technical atricle
TRANSCRIPT
-
8/10/2019 Technical Atricle
1/52
Technical Atricle
Engineering article useful for electrical and mechanical engineers prepared on the basis of practical experience in the
different industries.
Tuesday, 6 December 2011
Calculation of Electrical Maximum DemandAbstract:
The Electricity provider does charge the fixed charges on the basis of consumers maximum
Electrical Demand. Consumer shall restrict the power consumption under the contracted maximum
demand. This article furnishes calculation for Maximum Contract Demand.
1. Introduction:
The Electricity provider does record maximum demand in pre-defined interval (e.g. 30 minutes or 15
minutes) through duly sealed and calibrated energy meter. Generally Maximum Demand denotes in
kVA for billing purpose.
Consumer need to sanction Maximum demand from Electricity Provider considering type of industry
and operation pattern of the equipments. Consumer shall pay fixed charges on the basis of
Maximum Demand obtained from the provider i.e. the maximum rate at which an electrical power
has been consumed during any period of defined consecutive minutes in the billing month.
2. Analysis:
General Formula to calculate the Maximum Demand is described below:
Maximum Demand= Connected Load * Load Factor / Power Factor.
Where,
Connected Load = Total Connected load in the facility in kW.Load Factor = Utility Factor * Diversity Factor.Power Factor = System average Power Factor.
Example:
Total connected load of facility: 6500 kWLoad Factor: 0.4 (Considering steel plant type)
Power Factor: 0.95
Maximum Demand= 6500 * 0.4 / 0.95
= 2737 kVA
Utility Factor and Diversity Factor can be finding out by the Time Profile of load and usage of theequipment. All equipments of facility may not operate at similar time and also may not run with
full load.Hence, Diversity Factor in percentage = Installed load / running load.
http://engineeringarticle.blogspot.in/http://engineeringarticle.blogspot.in/ -
8/10/2019 Technical Atricle
2/52
3. Conclusion:
Consumer should sanction Maximum Demand after studying the load pattern of the electrical
installation. Obtaining higher Maximum Demand shall result higher minimum fixed charges plus
higher deposit, and if sanctioned Maximum Demand exceed than consumer shall confront penalty.Posted byKrishnasinh K. Jadeja at03:46
Email ThisBlogThis!Share to TwitterShare to FacebookShare to Pinterest
1 comment:
1.
Gopal30 June 2014 02:38
Very useful sir....
ReplyAdd commentLoad more...
Newer PostHome
Subscribe to:Post Comments (Atom)
Followers
Blog Archive
2012(2)o March(2)
2011(3)o December(3)
Diameter Calculation for Winder application. Harmonics Analysis and Remedy Calculation of Electrical Maximum Demand
About Me
Krishnasinh K. Jadeja
View my complete profile
Simple template. Powered byBlogger.
http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=emailhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=twitterhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=pinteresthttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=pinteresthttp://www.blogger.com/profile/05914051158026833644http://www.blogger.com/profile/05914051158026833644http://www.blogger.com/profile/05914051158026833644http://engineeringarticle.blogspot.in/2011/12/harmonics-analysis-and-remedy.htmlhttp://engineeringarticle.blogspot.in/http://engineeringarticle.blogspot.in/http://engineeringarticle.blogspot.in/http://engineeringarticle.blogspot.com/feeds/8681973715309719888/comments/defaulthttp://engineeringarticle.blogspot.com/feeds/8681973715309719888/comments/defaulthttp://engineeringarticle.blogspot.com/feeds/8681973715309719888/comments/defaulthttp://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://engineeringarticle.blogspot.in/2011/12/diameter-calculation-for-winder.htmlhttp://engineeringarticle.blogspot.in/2011/12/diameter-calculation-for-winder.htmlhttp://engineeringarticle.blogspot.in/2011/12/harmonics-analysis-and-remedy.htmlhttp://engineeringarticle.blogspot.in/2011/12/harmonics-analysis-and-remedy.htmlhttp://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/http://www.blogger.com/http://www.blogger.com/http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/http://www.blogger.com/profile/13575910658802546888http://www.blogger.com/profile/13575910658802546888http://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://engineeringarticle.blogspot.in/2011/12/harmonics-analysis-and-remedy.htmlhttp://engineeringarticle.blogspot.in/2011/12/diameter-calculation-for-winder.htmlhttp://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://engineeringarticle.blogspot.com/feeds/8681973715309719888/comments/defaulthttp://engineeringarticle.blogspot.in/http://engineeringarticle.blogspot.in/2011/12/harmonics-analysis-and-remedy.htmlhttp://www.blogger.com/profile/05914051158026833644http://www.blogger.com/profile/05914051158026833644http://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=pinteresthttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=twitterhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=twitterhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=emailhttp://www.blogger.com/share-post.g?blogID=8170236914779056158&postID=8681973715309719888&target=emailhttp://engineeringarticle.blogspot.in/2011/12/calculation-of-electrical-maximum.htmlhttp://www.blogger.com/profile/13575910658802546888 -
8/10/2019 Technical Atricle
3/52
Personal tools
Create account Log in
Special:Search
Views
Page
Talk
View source
History
Languages
About us
> Collaborative
platform
brought to you
by
Schneider
Electric> Helping to
design electrical
installations
according to
standards
as IEC60364
Estimation of actual maximum kVAdemandFrom Electrical Installation GuideJump to:navigation,search
General rules of electrical installation design
Electrical installation design methodology
Electrical installation rules, standards
o Definition of voltage ranges
o Electrical regulations and standardso Quality and safety of an electrical installation
o Environmental directives
Installed power loads - Characteristics
o Induction motors
o Resistive-type heating appliances and incandescent lamps
(conventional or halogen)
o Fluorescent lamps
http://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demand&type=signuphttp://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demand&type=signuphttp://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demandhttp://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enw/index.php?title=Talk:Estimation_of_actual_maximum_kVA_demand&action=edit&redlink=1http://www.electrical-installation.org/enw/index.php?title=Talk:Estimation_of_actual_maximum_kVA_demand&action=edit&redlink=1http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=edithttp://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=edithttp://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=historyhttp://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=historyhttp://ru.electrical-installation.org/ruwiki/%D0%9E%D1%86%D0%B5%D0%BD%D0%BA%D0%B0_%D0%BC%D0%B0%D0%BA%D1%81%D0%B8%D0%BC%D0%B0%D0%BB%D1%8C%D0%BD%D0%BE%D0%B9_%D0%BD%D0%B0%D0%B3%D1%80%D1%83%D0%B7%D0%BA%D0%B8_(%D0%BA%D0%92%D0%90)http://ru.electrical-installation.org/ruwiki/%D0%9E%D1%86%D0%B5%D0%BD%D0%BA%D0%B0_%D0%BC%D0%B0%D0%BA%D1%81%D0%B8%D0%BC%D0%B0%D0%BB%D1%8C%D0%BD%D0%BE%D0%B9_%D0%BD%D0%B0%D0%B3%D1%80%D1%83%D0%B7%D0%BA%D0%B8_(%D0%BA%D0%92%D0%90)http://cn.electrical-installation.org/cnwiki/%E5%AE%9E%E9%99%85%E6%9C%80%E5%A4%A7%E8%A7%86%E5%9C%A8%E5%8A%9F%E7%8E%87%E9%9C%80%E6%B1%82%E4%BC%B0%E7%AE%97http://cn.electrical-installation.org/cnwiki/%E5%AE%9E%E9%99%85%E6%9C%80%E5%A4%A7%E8%A7%86%E5%9C%A8%E5%8A%9F%E7%8E%87%E9%9C%80%E6%B1%82%E4%BC%B0%E7%AE%97http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#column-onehttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#column-onehttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#column-onehttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#searchInputhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#searchInputhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#searchInputhttp://www.electrical-installation.org/enwiki/General_rules_of_electrical_installation_designhttp://www.electrical-installation.org/enwiki/General_rules_of_electrical_installation_designhttp://www.electrical-installation.org/enwiki/Electrical_installation_design_methodologyhttp://www.electrical-installation.org/enwiki/Electrical_installation_design_methodologyhttp://www.electrical-installation.org/enwiki/Electrical_installation_rules,_standardshttp://www.electrical-installation.org/enwiki/Electrical_installation_rules,_standardshttp://www.electrical-installation.org/enwiki/Definition_of_voltage_rangeshttp://www.electrical-installation.org/enwiki/Definition_of_voltage_rangeshttp://www.electrical-installation.org/enwiki/Electrical_regulations_and_standardshttp://www.electrical-installation.org/enwiki/Electrical_regulations_and_standardshttp://www.electrical-installation.org/enwiki/Quality_and_safety_of_an_electrical_installationhttp://www.electrical-installation.org/enwiki/Quality_and_safety_of_an_electrical_installationhttp://www.electrical-installation.org/enwiki/Environmental_directiveshttp://www.electrical-installation.org/enwiki/Environmental_directiveshttp://www.electrical-installation.org/enwiki/Installed_power_loads_-_Characteristicshttp://www.electrical-installation.org/enwiki/Installed_power_loads_-_Characteristicshttp://www.electrical-installation.org/enwiki/Induction_motorshttp://www.electrical-installation.org/enwiki/Induction_motorshttp://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Fluorescent_lampshttp://www.electrical-installation.org/enwiki/Fluorescent_lampshttp://hto.power.schneider-electric.com/CBT/Apps/index.aspxhttp://blog.schneider-electric.com/power-management-metering-monitoring-power-quality/http://www.schneider-electric.com/site/home/index.cfm/ww/http://www.electrical-installation.org/enwiki/Main_Pagehttp://hto.power.schneider-electric.com/CBT/Apps/index.aspxhttp://blog.schneider-electric.com/power-management-metering-monitoring-power-quality/http://www.schneider-electric.com/site/home/index.cfm/ww/http://www.electrical-installation.org/enwiki/Main_Pagehttp://hto.power.schneider-electric.com/CBT/Apps/index.aspxhttp://blog.schneider-electric.com/power-management-metering-monitoring-power-quality/http://www.schneider-electric.com/site/home/index.cfm/ww/http://www.electrical-installation.org/enwiki/Main_Pagehttp://hto.power.schneider-electric.com/CBT/Apps/index.aspxhttp://blog.schneider-electric.com/power-management-metering-monitoring-power-quality/http://www.schneider-electric.com/site/home/index.cfm/ww/http://www.electrical-installation.org/enwiki/Main_Pagehttp://hto.power.schneider-electric.com/CBT/Apps/index.aspxhttp://blog.schneider-electric.com/power-management-metering-monitoring-power-quality/http://www.schneider-electric.com/site/home/index.cfm/ww/http://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Fluorescent_lampshttp://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Resistive-type_heating_appliances_and_incandescent_lamps_(conventional_or_halogen)http://www.electrical-installation.org/enwiki/Induction_motorshttp://www.electrical-installation.org/enwiki/Installed_power_loads_-_Characteristicshttp://www.electrical-installation.org/enwiki/Environmental_directiveshttp://www.electrical-installation.org/enwiki/Quality_and_safety_of_an_electrical_installationhttp://www.electrical-installation.org/enwiki/Electrical_regulations_and_standardshttp://www.electrical-installation.org/enwiki/Definition_of_voltage_rangeshttp://www.electrical-installation.org/enwiki/Electrical_installation_rules,_standardshttp://www.electrical-installation.org/enwiki/Electrical_installation_design_methodologyhttp://www.electrical-installation.org/enwiki/General_rules_of_electrical_installation_designhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#searchInputhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#column-onehttp://cn.electrical-installation.org/cnwiki/%E5%AE%9E%E9%99%85%E6%9C%80%E5%A4%A7%E8%A7%86%E5%9C%A8%E5%8A%9F%E7%8E%87%E9%9C%80%E6%B1%82%E4%BC%B0%E7%AE%97http://ru.electrical-installation.org/ruwiki/%D0%9E%D1%86%D0%B5%D0%BD%D0%BA%D0%B0_%D0%BC%D0%B0%D0%BA%D1%81%D0%B8%D0%BC%D0%B0%D0%BB%D1%8C%D0%BD%D0%BE%D0%B9_%D0%BD%D0%B0%D0%B3%D1%80%D1%83%D0%B7%D0%BA%D0%B8_(%D0%BA%D0%92%D0%90)http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=historyhttp://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&action=edithttp://www.electrical-installation.org/enw/index.php?title=Talk:Estimation_of_actual_maximum_kVA_demand&action=edit&redlink=1http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demandhttp://www.electrical-installation.org/enw/index.php?title=Special:UserLogin&returnto=Estimation+of+actual+maximum+kVA+demand&type=signup -
8/10/2019 Technical Atricle
4/52
> Our Experts
continuously
improve the
content.
> Collaboration
is open
to all.
To know more
Navigation
Main
page
How to
browse
andsearch
Interaction
Toolbox
Share it
Share on email
o Discharge lamps
o LED lamps & fixtures
Power loading of an installation
o Installed power (kW)
o Installed apparent power (kVA)
o Estimation of actual maximum kVA demando Example of application of factors ku and ks
o Choice of transformer rating
o Choice of power-supply sources
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV and LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions and selection
Overvoltage protection
Energy Efficiency in electrical distribution
Power Factor Correction
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential and other special locations
ElectroMagnetic Compatibility (EMC)
Contents
[hide]
1- Factor of maximum utilization (ku)
http://www.electrical-installation.org/enwiki/About%20the%20Electrical%20Installation%20Wikihttp://www.electrical-installation.org/enwiki/About%20the%20Electrical%20Installation%20Wikihttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Discharge_lampshttp://www.electrical-installation.org/enwiki/Discharge_lampshttp://www.electrical-installation.org/enwiki/LED_lamps_%26_fixtureshttp://www.electrical-installation.org/enwiki/LED_lamps_%26_fixtureshttp://www.electrical-installation.org/enwiki/Power_loading_of_an_installationhttp://www.electrical-installation.org/enwiki/Power_loading_of_an_installationhttp://www.electrical-installation.org/enwiki/Installed_power_(kW)http://www.electrical-installation.org/enwiki/Installed_power_(kW)http://www.electrical-installation.org/enwiki/Installed_apparent_power_(kVA)http://www.electrical-installation.org/enwiki/Installed_apparent_power_(kVA)http://www.electrical-installation.org/enwiki/Example_of_application_of_factors_ku_and_kshttp://www.electrical-installation.org/enwiki/Example_of_application_of_factors_ku_and_kshttp://www.electrical-installation.org/enwiki/Choice_of_transformer_ratinghttp://www.electrical-installation.org/enwiki/Choice_of_transformer_ratinghttp://www.electrical-installation.org/enwiki/Choice_of_power-supply_sourceshttp://www.electrical-installation.org/enwiki/Choice_of_power-supply_sourceshttp://www.electrical-installation.org/enwiki/Connection_to_the_MV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/Connection_to_the_MV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/Connection_to_the_LV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/Connection_to_the_LV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/MV_and_LV_architecture_selection_guidehttp://www.electrical-installation.org/enwiki/MV_and_LV_architecture_selection_guidehttp://www.electrical-installation.org/enwiki/LV_Distributionhttp://www.electrical-installation.org/enwiki/LV_Distributionhttp://www.electrical-installation.org/enwiki/Protection_against_electric_shockshttp://www.electrical-installation.org/enwiki/Protection_against_electric_shockshttp://www.electrical-installation.org/enwiki/Sizing_and_protection_of_conductorshttp://www.electrical-installation.org/enwiki/Sizing_and_protection_of_conductorshttp://www.electrical-installation.org/enwiki/LV_switchgear:_functions_and_selectionhttp://www.electrical-installation.org/enwiki/LV_switchgear:_functions_and_selectionhttp://www.electrical-installation.org/enwiki/Overvoltage_protectionhttp://www.electrical-installation.org/enwiki/Overvoltage_protectionhttp://www.electrical-installation.org/enwiki/Energy_Efficiency_in_electrical_distributionhttp://www.electrical-installation.org/enwiki/Energy_Efficiency_in_electrical_distributionhttp://www.electrical-installation.org/enwiki/Power_Factor_Correctionhttp://www.electrical-installation.org/enwiki/Power_Factor_Correctionhttp://www.electrical-installation.org/enwiki/Power_harmonics_managementhttp://www.electrical-installation.org/enwiki/Power_harmonics_managementhttp://www.electrical-installation.org/enwiki/Characteristics_of_particular_sources_and_loadshttp://www.electrical-installation.org/enwiki/Characteristics_of_particular_sources_and_loadshttp://www.electrical-installation.org/enwiki/PhotoVoltaic_(PV)_installationhttp://www.electrical-installation.org/enwiki/PhotoVoltaic_(PV)_installationhttp://www.electrical-installation.org/enwiki/Residential_and_other_special_locationshttp://www.electrical-installation.org/enwiki/Residential_and_other_special_locationshttp://www.electrical-installation.org/enwiki/ElectroMagnetic_Compatibility_(EMC)http://www.electrical-installation.org/enwiki/ElectroMagnetic_Compatibility_(EMC)http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Factor_of_maximum_utilization_.28ku.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Factor_of_maximum_utilization_.28ku.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Factor_of_maximum_utilization_.28ku.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Factor_of_maximum_utilization_.28ku.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Factor_of_maximum_utilization_.28ku.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/ElectroMagnetic_Compatibility_(EMC)http://www.electrical-installation.org/enwiki/Residential_and_other_special_locationshttp://www.electrical-installation.org/enwiki/PhotoVoltaic_(PV)_installationhttp://www.electrical-installation.org/enwiki/Characteristics_of_particular_sources_and_loadshttp://www.electrical-installation.org/enwiki/Power_harmonics_managementhttp://www.electrical-installation.org/enwiki/Power_Factor_Correctionhttp://www.electrical-installation.org/enwiki/Energy_Efficiency_in_electrical_distributionhttp://www.electrical-installation.org/enwiki/Overvoltage_protectionhttp://www.electrical-installation.org/enwiki/LV_switchgear:_functions_and_selectionhttp://www.electrical-installation.org/enwiki/Sizing_and_protection_of_conductorshttp://www.electrical-installation.org/enwiki/Protection_against_electric_shockshttp://www.electrical-installation.org/enwiki/LV_Distributionhttp://www.electrical-installation.org/enwiki/MV_and_LV_architecture_selection_guidehttp://www.electrical-installation.org/enwiki/Connection_to_the_LV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/Connection_to_the_MV_utility_distribution_networkhttp://www.electrical-installation.org/enwiki/Choice_of_power-supply_sourceshttp://www.electrical-installation.org/enwiki/Choice_of_transformer_ratinghttp://www.electrical-installation.org/enwiki/Example_of_application_of_factors_ku_and_kshttp://www.electrical-installation.org/enwiki/Installed_apparent_power_(kVA)http://www.electrical-installation.org/enwiki/Installed_power_(kW)http://www.electrical-installation.org/enwiki/Power_loading_of_an_installationhttp://www.electrical-installation.org/enwiki/LED_lamps_%26_fixtureshttp://www.electrical-installation.org/enwiki/Discharge_lampshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demandhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/How_to_browse_and_searchhttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/Main_Pagehttp://www.electrical-installation.org/enwiki/About%20the%20Electrical%20Installation%20Wiki -
8/10/2019 Technical Atricle
5/52
2- Diversity factor - Coincidence factor (ks)
3- Diversity factor for an apartment block
4- Rated Diversity Factor for distribution switchboards
5- Diversity factor according to circuit function
All individual loads are not necessarily operating at full rated nominal powernor necessarily at the same time. Factors ku and ks allow the determination of
the maximum power and apparent-power demands actually required to
dimension the installation.
