page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Table of contents
Page
Safety Notes / Technical support 2----------------------------------------------------------------------------------------------------- Introducion Applications / Function / Features 3 ProfibusSystemImplementation 4-----------------------------------------------------------------------------------------------------
Technical data CN 8100
Dimensions 5 Electrical data 9 Mechanical data 10 Operating conditions 11 Approvals 15-----------------------------------------------------------------------------------------------------Mounting 16-----------------------------------------------------------------------------------------------------Electrical installation 20-----------------------------------------------------------------------------------------------------Operation-Electronicmodule:Standard 24-----------------------------------------------------------------------------------------------------Operation-Electronicmodule:Digital 30-----------------------------------------------------------------------------------------------------Notes for use in Hazardous Locations 31-----------------------------------------------------------------------------------------------------ProbeModifications Shorteningthecable(cableversion) 38
Subjecttotechnicalchange. Weassumenoliabilityfortypingerrors.
Alldimensionsinmm(inch). Differentvariationsthanspecifiedarepossible.Pleasecontactourtechnicalconsultants.
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 1
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Safety notes / Technical support
Notes
• Installation,maintenanceandcommissioningmaybeaccomplishedonlybyqualifiedtechnicalpersonnel.• Theproductmustbeusedonlyinthemanneroutlinedinthisinstructionmanual.• Thisproductisintendedforuseinindustrialareas.Operationofthisequipmentinaresidentialareamaycause interferencetoseveralfrequencybasedcommunications.
Specialattentionmustbepaidtowarningsandnotesasfollows:
WARNING
Relatestoacautionsymbolontheproduct:Afailuretoobservethenecessaryprecautionscanresultindeath,seriousinjuryand/orconsiderablematerialdamage.
WARNING
Relatestoacautionsymbolontheproduct:Riskofelectricshock
WARNING
Afailuretoobservethenecessaryprecautionscanresultindeath,seriousinjuryand/orconsiderablematerialdamage.
Thissymbolisused,whenthereisnocorrespondingcautionsymbolontheproduct.
CAUTION Afailuretoobservethenecessaryprecautionscanresultinconsiderablematerialdamage.
Safetysymbols
Inmanualandonproduct
Description
CAUTION:refertoaccompanyingdocuments(manual)fordetails.
Earth(ground)Terminal
ProtectiveConductorTerminal
Technical support
Pleasecontactyourlocalsupplier(foraddressseewww.uwt.de).Otherwiseyoucancontact:
UWTGmbH Tel.:0049(0)83157123-0Westendstr.5 Fax:0049(0)83176879D-87488Betzigau [email protected] www.uwt.de
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi1509172
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Introduction
Applications
CN8000isdesignedforleveldetectionandsimplepumpcontrolinavarietyofapplications: •Liquids,solids(powderandgranules),slurries,interfacedetection(forexample,oil/water),andfoamdetection •Foodsandpharmaceuticals •Chemicalandpetrochemical •Highpressureandtemperature
Function CN8000isaversatilecapacitanceswitch,idealforleveldetectionofinterfaces,solids,liquids,slurries,andfoam,andforsimplepumpcontrol.
Theswitchrespondstothepresenceofanymaterialwitharelativedielectricconstantof1.5ormorebydetectingachangeincapacitance,whichisregisteredasachangeinoscillatingfrequency.
Theswitchcanbesettodetectbeforecontactoroncontactwiththeprobe.ThedesignoftheCN8000allowstheinstrumenttooperateindependentlyofthetankwallorpipe,soitdoesnotrequireanexternalreferenceelectrodeforleveldetectioninanonconductivevesselsuchasconcreteorplastic.
Thepowersupplyisgalvanicallyisolated.
Thematerialsusedintheprobeconstructionprovideahighlevelofchemicalresistance,andanexcellenttemperatureratingontheprocesswettedportionoftheprobe:upto125°C(257°F).
CN8000isavailableintwomodels:thestandardmodel,andthedigitalmodelwithintegrallocaldisplay.
Features
•Pottedconstructionprotectscomponentsfromshock,vibration,humidity,and/orcondensation •Highchemicalresistanceonprobes •Leveldetectionindependentoftankwall/pipe •Freelyprogrammablesetupcoverswiderangeofapplications/materials •IntegratedLocalUserInterface(LUI)foreaseofuse •Rigidandcableversionsavailable •CommunicationviaPROFIBUSPA(profileversion3.0,ClassB) •IntrinsicallySafe(IS)transmitterdesignforhazardousareas(requiresexternalbarrierorISpowersupply)
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 3
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Introduction
CN8000supportsPROFIBUScommunicationprotocol,andSIMATICPDMsoftware.
Basic PLC configuration with PROFIBUS PA
Programming
CN8000carriesoutitslevelmeasurementfunctionaccordingtothesetofbuilt-inparameters.Youcanmakeparameterchangeslocallyviathelocaluserinterface,orfromaremotelocationviaaPCusingSIMATICPDMsoftware.
CN8000Digitalcanbeusedeither:
•asastandaloneunit,programmedlocallyusingtheLocalUserInterface,or •installedaspartofanetwork,programmedremotelyusingSIMATICPDMonProfibusPAnetwork(orlocally usingtheLocalUserInterface).
Alarm signalling
Thesolid-stateswitchcanbesettoreacteithertoadiagnosedfaultintheinstrument,ortoachangeintheprocesslevel. Fault Signalling
CN8000canactivelyreportinformationonitsownstatusviaPROFIBUSPAwhenusedaspartofanetwork,orbymeansofapre-definedoutputstatusatthesolidstateswitchandontheLocalUserInterface(LUI).
