page Level limit switch Series CN 8000 Technical Information / Instruction manual Table of contents Page Safety Notes / Technical support 2 ----------------------------------------------------------------------------------------------------- Introducion Applications / Function / Features 3 Profibus System Implementation 4 ----------------------------------------------------------------------------------------------------- Technical data CN 8100 Dimensions 5 Electrical data 9 Mechanical data 10 Operating conditions 11 Approvals 15 ----------------------------------------------------------------------------------------------------- Mounting 16 ----------------------------------------------------------------------------------------------------- Electrical installation 20 ----------------------------------------------------------------------------------------------------- Operation - Electronic module: Standard 24 ----------------------------------------------------------------------------------------------------- Operation - Electronic module: Digital 30 ----------------------------------------------------------------------------------------------------- Notes for use in Hazardous Locations 31 ----------------------------------------------------------------------------------------------------- Probe Modifications Shortening the cable (cable version) 38 Subject to technical change. We assume no liability for typing errors. All dimensions in mm (inch). Different variations than specified are possible. Please contact our technical consultants. 1 2 3 4 5 6 7 8 9 10 11 12 CN 8000 j gi150917 1 Capanivo ®

Upload: others

Post on 18-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Table of contents

Page

Safety Notes / Technical support 2----------------------------------------------------------------------------------------------------- Introducion Applications / Function / Features 3 ProfibusSystemImplementation 4-----------------------------------------------------------------------------------------------------

Technical data CN 8100

Dimensions 5 Electrical data 9 Mechanical data 10 Operating conditions 11 Approvals 15-----------------------------------------------------------------------------------------------------Mounting 16-----------------------------------------------------------------------------------------------------Electrical installation 20-----------------------------------------------------------------------------------------------------Operation-Electronicmodule:Standard 24-----------------------------------------------------------------------------------------------------Operation-Electronicmodule:Digital 30-----------------------------------------------------------------------------------------------------Notes for use in Hazardous Locations 31-----------------------------------------------------------------------------------------------------ProbeModifications Shorteningthecable(cableversion) 38

Subjecttotechnicalchange. Weassumenoliabilityfortypingerrors.

Alldimensionsinmm(inch). Differentvariationsthanspecifiedarepossible.Pleasecontactourtechnicalconsultants.

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 1

Capanivo®

Page 2: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Safety notes / Technical support

Notes

• Installation,maintenanceandcommissioningmaybeaccomplishedonlybyqualifiedtechnicalpersonnel.• Theproductmustbeusedonlyinthemanneroutlinedinthisinstructionmanual.• Thisproductisintendedforuseinindustrialareas.Operationofthisequipmentinaresidentialareamaycause interferencetoseveralfrequencybasedcommunications.

Specialattentionmustbepaidtowarningsandnotesasfollows:

WARNING

Relatestoacautionsymbolontheproduct:Afailuretoobservethenecessaryprecautionscanresultindeath,seriousinjuryand/orconsiderablematerialdamage.

WARNING

Relatestoacautionsymbolontheproduct:Riskofelectricshock

WARNING

Afailuretoobservethenecessaryprecautionscanresultindeath,seriousinjuryand/orconsiderablematerialdamage.

Thissymbolisused,whenthereisnocorrespondingcautionsymbolontheproduct.

CAUTION Afailuretoobservethenecessaryprecautionscanresultinconsiderablematerialdamage.

Safetysymbols

Inmanualandonproduct

Description

CAUTION:refertoaccompanyingdocuments(manual)fordetails.

Earth(ground)Terminal

ProtectiveConductorTerminal

Technical support

Pleasecontactyourlocalsupplier(foraddressseewww.uwt.de).Otherwiseyoucancontact:

UWTGmbH Tel.:0049(0)83157123-0Westendstr.5 Fax:0049(0)83176879D-87488Betzigau [email protected] www.uwt.de

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi1509172

Capanivo®

Page 3: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Introduction

Applications

CN8000isdesignedforleveldetectionandsimplepumpcontrolinavarietyofapplications: •Liquids,solids(powderandgranules),slurries,interfacedetection(forexample,oil/water),andfoamdetection •Foodsandpharmaceuticals •Chemicalandpetrochemical •Highpressureandtemperature

Function CN8000isaversatilecapacitanceswitch,idealforleveldetectionofinterfaces,solids,liquids,slurries,andfoam,andforsimplepumpcontrol.

Theswitchrespondstothepresenceofanymaterialwitharelativedielectricconstantof1.5ormorebydetectingachangeincapacitance,whichisregisteredasachangeinoscillatingfrequency.

Theswitchcanbesettodetectbeforecontactoroncontactwiththeprobe.ThedesignoftheCN8000allowstheinstrumenttooperateindependentlyofthetankwallorpipe,soitdoesnotrequireanexternalreferenceelectrodeforleveldetectioninanonconductivevesselsuchasconcreteorplastic.

Thepowersupplyisgalvanicallyisolated.

Thematerialsusedintheprobeconstructionprovideahighlevelofchemicalresistance,andanexcellenttemperatureratingontheprocesswettedportionoftheprobe:upto125°C(257°F).

CN8000isavailableintwomodels:thestandardmodel,andthedigitalmodelwithintegrallocaldisplay.

Features

•Pottedconstructionprotectscomponentsfromshock,vibration,humidity,and/orcondensation •Highchemicalresistanceonprobes •Leveldetectionindependentoftankwall/pipe •Freelyprogrammablesetupcoverswiderangeofapplications/materials •IntegratedLocalUserInterface(LUI)foreaseofuse •Rigidandcableversionsavailable •CommunicationviaPROFIBUSPA(profileversion3.0,ClassB) •IntrinsicallySafe(IS)transmitterdesignforhazardousareas(requiresexternalbarrierorISpowersupply)

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 3

Capanivo®

Page 4: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Introduction

CN8000supportsPROFIBUScommunicationprotocol,andSIMATICPDMsoftware.

Basic PLC configuration with PROFIBUS PA

Programming

CN8000carriesoutitslevelmeasurementfunctionaccordingtothesetofbuilt-inparameters.Youcanmakeparameterchangeslocallyviathelocaluserinterface,orfromaremotelocationviaaPCusingSIMATICPDMsoftware.

CN8000Digitalcanbeusedeither:

•asastandaloneunit,programmedlocallyusingtheLocalUserInterface,or •installedaspartofanetwork,programmedremotelyusingSIMATICPDMonProfibusPAnetwork(orlocally usingtheLocalUserInterface).

Alarm signalling

Thesolid-stateswitchcanbesettoreacteithertoadiagnosedfaultintheinstrument,ortoachangeintheprocesslevel. Fault Signalling

CN8000canactivelyreportinformationonitsownstatusviaPROFIBUSPAwhenusedaspartofanetwork,orbymeansofapre-definedoutputstatusatthesolidstateswitchandontheLocalUserInterface(LUI).

active PLC

PROFIBUSDP

PC/ laptop

DP/ PA coupler

PROFIBUSPA

CN 8000(PROFIBUSPA)

CN 8000 (PROFIBUSPA)

CN 8000 (PROFIBUSPA)

ProfibusPA-SystemImplementation

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi1509174

Capanivo®

PDM

Page 5: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Technical data - Dimensions

Enclosure

Temperaturextendedshaft

Temperaturextendedshaft

CN 8100Threaded process connection

CN 8100Flanged process connection

M20x1.5cablegland NPT 1/2" conduit CN 8100Top view

CN 8100Triclamp process connection

Temperaturextendedshaft

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 5

Capanivo®

Page 6: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Technical data - Dimensions

Threaded process connection

Detail "A"

L does not include any raisedface(seepage7)

