1 TECHINICAL SPE CI F ICATIONS PSC Pole (9 Mtr x 300 Kg ) I. Qualification Criteria of Sub Vendor / Manufacturer:- The prospective bidder may source PSC Poles from manufacturers who should have supplied PSC Poles to Electricity Supply Utilities / PSUs. The bidder should enclose Performance Certificates from the above users, issued in favour of the Sub Vendor / manufacturer, as proof of successful operation in field. Applicable Standard: The Poles shall comply with latest standards as under: REC Specification No. 15/1979, REC Specification No. 24/1983, IS 1678, IS 2905, IS 7321. II. Materials : Cement Cement to be used in the manufacture of pre-stressed concrete poles shall beordinary for rapid hardening Portland cement confirming to IS: 269-1976 (Specification for ordinary and low heat Portland cement) or IS: 8041 E-1978 (Specification for rapid hardening Portland cement). Aggregates Aggregates to be used for the manufacture of pre-stressed concrete poles shall confirm to IS:383 (Specification for coarse and fine aggregates from natural sources for concrete) .The nominal maximum sizes of aggregates shall in no case exceed 12mm. Water Water should be free from chlorides, sulphates, other salts and organic matter. Potable water will be generally suitable. Admixture Admixture should not contain Calcium Chloride or other chlorides and salts which are likely to promote corrosion of pre- stressing steel. The admixture shall conform to IS: 9103. Pres-StressingSteel Pre-stressing steel wires including those used as un tensioned wires should conform to IS:1785 (Part-I) (Specification for plain hard-drawn steel wire for pre-stressed concrete, Part-I cold drawn stress relieved wire).IS:1785 (Part- II)(Specification for plain hard-drawn steel wire) or IS:6003 (Specification for indented wire for pre-stressed concrete).The type design given in theannexure are for plain wires of 4 mm diameter with a guaranteed ultimate strength of 160kg/mm². All pre-stressing steel shall be free from splits, harmful scratches, surface flaw, rough, aged and imperfect edges and other defects likely to impair its use in pre- stressed concrete. Concrete Mix Concrete mix shall be designed to the requirements laid down for controlled concrete (also called design mix concrete) in IS: 1343-1980 (Code of practice for pre-stressed concrete) and IS: 456 1978 (Code of practice for plain and reinforced concrete) subject to the following specialconditions: i) Minimum works cube strength at 28 days should be at least 420 Kg/cm². The concrete strength at transfer should be at least 210Kg/cm². ii) The mix should contain at least 380 Kg of cement per cubic meter of concrete. iii) The mix should contain as low water content as is consistent with adequate workability. It becomes necessary to add water to increase the workability the cement content also should be raised in such a way that the original value of water cement ratio ismaintained. III. DesignRequirements The poles shall be designed for the following requirements: The poles shall be planted directly in the ground with a planting depth as per IS: 1678. Wherever, planting depth is required to be increased beyond the specified limits or alternative arrangements are required to be made on account of ground conditions e.g. water logging etc., the same shall be in the scope of the bidder at no extra cost to owner. The bidder shall furnish necessary design calculations/details of alternative arrangements in this regard. The working load on the poles should correspond tothose that are likely to come on the pole during their servicelife. The factor of safety for all poles 9.0Mts. Shall not be less than 2.5 and for 8.0 M poles, the factor of safety shall not be less than2.5. The average permanent load shall be 40% of the working load. The F.O.S. against first load shall be 1.0. At average permanent load, permissible tensile stress in concrete shall be 30 kg/cm². At the design value of first crack load, the modulus of rupture shall not exceed 53.0kg/cm² for M-40. The ultimate moment capacity in the longitudinal direction should be at least one fourth of that in the transverse direction.

Upload: others

Post on 15-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

  • 1

    TECHINICALSPECIFICATIONS

    PSC Pole (9 Mtr x 300 Kg ) I. Qualification Criteria of Sub Vendor /Manufacturer:- The prospective bidder may source PSC Poles from manufacturers who should have supplied PSC Poles to Electricity Supply

    Utilities / PSUs. The bidder should enclose Performance Certificates from the above users, issued in favour of the Sub Vendor / manufacturer, as proof of successful operation in field.

    Applicable Standard:

    The Poles shall comply with latest standards as under:

    REC Specification No. 15/1979, REC Specification No. 24/1983, IS 1678, IS 2905, IS 7321.

    II. Materials : Cement Cement to be used in the manufacture of pre-stressed concrete poles shall beordinary for rapid hardening Portland cement

    confirming to IS: 269-1976 (Specification for ordinary and low heat Portland cement) or IS: 8041 E-1978 (Specification for rapid

    hardening Portland cement). Aggregates

    Aggregates to be used for the manufacture of pre-stressed concrete poles shall confirm to IS:383 (Specification for coarse and

    fine aggregates from natural sources for concrete) .The nominal maximum sizes of aggregates shall in no case exceed 12mm. Water

    Water should be free from chlorides, sulphates, other salts and organic matter. Potable water will be generally suitable. Admixture

    Admixture should not contain Calcium Chloride or other chlorides and salts which are likely to promote corrosion of pre-stressing steel. The admixture shall conform to IS: 9103.

    Pres-StressingSteel

    Pre-stressing steel wires including those used as un tensioned wires should conform to IS:1785 (Part-I) (Specification for plain hard-drawn steel wire for pre-stressed concrete, Part-I cold drawn stress relieved wire).IS:1785 (Part- II)(Specification for plain hard-drawn steel wire) or IS:6003 (Specification for indented wire for pre-stressed concrete).The type design given in

    theannexure are for plain wires of 4 mm diameter with a guaranteed ultimate strength of 160kg/mm².

    All pre-stressing steel shall be free from splits, harmful scratches, surface flaw, rough, aged and imperfect edges and other defects likely to impair its use in pre- stressed concrete.

    Concrete Mix

    Concrete mix shall be designed to the requirements laid down for controlled concrete (also called design mix concrete) in IS:

    1343-1980 (Code of practice for pre-stressed concrete) and IS: 456 – 1978 (Code of practice for plain and reinforced concrete) subject to the following specialconditions:

    i) Minimum works cube strength at 28 days should be at least 420 Kg/cm². The concrete strength at transfer should be at least 210Kg/cm².

    ii) The mix should contain at least 380 Kg of cement per cubic meter of concrete.

    iii) The mix should contain as low water content as is consistent with adequate workability. It becomes necessary to add

    water to increase the workability the cement content also should be raised in such a way that the original value of water cement

    ratio ismaintained.

    III. DesignRequirements The poles shall be designed for the following requirements:

    The poles shall be planted directly in the ground with a planting depth as per IS: 1678. Wherever, planting depth is

    required to be increased beyond the specified limits or alternative arrangements are required to be made on account of ground

    conditions e.g. water logging etc., the same shall be in the scope of the bidder at no extra cost to owner. The bidder shall

    furnish necessary design calculations/details of alternative arrangements in this regard.

    The working load on the poles should correspond tothose that are likely to come on the pole during their servicelife. The factor of safety for all poles 9.0Mts. Shall not be less than 2.5 and for 8.0 M poles, the factor of safety shall not be less

    than2.5.

    The average permanent load shall be 40% of the working load. The F.O.S. against first load shall be 1.0.

    At average permanent load, permissible tensile stress in concrete shall be 30 kg/cm².

    At the design value of first crack load, the modulus of rupture shall not exceed 53.0kg/cm² for M-40. The ultimate moment capacity in the longitudinal direction should be at least one fourth of that in the transverse direction.

  • 2

    The maximum compressive stress in concrete at the time oftransfer of pre- stress should not exceed 0.8 times the cube strength.

    The concrete strength at transfer shall not be less than half, the 28 days strength ensured in the design, i.e. 420x0.5=210kg /cm². For model check calculations on the design of poles, referred to in the annexure, a reference may be made to the REC ―Manual

    on Manufacturing of solid PCC poles, Part-I-DesignAspects‖.

    IV. Dimensions andReinforcements

    The cross-sectional dimensions andthe details of pre-stressing wires should conform to the particulars given in the enclosed drawing. The provisions of holes for fixing cross-arms and other fixtures should conform to the REC specificationNo.15/1979.

    All pre-stressing wires and reinforcements shall be accurately fixed as shown in drawings and maintained inposition during

    manufacture. The un-tensioned reinforcement as indicated in the drawings should be held in position by the use of stirrups

    which should go round all thewires.

    All wires shall be accurately stretched with uniform pre-stressed in each wire. Each wire or group of wires shall be anchored

    positively during casing. Care should be taken to see that the anchorages do not yield before the concrete attains the

    necessarystrength.

    V. Cover The cover of concrete measured from the outside of pre-stressing tendon shall be normally 20mm.

    VI. Welding and Lapping of Steel The high tensile steel wire shall be continuous over the entire length of the tendon. Welding shall not be allowed in any case. However, joining or coupling may be permitted provided the strengthof the joint or coupling is not less than the strength of

    each individualwire. VII. Compacting

    Concrete shall be compactedby spinning, vibrating, shocking or other suitable mechanical means. Hand compacting shall not bepermitted.

    VIII. Curing

    The concrete shall be covered with a layer of sacking, canvass, Hessian or similar absorbent material and kept constantly wet

    up to the time when the strength of concrete is at least equal to the minimum strength of concrete at transfer of pre-stress.

    Thereafter, the pole may be removed from the mould and watered at intervals to prevent surface cracking of the unit the interval

    should depend on the atmospheric humidity and temperature. The pre-stressing wires shallbede-

    tensionedonlyaftertheconcretehasattainedthespecifiedstrengthattransfer (i.e. 200 or 210 kg/cm² as applicable). The cubes cast for

    the purpose of determining the strength at transfer should be coursed, a sear as possible, under condition similar to those under

    which the poles are cured. The transfer stage shall be determined based on the daily tests carried out on concrete cubes till

    the specified strength indicated above is reached. Thereafter the test on concrete shall be carried out asdetailed in IS: 1343(code

    of practice for pre-stressed concrete). The manufacture shall supply, when required by the owner or his representative, result of

    compressive test conducted in accordance with IS: 456 (Code of practice for plain and reinforced concrete) on concrete cubes

    made from the concrete used for the poles. If the manufacture so desired, the manufacture shall supply cubes for test purpose

    and such cubes shall be tested in accordance with IS: 456 (Code of practice for plain and reinforcedconcrete).

    IX. Lifting Eye-Hooks or Holes Separate eye-hooks or hoes shall be provided for handling the transport, one each at a distance of 0.15 times the overall

    length, from either end of the pole. Eye-hooks, if provided, should be properly anchored and should be on the face that has the shorter dimension of the cross-section. Holes, if provided for lifting purpose, should be perpendicular to the broad face of

    thepole.

    X. Holes for Cross Armsetc Sufficient number of holes shall be provided in the poles for attachment of cross arms and otherequipment.

    XI. Stacking & Transportation

    Stacking should be done in such a manner that the broad side of the pole is vertical. Each tier in

    the stack should be supported on timber sleeper located as 0.15 times the overall length, measured from the end. The timber

    supported in the stack should be aligned in verticalline.

