switchgear application guide 11e0.pdf

116
8/21/2019 Switchgear Application Guide 11E0.pdf http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 1/116  s Medium Voltage Technology Switchgear Application Guide

Upload: buferrero

Post on 07-Aug-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 1/116

s

Medium Voltage Technology

Switchgear Application Guide

Page 2: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 2/116

Page 3: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 3/116

s

© Siemens AG · 11E0 3

Medium Voltage Technology

Switchgear Application Guide

A Selection of Switching Devices

B Switching Duties in MV networks Overview on page 17

C Characteristic Values of Switching Devices

D Selection of HRC Fuses

E Selection of Surge Arresters

F Switchgear Configuration

G Influences and Stress Variables

H Selecting and Rating Switchgear Overview on page 84

I Annexes

J Standards

Dipl. Ing. Ansgar MüllerSiemens AGPTD M SPP.O. Box 322091050 ErlangenGermanyE-Mail: [email protected]

Edition 11E0 • 2006-07

Page 4: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 4/116

Page 5: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 5/116

Contents

© Siemens AG · 11E0 5

CONTENTS

A Selection of the Appropriate Device ..........................................................11

A 1 Selection criteria ................................................................................................................11

A 2 Suitability under normal operating conditions...................................................................12

A 3 Suitability under fault conditions.......................................................................................12

A 4 Switching frequency and endurance ..................................................................................13A 4.1 Circuit-breaker ...................................................................................................................13A 4.2 Switches and switch-disconnectors....................................................................................14A 4.3 Disconnectors and earthing-switches.................................................................................15A 4.4 Three-position switching devices.......................................................................................16

A 5 Aspects of selection for disconnectors...............................................................................16

B Switching Duties in Medium Voltage Networks.......................................17

B 1 Overview............................................................................................................................17

B 2 Transformers in distribution networks...............................................................................19

B 3 Unit transformer.................................................................................................................19

B 4 Petersen (arc quenching) coil.............................................................................................19

B 5 Cable and overhead line networks .....................................................................................20

B 6 Cable or line with short-circuit limiting reactor.................................................................21

B 7 Compensation coils (shunt reactors)..................................................................................22B 8 Motors ................................................................................................................................23B 8.1 Direct connected motor (direct on line) .............................................................................24B 8.2 Motor with transformer (unit) ............................................................................................25B 8.3 Motor with starting transformer.........................................................................................26B 8.4 Motors with starting converter...........................................................................................27B 8.5 Motors with their own p.f. improvement ...........................................................................27

B 9 Generators ..........................................................................................................................28B 9.1 Selection of the circuit-breaker..........................................................................................28B 9.2 Protective measures against overvoltage ...........................................................................29

B 9.3 Generators with Ik " ≤ 600 A feeding into a cable system..................................................30B 9.4 Generators with connection to an overhead line system, Ik " ≤ 600 A ...............................31B 9.5 Generators with connection to a cable or an overhead line system, Ik " > 600 A...............32B 9.6 Generators with connection to the HV grid, Ik " > 600 A...................................................33

B 10 Furnace transformers..........................................................................................................33B 10.1 Insulation co-ordination for operating voltages above 36 kV............................................34B 10.2 Protective measures against overvoltage ...........................................................................34

B 11 Converter transformers ......................................................................................................35B 11.1 Protective measures............................................................................................................35B 11.2 Systems up to 15 kV operating voltage .............................................................................35B 11.3 Systems above 15 kV operating voltage............................................................................36B 11.4 Selection of surge limiters and arresters ............................................................................36

Page 6: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 6/116

Contents

6 © Siemens AG · 11E0

B 12 Capacitor banks and filter circuits .....................................................................................37B 12.1 Capacitor banks (without reactor)......................................................................................37B 12.2 Reactor-capacitor combination ..........................................................................................37B 12.3 Filter circuits ......................................................................................................................38B 12.4 Permissible inrush current..................................................................................................38

B 12.5 Permissible voltage at the circuit-breaker..........................................................................39B 12.6 Calculation of the voltages at filter circuits and capacitor-reactor banks.........................41B 12.7 Additional measures necessary when switching single capacitors and filters ..................42B 12.8 Additional measures necessary when paralleling capacitors and filters ............................43

B 13 Audio frequency ripple control systems ............................................................................44

C Rated Values of Switching Devices ............................................................ 45

C 1 Overview............................................................................................................................45

C 2 Rated voltage Ur .................................................................................................................46

C 3 Rated insulation level Ud and U p........................................................................................46

C 4 Rated normal (operating) current Ir ....................................................................................46

C 5 Rated short time withstand current Ik .................................................................................47

C 6 Rated duration of short circuit tk ........................................................................................47

C 7 Rated peak withstand current I p .........................................................................................47

C 8 Rated short-circuit making current Ima...............................................................................47

C 9 Rated short-circuit breaking current Isc ..............................................................................47

C 10 Rated mainly active load-breaking current I1 ....................................................................47C 11 Rated closed-loop breaking current I2a, I2b ........................................................................48

C 12 Rated no-load transformer breaking current I3 ..................................................................48

C 13 Rated cable-charging breaking current I4a .........................................................................48

C 14 Rated line-charging breaking current I4b............................................................................48

C 15 Rated earth fault breaking current I6a.................................................................................48

C 16 Rated cable- and line-charging breaking current under earth fault conditionsI6b .............48

C 17 Cable switching current under earth fault conditions with superimposed load current..... 49

C 18 Rated transfer current Itransfer ..............................................................................................49

C 19 Rated voltage UL (surge arrester with spark gaps).............................................................50

C 20 Rated voltage Ur (metal oxide surge arrester)....................................................................50

C 21 Continuous operating voltage Uc (metal oxide surge arrester) ..........................................50

C 22 Sparkover voltage ..............................................................................................................50

C 23 Residual voltage ures...........................................................................................................50

C 24 Rated discharge current isn .................................................................................................50

Page 7: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 7/116

Contents

© Siemens AG · 11E0 7

D Short-Circuit Protection with HRC Fuses ................................................ 51

D 1 Selection criteria ................................................................................................................51

D 2 HRC fuses for transformers ...............................................................................................51

D 2.1 Fuse rated current IrHH........................................................................................................51D 2.2 Rated voltage UrHH .............................................................................................................52

D 3 HRC fuses for capacitors ...................................................................................................53D 3.1 Fuse rated current IrHH........................................................................................................53D 3.2 Rated voltage UrHH .............................................................................................................53

D 4 HRC fuses for motors ........................................................................................................53D 4.1 Fuse rated current IrHH........................................................................................................53D 4.2 Rated voltage UrHH .............................................................................................................54

D 5 Co-ordination with the switching device ...........................................................................54

D 6 Let-through (cut off) current ..............................................................................................57D 7 Heat losses..........................................................................................................................58

E Selection of Overvoltage Protection Devices............................................. 59

E 1 Selection criteria ................................................................................................................59

E 2 Residual and sparkover voltage (Protection levels)...........................................................59E 2.1 Switching overvoltages......................................................................................................60E 2.2 Lightning overvoltages ......................................................................................................61

E 3 Rated and continuous operating voltage ............................................................................62E 4 Rated discharge current......................................................................................................63

E 5 Energy absorption capacity................................................................................................63

E 6 Switchboards with overhead line connections...................................................................63

F Switchgear Configuration........................................................................... 65

F 1 Principles of configuration.................................................................................................65F 1.1 General...............................................................................................................................65F 1.2 Requirements and complementary characteristics.............................................................65

F 1.3 Procedure ...........................................................................................................................66F 2 Switchgear requirements....................................................................................................67

F 3 Properties to be selected.....................................................................................................68

G Influences and Stress Variables ................................................................. 69

G 1 Network characteristic values ............................................................................................69G 1.1 Line voltage........................................................................................................................69G 1.2 Short-circuit current ...........................................................................................................69G 1.3 Normal current and load flow ............................................................................................69

G 1.4 Neutral earthing..................................................................................................................70G 1.5 Underground / overhead lines ............................................................................................70

Page 8: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 8/116

Contents

8 © Siemens AG · 11E0

G 1.6 Overvoltage protection.......................................................................................................71G 1.7 Power quality (unstable loads)...........................................................................................72

G 2 Line Protection, measurement and metering......................................................................72G 2.1 Short-circuit protection ......................................................................................................72G 2.2 Protection functions ...........................................................................................................72G 2.3 Command times .................................................................................................................73G 2.4 Measurement and metering................................................................................................73G 2.5 Redundancy........................................................................................................................73

G 3 Infeed types........................................................................................................................74

G 4 Operating sites....................................................................................................................75G 4.1 Installation location............................................................................................................75G 4.2 Accessibility.......................................................................................................................75G 4.3 Switchgear room ................................................................................................................76G 4.4 Buildings ............................................................................................................................76G 4.5 Transportation and assembly .............................................................................................77

G 5 Environmental conditions ..................................................................................................77G 5.1 Ambient room conditions...................................................................................................77G 5.2 Altitudes above 1000 m .....................................................................................................78G 5.3 Ambient temperature and humidity ...................................................................................78

G 6 Industry-specific application..............................................................................................79G 6.1 Switching duty and capacity ..............................................................................................79G 6.2 Switching frequency of the loads.......................................................................................79G 6.3 Frequency of switchover between busbars ........................................................................80G 6.4 Availability (faults, redundancy, switchover time)............................................................80

G 6.5 Modifications or extensions...............................................................................................81G 7 Operating procedures.........................................................................................................81G 7.1 Operation............................................................................................................................81G 7.2 Work activities ...................................................................................................................82G 7.3 Inspection and maintenance...............................................................................................83

G 8 Regulations.........................................................................................................................83

H Selecting and Rating Switchgear................................................................84

H 1 Overview (Checklist) .........................................................................................................84

H 2 Primary rated values...........................................................................................................87H 2.1 Rated voltage Ur .................................................................................................................87H 2.2 Rated insulation level.........................................................................................................88H 2.3 Rated short-circuit currents................................................................................................89H 2.4 Rated duration of short-circuit tk ........................................................................................90H 2.5 Rated normal current Ir ......................................................................................................91

H 3 Circuit arrangement............................................................................................................91H 3.1 Single busbars ....................................................................................................................91H 3.2 Double busbars...................................................................................................................92H 3.3 Design of double busbars...................................................................................................92

H 3.4 Operating principle of bus couplings.................................................................................92H 4 Switching Devices .............................................................................................................93

Page 9: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 9/116

Contents

© Siemens AG · 11E0 9

H 5 Design and switchgear panel type......................................................................................94H 5.1 Basic selection criteria .......................................................................................................94H 5.2 Panel and block design.......................................................................................................95H 5.3 Installation conditions, transportation and assembly.........................................................96H 5.4 Additional aspects..............................................................................................................96

H 6 Electrical and mechanical reserves ....................................................................................97

H 7 Insulation medium..............................................................................................................97H 7.1 Comparative aspects ..........................................................................................................97

H 8 Isolating distance................................................................................................................98

H 9 Enclosure............................................................................................................................99H 9.1 Degree of protection...........................................................................................................99H 9.2 Internal arc classification ...................................................................................................99H 9.3 Pressure absorbers and pressure relief ducts....................................................................100

H 10 Compartments ..................................................................................................................100H 10.1 General selection criteria .................................................................................................100H 10.2 Loss of service continuity category .................................................................................101H 10.3 Access control..................................................................................................................102

H 11 Feeder circuit components ...............................................................................................102

H 12 Busbar / metering panel components...............................................................................103

H 13 Secondary Equipment ......................................................................................................104

I Appendix.....................................................................................................105

I 1 Damping relaxation oscillations.......................................................................................105I 2 RC-circuitry for protection of MV equipment.................................................................109

I 3 Overvoltage factors (Definition)......................................................................................110

I 4 Abbreviations, Symbols and Formula Variables .............................................................111

I 5 Diagram Symbols.............................................................................................................112

J Relevant Standards and Regulations....................................................... 113

J 1 Statutory regulations for medium-voltage equipment .....................................................113

J 2 Generic standards for switching devices and switchgear.................................................114J 3 Product standards for switching devices..........................................................................115

J 4 Product standards for switchgear and accessories ...........................................................116

Page 10: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 10/116

Page 11: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 11/116

Selection of the appropriate switching device

© Siemens AG · 11E0 11

A SELECTION OF THE APPROPRIATE DEVICE

A 1 Selection criteria

The effective selection of devices for a particular switching duty is determined by three main re-quirements:a) the operational current switching capability

b) the fault current switching capabilityc) the frequency of switching

The section below deals with the criteria for following devices:

• Circuit breakers • Vacuum contactors • HRC fuses• Vacuum switches • SF6 switch disconnectors

• Hard gas (gas evolving) and airbreak switches and switch disconnectorsThe most important of these is the required switching capability. If more than one device fulfilsthese requirements a) and b), the frequency of switching might be the critical factor. Individualequipments differ in the number of mechanical and electrical operations for which they are de-signed, the length of time between maintenance and the cost and inconvenience of that mainte-nance.

Additional criteria may be:

• the voltage withstand level of the gap;in switchboards where the switches are not withdrawable, devices which ensure a safe isolation

gap are needed. Switch disconnectors fulfil the safety gap requirements, switches, circuit break-ers and contactors do not. They need an additional disconnector or similar device in series. Inswitchboards with withdrawable or truck-mounted equipment this is unimportant, the gap is es-tablished by the act of withdrawal.

• the drive mechanism;for duties such as synchronising and (multiple-) auto-reclose, a drive mechanism with defined,short closing and opening times. Only stored energy systems suffice; springs which have to becharged first are unsuitable.

Circuit breakers can switch on and off (make or break) all values of current within their rated ca- pability, from small inductive or capacitive load currents up to full short circuit currents, and underall the fault conditions like earth fault, phase displacement (out-of-phase switching) etc.

Switches can switch on and off operating currents up to their rated interrupting capability and canclose onto existing short circuits up to their rated fault making current. They have very limited faultcurrent breaking capability only.

Switch disconnectors combine the functions of switches and disconnectors or, put another way,they are switches with the specific safety gap required of disconnectors.

Contactors are load switching devices with limited short circuit making and breaking capacity.They are electrically operated and are used for high switching rates, e.g. for motor control.

Fuses (or, more accurately, the fuse link) provides a single interruption of a short circuit current.Fuses are installed in combination with load switching devices.

Page 12: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 12/116

Selection of the appropriate switching device

12 © Siemens AG · 11E0

A 2 Suitability under normal operating conditions

Switch and switch-disconnector No. Operating duty Circuit- breaker Vacuum SF6 Air-, Hard gas

Vacuumcontactor

1 Transformer

(Star point transformer)

X X X X X

2 Converter transformer X

3 Furnace transformer X X

4 Petersen coil X X X

5 Compensation coil X

6 Motor X X ( X ) X

7 Generator X X ( X )

8 Cable, Ring mains X X X X

9 Overhead lines X X X X

10 Single capacitor X X X ( X ) X11 Paralleling ofcapacitors

X X X

12 Filter circuit X X

13 Ripple control circuit X X X

14 Synchronising X

X = suitable and effective use (X) = limitedly suitable

Table A-1: Switching capability under normal conditions

A 3 Suitability under fault conditions

Using the following three tables, check the fault currents the device must be able to switch.

Switch and switch-disconnector No. Fault duty Circuit- breaker Vacuum SF6 Air-, Hard gas

Vacuumcontactor

1 Closing onto fault X X X X ( 1 )

2 Terminal fault X ( 2 ) ( 2 ) ( 2 ) ( 2 )

3 Auto-reclose X

456

Fault on load side of- Generator- Reactor- Transformer

XXX ( 2 ) ( 2 ) ( 2 ) ( 2 )

7 Locked rotor motor X X ( 2 ) X

8 Double earth fault X ( 2 ) ( 2 ) ( 2 ) ( 2 )

9 Phase opposition X

(1) Without HRC fuse, only limited fault switching capability.(2) Only as switch-fuse combination; current interruption by the fuse.

Table A-2: Switching capability under fault conditions

Page 13: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 13/116

Selection of the appropriate switching device

© Siemens AG · 11E0 13

Switch and switch-disconnector No. Fault duty Circuit- breaker Vacuum SF6 Air-, Hard gas

Vacuumcontactor

10 Unloaded cable, OHLfault on network side

X X X ( 1 ) X

11 Loaded cable, OHLfault on network side

X X X X

12 Unloaded cable, OHLfault on load side

X X X X X

13 Loaded cable, OHLfault on load side

X X X ( 1 ) X

(1) for small currents only

Table A-3: Switching under earth fault conditions

Switch and switch-disconnector No. Fault duty Circuit-

breaker Vacuum SF6 Air-, Hard gas

Vacuum

contactor14 Safe disconnection

(Disconnection underload)

X X

15 Rapid changeover X

16 Transformer withshort-circuited winding

X X ( 1 ) ( 1 ) ( 1 )

(1) Only as switch-fuse combination; current interruption by the fuse.

Table A-4: Other fault conditions

A 4 Switching frequency and endurance

When a range of devices fulfils the electrical requirements, the frequency of switching in connec-tion with the endurance can be an additional selection criterion. The standards distinguish betweenmechanical and electrical endurance, which are also applicable to equipment "mixed"; e.g. a switchcan mechanically correspond to the class M1 and electrically to the class E3.

The following tables show the endurance classes of the switching devices and give a recommenda-

tion about useful use with that.

A 4.1 Circuit-breaker

IEC 62271-100 defines the mechanical endurance by a certain number of operating cycles (classM), the electrical endurance, however, merely with the verbal description “normal” and “extended”endurance.

To the orientation, what “normal” and “extended electrical endurance” means, the grey shaded tableelements indicate the operating cycles which average modern vacuum circuit-breakers can perform.The numbers for short circuit operation (Isc) are derived from the operating sequences of the typetest. As a rule these are minimum numbers; actually, vacuum circuit-breakers of the class E2 with

Page 14: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 14/116

Selection of the appropriate switching device

14 © Siemens AG · 11E0

auto-reclosing capability, which are used in electricity grids with overhead lines, may break thesmaller short-circuit currents, usual there, several hundred times.

Furthermore it is worth mentioning, that almost all modern vacuum circuit-breakers can switch therated normal current with the number of the mechanical operating cycles.

Class Description

M1 2.000 Operations normal mechanical enduranceM

M2 10.000 Operations extended mechanical endurance, limited maintenance

E1

* Ir 2.000 Operations* Isc 6 x Open

4 x Close

normal electrical endurance(circuit-breaker, not falling into class E2)

* Ir 10.000 Operations* Isc 6 x Open

4 x Close

without auto-reclosing duty

E

E2 * Ir 10.000 Operations* Isc 50 x Open

15 x Close

with auto-reclosingduty

extended electrical endurance

without maintenance of interrupting parts

* Derived numerical values to the orientation = > see text.

Table A-5: Classes of circuit-breakers

A 4.2 Switches and switch-disconnectors

IEC 60265-1 specifies classes for so-called general purpose switches. In addition there are „limited purpose“ and „special purpose“ switches1. General purpose switches – as the name suggests – haveto switch different kinds of operating currents: load currents, closed-loop currents, transformermagnetising currents, cable and line charging currents as well as making short-circuit currents.General purpose switches intended for use in isolated neutral systems or in systems earthed by ahigh impedance shall be capable of switching under earth fault conditions. This versatility is re-flected in the relatively comprehensive definition of the classes, which are applicable for

• Vacuum switches

• SF6 switches and switch-disconnectors

• Air and hard-gas switches and switch-disconnectors

For switch-disconnectors the table details apply to the function “switch”.

See also section A 4.4 Three-position switching devices.

1

Limited purpose switches need only cope with a certain range of the performance of a general purpose switch. Special purpose switches are used for selected duties such as switching of single capacitor banks, paralleling of capacitor banks, closed-loop circuits built up by transformers in parallel, or motors (under steady-state and stalled conditions).

Page 15: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 15/116

Selection of the appropriate switching device

© Siemens AG · 11E0 15

Class Operations Descriptions

M1 1000 Mechanical enduranceM

M2 5000 Extended mechanical endurance

E1 10 x I1 10 x I2a 2 x Ima

E2 30 x I1 20 x I2a 3 x Ima

E

E3 100 x I1 20 x I2a 5 x Ima

Additionally for allclasses:

20 x 0,05 ⋅ I1

10 x I4a 10 x 0,2…0,4 ⋅ I4a 10 x I4b

10 x I6a 10 x I6b

I1 Mainly active load-breaking currentI2a Closed-loop breaking currentI4a Cable-charging breaking currentI4b Line-charging breaking currentI6a Earth fault breaking currentI6b Cable- and line-charging breaking

current under earth fault conditions

Ima Short-circuit making current

Table A-6: Classes for switches

A 4.3 Disconnectors and earthing-switches

IEC 62271-102 defines the classes for disconnectors and earthing-switches. Since disconnectorshave no switching capacity2, only classes fort he mechanical endurance are specified.

Class Operations Description

M0 1000 for general duties

M1 2000M

M2 10.000extended mechanical endurance

Table A-7: Classes for disconnectors

The classes for earthing switches specify the short-circuit making capability (earthing in case ofvoltage still being present). E0 designates a normal earthing switch, whereas E1 and E2 correspondto earthing switches with short-circuit making capability; so-called make-proof earthing switches.

Class Operations Description

E0 0 x Ima no short-circuit making capability

E1 2 x Ima for general duties

E

E2 5 x Ima short-circuit making capability

reduced maintenance

Table A-8: Classes for earthing-switches

2

Disconnectors up to 52 kV rated voltage can switch off only “negligible” currents up to 500 mA (for example voltagetransformers), or higher currents only if no significant change in voltage occurs (for example busbar transfer when buscoupler is closed).

Page 16: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 16/116

Selection of the appropriate switching device

16 © Siemens AG · 11E0

A 4.4 Three-position switching devices

Three-position switching devices combine two or three functions within one device• Disconnecting• Earthing and short-circuiting• Load switching• Interrupting short-circuits

For three-position switching devices classes are designated for each individual function, i.e. as ifthere were two or three separate switching devices.

