svc (1)
TRANSCRIPT
-
8/13/2019 SVC (1)
1/27
Methods of voltage control
Control of voltage levels is accomplished by controlling the production, observationand flow of reactive power at all level in the system.
Automatic voltage regulators (ACR) control field excitation to maintain a scheduledvoltage level at the terminals of generators. Additional means are usually required tocontrolled voltage throughout the system.
The devices used for this purpose may be classified as Sources or sinks of reactive power, such as shunt capacitor, shunt reactors,
synchronous condensers and static var compensator (SVC).
Line reactance compensators, such as series capacitor. Regulating transformer such as step changing transformer and boosters.
Shunt capacitor compensation:-
Without compensation:
AC
VR
QR
VS
QS
T.LQ1=demand of the load
Q2=supply to load
Figure 9.1
Net reactive power at the bus bar. Reactive power demand by load. Reactive power supply to load.
Voltage at receiving end
Case 1:- If In this case
Case 2:- If In this case
Now to balance;
-
8/13/2019 SVC (1)
2/27
Shunt capacitor bank is connected, which supply
With shunt capacitor []:
C.B
QCQ2
Q1
Load
P1
VR=VS
Figure 9.2
[ ]
Where;
Active power input to the load
Where;
Power factor angle before compensation.
Power factor angle after compensation. Reactive power supply by capacitor bank.Shunt reactor compensation:
-
8/13/2019 SVC (1)
3/27
C.B
Lsh
QLQ2
Q1
VR
QR
Figure 9.3
This means the reactive power consumed by load is very less and hence there is over voltage
at the receiving end.
Now to keep a shunt reactor (Lsh) is connected in parallel to load which absorb orconsume reactive power as
Q2
Q1
QLS2
S1
P1=P2
Figure 9.4
Therefore,
[ ]Therefore, []
-
8/13/2019 SVC (1)
4/27
We know
From equation 1 and 2, we get [ ]
[ ]Relation between Q,V and f :
Therefore
Series capacitor [Cse] coponsation:
AC
LOAD
cosR
I
VRVS
Figure 9.5
Without Cse
[ ]With Cse
| | [ ]
Voltage regulation is minimum with series capacitor composition but it is normallypreferred for improving the transient stability.
-
8/13/2019 SVC (1)
5/27
In case of fault condition it discharge the energy store in capacitor so that high voltageis developed which damage the insulation hence practically not preferred.
Tap changing transformer (OLTC):
V1
4
3
2
1
4
3
2
1
R JXL
VS
VR
V2
tr:11:ts
Sending end X-merReceiving end x-mer
HV/LVHV/LV
LOAD
Figure 9.6
[ ]
Now
Therefore
By changing the transformer number of turns the voltage is controlled. The tapes are normally provided on high voltage side because current is minimum on
H.V side. During tap changing arc is developed, arc intensity is lower if current is
low.
-
8/13/2019 SVC (1)
6/27
Synchronous condensers:
A synchronous condenser is a synchronous machine running without a prime mover or a
mechanical load. By controlling the field excitation, it can be made to either generate or
absorb reactive power. With a voltage regulator, it can automatically adjust reactive power
output to maintain constant terminal voltage. It draws a small amount of active power from
the power system to supply losses.
Synchronous condensers have been used since the 1930s for voltage and reactive power
control at both transmission and sub transmission levels. They are often connected to the
tertiary winding of the transformers. They fall into category of active compensators.
Because of their high purchase and operating costs, they have been largely suppressed by
static var compensators.
Synchronous condensers have several advantages over static compensators. Synchronouscompensators contribute to system short circuit capacity. Their reactive power production is
not affected by system voltage. During power swing (electromechanical oscillations) there is
an exchange of kinetic energy between a synchronous condenser and the power system.
During such power swings, a synchronous condenser can supply a large amount of shunt
compensation, perhaps twice its continuous rating. It has about 10 to 20% overload capability
for up to. 30 minutes. Unlike other forms of shunt compensation, it has an internal voltage
source and is better able to cope with low system voltage conditions.
