Implementation Trip Circuit Supervision /
Trip Coil Supervision in SEL Relays
Using SELogic Equations
![Page 2: TCS Rev1 20111126](https://reader036.vdocuments.us/reader036/viewer/2022073020/577c7f271a28abe054a36e98/html5/thumbnails/2.jpg)
Doc.ref# TCS rev1 date code 20111126 Page | 2
ANSI ( 74 :Trip Circuit Supervision/Trip Coil Supervision) :
Scheme description :
TCS Scheme is designed to provide supervision of the trip coil with the breaker open or closed. Since
two opto inputs are used, this scheme is compatible with latched trip contacts. When the breaker is closed and there is no
trip signal, supervision current passes through the opto input no.1 and the trip coil. When breaker is open the current flows
through opto no.2 and trip coil .So, the supervision current is maintained through the trip path with the breaker in either
state, thus giving full supervision.
Power Supply
+
-
IN101
IN102
A10
A11
A12
A01
A02
Trip Circuit Supervision / Trip Coil Supervision
SEL-710LI+
LI-
DC Elementary
Supply.
O C
BUS SIDE
Motor
P1
P2
R
Y
B
N
Test Block
IR
IY
IB
CT
Inputs
Z01
Z02
Z03
Z04
Z05
Z06
LI+
LI-
OUT103
A05
A06
OUT104
A07
A08
OUT 302
C03
C04
52a
52b
Circuit Breaker
DC Supply.
Binary Inputs & Outputs
![Page 3: TCS Rev1 20111126](https://reader036.vdocuments.us/reader036/viewer/2022073020/577c7f271a28abe054a36e98/html5/thumbnails/3.jpg)
Doc.ref# TCS rev1 date code 20111126 Page | 3
Trip Circuit Supervision/Trip Coil Supervision configuration logic using SELogic equations and Graphical logic:
Using SELogic equations, The Trip circuit supervision/Trip Coil Supervision configuration will be as the following:
SV01 := NOT (IN101 OR IN102 )……SELogic variable number 01 will assert if both IN101 and IN102 not available .
SV01PU:=0.5 ( Seconds) … The SELogic variable number 01 timer ( SV01 will pick up after 500ms ).
SV01DO:= 0.5 (Seconds )…. The SELogic variable number 01 timer ( SV01 will Drop off after 500ms ).
T06_LED := SV01T … LED number 6 assigned to the output of the SELogic variable 01 .
Using SEL Graphical logic , We can represent the above SELogic equations which representing the TCS as the following :