tc7d series digital time clock

12
TC7D-W Wall mount TC7D-E Enclosure TC7D-W (Wall Mount) TC7D-E (Enclosure) TC7D SERIES DIGITAL TIME CLOCK Supplemental Installation Manual for Accessories

Upload: others

Post on 01-May-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TC7D SERIES DIGITAL TIME CLOCK

TC7D-W Wall mount

TC7D-E Enclosure

TC7D-W (Wall Mount) TC7D-E (Enclosure)

TC7D SERIES DIGITAL TIME CLOCKSupplemental Installation Manual for Accessories

Page 2: TC7D SERIES DIGITAL TIME CLOCK

1.800.627.44992

TC7D Series Digital Time ClockACCESSORY

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING RULES: Use the unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.

Before installing, servicing or troubleshooting the transformer/re-lay package, switch power off at service panel and lock service panel to prevent power from being switched on accidentally.

WARNING

More than one disconnect switch may be required to de-energize the equipment for servicing.

Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

When cutting or drilling into wall or ceiling, do not damage elec-trical wiring and other hidden utilities.

NEVER place a switch where it can be reached from a tub or shower.

Intended for use with 24VAC Class 2 power supplies only.

Do not connect loads that exceed the timer’s switch rating.

Confirm sufficient 24VAC power is available to operate the timer and the connected loads.

CAUTION

Page 3: TC7D SERIES DIGITAL TIME CLOCK

31.800.627.4499

TC7D Series Digital Time Clock ACCESSORY

1.0 OVERVIEW 4

1.1 SPECIFICATIONS ..................................................................................................4

1.2 DIMENSION DRAWINGS .......................................................................................5

2.0 SETTINGS 6

2.1 SETTING INSTRUCTIONS ......................................................................................6

3.0 ELECTRICAL 7

3.1 WIRING SCHEMATICS...........................................................................................7

TABLE OF ILLUSTRATIONSFigure 1.2.0 TC7D-W Dimensions........................................................................................................5Figure 1.2.1 TC7D-E Dimensions .........................................................................................................5Figure 2.1.0 Setting Instructions .........................................................................................................6

TABLE OF SCHEMATICSFigure 3.1.0 EV90, EV90P, EV130, EV200, and EV300 Schematic ........................................................7Figure 3.1.1 SL70 Schematic ..............................................................................................................7 Figure 3.1.2 EV Premium Schematic ....................................................................................................7Figure 3.1.3 EV450, HE1X, and HE1.5 Standard Wiring Schematic........................................................8Figure 3.1.4 HE1XRT, HE1.5RT with Independent Blower Control and HE2X–LE10X Schematic .............8Figure 3.1.5 EV450 ECM with Terminal Block Schematic ......................................................................8Figure 3.1.6 HE1X and HE1.5 ECM with Terminal Block Schematic .......................................................9Figure 3.1.7 EV450, HE1X, and HE1.5 ECM with Circuit Board Schematic .............................................9Figure 3.1.8 EV450, HE1X, and HE1.5 ECM with Circuit Board and CO2 Schematic ............................. 10Figure 3.1.9 RH-W Electric Heater Schematic .................................................................................... 10

TABLE OF CONTENTS

Page 4: TC7D SERIES DIGITAL TIME CLOCK

1.800.627.44994

TC7D Series Digital Time ClockACCESSORY

Operating Voltage: 24VAC 50/60Hz

Switching: Single Pole, Single Throw [SPST]

(can be field-modified to Single Pole, Double Throw [SPDT])

Power consumption: 3.5VA

Switch rating: 10 Amps at 131°F

Operating Temperature Range: 14°F–131°F

Connections (TC7D-W): (3) 16 GA pigtails (wire nuts not provided)

Connections (TC7D-E): (3) copper screw terminals

Setting Options: u 8 pairs of on-off time of day cycles can be programmed. u Each on-off cycle can be assigned to any one day of the week, or to the following groups

of days:

Monday–Friday; Monday–Saturday; Monday–Sunday; Saturday and Sunday.u Manual Over-ride provided by “On/Auto/Off” switch.u Program Reset button clears all settings.

Enclosure (TC7D-W): Requires a 4" x 4" electrical box by others. u Box must accommodate (4) mounting screws (see drawing). u Minimum box depth 1.5". White wall plate and mounting screws provided.

Enclosure (TC7D-E): NEMA 3R (see drawing page 4).

OVERVIEW

1.0 OVERVIEW1.1 SPECIFICATIONS

Page 5: TC7D SERIES DIGITAL TIME CLOCK

51.800.627.4499

TC7D Series Digital Time Clock ACCESSORY

SETTINGS

1.2 DIMENSION DRAWINGS

DIMENSIONS ARE APPROXIMATE.