Static Var Compensators
According to the IEEE terms and definition:
A Shunt-connected static var generator or absorber whose output is adjusted to exchange
capacitive or inductive current so as to maintain or control specific parameters of electrical
power system (typically bus voltage)
The term static is used to indicate that SVCs, unlike Synchronous compensators, have no
rotating or moving components. Thus an SVC consists of static var generator (SVG) or
absorber devices and a suitable control device.
Types of SVC
The following are the types of reactive power control elements which make up all or part of
any static var system:
Saturated reactor (SR) Thyristor-controlled reactor (TCR) Thyristor-switched capacitor (TSC) Thyristor-switched reactor (TSR) Thyristor-controlled transformer (TCT) Self- or line-commutated converter (SCC/LCC)
-
8/13/2019 SVC (1)
7/27
-
8/13/2019 SVC (1)
8/27
We consider an SVS composed of a controllable reactor and a fixes capacitor. The resulting
characteristics are sufficiently general and are applicable to a wide range of practical SVS
configurations.
The Composite characteristic is derived by adding the individual characteristics of the
components. The characteristics shown in figure () is representative of the characteristics ofpractical controllable reactors.
Figure (9.9) Composite characteristics of an SVS
Power system characteristics
The power system V/I characteristics may be determined by considering the Thevenin
equivalent circuit as viewed from the bus whose voltage is to be regulated by the SVS. The
Thevenin impedance in figure () is predominantly an inductive reactance. The correspondingvoltage versus reactive current characteristics is shown in figure (). The voltage increaseslinearly with capacitive load current and decreases linearly with inductive load current.For each network condition, an equivalent circuit such as that in shown in figure () can be
defined.
-
8/13/2019 SVC (1)
9/27
Figure (9.10) Power system voltage versus reactive current characteristic
Composite SVSpower system characteristics:
The system characteristics may be expressed as
-
8/13/2019 SVC (1)
10/27
The SVS characteristic, with in the control range defined by the slope reactance , is givenby
For further outside the control range, the ratio
is equal to the slopes of the two extreme
segments of figure. These are determined by the rating of the inductor and capacitor.
Three system characteristics are considered in the figure (), corresponding to three values of
the source voltage. The middle characteristic represents nominal system conditions, and is
assumed to intersect the SVS characteristics at point A where and .
Figure (9.11) Graphical solution of SVS operating point for given system conditions
If the system voltage increases by (for example, due to a decreases in system loadlevel), will increases to , without an SVS. With the SVS, however, the operating pointmoves to B; by absorbing inductive current , the SVS holds the voltage at . Similarly, ifthe source voltage decreases (due to increases in system load level), the SVS hold the voltage
at , instead of at without the SVS. If the slope of the SVS characteristics were zero,the voltage would have been held at for both cases considered above.Thyristor-controlled reactor (TCR)
According to IEEE definition
A shunt connected, thyristor-controlled inductor, whose effective reactance is varied to
provide a rapidly variable phase angle.
A TCR is one of the most important building blocks of thyristor-based SVCs. Although it can
be used alone, it is more often employed in conjunction with fixed or thyristor-switched
capacitors to provide rapid, continuous control of reactive power over the entire selected
lagging-to-leading range.
-
8/13/2019 SVC (1)
11/27
The Single-Phase TCR
A basic single-phase TCR comprises an anti-parallelconnected pair of thyristor valves, T1
and T2, in series with a linear air-core reactor, as illustrated in Fig. (5.12). The anti-parallel
connected thyristor pair acts like a bidirectional switch, with thyristor valveT1 conducting in
positive half-cycles and thyristor valve T2 conducting in negative half-cycles of the supplyvoltage. The firing angle of the thyristors is measured from the zero crossing of the voltage
appearing across its terminals.