active PLC
PROFIBUSDP
PC/ laptop
DP/ PA coupler
PROFIBUSPA
CN 8000(PROFIBUSPA)
CN 8000 (PROFIBUSPA)
CN 8000 (PROFIBUSPA)
ProfibusPA-SystemImplementation
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi1509174
Capanivo®
PDM
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Technical data - Dimensions
Enclosure
Temperaturextendedshaft
Temperaturextendedshaft
CN 8100Threaded process connection
CN 8100Flanged process connection
M20x1.5cablegland NPT 1/2" conduit CN 8100Top view
CN 8100Triclamp process connection
Temperaturextendedshaft
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 5
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Technical data - Dimensions
Threaded process connection
Detail "A"
L does not include any raisedface(seepage7)
CN 8100Short extension lenghtShortest length
CN 8100Cable version
Threaded process connection
Flanged process connection
CN 8100Pipe versionExtended
CN 8100Pipe versionExtended,withSlidingcoupling (pos.19)
Flanged process connection
Threaded process connection
probe(sensor)
probe(sensor)
Flanged process connection
pip
e
cableFEPinsulated
slid
ing
coup
ling
probe(sensor)
probe(sensor)
probe(sensor)
probe(sensor)
Triclampprocessconnection
Triclampprocessconnection
pip
e
pip
ep
ipe
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi1509176
Capanivo®
A
A
L=120mm(1.7")
L=98m
m(3.8")
84mm(3.3")
84mm(3.3")
84mm(3.3")
L L L
22mm
(0,87")
min.215mm(8.46")
ø20mm(0.79")
ø20mm(0.79")
ø6mm(0.3")
LL
A
L
L=98m
m(3.8")
ø20mm(0.79")
ø24mm(0.95")
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Technical data - Dimensions
Flanges
Type Facing thickness
ASME150lbASME300lb
2mm(0.08")
ASME600lb 7mm(0.28")
Raised facefa
cing
thickness
CN 8100Remote version(pos.12a,b)
Remoteversionexemplifiedwithpipe version, threaded process connection
Mounting bracket1.4404(316L)
Remotecable:ø6mm(0.24")FEP isolationBothsideswired
Probe(sensor)
Code Type Number of holes
d2mm(inch)
Lkmm(inch)
Dmm(inch)
Tthicknessmm(inch)
ASMEB
16.5,raisedface
5A 1"150lbs 4 15.9(0.63) 79.3(3.12) 108.0(4.25) 14.3(0.56)
5B 1"300lbs 4 19.1(0.75) 88.9(3.5) 123.8(4.87) 17.5(0.69)
5C 1"600lbs 4 19.1(0.75) 88.9(3.5) 123.8(4.87) 17.5(0.69)
5D 11/2”150lbs 4 15.9(0.63) 98.6(3.88) 127.0(5.0) 17.5(0.69)
5E 11/2"300lbs 4 22.2(0.87) 114.3(4.5) 155.6(6.13) 20.6(0.81)
5F 11/2"600lbs 4 22.2(0.87) 114.3(4.5) 155.6(6.13) 22.4(0.88)
5G 2"150lbs 4 19.1(0.75) 120.7(4.75) 152.4(6.01) 19.1(0.75)
5H 2"300lbs 8 19.1(0.75) 127.0(5.0) 165.1(6.5) 22.2(0.87)
5J 2"600lbs 8 19.1(0.75) 127.0(5.0) 165.1(6.5) 25.4(1.0)
5K 3"150lbs 4 19.1(0.75) 152.4(6.01) 190.5(7.5) 23.9(0.94)
5L 3"300lbs 8 22.2(0.87) 168.2(6.62) 209.6(8.25) 28.6(1.13)
5M 3"600lbs 8 22.2(0.87) 168.2(6.62) 209.6(8.25) 31.7(1.25)
5N 4"150lbs 8 19.1(0.75) 190.5(7.5) 228.6(9.0) 23.9(0.94)
5P 4"300lbs 8 22.2(0.87) 200.0(7.87) 254.0(10.0) 31.7(1.25)
5Q 4"600lbs 8 25.4(1.0) 215.9(8.5) 273.1(10.75) 38.1(1.5)
EN1092-1typeA,flatfaced
6A DN25PN16 4 14.0(0.55) 85.0(3.35) 115.0(4.53) 18.0(0.71)
6B DN25PN40 4 14.0(0.55) 85.0(3.35) 115.0(4.53) 18.0(0.71)
6C DN40PN16 4 18.0(0.71) 110.0(4.33) 150.0(5.91) 18.0(0.71)
6D DN40PN40 4 18.0(0.71) 110.0(4.33) 150.0(5.91) 18.0(0.71)
6E DN50PN16 4 18.0(0.71) 125.0(4.92) 165.0(6.5) 18.0(0.71)
6F DN50PN40 4 18.0(0.71) 125.0(4.92) 165.0(6.5) 20.0(0.79)
6G DN80 PN16 8 18.0(0.71) 160.0(6.3) 200.0(7.87) 20.0(0.79)
6H DN80PN40 8 18.0(0.71) 160.0(6.3) 200.0(7.87) 24.0(0.94)
6J DN100 PN16 8 18.0(0.71) 180.0(7.09) 220.0(8.66) 20.0(0.79)
6K DN100PN40 8 22.0(0.87) 190.0(7.48) 235.0(9.25) 24.0(0.94)
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 7
Capanivo®
57mm(2.24")
30mm(1.18")
ø9.5mm(0.37")
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Technical data - Electrical data
Performance
Repeatability Approx.±2mmforaconductivefluid
Power Supply 12to250VAC/DC(0to60Hz)
Exapprovals Max.voltagewhichdoesnotinvalidatetheintrinsicallysafeprotectionofthesensor(probe):Um=250VAC
Powerconsumption 2Wmax.
PerformanceRepeatability ±1%ofmeasurement
User InterfaceConfiguration Locally,usingdipswitchesandpotentiometers
Local display 3 LED indicators
Output Relaycontactandsolid-stateswitch
Polarity-independent Yes
Failsafe Relayandsolid-stateswitchcanbede-energizedintheabsenceofasensorsignal
Alarm Outputs Relay 1FormC(SPDT)contact(selectableNCorNOcontact)
max.switchingvoltage/current(DC):30VDC/5Amax.switchingvoltage/current(AC):250VAC/8A(resistiveload)
Solid-stateswitch Rated30VDCorpeak30VAC,82mA
Timedelay ON/OFFalarm,durationselectable1to42seconds/1to100seconds
Hysteresis DependentonDK:max.2mm(0.08”)@DK=1.5
Failsafe operation FailsafeHighorFailsafeLow
Delaytimers 2:AlarmONtoOFFandAlarmOFFtoON
Electronicmodule:Standard(RelaySPDT/SolidState)
Electronicmodule:Digital (ProfibusPA/SolidState)
Power
Busvoltage - General purpose - Intrinsically Safe
12to30VDC,12.5mA 12to24VDC,12.5mA,FISCOFieldDeviceIntrinsicallysafebarrierrequiredforATEX:Ui=24VIi=380mAPi=5.32WCi=5nFLi = 10uHforFM/CSA:seepage23
Exapprovals(Flameproof,Dustignitionproof)
Max.voltagewhichdoesnotinvalidatetheintrinsicallysafeprotectionofthesensor(probe):Um=250VAC
Starting current < current of normaloperation
Yes
Fault current 0mA(max.uninterruptedcurrentminuscurrentofnormaloperation)
Faultdisconnectequipment(FDE) Yes
Auxiliarysource Buspowered
Separate supply necessary No
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi1509178
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Technical data - Electrical data
User Interface
Configuration Locally,usinglocaluserinterface(LUI),forstandaloneoperation,orRemotely,usingSIMATICPDMonaProfibusPAnetwork
Local Digital Display LCD
Output (bus) PROFIBUSPA(IEC61158CPF3CP3/2)Busphysicallayer:IEC61158-2MBP(-IS)
Polarity-independent yes
Simultaneouscommunicationwith Master Class 2
4(max.)
Cyclic User data (normal operation) Byteoutput 2bytesrepresentingonevalue
Byteinput 0
Deviceprofile PROFIBUSPAProfileforProcessControlDevicesVersion3.0,ClassB
Functionblocks 1
Discrete input 1
Logical inversion Parameterizable
Simulation functions Output
yes
Input yes
Failsafe Parameterizable(lastusablevalue,substitutevalue,erroneousvalue)
Block Structure Physicalblock 1
Transducerblock 1
Transducerblockdiscreteinput Yes
Monitoringmeasuringlimits Yes
Signal Output Solid-stateswitch Galvanically isolated, non-polarity sensitive transistor
Rated30VDCorpeakACmax.,82mAmaxVoltagedropbelow1Vtypical@50mA WithIntrinsicallysafe:barrierrequiredforATEX:Ui=30VIi=200mAPi=350mWCi=0 L i = 0forFM/CSA:seepage23
Timedelay Controlledbysoftware 2delaytimers:alarmONdelayandalarmOFFdelay)
Hysteresis 100%adjustable
Failsafe operation FailsafeHighorFailsafeLow
Terminal Removableterminalblock,2.5mm2max.
Diagnostics Input Reedcontact:fortestfunction
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 9
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Probe
Weight Weightvariesbasedonconfiguration.Forexample:
•compact,100mm(4”)insertionlength, ¾” process connection
1kg(2.20lb.)approx.