A 5 Aspects of selection for disconnectors

For work on switchboard components, it must always be possible to establish a safe disconnection

gap. For this, a switching device or an arrangement of equal value is essential, also an interlock be-tween this disconnector and the load, power or earthing switch. With combined devices like switch-disconnectors or three-position devices, an additional disconnector is unnecessary and even separateinterlocking may become superfluous.

The average mechanical endurance of disconnectors (truck or withdrawable part) amounts 1000 or2000 operations, corresponding to the classes M0 or M1. This is completely sufficient for most ofthe applications.

The life of the disconnector in double busbar switchboards plays an important role: In somenetworks, for operational reasons, it is necessary to switch frequently from one busbar to the other.Because of the limited life of conventional disconnectors in comparison to the main switching de-

vices, not all switchboards are suitable for this application.

System 1

System 2

A B C

System 1 System 2

DB-switchboards are available in the "classic" arrangement (A), as double circuit breaker systems(B) or as a system with two single busbars (C). For frequent changeover, only designs B and C aresuitable. Here, one switches over with the circuit breakers, the disconnectors are opened only forwork. The classic arrangement A is not suitable because the disconnectors have to be operated foreach change-over. Their design life is rapidly exhausted, the maintenance intervals rapidly short-ened and the efficacy of the switchboard destroyed.

Page 17: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 17/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 17

B SWITCHING DUTIES IN MEDIUM VOLTAGE NETWORKS

B 1 Overview

The table gives an overview whether special measures have to be taken on selection of switchingdevices. Details are described in the chapters listed in the right column.

Switching duty Advice Section

Transformers in distribution

networks

Consider inrush current when selecting HRC fusesfor distribution transformers.Additional selection criteria for switch-fusecombinations.

B 2,D 2 +D 5 - D 7

Unit transformer

with a single • motor

• generator

• furnace

• converter

see • Motor• Generator• Furnace transformer• Converter transformer

B 8B 9B 10B 11

Petersen coil Surge arrester or limiter B 4

Overhead power line

and

cable network

Switches and switch-disconnectors are very limitedin suitability for earth fault location (by selective

switching of circuits): only up to their switchingcapability under earth fault conditions - with orwithout load (see manufacturer data)!

B 5

Cable or overhead line with

short-circuit limiting reactor

Surge arresters at the “short” end of the cable / line B 6

Compensation coil

(shunt reactor)

Protection with RC-circuits; additional surge ar-resters if I < 600 A; depending on the network con-figuration also protection at the busbar.

B 7

Motor • Overvoltage protection if motor starting currentIan < 600 A

• Selection of switching device: with large motorsthe ratio of peak to r.m.s. short-circuit current atthe busbar is possibly > 2.5; hence the ratedshort-circuit making current of the breaker hasto be ≥ the actual peak current!

• Motor with HRC fuse: select the fuse accordingto starting current and time of the motor!

B 8

D 4 +D 5 to D 7

Page 18: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 18/116

Switching duties in medium voltage systems

18 © Siemens AG · 11E0

Switching duty Advice Section

Generator • Overvoltage protection is necessary, if short-circuit current of generator is Ik " < 600 A

• Selection of switching device: with large motorsthe ratio of peak to r.m.s. short-circuit current atthe busbar is possibly > 2,5; hence the ratedshort-circuit making current of the breaker hasto be ≥ the actual peak current!

– Consider the effect of load shedding for the se-lection of the rated voltage

– Consider DC Component for the selection of therated short-circuit breaking current

B 9

Furnace transformer Protection by RC-circuits and surge arresters isindividually matched to the system (in most casesalso at the busbar)

B 10

Converter transformer Surge arresters B 11

Capacitor • Selection of switching device: consider the limitof closing current for breakers with tulip contactand flat contact surface!

– select next higher rated current(additional heating due to harmonic currents)

– match rated voltage to the higher operatingvoltage for capacitor-coil combinations

• HRC fuses: select rated voltage and current 1-2steps higher

B 12

D 3

Filter circuit • Consider operating voltage limits

• Selection of switching device: see capacitors

B 12

Audio frequency

ripple control system

– – – B 13

Page 19: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 19/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 19

B 2 Transformers in distribution networks

This covers all transformers in industrial and power utility networks, with exception of the specialtransformers in section B 3.

Switching: Unloaded transformer Loaded transformerCurrent: Magnetising current 1 to 3 %

of rated currentup to 120 % of rated current

cos φ: less than 0.3 ind. 0.7 to 1.0 ind.

Remarks: Vacuum switches have small chopping currents(less than 5A), Overvoltage factor k ≤ 3.1

– – –

Additional measures: None

B 3 Unit transformer

Transformers in this arrangement normally feed only one, special load. The switching duty is thendetermined by the characteristics of that load. For further clarification see:

• Motor (with transformer, starting transformer) → Section B 8

• Generator → Section B 9

• Furnace transformer → Section B 10

• Rectifier, converter transformer → Section B 11

B 4 Petersen (arc quenching) coil

Petersen coils in earth fault compensated, normally unearthed, networks earth the network at thestarpoint of either a transformer or an earthing transformer. When an earth fault occurs, the coil isswitched in to produce a purely inductive current which should compensate (equal) the capacitiveearth fault current which is flowing into the fault. If the Petersen coil is switched off during thefault, multiple re-ignitions can cause overvoltages. Surge arresters will protect against these.

Switching: without earth fault in network with earth fault in network

Current: approx. 1% of transformer ratedcurrent

up to 300 A

cos φ: less than 0.15 ind. less than 0.15 ind.

Remarks: as unloaded transformer overvoltages due to multiplere-ignition possible

Additional measures: Surge arresters are normally installed

Page 20: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 20/116

Switching duties in medium voltage systems

20 © Siemens AG · 11E0

Overvoltage protection circuit

Arresters at the transformer or neutral earthing transformer terminals in phase-earth connection, or parallel to Petersen coil; if the coil can be switched directly (left figure), the arrester has to be in-stalled there.

Selection of surge arresters

It is necessary that the transformer insulation corresponds to the higher standard value in accor-dance with IEC 60071-1, otherwise the arrester can be selected as described in section E.

Surge arrester orsurge limiter

At the primary terminals of the[neutral earthing] transformer

Parallel toPetersen coil

SiC-Arrester Rated voltage Ur ≥ Umax Ur ≥ 0,8 ⋅ Umax

MO-Arrester Cont. op. voltage Uc ≥ Umax Uc ≥ Umax / √3

UC Continuous operating voltage

Umax Maximum operating voltage of the power system

B 5 Cable and overhead line networks

This refers to unloaded cables and lines. In this case, only the capacitive charging current flows.See section 0 for cable and lines with short-circuit limiting reactor.

Switching: Cable Overhead line

Current: up to 100 A up to 10 Acos φ: capacitive capacitive

Remarks: Vacuum switches are restrike-free

Switches and switch-disconnectors are very limited in suitability for earth faultlocation (by selective switching of circuits): only up to their switching capabil-ity under earth fault conditions - with or without load (see manufacturer data)!

Additional measures: None

Page 21: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 21/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 21

B 6 Cable or line with short-circuit limiting reactor

A short-circuit limiting reactor can mainly be found in cable systems; however, the following rec-ommendations are equally valid for line connections with limiting reactor as well.

If two switchgear installations with different peak and short-time current ratings are connected, areactor must limit the short-circuit current which – in the event of a fault – is fed from the higherrated installation into the lower rated.

On energising the connection between station A and B under no-load condition impermissible over-voltages may occur if the circuit-breaker in station A closes the “long” cable (some hundred metres)while the breaker in station B is open. The very small earth capacitance of the short connection(only a few metres of cable or bar) together with the inductance of the reactor leads to a high-frequency inrush voltage which can reach unduly high amplitudes. This might cause disruptive dis-charges at the reactor terminals or at the open end of the “short” cable or bar connection in stationB. Hence surge arresters or limiters have to reduce the overvoltage to permissible values. In contrastto this, when the breaker in station B closes first, no significant overvoltages occur at the “long” endin station A, as the closing overvoltage at the open circuit-breaker remains small due to the muchhigher earth capacitance of the long cable.

Current: 0 A; only on closing under no-load condition

cos ϕ: – – –

Remarks: The energising of the cable at the “long” end can cause overvoltagesat the “short”, open end.

Additional measures: Surge arrester / limiters

Protective measures

Surge arresters should be installed in the station with the “short” cable or bar connection betweenreactor and circuit-breaker (station B). The arresters can be mounted either at the terminals of the

breaker or at the reactor.

open"short" cableor bar "short" cable

Station A Station BSurge limiters at the circuit-breaker or arresters at the reactor in line-to earth star-connection

Page 22: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 22/116

Switching duties in medium voltage systems

22 © Siemens AG · 11E0

Selection of surge arresters

Surge arresters for installation at …Operating voltage 3 of system up to: circuit-breaker short-circuit limiting reactor

3,6 kV 3EF1 036-0A4,8 kV 3EF1 048-0A

7,2 kV 3EF1 072-0A

12 kV 3EF1 120-0A

15 kV 3EF1 150-0A

Indoor: type 3EF1,same type as at the circuit-breaker.

Outdoor: arresters with equal protectionlevel; selection see chapter E.

B 7 Compensation coils (shunt reactors)

These compensate the capacitive charging current on unloaded networks. Often they are connectedto the tertiary winding of a transformer, when compensation of a high voltage (≥ 110 kV) networkis required. Direct compensation of medium voltage networks is more seldom. Compensation coilsare switched daily. The switching devices reach large numbers of operations. The high rate of riseof the recovery voltage makes this a very difficult duty for conventional units. Vacuum switchesand breakers master these conditions and simultaneously require very little maintenance for the highnumber of cycles.

Current: up to 2000 A

cos φ: 0.15 ind.

Remarks:During switch-off, multiple re-ignitions can excite resonant oscillations in thecoil; with currents less than 600 A high stresses can result from virtual currentchopping.

Additional measures: RC-circuits are generally required, and additionally surge arresters if thecoil current ≤ 600 A. The protection must be individually matched to thenetwork.

Overvoltage protection circuit

Compensation coils are always equipped with an RC-circuit. This prevents resonant harmonics inthe coil during switch-off. See also chapter I 2 for information.

When the coil current is ≤ 600 A, then surge arresters are also fitted to prevent overvoltages arisingfrom multiple re-ignitions.

3 For other voltages and those above 24 kV any surge arrester can be selected;selection criteria are described in section E.

Page 23: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 23/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 23

I

(x)

Coil current I Protection

I ≤ 600 A RC-circuits+ arresters

I > 600 A RC- circuits

(x) Protection circuits on the busbar side in case of certainnetwork conditions only.

Selection of protection devices

The protection devices must always be individually matched to the network characteristics. There-fore, a network calculation is always necessary.

B 8 Motors

This area of application covers many types of machines, in various connection modes:

• Asynchronous motor: cage rotor, slipring rotor

• Synchronous motor (with asynchronous start)

• Motor with unit transformer• Motor with starting transformer

• Motor with starting converter

• Motor with individual power factor compensation

• Variable speed drives (converter motors) see B 11, Converter transformers

Duty: Motor during startingMachine with locked rotor

Normal operation No-load … on-load

Current: Cage rotor 5 … 7 ⋅ IrMot Slip ring rotor 1 … 2 ⋅ IrMot

0,1 … 1,2 ⋅ IrMot

cos φ: 0.2 to 0.3 ind. 0.9 to 0.3 ind.

Remarks: Switching of starting currents Ian ≤ 600 A 4 can cause overvoltages as result of multi-

ple re-ignition and virtual current chopping

Switching of normal operatingcurrents causes no impermissibleovervoltage surges

Additional measures: Overvoltage protection for motors with Ian ≤ 600 A 4, 5

4 For motor-transformer combinations, the transformer primary current is the criterion5 Motors with individual power factor correction do not need a special circuit (→ B 8.5)

Page 24: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 24/116

Switching duties in medium voltage systems

24 © Siemens AG · 11E0

Overvoltage protection circuits

Overvoltage limiters 3EF are installed, when the starting current is ≤ 600 A. In motor-transformercombinations, the current through the switch is the criterion.

The length of cable connections to the motor, or other parameters, have no influence in this case.

Exception: Motors with individual power factor correction need no protection circuit, if

• the capacitors are permanently connected to the motor

• the compensation rating (QC) is at least 1/5 of the motor's demand (SMot), normallyQC = (1/3) ⋅ SMot

The compensation capacitance reduces the frequency of the transient recovery voltage for the first pole to clear to less than the limit for multiple re-ignition. Thus no overvoltages occur either. Thisgives the option to use individual compensation as an alternative to overvoltage limiters.

The following illustrations show installation points for limiters or surge arresters in various ar-rangements with motors. Due to the low protection level the surge limiters can be installed at the

breaker – against the general rule that they must be installed at the object to be protected (motor).

B 8.1 Direct connected motor (direct on line)

M

Ian ≤ 600 A

Overvoltage limiters phase to earth star at themain switch

Motorvoltage upto:

3,6 kV 4,8 kV 7,2 kV 12 kV 6 15 kV

Surge limitertypes

3EF1 036-0A 3EF1 048-0A 3EF1 072-0A 3EF3 120-1 3EF1 150-0A

Further selection criteria are described in section E and the surge arrester catalogues.

6 For direct connected motors with 12 kV surge limiters at the breaker the type underlined must be used to ensure the protection level required.

Page 25: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 25/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 25

B 8.2 Motor with transformer (unit)

The protective effect is the same in both cases.

Arrangement 1

Overvoltage limiter phaseto earth star at the mainswitch

MIan < 600 A

Arrangement 2

Overvoltage limiter or ar-rester in phase to earth starat the transformer

MIan < 600 A

Arrangement 2: At the transformer, surge arresters can be fitted instead of 3EF limiters, if thetransformer insulation has the higher insulation level specified in IEC 60071.For selection of arresters see section E.

Surge arresters for installation at …transformer

Motor or transformerrated voltage up to: 7 circuit-breaker

indoor limiters outdoor limiters

3,6 kV 3EF1 036-0A 3EF1 036-0

4,8 kV 3EF1 048-0A 3EF1 048-0

7,2 kV 3EF1 072-0A 3EF1 072-0

12 kV 3EF1 120-0A 3EF1 120-0A

15 kV 3EF1 150-0A 3EF1 150-0A

Arresters withequal protectionlevel; selectionsee chapter E.

7 For other voltages on request

Page 26: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 26/116

Switching duties in medium voltage systems

26 © Siemens AG · 11E0

B 8.3 Motor with starting transformer

MMain switch

Transfer switch

3EF

(1)

3EF

(2)

3EF

(3)

Star

point

switch

Starting current Connection of overvoltage limiters

Ian ≤ 600 A either at the main switch (1) or transformer (2);and at transformer star point (3)

Ian > 600 A at transformer star point (3)

The quality of the insulation of starting transformers frequently does not meet the value standard-ised in IEC 60071. Therefore, only limiters 3EF should be at transformers (2), because they haveespecially good voltage protection properties. Arresters are not particularly suitable for this duty.

Every surge limiter, also those at the star point (3), must be selected in accordance with the trans-former rated voltage.

Surge arresters for installation at …circuit-breaker transformer

Transformer ratedvoltage up to: 8

indoor limiters outdoor limiters

3,6 kV 3EF1 036-0A 3EF1 036-0A

4,8 kV 3EF1 048-0A 3EF1 048-0A

7,2 kV 3EF1 072-0A 3EF1 072-0A

12 kV 3EF3 120-1 9

15 kV 3EF1 150-0A

Arresters withequal protectionlevel; selectionsee chapter E.

8

For other voltages on request9 For 12 kV surge limiters at the breaker the type underlined must be usedto ensure the protection level required.

Page 27: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 27/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 27

B 8.4 Motors with starting converter

~

~M

S1, S3 Converter circuit-breaker S2 Motor circuit-breaker

S1

S2

S3

1a 1b

2

3a 3b

Surge limiters in line to earth

star connection at three con-nection points 1a or 1b, 2 and3a or 3b, if:

• Circuit-breakers S1 to S3are not interlocked withthe converter, and

• The motor starting currentis ≤ 600 A.

Usually only large motors are started by converters. In the case the motor must be switched off dur-ing start-up or with locked rotor, the converter controls the current and switches it off under normalcircumstances. Thus starting currents are not switched off by the circuit-breaker, which would re-quire surge protection at starting currents below 600 A.

• No surge protection measures are required if the converter control and corresponding interlock-ing ensure that the circuit-breakers (1) to (3) do not switch off starting currents ≤ 600 A.

• If the circuit-breakers are not included in the control of the converter and the motor starting cur-

rent is ≤ 600 A, surge protection must be installed for the converter transformers and the motor.The surge limiters for the motor must be mounted at the circuit-breaker S2 (connection point 2).For the converter transformers they may be mounted at the circuit-breaker (connection points 1aand 3a) or alternatively at the transformer terminals (connection points 1b and 3b). Surge limitersaccording to chapter B 8.1 are applied to the motor; for the converter transformers refer to chap-ter B 11.2 and B 11.4.

B 8.5 Motors with their own p.f. improvement

No overvoltage protection is necessary. Thus individual compensation can be used as an alternativemethod of providing protection.

M S

QC

Motor

Prerequisite: Motor C S Q ⋅≥5

1

normally Motor C S Q ⋅=

3

1

Page 28: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 28/116

Switching duties in medium voltage systems

28 © Siemens AG · 11E0

B 9 Generators

Current: short-circuit current up to 1,2 ⋅ IrG

cos φ: 0.15 lag. lag. ←→ lead.

Remarks: When short-circuit currents Ik " ≤ 600 A 10) 11)

are switched off, overvoltages due to multiplere-ignitions and virtual current chopping mayoccur

Switching off under load orno-load conditions causes no impermissible overvoltages

Additional measures: Overvoltage protection is required due to the breaker if the short circuit cur-rent is ≤ 600 A 10) 11). However, in many cases protection is basically installedto ensure safety of operation since overvoltages may be transferred from else-where in the network.

When selecting the breaker, special attention must be paid to the rated voltage and short-circuit

breaking and making current → see section B 9.1.

B 9.1 Selection of the circuit-breaker

Special attention has to be paid to the rated voltage, rated short-circuit breaking current and rated

short-circuit making current when selecting a breaker for generators!

Rated voltageThe event of load shedding has to be considered when selecting the rated voltage. The voltage onthe generator side of the breaker rises after load shedding. A standard value of 20 % rise is usuallyassumed. A higher value may be assumed if the simultaneous occurrence of several faults should beconsidered (e.g. load rejection and defective voltage regulator). The requirements for the circuit-

breaker should be co-ordinated with the client.

Rated short-circuit breaking current and rated short-circuit making current

The peak value (making current) and the DC component of the current during short-circuit close tothe generator are higher than during short-circuit elsewhere in the system (remote from generator).

The short-circuit is close to the generator if the ratio of initial to continuous symmetrical short-circuit current is Ik "/Ik > 2. The fault location, system and generator data as well as the operatingcondition (excitation) determine the short-circuit current. The high DC component is typical forclose to generator short-circuit. In some cases the AC component may decrease more rapidly thanthe DC component. This leads to delayed current zeros (DC component > 100 %). However thecircuit-breaker needs current zeros for clearing.

Rated short-circuit making current The circuit-breaker must be capable of closing on a short-circuit: the rated short-circuit making cur-rent must be equal to or higher than the value which occurs in service.

10 In case of fault at the busbar or breaker terminals11 The breaker current is decisive in motor-transformer arrangements

Page 29: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 29/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 29

Rated short-circuit breaking current The real breaking current depends on the time interval between initiation of the short-circuit and theopening of the breaker because of the current decays during that time (inherent operating and trip-

ping times of protection relays and opening time of c.b.). The values of the breaking current and theDC component must be calculated if not stated by the customer.

If either one of the values, short-circuit breaking current or DC component, exceeds the rated valuesaccording to Catalogue HG 11, individual selection is required. The breaking capacity of most ofthe circuit-breakers is higher than the ratings according to IEC listed in the Catalogue HG 11.Which type is suitable has to be determined for each individual application.

B 9.2 Protective measures against overvoltage

Switching of generators is similar to motor switching with respect to the transients. The decisivecriterion for surge protection on account of the breaker is the short-circuit current of the generatorduring fault at the busbar or breaker terminals. If it is ≤ 600 A, surge limiters or arresters are used.However, surge protection is often universally fitted because generators frequently feed into over-head line systems or connect to parts of the plant which are installed outdoors (e.g. unit transform-ers). Surge arresters then protect against overvoltages which may be carried over from the network.

Generator installations can be divided into the following groups for planning purposes:

Surge protectionGenerator short-circuit current

Infeeding into a cable system Infeeding into an overhead line system

Ik " ≤ 600 A limiters / arresters→ ref. to B 9.3 limiters / (arresters)→ ref. to B 9.4

Ik " > 600 A not required, however protectionis usual → ref. to B 9.5

arresters and surge capacitors→ ref. to B 9.6

Page 30: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 30/116

Switching duties in medium voltage systems

30 © Siemens AG · 11E0

B 9.3 Generators with Ik" 600 A feeding into a cable system

a) Direct connected generator

cableI " ≤ 600 Ak

Surge limiters / arresters at the

breaker terminals in line-to earth

star-connection

G

Generator volt-age up to: 12

3,6 kV 4,8 kV 7,2 kV 12 kV 15 kV

Limiters forinstallationat breaker:

3EF2 036-0A3EF3 036-03EH5 036-…

3EF2 048-0A3EF3 048-03EH5 048-…

3EF2 072-0A3EF3 072-03EH5 072-…

3EF2 120-0A3EF3 120-03EH5 120-…

3EF2 150-0A

b) Generator-transformer unit

The effect of protection is equal in both arrangements.

Arrangement 1

cableI " ≤ 600 Ak

Surge arresters / limiters at the

breaker terminals in line-to-earth

star-connection

G

Arrangement 2

cable I " ≤ 600 Ak

Surge arresters orlimiters at the transformer terminals in line-to-earthstar-connection

G

Surge arresters instead of limiters can be used if the insulation level of the transformer complieswith the higher value of the standard insulation levels according to IEC 60071-1.

