tceq - 40 cfr part 63, subpart uuuuu flowchart · last modified: march 22, 2019 from 40 cfr part...
TRANSCRIPT
§63.9981
Do you own
or operate a coal-fired EGU
or an oil-fired EGU defined
in §63.10042?
No
§63.9983(a)
Is the unit
designated a stationary
combustion turbine, other than
an IGCC unit, covered by 40
CFR part 63, subpartYYYY?
Yes
§63.9983(b)
Is the
unit not coal- or
oil-fired and combusts natural
gas for more than 10% of the averageannual heat input during any 3 calendar
years or for more than 15% of the
annual heat input during
any calendar
year?
Yes
40 CFR 63, Subpart
UUUUU does not apply.
101
No
No
Start
End
Below is a flowchart describing 40 CFR Part 63, Subpart UUUUU. It will likely not be accessible using a screen reader. For the text of the statute/rule, please go to
40 CFR Part 63, Subpart UUUUU(1 of 603)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018. LayeredThese flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(2 of 603)
§63.9983(c)
Can the
unit combust more
than 25 MW of coal or oil but
does not fire coal or oil for more than
10% of the average annual heat input during
any 3 calendar years or for more than
15% of the annual heat input
during any calendar
year?
No
Yes
101
§63.9983(d)
Does the
unit combust solid
waste?Yes
Any electric steam generating unit combusting solid waste is a solid waste
incineration unit subject to standards established under sections 129 and
111 of the Clean Air Act.
40 CFR 63, Subpart
UUUUU does not apply.
102
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(3 of 603)
102
§63.9990(b)(3)§63.63.10000(c)(2)(iv)
Does
your unit qualifyas a limited-use liquid oil-fired
as defined in
§63.10042?
No
Yes
The unit is not subject to the emission limits in Tables 1 and 2, but must comply
with the performance tune-up work practice requirements in Table 3.
Comply with the following:
Standard
§63.10000(c)(2)(iv)
§63.10005(e), (j)[G]§63.10011(g)
[G]§63.10021(h)
Monitoring/Testing
§63.10021(a)
Recordkeeping
§63.10032(j)
Reporting
§63.10005(k)
§63.10021(g), (i)
103
900
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(4 of 603)
103
§63.9982(b)
Is the EGU
new (i.e. constructioncommenced after May 3, 2011 and
meeting the applicability criteriaat the time construction
commenced)?
No
Yes
§63.9982(c)
Is the EGU recon-
structed (i.e. reconstruction
criteria as defined in §63.2 is met,
construction commenced after May 3, 2011
and meeting the applicability criteria
at the time construction
commenced)?
No
Yes 104
The EGU is existing.
209
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(5 of 603)
104
§63.9990(a)(1)
Is the EGU
designed for coalwith a heating value greater
than or equal to 8,300 Btu/lb(i.e. not low rank
virgin coal)?
No
Yes 106
§63.9990(a)(2)
Is the EGU
designed for low rank
virgin coal?
No
Yes 123
§63.9990(c)
Is the unit
an IGCC combust-
ing either gasified coal or
gasified solid oil-
derived fuel?
No
Yes 140
105
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(6 of 603)
105
§63.9990(b)(1)
192
Is the unit acontinental liquid oil-
fired EGU?Yes 158
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(7 of 603)
106
§63.9991(a)(1)-Table 1.1.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.a|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Particulate matter
107
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
401
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(8 of 603)
107
§63.9991(a)(1)-Table 1.1.a
Are you
using total non-Hg
HAP metals as thestandard?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.a|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d)
§63.10021(d)-Table 7.4, (d)(1)-(2)
Total non-
mercury HAP metals
108
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
407
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(9 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
120
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
108
Have allpollutant paths been
completed? Yes
No
Continue through next path.
109
110
112
114
116
118
111
113
115
117
119
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(10 of 603)
110
Comply with the following:
Standard§63.9991(a)(1)-Table 1.1.a|3
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(11 of 603)
111
Comply with the following:
Standard§63.9991(a)(1)-Table 1.1.a|4
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(12 of 603)
112
Comply with the following:
Standard§63.9991(a)(1)-Table 1.1.a|5
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(13 of 603)
113
Comply with the following:Standard
§63.9991(a)(1)-Table 1.1.a|6
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(14 of 603)
114
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.a|7
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(15 of 603)
115
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.a|8
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(16 of 603)
116
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.a|9
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(17 of 603)
117
Comply with the following:
Standard§63.9991(a)(1)-Table 1.1.a|10
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(18 of 603)
118
Comply with the following:Standard
§63.9991(a)(1)-Table 1.1.a|11
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(19 of 603)
119
Comply with the following:
Standard§63.9991(a)(1)-Table 1.1.a|12
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
413
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(20 of 603)
120
§63.9991(a)(1)-Table 1.1.b
Are you
using HCl as a
surrogate for acidgas HAP?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.b|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Hydrogen chloride
121
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
419
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(21 of 603)
121
Comply with the following:Standard
§63.9991(a)(1)-Table 1.1.b|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur dioxide
Sulfur dioxide is used as an alternate surrogate
for acid gas HAP.
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
425
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(22 of 603)
122
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.1.c
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (c)(1)(i)(B), (e), (l)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
[G]§63.10006(f)(1), (f)(2)[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Mercury
Comply with the following:Recordkeeping
§63.10000(l)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
431
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(23 of 603)
123
§63.9991(a)(1)-Table 1.2.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.2.a|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Particulate matter
124
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
437
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(24 of 603)
124
§63.9991(a)(1)-Table 1.2.a
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.2.a|2§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Total non-
mercury HAP metals
125
Are you
using total non-Hg
HAP metals as thestandard?
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
443
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(25 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
137
125
126
Have allpollutant paths been
completed?
No
Continue through next path.
Yes
135
133
131
129
127
128
130
132
134
136
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(26 of 603)
127
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|3
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(27 of 603)
128
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.2.a|4
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d§63.9991(a)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(28 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.2.a|5
)
e)
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4Comply with the following:
§63.10000(a)-(b), (e), (l)-(m), (m)(1)Recordkeeping
§63.10005(a), (d)-(e), [G](g), (j)§63.10000(l), (m)(2)
[G]§63.10006(i)[G]§63.10005(b)
§63.10007(e)§63.10020(a)-(b), (d)
§63.10011(f)(1)-(2), [G](g)[G]§63.10032(a), (c), [G](d), [G](f
[G]§63.10021(e)§63.10032(g)-(i)
§63.10021(e)-Table 7.5-7§63.10033(a)-(c)
[G]§63.10021(h)Reporting
§63.10040§63.10000(l), (m)(2)
Monitoring/Testing§63.10005(k)
§63.10000(c)(1), (l)-(m), (m)(1)§63.10021(f)-(g), (i)
§63.10005(a), (a)(1), [G](a)(2)(iii)§63.10030(a), (d), [G](e), (f)
[G]§63.10005(b), [G](d)(2)§63.10031(a)
§63.10006(b)(1), [G](f)(1), (f)(2)§63.10031(a)-Table 8.1.a-c
[G]§63.10006(f)(3), (g)-(h)[G]§63.10031(b)-(c), (e)-(f)
§63.10007(a), (a)(1)-(2), (b)§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
§63.10020(
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
449 Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
129
Yes
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(29 of 603)
130
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|6
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4Comply with the following:
§63.10000(a)-(b), (e), (l)-(m), (m)(1)Recordkeeping
§63.10005(a), (d)-(e), [G](g), (j)§63.10000(l), (m)(2)
[G]§63.10006(i)[G]§63.10005(b)
§63.10007(e)§63.10020(a)-(b), (d)
§63.10011(f)(1)-(2), [G](g)[G]§63.10032(a), (c), [G](d), [G](f)
[G]§63.10021(e)§63.10032(g)-(i)
§63.10021(e)-Table 7.5-7§63.10033(a)-(c)
[G]§63.10021(h)Reporting
§63.10040§63.10000(l), (m)(2)
Monitoring/Testing§63.10005(k)
§63.10000(c)(1), (l)-(m), (m)(1)§63.10021(f)-(g), (i)
§63.10005(a), (a)(1), [G](a)(2)(iii)§63.10030(a), (d), [G](e), (f)
[G]§63.10005(b), [G](d)(2)§63.10031(a)
§63.10006(b)(1), [G](f)(1), (f)(2)§63.10031(a)-Table 8.1.a-c
[G]§63.10006(f)(3), (g)-(h)[G]§63.10031(b)-(c), (e)-(f)
§63.10007(a), (a)(1)-(2), (b)§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(30 of 603)
131
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|7
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(31 of 603)
132
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|8
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(32 of 603)
133
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|9
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(33 of 603)
134
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|10
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(34 of 603)
135
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|11
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(35 of 603)
136
Comply with the following:
Standard§63.9991(a)(1)-Table 1.2.a|12
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
449
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(36 of 603)
137
§63.9991(a)(1)-Table 1.2.b
Are you
using HCl as a
surrogate for acidgas HAP?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.2.b|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Hydrogen chloride
138
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
455
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(37 of 603)
138
Comply with the following:Standard
§63.9991(a)(1)-Table 1.2.b|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur dioxide
Sulfur dioxide is used as an alternate surrogate
for acid gas HAP.