Factor of maximum utilization (ku)
In normal operating conditions the power consumption of a load is sometimesless than that indicated as its nominal power rating, a fairly common occurrence
that justifies the application of an utilization factor (ku) in the estimation ofrealistic values.
This factor must be applied to each individual load, with particular attention toelectric motors, which are very rarely operated at full load.
In an industrial installation this factor may be estimated on an average at 0.75
for motors.
For incandescent-lighting loads, the factor always equals 1.
For socket-outlet circuits, the factors depend entirely on the type of appliancesbeing supplied from the sockets concerned.
For Electric Vehicle the utilization factor will be systematically estimated to 1,as it takes a long time to load completely the batteries (several hours) and a
dedicated circuit feeding the charging station or wall box will be required by
standards.
Diversity factor - Coincidence factor (ks)
The determination of ks factors is the
responsibility of the designer, since it requires a
detailed knowledge of the installation and theconditions in which the individual circuits are to
be exploited.
http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_-_Coincidence_factor_.28ks.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_-_Coincidence_factor_.28ks.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_-_Coincidence_factor_.28ks.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_-_Coincidence_factor_.28ks.29http://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_for_an_apartment_blockhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_for_an_apartment_blockhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_for_an_apartment_blockhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_for_an_apartment_blockhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Rated_Diversity_Factor_for_distribution_switchboardshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Rated_Diversity_Factor_for_distribution_switchboardshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Rated_Diversity_Factor_for_distribution_switchboardshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Rated_Diversity_Factor_for_distribution_switchboardshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_according_to_circuit_functionhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_according_to_circuit_functionhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_according_to_circuit_functionhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_according_to_circuit_functionhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_according_to_circuit_functionhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Rated_Diversity_Factor_for_distribution_switchboardshttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_for_an_apartment_blockhttp://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand#Diversity_factor_-_Coincidence_factor_.28ks.29 -
8/10/2019 Technical Atricle
6/52
For this reason, it is not possible to give precisevalues for general application.
It is a matter of common experience that the simultaneous operation of all
installed loads of a given installation never occurs in practice, i.e. there isalways some degree of diversity and this fact is taken into account for
estimating purposes by the use of a factor (ks).
This factor is defined in IEC60050 - International Electrotechnical
Vocabulary,as follows:
Coincidence factor:the ratio, expressed as a numerical value or as a
percentage, of the simultaneous maximum demand of a group of electrical
appliances or consumers within a specified period, to the sum of their
individual maximum demands within the same period. As per this definition,
the value is always 1 and can be expressed as a percentage
Diversity factor:the reciprocal of the coincidence factor. It means it will
always be 1.
Note:In practice, the most commonly used term is the diversity factor, but it is
used in replacement of the coincidence factor, thus will be always
-
8/10/2019 Technical Atricle
7/52
10 to 14 0.63
15 to 19 0.53
20 to 24 0.49
25 to 29 0.46
30 to 34 0.44
35 to 39 0.42
40 to 49 0.41
50 and more 0.38
F ig. A10:Example of diversity factors for an apartment block as defined inFrench standard NFC14-100, and applicable for apartments without electrical
heating
Example(see Fig. A11):
5 storeys apartment building with 25 consumers, each having 6 kVA ofinstalled load.
The total installed load for the building is: 36 + 24 + 30 + 36 + 24 = 150 kVA
The apparent-power supply required for the building is: 150 x 0.46 = 69 kVAFrom Figure A10, it is possible to determine the magnitude of currents in
different sections of the common main feeder supplying all floors. For vertical
rising mains fed at ground level, the cross-sectional area of the conductors canevidently be progressively reduced from the lower floors towards the upper
floors.
These changes of conductor size are conventionally spaced by at least 3-floorintervals.
In the example, the current entering the rising main at ground level is:
the current entering the third floor is:
-
8/10/2019 Technical Atricle
8/52
F ig. A11:Application of the diversity factor (ks) to an apartment block of 5
storeys
Rated Diversity Factor for distribution switchboards
The standards IEC61439-1 and 2 define in a similar way the Rated Diversity
Factor for distribution switchboards (in this case, always 1) IEC61439-2 also
states that, in the absence of an agreement between the assembly manufacturer
(panel builder) and user concerning the actual load currents (diversity factors),the assumed loading of the outgoing circuits of the assembly or group of
outgoing circuits may be based on the values in Fig. A12.
http://www.electrical-installation.org/enwiki/File:FigA11.jpghttp://www.electrical-installation.org/enwiki/File:FigA11.jpg -
8/10/2019 Technical Atricle
9/52
If the circuits are mainly for lighting loads, it is prudent to adopt ks values close
to unity.
Type of load Assumed loading factor
Distribution - 2 and 3 circuits 0.9
Distribution - 4 and 5 circuits 0.8
Distribution - 6 to 9 circuits 0.7
Distribution - 10 or more circuits 0.6
Electric actuator 0.2
Motors 100 kW 0.8
Motors > 100 kW 1.0
F ig. A12:Rated diversity factor for distribution boards (cf IEC61439-2 table
101)
Diversity factor according to circuit function
ks factors which may be used for circuits supplying commonly-occurring loads,
are shown in Figure A13. It is provided in French practical guide UTE C 15-105.
Circuit function Dive
Lighting 1
Heating and air conditioning 1
Socket-outlets 0.1 to
Lifts and catering hoist(2)
For the most powerful motor
For the second most powerful motor
For all motors
1
0.75
0.60
(1) In certain cases, notably in industrial installations, this factor can be higher.(2) The current to take into consideration is equal to the nominal current of the
-
8/10/2019 Technical Atricle
10/52
motor, increased by a third of its starting current.
F ig. A13:Diversity factor according to circuit function (see UTE C 15-105
table AC)
Retrieved from "http://www.electrical-
installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand
&oldid=17018"
Category:
Chapter - General rules of electrical installation design
This page was last modified on 26 November 2014, at 22:19.