CN 8100Short extension lenghtShortest length

CN 8100Cable version

Threaded process connection

Flanged process connection

CN 8100Pipe versionExtended

CN 8100Pipe versionExtended,withSlidingcoupling (pos.19)

Flanged process connection

Threaded process connection

probe(sensor)

probe(sensor)

Flanged process connection

pip

e

cableFEPinsulated

slid

ing

coup

ling

probe(sensor)

probe(sensor)

probe(sensor)

probe(sensor)

Triclampprocessconnection

Triclampprocessconnection

pip

e

pip

ep

ipe

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi1509176

Capanivo®

A

A

L=120mm(1.7")

L=98m

m(3.8")

84mm(3.3")

84mm(3.3")

84mm(3.3")

L L L

22mm

(0,87")

min.215mm(8.46")

ø20mm(0.79")

ø20mm(0.79")

ø6mm(0.3")

LL

A

L

L=98m

m(3.8")

ø20mm(0.79")

ø24mm(0.95")

Page 7: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Technical data - Dimensions

Flanges

Type Facing thickness

ASME150lbASME300lb

2mm(0.08")

ASME600lb 7mm(0.28")

Raised facefa

cing

thickness

CN 8100Remote version(pos.12a,b)

Remoteversionexemplifiedwithpipe version, threaded process connection

Mounting bracket1.4404(316L)

Remotecable:ø6mm(0.24")FEP isolationBothsideswired

Probe(sensor)

Code Type Number of holes

d2mm(inch)

Lkmm(inch)

Dmm(inch)

Tthicknessmm(inch)

ASMEB

16.5,raisedface

5A 1"150lbs 4 15.9(0.63) 79.3(3.12) 108.0(4.25) 14.3(0.56)

5B 1"300lbs 4 19.1(0.75) 88.9(3.5) 123.8(4.87) 17.5(0.69)

5C 1"600lbs 4 19.1(0.75) 88.9(3.5) 123.8(4.87) 17.5(0.69)

5D 11/2”150lbs 4 15.9(0.63) 98.6(3.88) 127.0(5.0) 17.5(0.69)

5E 11/2"300lbs 4 22.2(0.87) 114.3(4.5) 155.6(6.13) 20.6(0.81)

5F 11/2"600lbs 4 22.2(0.87) 114.3(4.5) 155.6(6.13) 22.4(0.88)

5G 2"150lbs 4 19.1(0.75) 120.7(4.75) 152.4(6.01) 19.1(0.75)

5H 2"300lbs 8 19.1(0.75) 127.0(5.0) 165.1(6.5) 22.2(0.87)

5J 2"600lbs 8 19.1(0.75) 127.0(5.0) 165.1(6.5) 25.4(1.0)

5K 3"150lbs 4 19.1(0.75) 152.4(6.01) 190.5(7.5) 23.9(0.94)

5L 3"300lbs 8 22.2(0.87) 168.2(6.62) 209.6(8.25) 28.6(1.13)

5M 3"600lbs 8 22.2(0.87) 168.2(6.62) 209.6(8.25) 31.7(1.25)

5N 4"150lbs 8 19.1(0.75) 190.5(7.5) 228.6(9.0) 23.9(0.94)

5P 4"300lbs 8 22.2(0.87) 200.0(7.87) 254.0(10.0) 31.7(1.25)

5Q 4"600lbs 8 25.4(1.0) 215.9(8.5) 273.1(10.75) 38.1(1.5)

EN1092-1typeA,flatfaced

6A DN25PN16 4 14.0(0.55) 85.0(3.35) 115.0(4.53) 18.0(0.71)

6B DN25PN40 4 14.0(0.55) 85.0(3.35) 115.0(4.53) 18.0(0.71)

6C DN40PN16 4 18.0(0.71) 110.0(4.33) 150.0(5.91) 18.0(0.71)

6D DN40PN40 4 18.0(0.71) 110.0(4.33) 150.0(5.91) 18.0(0.71)

6E DN50PN16 4 18.0(0.71) 125.0(4.92) 165.0(6.5) 18.0(0.71)

6F DN50PN40 4 18.0(0.71) 125.0(4.92) 165.0(6.5) 20.0(0.79)

6G DN80 PN16 8 18.0(0.71) 160.0(6.3) 200.0(7.87) 20.0(0.79)

6H DN80PN40 8 18.0(0.71) 160.0(6.3) 200.0(7.87) 24.0(0.94)

6J DN100 PN16 8 18.0(0.71) 180.0(7.09) 220.0(8.66) 20.0(0.79)

6K DN100PN40 8 22.0(0.87) 190.0(7.48) 235.0(9.25) 24.0(0.94)

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 7

Capanivo®

57mm(2.24")

30mm(1.18")

ø9.5mm(0.37")

Page 8: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Technical data - Electrical data

Performance

Repeatability Approx.±2mmforaconductivefluid

Power Supply 12to250VAC/DC(0to60Hz)

Exapprovals Max.voltagewhichdoesnotinvalidatetheintrinsicallysafeprotectionofthesensor(probe):Um=250VAC

Powerconsumption 2Wmax.

PerformanceRepeatability ±1%ofmeasurement

User InterfaceConfiguration Locally,usingdipswitchesandpotentiometers

Local display 3 LED indicators

Output Relaycontactandsolid-stateswitch

Polarity-independent Yes

Failsafe Relayandsolid-stateswitchcanbede-energizedintheabsenceofasensorsignal

Alarm Outputs Relay 1FormC(SPDT)contact(selectableNCorNOcontact)

max.switchingvoltage/current(DC):30VDC/5Amax.switchingvoltage/current(AC):250VAC/8A(resistiveload)

Solid-stateswitch Rated30VDCorpeak30VAC,82mA

Timedelay ON/OFFalarm,durationselectable1to42seconds/1to100seconds

Hysteresis DependentonDK:max.2mm(0.08”)@DK=1.5

Failsafe operation FailsafeHighorFailsafeLow

Delaytimers 2:AlarmONtoOFFandAlarmOFFtoON

Electronicmodule:Standard(RelaySPDT/SolidState)

Electronicmodule:Digital (ProfibusPA/SolidState)

Power

Busvoltage - General purpose - Intrinsically Safe

12to30VDC,12.5mA 12to24VDC,12.5mA,FISCOFieldDeviceIntrinsicallysafebarrierrequiredforATEX:Ui=24VIi=380mAPi=5.32WCi=5nFLi = 10uHforFM/CSA:seepage23

Exapprovals(Flameproof,Dustignitionproof)

Max.voltagewhichdoesnotinvalidatetheintrinsicallysafeprotectionofthesensor(probe):Um=250VAC

Starting current < current of normaloperation

Yes

Fault current 0mA(max.uninterruptedcurrentminuscurrentofnormaloperation)

Faultdisconnectequipment(FDE) Yes

Auxiliarysource Buspowered

Separate supply necessary No

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi1509178

Capanivo®

Page 9: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Technical data - Electrical data

User Interface

Configuration Locally,usinglocaluserinterface(LUI),forstandaloneoperation,orRemotely,usingSIMATICPDMonaProfibusPAnetwork

Local Digital Display LCD

Output (bus) PROFIBUSPA(IEC61158CPF3CP3/2)Busphysicallayer:IEC61158-2MBP(-IS)

Polarity-independent yes

Simultaneouscommunicationwith Master Class 2

4(max.)