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
461
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(38 of 603)
139
Comply with the following:Standard
§63.9991(a)(1)-Table 1.2.c
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (c)(1)(i)(B), (e)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
[G]§63.10006(f)(1), [G](f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a)
Mercury
Comply with the following:
Recordkeeping[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
467
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(39 of 603)
140
§63.9991(a)(1)-Table 1.3.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
No
Particulate matter
142
§63.9991(a)(1)-Table 1.3.a
Is theduct burner on
syngas?No
Yes
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
141
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
473
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(40 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Duct burner uses natural gas.
141
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
473
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(41 of 603)
142
§63.9991(a)(1)-Table 1.3.a
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|3
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Total non-
mercury HAP metals
143
Are you
using total non-Hg
HAP metals as thestandard?
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
479
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(42 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
155
Have allpollutant paths been
completed? Yes144
No
Continue through next path.
143
145
147
149
151
153
146
148
150
152
154
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(43 of 603)
145
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|4
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
485
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(44 of 603)
146
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|5
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(45 of 603)
147
Comply with the following:Standard
§63.9991(a)(1)-Table 1.3.a|6§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(46 of 603)
148
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|7
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(47 of 603)
149
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|8
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(48 of 603)
150
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|9
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(49 of 603)
151
Comply with the following:Standard
§63.9991(a)(1)-Table 1.3.a|10§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(50 of 603)
152
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|11
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(51 of 603)
153
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|12
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(52 of 603)
154
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.a|13
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
485
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(53 of 603)
155
§63.9991(a)(1)-Table 1.3.b
Are you
using HCl as a
surrogate for acidgas HAP?
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 1.3.b|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen chloride
156
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
491
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(54 of 603)
156
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.3.b|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur dioxide
Sulfur dioxide is used as an alternate surrogate for
acid gas HAP.
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
497
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(55 of 603)
157
Comply with the following:
Standard§63.9991(a)(1)-Table 1.3.c
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (c)(1)(i)(B), (e)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
[G]§63.10006(f)(1), [G](f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a)
Mercury
Comply with the following:
Recordkeeping
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
503
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(56 of 603)
158
§63.9991(a)(1)-Table 1.4.a
Are
you using filter-
able PM as a surrogate
for total HAP
metals?
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.4.a|1§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii)
[G]§63.10005(b), (c), (d)(1)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate matter
159
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
509
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(57 of 603)
159
§63.9991(a)(1)-Table 1.4.a
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 1.4.a|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total HAP metals
160
Are you using
total HAP metals as the
standard?
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
515
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(58 of 603)
Individual HAP metals are used asalternative equivalent standards (Sb, As,Be, Cd, Cr, Co, Pb, Mn, Ni, Se and Hg).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
173
Mercury
160
Have allpollutant paths been
completed? 161 Yes
No
Continue through next path.
162
164
166
168
170
172
163
165
167
169
171
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(59 of 603)
162
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|3
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
521
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(60 of 603)
163
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|4
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(61 of 603)
164
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|5
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(62 of 603)
165
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|6
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(63 of 603)
166
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|7
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(64 of 603)
167
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|8
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(65 of 603)
168
Comply with the following:Standard
§63.9991(a)(1)-Table 1.4.a|9§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(66 of 603)
169
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.a|10
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(67 of 603)
170
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.4.a|11
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(68 of 603)
171
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.4.a|12
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
521
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(69 of 603)
172
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.4.a|13
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10005(a), (a)(1)-(2), (a)(2(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c)
§63.10006(c), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Comply with the following:
Recordkeeping[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
527
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(70 of 603)
173
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.4.b
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b), (c)
§63.10005(d)(1), [G](d)(4), [G](i)
§63.10006(b)(1), (e), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(3), (d)(3)-Table 7.3
Hydrogen
chloride
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
533
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(71 of 603)
174
Comply with the following:
Standard§63.9991(a)(1)-Table 1.4.c
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)§63.10005(a), (a)(1)-(2), (a)(2(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b), (c)
§63.10005(d)(1), [G](d)(4), [G](i)
§63.10006(b)(1), (e), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(3), (d)(3)-Table 7.3
Hydrogen
fluoride
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
539
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(72 of 603)
192
§63.9991(a)(1)-Table 1.6.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 1.6.a|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate matter
193
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
581
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(73 of 603)
193
§63.9991(a)(1)-Table 1.6.a
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Total
non-mercury HAP metals
194
Are you
using total non-Hg
HAP metals as thestandard?
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
587
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(74 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
206
194
Have allpollutant paths been
completed? Yes195
No
Continue through next path.
196
198
200
202
204
197
199
201
203
205
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(75 of 603)
196
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|3
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
593
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(76 of 603)
197
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|4
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), (f)-(i)
§63.10033(a)-(c)
Reporting
§63.10001(b)
§63.10005(k)
[G]§63.10006(j)
§63.10021(f)-(g), (i)
§63.10030(a), (d)-(e), (e)(1)-(3)
§63.10030(e)(5)-(6), [G](e)(7)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(77 of 603)
198
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|5
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(78 of 603)
199
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|6
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(79 of 603)
200
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|7
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(80 of 603)
201
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|8
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(81 of 603)
202
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|9
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(82 of 603)
203
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|10
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(83 of 603)
204
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|11
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(84 of 603)
205
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.a|12
§63.9991(a)(1), (a)(1)-Table 3.2§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)
[G]§63.10005(a)(2)(iii)[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
593
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(85 of 603)
206
§63.9991(a)(1)-Table 1.6.b
Are you
using HCl as a
surrogate for acidgas HAP?
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 1.6.b|1
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen chloride
207
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
599
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(86 of 603)
207
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.b|2
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur dioxide
Sulfur dioxide is used as an alternate surrogate for
acid gas HAP.
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
605
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(87 of 603)
208
Comply with the following:
Standard
§63.9991(a)(1)-Table 1.6.c
§63.9991(a)(1), (a)(1)-Table 3.2
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (c)(1)(i)(B), (e)§63.10005(a), (d)-(e), [G](g), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
[G]§63.10006(f)(1), [G](f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Mercury
Comply with the following:
Recordkeeping
[G]§63.10005(b)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
611
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(88 of 603)
209
211
243
275
§63.9990(a)(1)
210
Is the EGU
designed for coal
with a heating value greater
than or equal to 8,300 Btu/lb
(i.e. not low rank
virgin coal)?
No
Yes
§63.9990(a)(2)
Is the EGU
designed for low rank
virgin coal)?
No
Yes
§63.9990(c)
Is the unit
an IGCC combust-
ing either gasified coal or
gasified solid oil-
derived fuel?
No
Yes
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(89 of 603)
210
§63.9990(b)(1)
369
Is the unit a
continental liquid oil-fired EGU?
