  • Air System Sizing Summary for 001. GF Seminar RoomProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 001. GF Seminar RoomEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 450.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.7 TonsTotal coil load 31.8 MBHSensible coil load 28.6 MBHCoil CFM at Jul 1700 1184 CFMMax block CFM 1184 CFMSum of peak zone CFM 1184 CFMSensible heat ratio 0.899ft/Ton 169.7BTU/(hr-ft) 70.7Water flow @ 10.0 F rise 6.37 gpm

    Load occurs at Jul 1700OA DB / WB 107.8 / 71.4 FEntering DB / WB 76.9 / 62.0 FLeaving DB / WB 54.0 / 52.3 FCoil ADP 50.8 FBypass Factor 0.120Resulting RH 56 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 9.6 MBHCoil CFM at Des Htg 1184 CFMMax coil CFM 1184 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 21.3Ent. DB / Lvg DB 62.8 / 70.5 F

    Supply Fan Sizing DataActual max CFM 1184 CFMStandard CFM 1154 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 245 CFMCFM/ft 0.54 CFM/ft

    CFM/person 8.43 CFM/person

    Hourly Analysis Program v4.60 Page 1 of 124

  • Air System Sizing Summary for 002. GF Staff Room(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 002. GF Staff Room(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 7.0 MBHSensible coil load 6.6 MBHCoil CFM at Jun 1700 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.939ft/Ton 257.3BTU/(hr-ft) 46.6Water flow @ 10.0 F rise 1.40 gpm

    Load occurs at Jun 1700OA DB / WB 106.8 / 71.4 FEntering DB / WB 72.5 / 61.7 FLeaving DB / WB 56.7 / 55.5 FCoil ADP 54.5 FBypass Factor 0.120Resulting RH 61 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 2.2 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 15.0Ent. DB / Lvg DB 68.1 / 73.5 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 39 CFMCFM/ft 0.26 CFM/ft

    CFM/person 8.02 CFM/person

    Hourly Analysis Program v4.60 Page 2 of 124

  • Air System Sizing Summary for 003. GF Staff Room(2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 003. GF Staff Room(2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 7.0 MBHSensible coil load 6.6 MBHCoil CFM at Aug 1500 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.940ft/Ton 239.4BTU/(hr-ft) 50.1Water flow @ 10.0 F rise 1.40 gpm

    Load occurs at Aug 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 73.1 / 61.5 FLeaving DB / WB 56.1 / 54.8 FCoil ADP 53.8 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 2.0 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 14.5Ent. DB / Lvg DB 65.5 / 70.8 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 38 CFMCFM/ft 0.27 CFM/ft

    CFM/person 7.90 CFM/person

    Hourly Analysis Program v4.60 Page 3 of 124

  • Air System Sizing Summary for 004. GF Faculty Cabin(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 004. GF Faculty Cabin(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.5 MBHSensible coil load 6.2 MBHCoil CFM at Jul 1700 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.956ft/Ton 260.3BTU/(hr-ft) 46.1Water flow @ 10.0 F rise 1.29 gpm

    Load occurs at Jul 1700OA DB / WB 107.8 / 71.4 FEntering DB / WB 72.0 / 61.0 FLeaving DB / WB 56.1 / 54.8 FCoil ADP 53.9 FBypass Factor 0.120Resulting RH 59 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.8Ent. DB / Lvg DB 66.1 / 70.7 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 4 of 124

  • Air System Sizing Summary for 005. GF Faculty Cabin(2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 005. GF Faculty Cabin(2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.3 MBHSensible coil load 6.1 MBHCoil CFM at Aug 1600 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.965ft/Ton 286.7BTU/(hr-ft) 41.9Water flow @ 10.0 F rise 1.26 gpm

    Load occurs at Aug 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 71.9 / 61.7 FLeaving DB / WB 57.3 / 56.1 FCoil ADP 55.3 FBypass Factor 0.120Resulting RH 62 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 11.7Ent. DB / Lvg DB 66.1 / 70.3 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 5 of 124

  • Air System Sizing Summary for 006. GF Faculty Cabin(3)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 006. GF Faculty Cabin(3)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.5 MBHSensible coil load 6.1 MBHCoil CFM at Aug 1600 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.929ft/Ton 275.0BTU/(hr-ft) 43.6Water flow @ 10.0 F rise 1.31 gpm

    Load occurs at Aug 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 71.9 / 61.9 FLeaving DB / WB 57.3 / 56.1 FCoil ADP 55.3 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 11.7Ent. DB / Lvg DB 66.1 / 70.3 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 6 of 124

  • Air System Sizing Summary for 007. Entrance FoyerProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 007. Entrance FoyerEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 350.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.2 TonsTotal coil load 14.6 MBHSensible coil load 14.1 MBHCoil CFM at Jun 1500 921 CFMMax block CFM 921 CFMSum of peak zone CFM 921 CFMSensible heat ratio 0.964ft/Ton 287.4BTU/(hr-ft) 41.7Water flow @ 10.0 F rise 2.92 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.0 / 61.0 FLeaving DB / WB 56.5 / 55.3 FCoil ADP 54.5 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 9.4 MBHCoil CFM at Mar 1200 921 CFMMax coil CFM 921 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Mar 1200BTU/(hr-ft) 26.8Ent. DB / Lvg DB 57.2 / 66.8 F

    Supply Fan Sizing DataActual max CFM 921 CFMStandard CFM 898 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 41 CFMCFM/ft 0.12 CFM/ft

    CFM/person 12.65 CFM/person

    Hourly Analysis Program v4.60 Page 7 of 124

  • Air System Sizing Summary for 008. GF Conference RoomProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 008. GF Conference RoomEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 6.7 MBHSensible coil load 6.4 MBHCoil CFM at Jul 1500 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.953ft/Ton 267.9BTU/(hr-ft) 44.8Water flow @ 10.0 F rise 1.34 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 73.0 / 62.3 FLeaving DB / WB 57.6 / 56.4 FCoil ADP 55.5 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.9 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 13.0Ent. DB / Lvg DB 66.1 / 70.8 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 39 CFMCFM/ft 0.26 CFM/ft

    CFM/person 8.02 CFM/person

    Hourly Analysis Program v4.60 Page 8 of 124

  • Air System Sizing Summary for 009. GF Faculty Cabin(4)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 009. GF Faculty Cabin(4)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.5 MBHSensible coil load 6.0 MBHCoil CFM at Jun 1600 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.917ft/Ton 257.6BTU/(hr-ft) 46.6Water flow @ 10.0 F rise 1.31 gpm

