Submittal Data For: Caterpillar Model D40-LC2, Enclosed 40 KW Diesel Generator Set with 260 AMP ASCO ATS Town of Christiansburg, VA Lubna PS Project Number: 15-072MO Date: June 12, 2015 Power Systems Sales Representative: Craig Brander Power Systems Project Manager: Michael Olszewski 971 Russell Dr. Office: (540) 682-2007 Salem, VA 24153

Upload: vuongthuy

Post on 06-Mar-2018

235 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Submittal Data For:

Caterpillar Model D40-LC2, Enclosed 40 KW Diesel

Generator Set with 260 AMP ASCO ATS

Town of Christiansburg, VA – Lubna PS

Project Number: 15-072MO

Date: June 12, 2015

Power Systems Sales Representative:

Craig Brander

Power Systems Project Manager:

Michael Olszewski

971 Russell Dr. Office: (540) 682-2007

Salem, VA 24153

Page 2: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

_____________________________________________________________________________________________________________________________________________________________

Carter Machinery Company, Inc. Phone (804) 823-1164 Fax (804)752-6772

10990 Air Park Road; Hanover Industrial Airpark; Ashland, VA 23005

Town of Christiansburg – Lubna Drive Booster Pump Station – 40KW Cat Generator

NJPA Contract # 080613-CAT

USING NJPA CONTRACT PRICING

GENERATOR SUBMITTAL BILL OF MATERIALS

One (1) Caterpillar Diesel Fueled Packaged Generator Set Model D40-LC2 with Brushless

Generator, 40 KW Standby at 0.8 P.F., 120/208 Volt, 3-Phase, 60 Hertz at 1800 RPM.

NJPA CONTRACT ITEMS BASE MODEL

EPA STATIONARY EMERGENCY CERTIFIED- EPA TIER 3 (PER EPA NSPS RULE)

o NAC147P [D40-LC2, 40kW, 3-PHASE, 208v, 60Hz ENGINE-GENERATOR SET]

ATTACHMENTS EMISSION CERTIFICATION

o CERTESE [EPA STATIONARY EMERGENCY]

UL LISTING o UL LISTED and CSA LISTED [NACERT LISTING]

NFPA 110 UPGRADE

o NFPA

VOLTAGE INDICATOR o VOP610 [120/208v 3-Phase]

APPLICATION INDICATOR o STANDBY [STANDBY RATING]

CONTROL PANEL o EMCP42 [EMCP 4.2 AUTOSTART CONTROL PANEL]

o FSS [PANEL CIRCUIT – FUEL LEVEL ALARMS included]

o VFRCON [GEN RUNNING RELAY and VOLT FREE CONTACT for ALARMS]

o PAA1 [LOCAL ALARM HORN w/ MUTE]

o PSV1 [VOLTAGE ADJUST POTENTIOMETER]

CIRCUIT BREAKER o CB2251A [225A/3P/100% RATED/ADJUSTABLE]

o NOSUSEA [NEUTRAL BAR]

o SHTAUX [12V SHUNT TRIP and AUX. CONTACTS]

COOLING SYSTEM o WSS1 [LOW COOLANT LEVEL SHUTDOWN CIRCUIT]

o WCA1 [LOW COOLANT TEMPERATUR ALARM 69/80]

o WHH [COOLANT WATER HEATER 90/130]

Page 3: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ENCLOSURE o ENCSA88 [SOUND ATTENUATED, WEATHERPROOF ENCLOSURE – CAT WHITE IN COLOR – WITH

CRITICAL SILENCER INSTALLED INSIDE ENCLOSURE]

o PVW2 [PANEL VIEWING WINDOW]

FUEL STORAGE SYSTEM o INFT140 [137-GALLON USEABLE UL-142 DOUBLE-WALLED INTEGRAL TANK]

(36-HR RUNTIME at 100% LOAD)

o FL4STG1 [FUEL SENDER included in tank]

o FLEKP [LEAK PROBE included in tank]

o FFLCK [LOCKING FUEL CAP included on tank]

GENERATOR

o OGNSEAJ – [CAT LC1514L GENERATOR END]

o IVR12 – [ PERMANENT MAGNET EXCITATION]

o AH1H – [GENERATOR ANTI-CONDENSATION HEATER]

STARTING/CHARGING SYSTEM o PBC10NU [BATTERY CHARGER 10A]

TESTS/REPORTS o PFT [0.8 PF PGS TEST REPORT.]

OTHER o MCM9EN [ONE (1) REMOTE ANNUNCIATOR – Ships Loose for others to wire and install)

o EBH [BATTERY HEATER]

FOUR (4) YEAR / 2000hr Extended Standby Warranty, Covering Travel, Parts and Labor for

the full term.