Yes 305
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(90 of 603)
211
§63.9991(a)(1)-Table 2.1.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.a|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate
matter
213
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes Table 2.1.a
212
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
617
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(91 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.a|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
212
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
617
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(92 of 603)
213
§63.9991(a)(1)-Table 2.1.a
Are you
using total non-Hg
HAP metals as thestandard?
No
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total non-
mercury HAP metals
215
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes Table 2.1.a
214
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
623
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(93 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
623
214
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(94 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
237
Have allpollutant paths been
completed? Yes
No
Continue through next path.
216
215
217
221
225
229
233
219
223
227
231
235
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(95 of 603)
217
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.a|5
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
218
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
629
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(96 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|6
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
218
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(97 of 603)
219
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|7
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
220
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(98 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|8
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
220
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(99 of 603)
221
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|9
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
222
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(100 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|10
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
222
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(101 of 603)
223
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|11
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
224
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(102 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|12
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
224
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(103 of 603)
225
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|13
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
226
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(104 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.a|14
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
226
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(105 of 603)
227
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|15
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
228
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(106 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|16
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
228
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(107 of 603)
229
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|17
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
230
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(108 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|18
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
230
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(109 of 603)
231
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|19
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
232
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(110 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|20
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
232
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(111 of 603)
233
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|21
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
234
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(112 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.a|22
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
234
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(113 of 603)
235
Comply with the following:Standard
§63.9991(a)(1)-Table 2.1.a|23
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.1.a
236
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(114 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.a|24
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
236
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
629
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(115 of 603)
237
§63.9991(a)(1)-Table 2.1.b
Are you
using HCl as a
surrogate for acidgas HAP?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.b|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen chloride
239
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Yes Table 2.1.b
238
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
635
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(116 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.b|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
238
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
635
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(117 of 603)
239
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.b|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur
dioxide
Sulfur dioxide is used as an alternate surrogate for
acid gas HAP.
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.1.bYes
240
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
641
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(118 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.b|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
240
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
641
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(119 of 603)
241
Comply with the following:
Standard
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Mercury
Is heatinput-based limit
used?No
§63.9991(a)(1)-Table 2.1.cYes
242
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
647A
Is LEE
testing done for30 days?
§63.9991(a)(1)-Table 2.1.c
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.c|1
Comply with the following:
Standard§63.9991(a)(1)-Table 2.1.c|3
Yes NoLEE testing must be
done for 90 days.
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(120 of 603)
647A
§63.10020(e)
647B
No
2)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(
Monitoring/Testing[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(1)
Yes
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(121 of 603)
Comply with the following:Standard
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
242
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
648A
Is LEEtesting done for
30 days?
§63.9991(a)(1)-Table 2.1.c
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.c|2
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.1.c|4
Yes NoLEE testing must be
done for 90 days.
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(122 of 603)
648B
648A
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping[G]§63.10020(e)
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Yes
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(123 of 603)
243
§63.9991(a)(1)-Table 2.2.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|1§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate matter
245
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Yes Table 2.2.a
244
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
654
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(124 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
244
§63.10020(e)
654
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(125 of 603)
245
§63.9991(a)(1)-Table 2.2.a
Are you
using total non-Hg
HAP metals as thestandard?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|3
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total non-
mercury HAP metals
247
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.2.a
Yes
246
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
660
Yes
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(126 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
660
246
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(127 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
269
Have allpollutant paths been
completed? Yes
No
Continue through next path.
248
247
249
253
257
261
265
251
255
259
263
267
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(128 of 603)
249
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|5
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Yes Table 2.2.a
250
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
666
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(129 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|6
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
250
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(130 of 603)
251
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|7
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Yes Table 2.2.a
252
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(131 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|8
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
252
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(132 of 603)
253
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|9
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
254
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(133 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|10
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
254
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(134 of 603)
255
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|11
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
256
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definitionof “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(135 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|12
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
256
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(136 of 603)
257
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|13
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
258
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(137 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|14
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
258
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(138 of 603)
259
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|15
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
260
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(139 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|16
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
260
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(140 of 603)
261
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|17
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
262
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(141 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|18
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
262
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(142 of 603)
263
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|19
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
264
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(143 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|20
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
264
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(144 of 603)
265
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|21
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
266
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(145 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.a|22
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
266
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(146 of 603)
267
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.a|23
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.2.a
268
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(147 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.a|24
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
268
§63.10020(e)
666
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(148 of 603)
269
§63.9991(a)(1)-Table 2.2.b
Are you
using HCl as a
surrogate for acidgas HAP?
No
Comply with the following:
Standard§63.9991(a)(1)-Table 2.2.b|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen chloride
271
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes
Table 2.2.b
270
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
672
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(149 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.b|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
270
§63.10020(e)
672
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(150 of 603)
271
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.b|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur dioxide
Sulfur dioxide is used as an alternate surrogate for
acid gas HAP.
Is heatinput-based limit
used?No
§63.9991(a)(1)-Table 2.2.bYes
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
272
678
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(151 of 603)
Comply with the following:Standard
§63.9991(a)(1)-Table 2.2.b|4§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
272
§63.10020(e)
678
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(152 of 603)
273
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.c|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Is heatinput-based limit
used?No
§63.9991(a)(1)-Table 2.2.c
Yes
Mercury 274
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
684
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(153 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.2.c|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Comply with the following:
Recordkeeping[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
685
274
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(154 of 603)
275
§63.9991(a)(1)-Table 2.3.a
Are
you using filter-
able PM as a surrogate
for non-Hg HAP
metals?
No
Particulate matter
277
§63.9991(a)(1)-Table 2.3.a
Is heat
input-based limit
used?
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 2.3.a|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
276
691
Yes
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(155 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.3.a|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
276
Yes
No
[G]§63.10020(e)
)
e)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
§63.10020(
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing691
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(156 of 603)
277
§63.9991(a)(1)-Table 2.3.a
Are you
using total non-Hg
HAP metals as thestandard?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|3
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total non-
mercury HAP metals
279
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.3.aYes
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
278
697
Yes
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(157 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|4
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
278
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
697
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(158 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
301
Have allpollutant paths been
completed? Yes
No
Continue through next path.
280
279
281
285
289
293
297
283
287
291
295
299
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(159 of 603)
281
Comply with the following:Standard
§63.9991(a)(1)-Table 2.3.a|5
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7, [G](h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
282
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
703
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(160 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|6
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
282
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(161 of 603)
283
Comply with the following:Standard
§63.9991(a)(1)-Table 2.3.a|7
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7, [G](h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
284
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(162 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|8
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
284
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(163 of 603)
285
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|9
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
286
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(164 of 603)
Comply with the following:Standard
§63.9991(a)(1)-Table 2.3.a|10§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
286
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(165 of 603)
287
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|11
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
288
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(166 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|12
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
288
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(167 of 603)
289
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|13
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-YesTable 2.3.a
290
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(168 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|14
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
290
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(169 of 603)
291
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|15
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
292
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(170 of 603)
Comply with the following:Standard
§63.9991(a)(1)-Table 2.3.a|16§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
292
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(171 of 603)
293
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|17
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
294
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(172 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|18
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
294
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(173 of 603)
295
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|19
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
296
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(174 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|20
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
296
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(175 of 603)
297
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|21
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
298
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(176 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|22
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
298
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(177 of 603)
299
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|23
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.3.a
300
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G§63.10031](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(178 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.a|24
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
300
§63.10020(e)
703
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(179 of 603)
301
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.3.b|1§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen
chloride
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes Table 2.3.b
302
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
709
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(180 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.3.b|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
302
709
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(181 of 603)
303
Comply with the following:
Standard§63.9991(a)(1)-Table 2.3.c|1
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Mercury
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes Table 2.3.c
304
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
715
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(182 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.3.c|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.b
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(3)
§63.10006(b)(2), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
716
304
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(183 of 603)
305
§63.9991(a)(1)-Table 2.4.a
Are
you using filter-
able PM as a surrogatefor total HAP
metals?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|1§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii)
[G]§63.10005(b), (c), (d)(1)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate
matter
307
§63.9991(a)(1)-Table 2.4.a
Is heat
input-based limitused?