    Load occurs at Jun 1600OA DB / WB 108.4 / 71.8 FEntering DB / WB 71.8 / 61.4 FLeaving DB / WB 56.4 / 55.2 FCoil ADP 54.3 FBypass Factor 0.120Resulting RH 61 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.7Ent. DB / Lvg DB 66.2 / 70.8 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 9 of 124

  • Air System Sizing Summary for 010. GF Faculty Cabin(5)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 010. GF Faculty Cabin(5)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 6.6 MBHSensible coil load 6.1 MBHCoil CFM at Jun 1500 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.918ft/Ton 254.2BTU/(hr-ft) 47.2Water flow @ 10.0 F rise 1.32 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.9 / 61.4 FLeaving DB / WB 56.2 / 55.0 FCoil ADP 54.1 FBypass Factor 0.120Resulting RH 61 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.8Ent. DB / Lvg DB 66.1 / 70.7 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 10 of 124

  • Air System Sizing Summary for 011. GF Faculty Cabin(6)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 011. GF Faculty Cabin(6)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 6.8 MBHSensible coil load 6.3 MBHCoil CFM at Jul 1700 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.925ft/Ton 265.3BTU/(hr-ft) 45.2Water flow @ 10.0 F rise 1.36 gpm

    Load occurs at Jul 1700OA DB / WB 107.8 / 71.4 FEntering DB / WB 71.6 / 61.4 FLeaving DB / WB 56.5 / 55.3 FCoil ADP 54.4 FBypass Factor 0.120Resulting RH 62 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.9 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.4Ent. DB / Lvg DB 66.3 / 70.8 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 11 of 124

  • Air System Sizing Summary for 012. GF Faculty Cabin(7)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 012. GF Faculty Cabin(7)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.6 TonsTotal coil load 6.8 MBHSensible coil load 6.3 MBHCoil CFM at Jul 1700 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.925ft/Ton 265.3BTU/(hr-ft) 45.2Water flow @ 10.0 F rise 1.36 gpm

    Load occurs at Jul 1700OA DB / WB 107.8 / 71.4 FEntering DB / WB 71.6 / 61.4 FLeaving DB / WB 56.5 / 55.3 FCoil ADP 54.4 FBypass Factor 0.120Resulting RH 62 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.9 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.4Ent. DB / Lvg DB 66.3 / 70.8 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 12 of 124

  • Air System Sizing Summary for 013. GF - Corridor(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 013. GF - Corridor(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1350.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 4.6 TonsTotal coil load 55.4 MBHSensible coil load 53.7 MBHCoil CFM at Jun 1500 3553 CFMMax block CFM 3553 CFMSum of peak zone CFM 3553 CFMSensible heat ratio 0.970ft/Ton 292.5BTU/(hr-ft) 41.0Water flow @ 10.0 F rise 11.08 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.4 / 61.3 FLeaving DB / WB 57.0 / 55.9 FCoil ADP 55.1 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 37.7 MBHCoil CFM at Jun 0900 3553 CFMMax coil CFM 3553 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Jun 0900BTU/(hr-ft) 28.0Ent. DB / Lvg DB 57.3 / 67.4 F

    Supply Fan Sizing DataActual max CFM 3553 CFMStandard CFM 3463 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 149 CFMCFM/ft 0.11 CFM/ft

    CFM/person 13.58 CFM/person

    Hourly Analysis Program v4.60 Page 13 of 124

  • Air System Sizing Summary for 014. GF Student CentreProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 014. GF Student CentreEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 450.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.0 TonsTotal coil load 24.3 MBHSensible coil load 22.9 MBHCoil CFM at Aug 1600 1184 CFMMax block CFM 1184 CFMSum of peak zone CFM 1184 CFMSensible heat ratio 0.942ft/Ton 222.4BTU/(hr-ft) 54.0Water flow @ 10.0 F rise 4.86 gpm

    Load occurs at Aug 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 73.1 / 60.7 FLeaving DB / WB 54.7 / 53.3 FCoil ADP 52.2 FBypass Factor 0.120Resulting RH 56 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 7.6 MBHCoil CFM at Des Htg 1184 CFMMax coil CFM 1184 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 16.8Ent. DB / Lvg DB 65.3 / 71.3 F

    Supply Fan Sizing DataActual max CFM 1184 CFMStandard CFM 1154 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 125 CFMCFM/ft 0.28 CFM/ft

    CFM/person 9.58 CFM/person

    Hourly Analysis Program v4.60 Page 14 of 124

  • Air System Sizing Summary for 015. GF - Corridor(2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 015. GF - Corridor(2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 350.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.4 TonsTotal coil load 17.2 MBHSensible coil load 15.7 MBHCoil CFM at Jun 1500 921 CFMMax block CFM 921 CFMSum of peak zone CFM 921 CFMSensible heat ratio 0.917ft/Ton 244.8BTU/(hr-ft) 49.0Water flow @ 10.0 F rise 3.43 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.9 / 61.1 FLeaving DB / WB 55.7 / 54.5 FCoil ADP 53.5 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 7.9 MBHCoil CFM at May 0500 921 CFMMax coil CFM 921 CFMWater flow @ 20.0 F drop N/A

    Load occurs at May 0500BTU/(hr-ft) 22.6Ent. DB / Lvg DB 57.1 / 65.2 F

    Supply Fan Sizing DataActual max CFM 921 CFMStandard CFM 898 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 71 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 15 of 124

  • Air System Sizing Summary for 016. GF - PantryProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 016. GF - PantryEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 70.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.0 TonsTotal coil load 11.9 MBHSensible coil load 9.9 MBHCoil CFM at Jul 1500 311 CFMMax block CFM 311 CFMSum of peak zone CFM 311 CFMSensible heat ratio 0.838ft/Ton 70.8BTU/(hr-ft) 169.6Water flow @ 10.0 F rise 2.38 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 83.0 / 64.3 FLeaving DB / WB 52.6 / 50.7 FCoil ADP 48.5 FBypass Factor 0.120Resulting RH 51 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 2.5 MBHCoil CFM at Des Htg 311 CFMMax coil CFM 311 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 35.6Ent. DB / Lvg DB 63.5 / 71.2 F

    Supply Fan Sizing DataActual max CFM 311 CFMStandard CFM 303 CFMActual max CFM/ft 4.44 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 88 CFMCFM/ft 1.25 CFM/ft