12 Maximum value, including voltage rise after load shedding

Page 31: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 31/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 31

Surge limiters for installation at …Breaker transformer

Transformervoltageup to: 13, 14 indoor limiters outdoor limiters

3,6 kV 3EF1 036-0A 3EF1 036-0A

4,8 kV 3EF1 048-0A 3EF1 048-0A

7,2 kV 3EF1 072-0A 3EF1 072-0A

12 kV 3EF3 120-1 15 3EF1 120-0A

15 kV 3EF1 150-0A 3EF1 150-0A

Arresters withequal protectionlevel; selectionsee chapter E

The selection of other limiters or surge arrester is described in section E.

B 9.4 Generators with connection to an overhead line system,

Ik" 600 A

The same protection methods as listed under section B 9.3 apply to this group provided the light-

ning protection is additionally installed at the end of the overhead line.

Lightning protection

at the end of the line

overhead line

to the generator,

arrangements as

under item B 9.3

13 For different voltages on request14

Maximum value, including voltage rise after load shedding15 For 12 kV surge limiters at the breaker the type underlined must be usedto ensure the protection level required

Page 32: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 32/116

Switching duties in medium voltage systems

32 © Siemens AG · 11E0

B 9.5 Generators with connection to a cable or an overhead line system,

Ik" > 600 A

Independent of the circuit-breaker type installed, surge arresters are standard for generators of largesize. They protect against any surges transmitted from the system, e.g. earth fault overvoltages.Special machine arresters are used which have a low protection level and a large energy absorptioncapacity. They are attached directly to the generator terminals.

a) Direct connected generator

Machine arresters inline-to-earth connection

G

b) Generator-transformer unit

Machine arresters in

line-to-earth star connection

G

Devices: Surge arrestersType: 3EE2

Selection: The selection of the data of the type 3EE2 is described in section E.

Consider the maximum voltage at the generator or transformer terminalsincluding the voltage rise after load shedding.

For further detail see also catalogue and data sheet of the surge arresters.

Page 33: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 33/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 33

B 9.6 Generators with connection to the HV grid,

Ik" > 600 A

This almost only concerns generators of large size, which feed into high voltage systems ≥ 110 kV.The protective measures must be planned individually; they are independent of the breaker.

G

Protective

capacitors

Machine

transformer

Station services

transformer

High voltage

system ≥ 110 kV

Generator

circuit-breaker

Machine

arrester

~

B 10 Furnace transformers

The following duties are included in this field:

• Arc furnaces, reduction furnaces, induction furnaces

• Exception: medium frequency furnaces are not included → see converter transformers.

Switching duty: Arc furnace Reduction furnace,

induction furnaceCurrent: 0.01 up to 2.0 x

rated transformer current0.01 up to 2.0 xrated transformer current

cos φ 0.2 ←→ 0.9 lag. 0.5 ←→ 0.8 lag.

Remarks: During opening operations, multiple re-ignitions may cause resonant oscil-lations in the transformer; at currents ≤ 600 A high overvoltages due tovirtual current chopping may occur as well.Consider the insulation co-ordination; see section B 10.1

Additional measures: RC-circuitry and surge arresters at the transformer and the busbar.

Circuit-breakers for furnace transformers have to meet very high electrical and mechanical require-ments partly under unfavourable operating conditions such as high temperature environments or

pollution from electrically conductive dust. The currents to be switched are between almost zeroand two times the rated current of the furnace transformer; they may be unbalanced and distorted.The switching frequency may be up to 100 cycles per day and in exceptional cases it may be evenhigher.

Page 34: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 34/116

Switching duties in medium voltage systems

34 © Siemens AG · 11E0

B 10.1 Insulation co-ordination for operating voltages above 36 kV

Under certain conditions 36 kV vacuum circuit-breakers can also be used with higher operatingvoltages up to 40.5 kV (mainly in networks with effectively earthed neutral). Frequently a maxi-mum voltage of 38.5 kV is used which corresponds to installations with 35 kV, plus 10% tolerance.

Insulation co-ordination: the insulation level of 36 kV circuit-breakers can be rated to maximumvalues 185 kV lightning impulse withstand voltage (BIL) and 85 kV short-duration power-frequency withstand voltage (the standard insulation relating to the upper values according to IEC is170 kV / 70 kV). All other equipment, including protective components such as RC-circuits andsurge arresters, shall be correspondingly dimensioned; the complete switchgear installation mustfulfil these insulation values.

B 10.2 Protective measures against overvoltage

Furnace transformers are generally equipped with RC-circuitry and surge arresters. RC elements prevent resonant oscillations in the transformer in that they form a high pass filter to earth for tran-sient high-frequency currents caused by multiple re-ignitions. Arresters limit the overvoltagescaused by virtual current chopping, which can occur on switching off currents up to 600 A. Currentsin this range are possible even if the rated operating current of the transformer is far above 600 A,as the actual values to be switched during operation lie between the magnetising current (no-load)of the furnace and twice the rated value (electrode short circuit). Depending on the method of neu-tral point earthing 3 surge arresters in phase-earth connection are used or additionally between the

phases (6 arrester connection).

It depends on the network configuration whether the busbar needs surge protection as well. Installa-tions with a low earth capacitance of the inferring system require power capacitors at the busbarwith a damping resistor (as shown in the figure below) or RC-circuitry similar to that on the trans-former. Under certain conditions surge arresters must be additionally fitted to busbar: they limit –together with the arresters at the transformer – the overvoltages across the contact gap.

Furnace transformer

Arc furnace

R

CC-R circuitry

at the busbar

The protection devices have to be matched individually to each system configuration by means of asystem study. This optimises the efficiency of protection and is inevitably necessary to protect thecomponents themselves. The arc furnace causes harmonics which in turn drive harmonic currentthrough the capacitors. The latter plus the damping resistors must be dimensioned for the resultingthermal load. Furthermore the capacitance must be matched to the inductance of the inferring net-work in order to avoid resonances, which stress the equipment by voltage rise and reactive current.

See also chapter I 2 for information.

Page 35: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 35/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 35

B 11 Converter transformers

This heading comprises transformers with:

• rectifiers

• converter-fed drives

• voltage / frequency converters, for example, medium frequency furnaces

• Static compensators (static VAR)

Duty: unloaded loaded

Current: magnetising current0.5 - 3 % rating current

up to rated current

cos φ: < 0.3 ind. lag. ←→ lead.

Note: Vacuum circuit-breakers have

small chopping current (< 5 A),overvoltage factor k ≤ 3.1

when currents ≤ 600 A are switched off,

overvoltages due to multiple re-ignitionsand virtual current chopping may occur

Additional measures: Surge arresters / limiters

B 11.1 Protective measures

No protection is required if converter transformers are switched off under no-load conditions. How-ever, if the transformer is switched off within a load range up to 600 A, unduly high overvoltagescan occur and protection becomes necessary. Surge arresters or limiters will prevent this. This also

applies to plants in which the rated transformer current is higher than 600 A, since depending on theload, breaking operations in the critical range may also occur. Experience has revealed that in con-verter installations the line-to-line insulation must also be protected against overvoltage whereasnormally the line-to-earth insulation is critical. 3EF surge limiters in line-to-earth star-connectionalso reduce the line-to-line switching surges to permissible values. For operating voltages of up to24 kV, if the transformer is insulated in accordance with the higher voltage levels of IEC 60071.For higher operating voltages, surge arresters must be individually rated according to the systemvoltage star point treatment and insulation level.

B 11.2 Systems up to 15 kV operating voltage

Surge limiters in line-to-earth star connectioneither at the breaker (1) or the transformer (2)

~

u, f

(1) Only possible if transformer insulation complies with upper insulation levels accordingto IEC 60071-1.

(2) If the insulation level is of the lower grade, the limiters must be installed at the transformer.

Page 36: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 36/116

Switching duties in medium voltage systems

36 © Siemens AG · 11E0

B 11.3 Systems above 15 kV operating voltage

Surge limiters / arresters at thetransformer in star or delta connection

~

U, f

B 11.4 Selection of surge limiters and arresters

Surge limiters for installation at…transformer

Transformer ratedvoltage up to: 16 breaker

indoor limiter outdoor limiter

3,6 kV 3EF1 036-0A 3EF1 036-0A

4,8 kV 3EF1 048-0A 3EF1 048-0A

7,2 kV 3EF1 072-0A 3EF1 072-0A12 kV 3EF1 120-0A 3EF1 120-0A

15 kV 3EF1 150-0A 3EF1 150-0A

> 15 kV For selection see section E.

Arresters with

equal protectionlevel; selectionsee chapter E

16 For other voltages on request

Page 37: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 37/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 37

B 12 Capacitor banks and filter circuits

This switching duty covers power capacitor banks and filter circuits. Capacitor banks correct the power factor. Filter circuits prevent excessive harmonic oscillations of the system voltage, but alsocompensate the power factor.

Capacitor banks are often equipped with reactors for limitation of the inrush current. These reactor-capacitor units then behave similarly to filter circuits, depending on the values of reactor and ca-

pacitor. This application field is divided into three groups:

• Capacitor banks

• Reactor-capacitor units

• Filter circuits

B 12.1 Capacitor banks (without reactor)

Duty: Single capacitor bank and paralleling of capacitors

Current: up to 1.4 x capacitor current

cos φ: leading

Remarks: When paralleling, high inrush currents (Ie) with high rate of rise may occur.The permissible peak value depends on the geometry of the breaker contactand must not exceed following values:- with flat contact pieces (vacuum circuit-breaker and contactor) Î = 10 kA- with tulip contact pieces (SF6-, minimum oil, compressed air) Î = 5 kA

Additional measures

Single capacitor bank : none

Paralleling of capacitors: → Please follow section B 12.4

B 12.2 Reactor-capacitor combination

Duty: Single capacitor bank Paralleling

Current: up to rated capacitor current

cos φ: leading

Remarks: After the opening operation the voltage on the load side is higher than the sys-tem voltage. The rated voltage of the breaker must not be exceeded by thiseffect.

When paralleling, high inrush currents (Ie) with high rate of rise may occur,depending on the reactor ratings.

Page 38: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 38/116

Switching duties in medium voltage systems

38 © Siemens AG · 11E0

Additional measures: If the voltage at the breaker exceeds the rated value, either a breaker of ahigher rated voltage level or 2 series-connected breakers (only at 36 kV)have to be used → ref. to B 12.5

When paralleling capacitors 17, please follow section B 12.4

B 12.3 Filter circuits

Duty: Single filter circuit Paralleling

Current: up to rated current of filter

cos φ: leading

Remarks: After the opening operation the voltage on the load side is higher than the

system voltage. The rated voltage of the breaker must not be exceeded bythis effect.

Additional measures: If the voltage at the breaker exceeds the rated value, either a breaker of ahigher rated voltage level or 2 series-connected breakers (only at 36 kV)have to be used → ref. to B 12.5

B 12.4 Permissible inrush current

The permissible inrush current depends on both the circuit-breaker and the capacitor.

B 12.4 a Capacitor

Independent of the circuit-breaker, the peak value of the inrush current may not exceed 100 timesthe rated normal current of the capacitor, in order to limit the effect of the electrodynamic forces.However, as this factor is a general rule only, it must be verified in each case with the individualdata of the capacitors.

Discharge devicesCapacitors are normally equipped with discharge voltage transformers or resistors. If re-closingcycles may occur in normal service, the discharge time constant must be chosen short enough thatthe capacitor is almost completely discharged before re-energising. Otherwise the inrush current canincrease if the polarity of the system voltage is in opposition to the residual charge.

B 12.4 b Circuit-breaker

In order to avoid inadmissible stress and wear of the contact pieces, permissible limits of the inrushcurrent must be observed. Usually the following inrush currents are permissible for circuit-breakerswithout reservations:

17 When closing on a single capacitor bank the inrush current usually remains below 10 kA due to the inductance ofthe infeeding system

Page 39: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 39/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 39

• Îe ≤ 10 kA for flat contact pieces

• Îe ≤ 5 kA for tulip contact pieces

The permissible limit has to be checked with the circuit-breaker manufacturer in individual case. Ifthe inrush current exceeds the general limit, it must be investigated whether the magnitude and thedecay time constant τ of the inrush current still lie in the permissible region.

0

2

4

6

8

10

0 5 10 15 20 25 30 35 40

Inrush current (peak value) [ kA ]

T i m e c o n s t a n t [ m s ]

Permissiblerange

Paralleling ofcapacitor banks

Figure: Permissible limit of the inrush current for vacuum circuit-breakers

B 12.4 c Measures to limit the inrush current

There are two possible ways to move an operation point out of the critical region:

• limitation of the inrush current ≤ 10 kA by means of a reactor

• reduction of the time constant by means of a resistor-inductor unit in parallel with the reactor.However this measure is only convenient for existing reactor-capacitor units.

Reactor and parallel-damping devices are individually planned. If a reactor is used to reduce theinrush current, this reactor-capacitor unit now behaves similarly to a filter circuit. Hence, the per-missible voltage stress for the breaker must be checked. → see following section B 12.5.

B 12.5 Permissible voltage at the circuit-breaker

When filter circuits or reactor-capacitor units are switched off the recovery voltage across the breaker is higher than when other loads are switched. The reasons for this are on the one hand the properties of the combination of reactor + capacitor and on the other hand the fact that these filtersare used in systems with distorted voltage due to harmonic oscillations.

Even if the power-frequency system voltage is below the rated breaker voltage, the actual value(including harmonics) can exceed the rated values of the breaker: The instantaneous voltage on theload side of the breaker after switching off is higher than in the closed state because the capacitorvoltage is present there now (→ see B 12.6).

Page 40: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 40/116

Switching duties in medium voltage systems

40 © Siemens AG · 11E0

The system voltage may additionally drop after switching off the filter if the system is still induc-tively loaded, because of the loss of the capacitance when, for example, the breaker was tripped dueto a fault or unintentionally. Harmonic voltages are superimposed on the power-frequency voltage,so that the addition of all the unfavourable effects leads to a very high voltage stress across the

breaker. Consequently it must be checked thoroughly whether the stress is within the permissible

range.If the capacitor voltage exceeds the rated breaker voltage, a breaker of the next higher rated voltagelevel must be used; e.g. a 24 kV breaker instead of a 17.5 kV breaker. If the value exceeds 36 kV on36 kV breakers, two breakers must be connected in series.

The following pages illustrate:

• the calculation of the voltages at filter circuits and capacitor-reactor banks;

• the measures necessary when switching single capacitors and filters;

• the measures necessary when paralleling capacitors and filters

Page 41: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 41/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 41

B 12.6 Calculation of the voltages at filter circuits

and capacitor-reactor banks

IF

UL

UC

UF

U N

U L

U F

U C

U

C

ULIF

IF

U N = Voltage of networkUF = Voltage at filterUL = Voltage across reactorUC = Voltage at capacitorIF = Filter current

Filters frequency: C L f F ⋅⋅⋅= π 2

1

Filter- / system frequency ratio ν = f F / f N ν = Harmonic number (ordinal number)

Filter and system voltage are equal when circuit is closed (UF = U N). Since the capacitor remainscharged, the higher capacitor voltage appears at the breaker: since UL = 0, therefore UF0+ = UC0- atthis instant.

After the opening operation the filter voltage is equal to the ca- pacitor voltage which is calculated with the harmonic number ν: 12

2

00 −⋅== −+ν

ν

N C F U U U

Example: for ν = 5, filter frequency 250 Hz: 042,115

52

2

00 ⋅=−

⋅== −+ N N C F U U U U

The capacitor voltage with a filter for the 5th harmonic is 4.2% higher than the systemvoltage.

Page 42: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 42/116

Switching duties in medium voltage systems

42 © Siemens AG · 11E0

B 12.7 Additional measures necessary when switching

single capacitors and filters

Ur U N

no

Single filter circuit

Capacitor voltageUc < Ur

Single capacitor bank

reactor-capacitor unit without reactor

yes

noadditional measures

A circuit-breaker of the next higher

rated voltage level has to be used

Up to Ur = 24 kV:

2 series-connected breakers have to be used.If Ur = 36 kV:

UC

U NUC

Up to operating voltage

UN < Ur

without additional measures

Ur

Calculation of the capacitor voltage:

12

2

0 −⋅=−ν

ν

N C U U

ν = harmonic number of filter (f F/f N) U NU

C

Ur

Page 43: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 43/116

Switching duties in medium voltage systems

© Siemens AG · 11E0 43

B 12.8 Additional measures necessary when paralleling capacitors and filters

Capacitor voltage

UC < Ur

Damping timeconstant

permissible?

Ur U N

no

Filter circuits Capacitor banks

yes

noadditional measures

A circuit-breaker of the next higher voltage level has to be used

2 series-connected breakershave to be used

If Ur = 36 kV:

U C

Ur U N U C

yes

noadditional measures

no

Up to Ur = 24 kV:

The inrush current is limited by means of a reactor to 10 kA; or the time constant is reduced by a parallel-connected damping device

Inrush current(peak value)

Ie < 10 kA

Ie > 10 kA Up to operating voltageUN < Ur

without additional measures

Calculation of the capacitor voltage:

12

2

0 −⋅=−ν

ν

N C U U

ν = harmonic number of filter (f F/f N) U N UC

Ur

Page 44: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 44/116

Switching duties in medium voltage systems

44 © Siemens AG · 11E0

B 13 Audio frequency ripple control systems

AF ripple control systems feed audio-frequency impulses into distribution systems. The audio-frequency varies from 160 Hz up to 1.600 Hz. Series injection is usual for the lower frequencies, forthe upper range only parallel injection is used. In both cases the circuit-breaker switches a capaci-

tive current, consisting of a power-frequency proportion on which the audio-frequency proportion issuper-imposed. Vacuum circuit breakers are restrike-free and thus they are well suited for thisswitching duty.

Current: up to 20 A

cos φ: leading

Remarks: An audio-frequency current (160 Hz up to 1.6 kHz) is superimposed on the power-frequency control (50/60 Hz).

Air and hard gas (gas evolving) switches are not suitable for this switching

duty.

Additional measures: None

Page 45: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 45/116

Rated values of switching devices

© Siemens AG · 11E0 45

C RATED VALUES OF SWITCHING DEVICES

C 1 Overview

The following table lists the most important values of the primary circuit, in accordance with whicha device has to be selected. The symbols are those used in the corresponding IEC standards.

Value

„Rated - …“

Symbol Circuit- breaker

Switch (dis-connector)

Contactor 1) HRCfuse

Surgearrester

Voltage Ur x x Ue x UL/Uc/Ur

Insulation level- lightning impulse withst. volt.- power-frequency withst. volt.

U p Ud

xx

xx

xx

Ures/uai

Frequency f r x x x

Current Ir x x 2) Ie 2) xShort-time withstand current Ik x x x

Duration of short-circuit tk x x xPeak withstand current I p x 3) discharge

current Is

Short-circuit making current Ima x x Im Short-circuit breaking current Isc x Ic

Mainly active load-breakingcurrent

I1 x

Closed-loop breaking current I2a, I2b x

No-load transformer breakingcurrent

I3 x

Cable-charging breaking cur. I4a x

Line-charging breaking current I4b x

Earth fault breaking current I6a xCable- and line-charging break-ing current under earth faultconditions

I6b x

Cable- and line-charging break-ing current under earth fault

conditions with superimposedload current

*

Transfer current Itransfer x 4)

x Selection values foreseen by the standards.* Recommended selection value, not required by the standards.

1) The symbols used for high voltage contactors are sometimes different, since theywere – historically – constructed in accordance with the low voltage standards.

2) In switch and fuse combinations the rated current is limited to the rated current of the fuse.3) Not defined in the standard; see note (1).4) Applies only to switch and fuse combinations.

Page 46: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 46/116

Rated values of switching devices

46 © Siemens AG · 11E0

C 2 Rated voltage Ur is the upper limit of the highest voltage of systems for which the device is intended and designed. Itmust be at least equal to the highest expected operational voltage at the installed location, consider-ing effects such as:

• short duration voltage rises• harmonics

• load shedding

• increased levels at capacitors and filters

C 3 Rated insulation level Ud and Up

is the dielectric strength (lightning impulse and power-frequency withstand) phase to earth, between phases and across open switch gaps or isolating distances. The insulation level comprises the

• Rated lightning impulse withstand voltage U p (1.2/50 µs)

• Rated power-frequency withstand voltage Ud (50 Hz / 1 min)

Instead of rated lightning impulse withstand voltage U p the term BIL (basic impulse level) is alsooften used.

For medium voltage the standards do not specify a switching impulse voltage withstand but thisvalue is of importance for the selection of overvoltage protection devices for transient switchingsurges. This switching impulse level (SIL) is set at

0.8 ⋅ BIL, because the much longer transient tail time of the switching impulse requires a lower di-electric strength than the lightning impulse.

The insulation level is related to the rated voltage. If it is not adequate for a particular duty, becauseexternal or internal overvoltage sources have to be considered, the fitting of surge arresters is rec-ommended.

C 4 Rated normal (operating) current Ir is the (r.m.s.) current which the main current path of the device can carry continuously under de-

fined conditions.The value normally applies to equipment in free air. The actual permissible value depends, there-fore, on the temperature at the installed location. The permissible value may be reduced by

• installation within a housing or cubicle (restricted heat dispersion)

• the current carrying capacity of connected equipment (cables, fuses)

• harmonics (total current ∑+≤ 2250 OS Hzges

I I I )

With HRC fuses, the rated current is just an "ordering size". Because of the particular character ofthis device, the actual value to be chosen depends on various other factors; see section D.

Page 47: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 47/116

Rated values of switching devices

© Siemens AG · 11E0 47

C 5 Rated short time withstand current Ik is the effective (r.m.s.) value of the short circuit current which the device, when closed, can carryfor a specified time under defined conditions.

C 6 Rated duration of short circuit tk is the time for which the device, when closed, can carry a current equal to its rated short time with-stand current. The standard value is 1 second. If a longer time is necessary, the recommended alter-native is 3 seconds. By agreement between manufacturer and user, a value < 1 s may be chosen.

