SYSTEM MANUAL Rev.01 17.02.17 www.puckfire.com © 2016 by Puck Fire Ltd Description PUCK is a revolutionary fire suppression system offering discrete protection coupled with industry leading pricing, efficient system design and easy install. PUCK’s lightweight nozzles sit just 3mm below the ceiling making them non-intrusive whilst offering complete protection. These nozzles connect to a compact pump unit using flexible pipework and easyfit fittings. This keeps design and install time to an absolute minimum and allows for potentially large install savings. The PUCK pump unit includes a self-test facility which is adjustable in the companion app. The app monitors the unit in real time whilst receiving alerts on faults and activations. PUCK is compatible with all fire panels offering fire and fault n/o and n/c contacts.

Upload: others

Post on 05-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

SYSTEM MANUAL

Rev.01 17.02.17

www.puckfire.com © 2016 by Puck Fire Ltd

Description

PUCK is a revolutionary fire suppression system offering discrete protection coupled with industry leading pricing, efficient system design and easy install. PUCK’s lightweight nozzles sit just 3mm below the ceiling making them non-intrusive whilst offering complete protection. These nozzles connect to a compact pump unit using flexible pipework and easyfit fittings. This keeps design and install time to an absolute minimum and allows for potentially large install savings. The PUCK pump unit includes a self-test facility which is adjustable in the companion app. The app monitors the unit in real time whilst receiving alerts on faults and activations. PUCK is compatible with all fire panels offering fire and fault n/o and n/c contacts.

Page 2: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Certifications

● PUCK is 3rd party fire tested to BS:8458 for use up to 80m2

● PUCK is 3rd party fire tested BS:9252

Requirements

● PUCK’s flexible pipework must be installed behind fire rated barrier

● Only PUCK supplied products to be used to ensure system performs as marketed

● Connected water source must supply no less than 12 litres per minute

● Pump unit must not be installed in sealed area, ventilation required.

Advantages

● Industry leading pricing

● Low profile nozzles (colour matching available)

● Compact pump unit

● Low flow system, mains supplied, does not require large water storage tank

● Push fit fittings, allows for easy system install

● Flexible pipework, pipework can be easily measured and cut on site minimising design time

● Customisable self-test facility

● Compatible with fire panels using voltage free contacts

● Wireless monitoring

● Stainless steel pipework available where system is not installed behind fire rated barrier

Page 3: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

TECHNICAL DATA

Technical Data

Pump Unit

Part No: PU_0001

Dimensions: 345mm x 280mm x 268mm

Voltage rating: 240V

Current rating: 13A

Fire relay contact rating: 30VDC, 1A max

Fault relay contact rating: 30VDC, 1A max

Inlet connection: ½” BSP

Outlet connection: ¼” BSP

Water requirement: 12 lpm - 1 bar Minimum

LED status colours: Blue - Primed

Orange - Wi-Fi connection fault

Red - Activation

Page 4: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Nozzle

Part No: PU_0034

Dimensions: ⌀72mm x 19mm

Weight: 48g

Standard Colour: White

Bulb specification: 57°C, quick response

Fixing method: Torsion springs

Hole diameter for install: ⌀56-60mm

Flexible Pipework - 30m coil

Part No: PU_0031

Dimensions: ⌀10mm, 30m reels (longer on request)

Colour: Bend Radius:

Red 40mm

Max pipework length: Straight run reach - 20m Loop reach - 30m (60m total pipework)

Fixing method: P-clips

Page 5: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Stainless Steel Rigid Pipework

Part No: PU-0045

Dimensions: 3/8”, 3m lengths

Material: Stainless steel

Finish: Metallic

Max pipework length: TBC

Fixing method: 8mm munsen ring

Page 6: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Compression Fittings

Part No: PU-0046 - Tee PU-0047 - Elbow PU-0048 - Threaded adapter PU-0049 - Straight