Technical data - Mechanical data
Model Length(max)
ProcessConnections
Extension Tensile(max)
Wetted Parts
Pipe 5,500mm/216.5”
•Threaded:¾”1"11/2"BSPT(R),BSPP(G) ¾” 1" 1 ¼” 1 1/2" NPT
•Weldedflange:ASME1”11/2”2”3”4”DN25405080100
•Triclamp:1"11/2"2"21/2"3"ISO2852
1.4404(316L) n/a •1.4404(316L) optional PFA coating•FKMsealsoptionalFFKM•PPSprobeoptionalPVDF
Cable 30,000mm/1,181.1”
•Threaded:¾”1"11/2"BSPT(R),BSPP(G) ¾” 1" 1 ¼” 1 1/2" NPT
•Weldedflange:ASME:1”11/2”2”3”4”DN25405080100
FEP(FluorinatedEthylenePolymer)
180kg/400lbs
•1.4404(316L)•FEPjacketedcable•FKMsealsoptionalFFKM•PPSprobeoptionalPVDF
EnclosureTermination Removableterminalblock
Tighteningtorqueofterminalscrews:0.5to0.6Nm
Conductorcrosssection:
1 conductor-solid:0.2to2.5mm²-flexible:0.2to2.5mm²-flexible,withferrulewithorwithoutplasticsleeve:0.25to2.5mm²-AWG24to12
2conductorswithsamecrosssection-solid:0.2to1.0mm²-stranded:0.2to1.5mm²-stranded,withferrulewithoutplasticsleeve:0.25to1.0mm²-stranded,TWINferrulewithplasticsleeve:0.5to1.0mm²
Construction Powder-coatedaluminumwithgasket
Optionalthermalisolator 1.4404(316L)stainlesssteel
Cableentry 2xM20thread,option:2x1/2”NPTthreadwithadaptor
WithATEXapproval:-Default:2xM20x1.5-WithselectionofoptionPos.33a:2xNPT1/2"taperedANSIB1.20.1
Ingress protection Type4/IP65orIP68(dependingonCableEntryoption)
Note:Theuseofapprovedwatertightconduithubs/glandsisrequiredforType4/IP65orIP68(outdoorapplications).
SeparationbetweenZone0andZone1(ATEXII1/2G)
Materialoftheseparationelement(partitionwall)-Stainlesssteel,1.4404(316L)-Glass,Inconel600(Glassseal)
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091710
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Technical data - Operating conditions
Process
Relative dielectric constant 1.5minimum
Temperatureatprocessconnection Withouttemperatureextendedshaft: –40to85°C(–40to185°F)-20to85°C(-4to+185°F)withoptionFFKMsealO-ringWithtemperatureextendedshaft:–40to125°C(–40to257°F)-20to125°C(-4to+257°F)withoptionFFKMsealO-ring
WithATEXapproval:DependingonSurfaceTemperatureandTemperatureClass,detailsseepage36/37.
Pressure(vessel): - pipe version -cableversion/triclampversion - sliding coupling version
–1to25barg/–14.6to365psig(nominal) –1to10barg/–14.6to150psig(nominal) –1to10barg/–14.6to150psig(nominal)
Note:pleaseseePressureversusTemperatureCurvesonnextpages.
Environmental Location Indoor/outdoor
Altitude 2.000m(6.562ft.)max.
Ambienttemperature –40to85°C(–40to185°F)
WithATEXapproval:DependingonSurfaceTemperatureandTemperatureClass,detailsseepage36/37.
LUI(localuserinterface) –30to85°C(–22to185°F)
Storagetemperature –40to85°C(–40to185°F)
Relativehumidity Suitableforoutdoor
Installation category II(Electronicmodule:Standard)I(Electronicmodule:Digital)
Pollution degree 4
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 11
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Technical data - Operating conditions
PressureversusTemperatureCurves
Shortestlengthandextendedpipe,threaded
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
Shortestlengthandextendedpipe,ASMEweldedflange
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091712
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Technical data - Operating conditions
1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.
Shortestlengthandextendedpipe,ENweldedflange
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
Triclamp
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 13
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Cable,ASMEweldedflange
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
Cable,ENweldedflange
P=permittedoperatingpressure T=permittedoperatingtemperature
1)Thecurvesdenotetheminimumallowableflangeclassfortheshadedareabelow.
Technical data - Operating conditions
atmosheric
Cable,threaded
P=permittedoperatingpressure T=permittedoperatingtemperature
atmosheric
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091714
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Approvals
Note:EN61326(CEEMC)testingwasconductedwhilemountedinametallicvesselandwiredusingshieldedcable,wherethecablewasterminatedinanEMCcableglandatthedeviceentrypoint.Inaddition,unitswithaflangeprocessconnectionweremountedusingametallicgasket.
1 BarrierorIntrinsicallySafepowersupplyrequiredforIntrinsicallySafeprotection
Electronicmodule:Digital (ProfibusPA/SolidState)
General Purpose CE, CSA, FM, TR-CU
Dust Ignition Proof ATEX II 1/2D, IIICCSA/FMClassII,Div.1,Gr.E,F,GClassIIITR-CUINMETRO
FlameProof/ExplosionProof ATEX II 1/2G, IIC CSA/FMClassI,Div.1,Gr.A,B,C,DTR-CUINMETROKC
Intrinsically Safe 1 ATEX II 1G, IICATEX II 1/2D, IIICCSA/FMClassI,Div.1,Gr.A,B,C,DTR-CU
Type of protection nNon-incendive
ATEX II 3G, IICCSA/FMClassI,Div.2,Gr.A,B,C,D
Electronicmodule:Standard(RelaySPDT/SolidState)
General Purpose CE, CSA, FM, TR-CU
Dust Ignition Proof ATEX II 1/2D, IIICCSA/FMClassII,Div.1,Gr.E,F,GClassIII TR-CUINMETRO
FlameProof/ExplosionProof ATEX II 1/2G, IIC CSA/FMClassI,Div.1,Gr.A,B,C,DTR-CUINMETROKC
Marine LloydsRegisterofShipping,CategoriesENV1,ENV2andENV5
OverfillProtection WHG
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 15
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Mounting
•Installationshallonlybeperformedbyqualifiedpersonnelandinaccordancewithlocalgoverningregulations.•Thisproductissusceptibletoelectrostaticshock.Followpropergroundingprocedures.•Thehousingmayonlybeopenedformaintenance,localoperation,orelectricalinstallation.•Beforeinstallingtheinstrument,verifythattheenvironmentcomplieswithanyrestrictionsspecifiedontheproductnameplate.•TocomplywithCEEMCregulations,whereapplicable,theCN8000shouldbeinstalledinaccordancewiththetestingdetailsonpage15.
Handling Precautions
WARNING:Topreventdamage,allunitswithapipelongerthan2m(6.5ft)mustbehandledasdescribedbelow.
WhenliftingCN8000fromahorizontalposition,supportitatthesethreepoints:
At the end of the pipebeforethesensor
Midwayalongthe pipe
At the processconnection or flange
Oncevertical,CN8000maybeheldbytheprocessconnectionorflange:
At the processconnection or flangeNote:
Unitshownwithextendedpipeversion.Handlingprecautionsapplytoallunitswithpipeslongerthan2m(6.5ft).
General Safety Instructions
Additional Safety Instructions for Hazardous Locations
see page 31ff
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091716
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Mounting
Location
Recommended:•Provideasunshieldtoprotectthetransmitterfromdirectheatradiation.