.8750

1.250

7.0 ACCESS

2.750

.940

1.250

6.150

2.060

4.120

1.250

2.500

8.040

ISOMETRIC VIEW

FRONT VIEW

.955

.938

1.875

ø0.8750Knockout

ø1.1250 Knockout (5)

ø0.2580Thru

FIGURE 1.2.1 TC7D-E ENCLOSURE DIMENSIONS

4 1/2"

4 1/2"

1 13/16"

3 5/16"

FIGURE 1.2.0 TC7D-W WALL MOUNT DIMENSIONS

Page 6: TC7D SERIES DIGITAL TIME CLOCK

1.800.627.44996

TC7D Series Digital Time ClockACCESSORY

SETTINGS

Set Time and Day Slide Set switch to press 1…7 button until arrow points to the correct day (1=Monday). Press h then m buttons to set correct time. PM indicator shows noon to 11:59 PM. Slide Set switch to Run. Clock colon will blink.

Set Switch “On” Cycle Slide Set switch to . A “1” indicates the first switch cycle and a “Bulb” indicates a switch-on (circuit closes). Press 1…7 button until arrows point to selected day(s) for this cycle. Press h and m buttons to show switch-on time, noting PM indicator.

Set Switch “Off” Cycle With Set switch at , press button, note switch cycle number changes to “2” and bulb blanks, indicating switch-off (circuit opens). Press 1…7 button to match day(s) set for switch cycle “1.” Press h and m buttons to select switch-off time.

Autorun Slide Set switch to Run and Mode switch to Auto, switching begins with next switch-on set time.

Override “On” Slide Mode switch to I. Switch remains on indefinitely (circuit closed).

Override “Off” Slide Mode switch to O. Switch remains on indefinitely (circuit open).

Skip Cycle In automatic run mode, press x→ button. The next calendar day is skipped.

Setting ERROR If EEE appears, a setting error exists. The switch cycle number in error is shown. Slide set switch to , press button until cycle is shown, review this and the following setting to correct error, slide set switch to Run.

Clear any setting Setting slide set switch to , press button to show switch cycle to clear. Press the button and the skip (x) button simultaneously, hold for several seconds.

Clear All To erase all settings, Press R.

2.0 SETTINGS2.1 SETTING INSTRUCTIONS

FIGURE 2.1.0 SETTING INSTRUCTIONS

Page 7: TC7D SERIES DIGITAL TIME CLOCK

71.800.627.4499

TC7D Series Digital Time Clock ACCESSORY

ELECTRICAL

3.0 ELECTRICAL3.1 ELECTRICAL SCHEMATICS

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1 1

2

3

BLACK

RED

YEL

24 VAC

ERV INTERNAL CONTROLWIRING (SIMPLIFIED)

COMM

HIGH OR LOW SPEED INPUT

SL70

SL70

FIGURE 3.1.1 SL70 SCHEMATIC

CHANGESNAMEREV. DATE

SCHEMETimer

RenewAire

1

A B C D E

1

EV Premium Field

2

3

4

5

6

7

8

9

10

11

12

13

SF_ECM_SIGNAL

SF_ECM_POWER

120VAC

120COM

24VAC

HIGH

COM

EF_ECM_POWER EF_ECM_SIGNAL

Control Board

WHT

RD

BK

2

1

3

1

2

2 1 122

1

2

3

FIGURE 3.1.2 EV PREMIUM SCHEMATIC

FIGURE 3.1.0 EV90, EV90P, EV130, EV200, EV240, AND EV300 SCHEMATIC

Control Terminals

Unit Internal WiringNot Shown

EV90EV90PEV130 EV200EV240EV300

24VAC Class II Power Supply provided by other

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1

EV Residential

NOTE: There is a wire on the TC7D that connects

terminal 1 to terminal 5. You must cut this wire to eliminate voltage to terminal 5.

In this example, the timer turns the Energy Recovery Ventilator (ERV) on at High speed when the timer dictates it is an occupied time.

Page 8: TC7D SERIES DIGITAL TIME CLOCK

1.800.627.44998

TC7D Series Digital Time ClockACCESSORY

ELECTRICAL

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1 1

2

3

Unit's 24VAC Power Supply

ERV INTERNAL CONTROL

C Isolation Relay Coil or Damper

Actuator Coil

WIRING (SIMPLIFIED)

123

10

The Normally Open (N.O.) contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the TC7D-E and TC7D-W.

EV450 +EC

FIGURE 3.1.5 EV450 ECM WITH TERMINAL BLOCK SCHEMATIC

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1 1

2

3

BLACK

RED

YEL

BLUE

RED

YELLOW

The Normally Closed (N.C.) contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the TC7D-E/W.

Unit's 24VAC Power Supply

ERV INTERNAL CONTROL

C IsolationRelay Coil

WIRING (SIMPLIFIED)

BLUE

YEL

YEL

RED

EV450 , 1X, 1.5IN

FIGURE 3.1.3 EV450, HE1X, AND HE1.5 STANDARD WIRING SCHEMATIC

NOTE: For EV450 and HE1XIN models built prior to 1/22/2011, please

call RenewAire Customer Service at 800-627-4499 or email [email protected].