Principle of operation:
The controllable range of the TCR firing angle, , extends from to . A firing angleof results in full thyristor conduction with a continuous sinusoidal current flow in theTCR. As the firing angle is varied from to close to the current flows in the form ofdiscontinuous pulses symmetrically located in the positive and negative half-cycles, as
displayed in Fig.(5.13). Once the thyristor valves are fired, the cessation of current occurs at
its natural zero crossing, a process known as the line commutation. The current reduces tozero for a firing angle of . Thyristor firing at angles below introduces dccomponents in the current, disturbing the symmetrical operation of the two anti-parallel valve
branches.
Figure (9.12) A TCR
-
8/13/2019 SVC (1)
12/27
-
8/13/2019 SVC (1)
13/27
-
8/13/2019 SVC (1)
14/27
( ) The variation of per-unit value of with firing angle is depicted in Fig. (9.14). The per-unit value of
is obtained with respect to its maximum value
as the base quantity.
Figure (9.14) Control Characteristics of the TCR susceptance, .The TCR thus acts like a variable susceptance. Variation of the firing angle changes the
susceptance and, consequently, the fundamental-current component, which leads to a
variation of reactive power absorbed by the reactor because the applied ac voltage is constant.
However, as the firing angle is increased beyond , the current becomes non-sinusoidal,and harmonics are generated. If the two thyristors are fired symmetrically in the positive and
negative half-cycles, then only odd-order harmonics are produced.
Operating Characteristics of TCR
(a) Operating Characteristics without Voltage Control
The simplest SVC configuration consists of a TCR connected to the power system as shown
in Fig.(). In the analysis of compensator performance, the fundamental frequency behavior is
generally considered. In practice, harmonics are filtered and reduced to very low values. The
approach shown in Fig () is convenient for the performance analysis because the whole TCR
branch is replaced by an equivalent continuously variable reactor.
Figure (9.15) A simple SVC circuit using a TCR
-
8/13/2019 SVC (1)
15/27
For a general SVC, which can be considered as a black box with an unknown but purely
reactive circuit inside, the overall compensator susceptance can be defined with thefollowing equation:
In the simple case of a TCR, the compensator susceptance is
Usually, three kinds of characteristics are of interest while analyzing an SVC, as described in
the paragraphs that follow.
VoltageCurrent Characteristic or Operating Characteristic:
This shows the SVC current as a function of the system voltage for different firing angles, as
depicted in Fig. (9.16).This V-I characteristic is given in a very general sense. No control
system is assumed to vary the firing angle, and any operating point within the two limits ispossible depending on the system voltage and the setting of the firing angle (other currents
and voltages may be shown, too). This characteristic clearly illustrates the limits of the
operating range, and it may include the steady-state characteristics of the various possible
controls.
Figure (9.16): VoltageCurrent Characteristic or Operating Characteristic
SVC TCR Susceptance Characteristics:
These illustrate the change of the total SVC susceptance when the TCR susceptance is varied,
as shown in Fig. (9.17). The susceptance characteristic for this case is very simple
because . Note that the TCR susceptance is negative, indicating that the TCR isan absorbing reactive component. These characteristics are of most interest to control-system
analysis because the controls affect the TCR firing angle, whereas the total susceptance
influences the power system.
-
8/13/2019 SVC (1)
16/27
Figure (9.17): SVC TCR Susceptance Characteristics
(b) Operating Characteristic with Voltage Control
The operating range of Fig () can be reduced to a single characteristic of operating points if
the effect of the voltage control is incorporated. Let us assume that the compensator is
equipped with the voltage control shown in Fig. ().The system voltage is measured, and the
feedback system varies to maintain on the system.This control action is represented in the operating characteristic in Figure () by the horizontal
branch marked as control range. This characteristic shows the hard-voltage control of the
compensator, which stabilizes the system voltage exactly to the set point
.
Figure (9.18): The operating characteristics of a TCR with voltage control: (a) an SVC
control system and (b) the V/I characteristic.
Two system characteristicssystem 1and system2are depicted in Fig. () that illustrate the
decline in system node voltage when the node is loaded inductively and reactive power is
absorbed. The corresponding operating points for the two system conditions are .