Cyclic User data (normal operation) Byteoutput 2bytesrepresentingonevalue

Byteinput 0

Deviceprofile PROFIBUSPAProfileforProcessControlDevicesVersion3.0,ClassB

Functionblocks 1

Discrete input 1

Logical inversion Parameterizable

Simulation functions Output

yes

Input yes

Failsafe Parameterizable(lastusablevalue,substitutevalue,erroneousvalue)

Block Structure Physicalblock 1

Transducerblock 1

Transducerblockdiscreteinput Yes

Monitoringmeasuringlimits Yes

Signal Output Solid-stateswitch Galvanically isolated, non-polarity sensitive transistor

Rated30VDCorpeakACmax.,82mAmaxVoltagedropbelow1Vtypical@50mA WithIntrinsicallysafe:barrierrequiredforATEX:Ui=30VIi=200mAPi=350mWCi=0 L i = 0forFM/CSA:seepage23

Timedelay Controlledbysoftware 2delaytimers:alarmONdelayandalarmOFFdelay)

Hysteresis 100%adjustable

Failsafe operation FailsafeHighorFailsafeLow

Terminal Removableterminalblock,2.5mm2max.

Diagnostics Input Reedcontact:fortestfunction

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 9

Capanivo®

Page 10: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Probe

Weight Weightvariesbasedonconfiguration.Forexample:

•compact,100mm(4”)insertionlength, ¾” process connection

1kg(2.20lb.)approx.

Technical data - Mechanical data

Model Length(max)

ProcessConnections

Extension Tensile(max)

Wetted Parts

Pipe 5,500mm/216.5”

•Threaded:¾”1"11/2"BSPT(R),BSPP(G) ¾” 1" 1 ¼” 1 1/2" NPT

•Weldedflange:ASME1”11/2”2”3”4”DN25405080100

•Triclamp:1"11/2"2"21/2"3"ISO2852

1.4404(316L) n/a •1.4404(316L) optional PFA coating•FKMsealsoptionalFFKM•PPSprobeoptionalPVDF

Cable 30,000mm/1,181.1”

•Threaded:¾”1"11/2"BSPT(R),BSPP(G) ¾” 1" 1 ¼” 1 1/2" NPT

•Weldedflange:ASME:1”11/2”2”3”4”DN25405080100

FEP(FluorinatedEthylenePolymer)

180kg/400lbs

•1.4404(316L)•FEPjacketedcable•FKMsealsoptionalFFKM•PPSprobeoptionalPVDF

EnclosureTermination Removableterminalblock

Tighteningtorqueofterminalscrews:0.5to0.6Nm

Conductorcrosssection:

1 conductor-solid:0.2to2.5mm²-flexible:0.2to2.5mm²-flexible,withferrulewithorwithoutplasticsleeve:0.25to2.5mm²-AWG24to12

2conductorswithsamecrosssection-solid:0.2to1.0mm²-stranded:0.2to1.5mm²-stranded,withferrulewithoutplasticsleeve:0.25to1.0mm²-stranded,TWINferrulewithplasticsleeve:0.5to1.0mm²

Construction Powder-coatedaluminumwithgasket

Optionalthermalisolator 1.4404(316L)stainlesssteel

Cableentry 2xM20thread,option:2x1/2”NPTthreadwithadaptor

WithATEXapproval:-Default:2xM20x1.5-WithselectionofoptionPos.33a:2xNPT1/2"taperedANSIB1.20.1

Ingress protection Type4/IP65orIP68(dependingonCableEntryoption)

Note:Theuseofapprovedwatertightconduithubs/glandsisrequiredforType4/IP65orIP68(outdoorapplications).

SeparationbetweenZone0andZone1(ATEXII1/2G)

Materialoftheseparationelement(partitionwall)-Stainlesssteel,1.4404(316L)-Glass,Inconel600(Glassseal)

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091710

Capanivo®

Page 11: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Technical data - Operating conditions

Process

Relative dielectric constant 1.5minimum

Temperatureatprocessconnection Withouttemperatureextendedshaft: –40to85°C(–40to185°F)-20to85°C(-4to+185°F)withoptionFFKMsealO-ringWithtemperatureextendedshaft:–40to125°C(–40to257°F)-20to125°C(-4to+257°F)withoptionFFKMsealO-ring

WithATEXapproval:DependingonSurfaceTemperatureandTemperatureClass,detailsseepage36/37.

Pressure(vessel): - pipe version -cableversion/triclampversion - sliding coupling version

–1to25barg/–14.6to365psig(nominal) –1to10barg/–14.6to150psig(nominal) –1to10barg/–14.6to150psig(nominal)

Note:pleaseseePressureversusTemperatureCurvesonnextpages.

Environmental Location Indoor/outdoor

Altitude 2.000m(6.562ft.)max.

Ambienttemperature –40to85°C(–40to185°F)

WithATEXapproval:DependingonSurfaceTemperatureandTemperatureClass,detailsseepage36/37.

LUI(localuserinterface) –30to85°C(–22to185°F)

Storagetemperature –40to85°C(–40to185°F)

Relativehumidity Suitableforoutdoor

Installation category II(Electronicmodule:Standard)I(Electronicmodule:Digital)

Pollution degree 4

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 11

Capanivo®

Page 12: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Technical data - Operating conditions

PressureversusTemperatureCurves

Shortestlengthandextendedpipe,threaded

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

Shortestlengthandextendedpipe,ASMEweldedflange

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091712

Capanivo®

Page 13: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Technical data - Operating conditions

1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.

Shortestlengthandextendedpipe,ENweldedflange

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

Triclamp

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 13

Capanivo®

Page 14: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Cable,ASMEweldedflange

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

Cable,ENweldedflange

P=permittedoperatingpressure T=permittedoperatingtemperature

1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.

Technical data - Operating conditions

atmosheric

Cable,threaded

P=permittedoperatingpressure T=permittedoperatingtemperature

atmosheric

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091714

Capanivo®

Page 15: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Approvals

Note:EN61326(CEEMC)testingwasconductedwhilemountedinametallicvesselandwiredusingshieldedcable,wherethecablewasterminatedinanEMCcableglandatthedeviceentrypoint.Inaddition,unitswithaflangeprocessconnectionweremountedusingametallicgasket.

1 BarrierorIntrinsicallySafepowersupplyrequiredforIntrinsicallySafeprotection

Electronicmodule:Digital (ProfibusPA/SolidState)

General Purpose CE, CSA, FM, TR-CU

Dust Ignition Proof ATEX II 1/2D, IIICCSA/FMClassII,Div.1,Gr.E,F,GClassIIITR-CUINMETRO

FlameProof/ExplosionProof ATEX II 1/2G, IIC CSA/FMClassI,Div.1,Gr.A,B,C,DTR-CUINMETROKC

Intrinsically Safe 1 ATEX II 1G, IICATEX II 1/2D, IIICCSA/FMClassI,Div.1,Gr.A,B,C,DTR-CU

Type of protection nNon-incendive

ATEX II 3G, IICCSA/FMClassI,Div.2,Gr.A,B,C,D

Electronicmodule:Standard(RelaySPDT/SolidState)

General Purpose CE, CSA, FM, TR-CU

Dust Ignition Proof ATEX II 1/2D, IIICCSA/FMClassII,Div.1,Gr.E,F,GClassIII TR-CUINMETRO

FlameProof/ExplosionProof ATEX II 1/2G, IIC CSA/FMClassI,Div.1,Gr.A,B,C,DTR-CUINMETROKC

Marine LloydsRegisterofShipping,CategoriesENV1,ENV2andENV5

OverfillProtection WHG

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 15

Capanivo®

Page 16: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Mounting

•Installationshallonlybeperformedbyqualifiedpersonnelandinaccordancewithlocalgoverningregulations.•Thisproductissusceptibletoelectrostaticshock.Followpropergroundingprocedures.•Thehousingmayonlybeopenedformaintenance,localoperation,orelectricalinstallation.•Beforeinstallingtheinstrument,verifythattheenvironmentcomplieswithanyrestrictionsspecifiedontheproductnameplate.•TocomplywithCEEMCregulations,whereapplicable,theCN8000shouldbeinstalledinaccordancewiththetestingdetailsonpage15.