Delivery to Jobsite included – Off-Loading and Setting by Others

OTHER NJPA ITEMS One (1) AUTOMATIC TRANSFER SWITCH

o 260AMP, 3-Pole, 120/208V 3-Phase, Nema-4 Enclosure, Open Transition, Programmable Engine

Exerciser, NON-Service Entrance Rated. (Quoting 260 Amp to meet kAIC Rating Requirement)

STANDARD STARTUP SERVICE

o INCLUDES ANY MILEAGE AND TRAVEL CHARGES

ALL INCOMING/OUTGOING FREIGHT AND JOBSITE DELIVERY

ONSITE OWNER PERSONNEL TRAINING SESSION DURING STARTUP

NOTES:

Ordering from NJPA now includes a total of 4-YEAR warranty at no additional charge!

Based on Spec 16210 dated 4/1/15 as well as riser C4 of the same date

NOT included in pricing above:

Additional fuel needed to top off tank.

Any Applicable Taxes or Coordination Studies.

Page 4: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

C4.4 Generator SetElectric Power

LEHE0872-00 Page 1 of 7

Generator Set SpecificationsRating 40 ekW (50 kVA)

Voltage 480 Volts

Frequency 60 Hz

Speed 1800 rpm

Generator Set Configurations

Emissions/Fuel StrategyU.S. EPA Certified for Stationary Emergency Application (Meets nonroad U.S. EPA Tier 3

equivalent emission standards)

Specifications

Image shown may not reflect actual configuration

Engine SpecificationsEngine Model C4.4 In-line 4, 4-cycle diesel

Bore 105.0 mm 4.13 in

Displacement 4.4 L 268.5 in³

Stroke 127.0 mm 5.0 in

Compression Ratio 18.2:1

Aspiration Turbocharged

Governor Type Electronic (adjustable)

Fuel System Common Rail

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Package Dimensions*Length 1972 mm 77.6 in

Width 1000 mm 39.4 in

Height 1175 mm 46.3 in

Weight† 861 kg 1898 lb

* Note: For reference only – do not use for installation design. Please contact your local dealer for exact weight and dimensions.

†Weight includes: Oversize generator, skid base, circuit breaker, oil, and coolant.

d100mdo
Text Box
208
d100mdo
Text Box
Town of Christiansburg Lubna PS 208V, 40 KW
Page 5: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

C4.4 Generator SetElectric Power

LEHE0872-00 Page 2 of 7

Benefits & FeaturesCat® Diesel Engine

• Reliable, rugged, durable design• Field-proven in thousands of applications worldwide• Four-stroke cycle diesel engine combines consistent performance and excellent fuel economy

with minimum weight• Electronic engine control

Generator • Matched to the performance and output characteristics of Cat engines • Industry-leading mechanical and electrical design • Industry-leading motor starting capabilities • High efficiency

Cat EMCP Control PanelThe EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules.

Design Criteria• The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response• Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow

restriction of 0.5 in. water

UL 2200/CSA – Optional• UL 2200 Listed • CSA Certified Certain restrictions may apply. Consult with your Cat dealer.

Single-Source SupplierFully prototype tested with certified torsional vibration analysis.

Worldwide Product SupportCat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat S•O•SSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.

Page 6: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

C4.4 Generator SetElectric Power

LEHE0872-00 Page 3 of 7

Standard EquipmentAir Inlet

• Dry replaceable paper element type with restriction indicator

Cooling

• Radiator and cooling fan complete with protective guards• Standard ambient temperatures up to 50°C (122°F)

Exhaust

• Exhaust flange outlet

Fuel

• Primary and secondary fuel filters• Fuel priming pump• Flexible fuel lines

Generator• Matched to the performance and output characteristics of Cat engines• Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time• IP23 protection• Integrated Voltage Regulation

Governor

• Electronic governor – ADEM™ A4

Control Panels

• EMCP 4.2 Series generator set controller

Mounting

• Rubber vibration isolators

Starting/Charging

• 12 volt starting motor• Batteries with rack and cables

General

• Paint – Caterpillar Yellow except rails and radiators gloss black

Page 7: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

C4.4 Generator SetElectric Power

LEHE0872-00 Page 4 of 7

Optional EquipmentGenerator

• Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE) • Oversize and premium generators

Starting/Charging

• Battery charger – UL 10 amp• Battery disconnect switch • Battery removal (does not remove rack and cables)• Jacket water heater

General

• UL 2200• CSA Certification • Enclosures: sound attenuated, weather protective• Integral or sub-base dual wall UL Listed fuel tanks• Automatic transfer switches (ATS)

d100mdo
Line
d100mdo
Line
d100mdo
Line
d100mdo
Line
d100mdo
Line
Page 8: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ELECTRIC POWER – Technical Spec SheetSTANDARD

C4.440 ekW/ 50 kVA/ 60 Hz/ 1800 rpm/ 480V/ 0.8 Power Factor

LEHE0872-00 Page 5 of 7

Rating Type: STANDBY Emissions: U.S. EPA Certified for Stationary Emergency Application(Meets nonroad U.S. EPA Tier 3 equivalent emission standards)

