138013601340

1670169016701640161015701540

178017801770176017301710

PMFL 80-7 +100

−10−20−30−40−50

881909910887844794750

1060108010701030975921875

119012101190115010901030984

1300131013001250119011301080

PMFL 80-7PMFH 80-7

+100

−10−20−30−40−50

1690167016601630158015301490

2220215020902050201019701940

2480250024702410235023002250

261026102610259025502510

PMFL 125 +100

−10−20−30−40−50

1400145014601450140013301260

1690173017401700163015501480

1910195019501930182017301660

2100214021402080199019001830

PMFL 125PMFH 125

+100

−10−20−30−40−50

2770277027702720265025702490

3650357035003430337033203260

4100414040904010392038403770

435043504340430042404180

PMFL 200 +100

−10−20−30−40−50

2250232023402310222021102000

2710277027802710259024802340

3060312031203030289027502630

3360342034103310316030202900

PMFL 200PMFH 200

+100

−10−20−30−40−50

4410442044004330421040803960

5810568055505450536052605170

6530659065106370624061105990

692069206900683067406640

PMFL 300 +100

−10−20−30−40−50

3420353035603500337031903030

4110421042104100391037103540

4650474047304590437041603980

4990518051705010478045604380

PMFL 300PMFH 300

+100

−10−20−30−40−50

6690669066606550636061705990

8810860084008240810079607820

9880998098509650943092409050

105001050010400103001020010000

PMFH 500 +100

−10−20−30−40−50

107001070010600104001010098309540

14100137001340013100129001270012400

15800159001570015400150001470014400

167001670016700165001630016000

Page 8: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

8 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

Capacity in kW (continued)

Type Evaporatingtemperature te

°C

Rated capacity in kWat pressure drop across valve Dp bar

Type Evaporatingtemperature te

°C

Rated capacity in kWat pressure drop across valve Dp bar

0.8 1.2 1.6 2.0 4.0 8.0 12.0 16.0

R 22 R 22PMFL 80-1 +10

0−10−20−30−40−50

11121212131313

13141515151616

15161717171818

17181819191919

PMFL 80-1 +100

−10−20−30−40−50

22232425252524

28293030303029

31323232323231

32333434333232

PMFL 80-2 100

−10−20−30−40−50

18192020212121

22232424252525

25262728282828

27293030313131

PMFL 80-2PMFH 80-2

100

−10−20−30−40−50

36383940404039

46474848484847

51525252525149

52535454535251

PMFL 80-3 100

−10−20−30−40−50

29303132333434

35363739394040

39414344444544

43464748484948

PMFL 80-3PMFH 80-3

100

−10−20−30−40−50

57606263636261

72747676767573

80828282817977

82848585838179

PMFL 80-4 100

−10−20−30−40−50

47495152545455

57596163646464

64677071727271

71747778787877

PMFL 80-4PMFH 80-4

100

−10−20−30−40−50

9498

1011021019997

118121123123122120117

130133133132130127124

133136138137134131127

PMFL 80-5 100

−10−20−30−40−50

74788083848484

89949699999997

102107110112112110108

112117121122122120117

PMFL 80-5PMFH 80-5

100

−10−20−30−40−50

147153157157156152148

184188190189187184179

202205205203199195189

206211212210206200194

PMFL 80-6 100

−10−20−30−40−50

129135140142143141137

156162167168167163158

177184188189186181175

194202206205202196189

PMFL 80-6PMFH 80-6

100

−10−20−30−40−50

251260263262257249241

310314315313308302294

341343341335328320312

345352353348340331321

PMFL 80-7 100

−10−20−30−40−50

202211216218215209200

242251256255249240230

273283286283275265254

299308311307298286275

PMFL 80-7PMFH 80-7

100

−10−20−30−40−50

381390393389378366353

466467465461454444433

510510504495483471458

515524523516503489473

PMFL 125 100

−10−20−30−40−50

321336346352352346335

386402412415410399386

437455464464455442426

479498507505494478461

PMFL 125PMFH 125

100

−10−20−30−40−50

620639647643628609589

763770771767755739720

837842835821804784762

847864865853834810785

PMFL 200 100

−10−20−30−40−50

515538555563561550532

618645660663653635612

700728742740725702677

767796810805786760732

PMFL 200PMFH 200

100

−10−20−30−40−50

9901020103010201000969937

1220123012301220120011701150

1330134013301310128012501210

1350138013801360133012901250

PMFL 300 100

−10−20−30−40−50

782819843855851833804

940980

10001010990961925

1060111011301120110010601020

1170121012301220119011501110

PMFL 300PMFH 300

100

−10−20−30−40−50

1500155015601550151014701420

1850186018601850182017801730

2020203020101980193018901830

2050208020902060201019501890

PMFH 500 100

−10−20−30−40−50

2410248025002480242023402260

2950297029702950290028402770

3240325032103160309030102930

3270333033303290321031203020

Page 9: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GE0.C7.02 / 520H3489 9

