task 3.4. validation of horizontal solutions fire and mechanical characterization
TRANSCRIPT
Task 3.4. Validation of horizontal solutions
Fire and mechanical characterization
I. Fire validation
Reaction to Fire Tests EN-13501-1Determines whether a material fuels a fire. The EU Reaction to fire evaluation criteria are:
the material’s ignitability, rate of heat release, rate of spread of flame, rate of smoke emission, toxic gas emission, flaming droplets/particles and/or a combination of these safety aspects.
Fire reaction requirements:
Bfl-s2 or Efl (depending on the type of building)B-s3d0 (suspended ceiling), SBI test
Contribution to fireB Very limited contribution
E Significant contribution to flashover
Smoke productions2 middle smoke production
s3 High smoke production
Flaming droplets d0 no production of flaming droplets or particles
• Ignitability test EN ISO-11925-2
• Determination of the burning behavior of floorings, using a radiant heat source EN ISO 9239-1
• Single Burning Item test EN 13823 (recommended but not required for raised floors). If this test is performed, panels could be also employed for other applications, such as suspended ceilings.
StandardNumber
of samples
Number of 500x500 mm
panels
Dimensions (mm) of test
samples
EN ISO 11925-2 6 1 250 x 90
EN ISO 9239-1 4 2 1050 x 230
EN 13823 4 4
126
1000 x 15001500 x 495
Tests to be performed:
EN 13823EN 13823
Heat and smoke release rates are measured instrumentally and physical characteristics are assessed by observation.
EN 9239-1EN 9239-1
EN 11925-2EN 11925-2
The test specimen is placed in a horizontal position below a gas-fired radiant panel inclined at 30° where it is exposed to a defined heat flux. A pilot flame is applied to the hotter end of the specimen.
The test determines the ignitability of a vertically oriented test specimen when exposed to a small flame, either at the edge or the surface of the specimen.
Resistance to fire EN-13501-2
Test criteriaTest criteria
Fire resistance tests evaluate the behaviour of the elements used in the construction sector when exposed to fire, assessing the period of time during which these elements continue to fulfill the roles for which they were designed in case of fire.
Classification Time of exposure (min)
R 15 30
RE 30
REI 30
R. The structural element should not collapse or deflect beyond the permitted levels when subjected to the applied load.
E. The integrity of the room must be maintained. No breakthrough of flames is permitted.
I. The temperature on the non-exposed side of the structural element must not rise more than 140° C above ambient as an average measurement and no more than 180° C at any one location.
• Fire resistance requirements
EN 1366-6EN 1366-6
Fire is applied below raised access floors between the underside of the raised floor and the upper side of the structural floor slab.
Tests to be performed
•Fire resistance tests for service installations - Part 6: Raised access and hollow core floors EN 1366-6:2005
•Fire resistance tests. Part 1: General Requirements EN 1363-1 (Experimental test, not required for classification)
StandardNumber
of samples
Number of 500x500 mm
panels
Dimensions (mm) of test
samples
EN 1366-6 1 48 3000 x 4000
Fire reaction tests 2980 euros (2 samples)
-UNE EN ISO 11925-2:2011-UNE EN ISO 9239-1:2011
Experimental test EN-1363-11575 euros (1 sample)
Experimental test EN-1363-11575 euros (1 sample)
Fire reaction test 1950 euros (1 sample)
UNE-EN 13823:2012
Design of the facade
Fire resistance tests Change material?
Certification test UNE EN 1366-6:20056345 euros (1 sample)
Change final applicationi.e. ventilated facade
Test Number of tests
Static load (steel cube in 3 different positions) 3 (x4)
Pedestal vertical load test Not definedPermanent deformation test on element 2
Dynamic load (in the weakest point of the panel)
Hard body impact load (steel indentor in 3 different positions)
111
Soft body impact load11
Measurement of dimensions 3Peel resistance? 2
Total number of samples 24
II. Mechanical validation (EN 12825)
Static load Pedestal load test Dynamic load
Task 3.4. Validation of horizontal solutions
Fire and mechanical characterization
Mechanical validation • Static load test:
– Panels mounted in the particular pedestals as would be on site
– Stringers shall be included with another fixing elements.
– Indentor: 25mm steel cube with rounded corners
– 4 tests in different points of the panel:• At the centre of the weakest edge• At the centre of the panel• At a diagonal 70 mm from the edge of a
pedestal head
• Pedestal vertical load test: – The requirements for the test results:
• The understructure has to support 4 times the working load of the system tested
• The pedestal may not become distorted or damaged.– Indentor: 50 x 50 mm– Same fixing as intended to be use in practice.– The test has to be performed to the worst conditions of work
• Permanent deformation test on element– As a result of the test after the application of 30 min of a test load,
the residual deflection 5 min after the removal of the load shall not exceed 0,5mm.
