MODELS: TCP/ TRTA / TRTAU/ TRTH/ TRTHU
T SERIES: TUBULAR FRAMEAIR HANDLING UNITS
T SERIES: 800-30,000 CFM AHU
Page No.
Product Overview 1
Unit Selection Guideline 2
Step 1: Selection Data • Pressure Drop 3
Step 3: Selection Data • Fan • Forward Curved Type 4 - 5
Step 3: Selection Data • Fan • Airfoil Type 6 - 7
Step 3: Selection Data • Fan • Plenum Type 8 - 9
Step 4: CFM / Unit Dimensions 10
Step 5: Module • Filter • Types 11
Step 5: Module • Filter • Flat Filter Selection 12 - 13
Step 5: Module • Mixing 14
Step 5: Module • Coil • Cooling 15
Contents
1
T SERIES: 800-30,000 CFM AHU
PRODUCT OVERVIEWThermal Corporation’s T Series (Tubular Frame) of air handlers are constructed around a weldedtubular frame. The flexibility of the tubular design lends itself to a wide range of available sizes andconfigurations. By providing a customizable platform, the T Series units provide the optimum balancein quality and value.
Construction Features:• 16 ga. fully welded tubular steel frame to form a unitized
assembly.
• 16 ga. galvanized steel panels with closed cellneoprene gasket around the perimeter. All panels areinstalled with 1/4" sealed fasteners. Panels can beremoved without affecting the structural integrity of theunit.
• 2", 3", or 4" thick walls with single or double wallconstruction.
• Structural steel fan bases are internally spring-isolated.
• AMCA-rated forward-curved (DWDI), housed airfoil(DWDI), or plenum fans (SWSI) are available.
• Full walk-on floor of galvanized steel. True "doublebottom" construction with 4" thick insulation.
• AHRI certified coils in 1/2" or 5/8" O.D. copper tubes. 1"O.D. steam distributing coils are also available uponrequest.
Design Flexibility:• Units are customized to your particular application.
• Any unit size available up to 30,000 CFM.
• Units can be designed for indoor or outdoorapplications. Only indoor units are available in verticalconfigurations.
• Special third-party vendor items such as humidifiers,blenders, evaporative coolers, and IFB coils can befactory mounted.
• Units can be designed with multiple fans for low profilecabinets or redundant operation.
• Full selection of air filters to meet indoor air qualitystandards.
• Outdoor units can be provided with roof curbs.
TUBULAR FRAME AIR HANDLING UNITS
MODELS:
TCP Central Plant
TRTA Rooftop
TRTAU Rooftop with Utility Vestibule
TRTH Rooftop Hospital
TRTHU Rooftop Hospital with Utility Vestibule
TUBULAR FRAME CONSTRUCTIONCUSTOM AIR HANDLERS
2
T SERIES: 800-30,000 CFM AHU
Getting StartedThe designer must know the following information in order to properly design a Thermal T Series air handling unit:• Unit Airflow • Coil Conditions• Total Static Pressure (TSP) • Filtration Requirements• Unit Configuration
UNIT SELECTION GUIDELINESShippingStandard legal loads are used to ship air handling units that are less than or equal to 106" tall and 102" wide. Units less than or equalto 144" wide and 312" in direction of airflow can be built and shipped as one piece, but will require special permits. Demounts shouldbe added when using these dimensions.As long as there are no shipping limitations, multiple section air handlers ship as a single unit, unless otherwise requested. Modularsections may then be demounted in the field by others.
Fan Type GuidelinesThe fans that produce the highest mechanical efficiency are DWDI housed airfoil. However, when you have a blow throughapplication, unducted discharge system effect losses often offset their efficiency. While DWDI housed airfoil fans can be used inapplications greater than 4" w.g., DWDI forward curved fans offer quiet operation for return air applications and static pressures lessthan 4" w.g.
SWSI Plenum fans pressurize the entire plenum and generate very little velocity pressure, making them ideal for blow throughapplications and when you require multiple duct take-offs. Built-in noise control characteristics are accomplished as air is dischargedagainst the plenum casing walls. Thermal utilizes plenum fans with a large quantity of blades.