    CFM/person 10.81 CFM/person

    Hourly Analysis Program v4.60 Page 16 of 124

  • Air System Sizing Summary for 017. GF - UPSProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 017. GF - UPSEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 250.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.0 TonsTotal coil load 23.4 MBHSensible coil load 23.0 MBHCoil CFM at Jul 1500 1599 CFMMax block CFM 1599 CFMSum of peak zone CFM 1599 CFMSensible heat ratio 0.982ft/Ton 128.0BTU/(hr-ft) 93.7Water flow @ 10.0 F rise 4.69 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 66.6 / 57.5 FLeaving DB / WB 53.0 / 51.9 FCoil ADP 51.1 FBypass Factor 0.120Resulting RH 58 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 1599 CFMStandard CFM 1559 CFMActual max CFM/ft 6.40 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 35 CFMCFM/ft 0.14 CFM/ft

    CFM/person 10.80 CFM/person

    Hourly Analysis Program v4.60 Page 17 of 124

  • Air System Sizing Summary for 018. GF - Corridor(3)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 018. GF - Corridor(3)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 430.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.7 TonsTotal coil load 8.1 MBHSensible coil load 8.1 MBHCoil CFM at Jun 1500 1132 CFMMax block CFM 1132 CFMSum of peak zone CFM 1132 CFMSensible heat ratio 1.000ft/Ton 635.7BTU/(hr-ft) 18.9Water flow @ 10.0 F rise 1.62 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.4 / 65.7 FLeaving DB / WB 64.6 / 63.5 FCoil ADP 63.7 FBypass Factor 0.120Resulting RH 81 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 3.6 MBHCoil CFM at Des Htg 1132 CFMMax coil CFM 1132 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 8.5Ent. DB / Lvg DB 70.3 / 73.4 F

    Supply Fan Sizing DataActual max CFM 1132 CFMStandard CFM 1103 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 62 CFMCFM/ft 0.14 CFM/ft

    CFM/person 10.62 CFM/person

    Hourly Analysis Program v4.60 Page 18 of 124

  • Air System Sizing Summary for 019. GF - SemiconductorProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 019. GF - SemiconductorEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1200.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 3.5 TonsTotal coil load 42.5 MBHSensible coil load 42.5 MBHCoil CFM at May 1400 3032 CFMMax block CFM 3032 CFMSum of peak zone CFM 3032 CFMSensible heat ratio 1.000ft/Ton 338.9BTU/(hr-ft) 35.4Water flow @ 10.0 F rise 8.50 gpm

    Load occurs at May 1400OA DB / WB 105.4 / 69.8 FEntering DB / WB 68.5 / 59.0 FLeaving DB / WB 55.2 / 53.9 FCoil ADP 53.3 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 3032 CFMStandard CFM 2955 CFMActual max CFM/ft 2.53 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 236 CFMCFM/ft 0.20 CFM/ft

    CFM/person 118.00 CFM/person

    Hourly Analysis Program v4.60 Page 19 of 124

  • Air System Sizing Summary for 020. GF - NanomaterialsProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 020. GF - NanomaterialsEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 3.6 TonsTotal coil load 43.2 MBHSensible coil load 42.7 MBHCoil CFM at Jul 1300 2905 CFMMax block CFM 2905 CFMSum of peak zone CFM 2905 CFMSensible heat ratio 0.988ft/Ton 319.5BTU/(hr-ft) 37.6Water flow @ 10.0 F rise 8.64 gpm

    Load occurs at Jul 1300OA DB / WB 107.6 / 71.3 FEntering DB / WB 68.6 / 59.0 FLeaving DB / WB 54.6 / 53.5 FCoil ADP 52.7 FBypass Factor 0.120Resulting RH 59 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 2905 CFMStandard CFM 2832 CFMActual max CFM/ft 2.53 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 227 CFMCFM/ft 0.20 CFM/ft

    CFM/person 113.50 CFM/person

    Hourly Analysis Program v4.60 Page 20 of 124

  • Air System Sizing Summary for 021. GF - Dielectric LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 021. GF - Dielectric LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 860.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.7 TonsTotal coil load 32.5 MBHSensible coil load 32.2 MBHCoil CFM at Jul 1500 2173 CFMMax block CFM 2173 CFMSum of peak zone CFM 2173 CFMSensible heat ratio 0.990ft/Ton 317.4BTU/(hr-ft) 37.8Water flow @ 10.0 F rise 6.51 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.6 / 59.8 FLeaving DB / WB 55.6 / 54.4 FCoil ADP 53.7 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 12.5 MBHCoil CFM at Jun 1200 2173 CFMMax coil CFM 2173 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Jun 1200BTU/(hr-ft) 14.5Ent. DB / Lvg DB 55.7 / 61.2 F

    Supply Fan Sizing DataActual max CFM 2173 CFMStandard CFM 2118 CFMActual max CFM/ft 2.53 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 175 CFMCFM/ft 0.20 CFM/ft

    CFM/person 87.40 CFM/person

    Hourly Analysis Program v4.60 Page 21 of 124

  • Air System Sizing Summary for 022. GF - Target PreparationProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 022. GF - Target PreparationEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 260.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.0 TonsTotal coil load 12.4 MBHSensible coil load 12.0 MBHCoil CFM at Jul 1500 664 CFMMax block CFM 664 CFMSum of peak zone CFM 664 CFMSensible heat ratio 0.973ft/Ton 252.5BTU/(hr-ft) 47.5Water flow @ 10.0 F rise 2.47 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 70.1 / 58.6 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.5 FBypass Factor 0.120Resulting RH 53 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 664 CFMStandard CFM 648 CFMActual max CFM/ft 2.56 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 57 CFMCFM/ft 0.22 CFM/ft

    CFM/person 56.80 CFM/person

    Hourly Analysis Program v4.60 Page 22 of 124

  • Air System Sizing Summary for 023. GF - Air Lock (1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 023. GF - Air Lock (1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 100.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.1 TonsTotal coil load 1.5 MBHSensible coil load 1.5 MBHCoil CFM at Jul 1600 253 CFMMax block CFM 253 CFMSum of peak zone CFM 253 CFMSensible heat ratio 1.000ft/Ton 807.7BTU/(hr-ft) 14.9Water flow @ 10.0 F rise 0.30 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 69.7 / 62.1 FLeaving DB / WB 64.1 / 60.1 FCoil ADP 63.4 FBypass Factor 0.120Resulting RH 71 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 253 CFMStandard CFM 246 CFMActual max CFM/ft 2.53 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 18 CFMCFM/ft 0.18 CFM/ft