-
8/13/2019 SVC (1)
17/27
If the system voltage of system 2 raises, a new characteristicsystem 2results. Operating
point A then moves to the right and reaches the absorption limit of the compensator. Any
further increase in system voltage cannot be compensated for by the control system, because
the TCR reactor is already fully conducting.
The operating point will, therefore, move upward on the characteristic, corresponding tothe fully on reactor connected to the system ( ). The compensator then operates in theoverload range, beyond which a current limit is imposed by the firing control to prevent
damage to the Thyristor valve from an over current. At the left-hand side, the compensator
will reach the production limit if the system voltage drops excessively; the operating point
will then lie on the characteristic of the under voltage range.
The Fixed-Capacitor-Thyristor-Controlled Reactor (FC-TCR):
Configuration:
The TCR provides continuously controllable reactive power only in the lagging power-factor
range. To extend the dynamic controllable range to the leading power factor domain, a fixed-
capacitor bank is connected in shunt with the TCR. The TCR MVA is rated larger than the
fixed capacitor to compensate the capacitive MVA and provide net inductive-reactive power
should a lagging power factor operation be desired. The fixed capacitor banks, usually
connected in a star configuration, are split into more than three phase groups. Each capacitor
contains a small tuning inductor that is connected in series and tunes the branch to act as a
filter for a specific harmonic order. For instance, one capacitor group is connected to 5 th
harmonic and another to 7th, whereas yet another is designed to act as a high pass filter. At
fundamental frequency, the tuning reactors slightly reduce the net MVA rating of the fixed
capacitors.
Figure (9.19) FC-TCR SVC
Operating Characteristics:
Without the step-down transformer:
-
8/13/2019 SVC (1)
18/27
The fixed capacitor extends the operating control range of SVC to the leading side as
compared to the characteristics of TCR with voltage control. The SVC current can beexpressed as a function of system voltage and compensator susceptance as
Where, and Figure shows the operating characteristics and the susceptance characteristics of an FC-TCR
without a coupling transformer and both also show that var production as well as var
absorption is possible.
Figure (9.20) The operating characteristics of an FCTCR without a coupling transformer
With the step-down transformer:
An FC-TCR SVC is usually connected to the high voltage power system by means of a step
down coupling transformer as shown in figure.
-
8/13/2019 SVC (1)
19/27
-
8/13/2019 SVC (1)
20/27
( )
(
)
The susceptance characteristic is shown in figure. Both the exact characteristic from Eq. ( ) and thelinearized characteristic from Eq. ( ) are displayed. The errors from linearization are clearly visible.
Figure (9.22) Susceptance characteristics of an FC-TCR SVC with a step down transformer
Losses:A drawback of the FCTCR SVC is the circulation of large currents in the FCTCR loop
needed for cancellation of capacitive vars. This results in high steady-state losses, even when
the SVC is not exchanging any reactive power with the power system, as shown in Figure.Typical losses in an FCTCR scheme vary from 0.5% to 0.7% of the MVA rating. However,
these losses can be minimized by switching the fixed capacitors through mechanical breakers,
ensuring that the capacitors are inserted in the compensator circuit only when leading vars are
needed. Thus a smaller-sizeinterpolating TCR can be used, and consequently, the steady-
state operating losses can be reduced. Those FCTCRs having a 300-MVA inductive rating
have been already installed in the field.
Figure (9.23) Losses in an FC-TCR
-
8/13/2019 SVC (1)
21/27
The Thyri stor-Switched Capacitor (TSC).
A single-phase thyristor switched capacitor (TSC) is shown in Figure 5.13(a). It consists of a
capacitor, a bidirectional thyristor valve, and a relatively small surge current limiting reactor.
This
reactor is needed primarily to limit the surge current in the thyristor valve under abnormaloperating conditions (e.g., control malfunction causing capacitor switching at a "wrong time,"
when transient free switching conditions are not satisfied); it may also be used to avoid
resonances with the ac system impedance at particular frequencies.