The Normally Closed (N.C) contacts of one or more additional Low Voltage Controls may be connected to ERV unit's Terminals 1 & 4. Do not apply power to these terminals.

Unit's 24VAC Power Supply

ERV INTERNAL CONTROL

CIsolation

Relay Coil or Damper

Actuator Coil

WIRING (SIMPLIFIED)

12345

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1 1

2

3

BLACK

RED

YEL

1X, 1.5RT-LE

C

FIGURE 3.1.4 HE1XRT AND HE1.5RT WITH INDEPENDENT BLOWER CONTROL AND HE2X–LE10X SCHEMATIC

NOTE: For HE1XRT and HE2X through LE10X models built prior to 1/22/2011,

please call RenewAire Customer Service at 800-627-4499 or email [email protected].

Page 9: TC7D SERIES DIGITAL TIME CLOCK

91.800.627.4499

TC7D Series Digital Time Clock ACCESSORY

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1 1

2

3

1X and 1.5 +EC

Unit's 24VAC Power Supply

ERV INTERNAL CONTROL

C Isolation Relay Coil or Damper

Actuator Coil

WIRING (SIMPLIFIED)

12

8

12

8

C Isolation Relay Coil or Damper

Actuator Coil

TB(EA/RA)

TB(OA/FA)

The Normally Open (N.O.) contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the TC7D-E and TC7D-W.

FIGURE 3.1.6 HE1X AND HE1.5 ECM WITH TERMINAL BLOCK SCHEMATIC

ELECTRICAL

CHANGESNAMEREV. DATE

Description

Family

ConfigTimer

RenewAire

1

A B C D E

EV450 ECM

2

3

4

5

6

7

8

9

10

11

12

13

EV450Jxx--x11,15-----GxTx-xx_006

24VA

C

BKRDYLYL VAR

EN24VACCOM

Circuit Board

YLPU

OR

GND

W

10V

COM BK

RD

1

12

R2

FIGURE 3.1.7 EV450, HE1X AND HE1.5 ECM WITH CIRCUIT BOARD SCHEMATIC

In this example, the timer turns ERV on at speed set by potentiometer(s) when space is occupied. EV450 Circuit Board shown with one potentiometer. HE1X and HE1.5 Circuit Boards have two potentiometers.

Page 10: TC7D SERIES DIGITAL TIME CLOCK

1.800.627.449910

TC7D Series Digital Time ClockACCESSORY

24VAC Class II Power Supply provided by other

1

2

3

4

5

TC7D-WTC7D-E

5

4

3

2

1

6 5 4 3 2 R C

0-10VDC

24 VAC

CO

MM

ON

RH-WCTH-2910-10VDC THERMOSTAT Supplied with RH-W Heaters

When Normally Closed (NC) contacts open at desired times, the thermostat will operate in Comfort Mode. When NC contacts are across RH-W thermostat terminals the thermostat will operate in Economy Mode which reduces the RH-W heater outlet set-point temperature by 8 degrees F.

RH

FIGURE 3.1.9 RH-W ELECTRIC HEATER SCHEMATIC

NOTE: Remove supplied wires from the time clock spade terminals prior to

wiring to a RH-W thermostat as shown.

ELECTRICAL

FIGURE 3.1.8 EV450, HE1X, AND HE1.5 ECM WITH CIRCUIT BOARD AND C02 SCHEMATIC

CHANGESNAMEREV. DATE

Description

Family

ConfigTimer and CO2 Sensor

RenewAire

1

A B C D E

EV450 ECM

2

3

4

5

6

7

8

9

10

11

12

13

EV450Jxx--x11,15-----GxTx-xx_00624

VAC

BKRDYLYL VAR

EN24VACCOM

Circuit Board

YLPU

OR

GND

W

10V

COM BK

RD

1

12

In this example, the ERV does not run while unoccupied, set by timer. During occupancy, ERV runs at variable Speed. CO2 Controller sets speed based on CO2 levels. Remove the potentiometer(s) by cutting the wires at the potentiometer. Cap the orange and purple wires from the potentiometer with wire nuts. EV450 Circuit Board shown with one potentiometer. HE1X and HE1.5 Circuit Board has two potentiometers and the cut wires can be wired in parallel back to the CO2 Controller.

Page 11: TC7D SERIES DIGITAL TIME CLOCK

111.800.627.4499

TC7D Series Digital Time Clock ACCESSORY

THIS PAGE IS INTENTIONALLY LEFT BLANK.

Page 12: TC7D SERIES DIGITAL TIME CLOCK

About RenewAireFor over 30 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size.This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick Response Manufacturing (QRM).

As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV producer in the USA. We’re committed to sustainable manufacturing and lessening our environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes certified, as well as having achieved ENERGY STAR Building status. In 2010, RenewAire joined the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energy-efficient air-moving technologies. For more information, visit: renewaire.com

201 Raemisch Road | Waunakee, WI | 53597 | 800.627.4499 | RenewAire.com

Member of the S&P Group Family of Brands

2021 © RenewAire LLC138200_007_JUN21