Handling Precautions

WARNING:Topreventdamage,allunitswithapipelongerthan2m(6.5ft)mustbehandledasdescribedbelow.

WhenliftingCN8000fromahorizontalposition,supportitatthesethreepoints:

At the end of the pipebeforethesensor

Midwayalongthe pipe

At the processconnection or flange

Oncevertical,CN8000maybeheldbytheprocessconnectionorflange:

At the processconnection or flangeNote:

Unitshownwithextendedpipeversion.Handlingprecautionsapplytoallunitswithpipeslongerthan2m(6.5ft).

General Safety Instructions

Additional Safety Instructions for Hazardous Locations

see page 31ff

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091716

Capanivo®

Page 17: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Mounting

Location

Recommended:•Provideasunshieldtoprotectthetransmitterfromdirectheatradiation.

Precautions:•AvoidmountingCN8000inlocationssubjecttostrongvibrationsinthevicinity,wheneverpossible.•Donotexceedthepermissibleambienttemperaturelimits(seeEnvironmentalonpage11fordetails).

MountingCompact probe

Highlevelalarm Lowlevelalarm

Forhighlevelalarm(levelexceedsnormalprocesslevel): •normallymountedintothevesseltop,or •mountedthroughthetankwallatthedetectionlevel

Forlowlevelalarm(leveldropsbelownormalprocesslevel): •mountedthroughthetankwallatthedetectionlevel

Typical configuration with extensions

Forhighorlowlevelalarm: •designedfortopmounting.Theprobesuspendsverticallysothatitreachesintotheprocessatthedesired detectionlevel(highorlowdetectionalarm).

Highlevelalarm Lowlevelalarm

Angle

normalprocesslevel

normalprocesslevel

normalprocesslevel

normalprocesslevel

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 17

Capanivo®

Page 18: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Mounting

Mounting Restrictions

•Keepthesensoratleast50mm(2")awayfromanynozzleortankwall.•Ifmultipleunitsareused,allowatleast100mm(4")betweenthem,topreventinterference.

In nozzle Close to tank walls

Multiple Units

SideView EndView

Sensorsmustbeatleast100mm(4")apart.

Mount diagonally if space is restricted

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091718

Capanivo®

50mm(2") min

50mm (2") min

50mm(2")min

100mm (4")min

100mm (4")min

100mm (4")min

Page 19: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Mounting

Process Cautions for solids

•Themaximumallowabletorqueonahorizontallyinstalledpipeis15Nm.•Keepunitoutofpathoffallingmaterial,orprotectprobefromfallingmaterial.

Considermaterialsurfaceconfigurationwheninstallingunit.

Tensileloadmustnotexceedprobeorvesselrating(seeTensile(max)onpage10). 

Avoidareaswherematerialbuildupoccurs.

In Hazardous Locations: Observe Specifc condition of use for electrostatic charge (see page 34)

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 19

Capanivo®

50mm (2")min

Page 20: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Electrical installation

WARNING: •Observethespecificationsoftheexaminationcertificatevalidinyourcountry. •Observethelawsandregulationsvalidinyourcountryforelectricalinstallationsinpotentiallyexplosive atmospheres. •RefertoHazardousAreaInstallationonpage31ifapplicable. •Ensurethattheavailablepowersupplycomplieswiththepowersupplyspecifiedontheproductnameplate andspecifiedintheexaminationcertificatevalidinyourcountry. •Shippingplugsinthecableinletsmustbereplacedbysuitablescrewtypeglandsordummyplugs,whichare appropriatelycertifiedfortransmitterswithexplosion-proofprotection. •ForCEinstallations,useacablewithabraidedmetallicshield(orarmouredcablewhereapplicable). •Thelidmustnotbeopenedinwetlocationswhiletheunitispowered.(Awetlocationisalocationwhere wateroranotherconductivefluidmaybepresentandislikelytoincreasetheriskofelectricshock.) •Cableentrydevicesandclosingelementsofunusedaperturesmustmeetatemperaturerangefrom min.-40°Cto10Kabovemax.ambienttemperature.

Notes: •LayPROFIBUSPAcableseparatelyfrompowercablewithvoltagesgreaterthan60V. •Avoidlocatingtheunitnearlargeelectricalequipmentwhereverpossible. •Connectthecableshieldtoearth(forexample,tothehousingbymeansofametallicscrewedgland).

WARNING: •Allfieldwiringmusthaveinsulationsuitableforatleast250V. •Onlyqualifiedpersonnelareauthorizedtoinstallandoperatethisequipmentinaccordancewithestablished safetypracticesandstandards.

•TheProtectiveEarthTerminalindicatedby mustbeconnectedtoreliableground.Usecrimptypecable socketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234). Incaseofnon-metallicvessels,theexternalearthwireshouldbeconnectedtoanearthedcomponent whichisearthednearthevessel. •Allwiringmustbedonebyqualifiedpersonnelinaccordancewithallgoverningregulations. •Theequipmentmustbeprotectedbya16Afuseorcircuitbreakerinthebuildinginstallation. •Acircuitbreakerorswitchinthebuildinginstallation,markedasadisconnectswitch,shallbeinclose proximitytotheequipmentandwithineasyreachoftheoperator. •Useshieldedcable,wiregauge20AWGto14AWG(0.5mm2to2.0mm2).ForCEinstallationsuseacable withabraidedmetallicshield(orarmouredcablewhereapplicable). •Maximumworkingvoltagebetweenadjacentrelaycontactsis250V. •Relaycontactterminalsareforusewithequipmentwhichhasnoaccessiblelivepartsandwiringwhichhas insulationsuitableforatleast250V. •Cableentrydevicesandclosingelementsofunusedaperturesmustmeetatemperaturerangefrom min.-40°Cto10Kabovemax.ambienttemperature.

Additional Safety Instructions for Hazardous Locationssee page 31ff

General Safety Instructions

Electronicmodule:Standard(RelaySPDT/SolidState)

Electronicmodule:Digital (ProfibusPA/SolidState)

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091720

Capanivo®

Page 21: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Electrical installation

Electronicmodule:Standard(RelaySPDT/SolidState)

Note:Switchandpotentiometersettingsareforillustrationpurposesonly.

red

black

white

Connectprotectiveearthwiretoterminalprovidedinhousingandmarkedwith

Usecrimptypecablesocketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234).

1.Loosenthelidclipandremovethelidtoaccesstheconnectorsandelectronics.2.Connectthewirestotheterminals3.Groundtheinstrumentaccordingtolocalregulations.4.Tightentheglandtoformagoodseal.

Power supply:

12to250VAC/DC(0to60Hz) 2Wmax.

Signal output:

Relay:Floating relay SPDTACmax.250V,8A,2000VA,noninductiveDCmax.30V,5A,150W,noninductive

Solidstateswitch:30VDCor30VAC(peak),82mAObserveprotection(seebelow)

Powersupply

Relay

internal wiring

Solidstateswitch(polaritynotimportant)

Protection diode

ObserveaProtectiondiodeincaseofconnectinganexternalrelaytotheSolidstateswitch

Protection of Solid State Switch

Solid state switch

internal wiring

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 21

Capanivo®

Page 22: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Electrical installation

1.Loosenthelidclipandunscrewthelidoftheenclosure.2.Unscrewandliftupthedigitaldisplay(looseneachscrewtwoturnsbeforecompletelylooseningboth,tokeeptherubberretainingringsinplace.)3.Connectthewirestotheterminals4.Groundtheinstrumentaccordingtolocalregulations.5.Tightenthecableglandtoformagoodseal.6.Fixthedigitaldisplay.7.Toadjustthetransmitterlocally,usingthekeypad,gotoProgrammingviatheLocalUserInterface(LUI).Afteradjustment,replacetheenclosurelidandtightenthelidclip.