    CFM/person 18.00 CFM/person

    Hourly Analysis Program v4.60 Page 23 of 124

  • Air System Sizing Summary for 024.GF - Functional Material LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 024.GF - Functional Material LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1450.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 5.4 TonsTotal coil load 64.7 MBHSensible coil load 63.8 MBHCoil CFM at Jul 1500 3663 CFMMax block CFM 3663 CFMSum of peak zone CFM 3663 CFMSensible heat ratio 0.986ft/Ton 268.8BTU/(hr-ft) 44.6Water flow @ 10.0 F rise 12.95 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.5 / 58.3 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.6 FBypass Factor 0.120Resulting RH 53 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 3663 CFMStandard CFM 3570 CFMActual max CFM/ft 2.53 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 281 CFMCFM/ft 0.19 CFM/ft

    CFM/person 140.50 CFM/person

    Hourly Analysis Program v4.60 Page 24 of 124

  • Air System Sizing Summary for 025. GF - SemProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 025. GF - SemEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.7 TonsTotal coil load 7.9 MBHSensible coil load 7.6 MBHCoil CFM at Jul 1500 409 CFMMax block CFM 409 CFMSum of peak zone CFM 409 CFMSensible heat ratio 0.960ft/Ton 228.2BTU/(hr-ft) 52.6Water flow @ 10.0 F rise 1.58 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 70.5 / 58.8 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.5 FBypass Factor 0.120Resulting RH 53 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 409 CFMStandard CFM 399 CFMActual max CFM/ft 2.73 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 37 CFMCFM/ft 0.25 CFM/ft

    CFM/person 37.00 CFM/person

    Hourly Analysis Program v4.60 Page 25 of 124

  • Air System Sizing Summary for 026. GF - XRDProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 026. GF - XRDEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 200.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.9 TonsTotal coil load 10.6 MBHSensible coil load 10.2 MBHCoil CFM at Jul 1500 571 CFMMax block CFM 571 CFMSum of peak zone CFM 571 CFMSensible heat ratio 0.970ft/Ton 227.1BTU/(hr-ft) 52.8Water flow @ 10.0 F rise 2.11 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.9 / 58.6 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.6 FBypass Factor 0.120Resulting RH 53 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 571 CFMStandard CFM 556 CFMActual max CFM/ft 2.85 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 46 CFMCFM/ft 0.23 CFM/ft

    CFM/person 46.00 CFM/person

    Hourly Analysis Program v4.60 Page 26 of 124

  • Air System Sizing Summary for 027. GF - Physics StoreProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 027. GF - Physics StoreEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 125.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.5 MBHSensible coil load 5.2 MBHCoil CFM at Jul 1500 329 CFMMax block CFM 329 CFMSum of peak zone CFM 329 CFMSensible heat ratio 0.943ft/Ton 274.5BTU/(hr-ft) 43.7Water flow @ 10.0 F rise 1.09 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.7 / 59.7 FLeaving DB / WB 54.8 / 53.6 FCoil ADP 52.7 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 3.4 MBHCoil CFM at Apr 1200 329 CFMMax coil CFM 329 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Apr 1200BTU/(hr-ft) 27.4Ent. DB / Lvg DB 55.2 / 65.1 F

    Supply Fan Sizing DataActual max CFM 329 CFMStandard CFM 321 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 15 CFMCFM/ft 0.12 CFM/ft

    CFM/person 12.00 CFM/person

    Hourly Analysis Program v4.60 Page 27 of 124

  • Air System Sizing Summary for 028. GF - Surface LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 028. GF - Surface LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 230.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.2 TonsTotal coil load 14.9 MBHSensible coil load 14.6 MBHCoil CFM at Jul 1500 846 CFMMax block CFM 846 CFMSum of peak zone CFM 846 CFMSensible heat ratio 0.978ft/Ton 184.8BTU/(hr-ft) 64.9Water flow @ 10.0 F rise 2.99 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.3 / 58.3 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.6 FBypass Factor 0.120Resulting RH 53 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 846 CFMStandard CFM 824 CFMActual max CFM/ft 3.68 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 51 CFMCFM/ft 0.22 CFM/ft

    CFM/person 51.40 CFM/person

    Hourly Analysis Program v4.60 Page 28 of 124

  • Air System Sizing Summary for 029. GF - Solid State LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 029. GF - Solid State LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 125.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.9 TonsTotal coil load 10.4 MBHSensible coil load 10.1 MBHCoil CFM at Jul 1500 586 CFMMax block CFM 586 CFMSum of peak zone CFM 586 CFMSensible heat ratio 0.970ft/Ton 144.7BTU/(hr-ft) 82.9Water flow @ 10.0 F rise 2.07 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.2 / 58.3 FLeaving DB / WB 52.9 / 51.6 FCoil ADP 50.7 FBypass Factor 0.120Resulting RH 54 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 586 CFMStandard CFM 571 CFMActual max CFM/ft 4.68 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 33 CFMCFM/ft 0.26 CFM/ft

    CFM/person 32.50 CFM/person

    Hourly Analysis Program v4.60 Page 29 of 124

  • Air System Sizing Summary for 030. GF - Raman SpectroscopyProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 030. GF - Raman SpectroscopyEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 90.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.9 TonsTotal coil load 10.6 MBHSensible coil load 10.3 MBHCoil CFM at Jul 1500 609 CFMMax block CFM 609 CFMSum of peak zone CFM 609 CFMSensible heat ratio 0.971ft/Ton 101.9BTU/(hr-ft) 117.8Water flow @ 10.0 F rise 2.12 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.0 / 58.2 FLeaving DB / WB 52.9 / 51.7 FCoil ADP 50.7 FBypass Factor 0.120Resulting RH 54 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 609 CFMStandard CFM 593 CFMActual max CFM/ft 6.76 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 26 CFMCFM/ft 0.29 CFM/ft

    CFM/person 26.20 CFM/person

    Hourly Analysis Program v4.60 Page 30 of 124

  • Air System Sizing Summary for 031. GF - Lobby - 01Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 031. GF - Lobby - 01Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 550.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.0 TonsTotal coil load 24.6 MBHSensible coil load 23.2 MBHCoil CFM at Aug 1500 1447 CFMMax block CFM 1447 CFMSum of peak zone CFM 1447 CFMSensible heat ratio 0.945ft/Ton 268.7BTU/(hr-ft) 44.7Water flow @ 10.0 F rise 4.92 gpm

    Load occurs at Aug 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 69.9 / 59.7 FLeaving DB / WB 54.7 / 53.5 FCoil ADP 52.6 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 15.8 MBHCoil CFM at Sep 1100 1447 CFMMax coil CFM 1447 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Sep 1100BTU/(hr-ft) 28.7Ent. DB / Lvg DB 55.3 / 65.6 F

    Supply Fan Sizing DataActual max CFM 1447 CFMStandard CFM 1411 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 79 CFMCFM/ft 0.14 CFM/ft