C 7 Rated peak withstand current Ip is the peak current of the first major loop of the rated short time withstand current which the device

can carry, when closed, under defined conditions. For devices which have full fault closing capabil-ity ( rated short-circuit making current) this value is inherent.

In switch and fuse combinations, the magnitude of the let through current of the largest fuse forwhich the combination is designed, is adequate.

C 8 Rated short-circuit making current Ima is the current which the device can safely handle when making onto a short circuit at its terminals.The stress is greater than that given by the rated peak withstand current since dynamic forces and

the movement of the switch blades aggravate the condition. Normally the short circuit making current is taken as 2.5 times the r.m.s. short time short cir-

cuit current. That multiple corresponds to the relationship in distribution networks when agenerator-remote short circuit occurs (peak value of the initial short circuit a.c. current IP =1.8 ⋅ √2 ⋅ Isc"; peak factor κ = 1.8). Close up to motors and generators, the peak value of themaking current may be more than the power frequency short circuit current. In such cases, theswitching device must have a rated value at least equal to this duty!

In switch and fuse combinations, the magnitude of the let through current of the largest fusefor which the combination is designed, is adequate.

C 9 Rated short-circuit breaking current Isc is the current which the device can safely interrupt when the short circuit is at its terminals.

In the selection of this value, the rated making current shall also be considered. NormallyIma = 2.5 ⋅ Isc, but if the relationship Im/Isc > 2.5 in the network, then a device with a largerrated breaking current must be chosen.

C 10 Rated mainly active load-breaking current I1 is the same as the rated (normal) current.

Page 48: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 48/116

Rated values of switching devices

48 © Siemens AG · 11E0

C 11 Rated closed-loop breaking current I2a, I2b is the same as the rated (normal) current.

C 12 Rated no-load transformer breaking current I3 applies to general purpose switches and is defined as the current of an unloaded transformer; thevalue amounts 1 % of the rated operating current.

C 13 Rated cable-charging breaking current I4a is between 6A (at 7,2 kV) and 20 A (at 36 kV) according to the standard. Manufacturers may givehigher values. Here, the charging current of unloaded cables is meant.

C 14 Rated line-charging breaking current I4b is between 0.5A (at 7,2 kV) and 2 A (at 36 kV) according to the standard. Manufacturers may givehigher values. Here, the charging current of unloaded overhead lines is meant.

C 15 Rated earth fault breaking current I6a is the largest earth fault current which the switching device, in a network with unearthed neutral

point, must be able to interrupt.This refers to a fault on the line side of the switch, with unloaded line (see Table A-3, case No. 11).The switch must be able to interrupt the charging current of all galvanically connected lines (some-times a larger value), at normal recovery voltage

C 16 Rated cable- and line-charging breaking current

under earth fault conditionsI6b is the largest current in the fault-free conductors, which the switch must be able to interrupt.

This refers to a fault on the line side of the switch, with unloaded cable (see Table A-3, case No. 9).The switch must be able to interrupt the charging current of the connected cables (or lines). Andthat at √3 x recovery voltage, because the earth fault remains, on the line side. Hard gas and air-

break switches have very small capability in this case.

Page 49: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 49/116

Rated values of switching devices

© Siemens AG · 11E0 49

C 17 Cable switching current under earth fault conditions

with superimposed load current

This current is not defined in the standards but is a realistic operational case. The standard requiresonly a value for unloaded cable switching under fault conditions. In practice, however, load currentsare almost always present.

For hard gas and airbreak switches, this is a very critical case (see Table A-3, case No. 10). Beforeusing such a switch, the network conditions must be ascertained and the capability requested fromthe manufacturer.

C 18 Rated transfer current Itransfer is the largest current which a switch, in a fuse switch combination, must be able to interrupt. Thisvalue is critical for the selection of the associated fuse; see section D.

Page 50: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 50/116

Rated values of switching devices

50 © Siemens AG · 11E0

C 19 Rated voltage UL (surge arrester with spark gaps)is the highest power frequency (network) operating voltage at which the arrester can still extinguishthe follow current after sparkover.

C 20 Rated voltage Ur (metal oxide surge arrester)is the maximum power frequency voltage which the arrester can withstand, when operating, underthe conditions of a short term voltage rise of at least 10 seconds.

C 21 Continuous operating voltage Uc (metal oxide surge arrester)is the maximum network operating voltage which may be applied continuously to the arrester.

C 22 Sparkover voltageis the voltage which causes the arrester to operate; that is, to break down its spark gap(s). The formof the voltage determines the speed of the breakdown and the threshold; one therefore qualifies thisvalue by distinguishing between switching impulse sparkover voltage uai, front of wave sparkovervoltage uast and 100% lightning impulse sparkover voltage uas100.

C 23 Residual voltage ures is the maximum voltage across the arrester terminals when the discharge current is flowing. Spark-over and residual voltage determine the protection quality of the arrester and are thus very impor-tant values for insulation coordination calculations.

C 24 Rated discharge current isn is the maximum value of the discharge current which the arrester can carry without exceeding thehighest permissible residual voltage.

Page 51: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 51/116

Selection of HRC fuses

© Siemens AG · 11E0 51

D SHORT-CIRCUIT PROTECTION WITH HRC FUSES

D 1 Selection criteria

In switch and fuse combinations, protection against short circuit is performed by the fuses. Switcheswill interrupt operating currents and only small overcurrents, since their interrupting capability islimited. Between operating current and full short circuit the switching duty transfers from one com-

ponent to the other. Switch and HRC fuses must, therefore, be matched correctly to each other.Mostly, one uses current limiting fuses; selection procedures are described later in this chapter.

The electrical characteristics of a fuse are: rated voltage and rated current (UrHH, IrHH). The diagramsclarify the factors which determine selection. In the diagrams the factors are coupled by a logic"AND", that is, they must all be considered in determining rated voltage and current.

Load characteristics

Switching capabilityof switch

Dynamic strengthof devices

Heating effect

IrHHU rHH

Network voltage

Load characteristics

Mechanical criteria, e.g. diameter, length, striker pin power, all depend upon the type and design ofthe switchboard or switch; they are not discussed here.

D 2 HRC fuses for transformers

D 2.1 Fuse rated current IrHH

There is a "Fuse rating table for transformers" recommended through IEC 60787 and the manufac-turers, which shows the fuse ratings suitable for all transformer power ratings.Selection is determined by:

• the inrush current on energising the transformer

• the primary current when the secondary is short circuited

• selectivity or grading considerations

Inrush current It affects the fuse in the same way as a large, time limited overcurrent. The fuse element of the fuseshall not be pre-conditioned by the heating effect of this current. A fuse with rated current largerthan the transformer rated current is therefore selected. Depending on power, short circuit voltageand connection group, the smallest usable fuse size results.

• For a simplified selection method the inrush current is set to 12 … 15 times the rated normalcurrent of the transformer, with a duration of 0.1 s; point ‚A’ in the overleaf figure.

Primary current while terminal short circuit on the low voltage side of the transformer

On interruption of such a terminal short circuit, very steep transients result. Because of the limitedinterrupting capability of the switch, these currents should be interrupted by the fuses. The primary

Page 52: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 52/116

Selection of HRC fuses

52 © Siemens AG · 11E0

side short circuit current can be very much damped but, evenso, the HRC fuses must operate andinterrupt positively and safely. This factor determines the largest possible rated fuse current.

• For a simplified selection method the short-circuit duration on the HV side shall correspond tothe maximum permissible short-circuit duration of the transformer; as a rule the value is 2 s.

• Minimum values of the short-circuit impedance urz 18

are listed in IEC 60076-5.

102

102 2 5 103 1042 5

101

100

10-1

10-2

Sustained short-circuit current Ik [A]

HRC fuse characteristic

A

Meltingtime Tm [s]

Imin

B

Simplified selection method for aHRC fuse:

The time current curve must lie between the points A and B.

Point A: I = ≈ 12 x IrT t = 0,1 s

Point B: I = IrT / urZ t = 2 s

The simplified selection method doesnot consider selectivity requirementsto other protection equipment up- ordownstream the HRC fuse.

Selectivity considerations Between HRC fuses: when two fuses are in series, the rating of the upstream fuse must be two stepsabove the rating of the downstream fuse. This situation often occurs, for example, in long radialfeeders (branch stations).

Between high and low voltage fuses: firstly, the currents must be adjusted for the voltage levels.The rated current of the high voltage fuse must be compatible with the current of the (largest - if anumber are in parallel) low voltage fuse.

Between high voltage fuse and low voltage circuit breakers: the LV breaker shall clear all faults

which are downstream of its terminals. For selectivity one needs the pre-arcing time characteristicof the fuse (calculated for the low voltage side) and the opening time of the LV breaker. The proce-dure is similar to that determining selectivity between fuse and motor protection relay.

⇒ additionally, the requirements of chapters D 5 to D 7 must be observed!

D 2.2 Rated voltage UrHH

The rated voltage of the fuse in most cases is determined by the network voltage only.

18 formely also designated as: uK

Page 53: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 53/116

Selection of HRC fuses

© Siemens AG · 11E0 53

D 3 HRC fuses for capacitors

D 3.1 Fuse rated current IrHH

When energising capacitors - particularly when paralleling them - extremely high inrush currents

can occur, with amplitudes of the order of short circuit magnitude. Inrush duration, however, isshort - in the range of milliseconds. These short circuit-like currents impose a very high degree ofstress on the fuses.

In addition to the 50/60 Hz basic frequency, higher harmonics always flow through a capacitor,dependent upon the harmonic content of the network. The effective value of the total current can,under normal network conditions, reach 1.4 x capacitor rated current.

For these reasons, the rated fuse current shall be at least twice the capacitor rated current.

⇒ Additionally, the requirements of chapters D 5 to D 7 must be observed!

D 3.2 Rated voltage UrHH

The rated voltage of the fuses shall be one step higher than the network voltage, so that there is ade-quate margin to cover the harmonic content.

D 4 HRC fuses for motors

Fuses provide short circuit protection, not overload protection for the motor! For motor protection, a

definite minimum time, current proportional protection relay is used. (In English terminology ani.d.m.t. relay, in German, an AMZ relay).

D 4.1 Fuse rated current IrHH

Catalogues from fuse manufacturers give selection recommendations, which consider the following points:

• the starting current of the motor

• the run up time and starting frequency

• compatibility with a motor protection relay, if fitted.

Motor starting current, run up time and frequency of starting

Starting currents, which can be up to 7 times the motor full load current, have the same effect on thefuses as a large, time limited overcurrent. The fuse element of the fuse shall not be pre-conditioned

by the heating effect of this current. The motor starting current and run up time gives the smallestusable fuse.

Page 54: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 54/116

Selection of HRC fuses

54 © Siemens AG · 11E0

Co-ordination with a definite minimum time (AMZ) relay

102

102 2 5 103 1042 5

101

100

10-1

10-2

Sustained short-circuit current Ik [A]

Motor startingcurrent

HRC fuse characteristic

i.d.m.t characteristic

Motor A

B

Imin

Meltingtime Tm [s]

run up time

125 A

⇒ the time current curve of the fuse must lie to the right of the motor run up current (point A).

⇒ the fuse rated current IrHH must be larger than the motor full load current (for slipring motors,reduced starting current)

⇒ the current at intersection B must be larger than the minimum operating current Imin of the fuse.If that cannot be achieved then it must be ensured that overcurrents up to Imin will be broken bythe switching device, for example, by a switch fuse combination with tripping by the fusestriker pin.

⇒ additionally, the requirements of chapters D 5 to D 7 must be observed!

D 4.2 Rated voltage UrHH

The rated voltage of the fuse is determined by the network voltage only in almost all cases.

D 5 Co-ordination with the switching device

A switch and fuse combination must be able to safely interrupt every possible current, up to fullshort circuit. The procedure is laid down in IEC 62271-105. Switch and fuse must be so co-ordinated that

• the switch safely handles all currents up to the minimum interruption current of the fuse;• the fuse interrupts all currents which lie beyond the interruption capability of the switch.

The largest (inductive) current which the switch can interrupt is called the rated transfer current of

the switch.

Page 55: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 55/116

Selection of HRC fuses

© Siemens AG · 11E0 55

Dependent upon the fuse rated current and the opening time of the switch there is a current abovewhich the fuses alone must interrupt the circuit. This current is the transfer current for the fuse andswitch combination, with the fitted HRC fuse. The transfer current shall not be larger than the ratedtransfer current of the switch.

Determination of the transfer current uses the following data:• the time current characteristic of the fuse

• the characteristic opening time of the switchT0 (for direct release by striker pin or tripping coil)

• the rated transfer current of the switch Itransfer (manufacturer's data)

For direct mechanical striker pin release of the switch: Draw a line parallel to the currentaxis through the point 0.9 T0 , to the pre-arcing time axis. Then to.

For electrical release of the switch, by a tripping coil: Draw a line parallel to the current axisthrough the point T0 to the melt axis; if a relay is in circuit with the tripping coil, draw the linethrough the point T0 + 0.02s.

The intersection of this line with the lower time/current characteristic of the fuse gives the as-sociated transfer current Itransfer (three pole, symmetrical value).

The transfer current Itransfer thus determined shall not be larger than the rated transfer currentIr-transfer stated by the manufacturer.

If the switch-fuse combination controls a distribution transformer, an additional condition must be fulfilled that the transfer current Itransfer is below the short-circuit current I”

kT-3pol of the trans-former at secondary terminal short-circuit.

Current

42 6 4102101 8 2

40 A

100

10-1

10-2

Tx

Meltingtime Tm [s]

Lower time-current characteristicTolerance limit -6,5 % Imin

Ik [A]

0,9 T0

Ir-tansfer Ratedtransfer current

Itransfer < Ir-transfer

Itransfer Ir-transfer

I"kT-3pol

Page 56: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 56/116

Selection of HRC fuses

56 © Siemens AG · 11E0

Determination of a transfer current from a fuse characteristic

Example, using 40 A high voltage HRC fuse and ring main unit 8DJ10

• HRC fuse, type 3GA: IrHH = 40 A• characteristic opening time of switch: T0 = 30 ms

⇒ transfer current of this combination: Itransfer = 250 A

Largest permissible HRC fuse

Conversely one can determine the largest permissible fuse for a combination, using the openingtime of the switch (T0) and the rated transfer current (Itransfer ).

For direct mechanical striker pin release of the switch: Draw a line parallel to the currentaxis through the point 0.9 T0, to the pre-arcing time axis. Then to .

For electrical release of the switch, by a tripping coil:Draw a line parallel to the current axis through the point T0 to the pre-arcing time axis; if a re-lay is in circuit with the tripping coil, draw the line through the point T0 + 0.02s.

Draw a line parallel to the time axis, through the point Itransfer on the current axis.

This gives an area bordered by current axis, time axis, line through 0.9 ⋅ T0 and line throughItransfer .

All fuses whose characteristics run through this area are suitable for use in this switch and fusecombination.

The illustration shows this procedure in diagram form.

Sustained short-circuit current Ik [A] Itransfer

suitable HRC fuses

HRC fuse characteristics

Meltingtime Tm [s]

Tx

Tx dependson the type of trippingmechanism= 0,9 T0= T0= T0 + 0,02 s

Page 57: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 57/116

Selection of HRC fuses

© Siemens AG · 11E0 57

D 6 Let-through (cut off) current

An HRC, current limiting fuse restricts the rising prospective fault current to its let-through valueand protects connected equipment from the extreme dynamic and thermal effects of the unrestrictedcurrent. The connected equipment does not need to be designed for the full prospective short circuit

current of which the network in front of the fuse is capable.• The let-through current must not exceed the rated withstand current of connected equipment; and• must not exceed the rated short circuit making current of the associated switch.

Current limiting characteristics give the maximum let-through (cut off) current ICO related to initial power frequency short circuit current and fuse rating. Conversely, one can determine the maximum permissible fuse rating from the given dynamic withstand capability of the equipment.

The diagram shows how the let-through current can be found from the characteristic.

4 10-1 2 4 6 100 101 4 102

Initial short-circuit current Ik" [kA]

40 A

Let-through

currentIco [kA]

7,25 kA

4

2

10

4

2

10-1

0

prospective peak current at cos phi < 0,15

Page 58: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 58/116

Selection of HRC fuses

58 © Siemens AG · 11E0

D 7 Heat losses

The actual maximum permissible operating current of a fuse is, in general, less than its nominalrated current due to the thermal conditions at the point of installation (in a cubicle or enclosure),where heat dissipation may be restricted in comparison with installation in free air. In that case, the

fuse cannot be operated at its full rating.

Heat loss check

The actual heat loss in operation is: PV = PVn ⋅ ( IB / IrHH )2

PV heat loss generated by HRC fuse at operating currentPVn rated heat loss from HRC fuse at IrHH IB actual operating current

⇒ For IB insert the maximum value which can occur continuously in operation; e.g. transformer

rated current or 1.2x transformer rated current for extensive overcurrent operation.⇒ Check if this heat loss is properly dissipated at the installed location.

⇒ If not, choose the next higher fuse rating, as long as the other selection criteria permit it.

Example: HRC fuse with Ur = 12 kV; IrHH = 100 A; PVr = 110 W

10-kV- transformer 800 kVA, operating current IB = 46,2 A

⇒ heat loss PV = 23,5 W

Page 59: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 59/116

Selection of surge arresters

© Siemens AG · 11E0 59

E SELECTION OF OVERVOLTAGE PROTECTION DEVICES

E 1 Selection criteria

The selection of surge arresters or voltage limiters is governed by the insulation capability (dielec-tric strength) of the equipment to be protected and the network data. Firstly, the following data must be available, from which one can then choose the correct device.

Arrester with spark gap (SiC arresters and overvoltage limiters)• residual and sparkover voltage• rated voltage• rated discharge current• energy absorption capacity

Metal oxide arrester • residual voltage

• rated and continuous voltage• rated discharge current• energy absorption capacity

The selection of surge arresters can be done by the following scheme:

Protection against

• Switching overvoltages=> Chapter E 2.1

• Lightning overvoltages=> Chapter E 2.2 (Overhead line ?)

Installation of arresters

at the cable terminals ?=> Chapter E 6

Switching

insulation level

Basic (impulse)

insulation level

• Residual and sparkover voltage

rated and continuous voltage

• Rated discharge current

• Energy absorption capacity

Arrester Type

=> Chapter E 3

=> Chapter E 4

=> Chapter E 5

E 2 Residual and sparkover voltage (Protection levels)

The insulation capability of the object(s) to be protected determines the required residual and spark-over voltages of an arrester. Reference variable for the dielectric strength and calculation of thelevel of protection of an object is its rated lightning impulse withstand voltage (1.2/50 µs), usuallyreferred to in insulation coordination terms as the BIL value ( Basic I mpulse Level).

Sparkover (for gapped arresters) and residual voltage (MO arresters) must be less than the insula-tion strength of the connected equipment whereby the sparkover voltage of gapped arresters may lie

a few kV above their residual voltage. The withstand capability of an insulation material depends onthe duration of the overvoltage; it is greater for a short, steep front than for the slowly decaying

Page 60: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 60/116

Selection of surge arresters

60 © Siemens AG · 11E0

transient. Devices can, therefore, withstand a short lived sparkover voltage which is slightly greaterthan the residual voltage.

E 2.1

Switching overvoltagesSwitching operations can initiate transient oscillations with different instantaneous polarity of thevoltages in the phases, so that the voltage between them can add up to greater values than to earth.If the switching operation might cause unduly high overvoltages, arresters must be so selected thatthe overvoltages between the phases (L-L), just as phase to earth (L-E), lie within acceptable limits.The objective is to achieve this with 3 arresters in phase to earth connection. If this is not possible,one needs a 6 arrester format.

Protection against switching overvoltages is always necessary in any case where multiple re-ignition or virtual current chopping can occur, when circuit breakers may interrupt pure inductivecurrents of less than 600 A. The necessary residual current of an arrester relates then to a discharge

current in this range. The rated values are somewhat differently arranged. One looks in the datasheets for the residual voltage at a discharge current of 0.5 kA. If 0.5 kA is not listed as a ratedvalue, one must take the smallest given value.

Both metal oxide and spark gap arresters are equally suitable for protection against switching over-voltages. If spark gap arresters are used, select only types for which a switching impulse spark-

over voltage is given in the selection tables.

E 2.1 a 3 arresters in line-earth connection

BIL

BIL

Protectedobject

L1

URes

L2

L32 URes

Required residual, respectively switching surge sparkover voltage: uRes; uai 15,1

83,021 ⋅⋅≤ PU

uRes Residual voltage at 0.5 kA follow current (→ rated discharge current)uai Switching impulse sparkover or residual voltageU p Basic Insulation Level of protected object (BIL)0,83 Reduction factor for switching impulse voltage withstand1,15 Recommended safety factor to IEC½ Since the line-line overvoltage – caused by transient oscillations – can rise to twice the line-

earth voltage, the arresters must limit the overvoltage to half the permissible line-line value.

Arresters with sufficiently small residual or sparkover voltage are not always available, since other peripheral requirements also have to be considered. This applies particularly for operating voltages

Page 61: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 61/116

Selection of surge arresters

© Siemens AG · 11E0 61

over 15 kV in networks with free or resonant earthed star point. In these cases one needs to installthree additional arresters in line-line format.

E 2.1 b 6 arrester connection

URes L-L BIL

BIL

Protectedobject

L1

URes L-E

L2

L3

Required residual, respectively switching surge sparkover voltage: uRes; uai 15,1

83,0⋅≤ P

U

uRes Residual voltage at 0.5 kA follow current (→ rated discharge current)uai Switching impulse sparkover (or residual) voltageU p Basic Insulation Level of protected object (BIL)0,83 Reduction factor for switching impulse voltage withstand1,15 Recommended safety factor to IEC

E 2.2 Lightning overvoltages

These occur only between conductor and earth, single phase, in all conductors. Therefore, to selectthe correct protection level one needs only to consider the stress to earth; 3 arresters in line-earth-

connection always provide sufficient protection against lightning surge.