SizingNote: Alternate unit sizes are available. Use the following guidelines to determine available fin height and length for a given unit outercasing height and width:
Fin Height
1. Standard units with 1 coil high, allow fin height +11"2. Standard units with 2 coils high, allow fin height +13"3. Standard units with 3 coils high, allow fin height +15"
Fin Length1. Standard units with 1 coil wide, allow fin length +14"2. Outdoor units with a 12" internal pipe chase, allow total fin
length +30"
Miscellaneous Options
1. Cleanable return bends, allow fin length +15"
2. 4" connections, allow fin height +12" and fin length +16"
Note: These guidelines do not include outdoor roof pitch andare based on 5" unit base, 2" casing and up to 3" coilconnections.
STEP 1:
Using a copy of the form provided at the back of theCatalog & Design Guide, select whether the unit isindoor or outdoor. Next, enter the CFM and TSP of eachfan.
If you are only provided with the external static pressure(ESP) use the quick pressure drop tables on thefollowing pages to establish the total static pressure(TSP) of the unit.
STEP 2:
Now that you have established the TSP and CFM usethe supplied fan selection software to pick the properfan(s). Make sure to record the type of fan(s), requiredhorsepower(s), and motor frame size(s).
STEP 3:
Record the minimum cabinet height and length requiredfor your fan from the fan reference tables. Motorposition and size determine the minimum cabinet width.
STEP 4:
Now turn to the unit selection table. Locate theselection that meets your airflow requirements usingyour total airflow. Move right and down to any otherblock that will work if cabinet height and width is lessthan the minimum required for the fan. Enter thecabinet size in the space provided on the selectiontemplate.
STEP 5:
From the unit selection grid, enter the coil finned heightand width. Proceed to the component section andselect the required modules.
3
T SERIES: 800-30,000 CFM AHU
STEP 1:Selection Data • Pressure Drop • Air
5/8" Cooling Coils
Face Velocity (FPM)FPI 450 500 550
6 Row 8 Row 10 Row 12 Row 6 Row 8 Row 10 Row 12 Row 6 Row 8 Row 10 Row 12 Row
6 0.50 0.62 0.76 0.90 0.62 0.72 0.89 1.05 0.74 0.86 1.02 1.238 0.62 0.76 0.90 1.03 0.72 0.89 1.05 1.22 0.84 1.04 1.22 1.4110 0.76 0.94 1.10 1.28 0.89 1.09 1.30 1.53 1.04 1.28 1.51 1.7712 0.89 1.10 1.34 1.55 1.06 1.31 1.58 1.81 1.21 1.51 1.80 2.17
5/8" Heating Coils
Face Velocity (FPM)FPI 500 600 700 800
1 Row 2 Row 1 Row 2 Row 1 Row 2 Row 1 Row 2 Row
6 0.06 0.12 0.08 0.16 0.11 0.22 0.14 0.288 0.08 0.16 0.11 0.22 0.14 0.27 0.18 0.3310 0.10 0.20 0.14 0.28 0.18 0.35 0.22 0.4012 0.12 0.25 0.17 0.33 0.22 0.40 0.27 0.50
Based on 80/67°F EAT, 55/54°F LAT, 42°F EWT - 12°F ΔTUnits are "w.g.
Based on 55°F EAT, 80°F LAT, 180°F EWT - 20°F ΔTUnits are "w.g.
Standard Vee-Blade Damper
Velocity (FPM)Damper Size
1000 1500 2000
24" x 24" 0.11 0.24 0.47
36" x 36" 0.08 0.22 0.38
Rain Hood w/ Bird Screen
Dual Drainable Louvers2
Damper / Louver Pressure Loss1
Aluminum Airfoil Blade Damper
Velocity (FPM)Damper Size
1000 1500 2000
24" x 24" 0.13 0.19 0.31
36" x 36" 0.06 0.16 0.21
Velocity (FPM)Damper Size
500 750 1000 1250 1500
24" x 24" 0.05 0.09 0.12 0.15 0.20
Units are "w.g. Units are "w.g.
Velocity (FPM)Gross Face Velocity 200 300 400 500 600 700 800 900 1000
A. P. D. 0.02 0.05 0.09 0.13 0.16 0.24 0.30 0.40 0.50
Units are "w.g.Note:1. Values based on unducted mounting.2. Nailor model 1604DD.
Units are "w.g.