Precautions:•AvoidmountingCN8000inlocationssubjecttostrongvibrationsinthevicinity,wheneverpossible.•Donotexceedthepermissibleambienttemperaturelimits(seeEnvironmentalonpage11fordetails).
MountingCompact probe
Highlevelalarm Lowlevelalarm
Forhighlevelalarm(levelexceedsnormalprocesslevel): •normallymountedintothevesseltop,or •mountedthroughthetankwallatthedetectionlevel
Forlowlevelalarm(leveldropsbelownormalprocesslevel): •mountedthroughthetankwallatthedetectionlevel
Typical configuration with extensions
Forhighorlowlevelalarm: •designedfortopmounting.Theprobesuspendsverticallysothatitreachesintotheprocessatthedesired detectionlevel(highorlowdetectionalarm).
Highlevelalarm Lowlevelalarm
Angle
normalprocesslevel
normalprocesslevel
normalprocesslevel
normalprocesslevel
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 17
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Mounting
Mounting Restrictions
•Keepthesensoratleast50mm(2")awayfromanynozzleortankwall.•Ifmultipleunitsareused,allowatleast100mm(4")betweenthem,topreventinterference.
In nozzle Close to tank walls
Multiple Units
SideView EndView
Sensorsmustbeatleast100mm(4")apart.
Mount diagonally if space is restricted
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091718
Capanivo®
50mm(2") min
50mm (2") min
50mm(2")min
100mm (4")min
100mm (4")min
100mm (4")min
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Mounting
Process Cautions for solids
•Themaximumallowabletorqueonahorizontallyinstalledpipeis15Nm.•Keepunitoutofpathoffallingmaterial,orprotectprobefromfallingmaterial.
Considermaterialsurfaceconfigurationwheninstallingunit.
Tensileloadmustnotexceedprobeorvesselrating(seeTensile(max)onpage10).
Avoidareaswherematerialbuildupoccurs.
In Hazardous Locations: Observe Specifc condition of use for electrostatic charge (see page 34)
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 19
Capanivo®
50mm (2")min
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Electrical installation
WARNING: •Observethespecificationsoftheexaminationcertificatevalidinyourcountry. •Observethelawsandregulationsvalidinyourcountryforelectricalinstallationsinpotentiallyexplosive atmospheres. •RefertoHazardousAreaInstallationonpage31ifapplicable. •Ensurethattheavailablepowersupplycomplieswiththepowersupplyspecifiedontheproductnameplate andspecifiedintheexaminationcertificatevalidinyourcountry. •Shippingplugsinthecableinletsmustbereplacedbysuitablescrewtypeglandsordummyplugs,whichare appropriatelycertifiedfortransmitterswithexplosion-proofprotection. •ForCEinstallations,useacablewithabraidedmetallicshield(orarmouredcablewhereapplicable). •Thelidmustnotbeopenedinwetlocationswhiletheunitispowered.(Awetlocationisalocationwhere wateroranotherconductivefluidmaybepresentandislikelytoincreasetheriskofelectricshock.) •Cableentrydevicesandclosingelementsofunusedaperturesmustmeetatemperaturerangefrom min.-40°Cto10Kabovemax.ambienttemperature.
Notes: •LayPROFIBUSPAcableseparatelyfrompowercablewithvoltagesgreaterthan60V. •Avoidlocatingtheunitnearlargeelectricalequipmentwhereverpossible. •Connectthecableshieldtoearth(forexample,tothehousingbymeansofametallicscrewedgland).
WARNING: •Allfieldwiringmusthaveinsulationsuitableforatleast250V. •Onlyqualifiedpersonnelareauthorizedtoinstallandoperatethisequipmentinaccordancewithestablished safetypracticesandstandards.
•TheProtectiveEarthTerminalindicatedby mustbeconnectedtoreliableground.Usecrimptypecable socketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234). Incaseofnon-metallicvessels,theexternalearthwireshouldbeconnectedtoanearthedcomponent whichisearthednearthevessel. •Allwiringmustbedonebyqualifiedpersonnelinaccordancewithallgoverningregulations. •Theequipmentmustbeprotectedbya16Afuseorcircuitbreakerinthebuildinginstallation. •Acircuitbreakerorswitchinthebuildinginstallation,markedasadisconnectswitch,shallbeinclose proximitytotheequipmentandwithineasyreachoftheoperator. •Useshieldedcable,wiregauge20AWGto14AWG(0.5mm2to2.0mm2).ForCEinstallationsuseacable withabraidedmetallicshield(orarmouredcablewhereapplicable). •Maximumworkingvoltagebetweenadjacentrelaycontactsis250V. •Relaycontactterminalsareforusewithequipmentwhichhasnoaccessiblelivepartsandwiringwhichhas insulationsuitableforatleast250V. •Cableentrydevicesandclosingelementsofunusedaperturesmustmeetatemperaturerangefrom min.-40°Cto10Kabovemax.ambienttemperature.
Additional Safety Instructions for Hazardous Locationssee page 31ff
General Safety Instructions
Electronicmodule:Standard(RelaySPDT/SolidState)
Electronicmodule:Digital (ProfibusPA/SolidState)
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091720
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Electrical installation
Electronicmodule:Standard(RelaySPDT/SolidState)
Note:Switchandpotentiometersettingsareforillustrationpurposesonly.
red
black
white
Connectprotectiveearthwiretoterminalprovidedinhousingandmarkedwith
Usecrimptypecablesocketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234).
1.Loosenthelidclipandremovethelidtoaccesstheconnectorsandelectronics.2.Connectthewirestotheterminals3.Groundtheinstrumentaccordingtolocalregulations.4.Tightentheglandtoformagoodseal.
Power supply:
12to250VAC/DC(0to60Hz) 2Wmax.
Signal output:
Relay:Floating relay SPDTACmax.250V,8A,2000VA,noninductiveDCmax.30V,5A,150W,noninductive
Solidstateswitch:30VDCor30VAC(peak),82mAObserveprotection(seebelow)
Powersupply
Relay
internal wiring
Solidstateswitch(polaritynotimportant)
Protection diode
ObserveaProtectiondiodeincaseofconnectinganexternalrelaytotheSolidstateswitch
Protection of Solid State Switch
Solid state switch
internal wiring
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 21
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Electrical installation
1.Loosenthelidclipandunscrewthelidoftheenclosure.2.Unscrewandliftupthedigitaldisplay(looseneachscrewtwoturnsbeforecompletelylooseningboth,tokeeptherubberretainingringsinplace.)3.Connectthewirestotheterminals4.Groundtheinstrumentaccordingtolocalregulations.5.Tightenthecableglandtoformagoodseal.6.Fixthedigitaldisplay.7.Toadjustthetransmitterlocally,usingthekeypad,gotoProgrammingviatheLocalUserInterface(LUI).Afteradjustment,replacetheenclosurelidandtightenthelidclip.
PowersupplyorProfibusPA
Solid state switch
Digital display
Electronicmodule:Digital (ProfibusPA/SolidState)
PowersupplyorProfibusPA*(polaritynotimportant)
internal wiring
Solidstateswitch(polaritynotimportant)
internal wiring
blue
blue
red
black
white
Protection diode
ObserveaProtectiondiodeincaseofconnectinganexternalrelaytotheSolidstateswitch
Protection of Solid State Switch:
Solid state switch
*WithuseofProfibusPAthewiringmustbeaccordingtoProfibusPAstandards.IfProfibusPAisnotused,ashieldedcableisrecommendedtoensurestablemeasurement.