    XII. Earthing

    (a) Earthing shall be provided by having length of 8 SWG GI wire embedded in Concrete during manufacture and the ends of the wires left projecting from the pole to a length of 100mm at 250 mm from top and 150 mm below groundlevel.

    (b) Earth wire shall not be allowed to come in contract with the pre-stressingwires XIII. Embossing/ Engraving :During manufacturing the Pole size, Sl. No. NESCO

    Utility,Manufacturer‘sname,P.ONo.&Date,MRHeadtobeEmbossed

  • 3

    / Engraved on each pole that can be clearly visible in naked eye

    GUARANTEED TECHNICAL PARTICULARS OF 9MTR.300 KG PRESTRESSED

    CONCRETE POLE

    Sl No.

    Description

    Unit

    Required Specification

    Bidder’s

    Offer

    1 Name of the Manufacturer & Address

    2 Type of pole Pre- Stress Concrete

    3 Factor of Safety 2.5

    4 Overall Length of Pole Meters Mtr. 9

    5 Working Load Kg Kg 300

    6 Point of application of load 600 mm below from top

    7 Depth of plantation mm 1500

    8 Overall Dimensions

    i) Bottom Depth 355

    ii) Top Depth mm 185

    iii) Breadth mm 100

    9 Reinforcement Detail:

    i) Diameter of Pre-stressing wire mm 4

    ii) No. of Tensioned wires Nos. 16

    iii) No. of Un-tensioned wire Nos. --

    iv) Length of each Pre-stressing wire Mtr. 9

    v) Ultimate Tensile Strength Kg/cm² 17500

    vi) Steel Quantity Kg/pole 14.20

    10 Concrete Detail

    i) Cement Type Ordinary Portland Cement

    ii) Concrete mix strength Kg/cm² a) 210 Kg/cm² at time of transfer of

    prestress (min)

    Kg/cm² b) 420 Kg/cm² at age of 28 days (min)

    iii) Concrete Quantity Cubic

    meter/ pol 0.243 m³

    iv) Concrete covering to wires mm 20

    11 GI earthing wire size SWG/

    mm 8/4.06

    12 Weight of PSC Pole Kg 607

    13 Standard confirming to:

    Pole IS: 1678 /2000

    Cement IS: 8041

    Aggregates IS: 383/1970

    Pre-stressing wire IS: 6003/1983

    Concrete Mix IS: 456/2000

    14 Tolerances Dimensions a)±15 mm on overall length of pole

    b) ±5 mm on sectional dimension

    c)0.5% on the uprightness of

    pole

    Signature of Bidder with seal

  • 4

    TECHINICALSPECIFICATIONS LT XLPE AB CABLE

    1. SCOPE:

    This specification covers the design,manufacturing, testing,supply, deliveryandperformance requirements ofLVoverhead ISI marked 3Ph 4 wire and 1PH 2 wire XLPE insulated AerialBunchedCable(ABC)indicated in our Schedule of Requirements for use in the LVnetwork of NESCO Utility. The materials offered should have been successfully type testedatany NABLAccreditedTesting Laboratory within a period of five years on the date of bid opening. Compliance shall be demonstrated by submitting with the bid(i) authenticated copies of the type test reportsand (ii) performance certificatesfromthe users.

    The Aerial Bunched Cable shall conform in all respects to highest standards of engineering, design, workmanship, this specificationand the latestrevisionsofrelevantstandardsat the time of offer and the Purchaser shall have the power to reject any work or material,which,in his judgment is not in full accordance therewith.

    2. STANDARDS:

    Except where modified bythis specification, the Aerial Bunched Cable shall be designed,

    manufactured and testedin accordancewith thelatest editions of the followingstandards.

    IES/ISO Indian Standard Material

    IEC:1089 IS: 398/1994 Round wire concentriclay

    Overhead electrical

    Stranded Conductors.

    IS: 398(Part-4)/1994 All AluminumAlloy

    Conductors, Quality

    ISO: 9000 Management Systems.

    IS: 8130/1984 Conductors forinsulated

    Electric cables.

    IS: 10810/1984 Method ofTestsforcables.

    IEC:502 IS:7098/1998 XLPEInsulated PVC.

    Sheathed power

    cables.IS:14255/1995 AerialBunched Cables for

    workingvoltageup to and

    including1100 volts.

    The Bidder may proposealternativestandards,provide ditisdemonstratedthattheygivea degreeofquality

  • 5

    andperformanceequivalenttoorbetterthanthereferencedstandards.The purchaser shalladjudgewhetherto accept or reject any standards.

    TheBiddershallfurnishacopyofthealternativestandardproposedalongwithhisbid.Ifthe

    alternativestandardisinalanguageotherthanEnglish,anEnglishtranslationshallbesubmitted with thestandard.

    Incaseofconflicttheorderoftheprecedenceshallbe(1)IECorISOstandards,(2)Indian Standards,(3) Otheralternativestandards.This listisnottobeconsidered exhaustiveand referencetoaparticularstandard orrecommendationinthisspecificationdoesnotrelievethe

    Contractororthenecessityofprovidingthegoodscomplyingwithotherrelevantstandardsor recommendation.

    3.0 SERVICE CONDITIONS:

    Theservice conditions shallbe as follows:

    Maximum altitude abovesealevel 500m

    Maximum ambient airtemperature 500C

    Maximum dailyaverageambient airtemperature 350C

    Maximum ambient air temperature 50C

    Maximumtemperatureattainablebyan object exposedto sun 600C

    Maximumyearlyweighted averageambient temperature 320C

    Maximum relativehumidity 100%

    Averagenumberof thunderstorm days per annum 70

    Averagenumberof rainydays per annum 120

    Average annualrainfall 150cm

    Wind pressure as perIS:5613(Part-I/Sec.I) 1985

    Wind Zones IS:5613 Part-I/Sec-I

    Light Medium Heavy

    Terrain Category 100Kg/m2 150Kg/m2 200Kg/m2

    Environmentally,theregionwheretheworkwilltakeplaceincludescoastalareas,subjectto highrelativehumidity,whichcangiverisetocondensation.Onshorewindswillfrequentlybe salt laden.

    On occasions, the combination of salt and condensation may create pollution conditions for outdoor insulators. Therefore,outdoor material shall be designed and protected for use in exposed,heavilypolluted

    saltycorrosive and humid coastal atmosphere.

    4. SYSTEMCONDITIONS: The materials shall be suitable for installation in supply systems of the following characteristics.

    Frequency 50Hz

    Nominal System Voltage 400/230V

    MaximumSystem VoltageLVSystem 440/250 V

    Minimum LVVoltage 370 V

    Power frequencyoneminute withstand 2KV (set &dry)

    Neutral EarthingarrangementLV System Solidlyearthed

  • 6

    5.0 GENERAL/ TECHNICAL

    ThedesignofAerialBunchedCableofferedshallcompriseacompacted,standard,harddrawn H2/

    H4grade aluminum phaseconductorasapplicableunderIS-8130/84 withcrosslinked polyethylene(XLPE)insulation0.65to1.1.KVclass,havingofcarbonblackcontent2.5%± 0.5%.

    Thesizes andnumberofcores requiredare: 3x50mm2 +1x35mm2(catenaries type) and 1X 35mm2

    +1x25mm2

    ThetypeofBunchedCablesshallbethreephaseinsulatedbundled.All Aluminum

    Conductorscombinedwithaneutralandcatenaries(bare)whichshallbeofheat treated aluminum magnesium silicon alloy wires containing approximately 0.5% each of

    magnesiumandsiliconrespectively.Thecatenariesmusthaveanultimatetensilestressofnot less than that specifiedinthe table oftechnical requirements.

    The Bidder shall specify the standard to which this bundleshall be manufactured.

    Theconductor bundle offered shall be designed to meet the requirements set out in this specification takingnoteofsafetyfactorspertainingtoconductororcatenarytensioningand NESCO specification: General Technical Requirements for LV overhead lines.

    However,abidofAerialBunchedCablesshallnotbeconsidered,unlessitisaccompaniedbya list of allspecial tools andequipments necessaryto complete theinstallation.

    6.0 CONDUCTORS:

    The phase conductors shall be of multi-stranded aluminum of compacted circular cross section.The aluminum shall comply with IS8130:1984. The messenger conductor shall be of multi-stranded Aluminum Alloy conforming to IS398(Part4)–1994.In addition to meeting all requirement of relevant ISS the LT XLPE AB Cables supplied shall satisfy following general requirements.

    (a) FOR PHASECONDUCTORS:

    Sl.No. Specified Cross Section Area(mm2)

    No.of strands

    Min.Diaof eachstrandin

    mm

    Min. overall dia.

    of conducting

    part

    Maxm. D.C Resistanceat

    20degree centigrade.( Ohm/Km)

    Nominal Insulation thickness

    (mm)

    1 35 7 2.5

    4

    7.62 As perISS/GTP 1.2

    2 50 7 3.0

    5

    9.15 As perISS/GTP 1.5

  • 7

    (b) FOR MESSANGER CONDUCTORS

    Sl. No.

    Phase conductor sizeofLT AB Cable

    inmm2

    Specified Cross

    Section Area (mm2) of the

    Messenger

    conductor

    No.of strands

    Nominal dia.of each

    strand

    Min overall dia. Ofconducting

    part of the compacted

    conductor(mm)

    Maxm. D.C Resistance

    of the messenger

    at20degree centigrade.( Ohm/Km)

    Approx. Mass

    (Kg/Km) forthe

    messenger

    1 25 7 2.14 6.42 As per

    ISS/GTP

    65

    2 35 7 2.54 7.6 As per

    ISS/GTP

    95

    6.0(b) The bidder must take required precaution to ensure that the averagediameterofeachstrandof

    conductor shall be ascertained through physical measurement of dimensions of finished cables at

    ambient temperature during pre-dispatch inspection or/and verification at NESCOStore by

    consignee and the value so obtained shall have a tolerance limit with reference to the nominal

    diameter of each strand of conductor as stated in the tables above.

    7.0 TOLERANCES:

    The measurement of strand diameter of the finished AB Cable shall not be less0.03mmfor

    Strands upto and including 3.00mmdiameter.Forstrandsabovethatsize, measurementofstrand

    diametershall not be lessthan 1%of thenominalstrand diameter.

    For the purpose of checking compliance with the above requirement, the diameter shall be

    determined by two measurement satright angles taken at the same cross section.The physical

    measurement of strands shall be conducted after opening the strands of a finished AB Cable

    offered forinspection.

    8.0 SPLICESIN WIRES:

    Splices in Wires shall generallycomplywith requirements ofIEC 1089. Thealuminumalloyrodsmaybesplicedbycoldpressurebutweldingbeforedrawingprovided

    themanufacturercanguaranteethatthesplicecandevelop90%ofthetensilestrengthoftheun

    slicedrod.Wireswhichbreakduringstrandingmaybeslicedbycoldpressurebutt-welding provided

    that:

    Notwosplicesinthecompletedconductoroccurwithin15mofeachotherandnotwosplicesin

    anyindividual wire areless than 150m apart.