    CFM/person 10.62 CFM/person

    Hourly Analysis Program v4.60 Page 31 of 124

  • Air System Sizing Summary for 032. GF - Hub RoomProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 032. GF - Hub RoomEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.8 TonsTotal coil load 9.2 MBHSensible coil load 9.1 MBHCoil CFM at Jul 1500 630 CFMMax block CFM 630 CFMSum of peak zone CFM 630 CFMSensible heat ratio 0.988ft/Ton 196.5BTU/(hr-ft) 61.1Water flow @ 10.0 F rise 1.83 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 66.6 / 57.4 FLeaving DB / WB 53.0 / 51.9 FCoil ADP 51.1 FBypass Factor 0.120Resulting RH 57 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 630 CFMStandard CFM 614 CFMActual max CFM/ft 4.20 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 14 CFMCFM/ft 0.09 CFM/ft

    CFM/person 17.28 CFM/person

    Hourly Analysis Program v4.60 Page 32 of 124

  • Air System Sizing Summary for 033. GF - Low Temperature LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 033. GF - Low Temperature LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 250.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.5 TonsTotal coil load 29.5 MBHSensible coil load 28.9 MBHCoil CFM at Jul 1600 1828 CFMMax block CFM 1828 CFMSum of peak zone CFM 1828 CFMSensible heat ratio 0.980ft/Ton 101.8BTU/(hr-ft) 117.8Water flow @ 10.0 F rise 5.89 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 68.1 / 58.0 FLeaving DB / WB 53.1 / 51.9 FCoil ADP 51.0 FBypass Factor 0.120Resulting RH 55 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 1828 CFMStandard CFM 1782 CFMActual max CFM/ft 7.31 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 65 CFMCFM/ft 0.26 CFM/ft

    CFM/person 32.50 CFM/person

    Hourly Analysis Program v4.60 Page 33 of 124

  • Air System Sizing Summary for 034. GF - PL RoomProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 034. GF - PL RoomEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 120.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.2 TonsTotal coil load 13.8 MBHSensible coil load 13.6 MBHCoil CFM at Jul 1600 841 CFMMax block CFM 841 CFMSum of peak zone CFM 841 CFMSensible heat ratio 0.979ft/Ton 104.0BTU/(hr-ft) 115.4Water flow @ 10.0 F rise 2.77 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 68.4 / 58.1 FLeaving DB / WB 53.0 / 51.9 FCoil ADP 51.0 FBypass Factor 0.120Resulting RH 54 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 841 CFMStandard CFM 820 CFMActual max CFM/ft 7.01 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 32 CFMCFM/ft 0.26 CFM/ft

    CFM/person 31.60 CFM/person

    Hourly Analysis Program v4.60 Page 34 of 124

  • Air System Sizing Summary for 035. GF - Clean LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 035. GF - Clean LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 200.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.8 TonsTotal coil load 21.3 MBHSensible coil load 20.7 MBHCoil CFM at Jul 1600 1278 CFMMax block CFM 1278 CFMSum of peak zone CFM 1278 CFMSensible heat ratio 0.972ft/Ton 112.6BTU/(hr-ft) 106.5Water flow @ 10.0 F rise 4.26 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 68.5 / 58.2 FLeaving DB / WB 53.1 / 51.9 FCoil ADP 51.0 FBypass Factor 0.120Resulting RH 55 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 1278 CFMStandard CFM 1246 CFMActual max CFM/ft 6.39 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 56 CFMCFM/ft 0.28 CFM/ft

    CFM/person 28.00 CFM/person

    Hourly Analysis Program v4.60 Page 35 of 124

  • Air System Sizing Summary for 036. GF - Oven labProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 036. GF - Oven labEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 210.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.3 TonsTotal coil load 27.4 MBHSensible coil load 26.9 MBHCoil CFM at Jul 1600 1696 CFMMax block CFM 1696 CFMSum of peak zone CFM 1696 CFMSensible heat ratio 0.978ft/Ton 91.8BTU/(hr-ft) 130.7Water flow @ 10.0 F rise 5.49 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 68.1 / 58.0 FLeaving DB / WB 53.1 / 51.9 FCoil ADP 51.0 FBypass Factor 0.120Resulting RH 55 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 1696 CFMStandard CFM 1653 CFMActual max CFM/ft 8.07 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 58 CFMCFM/ft 0.28 CFM/ft

    CFM/person 28.90 CFM/person

    Hourly Analysis Program v4.60 Page 36 of 124

  • Air System Sizing Summary for 037. GF - StoreProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 037. GF - StoreEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 120.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.4 TonsTotal coil load 4.4 MBHSensible coil load 4.2 MBHCoil CFM at Jul 2200 316 CFMMax block CFM 316 CFMSum of peak zone CFM 316 CFMSensible heat ratio 0.951ft/Ton 327.1BTU/(hr-ft) 36.7Water flow @ 10.0 F rise 0.88 gpm

    Load occurs at Jul 2200OA DB / WB 95.3 / 67.7 FEntering DB / WB 70.1 / 61.4 FLeaving DB / WB 57.5 / 56.5 FCoil ADP 55.8 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.3 MBHCoil CFM at Des Htg 316 CFMMax coil CFM 316 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 10.8Ent. DB / Lvg DB 66.7 / 70.6 F

    Supply Fan Sizing DataActual max CFM 316 CFMStandard CFM 308 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 14 CFMCFM/ft 0.12 CFM/ft

    CFM/person 12.00 CFM/person

    Hourly Analysis Program v4.60 Page 37 of 124

  • Air System Sizing Summary for 038. GF - Corridor(4)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 038. GF - Corridor(4)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1250.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 4.6 TonsTotal coil load 55.2 MBHSensible coil load 52.5 MBHCoil CFM at Aug 1500 3289 CFMMax block CFM 3289 CFMSum of peak zone CFM 3289 CFMSensible heat ratio 0.952ft/Ton 271.7BTU/(hr-ft) 44.2Water flow @ 10.0 F rise 11.05 gpm

    Load occurs at Aug 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 71.4 / 61.0 FLeaving DB / WB 56.2 / 55.1 FCoil ADP 54.2 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 35.2 MBHCoil CFM at Jun 0900 3289 CFMMax coil CFM 3289 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Jun 0900BTU/(hr-ft) 28.2Ent. DB / Lvg DB 57.2 / 67.4 F

    Supply Fan Sizing DataActual max CFM 3289 CFMStandard CFM 3206 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 179 CFMCFM/ft 0.14 CFM/ft