Power supply:
12..30VDC,12.5mA
IntrinsicallySafe:12..24VDC,12.5mA
Intrinsicallysafebarrierrequired
ForATEX:Ui=24V,Ii=380mA,Pi=5.32W,Ci=5nF,Li=10 uH
ForFM/CSA:See"Connectiondrawingonpage23"
Signal output:
Solidstateswitch:30VDCor30VAC(peak),82mAObserveprotection(seebelow)
Intrinsicallysafe:Intrinsicallysafebarrierrequired
ForATEX:Ui=30V,Ii=200mA,Pi=350mW,Ci=0, Li=0
ForFM/CSA:See"Connectiondrawingonpage23"
Connecting the electronic module:
Connectprotectiveearthwiretoterminalprovidedinhousingandmarkedwith
Usecrimptypecablesocketfor4mmscrewdiameter,ringformorU-form(e.g.DIN46234).
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091722
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Electrical installation
FM/CSAapprovalConnectiondrawing
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 23
Capanivo®
Pro
du
ct
Gro
up
FO
R IN
TE
RN
AL
US
E O
NLY
Poin
t Level S
ensors
RF
80
00
/ C
N 8
00
0 u
nit
Enclo
surePA– PA+
so
lid s
tate
ou
tpu
t
Alarm OutputSolid State Switch
No
te 3
No
te1
& 2
No
te1
& 2
Com
munic
ation I/O
Com
munic
ation I/O
Insta
llatio
n m
ust
in a
cco
rda
nce
with
th
e N
atio
na
l E
lectr
ica
l C
od
e (
R)
(NF
PA
70
,A
rtic
le 5
04
) a
nd
AN
SI/
ISA
-RP
12
.06
.01
Hazard
ous (
Cla
ssifie
d)
Location
Uncla
ssifie
d L
ocation
IS C
LA
SS
I,
II,
III,
DIV
.1 G
RO
UP
SA
, B
, C
, D
, E
, F
& G
T6
...T
4
XP
CL
AS
S I
, D
IV.
1 G
RO
UP
SA
, B
, C
& D
T4
CL
AS
S I
, D
IV.
2 G
RO
UP
SA
, B
, C
& D
T4
CL
AS
S I
I, I
II,
DIV
. 1
GR
OU
PS
E,
F &
GT
4
Te
mp
era
ture
Cla
ss
T4
fo
r–
40
°C≤
am
bie
nt
tem
pe
ratu
re≤
+8
5°C
En
tity
Pa
ram
ete
r
GR
OU
PS
A
, B
, C
, D
, E
, F,
G;
IIC
GR
OU
PS
C
, D
, E
, F,
G;
IIB
Cu
rren
t Lo
op
Ou
tpu
t
Cu
rren
t Lo
op
Ou
tpu
tS
olid
Sta
te
Ou
tpu
t
So
lid S
tate
Ou
tpu
t
Ui (V
max)
24
V2
4 V
30
V3
0 V
Ii (
imax)
38
0 m
A3
80
mA
11
0 m
A2
00
mA
Pi
5.3
2 W
5.3
2 W
82
5 m
W1
.5 W
Ci
5 n
F5
nF
00
Li
10
µH
10
µH
00
NO
TE
S:
1)
Fie
ldbus input: s
pecifie
d to the fis
co m
odel
2)
Manufa
ctu
re’s
insta
llation instr
uctions m
ust be follo
wed for
insta
llation o
fA
ssocia
ted Intr
insic
ally
Safe
Appara
tus
3)
Either
one o
r both
wire p
airs b
etw
een
Associa
ted Intr
insic
ally
Safe
Appara
tus m
ust be
gro
unded s
cre
ened o
r shie
lded w
ires.
4)
For
FM
: In
sta
llation m
ust be in a
ccord
ance w
ith
AN
SI / IS
A12.0
6.0
1 a
nd the N
ational E
lectr
ical C
ode (
AN
SI / N
FP
A70)
5)
For
CS
A: In
sta
llation m
ust be in a
ccord
ance w
ith a
pplic
able
section o
f C
anadia
n E
lectr
ical C
ode (
CE
C)
6)
For
Div
isio
n 2
insta
llation, associa
ted a
ppara
tus is n
ot re
quired, in
sta
llation m
ust be in a
ccord
ance
with D
ivis
ion 2
wirin
g m
eth
ods a
nd s
upply
voltage m
ust not exceed 3
0 V
olts
7)
Dust-
tight seals
must be u
sed for
Cla
ss II and III insta
llations
8)
The
transm
itte
r is
appro
ved for
Cla
ss I, Z
one 0
applic
ations if connecting to
AE
x[ia] ra
ted
RF
8000 / C
N 8
000
Associa
ted Intr
insic
ally
Safe
Appara
tus.
The tra
nsm
itte
r is
suitable
only
for
Cla
ss I, Z
one 1
or
Zone 2
, and n
ot
suitable
for
Cla
ss 1
, Z
one 0
or
Cla
ss, D
ivis
ion 1
applic
ations
9)
For
FM
the u
nit m
ust be insta
lled u
sin
g F
MA
ppro
ved
Appara
tus
Exte
rna
l fr
am
e e
art
h t
erm
ina
l
Temperatureclass:
T4for–40°C<=ambienttem
perature<=+85°C
T6for–40°C<=ambienttem
perature<=+40°C
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Operation - Electronic module: Standard
Settings
S1:Delay(coveredtouncovered)
S3:FailsafeHigh/LowS4:Test
P1
P2
switchpointDIPswitches
L2 red
delay
Usethedelayfunctiontoslowthesignaloutputresponse,andcompensateforturbulenceorfalsereadings.
S1 / S2: Signal output delay
S3: Failsafe High / Low
Failsafe Mode S3
Failsafe High
FailsafeLow*
relay switch relay switch
relay switch relay switch
*Factorysetting
*Factorysetting
S2:Delay(uncoveredtocovered)
S1
S2
Delay active*
Delay off
Delay active*
Delay off
Signaloutputdelay:Sensor covered to uncovered
Signaloutputdelay:Sensor uncovered to covered
Delaytime/seconds
DIPswitches
L3 green
L1 yellow
*Factorysetting
LEDsL1:Sensorstatus(yellow)ONifsensorisdetectedascovered(capacitanceonsensorisgreaterthansettedswitchpoint)L2:Signaloutput(red) ONifRelayisactivated/Solidstateswitchisclosed.L3:Powersupply(green)ONifpowerispresent
S5:Set-upmode/runmode
Delaytime/seconds
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091724
Capanivo®
1 2 3 4 5
1*
P1
12
2540 60
80
100
1*
7
1421 28
35
42
P1
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Operation - Electronic module: Standard
Allowstotestthesettedsignaloutputdelaytimewithouttheneedtochangethesensorfromcoveredtouncoveredorfromuncoveredtocovered.
S4 Normaloperation*
S4 Testmode If sensor is uncovered:SettingS4toTestmodesimulatesacoveredprobe.Afterthesetteddelaytime"Sensoruncoveredtocovered"(seeDIPswitchS2)haspassed,thesignaloutputandLED2(red)areswitching.
If sensor is covered:SettingS4toTestmodesimulatesauncoveredprobe.Afterthesetteddelaytime"Sensorcoveredtouncovered"(seeDIPswitchS1)haspassed,thesignaloutputandLED2(red)areswitching.