This page has been accessed 88,093 times. Disclaimers
About Electrical Installation Guide
Privacy policy
Top of Form
/w EPDwUJNTQy
CA0B0334
Register
Login
Search
Home
http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enwiki/Special:Categorieshttp://www.electrical-installation.org/enwiki/Special:Categorieshttp://www.electrical-installation.org/enw/index.php?title=Category:Chapter_-_General_rules_of_electrical_installation_design&action=edit&redlink=1http://www.electrical-installation.org/enw/index.php?title=Category:Chapter_-_General_rules_of_electrical_installation_design&action=edit&redlink=1http://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:General_disclaimerhttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:General_disclaimerhttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Abouthttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Abouthttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Privacy_policyhttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Privacy_policyhttp://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnoteshttp://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f74%2festimating-power-demand-using-iec-methodshttp://__dopostback%28%27dnn%24dnnsearch%24cmdsearch%27%2C%27%27%29/http://myelectrical.com/http://myelectrical.com/http://www.mediawiki.org/http://www.schneider-electric.com/http://myelectrical.com/http://www.mediawiki.org/http://www.schneider-electric.com/http://myelectrical.com/http://www.mediawiki.org/http://www.schneider-electric.com/http://myelectrical.com/http://__dopostback%28%27dnn%24dnnsearch%24cmdsearch%27%2C%27%27%29/http://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f74%2festimating-power-demand-using-iec-methodshttp://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnoteshttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Privacy_policyhttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:Abouthttp://www.electrical-installation.org/enwiki/Electrical_Installation_Guide:General_disclaimerhttp://www.electrical-installation.org/enw/index.php?title=Category:Chapter_-_General_rules_of_electrical_installation_design&action=edit&redlink=1http://www.electrical-installation.org/enwiki/Special:Categorieshttp://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018http://www.electrical-installation.org/enw/index.php?title=Estimation_of_actual_maximum_kVA_demand&oldid=17018 -
8/10/2019 Technical Atricle
11/52
Advertise
Policy
Notes
Notes Table View
Notes Index View
Authors & Comments
Questions
Tools
Document Library
News
Community
Award Points
Store
Support
Knowledge Base
Support Forums
Contact Us
Main menu
Notes
Loading, please wait.
http://myelectrical.com/home/advertisehttp://myelectrical.com/home/policyhttp://myelectrical.com/noteshttp://myelectrical.com/notes/notes-table-viewhttp://myelectrical.com/notes/notes-index-viewhttp://myelectrical.com/notes/authors-commentshttp://myelectrical.com/questionshttp://myelectrical.com/toolshttp://myelectrical.com/tools/document-libraryhttp://myelectrical.com/tools/newshttp://myelectrical.com/communityhttp://myelectrical.com/community/award-pointshttp://myelectrical.com/storehttp://myelectrical.com/supporthttp://myelectrical.com/notes/tag/myelectrical/page/1http://myelectrical.com/support/support-forumshttp://myelectrical.com/support/contact-ushttp://myelectrical.com/noteshttp://myelectrical.com/noteshttp://myelectrical.com/support/contact-ushttp://myelectrical.com/support/support-forumshttp://myelectrical.com/notes/tag/myelectrical/page/1http://myelectrical.com/supporthttp://myelectrical.com/storehttp://myelectrical.com/community/award-pointshttp://myelectrical.com/communityhttp://myelectrical.com/tools/newshttp://myelectrical.com/tools/document-libraryhttp://myelectrical.com/toolshttp://myelectrical.com/questionshttp://myelectrical.com/notes/authors-commentshttp://myelectrical.com/notes/notes-index-viewhttp://myelectrical.com/notes/notes-table-viewhttp://myelectrical.com/noteshttp://myelectrical.com/home/policyhttp://myelectrical.com/home/advertise -
8/10/2019 Technical Atricle
12/52
Estimating Power Demand Using IEC Methods
BySteven McFadyen on July 27th, 2011
Estimating power demand is combination of science and art. It is an area of electrical engineering where
there is no correct answer. Plug the figures in your preferred method of calculation and then as an
engineer you need to relay on instincts to say if the answer feels right or not. This is a look at one
method inline with what could be considered IEC practice.
reproduced from
Schneider's 'Electrical Installation
Guide - According to IEC International Standards' Estimating power demand is combination of science
and art. It is an area of electrical engineering where there is no correct answer. Plug the figures in your
preferred method of calculation and then as an engineer you need to relay on instincts to say if theanswer feels right or not.
Individual loads do not necessarily operate at full rated nominal power nor at the same time. Estimating
power demand involves both looking at the total connected load and the maximum expected demand
on the system. As we will see these are not the same.
Contents [hide]
IEC Method
Typical Utilisation & Simultaneity Factors
Utilization Factor (ku)
Simultaneity Factor (ks)
Basic Demand Data and Preliminary Planning
Related Links
http://myelectrical.com/users/stevenhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310031http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310032http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310033http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310034http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310035http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310036http://myelectrical.com/Portals/0/SunBlogNuke/2/Windows-Live-Writer/Estimating-Power-Demand-Using-IEC-Method_DE69/IECDemandEstimation_2.jpghttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310036http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310035http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310034http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310033http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310032http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#myID1310031http://myelectrical.com/users/steven -
8/10/2019 Technical Atricle
13/52
IEC Method
Depending where you are, different methods, figures and procedures are used to estimate the power
demand of an installation. This is a look at one method inline with what could be considered IEC
practice.
To get going it is useful to understand some basic definitions:
voltage V - the voltage of the electrical system
load current Ib - the current required to operate an item of equipment
apparent power kVA - the product of the voltage V and load current Ib
real power kW - the actual power consumed by the load or equipment
power factor - the ratio of the real power to apparent power (kW/kVA)
utilisation factor ku - see below
simultaneity factor ks - see below
Utilisation factor ku - name plate ratings invariably list higher values of current than will be seen in use,
motors rarely run at full load, etc. A utilisation factor can be applied to these ratings to establish a more
realistic load current, thereby not overestimating the demand.
Simultaneity factor ks - not all equipment runs a the same time; for example one motor may be duty and
the other standby. The same applies to installations; for example a group of houses or apartments will
not all consume the full design current at the same time. Applying a simultaneity factor takes care of
this. Often the term diversity is used and has the same meaning.
The diagram illustrates how the utilisation and simultaneity factors are used to estimate the power
demand of an installation. Click on the image for a larger version.
Following the diagram, the apparent power of the load or equipment is multiplied by the utilisation
factor to give a realistic power demand to be supplied by a distribution board. Summing these power
demand figures gives the total connected apparent demand (at that board). The distribution board
would normally be sized for this demand.
An appropriate simultaneity factor is applied to the connected apparent demand at the distribution
board and this [diversified] load is carried upstream to higher levels boards. Repeating this procedure
will lead to an expected total demand for the full installation.
In a nutshell, thats all there is to it - in principal at least. There are often problems in deciding what
simultaneity factor to use and here experience can be really useful.
-
8/10/2019 Technical Atricle
14/52
Tip: estimating power demand this is normally carried out using either apparent or real power. I prefer
real power as it gives me the actual kW required and is an algebraic sum. Many people will use apparent
power, which strictly speaking is a vector sum. As we are dealing with estimates (ball park figures
even), using either real or apparent power will yield usable results.
Typical Utilisation & Simultaneity Factors
Ideally utilisation and simultaneity factors should be developed specifically for each application and
based on a knowledge of how that particular system will operate. For certain situations it may be
necessary to use factors given by supply authorities or some other industry adopted factors.
The factors below are based on those given in the Schneider Electrical Installation Guide and can be
used in the absence of other sources or to provide reality checks on figures being used.
Utilization Factor (ku)
Actual power used in equipment is often less than the rated power. A utilization factor (ku) is used to
give a more realistic estimation of maximum power.
Typical values of Utilization Factor ku:
Type of load ku
Motors (Typical 0.75
Lighting Circuits 1
Socket Outlets 0.1 to 0.2
Simultaneity Factor (ks)
If is rare in practice that all loads operate simultaneously. The simultaneity factor ks is applied to each
group of loads (e.g. being supplied from a distribution or sub-distribution board). Simultaneity factor is
sometimes called diversity factor.
Typical values of Simultaneity Factor ks by circuit function:
Type of load ks
Lighting 1
General Heating 1
Space Heating 0.8
Building Installations ks
Escalator 0.5
Elevator 0.3
Sanitary systems 0.5
Apartment Blocks ks
2 to 4 1
5 to 9 0.78
10 to 14 0.63
-
8/10/2019 Technical Atricle
15/52
Air Conditioning 1
Socket Outlets 0.1 to 0.2
Lifts/Hoists Most powerful
motor
1
Second most
powerful motor
0.75
For all motors 0.6
Assemblies -Number of Circuits ks
2 and 3 0.9
4 and 5 0.8
6 to 9 0.7
10 and more 0.6
Sprinklers 0.1
Heating 0.8
Air conditioning 0.8
Cooling water system 0.7
Refrigeration 0.7
15 to 19 0.53
20 to 24 0.49
25 to 29 0.46
30 to 34 0.44
35 to 39 0.42
40 to 49 0.41
50 and more 0.40
We've produced an Excel spreadsheet for estimating building total connected load and maximum
demand.
If your interested in obtaining a copy,you can get it here.