Required residual, respectively switching surge sparkover voltage: uRes; uax γ

PU

uax 100% sparkover lightning impulse voltage uas100 respectively front-of-wave impulse sparkovervoltage uast

U p Lightning impulse withstand voltage (BIL)γ 1.25 ... 1.4 recommended safety factor for lightning protection

The recommended safety factor γ is higher than for switching overvoltages. It shall be at least 1.25 but it is recommended that one should aim for γ = 1.4.

Page 62: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 62/116

Selection of surge arresters

62 © Siemens AG · 11E0

E 3 Rated and continuous operating voltage

The terminology is as follows for surge arresters and surge limiters:

Rated voltage: Nominal term which describes an arrester; mainly used as ordering

information. According to the standard the rated voltage is themaximum voltage which the arrester can withstand for 10 secs.during the operating test without suffering damage.

For arresters with sparkgap (SiC and surge limiters), it is the power-frequency voltage at which the discharge follow current canstill be safely interrupted. The term corresponds to the continuousoperating voltage.

Continuous operating voltage: It is the maximum power-frequency voltage which may be appliedcontinuously - without limitation - across the terminals; decisive

term for metal oxide arresters (MO arresters).

For metal oxide arresters, one first selects the continuous voltage, then the rated voltage. In net-works with free or resonant earthed star point, the continuous voltage must be equal to the max.line-line voltage, so that the arrester is also suitable for continuous earth fault conditions (voltagerise in the healthy phases); rated voltage plays no part here.

For arresters with spark gap and surge limiters, almost only the rated voltage needs to be selected.If the values of rated and continuous operating voltage are not equal for the devices selected, theselection must be done as described for metal oxide arrester.

Neutral point

connection

Arrester with

spark gap

Metal oxide arrester

Rated voltage Ur Continuous

operating voltage

UC

Rated voltage Ur

solidly earthed Ur ≥ 1,4 · Umax / √3 Uc ≥ 1,05 · Umax / √3 Ur ≥ 1,4 · Umax / √3

resistance earthed Ur ≥ Umax Uc ≥ 1,05 · Umax / √3 Ur ≥ Umax

free orresonant earthed Ur ≥ Umax Uc ≥ Umax Ur > Uc

Umax = maximum operating voltage of the power system, or - if this value is not specified - themaximum permissible voltage for protected object.

Note: Umax is the maximum network voltage at the arrester terminals, including operationalincreases (caused by earth fault, load shedding etc.)

If the value Umax is not known the rated voltage of the protected electrical equipment

(for example 7,2 / 12 / 24 kV) shall be used.

Page 63: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 63/116

Selection of surge arresters

© Siemens AG · 11E0 63

E 4 Rated discharge current

This is a characteristic value for use in insulation coordination, which defines the discharge currentat which a given residual voltage will not be exceeded (rated operating point). The arrester will not

be destroyed when the rated discharge current is exceeded during a discharge, only the residual

voltage is greater. When selecting an arrester to protect against switching overvoltages the permit-ted residual voltage should be related to a discharge current of 0.5 kA. If this value is not present inthe selection tables, one must take the value for the smallest given current (e.g. at 1 kA, 2.5 kA or 5kA).

E 5 Energy absorption capacity

In medium voltage networks, this value is not a criterion. If more than one value is available, thesmallest can be safely selected. Exempted from this rule are arresters in connection with

- very large capacitors- large generators or motors- applications with extremely frequent discharges (for example arc furnaces).

E 6 Switchboards with overhead line connections

Such switchboards mostly have a (short) cable connection between station and overhead line. At theend of the OHL, an arrester is installed as lightning protection. Dependent upon the length of thecable, a second arrester, in the station, may be worthy of recommendation.

A lightning surge, limited to the residual voltage of the first arrester travels down the cable and, because of the alteration in wave resistance at the junction between cable and switchboard, will bereflected at point. The voltage at this cable end can approach double the value point. To pro-tect the switchboard and, particularly the cable terminal, an arrester should always be installed atthat point if travelling waves can build up in the cable. Above specific lengths that is always thecase.

ZK = 5 ... 50 ohms

Overhead line cable

ZF = 300 ... 500 ohms

Switchboard ZW >> ZK

Switchboard with overhead line infeed. Example of substation.

Lower limit of cable length

IEC 60071 recommends to install additional arresters in the substation at for cable lengths ex-ceeding the following length:

Page 64: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 64/116

Selection of surge arresters

64 © Siemens AG · 11E0

Highest voltagefor protected object

Cable travellingwave resistance ZK

Dielectric strengthof protected object

Maximum permissiblecable length without arrester

12 kV 10 Ω 15 Ω 20 Ω

75 kV 50 m30 m20 m

24 kV 15 Ω 20 Ω 30 Ω

125 kV 20 m15 m10 m

Overhead line: ZF ≈ 400 Ω

For lower values of insulation rating, the recommended cable lengths are shorter.

Upper limit of cable length

If the length of plastic insulated cables exceeds approximately 500 m or with oil-paper insulatedcables exceeds approximately 300 m the arrester at in the substation is not necessary since thetravelling wave is effectively damped and furthermore the earth capacitance of the cable reduces thesurge amplitude additionally.

The surge impedance of a cable is:

s

mC

Z r

K

µ

ε

300'⋅=

εr relative dielectric factor for the cable insulationC' operational capacity of the cable per unit length (from data sheets)

Typical values εr : 3,4 ... 4 oil paper2,4 PE, XLPE5 ... 8 PVC

Arrester is an outdoor arrester, which must be suitable for lightning protection duty; for arrester, an indoor arrester with smaller energy absorption capacity. If the energy absorption capacity ofarrester is smaller, it must be ensured that the sparkover or residual voltages are properly graded,so that the outdoor arrester always operates first.

Page 65: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 65/116

Switchgear configuration

© Siemens AG · 11E0 65

F SWITCHGEAR CONFIGURATION

F 1 Principles of configuration

F 1.1 General

The switchgear configuration process described here focuses on the primary section and covers the basic technical aspects involved in selecting and rating the main switchgear components. This con-figuration guide does not, therefore, replace the ordering data catalogue.

The process of designing secondary systems with devices for protection, control, measurement, andcounting purposes is not covered here.It is assumed that the network parameters for configuring the switchgear are already known.

F 1.2 Requirements and complementary characteristics

Optimum

Medium Voltage

Switchgear

Product charactistics

• Rated values

• Operating

properties

• Reserves

Requirements

• must be observed

• can be influenced

• freely selectable

Result

Configuration

Selecting and

rating the

product properties

The requirements specified must be used as a basis for selecting the right products with the rightrated values from the range available. Due to the wide range of often very different requirements,

however, it is not always easy to know which products to select or how to rate them.• Requirements that must be observed are those that relate to the electrical aspects of the switch-

gear, whereby the switchgear must offset the complementary strength properties against the physical stresses. Legal regulations as well as personnel protection, fire protection, and environ-mental compatibility requirements must also be strictly observed.

Clearly-defined configuration rules are normally available for requirements that must be observed.

• Some requirements can be influenced, that is, measures taken in other areas may affect the re-quirements regarding the switchgear which, in turn, makes it easier to select and rate the switch-

gear. For example, measures can be taken to reduce the duration of the short-circuit current,

Page 66: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 66/116

Switchgear configuration

66 © Siemens AG · 11E0

overvoltage protection can help avoid excessive insulation levels, while the building housing theswitchgear may be modified to improve environmental conditions and reduce climatic stress.

Selection and rating rules are not defined for these "soft" requirements, although recommenda-tions are provided.

• Freely-definable – even "negotiable" – requirements offer the greatest scope with regard to de-signing the switchgear. Operators can select specific product characteristics at their discretion tooptimize the switchgear in line with their own requirements. Decisions may be based on, for ex-ample, tried-and-tested operating processes or internal company guidelines.

This document only covers those aspects of freely-selectable requirements that are relevant forconfiguration activities.

F 1.3

ProcedureSection G of this guide not only covers the influences and stress variables but also the associatedcharacteristics and properties of the switchgear.

Section H breaks down the process of selecting and rating a switchgear system into individual stepsand describes which influences and stress variables must be taken into account in each individualstep. Where relevant, rules and recommendations are provided along with aspects that must betaken into account.

A wide range of non-technical aspects must be taken into account when switchgear is configured:

• Requirements of state legislation always take priority over normative regulations (e.g. protectingthe public, work safety, environmental protection).

• Tried-and-tested operations and procedures carried out by the operators can determine whichequipment is required. After all, taking into account "standard practices" of operators also con-tributes to a safe working environment.

• Requirements and features that focus on operations and procedures can vary considerably fromregion to region.

• If applicable, company guidelines may also have to be taken into account.

• Recommendations of industrial associations.

These are just some of the requirements that manufacturers, planners, and operators must agreeupon. A configuration guide cannot cover all aspects of these requirements. It can only highlightthose points that are applicable to all switchgear systems at all times.

Page 67: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 67/116

Switchgear configuration

© Siemens AG · 11E0 67

F 2 Switchgear requirements

The key influences and stress variables for switchgear depend on the task in hand and its position inthe distribution network.

Line parameters

Line protection and measurement

Infeeds

Operating sites

Environmental conditions

Industry-specific applications

Specific operating procedures

Regulations

• Rated voltage • Neutral point grounding• S.-c. current • Underground/overhead lines• Normal current • Overvoltage protection• Load flow • Energy quality

• Protection functions • Redundancy• Selectivity • Tripping times• Measurement • Metering

• Ambient conditions • Altitude

• Temperature • Humidity

• Public grid • Emergency supply• In-plant generation • Redundancy

• Installation location • Accessibility• Service room • Building• Transportation • Assembly

• Switching duty • Switching frequency• Busbar switchover • Availability

• Operation • Personnel protection• Work activities • Work instructions• Inspection • Maintenance

• Standards • Laws• Association guidelines • Company guidelines

These influencing factors and stresses, which are explained in detail in Section G, determine theselection and rating variables for the switchgear.

Page 68: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 68/116

Switchgear configuration

68 © Siemens AG · 11E0

F 3 Properties to be selected

This diagram provides an overview of the main switchgear features to be configured in the se-quence normally carried out when switchgear is selected and rated.

Switchgear features Selection and rating variables

Primary rating values

Circuit arrangement

Switching devices

Design and switchgear panel types

Enclosure

Compartmentalisation

Components in the feeder

Components at the busbar

Secondary equipment

• Voltage • Normal current• Insulation level • Short-circuit current

• Single / double busbar • Bus section / transfer • Bus coupler unit

• Degree of protection• Internal arc classification

• Circuit-breaker • Contactor • Switch • HRC fuse

• Circuit-breaker/switch-disconnector unit• Air / gas insulation• Withdrawable unit (truck) / fixed mounted

• Accessibility / access control• Loss of service continuity + partition class

• Cable terminals • Instrument transformers• Surge arresters • Earthing switch

• Instrument transformers • Earthing switch• Surge arresters • Cable terminals

• Interlocks, protection, measurement, metering• Control, monitoring, communication• Manual / motorised drive mechanisms

Section H contains a detailed explanation of the configuration rules that need to be applied andother aspects that need to be taken into account.

Page 69: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 69/116

Switchgear configuration

© Siemens AG · 11E0 69

G INFLUENCES AND STRESS VARIABLES

G 1 Network characteristic values

G 1.1 Line voltage

This determines the rated voltage of the switchgear, switching devices, and other installed compo-nents. The determining factor here is the maximum line voltage at the upper tolerance limit.

Assigned configuration criteria for switchgear:

• Rated voltage Ur

• Rated insulation level Ud; U p

• Rated primary voltage of voltage transformers U pr

G 1.2 Short-circuit current

This is characterized by the variables peak current I p (peak value of the initial symmetrical short-circuit current) and sustained short-circuit current Ik . The required short-circuit current level in thenetwork is specified by the dynamic behaviour of the loads and the quality of the energy, whichmust be maintained, and determines the making, breaking, and withstand capacity of the switch-gear.

Note that the ratio of the peak current to the sustained short-circuit current in the network can besignificantly greater than the standard factor I p/Ik = 2.5 (50 Hz) or 2.6 (60 Hz) according to whichthe circuit-breakers and switchgear are designed. This could be due, for example, to motors thatsupply energy back to the network if a short-circuit occurs, which significantly increases the peakcurrent.

For the short-circuit duration, see G 2.3 Command times

Assigned configuration criteria for switchgear:

• Main and earthing circuit: - Rated peak current I p

- Rated short-time current Ik • Switchgear: - Rated short-circuit making current Ima

- Rated short-circuit breaking current Isc

• Current transformer: - Rated dynamic current Idyn - Rated short-time thermal current Ith

G 1.3 Normal current and load flow

The normal current refers to the current paths of the infeeds, busbar(s), and load feeders. The cur-rent is also subdivided due to the physical arrangement of the switchgear panels with the effect that

Page 70: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 70/116

Switchgear configuration

70 © Siemens AG · 11E0

different rated current values can be found in sequence along the conducting path (the currents in busbars and feeders are normally different).

Reserves must be planned for the value of the rated normal current:

- In accordance with the ambient temperature;

- For the planned overload;- For temporary overloads in the event of faults.

With high normal currents, large cable cross-sections or several parallel cables must be connectedin the switchgear panel; the field terminal must be designed to accommodate this.

Assigned configuration criteria for switchgear:

• Rated current of busbar(s) and feeders

• Number of cables for each conductor in the switchgear panel (parallel cables)

• Rating of the current transformers

G 1.4 Neutral earthing

The type of neutral earthing used, insulated neutral / earthed with an arc suppression coil19 / (tempo-rarily) resistively earthed / solidly (directly) earthed – governs the behaviour of the line voltagewhen switching operations are carried out or if a earth fault occurs in the network as well as the

characteristics of the earth fault currents. This means that neutral earthing has a major influence onthe dielectric stress on the equipment and is important for insulation coordination.

Assigned configuration criteria for switchgear:

• Insulation level of the equipment

• Choice of switchgear

• Rating and damping of voltage transformers

• Design of current transformers and protection relays for earth fault detection

• Rating of surge arresters

G 1.5 Underground / overhead lines

The network type governs insulation coordination and which overvoltage protection measures needto be taken. In overhead systems, powerful overvoltages can be caused by a lightning strike, whileonly weak switching overvoltages generally occur in underground networks. Overvoltages fromoverhead systems can reach switchgear indirectly or via a transformer. These connecting pointsmust be taken into account and checked to determine whether surge arresters are needed.

19 Petersen coil

Page 71: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 71/116

Switchgear configuration

© Siemens AG · 11E0 71

The network type also affects the choice of switchgear: in overhead systems, for example, transientfaults are more likely to occur. Circuit-breakers must be able to manage reclosing cycles and a highnumber of make-break operations. The short-circuit currents in medium-voltage overhead systems,however, are low (generally between 8 kA and 12 kA).

Assigned configuration criteria for switchgear:

• Selection and rating of circuit-breakers

• Insulation level

• Use and rating of surge arresters

G 1.6 Overvoltage protection

If the expected voltage stresses exceed the insulation level of the equipment, insulation coordinationrequires overvoltage protection. This can apply, for example:- When external overvoltages can be expected as a result of lightning strikes;- When (multiple) earth faults occur frequently;

- High transient overvoltages may occur as a result of switching operations;- When, in the interests of economy, certain equipment (e.g. motors, resin-encapsulated / dry-type

transformers) is rated for lower insulation levels than the other network components.

Overvoltage protection is also used as a general precaution to minimize the risk of failure and to protect equipment against any form of overvoltage. It is generally used for very large motors ortransformers that are not only expensive and difficult to procure but also incur high costs if theyfail.

Frequent overvoltages can also cause some insulation systems to age, even if the stresses are stillwithin permissible limits. Overvoltage protection measures are also recommended in “unstable”networks (=> see G 1.7 Power quality).

Overvoltage protection systems normally comprise surge arresters. In certain cases, surge capacitorsor resistance-damped surge capacitors (RC elements) are also required.

Switchgear must be checked to determine whether overvoltage protection is required, whether pro-tection measures have already been taken, or whether existing protection devices need to be up-graded.

Assigned configuration criteria for switchgear:

• Insulation level

• Check for "critical" switching duties

• Rating of the surge arresters

Page 72: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 72/116

Switchgear configuration

72 © Siemens AG · 11E0

G 1.7 Power quality (unstable loads)

The power quality refers to unwanted interference, such as voltage dips, flickers, asymmetry, har-monics etc.. These can be caused for example by rectifiers, converters, welding machines, direct-starting motors. Other loads (e.g. IT systems), however, are sensitive. To protect them, the interfer-

ence is compensated as much as possible or the "stable" and "unstable" loads are distributed acrosssub-networks with separate infeeds. Depending on the circuit arrangement, switchgear with singleor double busbars is required.

Assigned configuration criteria for switchgear:

• Single/double busbar- Bus section panel- Bus coupler unit

• Rated normal current (busbar)

• Rated short-circuit currents

G 2 Line Protection, measurement and metering

G 2.1 Short-circuit protection

The line protection concept has a major influence on the switchgear that is selected and its design.

The following devices can be used for short-circuit protection:- HRC fuse (in a switch- or contactor-fuse combination)- Instrument transformer + protection relay + circuit-breaker

If the majority of network branches are equipped with switch-fuse combinations, switch-discon-nector units can be used; otherwise, circuit-breakers are used.

Assigned configuration criteria for switchgear:

• Design: circuit-breaker or switch-disconnector unit

G 2.2 Protection functions

Protection relays obtain their measurement signals from current and voltage transformers, which areinstalled in the switchgear. The range of available protection functions (e.g. inverse/definite-timeovercurrent, distance/differential protection) requires current transformers whose cores can be com-

bined in a variety of ways with different rated currents, overcurrent number, output, and class accu-racy. Voltage transformers are also provided for protection with directional control or for determin-ing the fault location (distance protection). Sensitive earth fault protection devices require a core-

balance transformer around the three conductors to measure small earth fault currents in compen-

sated networks or networks with an insulated neutral point.

Page 73: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 73/116

Switchgear configuration

© Siemens AG · 11E0 73

The switchgear must provide a space in which these instrument transformers can be installed aswell as space for the protection relays and their wiring. This may seem obvious, but it is importantto remember that other components (surge arresters, multiple cable terminals etc.) also need spacein the switchgear.

Assigned configuration criteria for switchgear:

• Installation of instrument transformers in the switchgear panel and on the busbar

• Installation of a core-balance transformer(normally cable-type current transformer, or "earth fault winding")

• Installation of protection relays and wiring in the low-voltage compartment

G 2.3 Command times

The set command times (specified by means of selectivity requirements in accordance with thenumber of subordinate network levels and their equipment) are governed by the rated short-circuitduration of the switchgear, the current transformer, and the earthing circuit. The standards permitvarious rated values for the components. For short-circuit durations of > 1 s in particular, it is im-

portant to ensure that all components are dimensioned to manage the actual short-circuit duration atthe minimum.

For the actual short-circuit duration, the mechanical delay (opening time) of the switching devicemust also be added to the command time of the protection system.

Assigned configuration criteria for switchgear: • Rated duration of short-circuit

- Main circuit (switchgear, disconnector, and earthing switch)- Earthing circuit- Current transformer

G 2.4 Measurement and metering

Measurement and metering systems generally require separate, additional transformer cores with adifferent rating to that of the protection cores.

Assigned configuration criteria for switchgear:

• Room for installing transformers as well as measurement devices and meters (see G 2.2).

G 2.5 Redundancy

Different protection functions can be combined in a single network branch (e.g. differential andovercurrent-time protection as backup). Depending on the degree of redundancy required, addi-

Page 74: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 74/116

Switchgear configuration

74 © Siemens AG · 11E0

tional instrument transformers and protection devices may also have to be installed in the switch-gear. Enough space must be available for these too (see above).

For contractual reasons, the same measurement device or meter may also be installed twice if con-tractual partners use their own devices at the point of supply ("check measurement"). This increasesthe number of built-in components.

Assigned configuration criteria for switchgear:

• Room for installing transformers as well as measurement devices and meters (see G 2.2).

G 3 Infeed types

The operating principle and number of infeeds are crucial for connecting the switchgear and for itsrated current values. The supply from different networks, such as …

- the public network

- in-plant generation

- the emergency power supply

… sometimes has to be disconnected during normal operation for safety, business, or contractualreasons. A decision must, therefore, be made regarding how the supply can be divided into busbarsections and which ones can be linked. The switchgear design as well as the rated normal and short-circuit current values depend on the infeed operating principle and the couplings.

Assigned configuration criteria for switchgear:

• System connection- Single/double busbar- Bus section panel

• Rated values of the switchgear- Normal current of the busbar(s)- Peak current and short-time current

• Control, interlocks, and switchgear interlocking

• Installation of instrument transformers in the switchgear panel and on the busbar

• Room for installing the protection relays and wiring in the low-voltage compartment

Page 75: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 75/116

Switchgear configuration

© Siemens AG · 11E0 75

G 4 Operating sites

The type of operating site can also govern the choice and rating of switchgear. Given the broadrange of different influencing factors, only the key points that need to be taken into account can bedescribed here.

G 4.1 Installation location

Many locations are subject to legal regulations concerning safety and health, fire protection, andenvironmental compatibility. This mainly applies to systems in public areas (e.g. pedestrian zones),industrial premises (offices, workshops), public buildings (high-rises, hospitals, office buildings,

bars, conference centers etc.). Special regulations also apply for nature reserves, mines, railways,and boats.

Even if the switchgear malfunctions, it must behave in such a way as to minimize negative impact.

Malfunctions include situations in which the switchgear is subject to external damage (e.g. fire) oris itself the cause of the problem (e.g. internal faults).

Assigned configuration criteria for switchgear:

• Design

• Internal arc fault classification

• Pressure absorber, pressure release duct

G 4.2 Accessibility

The standards also take into account the different levels of accessibility of operating sites:

- Only authorized and trained personnel have access to closed electrical operating area; all other people must be accompanied.

- Operating sites in public areas can be accessed by everyone (e.g. standard for stations andswitchgear in workshops).

Switchgear in public areas are subject to more stringent requirements.