    Thespliceshallbedonewithhighskilledworkmanship.Thefinishedspliceshallbesmoothand at no

    point shall the cross sectional areabeless than that ofthe un sliced wire.

    Splicingofthealloywiresonthestrandingmachineinordertoutilizelengthsofwiresonreels shall not

  • 8

    bepermitted.

    9.0 STRANDINGANDCORE LAY:

    Theconductorcores shallbestranded and thedirection oflaymustbeas defined inIEC:1089.

    10.0 INSULATION:

    TheAerialBunchedCablesshallbeinsulatedforavoltageclassof0.65/1.1KVandshallbe capable of

    operatingpermanentlyat 1.2KV.

    TheinsulationwallthicknessshallbedeterminedinaccordancewithTable-4(Clause-7.2and

    Clause7.3)ofIS: 14255/1995.

    Theinsulatingmaterialshallbeblackandsuitabletoresistultravioletradiation,saltladen

    sprays,chemicalpollution,ageingeffects,abrasionandmechanicalshocksandmechanicaland

    electricalstressattemperatureup to90˚Cinnormaloperationand2500Cundershortcircuit conditions

    perIEC:502/1994.

    Thecarbonblackcontentin theXLPE insulation shallbe2.5%± 0.5%

    11.0 PHASE IDENTIFICATION:

    Theindividualinsulatedconductorswithinabundleshallbeidentifiedbymeansoflongitudinal

    projections.

    Thethreephaseconductorsshallbemarkedbyone,twoorthreelongitudinalprojections, indicatingthe

    R,Y,Bphases respectively.

    Theprojections shall havethe followingdimensions.

    Thedistancebetweenthetipsoftwoadjacentprojections,wherethereismorethanone, shall

    bebetween 1.0and1.5m.

    Thewidth of theprojection at thebaseshall be 1.0mm; and

    Theheight of the projections shall be 0.5mm.

    For a single phase insulated conductor such type of phase identification shall not be required, but

    embossing the NESCO on it.

    12.0 INSULATION MARKINGS:

    Each individual conductor comprising abundle shall have the range of non-erasable distinct

    markings listed below legibly printed on the insulation surface at one meter intervals.The

    embossing should be very clear&easily visible to naked eye.

    ISIMark, IS14255-95, Manufacturer‟sB.I.S License No. legiblyembossed on the insulation.

  • 9

    Name ofthe Purchaser.: NESCO Utility

    P.O No.&Date Scheme :School &Anganwadi

    Manufacturer‘strademark identification for example ―UCXLPE50‖

    Year of manufacture:

    Designation of conductortype

    Size: for example ―3x50‖

    Shapeof conductor.

    Rated voltage class: 0.65/1.1KV

    Backupconductoridentification:conductorswithone,twoandthreeprojectionsshallbe marked

    R, Y andBrespectively. The conductor with no projection shallbemarked N and

    Theheightoftheprintedletteringshallbenotlessthan20%oftheoveralldiameterof the

    conductor

    13.0 TWIST: Thedirectionoflayoftheconductorscomprisingthebundleshallbeleft-handedandthelay ration

    shallcomplywithIEC:1089.

    Withabarecatenariesconfigurationtheinsulatedphasecablestogethershallbetwistedroundtheneutralc

    atenariestoformtheABC.Thiscablebundleisthen strungdirectlyontothe

    distributionpolessupportedbythecatenarieswithstandardapproved hardware.

    14.0 TESTS:

    14.1 General

    Wherenotspecified,alltestsandtestresultsshallconformtotherequirementsofIEC502/1994

    orIS7098(Part-I)1998,IS10810/1984,IS: 398(Part-IV) andIS: 14255/1955.

    Unlessexpresslystatedotherwise,theambienttemperatureforroutinetestsaswellasvoltage tests

    shallbe20 +150Cand for allothertests be 20+150C.

    Thefrequencyofthealternatingtestvoltageshallbe49Hzto51Hz.Thevoltagewaveform should

    besinusoidal.

    14.2 TypeTests

    Thetest sample shallbe10m to 15m in length. Allcores of thebundles shallbetested. Insulation resistanceat ambient temperature.

    Insulation resistanceat operatingtemperature. AC voltagetest.

    Theinsulationresistancetestatambienttemperatureshallbecarriedoutinawaterbathat ambient temperature.

    Theinsulationresistancetestataoperatingtemperatureshallbeconductedinawaterbathat 900C.

    Thelongitudinalprojectionsusedforphaseidentificationshallbeignored.Theresultsofthistest shallbeusedtocalculatethevolumereceptivityandtheresultsconformtotherequirementsof IEC: 502/1994

  • 10

    orIS10810 (Part-43).

    TheACvoltagetestshallbecarriedoutbyapplying1.95KV(3U0)forfourhourstothesample, whichshallbe

    submergedinawaterbathatambienttemperature,havingbeensteepedfora period not less than one hour. The

    test shall only be deemed to have been passed if no breakdown occurs.

    Furthermore, the followingnon-electrical typetests shallalso be carried out:

    Insulationwallthickness:thelongitudinalprojectionsusedforphase1identifications shall beignored as

    perIS10810 (Part-6);

    Ageingtest,consistingofanevaluationoftheretentionofthemechanicalpropertiesof the insulation after

    ageing.

    Wrappingtest: as perIS10810 (Part-3);

    Testsforbleedingand bloomingof pigment as perIS10810(Part-9)

    Thermal expansion of insulation.

    Measurement of carbonblack contentas perIS10810 (Part-32).

    Water absorption bytheXLPE insulation, shrinkingof theXLPE insulation.

    Tensiletest: adhesion between conductor and insulation.

    The adhesiontestrequiresatensiletestingmachine.Asampleofatleast300mmlengthshallbe selected and straightenedout.Theinsulationshallberemovedforalengthof150mm.The insulatedendshallbeheldintheuppergripheadandthebareconductoronthelowergriphead.

    Tensionshallbeapplied ataspeedof500mm/ minuntil theconductorfirstbeginstoslidewithin

    theinsulation.Thetestshallhavebeenpassediftheconductorandinsulationcombinationcan stand 75N/mm2

    withoutslippageoccurring. Theneutralconductor/catenariesshallbetypetestedinaccordancewiththerequirementsofIS

    398(Part-IV) 1994.

    14.3 RoutineTests

    Thefollowingmeasurement ortests shall be carried out on all drums and coils of Bunchedcable:

    Conductor resistance

    Voltagetest.

    Theconductortobetestedforconductorresistanceshallbestoredforatleast12hoursinaroom atparticularconstanttemperature.Ifitcannotbeestablishedthattheconductorshavereached the room temperature, the test should be postponed for a period of further 12 hours. Alternatively, the test

    can be carried out on short sample after remaining one hour in a temperature controlled waterbath. Thetest shall be carried out andthe conversion factors used to

    convert the resistance value to a base of 2000Cand one Km. The DCresistance of each

    conductor shallnot exceed the appropriatemaximum values specifiedinIEC:228/IS:6474.

    Thevoltagetestshallbeconductedbyapplyingtoeachcore3.5KVAC(2.5U0 plus2KV)or

    8.4KVDCfor5minuteswiththespecimenlyinginawaterbathatambienttemperature.The conductor

    shallpass thetest if no electrical breakdown occurs.

  • 11

    14.4 AcceptanceTests

    Thefollowingsamplecheck,measurementsandtestshallbecarriedoutinadditiontothe

    AcceptanceTestsas perIS 14255– 1955,IS: 398 ( Part–IV )1994,IS8130 / 1984

    Measurement of insulation wallthickness;

    Measurementofdiameterofeachstrand,overalloutsidedia&CrossSectionalAreaof the conductingPart out of the finishedproduct duringpre-dispatch inspection.

    Thermal expansion test; Check of physical characteristics

    Tensilestrength of individual wires ofconductor.

    High VoltageTest on drums immersed in water(applyvoltage3.5 KV AC for5 min)

    Thesetests should be carried out on one length form each production batchofthe same sample.

    Thethicknessoftheinsulationwallshallbemeasuredonapieceremovedfromeachendofthe samplelength.If eithermeansorminimumvaluesarenotmet,twofurthersamplesshallbe removedat0.5mformtheend correspondingtothefailedspecimen.Ifthesesamplesdonot

    satisfythemeanandminimumthickness requirements,thetestshallbedeemedtohavebeen failed.

    Thelongitudinal projections used forphaseidentifications shall be ignored. Thethermal expansion test need onlybe carried out on one core.

    Inrelationtothetensiletest,thetensilestrengthofthealuminumwiresbeforestrandingandthat ofthe

    finished conductorshall complywithIEC:1089.

    14.5 Test on theCatenary (messenger) Conductor

    Breaking load, elongation and resistance tests shall be completed on the aluminum alloy

    catenaries conductor in accordancewith therequirements ofIS:398 (Part-IV)/1994 orIEC:1089.

    14.6 BendingTest on a complete cable

    Thistestshallbeperformedonasampleofcompletedcable.Thesampleshallbebentarounda

    testmandrelatroomtemperatureforatleastonturn.Itshallthenbeunwoundandtheprocess

    shallberepeatedafterturningthecablesamplearounditsaxisby1800.Thisprocessshallbe

    repeatedtwicemore.Thereshallbenosignsof breakingorcrackingofthecableinsulation

    duringthis test.

    Thediameterof themandrel shall be:

    10(D+d)

    WhereD =Actual diameterof thecable (mm)

    d=Actual diameter ofthe conductor(mm)

  • 12

    14.7 Rejection andRetests

    Shouldanyoneofthetestpiecesfirstselectedfailtopassthetests,twofurthersamplesfromthe

    samebatchshallbeselectedfortesting,oneofwhichshallbefromthelengthfromwhichthe

    original test sample was taken unless the length has been withdrawn bythesupplier.

    Shouldthetestpiecesfrombothoftheseadditionalsamplessatisfy therequirementsofthetests,

    thebatchrepresentedbythesesamplesshallbedeemedtocomplywiththestandard.Shouldthe

    testpiecesfromeitherofthetwoadditionalsamplesfail,thebatchrepresentedshallbedeemed to

    have failed.

    15.0 COMPLIANCE WITH SPECIFICATION:

    The Aerial Bunched Cable shall comply in all respects with the requirements of this

    specification. However,anyminordeparturefromtheprovisionsofthespecificationshallbe

    disclosed at thetime ofbiddingin theNon-complianceSchedule ofthis document.

    16.0 COMPLIANCE WITH REGULATIONS:

    AllthecablesshallcomplyinallrespectswiththeIndianRegulationsandActsinforce.The

    cablesand connectionsshallbedesignedandarrangedtominimizetheriskoffireandany damage,

    which might becausedin the event of fire.

    17.0 NON-CONFORMING PRODUCT:

    ThePurchaserreservestherightfordecisionsregardingacceptance,modificationorrejectionof

    non-conformingitems.