Basic Demand Data and Preliminary Planning
http://myelectrical.com/home/myelectrical-store/categoryid/3/productid/6http://myelectrical.com/home/myelectrical-store/categoryid/3/productid/6http://myelectrical.com/home/myelectrical-store/categoryid/3/productid/6http://myelectrical.com/home/myelectrical-store/categoryid/3/productid/6http://myelectrical.com/home/myelectrical-store/categoryid/3/productid/6 -
8/10/2019 Technical Atricle
16/52
Siemens produce a series of publications providing typical demand figures for various building functions
[seeSteven's Technical List,Buildings Technology for a list of these]. The following tables are based on
values given in these publications:
Buildings according to their type of use:
Building Use Average
Power
Demand
Simultaneity
Factor
Bank 40-70 w/m2 0.6
Library 20-40 w/m2 0.6
Office 30-50 w/m2 0.6
Shopping centre 30-60 w/m2 0.6
Hotel 30-60 w/m2 0.6
Department store 30-60 w/m2 0.6
Small hospital
(40-80 beds)
250-400
w/m2
0.6
Hospital(200-500 beds)
50-80 w/m2 0.6
Warehouse (no
cooling)
2-20 w/m2 0.6
Cold store 500- 1,500
w/m2
0.6
Apartment complex
(withoutnight storage or
continuous-flow
water heater)
10-30 w/m2 0.6
Museum 60-80 w/m2 0.6
Different functional and building areas
Functional Area/
Building Area
Average
Power
Demand
Simultaneity
Factor
Hallway, anteroom or
lobby
5-15 w/m2 0.3
Staircase 5-15 w/m2 0.3
General utilities 5-15 w/m2 0.3
Foyer 10-30
w/m2
1.0
Access ways
(e.g. tunnel)
10-20
w/m2
1 .0
Recreation
room/kitchenette
20-50
w/m2
0.3
Toilet areas 5-15 w/m2 1 .0
Travel centre 60-80
w/m2
0.8
Office areas 20-40
w/m2
0.8
Bookstore 80-120
w/m2
0.8
Flower shop 80-120
w/m2
0.8
Bakery/butcher 250-350 0.8
http://myelectrical.com/tools/stevens-technical-listhttp://myelectrical.com/tools/stevens-technical-list -
8/10/2019 Technical Atricle
17/52
Parking garage 3-10 w/m2 0.6
Production plant 30-80 w/m2 0.6
Data centre 500-2,000
w/m2
1 .0
School 10-30 w/m2 0.6
Gym hall 15-30 w/m2 0.6
Stadium (40,000-
80,000 seats)
70-120
w/seat
0.6
Ol peoples home 15-30 w/m2 0.6
Greenhouse (artificial
lighting)
250-500
w/m2
w/m2
Groceries 80-120
w/m2
0.8
Bistro/ice cream
parlour
150-250
w/m2
0.8
Cafe 180-220
w/m2
0.8
Diner/restaurant 180-400
w/m2
0.8
Tobacco shop 80-120
w/m2
0.8
Hairdresser 220-280
w/m2
0.8
Dry-cleaners or
laundry
700-950
w/m2
0.7
Storage area 5-15
w1/m2
0.3
Office Equipment Demand Recommendations
Equipment Average
Power
Demand
Data
Source
All in one Printer/
Fax/Scanner
75 w CIBSE
Ceiling Projector Lift 50 w Estimated
Ceiling Projector
Screen
80 w Estimated
Other areas:
Area Average power
demand
Electric floor heating
bedrooms
65-1 00 w/m2
Electric floor heating
bathroom
130-150 w/m2
Night storage heating:
Low-energy house
60-70 w/m2
-
8/10/2019 Technical Atricle
18/52
Colour Printer/Copier 200 w CIBSE
Colour Scanner 50 w CIBSE
Computer Peripherals 400 w Estimated
Convenience Sockets 200
w/socket
DEWA
Cost Recovery Devices 3,000 w Estimated
Desktop 100 w CIBSE
DVD Player 70 w Estimated
Fixed Camera 30 w Estimated
Laptop 100 w CIBSE
Large Smart Board 300 w Estimated
Monitor 200 to 400
W
CIBSE
Paper Shredder 50 w CIBSE
Personal Printer/Fax 50 w CIBSE
Portable Wireless
Controller
20 w Estimated
Projector 300 w CIBSE
Rack Equipment in
Credenza
400 W Estimated
Shredder 190 w Estimated
Technology Wells in Table
Top
200 w Estimated
Night storage heating:
house with stanar
insulation
100-110 w/m2
Small air conditioning unit 60 w/m2
Photovoltaic (maximum
output of the modules)
100-130 w/m2
-
8/10/2019 Technical Atricle
19/52
Teleconference Module 50 w Estimated
Wall Mounted Controller 20 w Estimated
Wall Mounted LCD 200 w Estimated
Related Links
Maximum Demand for Buildings - Post
Power Demand,Buildings,Energy
More interesting Notes:
Possibly related posts:
Power Factor
What is Aircraft Ground Power
9 power supply issues solved by using a UPS
Three Phase Current - Simple Calculation
UPS - Uninterruptible Power Supply
Steven McFadyen
Steven has over twenty five years experience working on some of the largest construction projects. He
has a deep technical understanding of electrical engineering and is keen to share this knowledge. About
the author
http://myelectrical.com/opinion/entryid/53/maximum-demand-for-buildingshttp://myelectrical.com/notes?tag=power+demandhttp://myelectrical.com/notes/tag/buildingshttp://myelectrical.com/notes/tag/energyhttp://myelectrical.com/notes/entryid/197/power-factorhttp://myelectrical.com/notes/entryid/216/what-is-aircraft-ground-powerhttp://myelectrical.com/notes/entryid/110/9-power-supply-issues-solved-by-using-a-upshttp://myelectrical.com/notes/entryid/8/three-phase-power-simple-calculationshttp://myelectrical.com/notes/entryid/227/ups-uninterruptible-power-supplyhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/notes/entryid/227/ups-uninterruptible-power-supplyhttp://myelectrical.com/notes/entryid/8/three-phase-power-simple-calculationshttp://myelectrical.com/notes/entryid/110/9-power-supply-issues-solved-by-using-a-upshttp://myelectrical.com/notes/entryid/216/what-is-aircraft-ground-powerhttp://myelectrical.com/notes/entryid/197/power-factorhttp://myelectrical.com/notes/tag/energyhttp://myelectrical.com/notes/tag/buildingshttp://myelectrical.com/notes?tag=power+demandhttp://myelectrical.com/opinion/entryid/53/maximum-demand-for-buildings -
8/10/2019 Technical Atricle
20/52
Please enable JavaScript to view the comments
powered by Disqus.
View 15 Comments (old system)
aymenomer says:
9/1/2011 9:11 AM
Hi,
How can I pick the values for Ku and Ks
Steven says:
9/1/2011 9:11 AM
We have some typical values in the Wiki
- see/wiki/maximum-demand-estimation.aspx for example
Ku depends on situation and often I tend to leave it at 1. If I know the mechanical/process guys are over
sizing I may use a lower figure. Ks is the same as diversity - besides the typical given in the Wiki, people
have their own they like to use or sometime supply Authorities require certain values. A good starting
point for finding values are the Siemens building applications manuals, which I think you can download
from their site.
ahmed01451 says:
9/1/2011 9:11 AM
If you could give me calculation step giving with one example if i have 6 motors each 15kw , out of which
5 duty and 1 standby , how i can apply ks and ku .one example so that i can implement
Steven says:
9/1/2011 9:11 AM
http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#collapseOnehttp://myelectrical.com/users/stevenhttp://myelectrical.com/wiki/maximum-demand-estimation.aspxhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/wiki/maximum-demand-estimation.aspxhttp://myelectrical.com/users/stevenhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#collapseOne -
8/10/2019 Technical Atricle
21/52
With the given information I think it would be unlikely that the motors would be critically sized and I
would be tempted to use ku=0.8. You may even consider lower if you have some background as to how
the motor duties have been selected. On diversity you could use ks = 0.83 (5/6). This would give a
diversified load of 60 kW (6x15x0.8x0.83). I would size the individual supplies to each motor for 15 kW.
If these are being supplied by an MCB or DB it would be sized for the connected load 72 kW (15x6x0.8).
For any upstream switchboards I would assume they need to supply an average of 60 kW for these
motors.
real_brute says:
9/11/2011 9:16 AM
gents.... be careful in using the IEC guide.... make sure you read all paragraphs in there....
there is no straight forward guide and rule when estimating maximum demand...
the manual says that, the values are based in extensive research.... i agree... i also agree on theparagraph that says "experienced electrical engineer"... which defies all values stated in the reference
tables...
this means that the manual is trying to save it's own ass.... and i also agreed with it....
i just want to let everyone know that those values can never be accurate... tho accuracy is not
required...it will just give the engineer an indication of the derived values if within acceptable limits....
but then again, there is no easy substitute to extensive load studies and analysis... which should include
load profiling and energy studies....
i have used the manual and i have known that the straight forward values are easy to use but quite
misleading....
my suggestions is to categorize the loads effectively, get benchmark from existing projects, make
accurate load profiles including HVAC which has at least 60% effect on the outcome of the analysis...
Yuri Fernandez says:
11/18/2011 5:37 PM
What refers to IEC standard?
Thanks for the response
Steven says:
11/22/2011 7:27 AM
http://myelectrical.com/users/real_brutehttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/real_brute -
8/10/2019 Technical Atricle
22/52
The article is not in reference to a particular stanar. The IEC Metho in the title refers more to the
terminology and procedures that you will find if you read guides/books published in a context of using
IEC standards (as opposed to say NEC or IEEE)
Wael Roustom says:
5/14/2012 2:18 AM
Thanks a lot for your information and your efforts.