Assigned configuration criteria for switchgear:

• Air or gas insulation

• IP degree of protection

• IK degree of protection (mechanical shock)

• Internal arc fault classification

Page 76: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 76/116

Switchgear configuration

76 © Siemens AG · 11E0

G 4.3 Switchgear room

Certain standards (IEC 61936) and laws define specifications regarding how the system is set up inservice rooms (e.g. the minimum width of operating and assembly aisles) and define the bindingrequirements for escape routes (e.g. width and maximum length of escape routes, preferred direc-

tion in which doors close etc.).The service room might also contain other equipment for which operators can define their ownspecifications regarding free areas and setup.

The switchgear must enable all requirements to be fulfilled.

Assigned configuration criteria for switchgear:

• Dimensions of the switchgear panels, in particular the panel width

• Position of door stops; opening angle of the switchgear panel doors

• Position of controls and displays/indicators (front/rear)• Cable connection from the front or rear

• Required accessories (switching levers, tools, etc.)

G 4.4 Buildings

The building itself can also influence the choice of switchgear. The following aspects must be takeninto account:

- The available space- The quality of the building fabric (in existing, older buildings)- Vent outlets in the event of an internal arc fault

Assigned configuration criteria for switchgear:

• Switchgear panel width, depth, and height

• Air or gas insulation

• Internal arc fault classification

• Pressure absorber, pressure release duct

Irrespective of the chosen switchgear, a dynamic pressure calculation must be carried out for the building to determine the stresses on the structure and the required cross-sections for vent outlets.

The building is also a crucial factor regarding the conditions under which the switchgear operates; see G 5 Environmental conditions.

Page 77: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 77/116

Switchgear configuration

© Siemens AG · 11E0 77

G 4.5 Transportation and assembly

In certain – albeit rare – cases, transportation and assembly conditions are a key selection criterionfor the switchgear. Whether or not switchgear can be installed in a building depends on certain con-structional factors, such as:

- The size and position of doorways- Permissible floor loading- Floor level

- Goods elevator

Assigned configuration criteria for switchgear:

• Size of the transportation units

• Weight of the transportation units

• Packaging (stability, weather protection if the device is in temporary storage over a long period)

G 5 Environmental conditions

G 5.1 Ambient room conditions

Switchgear installed in service rooms can be subject to the following ambient conditions:

-

Heat and humidity- Pollution

- Dust and smoke

- Salt (near the coast or in mining)

- Corrosive gases and vapours (natural and artificial)

- Insects / small animals

Due to the infinite variety of ambient conditions at installation locations, the applicable standardsonly define basic requirements for "normal service conditions". Each system much be examined

individually to determine whether or not these are observed. Numerous measures can be taken to provide protection against exceptional climatic conditions. Forexample, gas-insulated, hermetically sealed compartments that are completely immune to externalconditions can be used. The degree of protection of the housing can also be increased. In parts ofthe world where high insect/small animal populations can cause problems, protection against bridg-ing may be appropriate by fitting additional insulation to live and exposed components.

Page 78: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 78/116

Switchgear configuration

78 © Siemens AG · 11E0

Assigned configuration criteria for switchgear:

• Design: air or gas-insulated switchgear

• IP degree of protection for housing (can be increased with drip-water protection if necessary)

• Type of ventilation• Additional insulation for live and exposed components

Measures to provide protection against extreme ambient conditions can also be taken in the serviceroom (air conditioning). In some cases, this can be more efficient than designing each individualcomponent accordingly. It is also important to remember that protection, measurement, and controlsystems are more sensitive than switchgear, which is reason enough to ensure that the minimumrequirements for air quality are observed.

G 5.2 Altitudes above 1000 m

The standardized insulation levels apply to normal ambient conditions at sea level. As the altitudeincreases, however, the air density decreases as do the insulating properties. The applicable stan-dards take this into account and allow for a reduction of approx. 9% at altitudes of up to 1000 m. Athigher altitudes, the required insulation level must be ensured by increasing the rated voltage (withrespect to sea level values). Insulation coordination can also be ensured by means of additionalsurge arresters. Alternatively, gas-insulated switchgear in which the primary section is hermeticallysealed can be used. In this case, the external air pressure is not an issue.

Assigned configuration criteria for switchgear:

• Design: air or gas-insulated switchgear

• Selection of a higher rated voltage with a higher insulation level

• Use of surge arresters

G 5.3 Ambient temperature and humidity

The ambient temperature directly affects the temperature of the switchgear which, in turn, affects itscurrent-carrying capacity. As the ambient temperature increases, the current-carrying capacity de-creases (and vice versa). To compensate for this, either the rated current value must be increased orsufficient ventilation must be ensured (ventilation openings affect the IP degree of protection).

Humidity has a negative effect on the insulating properties. High levels of humidity together withsudden temperature changes can cause condensation which, in turn, drastically reduces insulationlevels. To prevent this, controlled or permanent heaters can be used in conjunction with humidistats.

Page 79: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 79/116

Switchgear configuration

© Siemens AG · 11E0 79

Assigned configuration criteria for switchgear:

• Rated normal current

• Type of ventilation

• Differentiation of IP degree of protection according to protection against ingress of solid foreign bodies and shock-hazard protection

• Installation of a heater in the switchgear panel or in the low-voltage compartment

G 6 Industry-specific application

The following aspects cover the role and significance of the switchgear in the operator's network(industrial or public utility companies).

G 6.1 Switching duty and capacity

The choice and rating of the switchgear depends on the switching duty and the loads to be switched.Is the switchgear only required to switch normal currents? Or does it need to interrupt short-circuitstoo? Due to the transient switching operations, certain loads require overvoltage protection. In othercases, additional rating criteria apply to the switch and switchgear.

Assigned configuration criteria for switchgear:

• Switchgear: circuit-breaker, switch or contactor with HRC fuses

• Rated electrical values

• Additional measures (e.g. overvoltage protection)

• Classes for mechanical and electrical endurance

• Design: circuit-breaker or switch-disconnector unit

G 6.2

Switching frequency of the loadsAlongside the electrical requirements regarding the switching capacity, the switching frequency isan important selection criterion. The switching frequency depends on the process in which theswitching device is used. Switches are rated for a short electrical lifetime (number of make-breakoperations), while contactors are rated for extremely long lifetimes; circuit-breakers fall in between.Once a basic decision has been reached regarding the type of switchgear, standardized lifetime in-crements can be selected for the switches (endurance classes).

For higher switching frequencies under normal operating conditions, switchgear must be serviced orreplaced more often. In this case, the components must be easily accessible.

Page 80: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 80/116

Switchgear configuration

80 © Siemens AG · 11E0

Assigned configuration criteria for switchgear:

• Switching devices: circuit-breaker, switch or contactor

• Classes for mechanical and electrical endurance

• Design of the switchgear assembly- Air or gas-insulated system- Withdrawable or fixed disconnector

• Loss of service continuity category

G 6.3 Frequency of switchover between busbars

In switchgear with double busbars, the lifetime of the disconnector plays a crucial role. For opera-

tional reasons, some networks require frequent switchovers between busbars. Due to the short me-chanical lifetime of a disconnector / withdrawable unit as compared with a circuit-breaker, "stan-dard" double busbar switchgear systems with just one circuit-breaker are unsuitable for this type ofoperation. Standard double busbar systems have a common connection (cross connection betweenthe two busbars) between the two disconnectors and the circuit-breaker.

To prevent wear and tear to the disconnector / withdrawable unit and, in turn, minimize mainte-nance cycles, the busbars are switched by means of circuit-breakers. This requires two single busbarsystems each with two circuit-breakers in one feeder circuit.

Assigned configuration criteria for switchgear:

• Design of the switchgear

• Double busbar with common connection or two single busbars

• Interlocks and switchgear interlocking

G 6.4 Availability (faults, redundancy, switchover time)

The term "availability" in this context means providing ways of compensating for line failures, forexample, by means of redundant supply channels or defined switchover times. It also refers to the

reliability of switchgear and features for planned maintenance activities or troubleshooting.The switchgear provides the current paths for multiple supply channels and the switchover options.This can be used to determine the system circuit: single or double busbars and separated into differ-ent sections. The various options for linking busbars (busbar sections) with separate infeeds and theoperating principle (NO / NC) of the couplings govern the rated current values.

The switchgear itself must also be sufficiently reliable, maintenance friendly (and not require exces-sive maintenance), and accessible. A decision regarding the Design of the switchgear assembly andthe partitions can be made on the basis of there criteria.

Page 81: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 81/116

Switchgear configuration

© Siemens AG · 11E0 81

Assigned configuration criteria for switchgear:

• Circuit arrangement- Single/double busbar- Bus section panel

• Interlocks and switchgear interlocking

• Rated values of the switchgear- Normal current of the busbar(s)- Peak current and short-time current

• Design: air or gas-insulated switchgear

• Loss of service continuity category- Design of partitions

G 6.5 Modifications or extensions

Switchgear is sometimes set up in sub-sections or needs to be extended or modified during thecourse of its operating life. If such measures are anticipated, these should be taken into account inthe planning stage.

Assigned configuration criteria for switchgear:

• Design

• Extension to include additional switchgear panels• Rated values for normal and short-circuit current

• Replacement of instrument transformers

• Option of upgrading the secondary system

G 7 Operating procedures

Operating procedures is a catch-all term that, with respect to configuration activities, will only beused to describe the following activities:• Operation

• Work activities

• Maintenance

G 7.1 Operation

Operational activities include monitoring, switching, making settings, and reading displays / indica-tors. Operators can define how these activities are to be carried out, that is, whether they are to be

carried out on site or remotely, (completely or partially) manually or automatically.

Page 82: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 82/116

Switchgear configuration

82 © Siemens AG · 11E0

The automated integration of the switchgear in the network system management and production process makes important demands on the measurement, control, and remote control systems (sec-ondary technology).

During operation, the switchgear must provide the required level of personnel protection (e.g. pro-

tection against accidental contact with hazardous live or mechanical components (IP degree of pro-tection). Even in the (unlikely) event of an internal fault, the switchgear must offer means to protectthe operator.

Assigned configuration criteria for switchgear:

• Design of the switchgear- Air or gas-insulated system- Withdrawable or fixed disconnector

• Type of compartments (access control)

• Loss of service continuity category• Control and secondary equipment

• Interlocks and switchgear interlocking

• Manual or automatic drive mechanisms

• IP degree of protection

• Internal arc fault classification

G 7.2 Work activities

Activities in this context refers, for example, to modification, servicing, and maintenance activitiesor replacing fuses. When such activities are carried out, the system must be either fully or partiallytaken out of service. How much of the system is taken out of service depends on the ‘loss of servicecontinuity category’, which must be defined by the operator along with the type of access control tothe disconnected compartments. Shock-hazard protection for live components can, to varying de-grees, be installed permanently in the system or implemented manually. Again, the operator mustdecide which method to use. How the work procedures are organized and the level of training of the

personnel play an important role here.

Assigned configuration criteria for switchgear:

• Loss of service continuity category

• Type of compartments (access control)

• Partition class

Page 83: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 83/116

Switchgear configuration

© Siemens AG · 11E0 83

G 7.3 Inspection and maintenance

System inspection and maintenance requirements can vary enormously and are subject to numerousinfluencing factors completely unrelated to electrical engineering, such as:

- Environmental conditions

- Industry-specific operating procedure

- Legal regulations

- Internal organization and work instructions

- Level of personnel training

Inspection and maintenance must be treated as separate activities. It may be the case that certain procedures require more frequent inspections, for example, which means that the switchgear must be more readily accessible. In this case, therefore, a completely hermetically-sealed system may not be the best solution because it cannot be accessed. Components may need to be readily accessible if,

for instance, they need to be replaced more often due to a high switching frequency. The degree ofrequired accessibility also depends on various regulations and the level of personnel training. Theseaspects also govern the switchgear design.

Assigned configuration criteria for switchgear:

• Design of the switchgear- Air or gas-insulated system- Withdrawable or fixed disconnector

• Loss of service continuity category

• Type of compartments (access control)• Selection of switching devices and its endurance classes

G 8 Regulations

Switchgear is subject to numerous regulations relating to its design, manufacture, inspection, setup,and operation:

- Electrical engineering standards

- Recommendations of industry or utility associations

- Legal regulations

- Internal company regulations

While the electrical engineering standards are fulfilled by nearly all products, legal or internal regu-lations in different industries can pose special challenges.

Assigned configuration criteria for switchgear:

• Determine any deviations from the requirements defined in the IEC / EN standards.

Page 84: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 84/116

Switchgear configuration

84 © Siemens AG · 11E0

H SELECTING AND RATING SWITCHGEAR

H 1 Overview (Checklist)

This table lists all the rating and selection variables along with the requirements and influencingvariables, which are explained in detail in the following sections.

Selection variable Key influencing factors

• Line voltage• Ur Voltage• Ud, U p Insulation level Insulation coordination

• Neutral earthing• Underground/overhead lines• "Critical" loads• Overvoltage protection• Altitude• Ambient conditions (pollution)

• IP, IK , tK Withstand capability• Ima, Isc Switching capacity

• Characteristic line values• Loads and power quality• Line protection, selectivity, tripping time

P r i m a r y r a t e d v a l u e s

• Ir CurrentBusbars and feeder circuits

• Load, load flow• Ambient temperature

• Reserves / availability• Single/double busbar• Bus section panel• Bus coupler unit• Switchover with load interrupter switch

or circuit-breaker

• Line structure• Line protection, selectivity, trip times• Reserves / availability, switchover time• Operating procedures• In-plant generation, emergency supply• Power quality (unstable loads)

C i r c u

i t a r r a n g e m e n t a n d s e t u p

• Double busbar with common connection• Two single busbar systems

• Operating procedures• Frequency of busbar switchover• Interlocks and switchgear interlocking• Setup (physical)

S w i t c h i n g d e v i c e • Circuit-breaker

• Switch• Contactor• HRC fuse

• Switching duty (load)• Switching capacity• Switching frequency• Line protection,

selectivity, tripping times

Page 85: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 85/116

Switchgear configuration

© Siemens AG · 11E0 85

Selection variable Key influencing factors

D e s i g n a n d s w i t c h g e a r p a n

e l t y p e s • Circuit-breaker unit

• Switch-disconnector unit

- Panels (can be mounted side by side)- Block

• Line parameters

• Switching devices

• Operating current, switching capacity• Line protection

• Installation conditions

• Transportation and assembly

• No. of switch / circuit-breaker panels

• Operating procedures and operation

• Expandability,electrical / mechanical reserves

I n s u l a t i n g m e d i u m • Air (AIS)

• Gas (GIS)• Ambient room conditions: temperature

change, humidity, pollution, salt, corro-sive gases

• Type of operating site• Installation location (space requirements)• Fire protection requirements (fire load)• Altitude• Switching frequency and switch lifetime

D i s c o n n e c t

o r • Withdrawable unit / truck

• Disconnector (built in)

• Switching frequency

• Component lifetime

• Operational requirements(access to cable terminal)

• Degree of protection (IP)

E n c l o s u r e

• Internal fault qualification• Pressure release duct

• Ambient conditions• Personnel protection• Type of operating site• Building

• Accessible• Not accessible

• Access control by means of:- Interlock- Work instruction + lock- Tool

• Loss of service category(compartmentalization) C

o m p a r t m e n t s

• Partition class - PM

- PI

• Operating procedures

• Operation, work activities

• Maintenance requirements

• Servicing / maintenance(component lifetime)

• Operator regulations

• Personnel training

• Shock-hazard protection during workactivities

• Switchgear space requirements

Page 86: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 86/116

Switchgear configuration

86 © Siemens AG · 11E0

Selection variable Key influencing factors

• Cable connection- Sealing end: plug / standard- Number of cables

- Cable cross-sections• Surge arrester

• Operating and short-circuit current• Switching duty•

Underground / overhead cables• Altitude

• Voltage transformer- Earth fault winding (if required)- Current transformer- Core number and data

• Core-balance transformer(cable-type current transformer)

• Line protection• Measurement, metering• Control• Neutral earthing

F e e d e r c i r c u i t c o m p o n e n

t s

• Earthing switch- Class E0- Class E1 / E2

• Operating procedures

B u s b a r

c o m

o n e n t s • Instrument transformer

• Earthing switch- Class E0- Class E1 / E2

• Surge arrester

• Line protection and measurement• Operating procedures• Space requirements

S e c o n d a r y e q u i p m e n t

• Protection relay

• Interlocks and switchgear interlocking

• Measurement, counting, control, monitor-ing, communication devices

• Motorized drive mechanisms

• Voltage detecting system

• Damping resistance forvoltage transformers

• Line parameters• Type of line and load protection• Line system management• Integration in (industrial) processes• Operational procedures

Page 87: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 87/116

Switchgear configuration

© Siemens AG · 11E0 87

H 2 Primary rated values

Selection variable Key influencing variables

Rated voltage Ur • Rated insulation level

- Lightning impulse withstand voltage U p

- Short-duration power-frequencywithstand voltage Ud

Line voltage (operating voltage)• Insulation coordination- Neutral earthing- Underground / overhead cables- "Critical" switching duties- Overvoltage protection- Altitude- Ambient conditions (pollution)

• Rated peak current I p short-time current Ik

short-circuit duration tk • Rated short-circuit making current Ima

short-circuit breaking current Isc

• Characteristic line values

• Loads and power quality

• Line protection, selectivity, tripping times

• Rated normal current Ir (busbars and feeder circuits)

• Load (feeder circuit), power to be distributed (busbar)

• Ambient temperature

• Reserves / availability

H 2.1 Rated voltage Ur

The rated voltage largely depends on the maximum line operating voltage of the network U Nmax at the upper tolerance limit.

Rating rule: Ur ≥ U Nmax

• For switchgear, the next highest standard value above the maximum line operating voltage is setas the rated voltage.

• For further information, see B 1, C 2 and G.

Comments:

a) The rated voltage of the switchgear does not have to match the rated voltage of the:

• Voltage transformers• Surge arresters• HRC fuses

This is because these devices are subject to other, sometimes additional, rating criteria (see sec-tions D and E 3).

Page 88: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 88/116

Switchgear configuration

88 © Siemens AG · 11E0

b) Some switching duties require the switches to have an even higher rated voltage, although thisis rare (see table in B 1). In certain cases, the entire switchgear system must be designed forhigher voltages.

c) At altitudes of at least 1000 m above sea level, a higher rated value applies due to the insulating

properties (see H 2.2).d) A higher rated voltage can be set to fulfil the requirements of a higher insulation level

(see H 2.2).

H 2.2 Rated insulation level

The insulation level comprises the lightning impulse withstand voltage (U p) and the short-duration power-frequency withstand voltage (Ud).

Rating rule: Ur Ud and U p (see table in IEC 60694)• The rated insulation level is assigned to the rated voltage in accordance with the applicable stan-

dard and is, therefore, set at the same time as the rated voltage.

• In medium-voltage systems, the standard insulation levels do not differ with respect to the neu-tral earthing.

36 kV

24 kV

17.5 kV

12 kV

7.2 kV

3.6 kV

L i g h t n

i n g i m p u l s e w i t h s t a n d v o l t a g e [ k V ]

150

100

50

200

0 1000 2000 3000 4000 5000 m

Hight above sea level

Ratedvoltage Ur

0

Lightning impulse withstand voltage in air

for standardised rated voltages (i.e. as a

function of the installation altidude)

Example for diagram above:a lightning impulse withstand voltage of U p = 120 kV is required at an altitude of 1800 m. A system

with a rated voltage of 36 kV achieves this, while a 24 kV system is unsuitable because it can onlymaintain a lightning impulse withstand voltage of 125 kV up to 1000 m.

Page 89: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 89/116

Switchgear configuration

© Siemens AG · 11E0 89

Comments:

a) Operators can specify a higher insulation level in accordance with operational requirements.Reasons for this include high dielectric stresses during standard operation due to connectedoverhead systems, traction supply systems, expected reduction in insulation due to moisture or

pollution.

b) At altitudes of at least 1000 m above sea level, a higher standard rating is set to compensate forthe reduction in insulation level caused by the lower air density. Alternatives to increasing ratedvalues include:

• Surge arresters• Gas-insulated switchgear with shielded, earthed connections (cable plug connectors, insulated

bars)

c) In environments with high levels of pollution, longer creepage paths may be required. This can be achieved with a higher insulation level, although alternative methods are available:

• Avoiding unprotected insulation• Additional insulation for exposed parts (shrinkable tube or similar to act as bridging protection)

• Gas-insulated switchgear with shielded, earthed connections (cable plug connectors, insulated bars)

Note:

In many cases, surge arresters fitted at central points can be used as an alternative to increasing in-sulation levels.

H 2.3 Rated short-circuit currents

Rated short-circuit currents include:- The peak current I p and short-circuit making current Ima - The short-time current Ik and short-circuit breaking current Isc

The peak current and short-time current are withstand capability variables (steady state), while theshort-circuit making and breaking current indicate the switching capacity. The applicable standarddefines a fixed ratio between the impulse and short-time current as a basic design requirement forswitching devices and switchgear: I p/Ik = 2.5 (2.6 at 60 Hz). The same ratio applies to the dynamicvariables Ima/Isc. The values that actually occur in the network, however, have priority.

Rating rule: Devices, system Line variablea) Ima; I p ≥ I p line

b) Isc ; Ik ≥ Ik line

• Both conditions (a) and (b) must be fulfilled.

• For switchgear, the next highest standard value above the actual line variable is set.

Comments:

a) The ratio between I p/Ik = Ima/Isc = 2.5 (2.6 at 60 Hz) can be exceeded in the network, particu-

larly when regenerative loads are connected to the system. The following can indicate a I p/Ik ra-tio that differs from the standard:

Page 90: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 90/116

Switchgear configuration

90 © Siemens AG · 11E0

- Higher number of motors- High output from individual machines- Generators (windparks)

This is rarely the case in standard utility company distribution networks.

b) To minimize voltage drops (voltage quality) caused by large, direct-starting motors, the net-work is designed for high short-circuit current levels. In this case, the magnitude of the peakcurrent must be taken into account.

c) Main and earthing circuits can have different rated short-time currents.

H 2.4 Rated duration of short-circuit tk

This refers to the duration for which switchgear can conduct the rated short-time current in a steadystate.