    18.0 INSPECTION AND TESTING:

    The Purchaserorhisauthorizedrepresentativehasfreeentryatalltimes,whileworkonthe contract is being performed, to all parts of the manufacturer‘s works which concerns the processing of the cables ordered. The manufacturershall afford the purchaser or his

    authorizedrepresentativeswithoutcharge,allreasonablefacilitiestoensurethatthecablebeing furnished is in accordancewith thesespecifications.

    Thecablesshallsuccessfullypassalltheroutinetests&acceptanceTests referredto inthesectionontestsandthoselistedinthemostrecenteditionofthestandardsgiveninthe specification.

    ThePurchaserreservestherighttorejectanyofthecablesifthetestresultsdonotcomplywith thevalues

    specified or with thedategiven in the Technical data schedule.

    Type Test Certificates for the tests conducted earlier shall be submitted with the bid for evaluation. Therequirements of additional typetestswillbe at thediscretion ofthe Purchaser

  • 13

    ThePurchasershallwitnessroutinetests .Inordertofacilitatethis,thecontractorshall givethe purchaser

    of15daysnoticethatthematerialisreadyforinspection&testing.The

    suppliershallextendallassistancetotherepresentativeofthePurchaserduringhisinspection&

    testingofsamplesathisworks.Thematerialsshallbedispatchedonlyafterapprovalofsuch

    TestReportsandissueofDispatchclearancebythePurchaser.HoweverthePurchaserreserves

    therighttoretestthematerialsafterdeliveryatanyNABL Accredited TestingLaboratoryin case

    of anydisputes regarding size & quality of supplied materials at a later date during

    guaranteeperiod. Thecost of such retestingshallbebornebythe supplier.

    Allcostsinconnectionwiththetesting,includinganynecessaryretestingshallbebornebythe

    Contractor,who shallprovidethePurchaserwithallthetestshallhavetherighttoselectthe

    samplesfortestandshallalsohave therighttoensurethatthetestingapparatusiscorrect.

    Measuringapparatusforroutinetestsshallbecalibratedattheexpenseofthecontractoratan approved

    laboratoryandshall be approved bythepurchaser beforetesting.

    TheContractorshallberesponsibleforthepropertestingofthematerialssuppliedbysub- Contractor to

    thesame extent as if the materials were completed orsupplied bythe contractor.

    AnycostincurredbythePurchaserinconnectionwithinspectionorretestingasaresultof failureofthe

    equipmentundertestordamagedduringtransportoroffloadingshallbetothe account of theContractor.

    The Third Party Independent Evaluation Agency (TPIEA) if required may be engaged by NESCO Utility

    who shall have right to conduct pre & post despatch inspection jointly with NESCO Utility / independently

    of the equipment / materials procured by the Purchaser.

    TheContractorshallsubmittothePurchaserthreesignedcopiesofthetestCertificates,giving

    theresultsofthe testsasrequired.NomaterialsshallbedispatcheduntilthePurchaserhas received the test

    certificate and the contractor has been informed that theyareacceptable.

    Thetestcertificatemustshowtheactualvaluesobtainedfromthetests,intheunitsusedinthis specification,

    and mostmerelyconfirm that the requirements havebeen met.

    Inthecaseofcomponentsforwhichspecifictypetestsorroutinetestsarenotgiveninthis specification, the

    Contractor shall include a list of the tests normally required for these

    components.Allmaterialsusedin theContractshallwithstandandshallbecertifiedtohave

    satisfactorilypassed suchtests.

  • 14

    NoinspectionorlackofinspectionorpassingbythePurchaser‘s representativeofequipmentor

    materialswhethersupplied bytheContractororsub-Contractor,shallrelievethecontractorfrom

    hisliabilitytocompletethecontractworksinaccordancewithcontractorexoneratehimfrom anyof his

    guarantees.

    19.0 GUARANTEE:

    Thecontractor shallguaranteethe

    following: Qualityand strength

    ofmaterials used.

    Satisfactoryoperationduringtheguaranteeperiodof 12monthsfromthedateof commissioning.

    Performance figures as supplied bythe bidder in thetechnical datasheet.

    20.0 PACKINGANDSHIPPING:

    The cable shall be wound on strong drums or reels capable of withstanding all normal

    transportation and handing.

    Eachlengthofcableshallbedurablysealedbeforeshipmenttopreventingressofmoisture.The

    drums reels or coils shall belagged or covered with suitablematerial to provide

    physical protection for thecable duringtransitor duringstorage and handlingoperations.

    Inthecaseofsteel drums adequate precautions shallbetaken to prevent damagebeing caused

    by directcontactbetweenthecablesheathandthesteel.Theseprecautionshallbesubjecttothe

    approval of thePurchaser.

    Ifwoodendrumsareusedthenthewoodshallbetreatedtopreventdeteriorationfromattackby termites and fungi.

    Each drum orreel shall carryor bemarked with followinginformation:

    Individual serial number

    StandardISIMark, 14255-95, Manufacturer‟sB.I.SLicenseNo.

    Name ofthe Purchaser: NESCO Utility

    Destination

    PurchaseOrder No.&Date

    Manufacturer‘sName

    Yearof manufacture

    Cable size and type

  • 15

    Length of conductor(meters)

    Net and Gross mass ofconductor (Kg)

    Allnecessaryslingingand stackinginstructions

    Destination

    Countryof origin

    Thedirection ofrollingas indicated byan arrow shallbemarked ona flange.

    21.0 STORAGE:

    The sites elected for the storage of cable drums shall be well drained and preferably have a

    concrete/firmsurfacewhichwillpreventthedrumssinking into thegroundorbeing subjected to

    excess waterthus causingflange rot.

    Alldrumsshallstandonbattens,intheuprightpositionandinsuchamannertoallowsufficient

    spacebetweenthemforadequateaircirculation.Duringstoragethedrumsshallberotated900

    every threemonths.Innoinstancesshallbethedrumsbestored―flat‖ontheirflangesoroneon top

    of each other.

    22.0 SHIPPING:

    TheContractorshallberesponsiblefortheshippingofallcables,drumsandreelssuppliedfrom

    abroadtotheportsofentryandforthetransportofallgoodstovariousspecifieddestinations

    includingcustoms clearance, offloading,warehousingand insurance.

    TheContractorshallinformhimselffullyastoallrelevanttransportfacilitiesandrequirements

    andloadinggaugesandensurethattheequipmentaspackedfortransportshallconformtothese

    limitations. The contractor shallalso be responsible forverifyingthe access facilities

    specified.

    Thecontractorshallberesponsiblefortransportationofalltheloadsassociatedwiththecontract

    andshalltakeallreasonablestepstopreventdamageofanyhighwayorbridgesbyhisvehicles

    byselectingroutes,choosing propervehiclesforuseandrestrictinganddistributingloadsto

    avoidtheriskofdamage.TheContractorshallimmediatelyreporttothePurchaseranyclaims

    madeagainstthe contractor arising outof allegeddamageto a highwayorbridge.

    All itemsofequipmentsshallbesecurelyclampedagainstmovementtoensuresafetransitfrom themanufacturer‘s facilities to thespecifieddestinations.

  • 16

    23.0 HAZARDOUS SUBSTANCES:

    TheContractor shall submit safety data sheets for all hazardous substance used with the

    equipment.Thecontractorshallgiveanassurancethattherearenoothersubstancesclassifiedas

    hazardousintheequipmentsupplied.Heshallalsotakeresponsibilityforthedisposalofsuch

    hazardous substances that maybefound foranyinjuries resultingfrom those substances.

    24.0 SUBMITTALS:

    Thefollowingshallbe required in duplicate along with thebid:

    Completed technical datasheets;

    Descriptiveliterature givingfulltechnical detailsof equipment offered.

    Outlinedimensiondrawingforeachtypeofconductor,foreachbundleshowingthe conductor

    strand,composition and thebundle twist;

    Typetest certificates, whereavailable, and sampleroutinetest reports;

    Detailedreferencelistofcustomersalreadyusingequipmentofferedduringthelastfive years

    with particular emphasison units of similar design and rating;

    Performancereports from the customers forthe suppliedLT XLPE ABCables.

    Detailsofmanufacturer‘squalityassurancestandardsandprogrammeandISO9000

    series or equivalent national certificates;

    Deviations from this specification to be submitted as per Non-Compliance. Only deviationsapproved in writingbeforeaward of contract shall beaccepted;

    Listofrecommendedsparepartsforfiveyearsofoperationwithpricesandspareparts cataloguewith

    pricelist for futurerequirements.

    Anyotherdocumentstoestablishqualifying&credibilityrequirementsasspecifiedin this Tender

    Document.

    25.0 PERMANENT EMBOSSING: Allmaterialssuppliedunderthis tendershallbeardistinct markof―NESCO

    Utility,andPurchaseOrderNo.&Date , Size of cable , length marking , voltage grade, Manufacturer, Trade mark , ISI mark , Phase marking, School &Anganwadi Scheme‖ bywayofembossing /enamel painting etc. includingother informationmentioned in GTP.

    This should be clearlyvisibleto naked eye.

  • 17

    GUARANTEED TECHNICAL PARTICULARSFOR 3X50+1X35 MM² and 1X35+1X25 LT

    XLPE AB CABLE.

    Sl

    No

    Description

    Specified Bidder’s

    Offer

    1 Ref. ISS /IECfollowed IS 14255/95, IS 398 PartIV

    2

    PhaseConductormaterial/Insulationtype

    H2 /H4 E.CgradealuminiumasperIS

    8130/84 / XLPE insulation (IS

    14255/95)

    3 MaterialofNeutralCatenary AluminumalloyasperIS 398 Pt-IV

    4 Voltage Class 0.65/1.1 KV

    No. ofStrands ofPhase Conductor 7

    5 No. ofstrands/Average /MinimumStrand Dia. In

    mm. (Finished Phaseconductor.)

    7/3.05

    6

    Approximate Overall Dia.Ofcompactedphase

    conductor afterremovalof insulation.(in mm.)

    9.15

    7

    No. OfStrands/Average Strand Dia.Inmm.

    (NeutralCatenary.)

    7/2.54

    8

    MinimumOverall Dia. Ofcompacted Bare Neutral

    Caternary.(in mm.)

    7.62

    9

    Minimumaverage thickness ofinsulation ofphase

    Cond. (mm)

    1.5

    10

    Minimumthickness ofinsulation ofPhase Cond.

    Atany point (mm)

    1.25

    11 MaximumDCresistanceofPhaseconductorat20

    oC

    ohmn/ KM

    0.64

    15 MaximumDCresistanceofneutralcond. Ω/Km 0.986

    16 Ultimatetensile strength ofneutralconductor(KN) 9.8

    17 Maximumtemperature(Continuous) 90°Cforphaseand 75 °Cforneutral

    18

    Embossingon insulationateach one meterinterval

    DistinctNon-erasable ISIMark, IS

    14255-95, Manufacturer‟s B.I.S

    LicenseNo., Name ofthe Purchaser,

    Name of the manufacturer,Size

    ofcable, phase marking,voltage

    Gradealongwith sequentialmarkingof

    length, Phase identif ication mark, ―

    School &Anganwadi―

    19 Cable drumlength 500 /1000m

    20 Volume Resistivityofinsulation at27°C 1X1013

    Ώ-cmmin.