Yes
No
306
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
722
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(184 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii)
[G]§63.10005(b), (c), (d)(1)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
306
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
722
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)Recordkeeping
[G]§63.10020(e)
No
Comply with the following:Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(185 of 603)
307
§63.9991(a)(1)-Table 2.4.a
No
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total HAP
metals
309Are you using
total HAP metals as thestandard?
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Yes Table 2.4.a
308
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
728
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definitionof “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(186 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
308
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
728
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(187 of 603)
Individual HAP metals are used asalternative equivalent standards (Sb, As,
Be, Cd, Cr, Cobalt, Pb, Mn, Ni, Se and Hg).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
333
Mercury
Have allpollutant paths been
completed? Yes
No
Continue through next path.
310
309
311
315
319
323
327
331
313
317
321
325
329
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(188 of 603)
311
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|5
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Yes
Table 2.4.a
312
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(189 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|6
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
312
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(190 of 603)
313
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|7
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.4.aYes
314
Comply with the following:
Recordkeeping§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(191 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|8
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
314
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(192 of 603)
315
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|9
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
316
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(193 of 603)
Comply with the following:Standard
§63.9991(a)(1)-Table 2.4.a|10§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
316
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(194 of 603)
317
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|11
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
318
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(195 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|12
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
318
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(196 of 603)
319
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|13
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
320
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(197 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|14
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
320
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(198 of 603)
321
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|15
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
322
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(199 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|16
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
322
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(200 of 603)
323
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|17
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
324
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(201 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|18
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
324
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(202 of 603)
325
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|19
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
326
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(203 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|20
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
326
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(204 of 603)
327
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|21
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.4.a
328
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(205 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|22
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
328
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(206 of 603)
329
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|23§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Table 2.4.aYes
330
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(207 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|24
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), (c)
§63.10006(b)(1), (c), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
330
§63.10020(e)
734
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(208 of 603)
331
Comply with the following:
Standard§63.9991(a)(1)-Table 2.4.a|25
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)§63.10000(c)(2)(ii)(A)-(B)
§63.10005(a), (a)(1)-(2), (a)(2(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c)
§63.10006(b)(2), (c), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Table 2.4.a
Yes
332
Comply with the following:Recordkeeping
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
740
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(209 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.a|26
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)§63.10005(a), (d)-(f)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10005(a), (a)(1)-(2), (a)(2(i)-(ii)[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c)
§63.10006(b)(2), (c), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Comply with the following:
Recordkeeping[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
332
741
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(210 of 603)
333
Comply with the following:Standard
§63.9991(a)(1)-Table 2.4.b|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c), (d)(1), [G](d)(4), [G](i)
§63.10006(b)(1), (e), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(3), (d)(3)-Table 7.3
Hydrogen
chloride
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.4.b
Yes
334
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
747
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(211 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.b|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c), (d)(1), [G](d)(4), [G](i)
§63.10006(b)(1), (e), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(3), (d)(3)-Table 7.3
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
334
§63.10020(e)
747
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(212 of 603)
335
Comply with the following:Standard
§63.9991(a)(1)-Table 2.4.c|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f)
[G]§63.10006(i)
§63.10007(e)§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(2), (c)(2)(ii)
§63.10000(c)(2)(ii)(A)-(B)
§63.10000(l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii)
[G]§63.10005(a)(2)(iii), [G](b)
§63.10005(c), (d)(1), [G](d)(4), [G](i)§63.10006(b)(1), (e), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
[G]63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(3), (d)(3)-Table 7.3
Hydrogen
fluoride
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.4.c
Yes
336
753
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(213 of 603)
336
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.4.c|2
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f) Comply with the following:
[G]§63.10006(i) Recordkeeping
§63.10007(e) §63.10000(l), (m)(2)
§63.10011(f)(1)-(2), [G](g) [G]§63.10005(b), (f)[G]§63.10021(e) §63.10020(a)-(b), (d)
§63.10021(e)-Table 7.5-7 [G]§63.10032(a), (c), [G](d), [G](f)
[G]§63.10021(h) §63.10032(g)-(i)
§63.10040 §63.10033(a)-(c)
Monitoring/Testing Reporting
§63.10000(c)(2), (c)(2)(ii) §63.10000(l), (m)(2)
§63.10000(c)(2)(ii)(A)-(B) §63.10005(k)
§63.10000(l)-(m), (m)(1) §63.10021(f)-(g), (i)
§63.10005(a), (a)(1)-(2), (a)(2)(i)-(ii) §63.10030(a), (d), [G](e), (f)
[G]§63.10005(a)(2)(iii), [G](b) §63.10031(a)
§63.10005(c), (d)(1), [G](d)(4), [G](i) §63.10031(a)-Table 8.1.a-c
§63.10006(b)(1), (e), [G](f)(1), (f)(2) [G]§63.10031(b)-(c), (e)-(f)
[G]§63.10006(f)(3), (g)-(h) §63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)Are you§63.10020(a)-(c)
relying on para-§63.10021(a), (d), (d)-Table 7.4No graph (2) definition§63.10021(d)(1)-(3), (d)(3)-Table 7.3
of “startup” in§63.10042?
Comply with the following:
Standard §63.10020(e)§63.9991(a)(1)-Table 3.3.a.(1) Yes
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
753 Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(214 of 603)
369
§63.9991(a)(1)-Table 2.6.a
Are
you using filter-
able PM as a surrogatefor total HAP
metals?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Particulate
matter
371
§63.9991(a)(1)-Table 2.6.a
Is heatinput-based limit
used?
Yes
No
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
370
796
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(215 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.1
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
370
§63.10020(e)
796
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(216 of 603)
371
§63.9991(a)(1)-Table 2.6.a
Are you
using total non-Hg
HAP metals as thestandard?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Total non-mercury HAP
metals
373
Is heat
input-based limit
used?
No
§63.9991(a)(1)-Table 2.6.a
Yes
372
802
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(217 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
372
§63.10020(e)
802
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10010(l)
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(218 of 603)
Individual non-mercury HAP metals areused as alternative equivalent standards
(Sb, As, Be, Cd, Cr, Co, Pb, Mn, Ni and Se).Applicant must go through the flowchart
for each HAP metal pollutant.
Antimony
Arsenic
Beryllium
Cadmium
Chromium
Cobalt
Lead
Manganese
Nickel
Selenium
395
Have allpollutant paths been
completed? Yes
No
Continue through next path.
374
373
375
379
383
387
391
377
381
385
389
393
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(219 of 603)
375
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|5
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
376
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
§63.10031[G](b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
808
§63.10020(e)
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(220 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|6
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
376
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(221 of 603)
377
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|7
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
378
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(222 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|8
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
378
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(223 of 603)
379
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|9
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
380
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(224 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|10
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
380
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(225 of 603)
381
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|11
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
382
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(226 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|12
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
382
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(227 of 603)
383
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|13
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Yes Table 2.6.a
384
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(228 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|14
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
384
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(229 of 603)
385
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|15
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Yes Table 2.6.a
386
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(230 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|16
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
386
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(231 of 603)
387
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|17
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limitused?
No
§63.9991(a)(1)-Yes Table 2.6.a
388
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(232 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|18
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
388
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(233 of 603)
389
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|19
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
390
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(234 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.a|20
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
390
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(235 of 603)
391
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|21
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
392
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(236 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|22
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
392
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(237 of 603)
393
Comply with the following:Standard
§63.9991(a)(1)-Table 2.6.a|23
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Is heat
input-based limit
used?
No
Yes §63.9991(a)(1)-Table 2.6.a
394
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(238 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.a|24
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1), [G](a)(2)(iii)
[G]§63.10005(b), [G](d)(2)§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.2.a-f
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
394
§63.10020(e)
808
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(239 of 603)
395
§63.9991(a)(1)-Table 2.6.b
Are you
using HCl as a
surrogate for acidgas HAP?