    CFM/person 10.62 CFM/person

    Hourly Analysis Program v4.60 Page 38 of 124

  • Air System Sizing Summary for 039. Open Corridor (TH)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 039. Open Corridor (TH)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1350.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 10.8 TonsTotal coil load 129.8 MBHSensible coil load 127.4 MBHCoil CFM at Jun 1700 6088 CFMMax block CFM 6088 CFMSum of peak zone CFM 6088 CFMSensible heat ratio 0.981ft/Ton 124.8BTU/(hr-ft) 96.2Water flow @ 10.0 F rise 25.98 gpm

    Load occurs at Jun 1700OA DB / WB 106.8 / 71.4 FEntering DB / WB 73.3 / 59.8 FLeaving DB / WB 53.4 / 51.9 FCoil ADP 50.7 FBypass Factor 0.120Resulting RH 45 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 29.6 MBHCoil CFM at Des Htg 6088 CFMMax coil CFM 6088 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 21.9Ent. DB / Lvg DB 66.8 / 71.4 F

    Supply Fan Sizing DataActual max CFM 6088 CFMStandard CFM 5934 CFMActual max CFM/ft 4.51 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 81 CFMCFM/ft 0.06 CFM/ft

    CFM/person 7.41 CFM/person

    Hourly Analysis Program v4.60 Page 39 of 124

  • Air System Sizing Summary for 040. GF - Corridor(5)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 040. GF - Corridor(5)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1100.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 4.0 TonsTotal coil load 48.5 MBHSensible coil load 46.2 MBHCoil CFM at Aug 1500 2895 CFMMax block CFM 2895 CFMSum of peak zone CFM 2895 CFMSensible heat ratio 0.952ft/Ton 272.0BTU/(hr-ft) 44.1Water flow @ 10.0 F rise 9.71 gpm

    Load occurs at Aug 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 71.5 / 61.1 FLeaving DB / WB 56.3 / 55.1 FCoil ADP 54.3 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 30.5 MBHCoil CFM at Mar 1200 2895 CFMMax coil CFM 2895 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Mar 1200BTU/(hr-ft) 27.8Ent. DB / Lvg DB 56.9 / 66.9 F

    Supply Fan Sizing DataActual max CFM 2895 CFMStandard CFM 2821 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 158 CFMCFM/ft 0.14 CFM/ft

    CFM/person 10.62 CFM/person

    Hourly Analysis Program v4.60 Page 40 of 124

  • Air System Sizing Summary for 041.GF-Clean Room EntryProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 041.GF-Clean Room EntryEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 130.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.4 MBHSensible coil load 5.2 MBHCoil CFM at Jun 1500 342 CFMMax block CFM 342 CFMSum of peak zone CFM 342 CFMSensible heat ratio 0.966ft/Ton 287.2BTU/(hr-ft) 41.8Water flow @ 10.0 F rise 1.09 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 70.0 / 60.0 FLeaving DB / WB 55.5 / 54.3 FCoil ADP 53.5 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 3.0 MBHCoil CFM at Mar 1000 342 CFMMax coil CFM 342 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Mar 1000BTU/(hr-ft) 23.2Ent. DB / Lvg DB 55.3 / 63.7 F

    Supply Fan Sizing DataActual max CFM 342 CFMStandard CFM 333 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 23 CFMCFM/ft 0.18 CFM/ft

    CFM/person 23.40 CFM/person

    Hourly Analysis Program v4.60 Page 41 of 124

  • Air System Sizing Summary for 042. GF - Dry White LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 042. GF - Dry White LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 250.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.5 TonsTotal coil load 29.6 MBHSensible coil load 29.0 MBHCoil CFM at Jul 1700 2105 CFMMax block CFM 2105 CFMSum of peak zone CFM 2105 CFMSensible heat ratio 0.982ft/Ton 101.5BTU/(hr-ft) 118.2Water flow @ 10.0 F rise 5.91 gpm

    Load occurs at Jul 1700OA DB / WB 107.8 / 71.4 FEntering DB / WB 67.5 / 58.6 FLeaving DB / WB 54.4 / 53.4 FCoil ADP 52.6 FBypass Factor 0.120Resulting RH 59 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 4.3 MBHCoil CFM at Oct 0600 2105 CFMMax coil CFM 2105 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Oct 0600BTU/(hr-ft) 17.3Ent. DB / Lvg DB 57.9 / 59.8 F

    Supply Fan Sizing DataActual max CFM 2105 CFMStandard CFM 2052 CFMActual max CFM/ft 8.42 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 65 CFMCFM/ft 0.26 CFM/ft

    CFM/person 32.50 CFM/person

    Hourly Analysis Program v4.60 Page 42 of 124

  • Air System Sizing Summary for 043. GF - Air Lock (2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 043. GF - Air Lock (2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 55.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.2 TonsTotal coil load 2.4 MBHSensible coil load 2.3 MBHCoil CFM at Jun 1500 145 CFMMax block CFM 145 CFMSum of peak zone CFM 145 CFMSensible heat ratio 0.953ft/Ton 269.5BTU/(hr-ft) 44.5Water flow @ 10.0 F rise 0.49 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 70.1 / 59.8 FLeaving DB / WB 54.8 / 53.6 FCoil ADP 52.7 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 0.9 MBHCoil CFM at Mar 1200 145 CFMMax coil CFM 145 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Mar 1200BTU/(hr-ft) 16.3Ent. DB / Lvg DB 55.3 / 61.2 F

    Supply Fan Sizing DataActual max CFM 145 CFMStandard CFM 141 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 10 CFMCFM/ft 0.18 CFM/ft

    CFM/person 9.90 CFM/person

    Hourly Analysis Program v4.60 Page 43 of 124

  • Air System Sizing Summary for 044. GF - Dry Yellow LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 044. GF - Dry Yellow LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 200.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.0 TonsTotal coil load 23.7 MBHSensible coil load 23.2 MBHCoil CFM at Jun 1500 1684 CFMMax block CFM 1684 CFMSum of peak zone CFM 1684 CFMSensible heat ratio 0.980ft/Ton 101.2BTU/(hr-ft) 118.5Water flow @ 10.0 F rise 4.74 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 68.9 / 59.9 FLeaving DB / WB 55.8 / 54.8 FCoil ADP 54.0 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 6.6 MBHCoil CFM at Nov 0500 1684 CFMMax coil CFM 1684 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Nov 0500BTU/(hr-ft) 33.1Ent. DB / Lvg DB 57.8 / 61.5 F

    Supply Fan Sizing DataActual max CFM 1684 CFMStandard CFM 1642 CFMActual max CFM/ft 8.42 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 56 CFMCFM/ft 0.28 CFM/ft

    CFM/person 28.00 CFM/person

    Hourly Analysis Program v4.60 Page 44 of 124

  • Air System Sizing Summary for 045. GF - Wet Yellow LabProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 045. GF - Wet Yellow LabEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 230.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.7 TonsTotal coil load 32.8 MBHSensible coil load 32.2 MBHCoil CFM at Jul 1600 2041 CFMMax block CFM 2041 CFMSum of peak zone CFM 2041 CFMSensible heat ratio 0.982ft/Ton 84.2BTU/(hr-ft) 142.6Water flow @ 10.0 F rise 6.56 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 68.0 / 58.0 FLeaving DB / WB 53.1 / 51.9 FCoil ADP 51.0 FBypass Factor 0.120Resulting RH 55 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataNo central heating coil loads occurred during this calculation.