S4: Test
*Factorysetting
*Factorysetting
S5: Set-up mode / run mode
S5 Runmode* Normaloperationafterswitchpointadjustmentiscomplete.
S5 Set-upmode Usethissettingonlyduringswitchpointadjustment.
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 25
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Operation - Electronic module: Standard
Switchpoint Adjustment
Application Material Adjustment conditions
General • Dry solids•Lowviscosityliquids
Sensor uncovered
Demanding •Hygroscopic/wetsolids•Highviscosityandhighconductivityliquids
Sensorimmersedandthenuncovered,retainingmax.possiblematerialbuildup
Interfacedetection
•IgnoringliquidA/detectingliquidB•Ignoringfoam/detectingliquid
ImmersesensorinliquidAorfoam
General applications
1. Ensure material level is well below the probe
Theunitwillcalibratetoanuncoveredprobe.
2. Set to Set-up mode SetdipswitchS5toSet-upmode
3. Adjust switchpoint with poti P2
IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.
TurnP2clockwiseuntilL1juststopsglowing.
4. Set to Run mode SetdipswitchS5toRunmode
Switchpoint adjustment is finished
Selecttheswitchpointadjustmentaccordingtotheapplicationasfollows:
P2L1
yellow
S5
S5
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091726
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Operation - Electronic module: Standard
Demandingapplications
1. Ensure material level is well above the probe.
Incaseoftopmountingwithcableextensionthevesselshouldbefilledup.
2. Ensure material level is well below the probe
Itisimportantthatasmuchmaterialbuildupaspossibleisretainingonthesensor.
3. Set to Set-up mode SetdipswitchS5toSet-upmode
4. Adjust switchpoint with poti P2
IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.
TurnP2clockwiseuntilL1juststopsglowing.
5. Set to Run mode SetdipswitchS5toRunmode
Switchpoint adjustment is finished
S5
P2L1
yellow
S5
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 27
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Operation - Electronic module: Standard
Interface detection
LiquidAorfoam
LiquidB
LiquidAorfoam
LiquidB
L1 yellow
1. Immerse probe in liquid A or in foam which should NOT be detected
EnsurethatliquidAorfoam(whichshouldNOTbedetected)iscoveringtheprobe.
LiquidAorfoammusthavealower dielectric constantthanliquidB,whichshouldbedetected.
2. Set to Set-up mode SetdipswitchS5toSet-upmode
3. Adjust switchpoint with poti P2
IfLEDL1(yellow)isOFF,turnpotiP2counterclockwiseuntilL1isON.
TurnP2clockwiseuntilL1juststopsglowing.
Note:ThesensitivityisnowsettedthusthatliquidAorfoamisNOTdetected.
4. Set to Run mode SetdipswitchS5toRunmode
5. Immerse probe in liquid B which should be detected
EnsurethatliquidB(whichshouldbedetected)iscoveringtheprobe.
L1shouldglow.
Switchpoint adjustment is finished
S5
P2L1
yellow
S5
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091728
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Symptom Observation ActionNoAlarmResponse L3(green)off. Checkpowersupplyvoltage.
Alarmdoesn'tswitchwhensensorisuncovered.
L1(yellow)doesn'trespondwhensensorisuncovered.
ReadjusttrippointpotentiometerP2.
L1(yellow)respondswhensensorisuncovered.
CheckthatrelaychangesstatewhenS3istoggledONandOFF.
Alarmdoesn'tswitchonwhensensoriscovered.
L1(yellow)doesn'trespondwhensensoriscovered.
ReadjusttrippointpotentiometerP2.
L1(yellow)respondswhensensoriscovered.
CheckthatrelaychangesstatewhenS3istoggledONandOFF.
L1(yellow)flasheswhenmateriallevelapproachesthealarmsetpoint.
Operation - Electronic module: Standard
Troubleshooting
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 29
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Operation - Electronic module: Digital
Seeseparate"OperatingManual(DigitalElectronic)"
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091730
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Notes for use in Hazardous Locations
Use of this Manual
Foruseandassembly,refertotheinstructionsinthisManual.ItdoescontainallinstructionasrequiredbyATEXDirective2014_34_EU,AnnexII,1/0/6andOrdinanceINMETROnº179/2010
General notesRefertoappropriatecertificateforapplicationinspecifichazardousenvironment.
Theequipmenthasnotbeenassessedasasafetyrelateddevice(asreferredtobyDirective2014_34_EUAnnexII,clause1.5).
Thecertificatenumbershavean'X'suffix,whichindicatesthatspecificconditionofuseapply.Thoseinstallingorinspectingthisequipmentmusthaveaccesstothecertificates.
Qualificationofpersonnel/Servicing/Repair
Installationandinspectionofthisequipmentshallbecarriedoutbysuitablytrainedpersonnelinaccordancewiththeapplicablecodeofpractice(ABNTNBRIEC/EN60079-14andABNT/NBRIEC/EN60079-17inEurope).
Repairofthisequipmentshallbecarriedoutbysuitablytrainedpersonnelinaccordancewiththeapplicablecodeofpractice(e.g.ABNTNBRIEC/EN60079-19withinEurope).
Repairofflameproofpathisnotintended. Componentstobeincorporatedintoorusedasreplacementsintheequipmentshallbefittedbysuitablytrainedpersonnelinaccordancewiththemanufacturer'sdocumentation.
InpotentiallyexplosiveatmospheresopentheenclosureonlywhenCN8000isnotenergized.Turnoffpowerbeforeservicinganydevice(thetransmitterisinoperationwhenthepowersupplyisswitchedon).Incaseofremovingtheunitfromvessel,takecareofprocesspressureandmaterialpassingtheopening.
ATEX:Certificates/ListofStandards
Certificatenumbers:DEKRA18ATEX0042XandDEKRA18ATEX0044X
Seewww.uwt.deforthelatestcertificates
SeeEU-DeclarationofconformityforthelistofstandardsvalidforATEXcertificates
ATEX:Yearofmanufacturing
MarkingonthenameplateisdoneaccordingtoIEC60062asfollows:
Yearofmanufacturing 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029
Markingcode K L M N P R S T U V W X
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 31
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Notes for use in Hazardous Locations
ATEX:Ex-Marking
•DeviceswithATEXapprovalaremarkedonthenameplateasfollows.•IfbothFlameproofandDustignitionproofarepresentonthesamenameplate,atickbox ispresentwheretheenduserneedstoselect(mark)theprotectionmethodusedatthetimeofinstallation.