PowersupplyorProfibusPA

Solid state switch

Digital display

Electronicmodule:Digital (ProfibusPA/SolidState)

PowersupplyorProfibusPA*(polaritynotimportant)

internal wiring

Solidstateswitch(polaritynotimportant)

internal wiring

blue

blue

red

black

white

Protection diode

ObserveaProtectiondiodeincaseofconnectinganexternalrelaytotheSolidstateswitch

Protection of Solid State Switch:

Solid state switch

*WithuseofProfibusPAthewiringmustbeaccordingtoProfibusPAstandards.IfProfibusPAisnotused,ashieldedcableisrecommendedtoensurestablemeasurement.

Power supply:

12..30VDC,12.5mA

IntrinsicallySafe:12..24VDC,12.5mA

Intrinsicallysafebarrierrequired

ForATEX:Ui=24V,Ii=380mA,Pi=5.32W,Ci=5nF,Li=10 uH

ForFM/CSA:See"Connectiondrawingonpage23"

Signal output:

Solidstateswitch:30VDCor30VAC(peak),82mAObserveprotection(seebelow)

Intrinsicallysafe:Intrinsicallysafebarrierrequired

ForATEX:Ui=30V,Ii=200mA,Pi=350mW,Ci=0, Li=0

ForFM/CSA:See"Connectiondrawingonpage23"

Connecting the electronic module:

Connectprotectiveearthwiretoterminalprovidedinhousingandmarkedwith

Usecrimptypecablesocketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234).

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091722

Capanivo®

Page 23: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Electrical installation

FM/CSAapprovalConnectiondrawing

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 23

Capanivo®

Pro

du

ct

Gro

up

FO

R IN

TE

RN

AL

US

E O

NLY

Poin

t Level S

ensors

RF

80

00

/ C

N 8

00

0 u

nit

Enclo

surePA– PA+

so

lid s

tate

ou

tpu

t

Alarm OutputSolid State Switch

No

te 3

No

te1

& 2

No

te1

& 2

Com

munic

ation I/O

Com

munic

ation I/O

Insta

llatio

n m

ust

in a

cco

rda

nce

with

th

e N

atio

na

l E

lectr

ica

l C

od

e (

R)

(NF

PA

70

,A

rtic

le 5

04

) a

nd

AN

SI/

ISA

-RP

12

.06

.01

Hazard

ous (

Cla

ssifie

d)

Location

Uncla

ssifie

d L

ocation

IS C

LA

SS

I,

II,

III,

DIV

.1 G

RO

UP

SA

, B

, C

, D

, E

, F

& G

T6

...T

4

XP

CL

AS

S I

, D

IV.

1 G

RO

UP

SA

, B

, C

& D

T4

CL

AS

S I

, D

IV.

2 G

RO

UP

SA

, B

, C

& D

T4

CL

AS

S I

I, I

II,

DIV

. 1

GR

OU

PS

E,

F &

GT

4

Te

mp

era

ture

Cla

ss

T4

fo

r–

40

°C≤

am

bie

nt

tem

pe

ratu

re≤

+8

5°C

En

tity

Pa

ram

ete

r

GR

OU

PS

A

, B

, C

, D

, E

, F,

G;

IIC

GR

OU

PS

C

, D

, E

, F,

G;

IIB

Cu

rren

t Lo

op

Ou

tpu

t

Cu

rren

t Lo

op

Ou

tpu

tS

olid

Sta

te

Ou

tpu

t

So

lid S

tate

Ou

tpu

t

Ui (V

max)

24

V2

4 V

30

V3

0 V

Ii (

imax)

38

0 m

A3

80

mA

11

0 m

A2

00

mA

Pi

5.3

2 W

5.3

2 W

82

5 m

W1

.5 W

Ci

5 n

F5

nF

00

Li

10

µH

10

µH

00

NO

TE

S:

1)

Fie

ldbus input: s

pecifie

d to the fis

co m

odel

2)

Manufa

ctu

re’s

insta

llation instr

uctions m

ust be follo

wed for

insta

llation o

fA

ssocia

ted Intr

insic

ally

Safe

Appara

tus

3)

Either

one o

r both

wire p

airs b

etw

een

Associa

ted Intr

insic

ally

Safe

Appara

tus m

ust be

gro

unded s

cre

ened o

r shie

lded w

ires.

4)

For

FM

: In

sta

llation m

ust be in a

ccord

ance w

ith

AN

SI / IS

A12.0

6.0

1 a

nd the N

ational E

lectr

ical C

ode (

AN

SI / N

FP

A70)

5)

For

CS

A: In

sta

llation m

ust be in a

ccord

ance w

ith a

pplic

able

section o

f C

anadia

n E

lectr

ical C

ode (

CE

C)

6)

For

Div

isio

n 2

insta

llation, associa

ted a

ppara

tus is n

ot re

quired, in

sta

llation m

ust be in a

ccord

ance

with D

ivis

ion 2

wirin

g m

eth

ods a

nd s

upply

voltage m

ust not exceed 3

0 V

olts

7)

Dust-

tight seals

must be u

sed for

Cla

ss II and III insta

llations

8)

The

transm

itte

r is

appro

ved for

Cla

ss I, Z

one 0

applic

ations if connecting to

AE

x[ia] ra

ted

RF

8000 / C

N 8

000

Associa

ted Intr

insic

ally

Safe

Appara

tus.

The tra

nsm

itte

r is

suitable

only

for

Cla

ss I, Z

one 1

or

Zone 2

, and n

ot

suitable

for

Cla

ss 1

, Z

one 0

or

Cla

ss, D

ivis

ion 1

applic

ations

9)

For

FM

the u

nit m

ust be insta

lled u

sin

g F

MA

ppro

ved

Appara

tus

Exte

rna

l fr

am

e e

art

h t

erm

ina

l

Temperatureclass:

T4for–40°C<=ambienttem

perature<=+85°C

T6for–40°C<=ambienttem

perature<=+40°C

Page 24: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Operation - Electronic module: Standard

Settings

S1:Delay(coveredtouncovered)

S3:FailsafeHigh/LowS4:Test

P1

P2

switchpointDIPswitches

L2 red

delay

Usethedelayfunctiontoslowthesignaloutputresponse,andcompensateforturbulenceorfalsereadings.

S1 / S2: Signal output delay

S3: Failsafe High / Low

Failsafe Mode S3

Failsafe High

FailsafeLow*

relay switch relay switch

relay switch relay switch

*Factorysetting

*Factorysetting

S2:Delay(uncoveredtocovered)

S1

S2

Delay active*

Delay off

Delay active*

Delay off

Signaloutputdelay:Sensor covered to uncovered

Signaloutputdelay:Sensor uncovered to covered

Delaytime/seconds

DIPswitches

L3 green

L1 yellow

*Factorysetting

LEDsL1:Sensorstatus(yellow)ONifsensorisdetectedascovered(capacitanceonsensorisgreaterthansettedswitchpoint)L2:Signaloutput(red) ONifRelayisactivated/Solidstateswitchisclosed.L3:Powersupply(green)ONifpowerispresent

S5:Set-upmode/runmode

Delaytime/seconds

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091724

Capanivo®

1 2 3 4 5

1*

P1

12

2540 60

80

100

1*

7

1421 28

35

42

P1

Page 25: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Operation - Electronic module: Standard

Allowstotestthesettedsignaloutputdelaytimewithouttheneedtochangethesensorfromcoveredtouncoveredorfromuncoveredtocovered.