    Supply Fan Sizing DataActual max CFM 2041 CFMStandard CFM 1990 CFMActual max CFM/ft 8.88 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 61 CFMCFM/ft 0.27 CFM/ft

    CFM/person 30.70 CFM/person

    Hourly Analysis Program v4.60 Page 45 of 124

  • Air System Sizing Summary for 046. GF - Etching labProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 046. GF - Etching labEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 130.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.0 TonsTotal coil load 11.6 MBHSensible coil load 11.3 MBHCoil CFM at Jun 1600 714 CFMMax block CFM 714 CFMSum of peak zone CFM 714 CFMSensible heat ratio 0.973ft/Ton 134.6BTU/(hr-ft) 89.1Water flow @ 10.0 F rise 2.32 gpm

    Load occurs at Jun 1600OA DB / WB 108.4 / 71.8 FEntering DB / WB 68.3 / 58.3 FLeaving DB / WB 53.3 / 52.2 FCoil ADP 51.3 FBypass Factor 0.120Resulting RH 56 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 714 CFMStandard CFM 696 CFMActual max CFM/ft 5.50 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 33 CFMCFM/ft 0.26 CFM/ft

    CFM/person 33.40 CFM/person

    Hourly Analysis Program v4.60 Page 46 of 124

  • Air System Sizing Summary for 047. GF - NMR labProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 047. GF - NMR labEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 180.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.9 TonsTotal coil load 10.4 MBHSensible coil load 10.1 MBHCoil CFM at Sep 1700 651 CFMMax block CFM 651 CFMSum of peak zone CFM 651 CFMSensible heat ratio 0.977ft/Ton 208.2BTU/(hr-ft) 57.6Water flow @ 10.0 F rise 2.08 gpm

    Load occurs at Sep 1700OA DB / WB 105.8 / 70.4 FEntering DB / WB 68.8 / 58.7 FLeaving DB / WB 54.0 / 52.8 FCoil ADP 51.9 FBypass Factor 0.120Resulting RH 57 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Supply Fan Sizing DataActual max CFM 651 CFMStandard CFM 635 CFMActual max CFM/ft 3.62 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 42 CFMCFM/ft 0.24 CFM/ft

    CFM/person 42.40 CFM/person

    Hourly Analysis Program v4.60 Page 47 of 124

  • Air System Sizing Summary for 101. FF Lecture HallProject Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 101. FF Lecture HallEquipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 450.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 2.7 TonsTotal coil load 31.9 MBHSensible coil load 28.8 MBHCoil CFM at Jul 1600 1184 CFMMax block CFM 1184 CFMSum of peak zone CFM 1184 CFMSensible heat ratio 0.902ft/Ton 169.4BTU/(hr-ft) 70.8Water flow @ 10.0 F rise 6.38 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 77.8 / 62.6 FLeaving DB / WB 54.7 / 53.0 FCoil ADP 51.6 FBypass Factor 0.120Resulting RH 57 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 10.0 MBHCoil CFM at Des Htg 1184 CFMMax coil CFM 1184 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 22.3Ent. DB / Lvg DB 62.6 / 70.6 F

    Supply Fan Sizing DataActual max CFM 1184 CFMStandard CFM 1154 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 260 CFMCFM/ft 0.58 CFM/ft

    CFM/person 8.37 CFM/person

    Hourly Analysis Program v4.60 Page 48 of 124

  • Air System Sizing Summary for 102. FF Faculty Cabin(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 102. FF Faculty Cabin(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.8 MBHSensible coil load 5.6 MBHCoil CFM at Jun 1500 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.967ft/Ton 309.9BTU/(hr-ft) 38.7Water flow @ 10.0 F rise 1.16 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 71.8 / 62.3 FLeaving DB / WB 58.3 / 57.2 FCoil ADP 56.5 FBypass Factor 0.120Resulting RH 65 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.9 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.5Ent. DB / Lvg DB 69.0 / 73.5 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 49 of 124

  • Air System Sizing Summary for 103. FF Faculty Cabin(2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 103. FF Faculty Cabin(2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.8 MBHSensible coil load 5.6 MBHCoil CFM at Jul 1600 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.966ft/Ton 291.5BTU/(hr-ft) 41.2Water flow @ 10.0 F rise 1.15 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 72.1 / 62.0 FLeaving DB / WB 57.7 / 56.6 FCoil ADP 55.8 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.7 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.1Ent. DB / Lvg DB 65.9 / 70.3 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 50 of 124

  • Air System Sizing Summary for 104. FF Faculty Cabin(3)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 104. FF Faculty Cabin(3)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.2 MBHSensible coil load 5.9 MBHCoil CFM at Jun 1600 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.953ft/Ton 269.7BTU/(hr-ft) 44.5Water flow @ 10.0 F rise 1.25 gpm

    Load occurs at Jun 1600OA DB / WB 108.4 / 71.8 FEntering DB / WB 71.7 / 61.2 FLeaving DB / WB 56.4 / 55.2 FCoil ADP 54.3 FBypass Factor 0.120Resulting RH 61 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.8Ent. DB / Lvg DB 66.1 / 70.7 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 51 of 124

  • Air System Sizing Summary for 105. FF Faculty Cabin(4)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 105. FF Faculty Cabin(4)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.9 MBHSensible coil load 5.7 MBHCoil CFM at Jun 1500 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.968ft/Ton 306.6BTU/(hr-ft) 39.1Water flow @ 10.0 F rise 1.17 gpm

    Load occurs at Jun 1500OA DB / WB 109.0 / 72.0 FEntering DB / WB 72.0 / 62.3 FLeaving DB / WB 58.3 / 57.2 FCoil ADP 56.4 FBypass Factor 0.120Resulting RH 64 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 11.8Ent. DB / Lvg DB 66.1 / 70.4 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 52 of 124