    21 Volume Resistivityofinsulation at70°C 1X1011

    Ώ-cmmin.

    N.B: 1)Forvaluesnot availablein relevantISS,valuesindicatedinourGTP/ TenderSpecification shallbe valid. 2)Incaseof discrepancies betweenvaluesofISS& GTP, better will prevail. 3)Averagediametersofstrandsofeachcableshallbeascertainedbyphysicalmeasurementafter openingthestrandsof eachphaseofafinishedAB Cableoffered forinspection.

    Signature of the Bidder with Seal

  • 18

    TECHNICAL SPECIFICATION OF R.S Joist Pole

    1.0 Scope of Work:

    This specification covers design, manufacture, testing and supply of 150x150mm RS Joist designed for a working

    load of 346kg. The bidder should enclose Performance Certificates from the above users, issued in favourof the

    Sub Vendor / manufacturer, as proof of successful operation infield.

    Applicable Standards:

    This specification covers the manufacturing, testing before dispatch and delivery of following

    R.S Joists

    Sl No 150x150mmRS Joist

    1 150 x 150 mm R.S. Joist length:-13mtr&11mtr 34.6kg/mtr

    MT

    2.0 Standards:

    The R.S Joists shall comply with the requirements of latest issue of IS – 2062 Gr – A except where specified

    otherwise.

    3.0 Climatic Conditions :

    The climatic conditions at site under which the store shall operate satisfactory, are as follows Maximum

    temperature of airinshade 45ºc

    Maximum temperature of airinshade 0 cMaximum

    temperature of airinshade 50º c Maximum rain fall per annum

    2000mm Maximum temperature of air in shade 45º c

    Maximum ambienttemperature

    45º c Maximum humidity 100%

    Av. No. of thunder storm days per annum 70%

    Av. No. of dust storm per annum 20

    Av. Rain fall per annum 150mm

    Rolled SteelJoists

    The Rolled Steel joist (RSJ) support structures shall be fabricated from mild steel, grade A and in lengths dictated

    by design parameters .The joists, may include, but shall not be limited to the size i.e.150 X 150 mm;

  • 19

    Dimensions and Properties

    RSJ DES IGNATION 150 x 150 mm IS HB

    Length of Joist in Mtr with +100mm/-

    0% Tolerance

    13mtr,11mtr,9mtr

    Weight kg/m with±2.5% Tolerance 30.6

    Sect ional Area (cm2) 39.00

    Depth(D) o f Section (mm) with

    +3.0mm/ -2.0mm Tolerance as per IS

    1852-1985

    150.00

    Width(B)ofFlange(mm) ±4.0mm Tolerance for 150x

    150 mm ISHB IS1852-1985

    150.00

    Thickness of Flange(Tf) (mm)

    with±1.5mm Tolerance

    9.00

    Thickness of Web(Tw) (mm)

    with±1.0mm Tolerance 8.40

    Corner Radius of fillet o r root (R1) (mm) 8.00

    Corner Radius of Tow (R2) (mm) 4.00

    Moment o f Inertia

    Ixx (cm4) Iyy (cm

    4) 1540.00

    460.00

    Radius o f Gyration (cm)

    RxxRyy 6.29

    3.44

    Flange Slope(α) in Degree 94.0

    Tolerance in Dimension As perIS:1852

    MECHANICALPROPERTIES:

    Tensile Test : Requirement as perIS:2062/

    1999 Grade-A

    Yeild St ress(MPa) Min250

    Tensile Strength(MPa) Min410

    Lo=(5.65√So)Elongat ion% Min23

    Bend Test Shall not Crack

    CHEMICALPROPERTIES: Chemical Compos it ion Requirement as

    perIS:2062/

    1999 Grade-A

    Permissib le variat ion over the

    Specified Limit ,Percent,Max

    Grade A -

    Chemical Name Fe-410W A -

    Carbon(%Max.) 0.23 0.02

    Manganese(%Max.) 1.5 0.05

  • 20

    Sulphur(%Max.) 0.050 0.005

    Phosphorous(%Max.) 0.050 0.005

    Silicon(%Max.) 0.40 0.03

    Carbon Equivalent (%Max.) 0.42 -

    Deoxidat ion Mode Semi-killed o r killed -

    Supply condit ion As ro lled -

    However,Incase ofanydiscrepancybetweentheabovedata&therelevantISS,thevalues indicatedin the IS

    shallprevail.

    The Acceptance Tests shall be carried out as per RelevantISS.

    5.2.150x150mm RS Joists:

    RS Joists of Specific Weight 34.6kg/mtrwith length 15mtr, 13mtr,11mtr & 9mtr pole of 9n0s,20nos,41nos and

    11nos respectively with specif ied weight in MT shall have to be supplied as per IS:2062;2006 Grade‖A‖ ,

    IS:808;1989/2001, IS1608:1995 & IS:12779-1989 and their latest amendment if any complying the

    required Dimens ion, Weight, Chemical & Mechanical properties confirming to the relevant IS, as per the

    Tolerance givenBelow.

    APPLICABLE TOLLERANCES :

    1. Length o f each po le = + 100mm / - 0 % As per relevant IS:12779-1989

    (W ith p roportionate change in no o f Po les)

    2. Specific Weight o f RS Jo ists = ±2.5% As per relevantIS:1852/1985

    3. Weight for whole lot of supply for all categories = ±3.0% As per relevant IS: 12779-1989 for both type of RSJoists.

    EMBOSSING ON EACH R.SJOIST:

    Following distinct non-erasable embossing is to be made on each R.S Joists.

    a) Name & Logo of theManufacturer.

    b) B.I.S Logo (ISI Mark) if applicable.

    c) Size of the R.SJoist

  • 21

    GUARANTEED TECHNICAL PARTICULARS FOR

    (RS JOISTS of sizes 150x150mm) (To be submitted along w ith offer)

    1.1. Dimensions and Properties :

    PARTICULARS S peci fication S peci fication By

    the Bidder

    Length o f Jo ist in Mtr with +100mm/ -0% Tolerance 13mtr &11mtr

    Weight kg/m with±2.5% Tolerance 30.6

    Sect ional Area (cm2) 39.00

    Depth(D) o f Section (mm) with +3.0mm/ -

    2.0mm Tolerance as per IS 1852-1985

    150.00

    Width (B)of Flange (mm) with ±2.5mm

    Tolerance fo r116 x 100 mm ISMB&

    ±4.0mm Tolerance for 150 x 150mm

    ISHB IS 1852-1985

    150.00

    Thickness of Flange (Tf) (mm)

    with±1.5mm Tolerance

    9.00

    Thickness of Web(Tw) (mm) with±1.0mm

    Tolerance

    8.40

    Corner Radius of fillet o r root (R1) (mm) 8.00

    Corner Radius of Tow (R2) (mm) 4.00

    Moment o f Inertia

    Ixx (cm4) Iyy (cm

    4)

    1540.00

    Radius o f Gyration(cm)

    Rxx

    Ryy

    6.29

    3.44

    Modulus o f Section

    Zxx(cm3) Zyy(cm

    3)

    205

    60.2

    Flange Slope(α) in Degree 94.0

    Tolerance in Dimension As per IS:1852

    Distinct Non -Erasab le Embossings to be

    made on each R.S. Joist

    a) Name & Logo of theManufacturer.

    b) B.I.S Logo (ISI Mark) ifapplicable.

    c) Size

  • 22

    Signature of the bidder with Seal

    11 KV “V” CROSS ARM, BACK CLAMP FOR “V”CROSS ARM

    & POLETOP BRACKET (F CLAMP)

    TECHNICAL SPECIFICATIONS

    Qualifying Criteria:-

    The prospective bidder may source the above items from manufacturers /suppliers full filling the

    technical specification.

    a) Hot Dip Galvanised Cross arms and Pole Top Brackets for both 33KV & 11KV construction at

    intermediate and light angle pole shall be fabricated from grade 43A mild steel of channel section and

    for heavy angle poles, end poles and section poles fabricated from grade 43A mild steel of angle

    section. The grades of structural steel shall conform to IS – 226:1975.

    b) The Back Clamp for both 33KV & 11 KV ‗V‘ cross arm shall be made out of 50 x 8 GI Flat and

    shall be suitably designed to fit 150x150 mm RS Joistpole.

    c) The Pole Top Bracket (F Clamp) shall be made out of 100x50 mm MS Channel (GI) for 33 KV& 75x40 MS channel (GI) suitably designed to fit 150 x150xmm RS Joistpole.

    Except where otherwise indicated all dimensions are subject to the following tolerances: dimensions up

    to and including 50mm:+1mm: and dimensions greater than 50mm: +2%

    All steel members andother parts of fabricated material as delivered shall be free of warps, local

    deformation, unauthorized splices, or unauthorized bends. Bending of flat strap shall be carried out cold. Straightening shall be carried out by pressure and not byhammering.

    Straightness is of particular importance if the alignment of bolt holes along a member is

    referred to its edges.

    Holes and other provisions for field assembly shall be properly marked and cross referenced. Where

    required, either by notations on the drawing or by the necessity of proper identification and fittings for

    field assembly, the connection shall be match marked. A tolerance of not more than 1mm shall be

    permitted in the distance between the center lines of boltholes.

    The holes may be either drilled or punched and, unless otherwise stated, shall be not more than

    2mm greater in diameter than the bolts. When assembling the components force may be used to bring the boltholestogether(providedneithermembersnorholesaretherebydistorted)butall

    force must be removed before the bolt is inserted. Otherwise strain shall be deemed to be present

    and the structure may be rejected even though it may be, in all other respects, in conformity with the

    specification.

    The back of the inner angle irons of lap joints shall be chamfered and the ends of the members cut where necessary and such other measures taken as will ensure that all members can be bolted together

    without strain or distortion. In particular, steps shall be taken to relieve stress in cold worked steel so as

  • 23

    to prevent the onset of embitterment duringgalvanizing.

    Similar parts shall be interchangeable. Shapes and plates shall be fabricated and assembled in the shop to the greatest extent practicable.

    Shearing flame cutting and chipping shall be done carefully, neatly and accurately. Holes shall be cut,

    drilled or punched at right angles to the surface and shall not be made or enlarged by burning. Holes

    shall be clean- cut without torn or ragged edges, and burrs resulting from drilling or reaming operations

    shall be removed with the propertool.

    Shapes and plates shall be fabricated to the tolerance that will permit field erection within tolerance,

    except as otherwise specified. All fabrication shall be carried out in a neat and workmanlike manner

    soas to facilitate cleaning, painting, galvanizing and inspection and to avoid areas in which water and

    other matter canlodge.

    Contact surfaces at all connections shall be free of loose scale, dirt, burrs, oil and other foreign materials that might prevent solid seating of the parts.

    Fabrication has to be made as per drg. of„ V „ X-arm, Back clamp & „ F „clamp.