Dust Ignition Proof withintrinsicallysafeoutputtoprobe(TypecodePos.2W)Electronicmodule:StandardandDigital
Integralversion: II1/2DExia/tb[iaDa]IIICTXDa/Db
Remoteversion: Electronicsenclosure: II2(1)DExiatb[iaDa]IIICTXDb
Levelprobe: II1DExiaIIICTXDa
II1/2DExiaIIICTXDa/Db
Flameproof / Dust Ignition proof withintrinsicallysafeoutputtoprobe(TypecodePos.2T)Electronicmodule:StandardandDigital
Integralversion: II1/2GExia/db[iaGa]IICTXGa/Gb
II1/2DExia/tb[iaDa]IIICTXDa/Db
Remoteversion: Electronicsenclosure: II2(1)GExdbia[iaGa]IICTXGb
II2(1)DExiatb[iaDa]IIICTXDb
Levelprobe: II1GExiaIICTXGa
II1DExiaIIICTXDa
II1/2DExiaIIICTXDa/Db
Intrinsically Safe (TypecodePos.2Y)Elektronicmodule:Digital
Integralversion: II1GExiaIICTXGa
II1/2DExiaIIICTXDa/Db
Remoteversion: Electronicsenclosure: II1GExiaIICTXGa
II2DExiaIIICTXDb
Levelprobe: II1GExiaIICTXGa
II1DExiaIIICTXDa
II1/2DExiaIIICTXDa/Db
Type of protection n(TypecodePos.2G)Elektronicmodule:Digital
Integralversion: II3GExicnAIICTXGc
Remoteversion: Electronicsenclosure: II3GExicnAIICTXGc
Levelprobe: II3GExicIICTXGc
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091732
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
ATEX:Permittedzonesforinstallation
Ambientside
Process side
Shortest lengthandpipeextension
Sliding coupling
Cableversion
Dust applications Gas applications
Marking Da/Db Ga/Gb Ga Gc
EPL Db Gb Ga GcCategory 2D 2G 1G 3GZone 21 1 0 2
EPL Da Ga Ga Gc
Category 1D 1G 1G 3GZone 20 0 0 2
Notes for use in Hazardous Locations
Integral versionDevicescanbeinstalledasfollows:
Dust applications Gas applications
Markingelectronics enclosure
Db Db Ga Gb
EPL Db Db Ga GbCategory 2D 2D 1G 2GZone 21 21 0 1Markingsensorprobe
Da/Db Da Ga Ga
EPL Db Da Ga GaCategory 2D 1D 1G 1GZone 21 20 0 0
EPL Da Da Ga Ga
Category 1D 1D 1G 1GZone 20 20 0 0
Remote versionDevicescanbeinstalledasfollows:
Ambientside
Process side
Remoteversionelectronics enclsoure
Remoteversionsensorprobe
shownexamplarywithrod
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 33
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Specificconditionofuse
Notes for use in Hazardous Locations
Max. permitted temperature close to the enclosure
Iftheprocesstemperatureexceedsthemax.permissibleambienttemperature,themax.resultingtemperatureattheconnectionofthesensorhead(seedottedline)shallnotexceedtherelatedmax.permissibleambienttemperature(seepage36/37),takingtheworstcaseconditionsintoaccount.Thisshallbeverifiedbymeasurementwheninstalled.
process side
temperatureextendedshaft
Electrostatic charge
Theusershallensurethattheequipmentisnotinstalledinalocationwhereitmaybesubjectedtoexternalconditionswhichmightcauseabuild-upofelectrostaticchargeonnon-conductingsurfaces.
Impact / Friction Becausetheenclosureandoptionallytheprocessconnectionoftheequipmentismadeofaluminiumalloy,theapparatusmustbeinstalledso,thatevenintheeventofrareincidents,anignitionsourceduetoimpactorfrictionbetweenenclosureandiron/steelisexcluded,whenusedinpotentiallyexplosiveatmosphererequiringapparatusofequipment1G.
Flameproof joints
Theflameproofjointsarenotintendedtoberepaired.
Transient limitation for Type of protection n
Atransientprotectiondeviceshallbeused,setatalevelnotexceeding140%ofthepeakratedvoltgaeof85V.
Ambient and process temperature range
Therelationbetweentheambientandprocesstemperaturerangesandthesurfacetemperatureortemperatureclassisshowninthethermaldatatablespage36/37.
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091734
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Notes for use in Hazardous Locations
Intrinsically safe supply
Forintrinsicallysafemodels,powermustbesuppliedfromanIntrinsicallySafepowersource,otherwiseprotectionisnolongerguaranteed.
Process pressure Thedeviceconstructionallowsprocessover-pressureupto10or25bar(146or365psi).Thispressureisallowedfortestpurposes.ThedefinitionoftheExapprovalsareonlyvalidforacontainer-over-pressurebetween-0.2..+0.1bar(-2.9..+1.45psi).Forhigherorlowerpressurestheapprovalsarenotvalid.
Process and ambient temperature
Pleasechecktheambientandprocesstemperaturespage36/37forthespecificconfigurationyouareabouttouseorinstall.
Chemical resistanceagainst the medium
Iftheequipmentislikelytocomeintocontactwithaggressivesubstances,thenitistheresponsibilityoftheusertotakesuitableprecautionsthatpreventitfrombeingadverselyaffected,thusensuringthatthetypeofprotectionisnotcompromised.Aggressivesubstances:e.g.acidicliquidsorgasesthatmayattackmetals,orsolventsthatmayaffectpolymericmaterials.Suitableprecautions:e.g.establishingfromthematerial'sdatasheetthatitisresistanttospecificchemicals.
Cable entry devices /blanking elementsgeneral
DustIgnitionProof:Foruseininpotentiallyexplosivedustatmospheres:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedtype,suitablefortheconditionsofuseandcorrectlyinstalled.TheminimumingressprotectionrequirementofIP6XaccordingtoEN60529mustbesatisfied.
Flameproof:Foruseinpotentiallyexplosivegasatmospheres:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedflameprooftype,suitablefortheconditionsofuseandcorrectlyinstalled.
IntrinsicallySafe/Typeofprotectionn:Thecableentrydevicesandtheblankingelementsofunusedaperturesshallbeofacertifiedtype,suitablefortheconditionsofuseandcorrectlyinstalled.TheminimumingressprotectionrequirementofIP64accordingtoEN60529mustbesatisfied.
Versionswithcableglandmountedbydefault:Theusedcableglandisonlysuitableforfixedinstallations.Theinstallerisresponsibleforprovidingappropriatestrain-relieftopreventpullingortwisting.
Versionswithblankingelementmountedbydefault:Blankingelementsarenottobeusedwithanyformofadaptorsorreducers.
Versions with cable gland / blanking element mounted by default
Below-mentionedcablediametersandtighteningtorquesofthenutresp.blankingelementshallbeobservedfortheinstallation.