Rating rule: tk ≥ tk line

• A key factor here is the total short-circuit duration, which is governed by the line protection, theselectivity requirements, the set command times, and the switching delay times.20

• Values of between 3 s and 1 s are normal for switching devices and switchgear.

Comments:

a) In accordance with the applicable standard, the preferred value is tk = 1 s, although 3 s has sinceestablished itself for most switching devices and switchgear; the protection settings do not,

therefore, need to be taken into consideration.With very high short-circuit current values ≥ 40 kA, however, 1 s is still typical.

b) Main and earthing circuits can have different values.

c) For cost reasons, current transformers mostly are designed for times of < 3 s.

"Thermal" conversion between the short-time current and the short-circuit duration.

Warning:

The short-time current and the short-circuit duration can be converted by means of the I²t value:

222121 t I t I ⋅=⋅ . This conversion must only be carried out for smaller short-circuit currents withlonger durations.

The conversion must not be carried out for larger short-time currents with shorter durations

because the breaking capacity of the circuit-breakers cannot be converted by means of I²t.

20 The mechanical delay and internal arcing time of the circuit-breaker; a general value of 100 ms is normally assumed.

Page 91: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 91/116

Switchgear configuration

© Siemens AG · 11E0 91

H 2.5 Rated normal current Ir

A key factor for the rated value is the actual operating current IB, which flows continuously or for along period in the network, and the prevailing ambient temperature.

Rating rule: Ir ≥ IBmax at a fixed ambient temperature• Reserves may have to be taken into account in the standard value to be selected.

• For further information, see B 1, C 4 and G.

Comments:

a) Busbars and feeder circuits can have different rated values as can the individual sections of busbars that have been sub-divided.

b) Reserves for temporary (planned) overload or emergencies must be taken into account.

c) When busbars are rated, the operating principle of couplings with parallel infeeds must also be

taken into account at the planning stage.

H 3 Circuit arrangement

Selection variable Key influencing factors

• Single / double busbars

• Bus section panel

• Bus section panel / transfer panel withswitch or circuit-breaker

• Bus coupler unit (with double busbar)

• Line structure• Line protection, selectivity, tripping times

• Reserves / availability, switchover time• Operating procedures• In-plant generation, emergency supply

• Power quality (unstable loads)

If the switching principle has not yet been defined during network planning or in accordance withoperator specifications, the following general aspects should be taken into account to help reach adecision:

H 3.1 Single busbars

A single busbar is suitable for most supply duties. In systems with a higher number of feeder cir-cuits, the busbars can be sub-divided into sections each with their own infeed. In this way, eachsection can potentially draw a reserve supply from an adjacent section. Single busbar switchgearhas the following benefits:

• It is completely transparent in all switching states.

• As a result, it is easy to use if network failures need to be rectified urgently, which greatly re-duces the risk of switching faults.

Page 92: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 92/116

Switchgear configuration

92 © Siemens AG · 11E0

• If switchovers caused by faults need to be carried out, only the circuit-breakers need to be oper-ated. If the wrong circuit-breaker is operated, this will not affect safety because circuit-breakerscan make or break all load, short-circuit, and earth fault currents several times in sequence.

H 3.2 Double busbars

For technical or contractual reasons, some requirements can only be properly fulfilled by means ofdouble busbars.

• Two (or more) infeeds must always be operated separately (e.g. infeeds from different publicutility companies or the strict separation of in-plant generation and the public network).

• Power quality: a network can contain loads that generate strong load impulses, some of whichare sensitive to voltage fluctuations and others that are not. Depending on the load status, it must

be possible to switch non-sensitive loads to either the stable or the unstable busbar.

• Availability: a network can contain loads that are more important than others and so need to bedistributed across "safe" and "less safe" busbars.

• Due to the limited short-circuit strength of the installed equipment, one network must be dividedinto two sub-networks. Fluctuating current consumption necessitates switchovers to balance theloads.

H 3.3 Design of double busbars

The frequency of switchovers between busbars can affect the choice of preferred design for double busbar switchgear. Some designs, for example, have one or two circuit-breakers in each feeder cir-

cuit – standard design or two single busbars. If frequent switchovers are required, disconnectorsshould not be integrated in the switchover process due to their relatively short operating cycle life-time. A version with two circuit-breakers that switch between the busbars is more suitable.

For details, see A 5.

H 3.4 Operating principle of bus couplings

If the system contains more than one busbar section, the planned operating principle of couplingsgoverns the rated short-circuit current of the switchgear and the rated normal current of the busbars.

Normally open coupling (NO)In "open" mode, the short-circuit currents remains low, which allows systems, switches, cables etc.with low rated values to be used. With a bus section panel and an automatic changeover circuit,instantaneous reserves can still be ensured even if the infeed fails. The short-circuit current is notincreased as a result of this because one infeed line has already been disconnected.

Normally closed coupling (NC)In "closed" mode, the switchgear must be rated for the total fault current of all the interconnectedinfeeds, even if selective mains decoupling has been achieved by means of a bus section panel andquick-disconnect technology. Load differences can balance themselves, although they can cause

interference that affects the entire network.

Page 93: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 93/116

Switchgear configuration

© Siemens AG · 11E0 93

Comments:

a) Provided that certain safety measures are observed, system sections that are normally operatedseparately can be briefly interconnected during switchovers, even if the short-circuit currentexceeds the rated system values (IEC 61936-1).

b) Interlocking and switchgear interlocking: whenever any type of bus section panel or bus cou- pler unit is used for busbars, the extent to which interlocks and switchgear interlocking are re-quired must be determined.

• An interlock system must simulate the planned operating procedures and prevent impermissibleswitching states.

• If disconnectors are directly involved in busbar switchovers or coupling maneuvers, switchgearinterlocking must prevent impermissible switching operations with the disconnector.

H 4 Switching Devices

Selection variable Key influencing variables

• Circuit-breaker

• Switch

• Contactor

• HRC fuse

• Switching duty (load)

• Switching frequency

• Switching capacity (characteristic line values)

• Protection concept, selectivity

The listed influencing variables are equally important when it comes to choosing and rating theswitching devices.

Rating rules: See section A 1 to A 4 Selection of the appropriate deviceB Switching duties in medium voltage networksC Rated values of switching devices

Comments:

In cases where switches or circuit-breakers can be used for a particular switching duty, the switch-ing devices selected can be determined by the protection concept and selectivity conditions. Exam-

ples of this include:• Short-circuit protection requires tripping times that are in accordance with defined characteristics

for which only circuit-breakers are suitable.

• Overload protection cannot be achieved with standard HRC fuses. In the event of overload,switch-fuse combinations do not trip after a defined period. If overload protection is to beachieved by means of a switch or contactor, current transformers and protection relays are re-quired. The switch then must be equipped with a stored-energy spring mechanism.

• Protection functions (overload, load unbalance, etc.) for sensitive loads (motors, transformers)that are in accordance with defined characteristics can only be achieved by means of circuit-

breakers in conjunction with instrument transformers and protection relays.

Page 94: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 94/116

Switchgear configuration

94 © Siemens AG · 11E0

• On the other hand, selectivity criteria may also require that switches without HRC fuses be fittedat certain points in the network.

These requirements are normally already fulfilled by the network design.

H 5 Design and switchgear panel type

Selection variable Key influencing factors

• Circuit-breaker unit• Switch-disconnector unit

- Panels (can be mounted side by side)- Block

• Line parameters ( primary rated values)

• Switching devices

• Operating current, switching capacity

Line protection• Installation conditions

• Transportation and assembly

• No. of switch /circuit-breaker panels

• Operating procedures and operation

• Upgradeability,electrical / mechanical reserves

H 5.1 Basic selection criteria

• The primary rated values must always cover the requirements that result from the line parame-ters.

• Switchgear with the required properties (see H 4) must be available with the required design.

Unless the design is specified otherwise and the primary rated values permit switch-disconnectorunits and circuit-breaker units, the standard characteristics of the two designs may influence the

decision.

Which of the following characteristics apply to the switchgear to be configured?

Page 95: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 95/116

Switchgear configuration

© Siemens AG · 11E0 95

Switch-disconnector unit Circuit-breaker unit

• Normal current: up to 630 A • Normal current: up to 4000 A

• Short-circuit current strength:

up to 25 kArms / 63 kA peak

• Short-circuit current strength:

up to 63 kArms / 160 kA peak • Switching devices

- Mainly switches- Some circuit-breakers

• Switching devices- Mainly circuit-breakers- Some switches- Contactors

• No or low short-circuit breakingcapacity required

• High short-circuit breaking capacity required

• HRC fuses as short-circuit protection • Instrument transformers + protection relays

• Small switching frequency • High switching frequency

• Low number of items of secondaryequipment possible

• Complex secondary equipment possible

• Sometimes suitable for harsh climates • Generally requires a protected environment(for control, protection, and measurementelectronics)

H 5.2 Panel and block design

The list below highlights some of the differences between panel and block design, which could bekey decision-making criteria. Which of the following characteristics must the switchgear fulfil?

Panel design Block design

• Flexible applications • Special applications

• Panel type and switch can be freely se-lected- Switch with/without HRC fuse- Circuit-breaker- Transfer and measurement panel

• Standardized versions

• Number of switchgear panels can be freelyselected

• Number of switching functions depends oncontainer size, containers can be arrangedside by side

• All equipment variants • Customized equipment

• Range of functions can be extended • Standard range of functions

• Can be extended • Can only be extended after prior planning

Page 96: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 96/116

Switchgear configuration

96 © Siemens AG · 11E0

H 5.3 Installation conditions, transportation and assembly

Some 70% of new systems are replacements for "old" switchgear in existing buildings. Forthis reason, the dimensions are a key decision-making criterion.

In addition to space for the switchgear in the room, adequate space must be available for operating

and assembly activities as well as escape routes. Sufficient distance from other installations mustalso be ensured. Alongside the installation conditions specified by the manufacturer, legal specifica-tions must also be observed. Those regulations can vary from region to region.

• Wall clearances and minimum dimensions for free areas for operating and assembly activities(manufacturer)

• Minimum width of operating and assembly aisles

• Minimum width and maximum permissible length of escape routes

• Direction of pressure release (internal fault)

The following must be taken into account when switchgear is transported and installed:• Dimensions of the (door) openings in the switchgear room and access paths, including lifting

equipment (elevators).

• Size, weight, and packaging of the transportation unit(s).

• The device must be protected against climatic conditions if it is in temporary storage over a long period.

H 5.4 Additional aspects

There are no fixed rules for many of the selection criteria; decisions are usually made on the basisof the operator's specifications.

• A very "soft" selection factor is the ratio of switch panels to circuit-breaker panels. The dominantswitch type can sway the decision. On the other hand, circuit-breaker units are available that aremade up almost exclusively of switches and vice versa.

• Operating procedures defined by the operator are closely related to the secondary equipment.Decision-making criteria here include:- Actuating equipment (switching levers, instrument displays, locks)- Interlocks

- Integration in other (production) processes in the company

• The devices required for protection, control (automation, communication), measurement, andcounting functions govern the scope of the secondary equipment. The design must ensure thatthis equipment can be installed properly (e.g. instrument transformer in the primary section, de-vices in the low-voltage compartment). If remote control is used, the design concept must ac-commodate this by providing motorized drive mechanisms for the switchgear, for example. Thehigher the design category, the greater the design scope.

Page 97: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 97/116

Switchgear configuration

© Siemens AG · 11E0 97

H 6 Electrical and mechanical reserves

Reserves are provided to handle expected or planned requirements of the plant operator. A designequipped with mechanical and electrical reserves is "overdimensioned" when it is first put into op-eration, although it can be extended at a later stage. Which options is the design to offer?

• Panel extension• Space for installing replacement instrument transformers or additional cores

• Options for installing secondary devices in the low-voltage compartment

• Options for retrofitting control or automation devices

• Options for retrofitting motorized drive mechanisms

• Planned increase of the short-circuit current

• Increase of operating currents in the feeder circuits and busbars

H 7 Insulation medium

Selection variable Key influencing factors

• Air insulation AIS*

• Gas insulation 21 GIS*

* AIS: "air insulated switchgear"GIS: "gas insulated switchgear"

• Ambient room conditions: temperature change, humid-ity, pollution, salt, corrosive gases

• Type of operating site• Installation location (space requirements)• Fire protection requirements (fire load)

• Altitude• Switching frequency and switching device lifetime

H 7.1 Comparative aspects

The table below compares the main features of systems with the two types of insulation. Which ofthese features is the switchgear to be configured to have?

Feature AIS with air / solid insulation GIS with SF6 insulation22

Enclosure Metal enclosure Metal enclosure, the primary section ishermetically sealed

Climate • Suitable for normal conditions

• Increased degree of protection (IP)for harsh ambient conditions ormeasures taken in the service room

• Suitable for extreme conditions

• In extreme conditions, only thesecondary equipment needs protec-tion.

21

The standards use the neutral term "fluid" (normally SF6 gas).22 Or more precisely: "gas / solid insulation". The solid insulation is not mentioned because it is protected by the gas inthe system container and, therefore, is not subject to the usual stresses of unprotected insulation.

Page 98: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 98/116

Switchgear configuration

98 © Siemens AG · 11E0

Feature AIS with air / solid insulation GIS with SF6 insulation22

• Humidity and condensation in con- junction with pollution layers can re-duce insulation Remedy: heater in

switchgear panel

• Inert atmosphere minimizes exter-nal influences on the primary sec-tion; in humid conditions, heater in

low-voltage compartment onlyMaintenance Maintenance required Primary section does not need to be

maintained

Accessibility Easy access to all components Access to components in primary sec-tion not required/not possible

Switchingfrequency

Highly suitable for switching dutieswith high number of make-break opera-tions Frequent access for mainte-nance

Not suitable for switching duties withhigh number of make-break operations(exception: switchgear panels withcontactor)

Dimensions Larger dimensions Compact design, which allows greaterflexibility during installation

Installation alti-tude > 1000 m

May require a higher rated voltage (in-sulation level) or use of surge arresters

No measures required, even if theconnections are fully encapsulated(cable plug connectors)

Gas insulation has many benefits, although nearly all requirements can also be fulfilled with airinsulation. In addition, certain areas of application are better suited to air-insulated systems.

H 8 Isolating distance

The type isolating distance can only be selected for air-insulated systems.

Selection variable Key influencing factors

• Withdrawable unit / truck• Disconnector (built in)

• Switching frequency

• Component lifetime

• Operational requirements

(access to cable terminals)

If loads with a high switching frequency are connected to a switchgear system, a switch in a with-drawable unit (truck) is preferred because this enables it to be accessed quickly and easily for main-tenance purposes or if it needs to be replaced at the end of its service life.

Even if the cable terminals for the switchgear panel needs to be readily accessible (e.g. voltage testson cables in public utility companies], a withdrawable unit can still be a better solution than a fixedunit because more room is available for working on the switchgear panel once the unit has beenremoved. How easily the cable can be accessed depends on the type of partition.

For switchgear with double busbars, see also H 3.3.

Page 99: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 99/116

Switchgear configuration

© Siemens AG · 11E0 99

H 9 Enclosure

Selection variable Key influencing factors

• Degree of protection (IP)

• Internal fault qualification- A or B- F / L / R- Test current and duration

• Pressure absorber

• Pressure relief duct

• Ambient conditions• Personnel protection• Type of operating site• Building

H 9.1 Degree of protection• A minimum degree of protection of IP 2X is required. Degrees of protection IP 3XD or IP 4X

are standard. These degrees of protection are identical with respect to shock-hazard protection but differ with respect to protection against ingress of solid foreign bodies.

• Requirements regarding ventilation/cooling and protection against ingress of solid foreign bodiesare contrarily!

• Water protection is not specified for systems operating under normal conditions inside buildings.

H 9.2 Internal arc classification

This qualification specifies the type of accessibility of the operating site and the parts of the systemthat are qualified with respect to internal faults (e.g. IAC A FLR 25 kA 1s).

A applies to switchgear in closed electrical operating areas, accessible only for authorizedand qualified personnel

B applies to switchgear at publicly accessible locations (higher severity of test)

F / L / R designate the accessible sides of the switchgear that have been tested for resistance tointernal faults (front, lateral, rear).

• Medium-voltage switchgear is generally tested for accessibility type A. Only complete stations(transformer/load-center substations) are tested for type B. Standard systems do not need to betested according to type B because they are always integrated in additional (station) housing inareas that can be accessed by the public.

Qualification F / L / R must be in accordance with the type of installation in the service room."FL" is sufficient for a wall-mounted installation, while "FLR" is required for a free-standing in-stallation (all sides can be accessed during operation).

Page 100: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 100/116

Switchgear configuration

100 © Siemens AG · 11E0

H 9.3 Pressure absorbers and pressure relief ducts

With certain switchgear designs, pressure absorbers are available for low short-circuit currents(< 20 kA). If an internal fault occurs, they reduce the pressure in the service room.

• Using pressure absorbers can help protect the building fabric in older buildings.

A pressure relief duct can channel the internal fault gases out of the switchgear room, thereby pro-tecting the service room from the pressure wave and smoke.

Notes:

The service room must always be taken into account when measures to provide protection againstinternal faults are elaborated:

• Calculation of the dynamic pressure in the service room, which the architect/structural engineercan use to determine the stress on the building fabric.

• Pressure relief outlets with a sufficiently large cross-section or pressure relief duct.

Further requirements are defined in IEC 61936-1. Other regional legal building regulations alsoapply.

H 10 Compartments

Selection variable Key influencing factors

• Loss of service continuity category(compartmentalization)

- LSC 1- LSC 2A- LSC 2B

• Access control by means of:- Interlock- Work instruction + lock- Tool

• Non-accessible compartment

• Partition class- PM (metal)- PI (plastic)

• Operating procedures- Operation, work activities

- Maintenance requirements• Servicing / maintenance

(component lifetime)

• Operator regulations

• Personnel training

• Shock-hazard protection during work ac-tivities

• Switchgear space requirements

H 10.1 General selection criteria

The decision regarding the type of partition depends on the requirements of the operator.

• Which recurring operating procedures require access to compartments?(e.g. changing the HRC fuse, reading short-circuit indicators, making adjustments)

• What servicing and maintenance work intervals are planned?

• Which system components must remain live even while servicing / maintenance work is beingcarried out?

Page 101: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 101/116

Switchgear configuration

© Siemens AG · 11E0 101

• Is shock-hazard protection during servicing / maintenance work to be achieved by means of me-tallic / non-metallic partitions?

• What level of training is required for personnel? Is shock-hazard protection to be permanently orrealized automatically or manually?

• How much space is available for the system?

H 10.2 Loss of service continuity category

LSC 1 This category, which offers the least availability and does not include partitions betweenthe busbars or adjacent panels, is rarely available now.

LSC 2A Isolating distance and partition between busbar and switch or circuit-breaker / cable ter-minal.

LSC 2B Isolating distance and partition between busbar and switch or circuit-breaker as well as between switch or circuit-breaker and cable terminal (known as "metal clad").

Selection aspects

LSC 2A This option is recommended if quick and easy access to the cable terminal or transform-ers is required (on a regular basis too).

The systems are more compact than those in category LSC 2B.

• When the switch is accessed, the cable must be disconnected from the power supply(supply cable or reverse voltage from the load).

• A door interlock with the earthing switch is recommended.

Due to the potential hazards mentioned, using systems with loss of service category LSC2A makes more stringent demands regarding the training that staff working on the systemrequire.

LSC 2B Systems in this category offer the highest level of "in-built" shock-hazard protection, al-though this means that the components can be more difficult to access.

The systems are larger than those in category LSC 2A.

In conjunction with interlock-controlled access, these systems are also suitable for per-sonnel who do not work with high-voltage systems on a regular basis.

Comments:The ‘loss of service continuity categories’:

• Do not differentiate between permanently installed and temporary partitions (covers, removableshutters etc. that are present only temporarily);

• Are intended for systems with accessible compartments and are, therefore, applicable to gas-insulated systems under certain conditions only;

• Do not describe the partition for providing protection against an internal fault in an adjacentroom, but only the shock-hazard protection against live, adjacent parts (5. Safety Rules for Car-rying Out Work).

Beyond technical characteristics, cultural and regional aspects can influence the preferencefor LSC 2A or 2B.

Page 102: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 102/116

Switchgear configuration

102 © Siemens AG · 11E0

H 10.3 Access control

While the compartment for the busbar in nearly all system designs can only be opened with a spe-cial tool (“tool-based accessible compartment”), the switch and cable compartment can be openedin one of two ways:

• Interlock-controlled access With this method, shock-hazard protection is ensured automatically because the door / flap to thecompartment can only be opened when all the primary circuit components inside have beenshort-circuited and earthed.

• Process-based access With this method, the manufacturer must equip the compartments with locking devices. The op-erator is responsible for ensuring that access to the compartment is regulated by means of a workinstruction. If the instruction is not observed, personnel risk coming into contact with live parts!

Provided a choice exists, operators must decide according to their own requirements.

Interlock-controlled access is recommended due to the high level of inherent safety. Again, cultural and regional preferences can influence the choice of access control.

H 11 Feeder circuit components

Selection variable Key influencing factors

• Cable connection

- Sealing end: standard / plug- Number of cables- Cable cross-sections

• Surge arrester

• Operating and short-circuit current

• Switching duty• Underground / overhead cables

• Altitude

• Voltage transformer- Earth fault winding (if required)

• Current transformer- Core number and data

• Core-balance transformer

(cable-type current transformer)

• Line protection

• Control

• Measurement, metering

• Neutral-point earthing

• Earthing switch- Class E0- Class E1, E2

• Operating procedures

At the configuration stage, it is important to remember that many different components need to beinstalled in the limited space available on the switchgear panel.

Comments:

a) Cable connection: the operating and short-circuit current determine the minimum number andcross-section of the cables to be connected. In many cases, operators have standardized thecross-sections used in their companies.

Page 103: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 103/116

Switchgear configuration

© Siemens AG · 11E0 103

b) Instrument transformers: voltage transformers in networks with an insulated neutral should beequipped with a earth fault winding (da-dn winding, formerly "e-n winding"). Damping resis-tors are connected to the winding (see H 13 and I 1).

