SUPERHYDROPHOBIC COATINGFOR POLYMER INSULATORS
DEVELOPED BY NEETRAC / GEORGIA TECH
SUPERHYDROPHOBIC COATINGFOR POLYMER INSULATORS
DEVELOPED BY NEETRAC / GEORGIA TECH
MISSISSIPPI CHEMICAL –MOSS POINT EAST 115 KV T.L.
IEEE Insulators WG
7/22/2008
Jack Varner – Southern Company
Frank Lambert –NEETRAC
![Page 2: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/2.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 2/19
Lotus Effect Surface
Lotus Leaf
Lotus Effect Surfaces:
Avoid water sheeting – drops stay as drops
Self Cleaning – remove dust / contamination
![Page 3: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/3.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 3/19
Superhydrophobic Surface Coating• Contact angle≥ 150°
• Water droplets bead up, no “sheeting action”
• Prevents electrical tracking
• Improves insulator performance, especially in
contaminated areas.
![Page 4: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/4.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 4/19
Lotus Effect Surface for Insulators Developed
by Georgia Tech / NEETRAC
![Page 5: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/5.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 5/19
Lab Results
• Works on all
polymer
insulations
• Lasts at least
2000 hours in
energized salt fog
testing
• Increases the
endurance in
accelerated tests
E n d u r a n c e ( % )
TreatedUnTreated
140
130
120
110
100
90
80
70
60
50
100
in Endurance
Improvement
28%
![Page 6: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/6.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 6/19
SUPERHYDROPHOBIC COATING
• Gives insulators superior performance in contaminated environments.• Coating can be applied in several ways:
– Sprayed on in f ield
– Painted on with brush in field – Can be dipped in solution
• Treatment can also be applied to glass and porcelain insulators, but they
must be pre-treated to ensure the solution adheres to the surface.
• Both US and Foreign Patents Filed.
![Page 7: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/7.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 7/19
• Ohio Brass Polymer Silicone Insulators
• Southern Company Transmission Lines
• Test Site at Mississippi Power
• Miss. Chemical –Moss Point 115kv line
Field Test Participants
![Page 8: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/8.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 8/19
Insulator
InstallationSite
MISSISSIPPI CHEMICAL
MOSS POINT EAST
115 KV T.L.
![Page 9: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/9.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 9/19
CHEVRON
PLANTMISSISSIPPI
PHOSPHATE
X
X
![Page 10: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/10.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 10/19
XX
XX
XX STR#: 54
STR#: 55
STR#: 56
H W Y 6 1 1
Wooden H-Frame
Wooden H-Frame
Wooden 3PDDE
XX
XX
XXSTR#: 54
STR#: 55
STR#: 56
H W Y
6 1 1
Wooden H-Frame
Wooden H-Frame
Wooden 3PDDEX
![Page 11: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/11.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 11/19
STR# 54
• Replaced three Suspension Insulators installed in 2005 with three newPolymer Suspension Insulators.
• Insulators were new and NOT Coated with the new solution.
STR #55
• Replaced three Suspension Insulators installed in 2005 with three new
Polymer Suspension Insulators.
• Insulators were treated with the new coating solution.
![Page 12: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/12.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 12/19
Superhydrophobic solution applied to the new Quadri*silTM Insulators
![Page 13: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/13.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 13/19
Superhydrophobic solution on new Quadri*silTM Insulator
![Page 14: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/14.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 14/19
![Page 15: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/15.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 15/19
Installing new uncoated Insulator at Str.# 54
![Page 16: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/16.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 16/19
Severe Pin Corrosion was found on all of the Porcelain Insulators which were
removed. These insulators had been in service approximately three years.
![Page 17: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/17.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 17/19
This guy grip had been in service for six weeks. Notice that the loop that
wraps around the anchor attachment point has corroded out of theguy grip.
![Page 18: Superhydrophobicity 1](https://reader036.vdocuments.us/reader036/viewer/2022062317/5695cf2f1a28ab9b028cf93c/html5/thumbnails/18.jpg)
7/23/2019 Superhydrophobicity 1
http://slidepdf.com/reader/full/superhydrophobicity-1 18/19
This guy wire had been in service for six weeks. Notice that the individual strands
have necked down much like you would expect to see from a tensile failure.