Under steady-state conditions, when the thyristor valve is closed and the TSC branch is
connected to a sinusoidal ac voltage source, v = V sin on, the current in the branch is given by
Where
VSW
VL
Vc
i
Figure 9.24. Basic thyristor-switched capacitor (a) and associated waveforms (b).
The amplitude of the voltage across the capacitor is
The TSC branch can be disconnected ("switched out") at any current zero by prior removal of
the gate drive to the thyristor valve. At the current zero crossing, the capacitor voltage is at its
peak value, . The disconnected capacitor stays charged to this voltageand, consequently, the voltage across the non-conducting thyristor valve varies between zero
and the peak-to-peak value of the applied ac voltage, as illustrated in Figure 5.13(b).If thevoltage across the disconnected capacitor remained unchanged, the TSC bank could be
-
8/13/2019 SVC (1)
22/27
switched in again, without any transient, at the appropriate peak of the applied ac voltage, as
illustrated for a positively and negatively charged capacitor in Figure 2(a) and (b),
respectively. Normally, the capacitor bank is discharged after disconnection. Thus, the
reconnection of the capacitor may have to be executed at some residual capacitor voltage
between zero and Vn 2/(n 2 - 1). This can be accomplished with the minimum possible
transient disturbance if the thyristor valve is turned on at those instants at which the capacitorresidual voltage and the applied ac voltage are equal, that is, when the voltage across the
thyristor valve is zero. Figure 5.15(a) and (b) illustrate the switching transients obtained with
a fully and a partially discharged capacitor. These transients are caused by the nonzero dv /dt
at the instant of switching, which, without the series reactor, would result in an instantaneous
current of ic = Cdv/dt in the capacitor. (This current represents the instantaneous value of the
steady- state capacitor current at the time of the switching.) The interaction between the
capacitor and the current (and di/dt) limiting reactor, with the damping resistor, produces the
oscillatory transients visible on the current and voltage waveforms. (Note that the switching
transient is greater for the fully discharged than for the partially discharged capacitor because
the dv/dt of the applied (sinusoidal) voltage has its maximum at the zero crossing point.)
Figure 9.25 Waveforms illustrating transient free switching by a thyristor switched capacitor
-
8/13/2019 SVC (1)
23/27
Figure 9.26 Waveforms illustrating transient with thyristor switched capacitor fully (a) or
partially discharged (b)
The conditions for "transient-free" switching of a capacitor are summarized in Figure 3. As
seen, two simple rules cover all possible cases: (1) if the residual capacitor voltage is lower
than the peak ac voltage (Vc < V), then the correct instant of switching is when theinstantaneous ac voltage becomes equal to the capacitor voltage; and (2) if the residual
capacitor voltage is equal to or higher than the peak ac voltage (VC V), then the correct
switching is at the peak of the ac voltage at which the thyristor valve voltage is minimum.
From the above, it follows that the maximum possible delay in switching in a capacitor bank
is one full cycle of the applied ac voltage, that is, the interval from one positive (negative)
peak to the next positive (negative) peak. It also follows that firing delay angle control is not
applicable to capacitors; the capacitor switching must take place at that specific instant in
each cycle at which the conditions for minimum transients are satisfied, that is, when the
voltage across the thyristor valve is zero or minimum. For this reason, a TSC branch can
provide only a step-like change in the reactive current it draws (maximum or zero). In otherwords, the TSC branch represents a single capacitive admittance which is either connected to,
or disconnected from the ac system. The current in the TSC branch varies linearly with the
applied voltage according to the admittance of the capacitor as illustrated by the V-Iplot in
Figure 5.17. The maximum applicable voltage and the corresponding current are limited by
the ratings of the TSC components (capacitor and thyristor valve).
-
8/13/2019 SVC (1)
24/27
Figure 9.27 Conditions for transient-free switching for the thyrister-switched capacitor with
different residual voltages.
To approximate continuous current variation, several TSC branches in parallel (which would
increase in a step-like manner the capacitive admittance) may be employed, or, as is
explained later, the TSC branches have to be complemented with a TCR.