4
T SERIES: 800-30,000 CFM AHU
STEP 3:Selection Data • Fan • Forward Curved TypeDimensions
FC Minimum Width Motor Beside MinimumFan 143T/ 182T/ 213T/ 254T/ 284T/ 324T/ 364T/ 404T Width Motor DWSize 145T 184T 215T 256T 286T 326T 365T & up Behind
43 12 3/1644 13 3/847 15 1/450 17 5/8
18 65 65 71 77 – – – – 53 21 5/1620 71 71 77 77 83 – – – 64 24 1/422 71 71 77 83 83 89 – – 67 26 9/1625 77 77 83 83 89 89 – – 71 30 1/228 – 83 83 89 89 95 95 – 74 33 7/1630 – – 89 89 95 95 101 107 76 36 1/8
9101215
CONTACT FACTORY
Frame HP
143T 1145T 1.5, 2182T 3184T 5213T 7.5215T 10254T 15256T 20284T 25286T 30324T 40326T 50364T 60365T 75404T 100
Motor Chart
DW
WDW
W
Motor Beside Motor Behind
WIDTH
5
T SERIES: 800-30,000 CFM AHU
STEP 3: cont.Selection Data • Fan • Forward Curved TypeDimensions
L1
10
10
11
13
14
16
17
18
19
21
MinimumFC H* L FH2*
Fan Size Motor Motor DH FH1*1" 2" Beside Behind 1" 2"
9 29 31 CF 36 10 5/8 22 5/8 11 -
10 31 33 CF 38 11 7/8 22 5/8 11 -
12 34 36 CF 40 13 7/8 24 7/8 11 -
15 38 39 CF 46 16 1/4 25 11 12 3/4
18 43 44 48 53 19 5/16 26 1/4 11 12 3/4
20 49 51 48 59 22 5/16 27 1/8 11 12 3/4
22 53 55 48 62 24 1/8 29 11 12 3/4
25 58 60 52 70 27 7/16 30 1/2 11 12 3/4
28 63 65 52 75 29 13/16 32 1/8 11 12 3/4
30 67 69 55 78 32 1/2 36 1/2 11 12 3/4
Blow ThroughDiffuser Section
* Listed as 1" or 2" spring deflection.CF = Contact Factory
H
FH1
DH
L
FH2
DHH
L
FH1DH
L
H
6"DHL
H
DH 7"
H
L
FH2DH
H
L
L1
THD-CW(Top Horizontal)
UBD-CW(Up Blast)
DBD-CW(Down Blast)
BHD-CCW(Bottom Horizontal)
UBD-CCW(Up Blast)
DBD-CCW(Down Blast)
Blow ThroughDiffuser Section
PerforatedDiffuser
LENGTH AND HEIGHT
6
T SERIES: 800-30,000 CFM AHU
STEP 3: cont.Selection Data • Fan • Airfoil TypeDimensions
Frame HP
143T 1145T 1.5, 2182T 3184T 5213T 7.5215T 10254T 15256T 20284T 25286T 30324T 40326T 50364T 60365T 75404T 100
AF Minimum Width Motor Beside MinimumFan 143T/ 182T/ 213T/ 254T/ 284T/ 324T/ 364T/ 404T Width Motor DWSize 145T 184T 215T 256T 286T 326T 365T & up Behind
45 13 5/848 16 5/852 18 3/454 20 1/457 22 1/4
18 70 72 75 81 – – – – 64 24 3/420 71 74 77 83 – – – – 66 2722 75 77 80 86 – – – – 70 30 1/824 77 77 83 89 89 – – – 73 33 1/427 81 83 86 92 94 – – – 76 36 1/230 85 87 90 96 98 102 – – 80 40 1/233 90 92 95 101 103 107 109 – 84 44 5/836 94 96 99 105 107 111 113 – 89 49 1/440 99 101 104 110 112 116 118 121 94 54 3/844 105 107 110 116 118 122 124 128 99 60
1012131516
CONTACT FACTORY
Motor Chart
DW
WDW
W
Motor Beside Motor Behind
WIDTH
7
T SERIES: 800-30,000 CFM AHU
L1
101112131415161718202123252729
AF Minimum
Fan H* L FH2*
Size Motor Motor DH FH1*1" 2" Beside Behind 1" 2"
10 35 36 – 40 11 1/8 22 5/8 12 –12 39 41 – 46 13 5/8 22 5/8 12 –13 41 43 – 52 15 1/8 24 7/8 12 –15 44 46 – 54 16 3/4 25 12 –16 47 49 – 57 18 1/2 26 1/4 12 –18 50 52 52 64 20 1/2 27 1/8 12 12 3/420 54 56 52 67 22 1/2 27 1/8 12 12 3/4 22 58 60 58 73 24 7/8 29 12 12 3/424 62 64 59 77 27 3/8 30 1/2 12 12 3/427 67 69 59 80 30 1/4 32 1/8 12 12 3/430 75 75 63 88 33 1/2 34 12 12 3/433 80 80 66 92 36 7/8 36 1/2 12 12 3/436 87 87 74 99 40 3/4 39 1/8 12 12 3/440 94 94 80 109 44 7/8 41 5/8 12 12 3/444 102 102 87 114 49 5/8 44 7/8 12 12 3/4
Blow ThroughDiffuser Section
STEP 3: cont.Selection Data • Fan • Airfoil TypeDimensions
* Listed as 1" or 2" spring deflection.