    GALVANISING

    All type of cross arms back clamps, F clamps & stay clamps shall be hot dip galvanized, are as

    following: All galvanizing shall be carried out by the hot dip process, in accordance with Specification

    IS

    2629. However, high tensile steel nuts, bolts and spring washer shall be electro galvanized to Service

    Condition4. The zinc coating (610 gmsper sq.mt) shall be smooth, continuous and uniform. It shall be

    free from acid spot and shall not scale, blister or be removable by handling orpacking.

    There shall be no impurities in the zinc or additives to the galvanic bath which could have a

    detrimental effect on the durability of the zinccoating.

    Before picking, all welding, drilling, cutting, grinding and other finishing operations must be completed

    and all grease, paints, varnish, oil, welding slag and other foreign matter completelyremoved.

    All protuberances which would affect the life of galvanizing shall also be removed.

    The weight of zinc deposited shall be in accordance with that stated in Standard IS 2629 and shall

    not less than 0.61kg/m² with a minimum thickness of 86 microns for items of thickness more than

    5mm, 0.46kg/m² (64 microns) for items of thickness between 2mm and 5mm and 0.33kg/m²

    (47 microns) for items less than 2mmthick.

    Parts shall not be galvanized if their shapes are such that the pickling solutions cannot be removed with

    certainty or if galvanizing would be unsatisfactory or if their mechanical strength would be reduced.

    Surfaces in contact with oil shall not be galvanized unless they are subsequently coated with an oil

    resistant varnish orpaint.

  • 24

    In the event of damage to the galvanizing the method used for repair shall be subject to the a pproval of

    the Engineer in Charge or that of his representative.

    In no case the repair of galvanisation on site will be permitted.

    The threads of all galvanized bolts and screwed rods shall be cleared of spelterby spinning or brushing.

    A die shall not be used for cleaning the threads unless specifically approved by the Engineer in

    Charge. All nuts shall be galvanized. The threads of nuts shall be cleaned with a tap and the

    threadsoiled.

    Partial immersion of the work shall not be permitted and the galvanizing tank must therefore be

    sufficiently large to permit galvanizing to be carried out by one immersion.

    After galvanizing no drilling or welding shall be performed on the galvanized parts of the equipment

    excepting that nuts may be threaded after galvanizing. To avoid the formation of white rust galvanized

    materials shall be stacked during transport and stored in such a manner as to permit adequate ventilation.

    Sodium dichromate treatment shall be provided to avoid formationof white rust after hot dip

    galvanization.The galvanized steel shall be subjected to test as per IS-2633.

    11 KV V Cross Arm (GI): The Cross arm is to be made out of ISMC 75x40 with 50mmx6mm flat packing on top & bottom flange of the

    channel where the insulator pin is to be mounted conforming to REC construction standard &drawing .

    Galvanized the V cross arm as per IS-2633/1972.(Latest Amendment) , IS :2629/1985 (1st

    .Revision).

    Guaranteed Technical Particulars of 11KV 'V' Cross Arm

    Sl. No.

    Description

    Specified

    Bidders Offer

    1 Type of Cross Arm ISMC 75x40

    2 Channel Weight 7.14 Kg/mtr

    3 Grade of Steel FY 250

    4 Steel Standard IS:2062-1992

    5 Fabrication Standard IS:802 (part - 2) - 1978

    6 Dimension (75x40x4.8)mm

    7 Size of M S Flat welded at both

    ends 50x8mm

    8 Steel Tensile Strength 1500kgf/cm²

    9

    Working Load

    200/300/350/400Kg

    10

    Total Weight (with tolerance per meter + 4%)

    11.2 Kg (approx.)

    Signature of the bidder with Seal

  • 25

    GUARANTEED TECHNICAL PARTICULARS FOR 11KV POLE TOP BRACKET

    Sl.No. Constructional Features Spec if ied Bidders

    Offer

    1. Material used 65x65x6 mm MS Angle &

    100x50x6 mm MS Channel

    2. Overall height 380 mm

    3. Flange Width (one welded & 65 mm

    4. Spac ing between two flanges 100mm

    5. Spacing of 2 nos of 18 mm holes for

    fixing on pole top

    100mm

    6. C/L Distance of 2nos of 25mm

    holesontopflangesofthebracket

    40mm from edge

    of the flange

    7. Galvanization Hot dip

    8. ISS 2062 ,2633

    9. Draw ing enclosed

    Name & Signature of

    Bidder with seal

    11KV POLE TOP BRACKETS (FCLAMP)

    GURANTEED TECHNICAL PARTICULARS

    (To be submitted along with offer)

    Sl.

    No.

    Description Unit Unit Bidder‟s offer

    11 Kv

    1 Type of crossarm

    2 Grade of steel

    3 Steel standard

    4 Fabrication Standard

    5 Dimensions Mm

    6 Steel section utilized

    7 Steel tensile strength N/cm²

    8 Working load Kg

    9 Details of galvanizing method utilizedand standard/specification conforming to?

    10 Weight of bracket Kg

    11 Whether drawing has been submitted with the bid

    Signature of the bidder with Seal

  • 26

    BACK CLAMP FOR “V” CROSSARM

    GURANTEED TECHNICAL PARTICULARS

    (To be submitted along with offer)

    Sl.

    No.

    Description Unit Unit Bidder‟s offer

    11 Kv 33 Kv

    1 Type of Clamp

    2 Grade of steel

    3 Steel standard

    4 Fabrication Standard

    5 Dimensions Mm

    6 Steel section utilized

    7 Steel tensile strength N/cm²

    8 Working load Kg

    9 Details of galvanizing method utilized and standard/specification conforming to?

    10 Weight of back clamp Kg

    11 Whether drawing has been submitted with the

    bid

    Signature of the bidder with Seal

    Fixing of CrossArms

    After the erection of supports and providing guys, the cross-arms are to be mounted on the

    support with necessary clamps, bolts and nuts. The practice of fixing the cross arms before the

    pole erection should be followed.

    GI Clamp for HT Stay set:

    HT stay clamp suitable for 150x150 mm Joist pole made out of 50x8 mm GI Flat, confirming to

    latest IS Specification and .

    GI Clamp for LT Stay set:

    LT stay clamp suitable for PSC poles made out of 50x6 mm GI Flat, confirming to latest IS Specification.

  • 27

    11 KV PIN INSULATOR

    1. SCOPE:

    The specification cover the manufacture, testing at works supply and delivery of

    Porcelain insulators for overhead power lines with a nominal voltage below 12KV . Both P in

    and Shackle type insulators arecovered.

    2. APPLICABLESTANDARDS:

    Except when they conflict with the specific requirements of this specification, the insulators

    shall comply with IS : IS:731 & IS: 3188 or the latest version thereof.

    3. GENERALREQUIREMENTS:

    The porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed. The

    design ofthe insulators shall be such that the stresses due to expansion and contraction in any

    part of the insulator shall not lead to its deterioration. The glaze shall be brown in color for

    insulators. The glaze shall cover the entire porcelain surface parts except those areas that serve

    as supports during firing. The insulators shall be suitable for use with all Aluminum Conductor

    or Copper conductor or ACSR upto100 sq.mm. The insulators should withstand the conductor

    tension the reversible wind load as well as the high frequency vibrations set due towind.

    4. SYSTEM CONDITIONS:

    Frequency : 50Hz

    NominalSystemVoltage : 11KV

    Maximum System VoltageLTSystem : 12KV Minimum LTVoltage: :11KV

    Power frequency one minutewithstandVoltage(wet): 35KV

    5. TYPE OFINSULATORS:

    The standard Pin insulators shall be of designation Type –B of IS : 731 or its latest revision.

    6. TESTS:

    Typetests:

    a) Visualexamination

    b) Verification ofdimensions

    c) Temperature cycletest

    d) Dry one minute power frequency withstandtest

    e) Wet one minute power frequency withstandtest

    f) Mechanical strength test

    g) Porositytest

    Acceptancetest:

    The insulators, after having withstood the routine test shall be subjected to the following

  • 28

    acceptance tests in the order given below:

    a) Verification ofDimensions.

    b) Temperature cycletest

    c) Mechanical strength test

    d) Porositytest

    Routinetests:

    ii) Visual examination

    7. TESTING FACILITIES:

    a. The Bidder must clearly indicate what testing facilities are available in the works of the

    manufacturer and whether the facilities, are adequate to carry out all the routine as well as type tests.

    These facilities should be made available to Purchaser‟s Engineers if deputed to carry out or witness

    the tests. If any tests cannot be carried out at the manufacturer‘s works, the reasons should be clearly

    stated in thetender.

    b. TheBiddershallfurnishdetailedtypetestreportsoftheoffered11KVPineinsulatorasperclauseof this specification. All the above Type Tests shall be carried out at laboratories, which are accredited, by the National Accreditation Board of Testing and Calibration Laboratories (NABL) of Government ofIndia to prove that the insulators offered meet the requirements of the specification. These Type Tests should have

    been carried out within five years prior to the date of opening of thistender.

    c. There offered L.T. shackle Insulators & pin insulators are already fully Type Tested at Laboratories

    accredited by the National Accreditation Board of Testing and Calibration Laboratories (NABL)

    withinfiveyears prior to the date of opening of the tender.There is no change in the design of Type tested

    L.T. shackle Insulators andthose offers against this tender

    8. Drawings :

    The tender shall be accompanied with the detailed drawings showing the dimensions of the

    individual insulator, giving all the design dimensions of various component parts. Generally it

    shall be as perIS.

    9. MARKING:

    a. Each insulator shall be legibly and indelibly marked to show the following:

    i) Name of Purchaser-NESCO

    ii) Name or trade mark of themanufacturer

    iii) Year ofmanufacturer

    iv) ISI certificate, mark, ifany.

    b. Marking on porcelain shall be applied beforefiring.

    10. Packing:All insulators shall be packed in crates or boxes suitable for rough

    handling. Packing shall be marked with the strength and voltage rating.

  • 29

    GUARANTEEDTECHNICALPARTICULARS 11 KV PININSULATOR

    Sl.

    No.

    Description Specific Requirement Bidders offer

    Name of Manufacturer. & Address To be specified by

    the bidder

    Location of type testing To be specified by

    the bidder

    Applicable standard IS: 731,IS 3188 or

    the latest version

    1 Normal working voltage 11 Kv (rms)

    2 High system voltage. 12 Kv (rms)

    3 Visible Discharge voltage dry PF. 9 Kv (rms)

    4 1 Minute withstand voltage wet PF. 65 Kv (rms)

    5 1 Minute withstand voltage................. 35 Kv (rms)

    6 PF puncture withstand voltage. 110 Kv (rms)

    7 Impulse withstand voltage :

    (+ ve) 80 Kv peak

    (- ve) 80 Kv peak

    8 Impulse flashover voltage :

    (+ ve) 90 Kv peak

    (- ve) 120 Kv peak

    9 Minimum failing load. 5 KN.

    10 Minimum creepage distance. 240 mm.

    11 Colour of glaze. Brown.

    12 Weight per unit. 1.4 Kg. (Apprx.)

    13 Size of insulator. (Height) 125 mm.

    (Diameter 125 mm.