Fixing type: Compression

Material: Brass

Finish: Nickel Plated

Works with: PUCK Flexible pipework PUCK stainless steel rigid pipework

Inlet Manifold

Part No: PU-0041

Inlet connection: 15mm compression fitting

Outlet connection: ½” BSP (to pump)

Approvals: WRAS approved

¼” Isolation Valve

Part No: PU-0043

Inlet connection: ¼” BSP

Outlet connection: ¼” BSP

Material: Stainless steel

Page 7: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Self-Centring Bonded Seal

Part No: PU-0037

Material: Zinc plated steel

Seal type: Nitrile

Diameter: ¼” BSP

P-Clip

Part No: PU-0040

Material: Galvanised steel, Rubber

Diameter: ⌀12mm

Pressure Relief Valve

Part No: PU-0054

Material: Brass

Diameter: 1/4”- 1/8” BSP

Function: Prevents system over pressurisation

¼” BSP CAP

Part No: PU-045

Material: Brass Nickel Plated

Diameter: 1/4”- BSP

Function: End cap

Page 8: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

1/2” Strainer

Part No: PU-042

Material: Brass

Diameter: 1/2”- BSP

Function: Water Filtration

WARNING: ONLY PUCK APPROVED COMPONENTS MAY BE USED WITH THIS SYSTEM. NO COMPONENT OF THE PUCK SYSTEM MAY BE MODIFIED. DOING SO WILL VOID THE COMPONENTS/SYSTEMS WARRANTY

Page 9: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

SYSTEM DESIGN This manual contains manufacturers recommendations for the design, installation and commissioning of the PUCK fire and suppression system. This manual should be read in conjunction with the following standards as applicable: BS 8458 BS 9251 BS 9252 BS 7671 (Other standards may apply) Category of System The designer should at an early stage determine which category of system is applicable, as this affects various design considerations, such as the water requirements for the system. The category of system should be determined by the type of building as shown below. Domestic occupancy Single family dwellings such as: • Individual dwelling house

• Individual flat • Individual maisonette • Transportable home Houses of multiple occupation (HMOs) A) Bed and breakfast accommodation A) Boarding houses A) Blocks of flats 18 m or less in height and with a maximum total floor area of 2 400 m2 B), C)

Residential occupancy Blocks of flats greater than 18 m in height C) Sheltered and extra care housing

Residential care premises Residential rehabilitation accommodation Dormitories (e.g. attached to educational establishments) Hostels

A) Buildings with more than two floors and five or more lettable bedrooms should be treated as a residential occupancy. B) Where the fire strategy requires the communal rooms and corridors to be protected by a watermist system, then the building should be treated as a residential occupancy.

Page 10: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

C) This height is the height of the floor of the top storey above ground. Water Supplies

Our recommendation is to install 1 pump for domestic occupancies and a dual pump system for residential occupancies.

Where the mains water supply connection serves only the watermist system, the flow rates at each pump must be 12lpm.

Where the mains water supply connection serves both the watermist system and the domestic or residential occupancy supply, the watermist system should be capable of providing the water demand at the pump/s by:

a) the operation of an automatic priority demand valve; or

b) for domestic occupancies, the flow rate at the pump plus at least 25 L/min; or

NOTE 1 Attention is drawn to the water regulations, which might require a greater minimum flow rate.

c) for residential occupancies, the flow rate at the pump plus at least 50 L/min.

NOTE 2 Attention is drawn to the water regulations which might require a greater minimum flow rate depending on the design demand for the occupancy

Flows should be tested and verified at the main water supply pipe to the property

Page 11: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Nozzle Spacing, Flat Ceilings –

Nozzle Spacing, Sloped Ceilings- Where nozzles are fitted within a sloping ceilings, nozzle positions should be determined by the pitch of the ceiling. Where the pitch is below 30°, nozzles should be mounted at standard spacing’s when measured in line with the pitch of the ceiling. Where the pitch is 30° and above, the first row of nozzles should be mounted within 300 mm radially from the apex of the ceiling. All nozzles should be mounted perpendicular to the ceiling as shown below

• 4x4m Grid (16M2)

• Max 2m from wall

• Minimum distance

between nozzles =2m

Page 12: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Distance from Obstructions Nozzles should be positioned away from obstructions to allow a 140 degree spray pattern.