Liquid level regulating valves, types PMFL / PMFH and SV

Material specification

No. Part Material DIN/EN ISO ASTM

2 Gasket between body and flange

Non-metalNon-asbestos

3 Bolts for flange Stainless steel A2-70 A2-70 Type 308

4 Flange PM 5 - 65 Steel RSt. 37-2, 10025 Fe360 B, 630 Grade C, A 283

6 Plug Steel 9SMn281651

Type 2R683/9

1213SAE J 403

10 Valve spindle Steel 9SMn281651

Type 2R683/9

1213SAE J 403

12 Valve seat Teflon [PTFE]

19 Valve body Low temperature cast iron (spherical)

EN-GJS-400-18-LTEN-1693

20 Bottom cover Low temperature cast iron (spherical)

EN-GJS-400-18-LTEN-1693

23 Spring Steel

24 Servo piston Cast iron GG-25 Grade 250 Class 40B

30 Cover Low temperature cast iron (spherical)

EN-GJS-400-18-LTEN-1693

31 Trottle cone Steel 9SMn281651

Type 2R683/9

1213SAE J 403

32 Gasket between body and bottom cover

Non-metalNon-asbestos

34 Bolts for top and bottom cover

Stainless steel A2-70 A2-70 Type 308

41 Gasket Non-metalNon-asbestos

43 Spring Steel

53 Spindle cap Steel 9SMn281651

Type 2R683/9

1213SAE J 403

60 Setting / manual operating spindle

Steel 9SMn281651

Type 2R683/9

1213SAE J 403

73 Pilot connection Steel 9SMn281651

Type 2R683/9

1213SAE J 403

Material specification for PMFL/PMFH valves

PMFL PMFH

Page 10: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

10 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

Rated capacity in kW (1 kW = 0.284 TR)

The rated capacity is given at evaporating temperature te = +5°C, condensing temperature tc = +32°C and liquid temperature tl = +28°C.

Ordering

Main valve

The code nos. stated apply to main valves typePMFL or PMFH incl. flange gaskets, flange bolts,blanking plug and pilot connection with Ø6.5 / Ø10 mm weld nipple.

Weak/Strong

Spring set Special spring set for PMFL

Special spring set for PMFH

Valve type R 717 R 22 R 134a R 404A R 12 R 502

PMFL/H 80-1PMFL/H 80-2PMFL/H 80-3PMFL/H 80-4PMFL/H 80-5PMFL/H 80-6PMFL/H 80-7PMFL/H 125PMFL/H 200PMFL/H 300PMFL/H 500

139209348558835

13952080348055808350

13900

27.841.870

105174278435700

105017402780

22.135.353.188.9133221353552889

13332210

3349.782.7124207330569831

124320683300

17.427.841.870

105174278435700

10501740

3045.275.2113188300470755

113018803000

Valve typeCode no.

EN GJS 400-18-LT

PMFL 80-1 027F3054

PMFL 80-2 027F3055

PMFL 80-3 027F3056

PMFL 80-4 027F3057

PMFL 80-5 027F3058

PMFL 80-6 027F3059

PMFL 80-7 027F3060

PMFL 125 027F3061

PMFL 200 027F3062

PMFL 300 027F3063

Valve typeCode no.

EN GJS 400-18-LT

PMFH 80-2 027F3065

PMFH 80-3 027F3066

PMFH 80-4 027F3067

PMFH 80-5 027F3068

PMFH 80-6 027F3069

PMFH 80-7 027F3070

PMFH 125 027F3071

PMFH 200 027F3072

PMFH 300 027F3073

PMFH 500 027F3074

Subcooling Dtu

K

Pressure drop Dp in PMFL Pilot connection on SV 1-3

only

Pos. Type PMFL"WEAK" "STRONG"

4 → 15 bar 1.2 → 4 bar

Spring set Code no.

0-8 "STANDARD" "WEAK" P 23 + 43 80-1 → 80-7125200300

027F0123

027F0125 027F0126

027F0118 027F0119 027F0120

8-40 "STRONG" S

Pressure drop in PMFHDp bar

Type "WEAK"

Code no.