  • Air System Sizing Summary for 106. FF Faculty Cabin(5)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 106. FF Faculty Cabin(5)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 150.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.1 MBHSensible coil load 5.9 MBHCoil CFM at Jul 1600 395 CFMMax block CFM 395 CFMSum of peak zone CFM 395 CFMSensible heat ratio 0.968ft/Ton 294.3BTU/(hr-ft) 40.8Water flow @ 10.0 F rise 1.22 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 72.0 / 61.9 FLeaving DB / WB 57.7 / 56.6 FCoil ADP 55.8 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 395 CFMMax coil CFM 395 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 11.8Ent. DB / Lvg DB 66.3 / 70.6 F

    Supply Fan Sizing DataActual max CFM 395 CFMStandard CFM 385 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 29 CFMCFM/ft 0.19 CFM/ft

    CFM/person 8.95 CFM/person

    Hourly Analysis Program v4.60 Page 53 of 124

  • Air System Sizing Summary for 107. FF - Corridor(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 107. FF - Corridor(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 1100.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 3.8 TonsTotal coil load 45.1 MBHSensible coil load 43.9 MBHCoil CFM at Aug 1500 2895 CFMMax block CFM 2895 CFMSum of peak zone CFM 2895 CFMSensible heat ratio 0.972ft/Ton 292.6BTU/(hr-ft) 41.0Water flow @ 10.0 F rise 9.03 gpm

    Load occurs at Aug 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 71.2 / 61.1 FLeaving DB / WB 56.8 / 55.6 FCoil ADP 54.8 FBypass Factor 0.120Resulting RH 60 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 30.5 MBHCoil CFM at Jul 0900 2895 CFMMax coil CFM 2895 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Jul 0900BTU/(hr-ft) 27.7Ent. DB / Lvg DB 57.3 / 67.3 F

    Supply Fan Sizing DataActual max CFM 2895 CFMStandard CFM 2821 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 121 CFMCFM/ft 0.11 CFM/ft

    CFM/person 13.58 CFM/person

    Hourly Analysis Program v4.60 Page 54 of 124

  • Air System Sizing Summary for 108. FF Faculty Cabin(6)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 108. FF Faculty Cabin(6)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.8 MBHSensible coil load 5.6 MBHCoil CFM at Jul 1600 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.966ft/Ton 291.5BTU/(hr-ft) 41.2Water flow @ 10.0 F rise 1.15 gpm

    Load occurs at Jul 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 72.1 / 62.0 FLeaving DB / WB 57.7 / 56.6 FCoil ADP 55.8 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.7 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.1Ent. DB / Lvg DB 65.9 / 70.3 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 55 of 124

  • Air System Sizing Summary for 109. FF Faculty Cabin(7)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 109. FF Faculty Cabin(7)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 6.2 MBHSensible coil load 5.9 MBHCoil CFM at Jun 1600 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.953ft/Ton 269.7BTU/(hr-ft) 44.5Water flow @ 10.0 F rise 1.25 gpm

    Load occurs at Jun 1600OA DB / WB 108.4 / 71.8 FEntering DB / WB 71.7 / 61.2 FLeaving DB / WB 56.4 / 55.2 FCoil ADP 54.3 FBypass Factor 0.120Resulting RH 61 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.8Ent. DB / Lvg DB 66.1 / 70.7 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 56 of 124

  • Air System Sizing Summary for 110. FF Faculty Cabin(8)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 110. FF Faculty Cabin(8)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 140.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 0.5 TonsTotal coil load 5.8 MBHSensible coil load 5.6 MBHCoil CFM at Jul 1500 368 CFMMax block CFM 368 CFMSum of peak zone CFM 368 CFMSensible heat ratio 0.965ft/Ton 287.8BTU/(hr-ft) 41.7Water flow @ 10.0 F rise 1.17 gpm

    Load occurs at Jul 1500OA DB / WB 110.0 / 72.0 FEntering DB / WB 72.1 / 61.9 FLeaving DB / WB 57.6 / 56.4 FCoil ADP 55.6 FBypass Factor 0.120Resulting RH 63 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 1.8 MBHCoil CFM at Des Htg 368 CFMMax coil CFM 368 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 12.7Ent. DB / Lvg DB 66.2 / 70.8 F

    Supply Fan Sizing DataActual max CFM 368 CFMStandard CFM 359 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 28 CFMCFM/ft 0.20 CFM/ft

    CFM/person 8.77 CFM/person

    Hourly Analysis Program v4.60 Page 57 of 124

  • Air System Sizing Summary for 111.FF Student Centre(1)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 111.FF Student Centre(1)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 290.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individual peak space loads

    Calculation Months Jan to DecSizing Data Calculated

    Central Cooling Coil Sizing DataTotal coil load 1.2 TonsTotal coil load 14.8 MBHSensible coil load 14.0 MBHCoil CFM at Aug 1600 763 CFMMax block CFM 763 CFMSum of peak zone CFM 763 CFMSensible heat ratio 0.949ft/Ton 235.4BTU/(hr-ft) 51.0Water flow @ 10.0 F rise 2.96 gpm

    Load occurs at Aug 1600OA DB / WB 109.4 / 71.8 FEntering DB / WB 75.8 / 63.5 FLeaving DB / WB 58.3 / 56.9 FCoil ADP 55.9 FBypass Factor 0.120Resulting RH 66 %Design supply temp. 53.6 FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 F

    Central Heating Coil Sizing DataMax coil load 5.0 MBHCoil CFM at Des Htg 763 CFMMax coil CFM 763 CFMWater flow @ 20.0 F drop N/A

    Load occurs at Des HtgBTU/(hr-ft) 17.4Ent. DB / Lvg DB 67.2 / 73.5 F

    Supply Fan Sizing DataActual max CFM 763 CFMStandard CFM 744 CFMActual max CFM/ft 2.63 CFM/ft

    Fan motor BHP 0.00 BHPFan motor kW 0.00 kWFan static 0.00 in wg

    Outdoor Ventilation Air DataDesign airflow CFM 130 CFMCFM/ft 0.45 CFM/ft

    CFM/person 8.66 CFM/person

    Hourly Analysis Program v4.60 Page 58 of 124

  • Air System Sizing Summary for 112.FF Student Centre(2)Project Name: SNU, SNS Annex Building 08-05-2013Prepared by: ANA Design Consultancy 01:03PM

    Air System InformationAir System Name 112.FF Student Centre(2)Equipment Class CW AHUAir System Type SZCAV

    Number of zones 1Floor Area 450.0 ftLocation New Delhi, India

    Sizing Calculation InformationZone and Space Sizing Method:Zone CFM Sum of space airflow ratesSpace CFM Individ