H
FH1
DH
L
FH2
DHH
L
FH1DH
L
H
6"DHL
H
DH 7"
H
L
FH2DH
H
L
L1
THD-CW(Top Horizontal)
UBD-CW(Up Blast)
DBD-CW(Down Blast)
BHD-CCW(Bottom Horizontal)
UBD-CCW(Up Blast)
DBD-CCW(Down Blast)
Blow ThroughDiffuser Section
PerforatedDiffuser
LENGTH AND HEIGHT
8
T SERIES: 800-30,000 CFM AHU
Frame HP
143T 1145T 1.5, 2182T 3184T 5213T 7.5215T 10254T 15256T 20284T 25286T 30324T 40326T 50364T 60365T 75404T 100
Plenum Minimum Width Motor BehindFan 143T/ 182T/ 213T/ 254T/ 284T/ 324T/ 364T/Size 145T 184T 215T 256T 286T 326T 365
123 51 51 51 – – – –133 51 51 51 – – – –153 55 55 55 – – – –163 55 55 55 – – – –183 50 53 58 – – – –203 47 53 58 63 – – –223 51 55 59 65 – – –243 54 54 60 66 – –273 57 57 61 66 71 – –303 73 73 73 80 85 – –333 77 77 77 80 86 – –363 81 81 81 81 86 92 –403 85 85 85 85 87 93 –443 – 93 93 93 93 94 –493 – – 99 99 99 99 101
Motor ChartSTEP 3: cont.Selection Data • Fan • Plenum TypeDimensions
Plenum Minimum Width Motor BesideFan 143T/ 182T/ 213T/ 254T/ 284T/ 324T/ 364T/Size 145T 184T 215T 256T 286T 326T 365
183 58 60 62 – – – –203 59 61 63 67 – – –223 63 65 67 71 – – –243 66 68 70 74 – –273 69 71 73 77 82 – –303 79 81 83 87 92 – –333 83 85 87 91 96 – –363 87 89 91 95 100 103 –403 91 93 95 99 104 107 –443 – 101 103 107 112 115 –
123133153163
ARRANGEMENT 1
W
W
Motor Beside
Motor Behind
WIDTH
9
T SERIES: 800-30,000 CFM AHU
MinimumPlenum H* L
Fan Motor Motor DHSize 1" 2" Beside Behind
123 33 35 – 36 20 1/2133 33 35 – 36 21153 36 38 – 36 21 5/8163 36 38 – 36 20 3/4183 39 41 37 45 21 7/8203 40 42 37 50 23 3/4223 44 46 38 52 25 5/8243 47 49 40 56 29 1/8273 50 52 43 60 31 1/4303 53 55 46 62 35 1/4333 57 59 44 65 38 1/4363 61 63 47 70 42 1/8403 65 67 49 72 45 1/4443 73 75 55 78 48 3/4493 80 81 – 83 53 3/8
L
DH DH
L
Motor Beside Motor Behind
LENGTH
STEP 3: cont.Selection Data • Fan • Plenum TypeDimensions
* Listed as 1" or 2" spring deflection.