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.b|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Hydrogen chloride
397
Is heat
input-based limit
used?No
§63.9991(a)(1)-Yes Table 2.6.b
396
Comply with the following:Recordkeeping
§63.10000(l), (m)(2)[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
814
Yes
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(240 of 603)
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.b|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.3
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
396
§63.10020(e)
814
Are you
relying on para-
graph (2) definition
of “startup” in
§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(241 of 603)
397
Comply with the following:
Standard
§63.9991(a)(1)-Table 2.6.b|3
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)
[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Sulfur
dioxide
Sulfur dioxide is used as an alternate surrogate for acid gas
HAP.
Is heatinput-based limit
used?No
§63.9991(a)(1)-
Yes Table 2.6.b
398
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
820
§63.10020(e)
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(242 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.b|4
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.9991(c), (c)(1)-(2)
§63.10000(a)-(b), (e), (l)-(m), (m)(1)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1), (l)-(m), (m)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b), (d)(1)
§63.10006(b)(1), [G](f)(1), (f)(2)[G]§63.10006(f)(3), (g)-(h)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.5.a-c
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a), (d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Comply with the following:
Recordkeeping
§63.10000(l), (m)(2)
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10000(l), (m)(2)
§63.10005(k)
§63.10021(f)-(g), (i)
§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
398
§63.10020(e)
820
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(243 of 603)
399
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.c|1
§63.9991(a)(1), (a)(1)-Table 3.1
§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7
[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)
§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), [G](e)(2)
§63.10011(a), (e)
§63.10020(a)-(c)§63.10021(a)
Mercury
Is heatinput-based limit
used?No
§63.9991(a)(1)-Yes Table 2.6.c
400
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)
§63.10031(f)(4)-(5), [G](f)(6), (g)
§63.10020(e)
826
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(244 of 603)
Comply with the following:
Standard§63.9991(a)(1)-Table 2.6.c|2
§63.9991(a)(1), (a)(1)-Table 3.1§63.9991(a)(1)-Table 3.3.d
§63.9991(a)(1)-Table 3.4
§63.10000(a)-(b), (e)
§63.10005(a), (d)-(f), (j)
[G]§63.10006(i)
§63.10007(e)
§63.10011(f)(1)-(2), [G](g)
[G]§63.10021(e)
§63.10021(e)-Table 7.5-7[G]§63.10021(h)
§63.10040
Monitoring/Testing
§63.10000(c)(1)§63.10005(a), (a)(1)-(2)
§63.10005(a)(2)(i)-(ii), [G](a)(2)(iii)
[G]§63.10005(b)
§63.10006(b)(2), [G](f)(1)
[G]§63.10006(f)(3), (g)
§63.10007(a), (a)(1)-(2), (b)
§63.10007(b)-Table 5.4
§63.10007(d), (e)(1), (e)(3)
§63.10011(a), (e)
§63.10020(a)-(c)
§63.10021(a)
Comply with the following:
Recordkeeping
[G]§63.10005(b), (f)
§63.10020(a)-(b), (d)
[G]§63.10032(a), (c), [G](d), [G](f)
§63.10032(g)-(i)
§63.10033(a)-(c)
Reporting
§63.10005(k)
§63.10021(f)-(g), (i)§63.10030(a), (d), [G](e), (f)
§63.10031(a)
§63.10031(a)-Table 8.1.a-c
[G]§63.10031(b)-(c), (e)-(f)§63.10031(f)(4)-(5), [G](f)(6), (g)
400
§63.10020(e)
827
Are you
relying on para-
graph (2) definition
of “startup” in§63.10042?
Comply with the following:
Standard§63.9991(a)(1)-Table 3.3.a.(2)
Monitoring/Testing
[G]§63.10020(e)
Recordkeeping
[G]§63.10020(e)
Yes
No
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.a.(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(245 of 603)
401
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
402
No §63.10005(h)
Comply with the following:Monitoring/Testing
§63.10000(c)(1)(iv)120
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(246 of 603)
402
Do you use a CPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)§63.10000(d)(4)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
403
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No 405
§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(247 of 603)
403
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
404
No
405
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(248 of 603)
404
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
405
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(249 of 603)
405
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
406
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(250 of 603)
406
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
120
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(251 of 603)
407
Did you
start-up your affected
source before April 16,
2012?
NoYes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for thispollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i), (c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
Comply with the following: §63.10000(c)(1)(i)(A)Standard
§63.10000(c)(1)(i)(A)
No
408
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
120
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(252 of 603)
408
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
409
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 411
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(253 of 603)
409
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
410
No
411
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(254 of 603)
410
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
411
The unit has a single unit-single
stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(255 of 603)
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
412
No
411
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(256 of 603)
412
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
120
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(257 of 603)
413
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
414
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
109
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(258 of 603)
414
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
415
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 417
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(259 of 603)
415
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
416
No
417
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(260 of 603)
416
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
417
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(261 of 603)
417
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
418
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(262 of 603)
418
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
109
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(263 of 603)
419
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
420
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
122
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(264 of 603)
420
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
421
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
423
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(265 of 603)
421
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
422
No423
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(266 of 603)
422
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
423
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(267 of 603)
423
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
424
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(268 of 603)
424
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
122
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(269 of 603)
425
Did you start-up
your affected source before
April 16, 2012?
No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
426
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
122
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(270 of 603)
426
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(3)
427
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
429
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(271 of 603)
427
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
428
No
429
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(272 of 603)
428
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
429
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(273 of 603)
429
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
430
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(274 of 603)
430
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
122
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(275 of 603)
431
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
432
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(276 of 603)
432
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)
Monitoring/Testing
[G]§63.10010(j)Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)-(3)
433
Yes
Do you use
a CEMS or sorbenttrap to demonstrate
compliance?
No
§63.10007(f)
435
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(277 of 603)
433
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
434
No
435
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(278 of 603)
434
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
435
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(279 of 603)
435
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
436
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(280 of 603)
436
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(281 of 603)
437
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
438
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
137
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(282 of 603)
438
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
439
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
§63.10007(f) 441
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(283 of 603)
439
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
440
No
441
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(284 of 603)
440
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
441
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(285 of 603)
441
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
442
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(286 of 603)
442
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
137
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(287 of 603)
443
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
444
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
137
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(288 of 603)
444
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
445
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 447
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(289 of 603)
445
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
446
No
447
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(290 of 603)
446
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
447
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(291 of 603)
447
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
448
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(292 of 603)
448
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
137
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(293 of 603)
449
Did you start-up
your affected source before
April 16, 2012?
No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
450
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
126
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(294 of 603)
450
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
451
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 453
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(295 of 603)
451
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
452
No
453
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(296 of 603)
452
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
453
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(297 of 603)
453
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
454
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(298 of 603)
454
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
126
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(299 of 603)
455
Did you
start-up your affected
source before April 16, 2012?
No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
456
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
139
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(300 of 603)
456
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
457
Comply with the following:Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
459
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(301 of 603)
457Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Yes
§63.10010(a)
Yes
No
§63.10010(a)
458
No
:
:
:
459
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following
Monitoring/Testing
[G]§63.10010(a)(5)
Comply with the followingMonitoring/Testing
[G]§63.10010(a)(6)
Does the unithave a main stack and
a bypass stack?
Comply with the following
Monitoring/Testing
[G]§63.10010(a)(4)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(302 of 603)
458
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
459
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(303 of 603)
459
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
§63.10010(d)
460
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(304 of 603)
460
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
139
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(305 of 603)
461
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
462
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
139
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(306 of 603)
462
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
463
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
465
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(307 of 603)
463
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
464
No
465
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(308 of 603)
464
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
465
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(309 of 603)
465
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
466
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(310 of 603)
466
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
139
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(311 of 603)
467
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
468
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(312 of 603)
468
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)-(3)
469
Yes
Do you use
a CEMS or sorbenttrap to demonstrate
compliance?