    14 Material of thimble. Lead.

    15 Steel head. Small head.

    16 Standard. IS : 731/1971.

    17 Tolerance. Tolerance will be allowed as per IS :

    731/1971 or latest amendments if any.

    18 Drawing To be submitted

    19 Conforming standard As per IS

    NB- Every insulator should bear the marking of manufacturer’s name &

    Purchaser’s name and ISI mark.

    Name & Signature of Bidder with seal

  • 30

    11 KV Disc insulator 45 KN (T&CType)

    TECHNICAL SPECIFICATION FOR 11 KV

    45 KN DISCINSULATORS

    1. SCOPE:

    This specification covers the manufacture, testing and works supply and delivery of 11 KV Disc insulators. The

    Porcelain insulators shall conform to IS:731-1971ammended upto date. Insulators shall be of Tongue &

    Clevis type (T&C).Disc insulators made of glazed porcelain shall be used as insulators on dead ends or on

    suspension type lines of 11 KV and above. Tongue & Clevis type (T & C) disc insulators of mechanical strength

    not less than 45KN shall be used confirming to IS: 731/1971. These shall be mounted on metallic cross-arms

    with the help of suitable non-magnetic galvanised iron hardware fittings. Small f ittings like spring washers,

    nuts etc may beelectro-galvanised.

    2. SERVICE CONDITIONS:

    The insulators to be supplied against this specification shall be suitable for satisfactory continuous operation

    under the following tropical conditions.

    2.1.1 Maximum ambient temperature (Degree C) … 50

    2.1.2 Minimum ambient temperature (Degree C) … 3.5

    2.1.3 Relative Humidity (%) … 10 to 100

    2.1.4 Maximum Annual Rainfall (mm) … 1450

    2.1.5. Maximum Wind pressure (kg/m.sq.) … 150

    2.1.6 Maximum wind velocity (km/hour) … 45

    2.1.7 Maximum altitude above mean sea level (meter) … 1000

    2.1.8 Isoceraunic level (days/year) … 50

    2.1.9 Seismic level (Horizontal acceleration) … 0.3 g

    2.1.10 Moderately hot and humid tropical climate

    conductive to rust and fungusgrowth

    3. System Particulars:

    a) NominalSystemVoltage 11KV

    b) CorrespondinghighestsystemVoltage

    c) Frequency

    d) Number ofphase

    e) Neutralearthing f) Min. Impulse w ithstandvoltage

    12 KV

    50 Hz with 3% tolerance

    3

    effectively grounded.

    75 KV

  • 31

    4. Standards :

    Unless otherwise specified elsewhere in the specifications insulators shall confirm to the

    latest revisions of all relevant standards.

    5. GeneralRequirements

    i) The Porcelain insulators shall generally conform to IS:731-1971 and any amendments up to date to the same.

    ii) Conductors : The Disc Insulators will be used on lines on which the conductors will be A.A.A.

    Conductor of size up to 100 sq. mm. The insulators should w ithstand the conductor

    tension, the reversible wind load as well as the high frequency vibrations due towind.

    iii) Type

    a) Insulator shall be suitable for both the suspension and strain type of load & shall be of

    Tongue and Clevis type. The insulators shall conform to Type ‗B‘ ofIS:731-1971.

    b) Diameter of porcelain disc insulator shall be 255mm . The center to center distance between Tongue and Clevis shall be145mm.

    c) InsulatorEnds.

    Disc Insulators shall have Tongue and Cleave ends. The security clips will have to be

    provided asperfig.25ofI.S.2486(Part-

    2)1989(amendeduptodate)RECSpecif ication3/1971(Revised1993).

    d) The colour of the units shall be brown for 45 KN Disc Insulators.

    e) The number of units to be used both on suspension and tension strings shall be as given below:

    Voltage Class Suspension

    Single

    Strings

    Double

    Tension

    Single

    Strings.

    Double

    33 3 3x2 3 3x2

    22 2 2x2 2 2x2

    11 1 1x2 1 1x2

    iv). Electromechanical & Mechanical Strength:

    The mechanical and electromechanical strength of the individual and the complete Disc shall

    be 45 KN.

    v) CreepageDistances :The minimum creepage distance for each 11KV disc Insulator shall 320mm.

    6.0 Tests:

    Suitable number of individual units and complete string shall be subject to the following tests in

    accordance with IS:731/1971 with its latestamendments.

    i) Type Tests :

    Following Type test shall be carried out on porcelain insulators as specified in IS:

  • 32

    731 /971 amended up to date.

    1. VisualExamination.

    2. Verif ication ofdimens ions. 3. Vis ible DischargeTest.

    4. Impulsevoltagewithstandtest. 5. Impulsevoltageflashovertest.

    6. Wet one Minute Power Frequency withstand test and West Flashovertest. 7. Temperature Cyc letest.

    8. Electromechanical failing loadtest.

    9. Power frequency puncture w ithstandtest. 10. Poros itytest.

    11. Galvanizingtest. ii) AcceptanceTests :

    The test samples after having withstood the routine test shall be subject to the

    following acceptance tests in order indicated below:

    1. Verif ication ofdimens ions. 2. Temperature Cyc letest.

    3. Twenty four hour mechanicaltest. 4. Electromechanical failing loadtest.

    5. Power Frequency puncture w ithstandtest. 6. Poros itytest.

    7. Galvanizingtest.

    iii) RoutineTests :

    1. VisualExamination

    2. Mechanicaltest

    3. Electricaltest

    4. Twenty four hours mechanicaltest

    5. Electro mechanical failing loadtest

    7 Test Certificate:

    The tenderer shall furnish detailed type test reports of the offered Disc Insulators as per clause

    6.1 of the Technical Specifications at the NABL approved laboratories to prove that the Disc

    Insulators offered meet the requirements of the specification. These Type Tests should have

    been carried out within five years prior to the date of opening of thistender.

    i) Their offered Disc Insulators are already fully type tested at

    approved Laboratory CPRI/NABL within five years prior to the date of

    opening of this tender.

    ii) There is no change in the design of type tested Disc Insulators and those offers against thistender.

    iii) Such tenderers complying (i) and (ii) above shall furnish an undertaking in the

    format schedule.

    The purchaser reserves right to demand repetition of some or all the Type Test in

    presence of purchaser‘s representative at purchaser‘s cost. For this purpose, the tenderer shall

    quote unit rates for carrying out each Type Test. However, such unit rates will not be considered

    for evaluation of the offer. In case the unit fails in the Type Tests, the complete supply shall

    be rejected.

  • 33

    8. Testing Facilities: The tenderer must clearly indicate what testing facilities are available in the works of the

    manufacturer and whether facilities are adequate to carry out all Routine & acceptance Tests.

    These facilities should be available to Board's Engineers if deputed or carry out or witness the tests

    in the manufacturer works. If any test cannot becarried

    outat the manufacturer's work, the reasons should be clearly stated in the tender. The insulators

    shall be tested in accordance with the procedure detailed in IS-731/1971 amended up todate.

    9. Material Quality and Workmanship:

    The quality of porcelain and hardware in case of porcelain insulators and core & housing

    in case of polymeric insulators shall be of the highest grade and best workmanship such as

    is suitable and customary for extra high tens ion lines and shall conform to current IS or IEC

    (only in absence of the relevantI.S.S.).

    The porcelain shall be sound, free from defect, thoroughly vitr ified and smoothly glazed

    and brown incolour.

    Unless otherwise specified the glaze shall cover all exposed porcelain parts of the insulator.

    Glazing shall be uniform and freefromdefects. Small and isolated defects in the

    insulator glaze of a total surface less than 0.5 sq.cm. will however be ignored. Deviation

    on this account may be supported by relevantIS.

    10 Mechanical Design:

    The design shall be such that stresses due to expansion and contraction in any part of insulator

    shall not lead todeterioration.

    Cement used in manufacture of the insulators shall not cause fracture due to expansion or

    loosening due tocontraction.

    11. Drawings:

    The tender shall be accompanied with the detailed drawings showing the dimensions

    of the individual Disc giving all the design dimens ions of various component parts. The drawing

    for Insulators should clearly show the method of cementing the porcelain to the metal caps and

    balls. Generally it shall be as perIS.

    12. Markings:

    Eachinsulatorshallbelegiblyandindeliblymarkedtoshowthefollowing: a) Name or trade mark of themanufacturer.

    b) VoltageType

    c) Month and year ofmanufacturing.

    d) Electromechanical strength inKN

    e) Property of NESCOUtility.

    The―W‖clipshallbemarkedwith/punchedw iththeballandsockets izesforwhichitismeant e.g.16B,20etc. Marking on porcelain shall be printed and shall be applied beforefir ing.

    13 Packing:All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be

    marked with the strength and KVrating.

  • 34

    GUARANTEED TECHNICAL PARTICULARS FOR 45 KN DISC. INSULATOR ( T&C TYPE)

    Sl.

    No Particulars Specific

    Requirement

    Bidders offer

    1. Name of Manufacturer. & Address To be spec if ied by the

    bidder

    2. Location of type testing To be specified by

    the bidder

    3 Applic able standard IS-731/1971with

    latestamendment

    4 Type of insulator T&C type Disc insulator

    5 Nominal System Voltage 11 KV

    6 Highest System voltage 12 KV

    7 Visible discharge Test voltage (Minimum) 9 KV

    8 Dry Impulse withstand voltage +(1.2/50 microsecond wave) 75 KV

    9 Dry Impulse flashover voltage+(1.2/50 microsecond wave) 90 KV

    10. Dry 1 min. power frequency withstand Voltage kV. 60 KV

    11 Wet 1 min. power frequency withstand Voltage . 35 KV

    12 1 min. power frequency flashover Voltage kV. (Dry) 65 KV

    13. 1 min. power frequency flashover Voltage kV.(Wet) 45KV

    14 Power frequency puncture voltage 105 KV

    15 Mechanical Routine test load 18 KN

    16 Mechanical impact strength 45 KN

  • 35

    17 Shattered strengths (Glass) .. KV

    18 Electromechanical Failing Load 45 KN

    19 Safe working load 18 KN

    20 Minimum Failing Load 45 KN

    21 Creepage Distance 320 mm

    22 Type and Grade of Materials :

    i) Insulators Porcelain

    ii) Cap Malleable Casting or S.G

    iii) Pin Forged pin

    iv) Locking Split pin

    v) Cement Portland

    23 Type of semi conducting Glaze Ceramic

    24 Colour of Insulators Dark Brown

    25 Weight of single disc. kg. 4 Kg(Approx.)

    26 Number of Insulators per crate 4 nos./ 6 nos.

    27 Cross weight of Loaded crate 20 – 30 Kg

    28 Whether drawing showing dimensional details have

    been furnished along with bid.

    To be enclosed by

    bidder

    NB : Every insulator should bear the marking of Purchaser’s name/ Manufacturer’s name

    and ISI mark.