10
T SERIES: 800-30,000 CFM AHU
UW 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138UH FH/FL 16 22 28 34 40 46 52 58 64 70 76 82 88 94 100 106 112 118 124
28 15 833 1146 1458 1771 2083 2396 2708 30211.67 2.29 2.92 3.54 4.17 4.79 5.42 6.04
33 21 1167 1604 2042 2479 2917 3354 3792 4229 4667 51042.33 3.21 4.08 4.96 5.83 6.71 7.58 8.46 9.33 10.21
37 24 1833 2333 2833 3333 3833 4333 4833 5333 5833 6333 68333.67 4.67 5.67 6.67 7.67 8.67 9.67 10.67 11.67 12.67 13.67
39 27 2063 2625 3188 3750 4313 4875 5438 6000 6563 7125 7688 82504.13 5.25 6.38 7.50 8.63 9.75 10.88 12.00 13.13 14.25 15.38 16.50
45 33 3208 3896 4583 5271 5958 6646 7333 8021 8708 9396 10083 10771 11458 12146 12833 13521 142086.42 7.79 9.17 10.54 11.92 13.29 14.67 16.04 17.42 18.79 20.17 21.54 22.92 24.29 25.67 27.04 28.42
50 39 3792 4604 5417 6229 7042 7854 8667 9479 10292 11104 11917 12729 13542 14354 15167 15979 167927.58 9.21 10.83 12.46 14.08 15.71 17.33 18.96 20.58 22.21 23.83 25.46 27.08 28.71 30.33 31.96 33.58
53 42 4958 5833 6708 7583 8458 9333 10208 11083 11958 12833 13708 14583 15458 16333 17208 180839.92 11.67 13.42 15.17 16.92 18.67 20.42 22.17 23.92 25.67 27.42 29.17 30.92 32.67 34.42 36.17
57 45 6250 7188 8125 9063 10000 10938 11875 12813 13750 14688 15625 16563 17500 18438 1937512.50 14.38 16.25 18.13 20.00 21.88 23.75 25.63 27.50 29.38 31.25 33.13 35.00 36.88 38.75
60 48 6667 7667 8667 9667 10667 11667 12667 13667 14667 15667 16667 17667 18667 19667 2066713.33 15.33 17.33 19.33 21.33 23.33 25.33 27.33 29.33 31.33 33.33 35.33 37.33 39.33 41.33
66 54 8625 9750 10875 12000 13125 14250 15375 16500 17625 18750 19875 21000 22125 2325017.25 19.50 21.75 24.00 26.25 28.50 30.75 33.00 35.25 37.50 39.75 42.00 44.25 46.50
73 (2) 30 10833 12083 13333 14583 15833 17083 18333 19583 20833 22083 23333 24583 2583321.67 24.17 26.67 29.17 31.67 34.17 36.67 39.17 41.67 44.17 46.67 49.17 51.67
79 (2) 33 13292 14667 16042 17417 18792 20167 21542 22917 24292 25667 27042 2841726.58 29.33 32.08 34.83 37.58 40.33 43.08 45.83 48.58 51.33 54.08 56.83
87 (2) 36 16000 17500 19000 20500 22000 23500 25000 26500 28000 2950032.00 35.00 38.00 41.00 44.00 47.00 50.00 53.00 56.00 59.00
93 (2) 39 18958 20583 22208 23833 25458 27083 28708 3033337.92 41.17 44.42 47.67 50.92 54.17 57.42 60.67
98 (2) 42 22167 23917 25667 27417 29167 3091744.33 47.83 51.33 54.83 58.33 61.83
111 (2) 48 27333 2933354.67 58.67
Based on 5" Unit Base and 2" double Wall Casing.
LEGEND:
Example: Cabinet "H" = 37Cabinet "W" = 48
Coils (qty.) FH x FL = (1) 24" x 34"
2833 = CFM @ 500 fpm5.67 = Coil Face Area Ft²
STEP 4:CFM / Unit Dimensions
11
T SERIES: 800-30,000 CFM AHU
Filter Filter Filter MERV Initial FinalRecommended
Size Type Efficiency Rating Resistance Resistance500 FPM
2" Pleated30% MERV 7 0.28 1.00 0.6460% MERV 11 0.31 1.00 0.66
4" Pleated30% MERV 7 0.23 1.00 0.6260% MERV 11 0.25 1.00 0.63
40-45% MERV 9 0.25 1.50 0.88
12" Cartridge60-65% MERV 11 0.28 1.50 0.8980-85% MERV 13 0.44 1.50 0.9790-95% MERV 14 0.51 1.50 1.0140-45% MERV 9 0.30 1.00 0.65
21" Bag60-65% MERV 11 0.36 1.00 0.6880-85% MERV 13 0.43 1.00 0.7290-95% MERV 14 0.52 1.00 0.76
STEP 5:Module • Filter • Types
Filter Depth FL
2 124 12
123 18223 24
SINGLE FILTERSECTION
Notes:1. Must be selected
@< 500 fpm.2. Add 6" to FL if this
section is the first orlast section in the airhandler.