S4 Normaloperation*

S4 Testmode If sensor is uncovered:SettingS4toTestmodesimulatesacoveredprobe.Afterthesetteddelaytime"Sensoruncoveredtocovered"(seeDIPswitchS2)haspassed,thesignaloutputandLED2(red)areswitching.

If sensor is covered:SettingS4toTestmodesimulatesauncoveredprobe.Afterthesetteddelaytime"Sensorcoveredtouncovered"(seeDIPswitchS1)haspassed,thesignaloutputandLED2(red)areswitching.

S4: Test

*Factorysetting

*Factorysetting

S5: Set-up mode / run mode

S5 Runmode* Normaloperationafterswitchpointadjustmentiscomplete.

S5 Set-upmode Usethissettingonlyduringswitchpointadjustment.

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 25

Capanivo®

Page 26: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Operation - Electronic module: Standard

Switchpoint Adjustment

Application Material Adjustment conditions

General • Dry solids•Lowviscosityliquids

Sensor uncovered

Demanding •Hygroscopic/wetsolids•Highviscosityandhighconductivityliquids

Sensorimmersedandthenuncovered,retainingmax.possiblematerialbuildup

Interfacedetection

•IgnoringliquidA/detectingliquidB•Ignoringfoam/detectingliquid

ImmersesensorinliquidAorfoam

General applications

1. Ensure material level is well below the probe

Theunitwillcalibratetoanuncoveredprobe.

2. Set to Set-up mode SetdipswitchS5toSet-upmode

3. Adjust switchpoint with poti P2

IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.

TurnP2clockwiseuntilL1juststopsglowing.

4. Set to Run mode SetdipswitchS5toRunmode

Switchpoint adjustment is finished

Selecttheswitchpointadjustmentaccordingtotheapplicationasfollows:

P2L1

yellow

S5

S5

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091726

Capanivo®

Page 27: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Operation - Electronic module: Standard

Demandingapplications

1. Ensure material level is well above the probe.

Incaseoftopmountingwithcableextensionthevesselshouldbefilledup.

2. Ensure material level is well below the probe

Itisimportantthatasmuchmaterialbuildupaspossibleisretainingonthesensor.

3. Set to Set-up mode SetdipswitchS5toSet-upmode

4. Adjust switchpoint with poti P2

IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.

TurnP2clockwiseuntilL1juststopsglowing.

5. Set to Run mode SetdipswitchS5toRunmode

Switchpoint adjustment is finished

S5

P2L1

yellow

S5

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 27

Capanivo®

Page 28: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Operation - Electronic module: Standard

Interface detection

LiquidAorfoam

LiquidB

LiquidAorfoam

LiquidB

L1 yellow

1. Immerse probe in liquid A or in foam which should NOT be detected

EnsurethatliquidAorfoam(whichshouldNOTbedetected)iscoveringtheprobe.

LiquidAorfoammusthavealower dielectric constantthanliquidB,whichshouldbedetected.

2. Set to Set-up mode SetdipswitchS5toSet-upmode

3. Adjust switchpoint with poti P2

IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.

TurnP2clockwiseuntilL1juststopsglowing.

Note:ThesensitivityisnowsettedthusthatliquidAorfoamisNOTdetected.

4. Set to Run mode SetdipswitchS5toRunmode

5. Immerse probe in liquid B which should be detected

EnsurethatliquidB(whichshouldbedetected)iscoveringtheprobe.

L1shouldglow.

Switchpoint adjustment is finished

S5

P2L1

yellow

S5

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091728

Capanivo®

Page 29: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Symptom Observation ActionNoAlarmResponse L3(green)off. Checkpowersupplyvoltage.

Alarmdoesn'tswitchwhensensorisuncovered.

L1(yellow)doesn'trespondwhensensorisuncovered.

ReadjusttrippointpotentiometerP2.

L1(yellow)respondswhensensorisuncovered.

CheckthatrelaychangesstatewhenS3istoggledONandOFF.

Alarmdoesn'tswitchonwhensensoriscovered.

L1(yellow)doesn'trespondwhensensoriscovered.

ReadjusttrippointpotentiometerP2.

L1(yellow)respondswhensensoriscovered.

CheckthatrelaychangesstatewhenS3istoggledONandOFF.

L1(yellow)flasheswhenmateriallevelapproachesthealarmsetpoint.

Operation - Electronic module: Standard

Troubleshooting

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 29

Capanivo®

Page 30: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Operation - Electronic module: Digital

Seeseparate"OperatingManual(DigitalElectronic)"

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091730

Capanivo®

Page 31: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Notes for use in Hazardous Locations

Use of this Manual

Foruseandassembly,refertotheinstructionsinthisManual.ItdoescontainallinstructionasrequiredbyATEXDirective2014_34_EU,AnnexII,1/0/6andOrdinanceINMETROnº179/2010

General notesRefertoappropriatecertificateforapplicationinspecifichazardousenvironment.

Theequipmenthasnotbeenassessedasasafetyrelateddevice(asreferredtobyDirective2014_34_EUAnnexII,clause1.5).

Thecertificatenumbershavean'X'suffix,whichindicatesthatspecificconditionofuseapply.Thoseinstallingorinspectingthisequipmentmusthaveaccesstothecertificates.

Qualificationofpersonnel/Servicing/Repair

Installationandinspectionofthisequipmentshallbecarriedoutbysuitablytrainedpersonnelinaccordancewiththeapplicablecodeofpractice(ABNTNBRIEC/EN60079-14andABNT/NBRIEC/EN60079-17inEurope).

Repairofthisequipmentshallbecarriedoutbysuitablytrainedpersonnelinaccordancewiththeapplicablecodeofpractice(e.g.ABNTNBRIEC/EN60079-19withinEurope).

Repairofflameproofpathisnotintended. Componentstobeincorporatedintoorusedasreplacementsintheequipmentshallbefittedbysuitablytrainedpersonnelinaccordancewiththemanufacturer'sdocumentation.

InpotentiallyexplosiveatmospheresopentheenclosureonlywhenCN8000isnotenergized.Turnoffpowerbeforeservicinganydevice(thetransmitterisinoperationwhenthepowersupplyisswitchedon).Incaseofremovingtheunitfromvessel,takecareofprocesspressureandmaterialpassingtheopening.

ATEX:Certificates/ListofStandards

Certificatenumbers:DEKRA18ATEX0042XandDEKRA18ATEX0044X

Seewww.uwt.deforthelatestcertificates

SeeEU-DeclarationofconformityforthelistofstandardsvalidforATEXcertificates

ATEX:Yearofmanufacturing

MarkingonthenameplateisdoneaccordingtoIEC60062asfollows:

Yearofmanufacturing 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029

Markingcode K L M N P R S T U V W X

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 31

Capanivo®

Page 32: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Notes for use in Hazardous Locations

ATEX:Ex-Marking

•DeviceswithATEXapprovalaremarkedonthenameplateasfollows.•IfbothFlameproofandDustignitionproofarepresentonthesamenameplate,atickbox ispresentwheretheenduserneedstoselect(mark)theprotectionmethodusedatthetimeofinstallation.