I think it is better to draw an general example like a twin tower one residential and the other offices
including mall in the ground and first floor. Think we can share our knowledge to estimate the maximum
demand load.
Thanks again.
Steven says:
5/14/2012 2:19 AM
Thanks for the comment Wael.
Towards the end of last year I was busy writing a detailed guide explaining how to calculate demand for
buildings, including an example of a mixed use development. Currently it is about 80% complete. At the
beginning of the year, I took the decision to stop for a few months before returning for final editinga
think taking this break will make it a better guide. I hope to return to the project soon and get it finishedwithin the next few months.
If you want to keep an eye out Ill be posting etails on the site an in our newsletter as soon as its
finished
Carlos says:
3/11/2013 10:13 AM
Hi Steven,
Thanks for the useful information on this page. Did you by any chance finish the guide you were working
on. I would like to get hold of a copy if you are willing to share it?
Steven says:
http://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/steven -
8/10/2019 Technical Atricle
23/52
3/13/2013 12:23 AM
I ha a change in personal situation which put things on the back burner. Its about 70% complete an I
hope to get back to it soon.
SYAM says:
3/13/2013 4:05 AM
Dear sir,
I came across another method of calculation like
MD= 1x Continous load+ 0.6x Intermittent load + .2 x Standby load
Is the mentioned method right or is it applicable for industries...?
Thanks in advance.
Steven says:
3/19/2013 3:24 AM
Personally Ive never seen a metho as escribe. It seems a bit arbitrary to myself an I woul have
some doubts about any results from the method.
Akira says:
3/19/2013 2:39 AM
IEC rules is difficult for me to understand Japanese . However, I would like to have a clear answer so that
we esign in the Mile East.I have always reference to Electrical installation guie 2010 when oing
working. I under stand that this guide book iseferring IEC Standards.. Please lets me know What IEC
reference numberwith Chapter that escribe page A16 Factor of simultaneity for an
apartment block Regars. I woul like to know the grouns liste in theIEC stanar .
Steven says:
3/19/2013 3:22 AM
http://myelectrical.com/users/songsaahhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/stevenhttp://myelectrical.com/users/songsaah -
8/10/2019 Technical Atricle
24/52
Akira, I use the installation guide as well. Unfortunately it does not refer to any direct IEC standard for
the typical Simultaneity values given, so it may be these are Schneiers own or from some other
standard. I think the important thing is that any figures are just a guide and not fixed.
Each application is different and more detailed understanding of the energy use or better historical data
can help you employ more appropriate Simultaneity values. Estimating power is something that worries
a lot of engineers (myself inclue). Its almost impossible to get correct an has consequences for both
over and under estimating.
Comments are closed for this post:
have a question or need help, please use ourQuestions Section
spotted an error or have additional info that you think should be in this post, feel free toContact Us
Latest Questions:
HP & BHP in motor
Power DB
3 Phase Current and Load
Short Circuit Values, Icw, Icp, Icc
Lightning and Car Alarms
Power Transformer Temperature Measurement
Voltage Conversion
Arc Flash
more questions...
http://myelectrical.com/questionshttp://myelectrical.com/home/contact-ushttp://myelectrical.com/questionshttp://myelectrical.com/questions/view/question/id/554http://myelectrical.com/questions/view/question/id/553http://myelectrical.com/questions/view/question/id/547http://myelectrical.com/questions/view/question/id/543http://myelectrical.com/questions/view/question/id/539http://myelectrical.com/questions/view/question/id/538http://myelectrical.com/questions/view/question/id/536http://myelectrical.com/questions/view/question/id/534http://myelectrical.com/questionshttp://myelectrical.com/noteshttp://myelectrical.com/noteshttp://myelectrical.com/questionshttp://myelectrical.com/questions/view/question/id/534http://myelectrical.com/questions/view/question/id/536http://myelectrical.com/questions/view/question/id/538http://myelectrical.com/questions/view/question/id/539http://myelectrical.com/questions/view/question/id/543http://myelectrical.com/questions/view/question/id/547http://myelectrical.com/questions/view/question/id/553http://myelectrical.com/questions/view/question/id/554http://myelectrical.com/questionshttp://myelectrical.com/home/contact-ushttp://myelectrical.com/questions -
8/10/2019 Technical Atricle
25/52
Most Popular Notes:
more notes...
View a random note!
Our Newsletter
Receive updates on new posts by email
Subscribe
http://myelectrical.com/noteshttp://myelectrical.com/noteshttp://myelectrical.com/randomnote.aspxhttp://myelectricalengineering.co.uk/http://myelectrical.com/randomnote.aspxhttp://myelectrical.com/noteshttp://myelectrical.com/notes -
8/10/2019 Technical Atricle
26/52
Popular Tags
Automation
Batteries
Buildings
Cable Sizing
Cables
Circuit Breakers
Commissioning
Control Systems
Earth Fault
Editing
Education
Electrical Installations
Electronics
Energy
Equipment
Equipment Data
http://myelectricalengineering.co.uk/http://myelectrical.com/notes/tag/automationhttp://myelectrical.com/notes/tag/batterieshttp://myelectrical.com/notes/tag/buildingshttp://myelectrical.com/notes?tag=cable+sizinghttp://myelectrical.com/notes/tag/cableshttp://myelectrical.com/notes?tag=circuit+breakershttp://myelectrical.com/notes/tag/commissioninghttp://myelectrical.com/notes?tag=control+systemshttp://myelectrical.com/notes?tag=earth+faulthttp://myelectrical.com/notes/tag/editinghttp://myelectrical.com/notes/tag/educationhttp://myelectrical.com/notes?tag=electrical+installationshttp://myelectrical.com/notes/tag/electronicshttp://myelectrical.com/notes/tag/energyhttp://myelectrical.com/notes/tag/equipmenthttp://myelectrical.com/notes?tag=equipment+datahttp://myelectricalengineering.co.uk/http://myelectrical.com/notes?tag=equipment+datahttp://myelectrical.com/notes/tag/equipmenthttp://myelectrical.com/notes/tag/energyhttp://myelectrical.com/notes/tag/electronicshttp://myelectrical.com/notes?tag=electrical+installationshttp://myelectrical.com/notes/tag/educationhttp://myelectrical.com/notes/tag/editinghttp://myelectrical.com/notes?tag=earth+faulthttp://myelectrical.com/notes?tag=control+systemshttp://myelectrical.com/notes/tag/commissioninghttp://myelectrical.com/notes?tag=circuit+breakershttp://myelectrical.com/notes/tag/cableshttp://myelectrical.com/notes?tag=cable+sizinghttp://myelectrical.com/notes/tag/buildingshttp://myelectrical.com/notes/tag/batterieshttp://myelectrical.com/notes/tag/automationhttp://myelectricalengineering.co.uk/ -
8/10/2019 Technical Atricle
27/52
Equipment Ratings
Equipment Sizing
Fault Calculation
Fundamentals
Generation
High Voltage
History
IEC Standards
Innovation
Lighting
Materials
Medium Voltage
Motor Control
Motors
myElectrical
Off-Topic
Power Quality
Power Systems
Protection
Protective Devices
Relays
Safety
Scientists
Software
Standards
http://myelectrical.com/notes?tag=equipment+ratingshttp://myelectrical.com/notes?tag=equipment+sizinghttp://myelectrical.com/notes?tag=fault+calculationhttp://myelectrical.com/notes/tag/fundamentalshttp://myelectrical.com/notes/tag/generationhttp://myelectrical.com/notes?tag=high+voltagehttp://myelectrical.com/notes/tag/historyhttp://myelectrical.com/notes?tag=iec+standardshttp://myelectrical.com/notes/tag/innovationhttp://myelectrical.com/notes/tag/lightinghttp://myelectrical.com/notes/tag/materialshttp://myelectrical.com/notes?tag=medium+voltagehttp://myelectrical.com/notes?tag=motor+controlhttp://myelectrical.com/notes/tag/motorshttp://myelectrical.com/notes/tag/myelectricalhttp://myelectrical.com/notes/tag/off-topichttp://myelectrical.com/notes?tag=power+qualityhttp://myelectrical.com/notes?tag=power+systemshttp://myelectrical.com/notes/tag/protectionhttp://myelectrical.com/notes?tag=protective+deviceshttp://myelectrical.com/notes/tag/relayshttp://myelectrical.com/notes/tag/safetyhttp://myelectrical.com/notes/tag/scientistshttp://myelectrical.com/notes/tag/softwarehttp://myelectrical.com/notes/tag/standardshttp://myelectrical.com/notes/tag/standardshttp://myelectrical.com/notes/tag/softwarehttp://myelectrical.com/notes/tag/scientistshttp://myelectrical.com/notes/tag/safetyhttp://myelectrical.com/notes/tag/relayshttp://myelectrical.com/notes?tag=protective+deviceshttp://myelectrical.com/notes/tag/protectionhttp://myelectrical.com/notes?tag=power+systemshttp://myelectrical.com/notes?tag=power+qualityhttp://myelectrical.com/notes/tag/off-topichttp://myelectrical.com/notes/tag/myelectricalhttp://myelectrical.com/notes/tag/motorshttp://myelectrical.com/notes?tag=motor+controlhttp://myelectrical.com/notes?tag=medium+voltagehttp://myelectrical.com/notes/tag/materialshttp://myelectrical.com/notes/tag/lightinghttp://myelectrical.com/notes/tag/innovationhttp://myelectrical.com/notes?tag=iec+standardshttp://myelectrical.com/notes/tag/historyhttp://myelectrical.com/notes?tag=high+voltagehttp://myelectrical.com/notes/tag/generationhttp://myelectrical.com/notes/tag/fundamentalshttp://myelectrical.com/notes?tag=fault+calculationhttp://myelectrical.com/notes?tag=equipment+sizinghttp://myelectrical.com/notes?tag=equipment+ratings -
8/10/2019 Technical Atricle
28/52
Switchboards
Testing
Theory
Three Phase
Transformers
Voltage
Writing
View All Tags
Have some knowledge to share
If you have some expert knowledge or experience, why not consider sharing this with our community.