The design of the instrument transformers is not covered here.

c) Earthing switches: class E0 devices are standard earthing switches with no short-circuit makingcapacity. Class E1 or E2 switches can switch two times or five times onto a voltage that is pre-sent.

Earthing switches E1 / E2 are safe even if switching faults occur.

H 12 Busbar / metering panel components

Selection variable Key influencing factors

• Instrument transformer

• Earthing switch- Class E0- Class E1, E2

• Surge arrester

• Line protection and measurement

• Operating procedures

The aspects that were taken into account for the feeder circuit components also apply here (see sec-tion H 11).

Components that have a direct electrical connection with the busbar can be installed in meter-ing panels along with current and voltage transformers.

The following alternatives are available that do away with the need for a metering panel:

a) With certain system designs, earthing switches for the busbar can also be housed in incomingfeeder units, bus section panels, or bus coupler panels.

b) With certain system designs, instrument transformers can be installed directly in the busbarcompartment.

c) Surge arresters can also be installed in switchgear panels that are always connected to the bus- bar, generally in the incoming feeder unit. If a busbar has more than one connected infeed, each

incoming feeder unit has a set of arresters. This solution can be more cost effective than instal-lation on the busbar.

Page 104: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 104/116

Switchgear configuration

104 © Siemens AG · 11E0

H 13 Secondary Equipment

Selection variable Key influencing factors

• Protection relay

• Interlocks and switchgear interlocking

• Measurement, metering, control, monitoring,communication devices

• Motorized drive mechanisms

• Voltage detection system

• Damping resistors for voltage transformers

Line parameters• Type of line and load protection• Line system management• Integration in (industrial) processes• Operational procedures

Some of the equipment is linked with the switchgear features mentioned previously. The scope ofsecondary equipment is not subject to special technical rules, but is instead based on the agreementsreached between the manufacturer and operator.

Page 105: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 105/116

Standards

© Siemens AG · 11E0 105

I APPENDIX

I 1 Damping relaxation oscillations

I 1.1 Relaxation oscillations (ferroresonance)

Relaxation oscillations can occur in applications with single-pole, inductive voltage transformers incertain network configurations, such as short underground or overhead line distances (low capaci-tance between conductor and earth):

Neutral-point earthing Risk of relaxation oscillations

Effectively (solidly) earthed None

Resistance earthed None

Compensated (Petersen coil) Slight

Insulated High

Switching operations, earth faults, or other non-linear occurrences in the network can cause relaxa-tion oscillations that are associated with high overvoltages and can subject the equipment to ex-treme dielectric and thermal stress; voltage transformers are especially at risk. The oscillations satu-rate the core causing considerable iron loss (sometimes indicated by a loud drone). As a result,thermal overload and flashovers can destroy the transformers and, in turn, damage the switchgear.

a

n

da

dn

a

n

da

dn

a

n

da

dn max.110 V

RD

I∆

typical values I∆: 4 / 6 / 8 A

L 1L 2L 3

Relaxation oscillations can be damped by installing resistors on the earth fault windings connectedto the open triangle ("e-n winding"). The choice of resistor depends on the thermal limit rating (orrated long-time current) of the da-dn winding in the voltage transformer. Since a earth fault alwaysaffects the entire galvanically-connected network, specific measures must be taken to protect theentire network against earth faults (this includes damping resistors). In many cases, however, gen-eral measures can be sufficient.

Page 106: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 106/116

Appendix

106 © Siemens AG · 11E0

I 1.2 Standard values for damping resistors

Standard values for the resistors are provided in the table below. The choice of resistor depends onthe thermal limiting output (or rated long duration current) of the da-dn winding in the voltagetransformer.

da-dn winding of voltage transformer

Thermal limiting output Rated long duration current 23

Damping resistance

75 W 4 A 25 ohms / 500 W

100 W 6 A 25 ohms / 500 W

150 W 8 A 12.5 ohms 24 / 1 kW

If these standard values cannot be used, other values can be calculated.

I 1.3 Calculating the damping resistance

The damping resistance can be determined from the specifications on the rating plate of the voltagetransformer.

Specifications: Rated thermal limiting out put Ssr for 8 hoursSecondary rated voltage Usr of the da-dn winding (formerly "e-n winding")

Required: Lowest damping resistance value R D Power loss (load-carrying capacity) of the damping resistor

The resistor must be rated in such a way that neither it nor the voltage transformer are overloaded,even if an earth fault occurs.

I 1.4 Formula, symbols and indices

U Voltage D DampingS Apparent power r Rated valueP Active power s SecondaryR Resistance V Power loss

I 1.5 Standard, uninterrupted line operation

• Voltage at the output of a single da-dn winding: U2 = Usr (rated voltage)

Example: secondary rated voltage V U r 3

1002 =

• Voltage on the open triangle: U∆ = 0 V (due to symmetrical, uninterrupted operation)

23

The term „rated long duration current“is still in frequent use, although current standards use the term „rated thermallimiting output “. Both terms are synonymous, however.24 Two 25 ohm resistors (parallel)

Page 107: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 107/116

Standards

© Siemens AG · 11E0 107

Line voltage Voltage on da-dn winding

Uninterrupted

operation

L 1

L 2 L3

Uda-dn = 0 V

U ‘ L 2

U ‘ L 3

U ‘ L 1 1 0

0 / 3 V

Operation with

earth fault in L1

L 1

L 2 L3

U e L 2 U

e L 3

U ‘ e L 2

U ‘ e L 3

1, 1 ⋅ √ 3

⋅ ( 1 0 0 / 3

) V

da dn110 V

I 1.6 Operation with earth fault

• Values at the output of a single da-dn winding:

[F1] Voltage sr sr se U U U ⋅=⋅⋅= 9.131.1

[F2] Currentsr

sr

sr seU

S I I ⋅=⋅= 9.19.1

[F3] Apparent power sr sesese S I U S ⋅=⋅= 29.1

Factors:

1.1 Voltage increase at faultlocation

√3 Earth fault factor

1,9 Rated voltage factor 25 1.9 = 1.1 x √3

F2: with a constant load resistance, the 1.9 x voltage on the winding results in 1.9 x current if aearth fault occurs.

The rated thermal limiting output S2r refers to uninterrupted operation. It is a rated value, although itdoes not reflect the actual load-carrying capacity of the winding. In practice, the earth fault windingcan handle 3.6 x the rated thermal limiting output over a period of 8 hours.

• Values at the terminals for the da-dn windings connected to the "open" triangle:

[F4] Voltage ( )sr sr

U U U ⋅=⋅⋅⋅=∆ 3.331.13 Typical value for Usr : V 3

100

[F5] Apparent power sr

sr

sr

sr S U

S U S ⋅=⋅⋅⋅=∆ 3.69.13.3

[F6] Current se I I =∆ Maximum permissible value

25 Rated voltage factor: multiple of the primary rated voltage for which a voltage transformer must fulfill the thermalrequirements for a defined stress interval.

Page 108: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 108/116

Appendix

108 © Siemens AG · 11E0

I 1.7 Damping resistance

The resistance value can be calculated using [F4] and [F5]:

[F7] Resistancesr

sr D

S

U

S

U R

22

3 ⋅=≥∆

[F8] Power loss( )

D

sr

V R

U P

23.3 ⋅≥

R D and PV are the mini-mum permissible values

I 1.8 Sample calculations

Specifications on the rating plate of a voltage transformer:

- Rated secondary voltage of the earth fault winding Usr 100 V / 3

- Rated thermal limiting output Ssr 100 VA(same as the former "rated long-time current" specification) 6 A )

=> Damping resistance R D (acc. to F7) ≥ 19.2 Ω Load-carrying capacity PV (acc. to F8) ≥ 630 W |19.2 Ω

A 25 ohm resistor is used as standard; load-carrying capacity 500 W or higher.

Sources for Appendix I 1

- Documents from Peter Dorsch and Dr. Kerstin Kunde- IEC 60044-2 / VDE 0414-2

Page 109: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 109/116

Standards

© Siemens AG · 11E0 109

I 2 RC-circuitry for protection of MV equipment

Some, but rare, switching duties require RC circuitry for surge protection in order to protect theequipment against the effects of high-frequency switching transients. Due to the characteristic prop-erties of

• compensating coils (see section B 7) and

• furnace transformers (see section B 10)

there is the possibility that switching operations may initiate internal resonance oscillations. Withinthe coil or the transformer these resonances can lead to dielectric overstress, which cannot be sup-

pressed by surge arresters at the terminals. Hence resonant oscillations must be avoided from thefirst.

It is always necessary to match the RC circuitry to the individual system configuration. The fol-lowing exemplification may be used in order to estimate budget prices; by no means it can be usedas a general design.

RC-circuits form a bypass for high frequency currents (thus also voltages) in that the transients arediverted to earth instead of reaching the equipment to be protected. The RC installation at the loadis most economical since the capacitance of the surge capacitor – the determining size of the costs –then is smallest. Under some special circumstances an additional protection circuit is required at the

busbar.

Load

Cable or bar

Infeeding side(Busbar)

CRC

R RC

ZK

C N R N

CK

CRC = Capacitance of the RC-circuitryR RC = Value of the resistor of the RC-circuitryCK = Line to earth capacitance of the cable (or bar)ZK = Surge impedance of the cable (or bar)

C N = Capacitance of the capacitor on the feeding sideR N = Value of the resistor on the feeding side

RC-circuits at the load

With longer cables (> 50 m), the RC-circuits are installed directly at the load terminals.

- CRC ≥ 3 ⋅ CK (yet no distinct travelling wave effects occur)

- R RC = 1 … 2 ⋅ ZK

Switching transients which can cause travelling waves are not prevented in such manner, but theRC-circuits damp the travelling wave and prevent the refraction ("reflection") at the load-side cableterminals, where the RC-circuits divert the HF transients to earth (bypass).

RC-circuits at the load side of the circuit-breaker

Page 110: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 110/116

Appendix

110 © Siemens AG · 11E0

If CK is small ( < 50 m cable), no distinct travelling wave effects occur – depending on the effectiveinductance (length of busbar, c.t. cores) between supply and load side. The RC-circuits are installedclose to the circuit-breaker.

- CRC ≥ 6 ⋅ CK

- R RC > ZK The RC-circuitry archives an aperiodic damping of the HF equalising currents which occur duringswitching off in case of a re-ignition, thus only one re-ignition occurs. In this manner voltage esca-lation by repetitive re-ignitions is prevented.

RC-circuits at the supply side (system side)

With low system capacitance, i.e. if only few cables or cables of short length are connected to the busbar and thus the phase-to-earth capacitance is small, the RC-circuits replicate additional cables.

- C increases the system capacitance, forms a bypass for HF transients (since XC ∼ 1/f) to earth; so

travelling waves become spacially isolated at the system side. R replicates the surge impedance of a cable and damps the currents through the RC-bypass.

I 3 Overvoltage factors (Definition)

Overvoltages usually are indicated as a factor which represents as a multiple of the operating volt-age line-to-earth as reference value.

U [p.u.]

1

-1

t

ÛLEUunipolar U bipolar

Unipolar overvoltage factor k

m

unipolar

U

U k

=

3

2

Bipolar overvoltage factor k’

m

bipolar

U

U k

=

3

2'

Um Maximum operating (network) voltage (line-line)ULE Operating (network) voltage line-earth Um/√3

Page 111: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 111/116

Standards

© Siemens AG · 11E0 111

I 4 Abbreviations, Symbols and Formula VariablesSymbol Variable Device / Network* Unit

U Voltage, general kV

Ur Rated voltage Device kV

U N Network voltage Network kVUm Maximum voltage permissible for a device Device kV

UL Rated (reseal) voltage (gapped arrester) kV

Uc Continuous operating voltage (MO arrester) kV

Ur Rated voltage (MO arrester) kV

UC Capacitor voltage kV

U p Basic Insulation Level Device kV

Ud Power-frequency withstand voltage kV

I Current, general kA

Ir Rated current AIan Starting current Device A

Ith Short time withstand current Device kA

Ik Sustained symmetrical short circuit current Network kA

I"k Initial peak symmetrical short circuit current Network kA

I p Peak current peak value (first half wave) Network kA

Ima Rated short circuit making current (peak value) Device kA

Ie / Is Closing current (peak value) Device kA

I1 Rated mainly active load-breaking current Gerät A

I2a; I2b Rated closed-loop breaking current Gerät AI3 Rated no-load transformer breaking current Gerät A

I4a Rated cable-charging breaking current Gerät A

I4b Rated line-charging breaking current Gerät A

I6a Rated earth fault breaking current Gerät A

Itransfer Transfer current Netz A

Ir-transfer Rated transfer current Gerät A

Imin Minimum operating (clearance) current of HRC fuse Gerät A

ID Let through (cut off) current of HRC fuse kA

S Apparent power, general kVA; MVAQC Capacitor reactive power kVar; MVar

SMot Motor apparent power kVA; MVA

τ Time constant, general ms

tL Arcing time (HRC fuse) s

tm Melting (pre-arcing) time (HRC fuse) s

tth Short circuit duration Device s

T0 Opening time Device s

∗ Device / Network indicates whether the symbol or variable relates to network or device characteristics. Since the

various standards sometimes use different symbols, repetition is also sometimes unavoidable.

Page 112: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 112/116

Appendix

112 © Siemens AG · 11E0

I 5 Diagram Symbols

Transformer Current transducer (c.t.)

Circuit-breaker Voltage transducer (v.t.)

Disconnector (isolator) Surge arrester / limiter

Contactor Spark gap

Switch Fuse-link

Switch-disconnector Capacitor

Earthing switch Resistor

Make proof earthing switch Reactance

Compensation coil (shunt reactor),short-circuit limiting reactor

Page 113: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 113/116

Standards

© Siemens AG · 11E0 113

J RELEVANT STANDARDS AND REGULATIONS

The following list names the most important standards or specifications; it is structured according to

• Statutory regulations for medium-voltage equipment

• Generic standards for switching devices and switchgear• Product standards for switching devices

• Product standards for switchgear and accessories

Generally, the IEC standards concur with the relevant national standards. A standard uses the sym- bols customary in the respective technical field. It is consequently possible for the same physicalvariable to be differently designated.

J 1 Statutory regulations for medium-voltage equipment

International Germany Title ( English / German )

BGV A3 Unfallverhütungsvorschrift – Elektrische Anlagen und Betriebsmittel

BGV B11 Unfallverhütungsvorschrift – Elektromagnetische Felder

BGV A8 Unfallverhütungsvorschrift – Sicherheits- und Gesundheitsschutzkenn-zeichnung am Arbeitsplatz

1999/519/EC 26

26. BImSchV

Council recommendation of 12 July 1999 on the limitation of exposureof the general public to electromagnetic fields (0 Hz to 300 GHz)

EMVU-Verordnung – 26. Verordnung zur Durchführung des Bundes-Immissionsschutzgesetzes (Verordnung über elektromagnetische Fel-der - 26. BlmSchV) Vom 16. Dezember 1996

89/336/EEC 27

EMVG

Council directive 89/336/EEC – EMC Directive of 3 May 1989 on theapproximation of the laws of the Member States relating to electro-magnetic compatibility; amended by 92/31/EEC; 93/68/EEC

Gesetz über die elektromagnetische Verträglichkeit von GerätenVom 18. September 1998

BGI 766 Instandsetzungsarbeiten an elektrischen Anlagen auf Brandstellen

BGI 559 Handlungsanleitung zur Anpassung von Hochspannungsanlagen

- DIN VDE 0101 (05/89) - Note on BGV28: Accident prevention regulations issued by the statutory industrial accident insur-

ance institutions (Berufsgenossenschaften: BGs) are legally binding, according tothe 7th code of social law, §15.

Note on BGI29: BG information describes typical solutions for applying BG regulations. UnlikeUVV rulings, BG information does not have to be obligatorily applied.

26 An EU Council Recommendation need not obligatorily be implemented in applicable law in EU member states. InGermany this has taken place in the form of 26. BImSchV.

27 An EU Directive must be implemented in national law in EU member states. However, only respective national legis-

lation is legally binding.28 BGV = BG regulation29 BGI = BG information

Page 114: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 114/116

Standards

114 © Siemens AG · 11E0

J 2 Generic standards for switching devices and switchgear

=> Listed according to the number of the international standard

International

standard

German

standard

Title ( English / German )

EN 50110

VDE 0105-100 30

Operation of electrical installations

Betrieb von elektrischen Anlagen

IEC 60071

VDE 0111

Insulation coordination

Isolationskoordination

IEC 60376

VDE 0373-1

Specification and acceptance of new sulphur hexafluoride

Bestimmung für neues Schwefelhexafluorid SF6

IEC 60480

VDE 0373-2

Guidelines for the checking and treatment of sulfur hexafluoride (SF6)taken from electrical equipment and specification for its re-use

Prüfung von aus elektrischen Geräten entnommenem SF6

IEC 60529

VDE 0470-1

Degrees of protection provided by enclosures (IP Code)

Schutzarten durch Gehäuse (IP-Code)

IEC 60694

VDE 0670-1000

Common specification high-voltage switchgear and controlgear stan-dards

Gemeinsame Bestimmungen für Hochspannungs-Schaltgeräte-Normen

IEC 60865

VDE 0103

Short-circuit currents - Calculation of effects

Kurzschlußströme – Berechnung der WirkungIEC 60909

VDE 0102

Short-circuit current calculation in three-phase a.c. systems

Kurzschlußströme in Drehstromnetzen

IEC 61634 High-voltage switchgear and controlgear - Use and handling of sulphurhexafluoride (SF6) in high-voltage switchgear and controlgear

IEC 61936-1

VDE 0101 31

Power installations exceeding 1 kV ac

Starkstromanlagen mit Nennwechselspannungen über 1 kV

30 Part 1 of EN 50110 contains minimum requirements applicable in all CENELEC countries. The respective currently

valid safety requirements for the individual countries are described in national addenda. In Germany, the details ofParts 1 and 100 (VDE 0105-1 and -100) are significant.

31 The January 2000 edition also contains specifications for earthing systems (formerly VDE 0141)

Page 115: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 115/116

Standards

© Siemens AG · 11E0 115

J 3 Product standards for switching devices

=> Listed according to the number of the international standard

International

standard

German

standard

Title ( English / German )

IEC 60044

VDE 0414

Instrument transformers

Meßwandler

IEC 60099

VDE 0675

Surge arresters

Überspannungsableiter

IEC 60265-1

VDE 0670-301

High-voltage switches - Part 1: Switches for rated voltages above 1 kVand less than 52 kV

Hochspannungs-Lastschalter – Teil 1: Hochspannungs-Lastschalter für

Bemessungsspannungen über 1 kV und unter 52 kVIEC 60282

VDE 0670-4

High-voltage fuses - Current-limiting fuses

Hochspannungssicherungen –Strombegrenzende Sicherungen

IEC 62271-105

VDE 0671-105

High-voltage alternating current switch-fuse combinations

Hochspannungs-Lastschalter-Sicherungs-Kombinationen

IEC 60470

VDE 0670-501

High-voltage alternating current contactors and contactor-based motor-starters

Hochspannungs-Wechselstrom-Schütze und -Motorstarter mit Schüt-zen

IEC 60644

VDE 0670-401

Specification for high-voltage fuse-links for motor circuit applications

Anforderungen an Hochspannungs-Sicherungseinsätze für Motor-stromkreise

IEC 60787

VDE 0670-402

Application guide for the selection of fuse-links of high-voltage fusesfor transformer circuit applications

Wechselstromschaltgeräte für Spannungen über 1 kV – Auswahl vonstrombegrenzenden Sicherungseinsätzen für Transformatorstromkreise

IEC 62271-110

VDE 0671-110

HV alternating current circuit-breakers - Inductive load switching

HS-Schaltgeräte und -Schaltanlagen – Schalten induktiver Lasten

IEC 62271-100

VDE 0671-100

High-voltage switchgear and controlgear - High-voltage alternating-current circuit-breakers

Hochspannungs-Wechselstrom-Leistungsschalter

IEC 62271-102

VDE 0671-102

High-voltage switchgear and controlgear - High-voltage alternatingcurrent disconnectors and earthing switches

Wechselstromtrennschalter und Erdungsschalter

Page 116: Switchgear Application Guide 11E0.pdf

8/21/2019 Switchgear Application Guide 11E0.pdf

http://slidepdf.com/reader/full/switchgear-application-guide-11e0pdf 116/116

Standards

J 4 Product standards for switchgear and accessories

=> Listed according to the number of the international standard

International

standard

German

standard

Title ( English / German )

IEC 62271-200

VDE 0671-200

A.C. metal-enclosed switchgear and controlgear for rated voltagesabove 1 kV and up to and including 52 kV

Metallgekapselte Wechselstrom-Schaltanlagen für Bemessungsspan-nungen über 1 kV bis einschließlich 52 kV

IEC 62271-201

(VDE 0670-7) 32

A.C. insulation-enclosed switchgear and controlgear for rated voltagesabove 1kV and up to and including 38 kV

Isolierstoffgekapselte Hochspannungsschalt- und -steuergeräte für Nennspannungen über 1 kV bis einschließlich 38 kV

IEC 61219

VDE 0683-200

Live working – Earthing or earthing and short-circuiting equipmentusing lances as a short-circuiting device – Lance earthing

Arbeiten unter Spannung – Erdungs- oder Erdungs- und Kurzsch-ließvorrichtung mit Stäben als kurzschließendes Gerät – Staberdung

IEC 61230

VDE 0683-100

Live working – Portable equipment for earthing or earthing and short-circuiting

Arbeiten unter Spannung – Ortsveränderliche Geräte zum Erden oderErden und Kurzschließen

IEC 61243-1

VDE 0682-411

Life working – Voltage detectors

Capacitive type to be used for voltages exceeding 1 kV a.cArbeiten unter Spannung – SpannungsprüferKapazitive Ausführung für Wechselspannungen über 1 kV

IEC 61243-5

VDE 0682-415

Live working - Voltage detectorsVoltage detecting systems (VDS)

Arbeiten unter Spannung – SpannungsprüferSpannungsprüfsysteme (VDS)