Dust Ignition Proof withintrinsicallysafeoutputtoprobe(TypecodePos.2W)Electronicmodule:StandardandDigital

Integralversion: II1/2DExia/tb[iaDa]IIICTXDa/Db

Remoteversion: Electronicsenclosure: II2(1)DExiatb[iaDa]IIICTXDb

Levelprobe: II1DExiaIIICTXDa

II1/2DExiaIIICTXDa/Db

Flameproof / Dust Ignition proof withintrinsicallysafeoutputtoprobe(TypecodePos.2T)Electronicmodule:StandardandDigital

Integralversion: II1/2GExia/db[iaGa]IICTXGa/Gb

II1/2DExia/tb[iaDa]IIICTXDa/Db

Remoteversion: Electronicsenclosure: II2(1)GExdbia[iaGa]IICTXGb

II2(1)DExiatb[iaDa]IIICTXDb

Levelprobe: II1GExiaIICTXGa

II1DExiaIIICTXDa

II1/2DExiaIIICTXDa/Db

Intrinsically Safe (TypecodePos.2Y)Elektronicmodule:Digital

Integralversion: II1GExiaIICTXGa

II1/2DExiaIIICTXDa/Db

Remoteversion: Electronicsenclosure: II1GExiaIICTXGa

II2DExiaIIICTXDb

Levelprobe: II1GExiaIICTXGa

II1DExiaIIICTXDa

II1/2DExiaIIICTXDa/Db

Type of protection n(TypecodePos.2G)Elektronicmodule:Digital

Integralversion: II3GExicnAIICTXGc

Remoteversion: Electronicsenclosure: II3GExicnAIICTXGc

Levelprobe: II3GExicIICTXGc

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091732

Capanivo®

Page 33: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

ATEX:Permittedzonesforinstallation

Ambientside

Process side

Shortest lengthandpipeextension

Sliding coupling

Cableversion

Dust applications Gas applications

Marking Da/Db Ga/Gb Ga Gc

EPL Db Gb Ga GcCategory 2D 2G 1G 3GZone 21 1 0 2

EPL Da Ga Ga Gc

Category 1D 1G 1G 3GZone 20 0 0 2

Notes for use in Hazardous Locations

Integral versionDevicescanbeinstalledasfollows:

Dust applications Gas applications

Markingelectronics enclosure

Db Db Ga Gb

EPL Db Db Ga GbCategory 2D 2D 1G 2GZone 21 21 0 1Markingsensorprobe

Da/Db Da Ga Ga

EPL Db Da Ga GaCategory 2D 1D 1G 1GZone 21 20 0 0

EPL Da Da Ga Ga

Category 1D 1D 1G 1GZone 20 20 0 0

Remote versionDevicescanbeinstalledasfollows:

Ambientside

Process side

Remoteversionelectronics enclsoure

Remoteversionsensorprobe

shownexamplarywithrod

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 33

Capanivo®

Page 34: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Specificconditionofuse

Notes for use in Hazardous Locations

Max. permitted temperature close to the enclosure

Iftheprocesstemperatureexceedsthemax.permissibleambienttemperature,themax.resultingtemperatureattheconnectionofthesensorhead(seedottedline)shallnotexceedtherelatedmax.permissibleambienttemperature(seepage36/37),takingtheworstcaseconditionsintoaccount.Thisshallbeverifiedbymeasurementwheninstalled.

process side

temperatureextendedshaft

Electrostatic charge

Theusershallensurethattheequipmentisnotinstalledinalocationwhereitmaybesubjectedtoexternalconditionswhichmightcauseabuild-upofelectrostaticchargeonnon-conductingsurfaces.

Impact / Friction Becausetheenclosureandoptionallytheprocessconnectionoftheequipmentismadeofaluminiumalloy,theapparatusmustbeinstalledso,thatevenintheeventofrareincidents,anignitionsourceduetoimpactorfrictionbetweenenclosureandiron/steelisexcluded,whenusedinpotentiallyexplosiveatmosphererequiringapparatusofequipment1G.

Flameproof joints

Theflameproofjointsarenotintendedtoberepaired.

Transient limitation for Type of protection n

Atransientprotectiondeviceshallbeused,setatalevelnotexceeding140%ofthepeakratedvoltgaeof85V.

Ambient and process temperature range

Therelationbetweentheambientandprocesstemperaturerangesandthesurfacetemperatureortemperatureclassisshowninthethermaldatatablespage36/37.

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091734

Capanivo®

Page 35: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Notes for use in Hazardous Locations

Intrinsically safe supply

Forintrinsicallysafemodels,powermustbesuppliedfromanIntrinsicallySafepowersource,otherwiseprotectionisnolongerguaranteed.

Process pressure Thedeviceconstructionallowsprocessover-pressureupto10or25bar(146or365psi).Thispressureisallowedfortestpurposes.ThedefinitionoftheExapprovalsareonlyvalidforacontainer-over-pressurebetween-0.2..+0.1bar(-2.9..+1.45psi).Forhigherorlowerpressurestheapprovalsarenotvalid.

Process and ambient temperature

Pleasechecktheambientandprocesstemperaturespage36/37forthespecificconfigurationyouareabouttouseorinstall.

Chemical resistanceagainst the medium

Iftheequipmentislikelytocomeintocontactwithaggressivesubstances,thenitistheresponsibilityoftheusertotakesuitableprecautionsthatpreventitfrombeingadverselyaffected,thusensuringthatthetypeofprotectionisnotcompromised.Aggressivesubstances:e.g.acidicliquidsorgasesthatmayattackmetals,orsolventsthatmayaffectpolymericmaterials.Suitableprecautions:e.g.establishingfromthematerial'sdatasheetthatitisresistanttospecificchemicals.

Cable entry devices /blanking elementsgeneral

DustIgnitionProof:Foruseininpotentiallyexplosivedustatmospheres:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedtype,suitablefortheconditionsofuseandcorrectlyinstalled.TheminimumingressprotectionrequirementofIP6XaccordingtoEN60529mustbesatisfied.

Flameproof:Foruseinpotentiallyexplosivegasatmospheres:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedflameprooftype,suitablefortheconditionsofuseandcorrectlyinstalled.

IntrinsicallySafe/Typeofprotectionn:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedtype,suitablefortheconditionsofuseandcorrectlyinstalled.TheminimumingressprotectionrequirementofIP64accordingtoEN60529mustbesatisfied.

Versionswithcableglandmountedbydefault:Theusedcableglandisonlysuitableforfixedinstallations.Theinstallerisresponsibleforprovidingappropriatestrain-relieftopreventpullingortwisting.

Versionswithblankingelementmountedbydefault:Blankingelementsarenottobeusedwithanyformofadaptorsorreducers.

Versions with cable gland / blanking element mounted by default

Below-mentionedcablediametersandtighteningtorquesofthenutresp.blankingelementshallbeobservedfortheinstallation.

CableglandM20x1.5(DustIgnitionProof,IntrinsicallySafe,Typeofprotectionn)Cablediameter:6mmto12mmTighteningtorque:Dependingontheusedcableandthereforetobedeterminedbytheuser

CableglandM20x1.5(Flameproof)Cablediameter:Bedding3.1mmto8.6mm/Overall6.1mmto13.1mmTighteningtorque:Numberofturnsdependingontheoverallcablediameteroftheusedcable(e.g.1turn/cablediameter12.5mmto5.5turns/cablediameter6.5mm)

BlankingelementM20x1.5(allversions)Tighteningtorque:32.5Nm

Warnings for installation

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 35

Capanivo®

Page 36: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Notes for use in Hazardous Locations

Ambientandprocesstemperaturerange,max.SurfaceTemperatureandTemperatureClass

ATEX:

process side

thermalisolator

ambientside

Flameproof and Dust Ignition Proof withintrinsicallysafeoutputtoprobe(TypecodePos.2W,T)Electronicmodule:StandardandDigital

- Integral version-Remoteversion:levelprobe

Ambienttemperaturerange

Processtemperaturerange

Max.Surfacetemperature(EPLDa)

Max.Surfacetemperature(EPLDb)