By writing an electrical note, you will be educating our users and at the same time promoting your
expertise within the engineering community.
To get started and understand our policy, you can read ourHow to Write an Electrical Note.
Click here to view the notes list in a table format
Click here to view the notes indexed by tag
http://myelectrical.com/notes/tag/switchboardshttp://myelectrical.com/notes/tag/testinghttp://myelectrical.com/notes/tag/theoryhttp://myelectrical.com/notes?tag=three+phasehttp://myelectrical.com/notes/tag/transformershttp://myelectrical.com/notes/tag/voltagehttp://myelectrical.com/notes/tag/writinghttp://myelectrical.com/notes/viewtag/truehttp://myelectrical.com/notes/entryid/149/how-to-write-an-electrical-notehttp://myelectrical.com/notes/notes-table-viewhttp://myelectrical.com/notes/notes-index-viewhttp://myelectrical.com/notes/notes-index-viewhttp://myelectrical.com/notes/notes-table-viewhttp://myelectrical.com/notes/entryid/149/how-to-write-an-electrical-notehttp://myelectrical.com/notes/viewtag/truehttp://myelectrical.com/notes/tag/writinghttp://myelectrical.com/notes/tag/voltagehttp://myelectrical.com/notes/tag/transformershttp://myelectrical.com/notes?tag=three+phasehttp://myelectrical.com/notes/tag/theoryhttp://myelectrical.com/notes/tag/testinghttp://myelectrical.com/notes/tag/switchboards -
8/10/2019 Technical Atricle
29/52
Footer
(click here to extend)
Copyright (c) 2014 myElectrical
Home
Contact
Terms Of Use
Privacy Statement
Register
Login
3607 ` { __scdoff`:` 1 , jppKLWyooxiYfd
Bottom of Form
ShareThis Copy and Paste
- See more at:http://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-
methods#sthash.eoeFt69i.dpuf
Understanding Demand and Consumption
Demand = KW
Consumption = KWH
The difference between demand (KW) and consumption (KWH) is vital to your choices
inreducing your energy costs. A simple way to see the difference between demand andconsumption is by considering two examples.
LIGHTING EXAMPLE: One 100-watt light bulb burning for 10 hours consumes 1,000watt-hoursor 1 kWh. The entire time it is on, it requires or "demands" 100 watts or 0.1 kW fromthe utility.
http://myelectrical.com/http://myelectrical.com/home/contact-ushttp://myelectrical.com/termshttp://myelectrical.com/privacyhttp://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnoteshttp://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f74%2festimating-power-demand-using-iec-methodshttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methodshttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/notes/entryid/74/estimating-power-demand-using-iec-methods#sthash.eoeFt69i.dpufhttp://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f74%2festimating-power-demand-using-iec-methodshttp://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnoteshttp://myelectrical.com/privacyhttp://myelectrical.com/termshttp://myelectrical.com/home/contact-ushttp://myelectrical.com/ -
8/10/2019 Technical Atricle
30/52
That means the utility must have that 0.1 kW ready whenever the customer turns thelamp on.
Similarly, ten 100-watt light bulbs burning for 1 hour consume 1,000 watt-hours or 1kWh. Note that in bothexamples, the consumption is 1 kWh, however, look how differently the secondsituation impacts the utilityfrom a demand perspective. The serving utility must now be prepared to provide tentimes as much 'capacity'
in response to the "demand" of the 10 light bulbs operating all at once.
If both of these customers are billed for their consumption only, both will get thesame bill for 1 kWh of energy.And that is the way most residential customers are billed. But the requirement for theutility to meet this energyrequirement is very different. In the second case, the utility has to have 10 timesmore generating 'capacity' toprovide the second customer's brief high demand for power compared to the firstcase.
Commercial and industrial customers are often billed for their hourly consumptionpatterns andtheir peak demandfor energy. These customers often have special meters that measure both, unlike
residential meters that justrecord total consumption in a time period, usually one month.
http://www.think-energy.net/KW_KWH_explanation.jpg -
8/10/2019 Technical Atricle
31/52
So, you might ask, "why doesn't the utility bill all customers for demand andconsumption?" Seems like that is only fair.And it would be, but the fact is that most homes have a pretty similar demand profileand the meters capable of measuringboth demand and consumption are much more expensive. Far too expensive to justify
having one on every home. So allmost residential customers need to be concerned with now is consumption billing. Asthe cost of metering drops, and asautomatic metering advances, we may see increased use of demand billing for homes.
Analogies for Understanding Demand and Consumption
WATER EXAMPLE:
Another way of understanding demand and consumption is with a "filling the bucket"analogy.Suppose you want to fill a 5 gallon bucket with water. You can use an inexpensivehose connectionto your sink providing 1 gallon per minute to do it, and it will take 5 minutes.
Or you can get to a more expensive large faucet that provides 5 gallons per minute, itwill fill in just one minute.
The flow rate is the equivalent to demand, and the 5 gallons of water are equivalentto consumption.In this example, filling both buckets has the same "consumption" but very different
"demands."
http://www.think-energy.net/KW_KWH_meter1.jpg -
8/10/2019 Technical Atricle
32/52
The same is true of electricity. While you may be able to accomplish the same thingby operating a small
wattage appliance for many hours as operating something of higher wattage for just afew, the higherwattage piece of equipment will create a higher demand on the utility. Using our
analogy, you are askingfor a larger pipe, and that costs more. If time is of the essence, it might be worth
having the more expensivehigh flow rate or wattage. This is why utilities often charge some customers for bothdemand and consumption.A customer that sets a high demand requires more services from the utility--additional generating plant capacity,and more expense in lines, transformers and substation equipment.
Some people like to use a automobile analogy to explain and understand how demandand consumption relate.The car's speedometeris like the demandmeter and the odometeris like aconsumptionmeter.Two cars could travel the same 100 mile road, one at 10 miles per hour for 10 hoursand the other at100 miles per hour for 1 hour. It takes a much more capable and expensive engine topower the carat 100 miles per hour than it does to power the one going only 10 miles per hour.
http://www.think-energy.net/KW_KWH_water_example.jpg -
8/10/2019 Technical Atricle
33/52
How Demand Changes Are Computed and Billed
As you have just learned, electric power use is metered in two ways: on maximumkilowatt use during agiven time period (i.e., kW demandtypically measured in 15-minute or 30-minuteintervals) and on totalcumulative consumptionin kilowatt hours (kWh). A customer's electric rate is setusing a complex process
http://www.think-energy.net/KW_KWH_time%20clock_example.jpghttp://www.think-energy.net/KW_KWH_auto_example.jpghttp://www.think-energy.net/KW_KWH_time%20clock_example.jpghttp://www.think-energy.net/KW_KWH_auto_example.jpg -
8/10/2019 Technical Atricle
34/52
of tracking cost of services and often seeking regulatory approvals.
The general theory is that demand charges reflect the utilities' fixed costs ofproviding a given level ofpower availability to the customer, and energy charges reflect the variable portion of
those costs as thecustomer actually uses that power availability.
Power companies often use a meter that records the power use during either a 15- or30-minute time window.The average power used during that window is used to calculate the kW demand. Thepeak demand used forbilling purposes in any month can be:
1. Time of Day:Dependent on the time of day (i.e., on-peak {usually during the day}and off-peak
{usually at night time periods) and/or the day of the week (e.g., Monday throughFriday and separately for weekends):The metering system tracks the highest usage anytime during the month under theappropriate time windows.These pricing schedules are generally referred to as Time of Use (TOU) rates.
2. Seasonally Differentiated:For example, the demand charge might be higherduring the summer than duringthe winter, or vice versa.
3. Declining Blocks:This is where the demand charge up to a given level is at one
price with the price decliningabove that level. For example, the demand charge might be $10 per kW up to 10,000
kW demand, and drop to$6 per kW for demands in excess of 10,000 kW.