BC
VCmax
IC ICmax
V
CmaxI = current limit
VCmax= voltage limit
CB = admittance of capacitor
Figure 9.28 Operating V-I area of single TSC
Operating Characteristics:
-
8/13/2019 SVC (1)
25/27
Controller
Dead band DV
Vref
V
VISVC
C1 C C2 3 . . . Cn Figure 9.29 TSC scheme
TheV/I characteristics of a TSC compensator is shown in Figure . We see that the voltage control
provided is discontinuous or stepwise. It is determined by the rating and number of parallel connected
units. In high voltage application, the number of shunt capacitor banks are limited because high cost
of thyristors. The power system V/Icharacteristics, as system condition change, intersect the TSC V/I
characteristics at discrete points. The bus voltage Vis controlled within the range , whereDV is the dead band. When the system is operating so that its characteristics is represented by line,then capacitor will be switched and operating point A prevails. If the system characteristicssuddenly changes to S2, the bus voltage drops initially to a value represented by operating point B.
The TSC control switches in bank C2 to change the operating point to C, bringing the voltage within
the desired range. Thus the compensator current can change in discrete steps. The time taken forexecuting a command from the controller ranges one half cycle to one cycle.
Thyristor-Switched Capacitor, Thyristor-Controlled Reactor Type Var Generator.
The thyristor-switched capacitor, thyristor-controlled reactor (TSC-TCR) type compensator was developedprimarily for dynamic compensation of power transmission systems with the intention of minimizingstandby losses and providing increased operating flexibility.
A basic single-phase TSC-TCR arrangement is shown in Figure 5.22(a). For a given capacitive output
range, it typically consists of n TSC branches and one TCR. The number of branches, n, is determined by
practical considerations that include the operating voltage level, maximum var output, current rating of thethyristor valves, bus work and installation cost, etc. Of course, the inductive range also can be expanded to
any maximum rating by employing additional TCR branches.
The operation of the basic TSC-TCR var generator shown in Figure 5.22(a) can be described as follows:
-
8/13/2019 SVC (1)
26/27
Figure 9.30 Basic TSC-TCR type static var generator
The total capacitive output range is divided into n intervals. In the first interval, the output of the var
generator is controllable in the zero to range, where is the total rating provided by all TSCbranches. In this interval, one capacitor bank is switched in (by firing, for example, thyristor valve,)and, simultaneously,the current in the TCR is set by the appropriate firing delay angle so that the sum of the var output of theTSC (negative) and that of the TCR (positive) equals the capacitive output required.
In the second, third, and nth intervals, the output is controllable in the
,to
,
to ,. . . , and to range by switching in the second, third, ..., and nthcapacitor bank and using the TCR to absorb the surplus capacitive vars.By being able to switch the capacitor banks in and out within one cycle of the applied ac voltage, the
maximum surplus capacitive var in the total output range can be restricted to that produced by one
capacitor bank, and thus, theoretically, the TCR should have the same var rating as the TSC. However, toensure that the switching conditions at the endpoints of the intervals are not indeterminate, the var rating of
the TCR has to be somewhat larger in practice than that of one TSC in order to provide enough overlap
(hysteresis) between the "switching in" and "switching out" var levels.
In a way, this scheme could be considered as a special fixed capacitor, thyristor controlled reactorarrangement, in which the rating of the reactor is kept relatively small (
times the maximum capacitive
output), and the rating of the capacitor is changed in discrete steps so as to keep the operation of the TCRwithin its normal control range.
Susceptance Characteristic
The SVC susceptance in the TSCTCR scheme is as follows:
Where 1, 2. . . . is the number of TSC branches in operation and is the totalsusceptance of n TSC branches. With a linear approximation, Eq. () reduces to
-
8/13/2019 SVC (1)
27/27
( ) ( )
Figure 9.32 The Susuptance characteristics of the TSC-TCR SVC.
Figure gives the total susceptance BSVC as a function of the susceptanceof the controlled
reactor BTCR for the example data. These characteristics are of importance for control
design, for the controls varyBTCR and the effect on the system is caused by.