3. Requires header Track
AL
24
ANGLE FILTER SECTION
Notes:
1: Available with 2" or 4"Pleated Filters.
2. Add 6" to AL if thissection is the first orlast section in the airhandler.
3. Contact factory forfilter sizes.
Pre-Filter Final-Filter CLDepth Depth
4 146 16
212 2022 264 14
4 6 1612 2222 32
CARTRIDGE/BAG FILTER SECTIONFL CL
AL
12
T SERIES: 800-30,000 CFM AHU
UW 30 36 42 48 54 60 66 72 78 84UH
(1)12x24 (1)12x24 (1)12x24 (1)12x24 (2)12x24 (2)12x24 (2)12x24 (2)12x24
28 2.00 2.00 2.00 2.00 4.00 4.00 4.00 4.001000 1000 1000 1000 2000 2000 2000 2000
(1) 20x24 (1) 20x24 (1) 20x24 (2) 20x20 (2) 20x24 (2) 20x24 (3) 20x20 (3) 20x20 (3) 24x20 (4) 20x20
33 3.33 3.33 3.33 5.56 6.67 6.67 8.33 8.33 10.00 11.111667 1667 1667 2778 3333 3333 3667 4000 4000 4000
(1) 24x24 (1) 12x24 (1) 20x24 (2) 24x24 (1) 12x24 (1) 12x24 (2) 20x24 (3) 24x24 (4) 20x24(1) 20x24 (1) 24x24 (2) 20x24 (2) 24x24 (1) 24x2437
4.00 5.33 7.33 8.00 8.67 10.00 10.67 12.00 11.112000 2667 3667 4000 4333 5000 5333 6000 6000
(1) 24x24 (1) 12x24 (2) 20x24 (2) 24x24 (1) 12x24 (1) 12x24 (2) 20x24 (3) 24x24 (4) 20x24
39 (1) 20x24 (2) 20x24 (2) 24x24 (1) 24x244.00 5.33 6.66 8.00 8.67 10.00 10.67 12.00 11.112000 2667 3667 4000 4333 5000 5333 6000 6000
(2) 12x24 (2) 12x24 (2) 12x24 (2) 12x24 (3) 12x24 (3) 12x24 (3) 12x24 (3) 12x24
45 (1) 24x24 (1) 24x24 (2) 20x24 (2) 24x24 (2) 24x24 (2) 24x24 (3) 24x24 (3) 24x248.00 8.00 10.67 12.00 14.00 14.00 18.00 18.004000 4000 5335 6000 7000 7000 9000 9000
(2) 12x24 (4) 20x20 (4) 20x24 (4) 20x24 (6) 20x20 (6) 20x20 (6) 20x24 (6) 20x24
50 (1) 24x248.00 11.11 13.33 13.33 16.67 16.67 20.00 20.004000 5555 6665 6665 8335 8335 10000 10000
(4) 20x20 (4) 20x24 (4) 20x24 (6) 20x20 (4) 20x20 (3) 20x24 (3) 20x24
53 (2) 20x24 (3) 24x24 (3) 24x2411.11 13.33 13.33 16.67 17.78 22.00 22.005555 6665 6665 8335 8890 11000 11000
(4) 20x24 (4) 24x24 (6) 20x20 (4) 20x24 (6) 24x24 (6) 24x24
57 (2) 24x2413.33 16.00 16.67 21.33 24.00 24.006665 8000 8335 10665 12000 12000
(4) 20x24 (2) 12x24 (2) 12x24 (4) 20x24 (6) 24x24 (6) 24x24
60 (4) 24x24 (4) 24x24 (2) 24x2413.33 20.00 20.00 21.33 24.00 24.006665 8665 10000 10665 12000 12000
(2) 12x24 (2) 12x24 (4) 20x24 (6) 24x24 (3) 12x24
66 (4) 20x24 (4) 24x24 (2) 24x24 (6) 20x2417.33 20.00 21.33 24.00 26.008665 10000 10665 12000 13000
(4) 12x24 (4) 24x24 (4) 24x24 (4) 24x24
73 (4) 24x2424.00 16.00 16.00 16.0012000 12000 15000 15000
(6) 20x20 (3) 20x24 (3) 20x24
79 (3) 20x24 (6) 24x24 (6) 24x2426.67 34.00 34.0013335 16000 17000
(3) 20x24 (9) 24x24
87 (6) 24x2434.00 36.0016000 18000
(12) 20x24
9340.0020000
98
111
STEP 5:Module • Filter • Flat Filter Selection
LEGEND:
Example: Cabinet "H" = 39Cabinet "W" = 48
(2) 20x24 Filter (qty.) HxW6.66 Filter Face Area3667 Maximum CFM
Note: 1. Based on 5" Unit Base and 2" double Wall Casing.2. Filters are side loading.3. Front loading filters available, contact factory.