No
471
§63.10007(f)
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(313 of 603)
469
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
470
No471
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(314 of 603)
470
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
471
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(315 of 603)
471
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
472
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(316 of 603)
472
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(317 of 603)
473
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
474
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
155
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(318 of 603)
474
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)Recordkeeping
§63.10000(d)(1), [G](d)(2)[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
475
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
Yes
§63.10007(f) 477
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(319 of 603)
475
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
476
No
477
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(320 of 603)
476
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Does the unit
utilize a common stack with other affected unit(s)?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
477
The unit has a single unit-
single stack configuration
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(321 of 603)
477Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert Yes
measured pollutant
concentrations?
§63.10010(b)
No Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
a stack gas flow rate
monitor for routine operation of aYes
sorbent trap monitoring system
or to convert pollutantconcentrations?
§63.10010(c)
No Comply with the following:
Monitoring/Testing
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when Yes
converting pollutant
concentrations?
§63.10010(d)No
Comply with the following:
478 Monitoring/Testing
§63.10010(d)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(322 of 603)
478
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
155
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(323 of 603)
479
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
480
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
155
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(324 of 603)
480
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
481
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 483
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(325 of 603)
481
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
482
No
483
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(326 of 603)
482
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
483
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(327 of 603)
483
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
484
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(328 of 603)
484
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
155
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(329 of 603)
485
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
486
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
144
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(330 of 603)
486
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
487
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 489
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(331 of 603)
487
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
488
No
489
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(332 of 603)
488
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
489
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(333 of 603)
489
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
490
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(334 of 603)
490
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
144
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(335 of 603)
491
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
492
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
157
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(336 of 603)
492
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
493
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 495
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(337 of 603)
493
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
494
No
495
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(338 of 603)
494
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
495
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(339 of 603)
495
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
496
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(340 of 603)
496
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
157
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(341 of 603)
497
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
498
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
157
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(342 of 603)
498
Do you use aCPMS to demonstrate
compliance?
Yes
No
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
499
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the followi
Monitoring/Testing
§63.10007(f), [G](f)(1), (f
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
§63.1
Yes
No
ng:
)(2)
7.1
5010007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(343 of 603)
499
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
500
No501
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(344 of 603)
500
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
501
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(345 of 603)
501
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
502
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(346 of 603)
502
Do you use
CEMS or sorbent trapYes
systems to measure aHAP directly?
§63.10011(c)(1)
Comply with the following:
Monitoring/TestingNo
§63.10011(c)(1)
157
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(347 of 603)
503
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
504
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(348 of 603)
504
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
505
Yes
Do you usea CEMS or sorbent
trap to demonstrate
compliance?
No
507
§63.10007(f)
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(349 of 603)
505
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
506
No
507
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(350 of 603)
506
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
507
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(351 of 603)
507
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
508
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(352 of 603)
508
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(353 of 603)
509
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
510
§63.10005(h)No
173
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(354 of 603)
510
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2)
§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting
§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
511
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 513
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(355 of 603)
511
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
512
No
513
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(356 of 603)
512
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
513
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(357 of 603)
513
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
514
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(358 of 603)
514
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
173
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(359 of 603)
515
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
516
§63.10005(h)No
173
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(360 of 603)
516
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(c), (c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
517
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
519§63.10000(d)(1)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(361 of 603)
517
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
518
No
519
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(362 of 603)
518
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
519
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(363 of 603)
519
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
520
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(364 of 603)
520
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
173
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(365 of 603)
521
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
522
§63.10005(h)No
161
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(366 of 603)
522
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
Recordkeeping
[G]§63.10010(i)
Reporting
§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
523
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
525§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(367 of 603)
523
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
524
No
525
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(368 of 603)
524
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
525
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(369 of 603)
525
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
526
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(370 of 603)
526
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
161
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(371 of 603)
527
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
528
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(372 of 603)
528
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(c), (c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
529
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
531
§63.10007(f)
Comply with the following:Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(373 of 603)
529
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
530
No
531
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(374 of 603)
530
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
531
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(375 of 603)
531
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
532
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(376 of 603)
532
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
161
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(377 of 603)
533
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
534
§63.10005(h)No
174
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(378 of 603)
534
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)Recordkeeping
[G]§63.10010(h)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
§63.10010(k)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
535
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
537§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(379 of 603)
535
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
536
No
537
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(380 of 603)
536
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
537
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(381 of 603)
537
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
538
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(382 of 603)
538
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
174
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(383 of 603)
539
Did you
start-up your affected
source before April 16, 2012?
No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
540
§63.10005(h)No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(384 of 603)
540
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)Recordkeeping
[G]§63.10010(h)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
§63.10010(k)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
541
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
543§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(385 of 603)
541
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
542
No
543
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(386 of 603)
542
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
543
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(387 of 603)
543
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
544
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(388 of 603)
544
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(389 of 603)
581
Did you start-up your affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
582
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
206
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(390 of 603)
582
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4)Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
583
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
§63.10007(f) 585
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(391 of 603)
583
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
584
No
585
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(392 of 603)
584
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
585
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(393 of 603)
585
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
586
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(394 of 603)
586
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
206
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(395 of 603)
587
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
588
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
206
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(396 of 603)
588
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
589
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
591§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(397 of 603)
589
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
590
No
591
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(398 of 603)
590
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
591
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(399 of 603)
591
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
592
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(400 of 603)
592
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
206
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(401 of 603)
593
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
594
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
195
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(402 of 603)
594
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
595
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 597
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(403 of 603)
595
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
596
No
597
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(404 of 603)
596
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
597
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(405 of 603)
597
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
598
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(406 of 603)
598
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
195
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(407 of 603)
599
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack and
bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
600
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
208
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(408 of 603)
600
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
601
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
603
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(409 of 603)
601
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
602
No
603
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(410 of 603)
602
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
603
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(411 of 603)
603
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
604
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(412 of 603)
604
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
208
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(413 of 603)
605
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
606
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
208
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(414 of 603)
606
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
607
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
609
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(415 of 603)
607
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
608
No
609
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(416 of 603)
608
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
609
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(417 of 603)
609
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
610
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(418 of 603)
610
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
208
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(419 of 603)
611
Did you start-upyour affected source before
April 16, 2012?No
Yes
Comply with the following:
Reporting§63.10030(b)
§63.10030(b)
Comply with the following:
Reporting§63.10030(c)
612
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(420 of 603)
612
Do you use a
CPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
613
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
615
§63.10007(f)
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(421 of 603)
613
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
614
No
615
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(422 of 603)
614
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
615
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(423 of 603)
615
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
616
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(424 of 603)
616
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(425 of 603)
617
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
618
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
237
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(426 of 603)
618
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 ) Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
619
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
Yes
621§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(427 of 603)
619
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
620
No
621
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(428 of 603)
620
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
621
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(429 of 603)
621
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
622
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(430 of 603)
622
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
237
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(431 of 603)
623
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
624
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
237
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(432 of 603)
624
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
625
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 627
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(433 of 603)
625
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
626
No
627
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(434 of 603)
626
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
627
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(435 of 603)
627
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
628
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(436 of 603)
628
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
237
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(437 of 603)
629
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
630
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
216
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(438 of 603)
630
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c)
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c), (c)-Table 7.2
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
631
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 633
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(439 of 603)
631
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
632
No
633
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(440 of 603)
632
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
633
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(441 of 603)
633
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
634
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(442 of 603)
634
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
216
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(443 of 603)
635
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
636
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
241
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(444 of 603)
636
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
637
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
639
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(445 of 603)
637
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
638
No
639
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(446 of 603)
638
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
639
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(447 of 603)
639
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
640
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(448 of 603)
640
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
241
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(449 of 603)
641
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
642
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
241
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(450 of 603)
642
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
643
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
645
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(451 of 603)
643
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
644
No
645
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(452 of 603)
644
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
645
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(453 of 603)
645
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
646
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(454 of 603)
646
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
241
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(455 of 603)
647B
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for thispollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(1)
§63.10005(h)(3)(iii)(C)(3)
Monitoring/Testing
§63.10000(c)(1)(i)-(ii)§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(A)
[G]§63.10005(h)(4)-(5)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
649
No§63.10005(h)
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi) End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(456 of 603)
648B
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
649
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi)
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(2)
Monitoring/Testing§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(B)
[G]§63.10005(h)(4)-(5)§63.10006(b)
§63.10011(d)
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(457 of 603)
649
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
650
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
652
§63.10007(f)
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(458 of 603)
650
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
651
No
652
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(459 of 603)
651
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
652
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(460 of 603)
652
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
653
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(461 of 603)
653
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(462 of 603)
654
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
655
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
269
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(463 of 603)
655
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
Recordkeeping[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)
[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
656
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
658§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(464 of 603)
656
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
657
No
658
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(465 of 603)
657
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
658
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(466 of 603)
658
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
659
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(467 of 603)
659
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
269
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(468 of 603)
660
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
661
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
269
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(469 of 603)
661
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
662
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
664§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(470 of 603)
662
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
663
No
664
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(471 of 603)
663
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
664
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(472 of 603)
664
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
665
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(473 of 603)
665
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
269
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(474 of 603)
666
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
667
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
248
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(475 of 603)
667
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
668
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 670
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(476 of 603)
668
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
669
No
670
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(477 of 603)
669
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
670
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(478 of 603)
670
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
671
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(479 of 603)
671
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
248
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(480 of 603)
672
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing§63.10000(c)(1)(i)
§63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
673
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
273
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(481 of 603)
673
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
674
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
676
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(482 of 603)
674
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
675
No
676
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(483 of 603)
675
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
676
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(484 of 603)
676
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
677
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(485 of 603)
677
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
273
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(486 of 603)
678
Did you start-upyour affected source before
April 16, 2012?