Temperatureclass

(EPLGaorGb)-40to+45°C(-40to+113°F) -40to+45°C(-40to+113°F)(2) T200 95°C T55°C T6

-40to+60°C(-40to+140°F) -40to+60°C(-40to+140°F)(2) T200 110°C T70°C T5

-40to+80°C(-40to+176°F) -40to+95°C(-40to+203°F)(1)(2) T200 145°C T90°C T4

-40to+80°C(-40to+176°F) -40to+125°C(-40to+257°F)(1)(2) T200 175°C T90°C T3

-Remoteversion:electronicsenclosureAmbienttemperature

rangeMax.Surfacetemperature

(EPLDb)Temperatureclass

(EPLGb)-40to+45°C(-40to+113°F) T55°C T6

-40to+60°C(-40to+140°F) T70°C T6

-40to+80°C(-40to+176°F) T90°C T5

(1)Forprocesstemperature>85°C:Onlyapplicableforversionswiththermalisolator(2)WithoptionFFKMO-ringseal:Lowerprocesstemperaturelimitedto-20°C(-4°F)

Intrinsically safe(TypecodePos.2Y)Electronicmodule:Digital

- Integral version-Remoteversion:levelprobe

Ambienttemperaturerange

Processtemperaturerange

Max.Surfacetemperature(EPLDa)

Max.Surfacetemperature(EPLDb)

Temperatureclass

(EPLGaorGb)-40to+45°C(-40to+113°F) -40to+45°C(-40to+113°F)(2) T200 95°C T55°C T6

-40to+60°C(-40to+140°F) -40to+60°C(-40to+140°F)(2) T200 110°C T70°C T5

-40to+60°C(-40to+140°F) -40to+95°C(-40to+203°F)(1)(2) T200 145°C T70°C T4

-40to+60°C(-40to+140°F) -40to+125°C(-40to+257°F)(1)(2) T200 175°C T70°C T3

Type of protection n(TypecodePos.2G)Electronicmodule:Digital

- Integral version-Remoteversion:levelprobe

Ambienttemperaturerange

Processtemperaturerange

Temperatureclass(EPLGc)

-40to+45°C(-40to+113°F) -40to+75°C(-40to+167°F)(2) T6

-40to+60°C(-40to+140°F) -40to+90°C(-40to+194°F)(1)(2) T5

-40to+60°C(-40to+140°F) -40to+125°C(-40to+257°F)(1)(2) T4

-Remoteversion:electronicsenclosureAmbienttemperature

rangeTemperatureclass

(EPLGc)-40to+45°C(-40to+113°F) T6

-40to+60°C(-40to+140°F) T4

Ambienttemperaturerange

Max.Surfacetemperature(EPLDb)

Temperatureclass(EPLGa)

-40to+45°C(-40to+113°F) T55°C T6

-40to+60°C(-40to+140°F) T70°C T4

-Remoteversion:electronicsenclosure

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091736

Capanivo®

Page 37: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Notes for use in Hazardous Locations

Ambienttemperaturerange

Process temperaturerange

-20to+60°C(-4to+140°F) -20to+60°C(-4to+140°F)

Dust ignition proofThemaximumsurfacetemperatureofT100°Cisbasedonamaximumambienttemperatureof+85°C.

Flameproof withintrinsicallysafeoutputtoprobe

ApplicationinZone0(cat1G):

ApplicationinZone1(cat2G):

Ambienttemperaturerange

Process temperaturerange

Temperatureclass

-40to+70°C(-40to+158°F) -40to+85°C(-40to+185°F) T6

-40to+85°C(-40to+185°F) -40to+95°C(-40to+203°F)(1) T5

-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F)(1) T4

INMETRO:

FM / CSA:

Ambienttemperaturerange

Process temperaturerange

Temperatureclass

-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F) T4

Ambienttemperaturerange

Process temperaturerange

Temperatureclass

-40to+40°C(-40to+40°F) -40to+40°C(-40to+40°F) T6

-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F) T4

Intrinsically safeInstallationshallbedoneaccordingto"FM/CSAApproval-Connectiondrawing"onpage23

Explosion proof / Dust ignition proof

(1)Forprocesstemperature>85°C:Onlyapplicableforversionswiththermalisolator

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 37

Capanivo®

Page 38: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Probe modifications

Shorteningthecable(cableversion)

CAUTION: Possibleonlywiththegeneralpurposeconfiguration;pleaseverifyagainstproductnameplate.

Preparation

Determinetherequiredcablelength,andsubtractthatamountfromtheactuallength,tofindtheexcesslengthtocutoff.Forexample:10m(actuallength)minus9m(requiredlength)=1m(excess)

Steps1.Unscrewthecableglandcompressionnuttorelievethesealingconeandreleasethecable.

2.Unscrewtheprobesleevefromthelowerassemblyusingtwo17mm(0.67")wrenchesacrosstheflatsurfaces,asshownbelow.

a.Placetwowrenchesontheflatsurfacesoftheprobeasshown:holdthe probesleevestill,andturnthelowerwrenchcounter-clockwisetoloosen theprobelowerassembly.

b.Removethelowerassemblybyturningthethreadedelectrodeend counter-clockwise:thisexposesthethreeleads,thetensionblock,and thesteelspacer.

flatsurface

flatsurface

lowerwrench

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091738

Capanivo®

cable glandcompression nut

probe sleeve

probe, lowerassembly

actuallength

requiredlength

excesslength

Page 39: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

page

Level limit switchSeries CN 8000Technical Information / Instruction manual

Probe modifications

3.Removetheheatshrinkinsulationcoveringthesolderconnections.

4.Unsoldertheconnections. Note:Donotcuttheconnectionstotheprobeleads,asthiscanrenderthemtooshorttoworkwithlater.

5.Removethetensionblock,andsaveitforre-useinstep7.

6.Calculatetheexcesscable,thenaddbackanallowanceof75mm(3")formakingtheconnections: Forexample,1000mm=excess less75mm=allowanceforconnections 925mm=excesscabletoberemoved

7.Cutofftheexcesscable. Caution:Topreventwiresfrombeingpulledthroughthecablebundle,secureeachwireclosetowheretheouterblackjacketstopspriortostrippingcableinsulationfromit. 8.Removeapproximately75mm(3")ofcablejacket,shield,andfillerstrands.

9.Cutofftheexcesscablecore,makingsurethecutiscleanandsquare

10.Replacethesteelspacerandtensionblock,thenshortentheleadstoapproximately40mm(1.6").

11.Preparetheleadsforsoldering,andifheatshrinkisusedtoinsulatesplices,remembertoslipontheheatshrinkbeforesolderingtheleads.(Note:whiteheatshrinkhasbeenappliedtotheorangewiretosimplifycorrectconnection.) 12.Makethesolderconnectionsandpositiontheheatshrinktocompletelyinsulateeachsolderconnectionbeforeshrinkingit.

iead

25mm(0,37")heat shrinkinsulation

steel spacer

tensionblock

cablecore

1

2

3

4

5

6

7

8

9

10

11

12CN 8000 j gi150917 39

Capanivo®

Page 40: Table of contents · pae Level liit switch Series CN 8000 Technical Inforation / Instruction anual Introduction Applications CN 8000 is designed for level detection and simple pump

Level limit switchSeries CN 8000Technical Information / Instruction manual

page

Probe modifications

13.Removeanyexcesscablecore,ifnecessary.

14.ApplyPTFEtypetape/sealanttoallthreads.

15.Addapre-twisttothewiresbeforescrewingtheprobesleeveandlowerprobeassemblytogether:holdtheprobesleevestill,andgentlyturnthelowerprobeassemblycounter-clockwiseabout5fullturns.Thisavoidsthewiresbeingbrokenwhentheprobeandprobesleeveareassembled.

16.Screwthelowerprobeassemblyclockwiseintotheprobesleeve,andtightenitwitha17mm(0.67")wrench.

17.Checkthattheinstrumentisoperatingcorrectly,usingthetestprocedure(seeexternalOperatingManual).

1

2

3

4

5

6

7

8

9

10

11

12j CN 8000gi15091740

Capanivo®