Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickOutline of the Final Presentation
T h e s i s 2 0 0 4 T h e s i s 2 0 0 4 Andrea Hauber
Architectural EngineeringLighting/Electrical Thesis
Dr. Martin Luther King Jr. Library(San José Joint Library)
San José, CaliforniaPresentation: April 13, 2004Consultant: Prof. Mistrick
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickOutline of the Final Presentation
T h e s i s 2 0 0 4 T h e s i s 2 0 0 4
LightingExteriorLobbyYouth Reading AreaReading Area
Electrical Design Requirements/EvaluationRe-switching
Structural Exterior Lighting Connection Detail
Mechanical Design Requirements/Evaluation
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickOutline of the Final Presentation
T h e s i s 2 0 0 4 T h e s i s 2 0 0 4
LightingExteriorLobbyYouth Reading AreaReading Area
Electrical Design Requirements/EvaluationRe-switching
Structural Exterior Lighting Connection Detail
Mechanical Design Requirements/Evaluation
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
A Joint VentureA Joint Venture
The Library is a Joint Venture between the City of San José and San José State University
The purpose is to bring together the students and public in order to promote a growing sense of community in the area.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Location in San José, CALocation in San José, CA
Conveniently located on the corner of the San José State University Campus to be open to the City of San José residence.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
DesignDesign
City Entrance
Campus Entrance
$177 .5 million 475,000 sq. ft. LibraryEight floors plus a mezzanine and a lower levelConstruction 2000 - 2003
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Design TeamDesign Team
Construction Manager: GILBANE BUILDING COMPANY
General Contractor:HENSEL PHELPS
Design Architect:CARRIER JOHNSONGUNNAR BIRKERTS ARCHITECTS
Local Assoc. Architect:ANDERSON BRULE ARCHITECTS
Structural:FORELL / ELSESSER, INC.
MEP:FLACK + KURTZ CONSULTING ENGINEERS, LLP
Lighting Design:FRANCIS KRAHE & ASSOCIATES, INC.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance
Circulation Space
Youth Area
Evaluated Lighting SpacesEvaluated Lighting Spaces
Ground Floor
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area
Evaluated Lighting SpacesEvaluated Lighting Spaces
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance
Exterior Entrance from CityExterior Entrance from City
Ground Floor
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance from City Exterior Entrance from City Design RequirementsDesign Requirements
IES:IES:Active Exterior Entrance: Active Exterior Entrance: Very Important: Very Important: Horizontal: 50 lux Horizontal: 50 lux Vertical: 30 lux Vertical: 30 lux Appearance of Space and LuminairesAppearance of Space and Luminaires, Color appearance and contrast, Direct , Color appearance and contrast, Direct Glare, Glare, Light PollutionLight Pollution, Modeling of Faces or Objects, Peripheral Detection, , Modeling of Faces or Objects, Peripheral Detection, Points of Interest, Reflected Glare, Shadows, Source/Task/Eye GePoints of Interest, Reflected Glare, Shadows, Source/Task/Eye Geometry, ometry, Surface CharacteristicsSurface CharacteristicsImportant:Important:Light Distribution on Surfaces, Light Distribution on Surfaces, Sparkle/Desirable Reflected HighlightsSparkle/Desirable Reflected Highlights
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance from CityExterior Entrance from CitySchematic DesignSchematic Design
Initial design used the colors and symbols of the city and university to bring together the exterior of the building the way the library is to bring together the community.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance from CityExterior Entrance from CityFinal DesignFinal Design
Final design places emphasis on the geometric aspect of the architecture of the building.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance from CityExterior Entrance from CityFinal DesignFinal Design
Lower block: Lower block: Four Tubular Series 4” Four Tubular Series 4” @32’@32’--8” 8”
Upper tubes:Upper tubes:Three Tubular Series 6”Three Tubular Series 6”@ 60’@ 60’
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Exterior Entrance from CityExterior Entrance from CityStructural Detail & ConnectionStructural Detail & Connection
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area
Reading AreaReading Area
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area Reading Area Design RequirementsDesign Requirements
IES:IES:Study Desks:Study Desks:Very Important:Very Important:Horizontal: 300 luxHorizontal: 300 luxDirect glare, Reflected glare, Source/task/eye geometryDirect glare, Reflected glare, Source/task/eye geometry
California Title 24:California Title 24:Library reading: 1.2 W/Library reading: 1.2 W/sq.ftsq.ft..
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area Reading Area Schematic DesignSchematic Design
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area Reading Area Final DesignFinal Design
(13) Linear Fixtures(13) Linear Fixtureswith one 32 watt Twith one 32 watt T--8 lamp 8 lamp
(1) Linear Fixture (1) Linear Fixture with two 32 watt Twith two 32 watt T--8 lamps 8 lamps
Allowed:Allowed:34ft x 57ft x ½ = 970 sqft total 34ft x 57ft x ½ = 970 sqft total Stack area = 192 sqftStack area = 192 sqftReading Area = 778 sqftReading Area = 778 sqft
x 1.2 W/sqft = 933 Wx 1.2 W/sqft = 933 WActual:Actual:15 lamps x 32 W =420 W15 lamps x 32 W =420 W480 W / 778 sqft = 0.62 W/sqft 480 W / 778 sqft = 0.62 W/sqft
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area Reading Area Final DesignFinal Design
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Reading Area Reading Area Final DesignFinal Design
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Area
Youth Reading AreaYouth Reading Area
Ground Floor
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Design RequirementsDesign Requirements
IES IES Study DesksStudy DesksVery Important:Very Important:Horizontal: 300 luxHorizontal: 300 luxDirect glare, Reflected glare, Source/task/eye geometryDirect glare, Reflected glare, Source/task/eye geometry
California Title 24: California Title 24: Library reading: 1.2 W/Library reading: 1.2 W/sq.ftsq.ft..