1 → 4

PMFH 80.1 → 7PMFH 125PMFH 200PMFH 300

027F2190027F2191027F2192027F2193

Page 11: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

© Danfoss A/S (MWA), 2015-02 DKRCI.PD.GE0.C7.02 / 520H3489 11

Liquid level regulating valves, types PMFL / PMFH and SV

Flanges 2)

Stainless steel: flanges, bolts for flanges and topand bottom covers, see spare parts catalogue.

Ordering(continued)

Pilot valves SV 1-3

Spare parts and accessoriesSmaller orifices for the SV 4 are availableas spare parts.− Seal kit: 027B2070

Special orifice code no. for SV 4

1) The code no. includes orifice and all necessary gaskets

Pilot valves SV 4

1) Flange for mounting without housing Code no. 027B2027.2) Approved and CE-marked in accordance with Pressure Equipment Directive - 97/23/EC.

The code nos. stated apply to liquid level regulators type SV 4, 5 and 6 with two 1” weld connections for balance tubes and two ½” weld joints for liquid and evaporator connections respectively.

Pilot valve kits (EVM and coil)Can be screwed on to the PMFL or PMFH insteadof the blanking plug.

Valve type Flange type Weld flanges Solder flanges

in. Code no. 1) in. Code no. 1) mm Code no. 1)

PMFL 80 /PMFH 80

12 3/4

111/4

027N1220027N1225027N1230

7/8

11/8

027L1223027L1229

2228

027L1222027L1228

PMFL 125 /PMFH 125

23 11/4

11/2

027N2332027N2340

13/8 027L2335 35 027L2335

PMFL 200 /PMFH 200

24 11/2

2027N2440027N2450

15/8 027L2441 42 027L2442

PMFL 300 /PMFH 300

25 221/2

027N2550027N2565

21/8 027L2554 54 027L2554

PMFH 500 26 21/2

3027N2665027N2680

25/8 027L2666 76 027L2676

1) Code no. applies to one flange set consisting of one inlet and one outlet flange.2) Dimension sketch see spare part catalogue.

Type Connection Code no.

Float pilot valvetype SV

Balance tubeliquid / vapour

Pilot line SV 1:027B2021027B2021CE 2)

SV 3:027B2023027B2023CE 2)1 in.

weldØ 6.5 / Ø 10 mm

weld 1)1) 3/8 in. flare connection can be supplied under code no. 027B2033.2) Approved and CE-marked in accordance with Pressure Equipment Directive - 97/23/EC.

Valve type Orifice diameter Code no.

Code no. without

housing1)

SV 4 Ø 3.0 mm 027B2024 2) 027B2014 2)

Orifice diameter kv Code no.1)

Ø 1.0 mm 0,026 027B2080

Ø 1.5 mm 0,06 027B2081

Ø 2.0 mm 0.10 027B2082

Ø 2.5 mm 0,16 027B2083

Ø 2.8 mm 0.20 027B2084

Coils, 10 W a.c.

a.c.: 027B1122xx

where xx can be

110 V, 60 Hz 21

220 V, 50 Hz 31

220 V, 50/60 Hz 32

240 V, 50 Hz 33

Page 12: Technical brochure Liquid level regulating valves PMFL ...files.danfoss.com/TechnicalInfo/Dila/01/DKRCI.PD.GE0.C7.02_PMFH... · Technical brochure Liquid level regulating valves

12 DKRCI.PD.GE0.C7.02 / 520H3489 © Danfoss A/S (MWA), 2015-02

Liquid level regulating valves, types PMFL / PMFH and SV

Optional accessoriesOrdering(continued) Description Code no.

Pressure gauge connectionØ 6.5 / Ø 10 mm weld / solder 027B2035

Pressure gauge connection1/4 in. flare (self-closing)(Must not be used in ammonia plant)

027B2041

Pressure gauge connectionCutting ring connection

6 mm10 mm

027B2063027B2064

Pressure gauge connection 1/4 NPT 027B2062

Manual operating unit for PMFL. Can be fitted in place of the regulator bottom plug 027F01283/8 in. flare pilot connection for SV 027B2033

Dimensions and weights

PMFL/PMFH

Type

H1

mmH2

mmH3

mmH4

mmH5

mmL

mmL1

mm

L5 max.

B1

mmB2

mmB3

mm

Weight excl. solenoid valve

kg10 Wmm

20 Wmm

PMFL PMFH

80 66 162 79 113 176 177 106 130 140 75 87 7.0

125 72 178 96 128 193 240 170 130 140 84 82 94 11.3

200 79 187 105 138 202 254 170 130 140 94 89 102 14.2

300 95 205 123 155 220 288 200 130 140 104 106 113 19.8

PMFH 500 109 227 146 176 242 342 250 130 140 127 113 135 28.3