– Test made at the weakest point of the panel.– Working load is applied by a 25 mm cube.
• Dynamic loading: – Hard body impact:
• In the test a steel indentor with a mass of 4,5 kg and with a 50mm hemispherical end shall be dropped inside a guide tube from a height of 600mm in three diferrent positions and the panel shall not collapse
• Result is given as Pass or Fail– Soft boy impact:
• The indentor is a flat bottomed canvas bag containing dried sand 2 to 4 mm diameter and with a mass of 40 kg.
• The filled bag shall be dropped on to the test panel from a height of 1 at three points of the panel and the panel shall not collapse.
– In both test the result is given as pass or fail and sufficient free space shall be available under the test panel to permit the indentors to penetrate the panel in case of failure.
• Sampling and preparation for dimensional measurement– Length of panel sides– Squareness of the panel– Straightness of sides horizontally– Thickness of the panel– Panel twist
• Peel resistance– In the test a steel indentor with a mass of 4,5 kg and with a 50mm
hemispherical end shall be dropped inside a guide tube from a height of 600mm in three diferent positions and the panel shall not collapse
Activities performed within the last 6 months (WP3)Activities performed within the last 6 months (WP3)
1.Fire reaction tests
2.Fire resistance tests
3.Mechanical validation
4.Deliverable 3.4.1. Validation of horizontal solutions
1. Fire reaction tests
Aluminum -Reaction to fire tests for floorings - Part 1: Determination of the burning behavior using a radiant heat source
-Reaction to fire tests - Ignitability of products subjected to direct impingement of flame - Part 2: Single-flame source test
Fire reaction classification: Bfl-s1
It can be applied as raised floor
Method Parameter Result
UNE-EN ISO 9239-1:2011 Max distance of flame propagation 0,0 mm
Radiant flux, CHF (KW/m2) 10,9 KW/m2
Smoke development 4,33 % min
Max light attenuation 0,98 %
UNE-EN ISO 11925-2:2011 Fs ≤ 150 mm (60 s) YES
Filter paper inflammation NO
1. Fire reaction tests1. Fire reaction tests
Fiber/resin composite-Reaction to fire tests for floorings - Part 1: Determination of the burning behavior using a radiant heat source
-Reaction to fire tests - Ignitability of products subjected to direct impingement of flame - Part 2: Single-flame source test
Fire reaction classification: Efl-s2
Very low classification
Method Parameter Result
UNE-EN ISO 9239-1:2011 Max distance of flame propagation 590,0 mm
Radiant flux, CHF (KW/m2) 2,9 KW/m2
Smoke development 2070,7 % min
Max light attenuation 0,01 %
UNE-EN ISO 11925-2:2011 Fs ≤ 150 mm (60 s) YES
Filter paper inflammation NO
Fire source
1. Fire reaction tests1. Fire reaction tests
Aluminum-EN 13823: 2012-Reaction to fire tests for building products - Building products excluding floorings exposed to
the thermal attack by a single burning item.
Evaluated parameters over 21 minutes: heat emission smoke production lateral propagation dripping inflamed particles
1. Fire reaction tests1. Fire reaction tests
Aluminum-EN 13823: 2012-Reaction to fire tests for building products - Building products excluding floorings exposed to
the thermal attack by a single burning item.
Fire reaction classification: B-s1, d0
It can be applied as raised floor
2. Fire resistance tests
2. Fire resistance tests
Failure time in “experimental” test: 19 minutes
Classification REI 15?? (lowest possible)
“Large scale” test aprox. 7000€
3. Mechanical Validation
Static load
Coefficient Load (N)
K = 3 1698,6
K = 2 2548
Classification Ultimate load (KN)
1 ≥ 4
2 ≥ 6
3 ≥ 8
4 ≥ 9
5 ≥ 10
6 ≥ 12
Ultimate load
Coefficient Work load
Strain (mm)
Classification
K = 3 1698,6 1698,6 2,97 1A
K = 2 2548 2548 4,6 Not classified
3. Mechanical Validation
Vertical load on pedestal
Work load (k=2)
Load Result
2548 10192 N Satisfactory
Permanent deformation test on element
Work load (k=2)
Deformation with load
Deformation w/o load
Residual deformation
Result
2548 N 4,55 mm 0,85 mm 0,48 mm Satisfactory
Hard body impact test
Impact #
Impact zone Result
1 Center Satisfactory
2 Middle point of side Satisfactory
3 Diagonal 70 mm from pedestal Satisfactory
Soft body impact test
Impact #
Impact zone Result
1 Center Satisfactory
2 Middle point of side Satisfactory