CableglandM20x1.5(DustIgnitionProof,IntrinsicallySafe,Typeofprotectionn)Cablediameter:6mmto12mmTighteningtorque:Dependingontheusedcableandthereforetobedeterminedbytheuser
CableglandM20x1.5(Flameproof)Cablediameter:Bedding3.1mmto8.6mm/Overall6.1mmto13.1mmTighteningtorque:Numberofturnsdependingontheoverallcablediameteroftheusedcable(e.g.1turn/cablediameter12.5mmto5.5turns/cablediameter6.5mm)
BlankingelementM20x1.5(allversions)Tighteningtorque:32.5Nm
Warnings for installation
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 35
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Notes for use in Hazardous Locations
Ambientandprocesstemperaturerange,max.SurfaceTemperatureandTemperatureClass
ATEX:
process side
thermalisolator
ambientside
Flameproof and Dust Ignition Proof withintrinsicallysafeoutputtoprobe(TypecodePos.2W,T)Electronicmodule:StandardandDigital
- Integral version-Remoteversion:levelprobe
Ambienttemperaturerange
Processtemperaturerange
Max.Surfacetemperature(EPLDa)
Max.Surfacetemperature(EPLDb)
Temperatureclass
(EPLGaorGb)-40to+45°C(-40to+113°F) -40to+45°C(-40to+113°F)(2) T200 95°C T55°C T6
-40to+60°C(-40to+140°F) -40to+60°C(-40to+140°F)(2) T200 110°C T70°C T5
-40to+80°C(-40to+176°F) -40to+95°C(-40to+203°F)(1)(2) T200 145°C T90°C T4
-40to+80°C(-40to+176°F) -40to+125°C(-40to+257°F)(1)(2) T200 175°C T90°C T3
-Remoteversion:electronicsenclosureAmbienttemperature
rangeMax.Surfacetemperature
(EPLDb)Temperatureclass
(EPLGb)-40to+45°C(-40to+113°F) T55°C T6
-40to+60°C(-40to+140°F) T70°C T6
-40to+80°C(-40to+176°F) T90°C T5
(1)Forprocesstemperature>85°C:Onlyapplicableforversionswiththermalisolator(2)WithoptionFFKMO-ringseal:Lowerprocesstemperaturelimitedto-20°C(-4°F)
Intrinsically safe(TypecodePos.2Y)Electronicmodule:Digital
- Integral version-Remoteversion:levelprobe
Ambienttemperaturerange
Processtemperaturerange
Max.Surfacetemperature(EPLDa)
Max.Surfacetemperature(EPLDb)
Temperatureclass
(EPLGaorGb)-40to+45°C(-40to+113°F) -40to+45°C(-40to+113°F)(2) T200 95°C T55°C T6
-40to+60°C(-40to+140°F) -40to+60°C(-40to+140°F)(2) T200 110°C T70°C T5
-40to+60°C(-40to+140°F) -40to+95°C(-40to+203°F)(1)(2) T200 145°C T70°C T4
-40to+60°C(-40to+140°F) -40to+125°C(-40to+257°F)(1)(2) T200 175°C T70°C T3
Type of protection n(TypecodePos.2G)Electronicmodule:Digital
- Integral version-Remoteversion:levelprobe
Ambienttemperaturerange
Processtemperaturerange
Temperatureclass(EPLGc)
-40to+45°C(-40to+113°F) -40to+75°C(-40to+167°F)(2) T6
-40to+60°C(-40to+140°F) -40to+90°C(-40to+194°F)(1)(2) T5
-40to+60°C(-40to+140°F) -40to+125°C(-40to+257°F)(1)(2) T4
-Remoteversion:electronicsenclosureAmbienttemperature
rangeTemperatureclass
(EPLGc)-40to+45°C(-40to+113°F) T6
-40to+60°C(-40to+140°F) T4
Ambienttemperaturerange
Max.Surfacetemperature(EPLDb)
Temperatureclass(EPLGa)
-40to+45°C(-40to+113°F) T55°C T6
-40to+60°C(-40to+140°F) T70°C T4
-Remoteversion:electronicsenclosure
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091736
Capanivo®
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Notes for use in Hazardous Locations
Ambienttemperaturerange
Process temperaturerange
-20to+60°C(-4to+140°F) -20to+60°C(-4to+140°F)
Dust ignition proofThemaximumsurfacetemperatureofT100°Cisbasedonamaximumambienttemperatureof+85°C.
Flameproof withintrinsicallysafeoutputtoprobe
ApplicationinZone0(cat1G):
ApplicationinZone1(cat2G):
Ambienttemperaturerange
Process temperaturerange
Temperatureclass
-40to+70°C(-40to+158°F) -40to+85°C(-40to+185°F) T6
-40to+85°C(-40to+185°F) -40to+95°C(-40to+203°F)(1) T5
-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F)(1) T4
INMETRO:
FM / CSA:
Ambienttemperaturerange
Process temperaturerange
Temperatureclass
-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F) T4
Ambienttemperaturerange
Process temperaturerange
Temperatureclass
-40to+40°C(-40to+40°F) -40to+40°C(-40to+40°F) T6
-40to+85°C(-40to+185°F) -40to+125°C(-40to+257°F) T4
Intrinsically safeInstallationshallbedoneaccordingto"FM/CSAApproval-Connectiondrawing"onpage23
Explosion proof / Dust ignition proof
(1)Forprocesstemperature>85°C:Onlyapplicableforversionswiththermalisolator
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 37
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Probe modifications
Shorteningthecable(cableversion)
CAUTION: Possibleonlywiththegeneralpurposeconfiguration;pleaseverifyagainstproductnameplate.
Preparation
Determinetherequiredcablelength,andsubtractthatamountfromtheactuallength,tofindtheexcesslengthtocutoff.Forexample:10m(actuallength)minus9m(requiredlength)=1m(excess)
Steps1.Unscrewthecableglandcompressionnuttorelievethesealingconeandreleasethecable.
2.Unscrewtheprobesleevefromthelowerassemblyusingtwo17mm(0.67")wrenchesacrosstheflatsurfaces,asshownbelow.
a.Placetwowrenchesontheflatsurfacesoftheprobeasshown:holdthe probesleevestill,andturnthelowerwrenchcounter-clockwisetoloosen theprobelowerassembly.
b.Removethelowerassemblybyturningthethreadedelectrodeend counter-clockwise:thisexposesthethreeleads,thetensionblock,and thesteelspacer.
flatsurface
flatsurface
lowerwrench
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091738
Capanivo®
cable glandcompression nut
probe sleeve
probe, lowerassembly
actuallength
requiredlength
excesslength
page
Level limit switchSeries CN 8000Technical Information / Instruction manual
Probe modifications
3.Removetheheatshrinkinsulationcoveringthesolderconnections.
4.Unsoldertheconnections. Note:Donotcuttheconnectionstotheprobeleads,asthiscanrenderthemtooshorttoworkwithlater.
5.Removethetensionblock,andsaveitforre-useinstep7.
6.Calculatetheexcesscable,thenaddbackanallowanceof75mm(3")formakingtheconnections: Forexample,1000mm=excess less75mm=allowanceforconnections 925mm=excesscabletoberemoved
7.Cutofftheexcesscable. Caution:Topreventwiresfrombeingpulledthroughthecablebundle,secureeachwireclosetowheretheouterblackjacketstopspriortostrippingcableinsulationfromit. 8.Removeapproximately75mm(3")ofcablejacket,shield,andfillerstrands.
9.Cutofftheexcesscablecore,makingsurethecutiscleanandsquare
10.Replacethesteelspacerandtensionblock,thenshortentheleadstoapproximately40mm(1.6").
11.Preparetheleadsforsoldering,andifheatshrinkisusedtoinsulatesplices,remembertoslipontheheatshrinkbeforesolderingtheleads.(Note:whiteheatshrinkhasbeenappliedtotheorangewiretosimplifycorrectconnection.) 12.Makethesolderconnectionsandpositiontheheatshrinktocompletelyinsulateeachsolderconnectionbeforeshrinkingit.
iead
25mm(0,37")heat shrinkinsulation
steel spacer
tensionblock
cablecore
1
2
3
4
5
6
7
8
9
10
11
12CN 8000 j gi150917 39
Capanivo®
Level limit switchSeries CN 8000Technical Information / Instruction manual
page
Probe modifications
13.Removeanyexcesscablecore,ifnecessary.
14.ApplyPTFEtypetape/sealanttoallthreads.
15.Addapre-twisttothewiresbeforescrewingtheprobesleeveandlowerprobeassemblytogether:holdtheprobesleevestill,andgentlyturnthelowerprobeassemblycounter-clockwiseabout5fullturns.Thisavoidsthewiresbeingbrokenwhentheprobeandprobesleeveareassembled.
16.Screwthelowerprobeassemblyclockwiseintotheprobesleeve,andtightenitwitha17mm(0.67")wrench.
17.Checkthattheinstrumentisoperatingcorrectly,usingthetestprocedure(seeexternalOperatingManual).
1
2
3
4
5
6
7
8
9
10
11
12j CN 8000gi15091740
Capanivo®