13
T SERIES: 800-30,000 CFM AHU
UW 90 96 102 108 114 120 126 132 138UH
28
33
(4) 20x24 (2) 20x24 (2) 24x2437
13.33 14.676667 7333
(1) 12x24 (2) 20x24 (4) 24x24
39 (3) 24x24 (2) 24x2414.00 14.67 16.007000 7333 8000
(4) 12x24 (4) 12x24 (4) 12x24 (4) 12x24 (5) 12x24 (5) 12x24
45 (3) 24x24 (3) 24x24 (4) 24x24 (4) 24x24 (4) 24x24 (4) 24x2420.00 20.00 24.00 24.00 26.00 26.0010000 10000 12000 12000 13000 13000
(6) 20x20 (4) 20x20 (8) 20x24 (10) 20x20 (6) 20x20 (4) 20x20 (12) 20x20 (10) 20x20
50 (2) 20x24 (4) 20x24 (4) 20x24 (6) 20x24 (2) 20x2423.33 24.44 26.67 27.78 30.00 31.11 33.33 34.44 11665 12220 13335 13890 15000 15555 16665 17220
(8) 20x20 (4) 20x20 (8) 20x24 (10) 20x20 (6) 20x20 (4) 20x20 (12) 20x20 (5) 20x24 (6) 20x20
53 (4) 20x24 (4) 20x24 (6) 20x24 (5) 24x24 (6) 20x2422.22 24.44 26.67 27.78 30.00 31.11 33.33 36.67 36.6711110 12220 13335 13890 15000 15555 16665 18335 11667
(8) 20x24 (4) 20x24 (8) 24x24 (10) 20x24 (2) 12x24 (4) 12x24 (10) 24x24 (10) 20x24 (10) 24x24
57 (4) 24x24 (8) 24x24 (6) 24x24 (2) 24x24 (2) 12x2426.67 29.33 32.00 33.33 36.00 32.00 40.00 41.33 44.0013335 14665 16000 16665 18000 18665 20000 20667 22000
(8) 20x24 (4) 20x24 (8) 24x24 (10) 20x24 (2) 12x24 (4) 12x24 (10) 24x24 (10) 20x24 (10) 24x24
60 (4) 24x24 (8) 24x24 (6) 24x24 (2) 24x24 (2) 12x2426.67 29.33 32.00 33.33 36.00 32.00 40.00 41.33 44.0013335 14665 16000 16665 18000 18665 20000 20667 22000
(2) 12x24 (2) 20x24 (4) 12x24 (8) 20x24 (2) 12x24 (4) 20x24 (5) 12x24 (5) 12x24 (10) 24x24
66 (6) 24x24 (6) 24x24 (8) 20x24 (2) 24x24 (8) 24x24 (6) 24x24 (10) 20x24 (10) 20x24 (2) 12x2428.00 30.67 34.67 34.67 36.00 37.33 43.33 43.33 44.0014000 15335 17335 17333 18000 18665 21665 21665 22000
(6) 20x24 (6) 20x24 (4) 20x24 (15) 20x20 (6) 12x24 (6) 20x20 (10) 20x24 (18) 20x20 (7) 12x24
73 (2) 24x24 (8) 24x24 (9) 20x24 (5) 24x24 (10) 24x2420.00 20.00 21.33 41.67 44.00 46.67 53.33 50.00 54.0016665 17000 20000 20835 22000 23335 26665 25000 27000
(8) 20x20 (4) 20x20 (4) 20x24 (5) 20x20 (5) 20x20 (5) 20x20 (5) 20x24 (5) 20x24 (5) 20x24
79 (4) 20x24 (8) 20x24 (8) 24x24 (10) 20x24 (10) 20x24 (10) 20x24 (10) 24x24 (10) 24x24 (10) 24x2435.56 37.78 45.33 47.22 47.22 47.22 56.67 56.67 56.67
17780 18890 22665 23610 23610 23610 28335 28335 28335(12) 20x24 (6) 20x24 (12) 24x24 (15) 20x24 (3) 12x24 (3) 12x24 (15) 24x24 (15) 24x24 (3) 12x24
87 (6) 24x24 (12) 24x24 (12) 24x24 (15) 24x2440.00 44.00 48.00 50.00 54.00 54.00 60.00 60.00 66.0020000 22000 24000 25000 27000 28000 30000 30000 33000
(16) 20x20 (8) 20x20 (16) 20x24 (20) 20x20 (20) 20x20 (8) 20x20 (24) 20x20 (24) 20x20 (8) 12x24