    Bidders Signature with Seal

  • 36

    11KV H.W fittings(T&CType) :

    11 KV Hard Ware fittings Tongue & Clevis type ,confirming to REC Construction Standard C-2 and as per

    drawing.

    GUARANTEED TECHNICAL PARTICULARS FOR 11 KV H/W FITTINGS ( T&C )

    Sl.No. Description Specified Bidders Offer

    1. Manufacturer Name & Address

    To be specified by Bidder

    2. Standard Specification to which Hard ware Fittings

    shallconfirm.

    IS: 2486 (Part-I,II &II)

    3 Ultimate strength 3000 Kg (min)

    4. Dimensions in accordance with

    IS: 2486(Part-II)

    5 Type of washer thickness

    a) Spring 2.5 mm

    b)Flat 2.5 mm

    6. Type of Clamp size Tension Clamp suitable for

    Squiral/Weasel/ Rabbit

    7. Galvanised conform to IS 2633 , IS: 4759-1996 & IS: 6747

    8. Weight of Fittings ..

    9. Tolerance in dimension if any

    + 5%

    10. Manufacturer trade mark to be embossed on the sets

    Specified by the Bidder

    11. Specific drawing to be

    enclosed.

    Enclosed

    NB. All ferrous fittings and the parts other than those of stainless steel , shall be

    galvanized.

    Bidder’s Signature with Seal

  • 37

    11 KV GI Pin ) :

    11 KV hot-dipped galvanizing Pin suitable for 11 KV pin insulator , confirming to REC Construction

    Standard. C- 1 and confirming to IS: 2486/Part-I/1971 & Part-II/1989, IS: 1363/1984, IS: 3063/1972,

    IS:2633/1972.

    GUARANTEED TECHNICAL PARTICULARS FOR 11KV G.I PIN

    Sl.No. Description Spec if ied Bidders Offer

    1 Manufacturer Name & Address To be specified by

    Bidder

    2 Type of Pin 11KV

    3 Applic able International Standard IS:2486 (part-II)

    4 Grade Steel HDG Steel

    5 Steel Spec if ication HDG Steel

    6 Specification of Bolt & Nut As per ISS

    7 Spec if ication of Bolt Threads As per ISS

    8 Mechanical falling load (MFL) 10 KN

    9 Elongation at MFL As per ISS

    10 Maximum deflection of Pin Top at

    MFL

    1.5 mm

    11 Galvanis ing Specif ication IS- 2633

    12 MinimumweightofSteeldepos ited

    on steelsurface

    610 g/m²

    13 Pin Length 315 mm

    14 Shank Length 150 mm

    15 StalkLength 165 mm

    16 Type of Thread As per ISS

    17 Thread Length As per ISS

    18 Draw ing enclosed

    Bidder’s Signature with Seal

  • 38

    11 KV 200 Amp 3 Pole AB Switch

    Technical Specification

    01.0 Scope: -

    This specification covers manufacturing testing and supply of 11KV 200 Amps 50HZ Air Break

    switches for out door installation in horizontal configuration. The switches are suitable for

    operation under off load conditions only and are intended for use on Distribution Sub – stations

    and tapping sectionalizing points of 11 KVlines.

    Description of the materials:- The 11KV A.B. Switch sets shall confirm to the following parameters: -

    a. Numberofpoles 3 b. Number of Post insulatorper pole 2nos12KVpostinsulator. c. Nominalsystemvoltage 11KV

    d. Highestsystemvoltage 12KV

    e. Ratedfrequency 50Hz f. Systemearthling effectivelyearthed.

    g. Ratednominal current 200amps h. Altitudeofinstallation Not exceeding1000M

    The post insulators used in the A.B. Switches shall have the following ratings :-

    a. Power frequency withstandvoltage(dry) 35KV(RMS) b. Power frequencywithstandvoltage(wet) 35KV(RMS) c. Implieswithstandvoltage(dry) 75KV

    d. Power frequencypuncturewithstand 1.3

    Standards:-The AB Switch Set shall conform to the following standards: -

    a. IS-9920 (Part-I toV) b. IS-2544/1973 (for porcelain postinsulators) c. IS-2633, (for galvanization of ferrous parts.) or its latestamendments if any.

    04.0 Insulator make: -

    12KV post insulators complete with post and cap duly cemented to be used in the AB Switch

    Set conforming to IS-2544/1973.

    The bidder shall furnish the type test certificate of the post insulators from their manufacturer for

    reference andscrutiny.

    The bidder shall mention make, type of insulation materials, metal fittings, Creepage

    distance, protected Creepage distance, tensile Strength, compressing strength, torsion strength and

    cantileverstrength.

  • 39

    Climatic condition:-

    The A.B. Switch set shall be suitable for operation under the following climatic conditions

    a. Maximumambientairtemperature 45 oC

    b. Maximumdailyaverageairtemperature 35 oC

    c. Maximumyearlyaverageambientairtemperature 30 oC

    d. Maximum temperature attainably by abody

    e. Exposed totheSum. 50 oC

    f. Minimum ambientairtemperature 0 oC

    g. Maximumrelativehumidity 100% h. Minimum number of rainy daysperannum 70

    i. Average number of rainy daysperannum 120 j. Average annualrain fall 150cm.

    k. Number of months of tropicalmonsoonconditions 4 l. Maximumwindpressure 260Kg./mm2 m. Degree of exposure toatmosphericpollution normally

    n. Atmosphere. Polluted.

    Other technical details: -

    06.01 n General: - The 11KV A.B. Switch Set shall be the gang operated rotating single air break type having 2

    post insulators per phase. The operating mechanism shall besuitable for manual operation from the

    ground level and shall be so designed that all the three phases shall open or close simultaneous ly.

    The Switches shall be robust in construction, easy in operation and shall be protected against over travel or

    staining that might adversely affect any of its parts. The required base M.S. Channel (hot dip galvanized)

    phase coupling rod, operation rod with intermediate guide braided with f lexible electrolytic copper, tail

    piece of required current carrying capacity and operation mechanism with ‗ON‘ & ‗OFF‘ positions shall

    be provided. The operation rod shall be medium gage of 32mm diameter nominal bore G.I. pipe single

    length 6 meters. The phase coupling rod for gang operation shall be of medium gauge 25mm dia&2100

    mm length nominal bore G.I. pipe. The Rating post insulators shall be provide with suitable bearing

    mounted on a base channel with 8mm dia thrust collar and 6mm split pin made out of stainless steel. The

    operating down rod shall be coupled to the spindle (minimum dia – 32mm) for gang operation through

    another suitable bearing by two numbers 10mm dia stainless steel bolts with double nuts. All the

    bearings shall be provided with grease nipple. All metal (ferrous) parts shall be galvanized an polished.

    The pipe shall be galvanized in accordance with IS-4736/1968.The post insulators should be fixed with the

    base channel using Galvanized Nuts andBolts.

    Mounting:- The A.B. Switches shall be suitable for horizontal mounting in double pole sub-station structures. MS Galvanized base Channel &base support channel should be of min. size 75x40x6mm.

    Switching Blades: - It shall be made out of electricity copper with silverplated. The approximate size shall be 220mm X 35X 6mm. The Switch shall have such a spring mechanism so as to

    ensure that the speed of the opening of contact is independent of speed of manual operation.

    Fixed Contacts: - The Fixed Jaw type female contacts o f s ize (70x35x6) mm shall be made of electrolytic copper (minimum 95%copper composition) duly silver coated controlled by phosphorous

    bronze high pressure spring housed in robust G.I. Cover. It is essential that provision shall be made in

    fixed female contracts to take the shock arising from the clos ing of move contract blade without the

    same being transmitted to the post insulator. The arrangement made in this regard shall be specifically

    shown in thedrawing.

    Arcing Horn: - As the switches are generally meant for isolating transmission line and distribution

  • 40

    transformers, suitable arcing horns shall be provided for breaking the charging current horn shall be

    made of 8 mm dia G.I. Rod with spring assistedoperation.

    Terminal Connectors: - Terminal connectors shall be robust in design. The size of fixed connector shall be

    (65 X 35 X 6 mm) and size of movable connector shall be of (65 X 35) X (65 X 35) X 6mm of copper

    casting with uniform machine finishing duly silver plated made out of minimum 95% copper composition

    with 2nos.12mmdiaholesprovidedwithsuitablebrassboltsanddoublenuts,flatwashers&2nos.bimetallic solder less

    sockets suitable up to 55 mm2 conductor.

    Spacing:-Theminimumclearancebetweenphasestotheswitchshallbe

    760mm. The operation down rod shall be at a transverse distance of 300mm from the outer limb of

    the switch. The centre spacing between two post insulators of the same phase shall be 380 mm. In

    the open position ofthe

    A.B. switches the moving blade shall rotate through 90 o. This shall be exhibited in the drawing.

    Sample, Drawing & Literatures: - A copy of drawings of 11KV 200Amps. A.B. Switch shall be furnished along with the tender.

    The details of construction and materials of different parts of the A.B. Switch shall clearly be

    indicate in the tender and illustrative pamphlet / literature for the same shall be submitted along with

    thetender.

    07.0 TEST & TEST CERTIFICATE:-

    Type Test: - Certificate for the following type tests conducted on a prototype set of A.B. Switch in a NABL approved test house/CPRI shall have to be submitted along withoffer.

    Dielectric Test (impulse and one minute were power frequency withstand voltage test.)

    • Temperature rise test (for contracts andterminals)

    • ShortsTimecurrentandpeakwithstandcurrenttest.

    • Mainly active load breaking capacitytest.

    • Transformer off-load breaking capacitytest.

    • Line charging breaking capacitytest.

    • Cable charging breakingtest.

    • Operation and mechanical endurancetest.

    • Mechanical strength test for post insulator, asper IS-2444/1937 shall be furnished.

    • Testforgalvanizationofmetal(ferrous)parts.

    Routine /Acceptance Test:- The inspection may be carried out by the Purchaser at any stage of manufacture. The successful

    bidder shall grant free access to the Purchaser‘s representative at a reasonable time when the work is

    in progress. The following routine tests shall have to be conducted on each set and results are to be

    furnished for consideration of deputing inspecting officer for inspection and conduction testing of

    the materials at the works of the manufacturer. the supplier shall give f ifteen days advance

    intimation to the Purchaser to enable him to depute his representative for witnessing thetests.

    1. Power frequency voltage drytest. 2. Measurement of resistance of maincircuit. 3. Tests to prove satisfactoryoperation. 4. DimensionCheck

    5. Galvanizationtest. 6. Operationaltest. 08.00 Guaranteed Technical Particulars: -

    The bidder shall furnish the guaranteed technical particular duly filled in the format along with the tender.

  • 41

    09.0 Completeness of Equipment:-

    All f ittings, accessories of apparatus which may not have been specifically mentioned in this

    specification but which are usual or necessary in equipment of similar plat shall be deemed to be included

    in the specification and shall be supplied by the Tender without extra charge. All plant and equipment

    shall be completed in all details whether such details are mentioned in the specification ornot.

    200 Am