§63.10030(b)
Yes
Comply with the following:
ReportingNo
§63.10030(b)
Is the EGU
equipped with an acid gas
Yes scrubber and have a main stack
and bypass stack exhaust
configuration?
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
NoComply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
Is the unit §63.10005(h)(1), (h)(1)(i)
qualifying as low emitting Monitoring/TestingYes
EGU (LEE) for this §63.10000(c)(1)(i)
pollutant? §63.10000(c)(1)(iii)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10005(h) §63.10011(d)No
Comply with the following:
679 Monitoring/Testing 273
§63.10000(c)(1)(v)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(487 of 603)
679
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)§63.10000(d)(4)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
680
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
682
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(488 of 603)
680
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
681
No
682
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(489 of 603)
681
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
682
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(490 of 603)
682
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
683
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(491 of 603)
683
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
273
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(492 of 603)
684
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(1)
§63.10005(h)(3)(iii)(C)(3)
Monitoring/Testing
§63.10000(c)(1)(i)-(ii)§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(A)[G]§63.10005(h)(4)-(5)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
686
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi) End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(493 of 603)
685
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
686
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi)
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(2)
Monitoring/Testing§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(B)
[G]§63.10005(h)(4)-(5)§63.10006(b)
§63.10011(d)
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(494 of 603)
686
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
687
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f)
689
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(495 of 603)
687
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
688
No
689
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(496 of 603)
688
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
689
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(497 of 603)
689
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
690
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(498 of 603)
690
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(499 of 603)
691
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
692
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
301
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(500 of 603)
692
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 ) Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
693
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
695§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(501 of 603)
693
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
694
No
695
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(502 of 603)
694
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
695
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(503 of 603)
695
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
696
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(504 of 603)
696
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
301
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(505 of 603)
697
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
698
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
301
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(506 of 603)
698
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
699
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 701
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(507 of 603)
699
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
700
No
701
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(508 of 603)
700
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
701
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(509 of 603)
701
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
702
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(510 of 603)
702
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
301
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(511 of 603)
703
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
704
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
280
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(512 of 603)
704
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
705
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 707
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(513 of 603)
705
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
706
No
707
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(514 of 603)
706
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
707
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(515 of 603)
707
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
708
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(516 of 603)
708
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
280
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(517 of 603)
709
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack and
bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
710
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
303
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(518 of 603)
710
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
711
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
713§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(519 of 603)
711
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
712
No
713
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(520 of 603)
712
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
713
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(521 of 603)
713
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
714
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(522 of 603)
714
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
303
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(523 of 603)
715
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for thispollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C) §63.10005(h)(3)(iii)(C)(1)
§63.10005(h)(3)(iii)(C)(3)
Monitoring/Testing
§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(A)
[G]§63.10005(h)(4)-(5)§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
717
§63.10005(h)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(524 of 603)
716
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for thispollutant?
Yes
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
717
§63.10005(h)
No
Comply with the following:Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(2)
Monitoring/Testing
§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(B)
[G]§63.10005(h)(4)-(5)§63.10006(b)
§63.10011(d)
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(525 of 603)
717
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)-(3)
718
Yes
Do you usea CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f)
720
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(526 of 603)
718
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
719
No
720
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(527 of 603)
719
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
720
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(528 of 603)
720
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
721
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(529 of 603)
721
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(530 of 603)
722
333
Did you start-up
your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting
§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(2)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
723
§63.10005(h)
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(531 of 603)
723
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(a)(3), (c)§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)§63.10023(a)
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
724
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
§63.10007(f) 726
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(532 of 603)
724
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
725
No
726
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(533 of 603)
725
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
726
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(534 of 603)
726
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
727
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(535 of 603)
727
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
333
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(536 of 603)
728
333
Did you start-up
your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(2)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
729
§63.10005(h)
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(537 of 603)
729
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(c), (c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
730
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 732
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(538 of 603)
730
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
731
No
732
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(539 of 603)
731
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
732
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(540 of 603)
732
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
733
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(541 of 603)
733
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
333
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(542 of 603)
734
310
Did you start-up
your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(2)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
735
§63.10005(h)
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(543 of 603)
735
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(2)
736
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
738§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(544 of 603)
736
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
737
No
738
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(545 of 603)
737
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
738
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(546 of 603)
738
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
739
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(547 of 603)
739
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
310
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(548 of 603)
740
Did you start-up your affected source before
April 16, 2012?
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(1)
§63.10005(h)(3)(iii)(C)(3)
Monitoring/Testing
§63.10000(c)(2)(i)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(A)
[G]§63.10005(h)(4)-(5)
§63.10006(b)
§63.10011(d)
§63.10005(h)
742
No
310
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(549 of 603)
741
Did you start-upyour affected source before
April 16, 2012?
Yes
§63.10030(b)
Comply with the following:
Reporting
§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(2)
Monitoring/Testing
§63.10000(c)(2)(i)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(B)
[G]§63.10005(h)(4)-(5)
§63.10006(b)
§63.10011(d)
742
§63.10005(h)No
Comply with the following:Monitoring/Testing
§63.10000(c)(2)(ii)
310
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(550 of 603)
742
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10006(a)
§63.10007(c), (c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
743
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f)
745
Comply with the following:Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(551 of 603)
743
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
744
No
745
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(552 of 603)
744
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
745
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(553 of 603)
745
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
746
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(554 of 603)
746
Comply with the following:Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
310
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(555 of 603)
747
335
Did you start-up
your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting
§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(2)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
748
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
§63.10000(c)(2)(iii)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(556 of 603)
748
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )Monitoring/Testing
§63.10010(k)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
749
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 751
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(557 of 603)
749
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
750
No
751
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(558 of 603)
750
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
751
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(559 of 603)
751
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
752
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(560 of 603)
752
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
335
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(561 of 603)
753
Did you start-up
your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting
§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(2)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
754
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
§63.10000(c)(2)(iii)End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(562 of 603)
754
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )Monitoring/Testing
§63.10010(k)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
755
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f) 757
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(563 of 603)
755
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
756
No
757
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(564 of 603)
756
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
757
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(565 of 603)
757
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
758
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(566 of 603)
758
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(567 of 603)
796
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
797
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
395
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(568 of 603)
797
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:
Standard
§63.9991(a)(2), (a)(2)-Table 4
§63.10023(c)
Monitoring/Testing
§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:Monitoring/Testing
§63.10000(c)(1)(iv)(B)
§63.10007(f), [G](f)(1), (f)(2)[G]§63.10010(i)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Recordkeeping
[G]§63.10010(i)
Reporting§63.10031(f)(1)
Comply with the following:Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 ) Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
798
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
800§63.10007(f)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(569 of 603)
798
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
799
No
800
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(570 of 603)
799
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
800
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(571 of 603)
800
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
801
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(572 of 603)
801
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
395
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(573 of 603)
802
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
803
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
395
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(574 of 603)
803
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
804
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 806
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(575 of 603)
804
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
805
No
806
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(576 of 603)
805
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
806
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(577 of 603)
806
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
807
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(578 of 603)
807
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
395
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(579 of 603)
808
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
809
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(iv)
374
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(580 of 603)
809
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Standard
§63.9991(a)(2), (a)(2)-Table 4§63.10023(c)
Monitoring/Testing§63.10000(c)(1)(iv)(A)
§63.10006(a)
§63.10007(a)(3), (c)
§63.10007(c)-Table 6
[G]§63.10010(h)
§63.10011(b)
[G]§63.10021(c), (c)-Table 7.2
[G]§63.10023(b)
Recordkeeping
[G]§63.10010(h)
[G]§63.10021(c)
§63.10023(a)
Comply with the following:
Monitoring/Testing§63.10000(c)(1)(iv)(B)
Comply with the following:
Standard§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)Reporting
§63.10000(d)(3)§63.10031(d), (f)(2)
810
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No 812
§63.10000(c)(1)(iv)(B)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(581 of 603)
810
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
811
No
812
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(582 of 603)
811
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
812
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(583 of 603)
812
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
813
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(584 of 603)
813
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
374
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(585 of 603)
814
Did you
start-up your affected
source before April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
815
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
399
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(586 of 603)
815
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
816
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(e)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
818
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(587 of 603)
816Does the
unit have multipleparallel control devices Yes
with multiple
stacks?