4. Interruptible Blocks: The demand charge depends upon whether the customer canreduce electrical demand toa given level if it is notified in advance by the utility. The price reduction often varieswith the time of notice(i.e., the discount is higher if shorter notice is given). Some utilities also offer directload control for air conditioning
and water heating equipment, the utility itself can cycle this equipment on and offfor brief periods.
5. Ratchet: Certain rate designs incorporate minimum billing demands based uponhistorical peak demands.For example, if the peak demand last summer was 500 kW and the rate design has a50% ratchet, the minimumbilling demand would be 250kW (500 kW times 50%) for the following eleven months,
-
8/10/2019 Technical Atricle
35/52
regardless of whether theactual demands were lower.
The meter recording kWh power use during either a 15- or 30-minute time windowalso tallies total kWh use.
This meter is read at roughly monthly intervals and total power use is billed accordingto applicable pricing schedules.The type of energy charge pricing in common use includes:
1. Time of day: For example, on-peak and off-peak time periods and/or the day ofthe week (e.g., Monday through Friday):
These pricing schedules are generally referred to as Time of Use (TOU) rates.
2. Seasonally Differentiated:For example, the energy charge might be higher duringthe summer than during the winter, or vice versa.
3. Declining Blocks:This is typically where the energy charge to a given level is atone price and that price declines
above that level. For example the energy charge might be $0.05 per kWh for thefirst 100,000 kWhrs used in a month
and drop to $0.04 per kWh for the next 100,000 kWhrs.
Explanation of KW and KWH provided by Duke Energy.
false
Skip to main content
LinkedIn
Top of Form
Find People, Jobs, Companies, and More
Search for: AllAll
Search for people, jobs, companies, and more... ClearGLHD
groups/item_deta
Search
Advanced
https://www.linkedin.com/groups#a11y-contenthttps://www.linkedin.com/?trk=nav_logohttps://www.linkedin.com/vsearch/f?adv=true&trk=federated_advshttps://www.linkedin.com/vsearch/f?adv=true&trk=federated_advshttps://www.linkedin.com/?trk=nav_logohttps://www.linkedin.com/groups#a11y-content -
8/10/2019 Technical Atricle
36/52
Bottom of Form
Inbox. You have 0 new messages
Notifications. You have 3 unseen notifications 3
Add Connections 1
Add Connections
Account & Settings
ramesh ananthanarayanan Sign Out
Account: Basic Try Premium
Job Posting Manage
Language Change
Privacy & Settings Manage
Help Center Get Help
Home
Profile
Edit Profile
Who's Viewed Your Profile
Connections
Keep in Touch
Add Connections
Find Alumni
Jobs
Interests
Companies
Groups
https://www.linkedin.com/inbox/#messages?trk=nav_utilities_inboxhttps://www.linkedin.com/groups#notificationshttps://www.linkedin.com/fetch/importAndInviteEntry?trk=nav_utilities_add_connxhttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/mnyfe/subscriptionv2?displayProducts=&trk=nav_account_sub_nav_upgradehttps://www.linkedin.com/job/consumer/manageConsumer?trk=nav_account_sub_nav_job_managehttps://www.linkedin.com/settings/?tab=account&modal=nsettings-select-language&trk=nav_account_sub_nav_languagehttps://www.linkedin.com/settings/?trk=nav_account_sub_nav_settingshttps://help.linkedin.com/app/home/loc/hd/trk/groups/item_detail/https://www.linkedin.com/home?trk=nav_responsive_tab_homehttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profilehttps://www.linkedin.com/profile/edit?trk=nav_responsive_sub_nav_edit_profilehttps://www.linkedin.com/wvmx/profile?trk=nav_responsive_sub_nav_wvmphttps://www.linkedin.com/connections?type=combined&trk=nav_responsive_tab_networkhttps://www.linkedin.com/connections?type=combined&trk=nav_responsive_sub_nav_networkhttps://www.linkedin.com/fetch/importAndInviteEntry?trk=nav_responsive_sub_nav_add_connectionshttps://www.linkedin.com/edu/alumni?trk=nav_responsive_sub_nav_find_alumnihttps://www.linkedin.com/jobs?displayHome=&trk=nav_responsive_sub_nav_jobshttps://www.linkedin.com/company/home?trk=nav_responsive_sub_nav_companieshttps://www.linkedin.com/myGroups?trk=nav_responsive_sub_nav_groupshttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/myGroups?trk=nav_responsive_sub_nav_groupshttps://www.linkedin.com/company/home?trk=nav_responsive_sub_nav_companieshttps://www.linkedin.com/jobs?displayHome=&trk=nav_responsive_sub_nav_jobshttps://www.linkedin.com/edu/alumni?trk=nav_responsive_sub_nav_find_alumnihttps://www.linkedin.com/fetch/importAndInviteEntry?trk=nav_responsive_sub_nav_add_connectionshttps://www.linkedin.com/connections?type=combined&trk=nav_responsive_sub_nav_networkhttps://www.linkedin.com/connections?type=combined&trk=nav_responsive_tab_networkhttps://www.linkedin.com/wvmx/profile?trk=nav_responsive_sub_nav_wvmphttps://www.linkedin.com/profile/edit?trk=nav_responsive_sub_nav_edit_profilehttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profilehttps://www.linkedin.com/home?trk=nav_responsive_tab_homehttps://help.linkedin.com/app/home/loc/hd/trk/groups/item_detail/https://help.linkedin.com/app/home/loc/hd/trk/groups/item_detail/https://www.linkedin.com/settings/?trk=nav_account_sub_nav_settingshttps://www.linkedin.com/settings/?tab=account&modal=nsettings-select-language&trk=nav_account_sub_nav_languagehttps://www.linkedin.com/job/consumer/manageConsumer?trk=nav_account_sub_nav_job_managehttps://www.linkedin.com/mnyfe/subscriptionv2?displayProducts=&trk=nav_account_sub_nav_upgradehttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/profile/view?id=178651203&trk=nav_responsive_tab_profile_pichttps://www.linkedin.com/fetch/importAndInviteEntry?trk=nav_utilities_add_connxhttps://www.linkedin.com/groups#notificationshttps://www.linkedin.com/inbox/#messages?trk=nav_utilities_inbox -
8/10/2019 Technical Atricle
37/52
Pulse
Education
Business Services
Post a Job
Talent Solutions
Advertise
Sales Solutions
Try Premium for free
Main content starts below.
High Voltage Electric Power Equipment
17,580 members
Join
When you join a group, other members will be able to see your profile and message you. The group logowill be visible on your profile unless you change that setting.
Information and settings
Share group
Discussions
Promotions
Jobs
Members
Search
Join the group to receive daily or weekly activity updates.
Note: Content in an open group is visible to all LinkedIn visitors and is indexed for search.
https://www.linkedin.com/today/?trk=nav_responsive_sub_nav_pulsehttps://www.linkedin.com/edu/?trk=nav_responsive_sub_nav_eduhttps://www.linkedin.com/jobs/post?editAttributes=&trk=nav_responsive_sub_nav_post_jobhttps://www.linkedin.com/redir/redirect?url=http%3A%2F%2Fbusiness%2Elinkedin%2Ecom%2Ftalent-solutions%3Fsrc%3Dli-nav%26trk%3D&urlhash=NyH8https://www.linkedin.com/ads/start?utm_source=li&utm_medium=el&utm_campaign=hb_tab_ads&src=en-all-el-li-hb_tab_ads&trk=nav_responsive_sub_nav_advertisehttps://www.linkedin.com/mnyfe/subscriptionv2?displayProducts=&family=sales&trk=lss_global_nav_link2chooserhttps://www.linkedin.com/mnyfe/subscriptionv2?displayProducts=&trk=nav_responsive_sub_nav_upgradehttps://www.linkedin.com/groups?home=&gid=1801744&trk=anet_ug_hmhttps://www.linkedin.com/groups?members=&gid=1801744&trk=groups_item_detail-h-mbr-cnthttps://www.linkedin.com/groupRegistration?gid=1801744&csrfToken=ajax%3A-6746588675933475918&trk=groups_item_detail-h-join&goback=%2Egde_1801744_member_210744952https://www.linkedin.com/groups?about=&gid=1801744https://www.linkedin.com/groups/High-Voltage-Electric-Power-Equipment-1801744?trk=groups_item_detail-h-dsc&goback=%2Egde_1801744_member_210744952https://www.linkedin.com/groups?promosList=&gid=1801744&trk=groups_item_detail-h-promoshttps://www.linkedin.com/groups?jobs=&gid=1801744&trk=groups_item_detail-h-jobshttps://www.linkedin.com/groups?members=&gid=1801744&trk=groups_item_detail-h-mbrhttps://www.linkedin.com/groups?newItemsAbbr=&gid=1801744&trk=groups_item_detail-h-srphttps://www.linkedin.com/groups?home=&gid=1801744&trk=groups_item_detail-h-logohttps://www.linkedin.com/groups?newItemsAbbr=&gid=1801744&trk=groups_item_detail-h-srphttps://www.linkedin.com/groups?members=&gid=1