Nozzle orientation

Page 13: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

The preferred nozzle outlet orientation is perpendicular to the walls

Maximum Pipe Lengths

Pipe work should be configured as a loop not exceeding 60m in total length. Maximum 40 nozzles per loop. Loop length must be reduced by 1m for every tee or elbow added on the loop. Pipe length from the tee to the nozzle can be up to 1m long with one elbow without reducing the loop length.

Page 14: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Multi Loop Configuration example

Pipework Flexible tubing should only be used behind a fire rated barrier Stainless steel tubing should be used for any areas where pipework is exposed. Nozzles for exposed pipework should not be positioned more than 300mm below the slab

Page 15: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

The image below shows example piping networks for domestic and residential.

Domestic Residential

Pump 1 Pump 2

Page 16: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

INSTALLATION & COMMISSIONING

WARNING Mains voltage electricity and high pressure water are present within this product. Care should be taken when installing the product. Installation should only be carried out by trained engineers. Appropriate PPE should be worn at all times when installing the product. Eye protection, gloves, safety boots and hard hat.

1. Remove all packaging from the components provided.

2. Install a 240v, 13A un-switched spur next to the proposed pump position.

Page 17: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

3. Connect strainer, inlet manifold and flexible hose to the mains water (ensure mains water is switched off before breaking into the water supply).

4. Verify the water supply flow by running it into a bucket to confirm the correct flow

5. Ensure the isolation valve in the inlet manifold is set to the closed position.

6. If provided with a monitoring system make connections to fire and fault relays as required. Access

can be gained to the electronics by removing the screws on the lid on the underside of the pump.

Page 18: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

WARNING The pump unit must be completely powered down before opening the electronics

enclosure

7. Refit lid to the electronics and position the pump it it’s final location. The pump must be situated

in a well ventilated area with no less that 100mm of free space around all sides of the unit. The

top of the pump unit must stay clear of any objects to allow for proper airflow and performance.

The pump must be located in a position above 4°C.

8. Connect power cable to un-switched spur ensuring that the power remains switched off at all times. Do not run the pump without water running through it. This will damage the pumps.

9. Use the threaded end of the inlet Manifold to connect directly to the threaded fitting on the bottom section of the pump. Warning! This fitting should only need to be hand tight if this does not create a seal tighten very slightly with a spanner until a seal is created. Overtightening will damage the components.

Fire & fault connections

Page 19: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

10. Install pressure relief arrangement to the top of the pump ensuring it is correctly orientated and

connect the drain from the pressure relief manifold to the waste pipe. Do not adjust the pre-set pressure relief valve

11. Install pipework to the system using flexible pipework push fit fittings and supporting P-clips. All flexible pipework should be installed behind a fire rated barrier such as plaster board, any

CONNECT TO DRAIN

TO SYSTEM PIPEWORK AND NOZZLES

Page 20: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

exposed pipe should be installed in steel pipework. Pipework must never be exposed to temperatures below 4 °C.

12. Cut the pipework to length using pipe cutters ensuring a square edge is achieved with the cut.

13. Easyfit fittings – Insert pipe into fitting until it will not go any further. Tighten nut by using two

spanners. One spanner to tighten the nut and one spanner to hold the body of the fitting

CORRECT ✓ INCORRECT X

Example of ferrules correctly seated on pipe work

Page 21: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

14. Pushfit - Apply silicone lubricant to the end of the pipework. Insert the pipe into the fitting pushing hard to ensure that the pipe is inserted by 25mmmm. Ensure pipe is straight and is not being pulled to one side as this may create leaks

WARINING Pipework and fittings must not be installed in temperatures lower than 5°C as this can affect the ability of the pushfit to grip onto the pipework and create the required seal.