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Schematic DesignSchematic Design
The schematic design for a whimsical children’s reading area did not allow sufficient illumination for reading within the space.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design IFinal Design I
(10) Pendant Indirect (10) Pendant Indirect with (2) 24 watt Twith (2) 24 watt T--5HO mini bi5HO mini bi--pin base pin base and (3) 50 watt lowand (3) 50 watt low--voltage halogenvoltage halogen
Allowed:Allowed:Reading Area = 1780 sqftReading Area = 1780 sqftx 1.2 W/sqft = 2136 Wx 1.2 W/sqft = 2136 WActual:Actual:10 fixtures x 198 W = 1980 W10 fixtures x 198 W = 1980 W1980W / 1780 sqft = 1.11 W/sqft1980W / 1780 sqft = 1.11 W/sqft
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design IFinal Design I
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design IFinal Design I
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design II Final Design II
(10) Pendant Downlight(10) Pendant DownlightLamp 50 watt lowLamp 50 watt low--voltage halogenvoltage halogen(19) Downlight(19) DownlightLamp 50 watt lowLamp 50 watt low--voltage halogenvoltage halogen
Allowed:Allowed:Reading Area = 1780 sqftReading Area = 1780 sqftx 1.2 W/sqft = 2136 Wx 1.2 W/sqft = 2136 WActual:Actual:29 lamps x 50 W = 1450 W29 lamps x 50 W = 1450 W1450W / 1780 sqft = 0.82 W/sqft1450W / 1780 sqft = 0.82 W/sqft
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design II Final Design II
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Youth Reading Area Youth Reading Area Final Design II Final Design II
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space
Circulation SpaceCirculation Space
Ground Floor
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Design RequirementsDesign Requirements
IES: IES: Library Circulation DeskLibrary Circulation DeskVery Important: Very Important: Horizontal: 300 luxHorizontal: 300 luxReflected Glare, Source/Task/Eye GeometryReflected Glare, Source/Task/Eye GeometryImportant: Important: Appearance of space and luminairesAppearance of space and luminaires, Color appearance and , Color appearance and contrast, contrast, Direct Glare, Light Distribution on Surfaces and Task Plane Direct Glare, Light Distribution on Surfaces and Task Plane (uniform), (uniform), Modeling of Faces or ObjectsModeling of Faces or Objects
Lobby GeneralLobby GeneralSomewhat Important: Somewhat Important: Horizontal: 100 luxHorizontal: 100 luxImportant: Important: Appearance of space and luminairesAppearance of space and luminaires, Color appearance and color , Color appearance and color contrast, contrast, Day lighting integrationDay lighting integration and control, Direct glare, Light and control, Direct glare, Light distribution on surfaces, Luminance of room surfaces, Modeling odistribution on surfaces, Luminance of room surfaces, Modeling of faces or f faces or objects, and Points of interestobjects, and Points of interest
California Title 24: California Title 24: Lobby: 1.5W/sqft.Lobby: 1.5W/sqft. Corridor: 0.6W/sqftCorridor: 0.6W/sqft
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Schematic DesignSchematic Design
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Final DesignFinal Design
(16) Indirect/Direct Single Uplight fixtures (16) Indirect/Direct Single Uplight fixtures with six 25 watt Twith six 25 watt T--8 lamps 8 lamps
(4) Indirect/Direct Quad (4) Indirect/Direct Quad with four luminaires at six 25 watt Twith four luminaires at six 25 watt T--8 lamps each8 lamps each
(12) (12) ChieftanChieftan Sconce Sconce with two 21 watt Twith two 21 watt T--5 lamps 5 lamps
Allowed:Allowed:8790 sqft total 8790 sqft total 1.2 W/sqft as lobby= 10548 W1.2 W/sqft as lobby= 10548 W0.6 W/sqft as corridor= 5274 W0.6 W/sqft as corridor= 5274 WActual:Actual:32fixtures x 6lamps x 25W 32fixtures x 6lamps x 25W = 4800= 480012fixtures x 2lamps x 21W 12fixtures x 2lamps x 21W = 504= 504Total Total = 5304 Watts= 5304 Watts
= 0.601 W/sqft= 0.601 W/sqft
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Final DesignFinal Design
The architecture of the building allows for much day light to come through angular light shafts and windows. This fixture will bring that architectural detail into the ground floor lobby space.
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Final DesignFinal Design
Andrea Hauber; L/E AE Dr. Martin Luther King Jr. Library; San José, California
04/13/03; Consultant: Prof. MistrickFinal Presentation
Circulation Space Circulation Space Final DesignFinal Design
Higher illuminance levels have been used
at the entrances.
The general illuminance is around 300 lux to allow the lobby to be used for multiple purposes.