§63.10010(a) Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)No
Does the unit
have a common control de-Yes
vice and multiple stack or duct
configuration?
§63.10010(a) Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)No
Does the unithave a main stack and Yes
a bypass stack?
§63.10010(a)Comply with the following:
Monitoring/TestingNo [G]§63.10010(a)(4)
817 818
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(588 of 603)
817
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
818
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(589 of 603)
818
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
819
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(590 of 603)
819
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
399
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(591 of 603)
820
Did you
start-up your affected
source before April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), (h)(1)(i)
Monitoring/Testing
§63.10000(c)(1)(i)
[G]§63.10005(h)(2)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
821
§63.10005(h)No
Comply with the following:
Monitoring/Testing
§63.10000(c)(1)(v)
399
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(592 of 603)
821
Do you use aCPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)
Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)§63.10000(d)(4 )
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10032(b)
Reporting
§63.10000(d)(3)
§63.10031(d), (f)(3)
822
Comply with the following:
Monitoring/Testing
§63.10007(f), [G](f)(1), (f)(2)
§63.10010(f)(1)-(4)
§63.10011(c)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
Yes
No
Comply with the following:
Monitoring/Testing
§63.10006(d)
§63.10007(f)
824
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(593 of 603)
822
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
823
No
824
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(594 of 603)
823
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
824
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(595 of 603)
824
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
825
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(596 of 603)
825
Comply with the following:
Monitoring/Testing§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
399
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(597 of 603)
826
Did you start-up your affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(1)
§63.10005(h)(3)(iii)(C)(3)
Monitoring/Testing
§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(A)[G]§63.10005(h)(4)-(5)
§63.10006(b)
§63.10011(d)
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
828
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi) End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(598 of 603)
827
Did you start-upyour affected source before
April 16, 2012?
No
Yes
§63.10030(b)
Comply with the following:
Reporting§63.10030(b)
Is the unit
qualifying as low emitting
EGU (LEE) for this
pollutant?
Yes
Is the EGU
equipped with an acid gas
scrubber and have a main stack
and bypass stack exhaust
configuration?
Yes
§63.10000(c)(1)(i)(A)
§63.10005(h) Comply with the following:
Standard
§63.10000(c)(1)(i)(A)
No
828
§63.10005(h)
No
Comply with the following:
Monitoring/Testing
[G]§63.10000(c)(1)(vi)
Comply with the following:
Standard
[G]§63.10000(c)(1)(i)(C)
§63.10005(h)(1), [G](h)(1)(ii)
§63.10005(h)(3)(iii)(C)
§63.10005(h)(3)(iii)(C)(2)
Monitoring/Testing§63.10000(c)(1)(i)-(ii)
§63.10005(h)(3), [G](h)(3)(i)
§63.10005(h)(3)(ii)-(iii)
§63.10005(h)(3)(iii)(B)
[G]§63.10005(h)(4)-(5)§63.10006(b)
§63.10011(d)
End
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(599 of 603)
828
Do you use a
CPMS to demonstrate
compliance?
Yes
No
§63.10006(a)
Comply with the following:Monitoring/Testing
§63.10006(a)
[G]§63.10010(h)Recordkeeping
[G]§63.10010(h)
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.3.c
Monitoring/Testing
§63.10005(d)(3)
§63.10007(f), [G](f)(1), (f)(2)
§63.10021(b), (b)-Table 7.1
Reporting
§63.10031(f)(1)
Comply with the following:
Standard
§63.10000(d)(1), [G](d)(2)
§63.10000(d)(4 )
Monitoring/Testing
[G]§63.10010(j)
Recordkeeping
§63.10000(d)(1), [G](d)(2)
[G]§63.10000(d)(5)
[G]§63.10010(j)
[G]§63.10032(b)
Reporting§63.10000(d)(3)
§63.10031(d), (f)(2)-(3)
829
Yes
Do you use
a CEMS or sorbent
trap to demonstrate
compliance?
No
§63.10007(f)
831
Comply with the following:
Monitoring/Testing
§63.10006(f)(2)
§63.10021(d), (d)-Table 7.4
§63.10021(d)(1)-(2)
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(600 of 603)
829
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(6)
Does the
unit have multipleparallel control devices
with multiple
stacks?
Yes
§63.10010(a)
No
Does the unit
have a common control de-vice and multiple stack or duct
configuration?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(5)
Yes
§63.10010(a)
Does the unithave a main stack and
a bypass stack?
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(4)
Yes
No
§63.10010(a)
830
No
831
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(601 of 603)
830
Comply with the following:Monitoring/Testing
[G]§63.10010(a)(3)
Does the unit(s)utilize a common stack with
non-affected unit(s)?Yes
§63.10010(a)
No
Comply with the following:
Monitoring/Testing
[G]§63.10010(a)(2)
Yes
§63.10010(a)
Comply with the following:
Monitoring/Testing
§63.10010(a)(1)
No
831
The unit has a single unit-
single stack configuration
Does the unit
utilize a common stack with other
affected unit(s)?
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(602 of 603)
831
Comply with the following:
Monitoring/Testing§63.10010(b)
Do you use
an oxygen (O2) or carbondioxide (CO2) CEMS to convert
measured pollutant
concentrations?
Yes
§63.10010(b)
No
Do you use
a stack gas flow rate
monitor for routine operation of a
sorbent trap monitoring system
or to convert pollutantconcentrations?
Comply with the following:
Monitoring/Testing
§63.10010(c)
Yes
§63.10010(c)
Are you required
to make corrections for
stack gas moisture content when
converting pollutant
concentrations?
Comply with the following:
Monitoring/Testing
§63.10010(d)
Yes
No
§63.10010(d)
832
No
Last Modified: March 22, 2019 From 40 CFR Part 63, Subpart UUUUU, Amended: July 2, 2018.These flowcharts are for use by sources subject to the Federal Operating Permit Program and are subject to change.
40 CFR Part 63, Subpart UUUUU:Coal- and Oil-Fired Electric Utility Steam Generating Units
(603 of 603)
832
Comply with the following:
Monitoring/Testing
§63.10010(g)
§63.10011(c)(1)
Do you use
CEMS or sorbent trap
systems to measure aHAP directly?
Yes
§63.10011(c)(1)
No
End
900
Is the EGU new
or reconstructed?
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.1
Comply with the following:
Standard
§63.9991(a)(1)-Table 3.2
End
No Yes
§63.9982(b)§63.9982(c)