15. Use a 57-64mm hole saw to create the holes in the ceiling for fitting the nozzles.

16. Install nozzles ensuring that the 1/4” adaptor with a bonded seal is tightened with a spanner. Ensure bonded seal is used. Thread lock may be used if required. DO NOT USE PTFE OR ANY OTHER TYPE OF THREAD TAPE

17. Ensuring that the pipe network is complete open isolation valve on the inlet manifold to allow

mains pressure water into the system.

CORRECT ✓ INCORRECT X

Page 22: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

18. Slowly loosen the nozzle furthest away from the pump set to bleed the pipework of any trapped air. Allow any excess water to drain into a bucket. When all of the air has escaped remake the seal.

19. After ensuring that there are no initial leaks power up the pump to charge the system.

20. Leave to stand at system pressure for 1 hour. The pipe work will stretch over time causing some initial loss in pressure however it will settle to around 45bar.

The pumps may operate for up to 1 second to a day to make up for any small losses in pressure in the system. The pipe network should not be subject to significant leaks. The pumps should not operate more than once a day to make up loss of pressure or it may risk affect the life span of the components. Any leaks should be repaired immediately to avoid risk of damage to equipment.

21. When satisfied that there are no leaks power the pump down, shut off the water supply and put the nozzles into position using the retention springs.

22. Switch water supply and power back on to re-enable the system

Most remote nozzle

Max pipe length before tee 800mm

Page 23: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

SYSTEM MONITORING (COMING SOON)

Page 24: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Model Certificates

The system should be commissioned and inspected in accordance with the schedules below.

Page 25: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

SYSTEM INSTALLATION CERTIFICATE

Pump Serial Number

Address

Extent of system coverage

Ensure nozzles are not painted and are free from obstruction

Check nozzles are spaced in accordance with Puck design guide

Where possible ensure pipework in not damaged and in good condition

Check age of the system and condition.

Check that all relevant areas of the property are protected

Verify water supply is adequate for the property

Self-test the pump by pressing test button or opening a manual test valve

Confirm operation of fire and fault relays

Confirm operation of priority demand valve if provided

Check pump casing is in good condition

Ensure pump is positioned in a well ventilated cupboard with at least 100mm of space around top and sides

Check filter is clear

Optional - Test flow and pressure at the pump set through and open nozzle. Flow should be >10.8lpm

Exercise stop valves if provided to confirm correct operation

As the competent person responsible for the design, installation and commissioning of the PUCK fire suppression system identified above, I CERTIFY that the said work for which I have been responsible complies to the best of my knowledge and belief with the following standards where applicable BS8458, BS9251, BS7671 and manufacturer’s recommendations *except for the variations, as listed in the design specification and/or the attached schedule (delete if not applicable).

Name

Position

Signature

Date

Page 26: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

SYSTEM MAINTENANCE

Pump Serial Number

Address

Ensure nozzles are not painted and are free from obstruction

Check nozzles are spaced in accordance with Puck design guide

Where possible ensure pipework in not damaged and in good condition

Check age of the system and condition.

Check that all relevant areas of the property are protected

Verify water supply is adequate for the property

Self-test the pump by pressing test button or opening a manual test valve

Confirm operation of fire and fault relays

Confirm operation of priority demand valve if provided

Check pump casing is in good condition

Ensure pump is positioned in a well ventilated cupboard with at least 100mm of space around top and sides

Check filter is clear

Optional - Test flow and pressure at the pump set through and open nozzle. Flow should be >10.8lpm

Exercise stop valves if provided to confirm correct operation

Comments & Recommendations:

Name

Position

Signature

Date

Page 27: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 28: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 29: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 30: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 31: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 32: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 33: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 34: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 35: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 36: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 37: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 38: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 39: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.

Page 40: SYSTEM MANUAL · Refit lid to the electronics and position the pump it it’s final location. The pump must be situated in a well ventilated area with no less that 100mm of free space

www.puckfire.com ©Copyright 2016, Puck Fire Ltd. All rights reserved.