93 (8) 20x24 (12) 20x24 (15) 24x2444.44 48.89 53.33 55.56 55.56 62.22 66.67 66.67 76.0022220 24445 26665 27780 27780 31111 33335 33335 38000
(16) 20x20 (8) 20x20 (16) 20x24 (20) 30x20 (7) 12x20 (8) 20x20 (24) 20x20 (20) 20x20 (8) 12x24
98 (8) 20x24 (12) 24x24 (12) 20x24 (4) 20x24 (15) 24x2444.44 48.89 53.33 55.56 59.67 62.22 66.67 68.89 76.0022220 24445 26665 27780 31000 31111 33335 34445 38000
(4) 12x24 (16) 24x24 (20) 20x24 (25) 20x20 (15) 20x20 (30) 20x20 (30) 20x20 (30) 20x20
111 (12) 24x24 (10) 20x2456.00 64.00 66.67 69.44 75.00 83.33 83.33 83.3328000 32000 33335 34720 37500 41665 41665 41665
STEP 5:Module • Filter • Flat Filter Selection
Based on 5" Unit Base and 2" double Wall Casing.
LEGEND:
Example: Cabinet "H" = 73Cabinet "W" = 102
(4) 20x24Filter (qty.) HxW
(2) 24x2421.33 Filter Face Area20000 Maximum CFM
14
T SERIES: 800-30,000 CFM AHU
STEP 5:Module • Mixing
Unit Max. Damper Width
Width External Internal
30 24 12
36 30 18
42 36 24
48 42 30
54 48 36
60 54 42
66 60 48
72 66 54
78 72 60
84 78 66
90 84 72
96 90 78
102 96 84
108 102 90
114 108 96
120 114 102
126 120 108
132 126 114
138 132 120
144 138 126
Unit External Damper Internal Damper
Height SL DL SL IDL
28 12 6 18 6
33 18 12 24 12
37 18 12 24 12
39 24 18 30 18
45 24 18 36 24
50 30 24 36 24
53 30 24 36 24
57 30 24 42 30
60 30 24 42 30
66 36 30 42 30
73 36 30 48 36
79 42 36 48 36
87 42 36 54 42
93 48 42 54 42
98 48 42 60 48
111 54 48 66 54
Values based on unducted damper mounting.
3" DL
SL
External - 3"Internal - 9"
H
6" IDL
IDL
DL
Standard Vee-Blade Damper
Velocity (FPM)Damper Size
1000 1500 2000
24" x 24" 0.11 0.24 0.47
36" x 36" 0.08 0.22 0.38
Values based on unducted damper mounting.
Aluminum Airfoil Blade Damper
Velocity (FPM)Damper Size
1000 1500 2000
24" x 24" 0.13 0.19 0.31
36" x 36" 0.06 0.16 0.21
15
T SERIES: 800-30,000 CFM AHU
No. of Coil Rows Coil Depth
1 6"2 7 1/2"4 7 1/2"6 10"8 12 1/2"10 15"12 18"
STEP 5:Module • Coil • Cooling
Air DPL RecommendedVelocity FPI Drain Pan Length
8 6"10 6"
40012 12"14 12"8 6"10 12"
45012 12"14 18"8 12"
500 10 18"12 18"8 12"
550 10 18"12 24"
DPL
COIL
UNITFLOORSUB-
FLOOR
Drain Pan Length 1,2
Notes:1. Drain Pan Length table covers "Normal" wet-bulb conditions. Please consult Thermal when
selecting coils for use in extreme conditions, such as 100% outside air or coils with heavydehumidification loads.
2. Drain Pan Length table is based on 48" finned height coil. Moisture carry over beyond theleaving edge of the coil is proportional to the finned height of the coil.
4714 Winfield Road Houston, TX 77039Tel: 281-590-1172 • 281-897-9000