D40-2LC40 ekW/ 50 kVA

60Hz/ 1800 rpm/ 480V

Package Performance

Generator Set Power Rating with Fan @ 0.8 Power Factor 40 ekW

Generator Set Power Rating 50 kVA

Fuel Consumption

100% Load With Fan 13.9 L/hr 3.7 gal/hr

75% Load With Fan 10.8 L/hr 2.9 gal/hr

50% Load With Fan 8.1 L/hr 2.1 gal/hr

Cooling System1

Engine Coolant Capacity 7.0 L 1.8 gal

Radiator Coolant Capacity 9.5 L 2.5 gal

Engine Coolant Capacity with Radiator/Exp Tank 16.5 L 4.4 gal

Air Flow Restriction (System) 0.12 kPa 0.48 in. water

Inlet Air

Combustion Air Inlet Flow Rate 5.3 m³/min 187.2 cfm

Exhaust System

Exhaust Stack Gas Temperature 571°C 1060°F

Exhaust Gas Flow Rate 13.7 m³/min 483.8 cfm

Exhaust System Backpressure (maximum allowable) 15.0 kPa 60.2 in. water

Image shown may not reflect actual configuration

d100mdo
Text Box
208V
Page 9: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Rating Type: STANDBY Emissions: U.S. EPA Certified for Stationary Emergency Application(Meets nonroad U.S. EPA Tier 3 equivalent emission standards)

Heat Rejection

Heat Rejection to Coolant (total) 46.1 kW 2622 Btu/min

Heat Rejection to Exhaust (total) 66.9 kW 3805 Btu/min

Heat Rejection to Atmosphere from Engine 14.9 kW 847.3 Btu/min

Heat Rejection to Atmosphere from Generator 4.7 kW 267.3 Btu/min

Alternator2

Motor Starting Capability @ 30% Voltage Dip 105 skVA

Frame LC1514J

Temperature Rise 130°C 234°F

Excitation Self Excited

Lube System

Sump Refill with Filter 8.4 L 2.2 gal

Emissions (Nominal)3

NOx + HC 4.42 g/kW-hr

CO 1.02 g/kW-hr

PM 0.26 g/kW-hr

1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to the existing restriction from the factory.

2 Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.3The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% Prime load.

ELECTRIC POWER – Technical Spec SheetSTANDARD

C4.440 ekW/ 50 kVA/ 60Hz/ 1800 rpm/ 480V/ 0.8 Power Factor

LEHE0872-00 Page 6 of 7

d100mdo
Text Box
208V
Page 10: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

WIDTH OF PAD:

63.0”

LENGTH OF PAD: 122.0”

R

A

D

I

A

T

O

R

E

N

D

GenSet Stub Up Area

33.0” X 12.0”

RECOMMEND 12.0" MIN. APRON ON ALL SIDES OF GENSET

STUB UP DRAWING Caterpillar D40-LC2 GENSET

Carter Machinery Co. 06/15

LENGTH OF GENSET: 98.0”

WIDTH OF

GENSET:

41.0”

NOTE: THE OUTER DIMENSIONS ARE RECOMMENDED PAD DIMENSIONS, THE INNER DIMENSIONS ARE

ACTUAL GENSET DIMENSIONS. THE CONTROL PANEL AND CIRCUIT BREAKER ARE LOCATED AS MARKED.

NOT TO SCALE – ALLOW UP TO 3 FEET FOR DOOR SWING BASED ON DRAWING # 4837627

OLSZEWSKI 06/2015

Lubna PS WEIGHT w/fuel = 4400 lbs.

14.0”

12.0” 4.0”

Page 11: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

UNITED STATES ENVIRONMENTAL PROTECTION AGENCY2015 MODEL YEAR

CERTIFICATE OF CONFORMITYWITH THE CLEAN AIR ACT OF 1990

OFFICE OF TRANSPORTATIONAND AIR QUALITY

ANN ARBOR, MICHIGAN 48105

Certificate Issued To: Perkins Engines Co Ltd (U.S. Manufacturer or Importer)

Certificate Number: FPKXL04.4NH1-006

Effective Date:08/05/2014

Expiration Date:12/31/2015

_________________________Byron J. Bunker, Division Director

Compliance Division

Issue Date:08/05/2014

Revision Date:N/A

Model Year: 2015Manufacturer Type: Original Engine ManufacturerEngine Family: FPKXL04.4NH1

Mobile/Stationary Indicator: StationaryEmissions Power Category: 56<=kW<75Fuel Type: Non-Standard Fuel, DieselAfter Treatment Devices: No After Treatment Devices InstalledNon-after Treatment Devices: Electronic Control, Engine Design Modification

Pursuant to Section 111 and Section 213 of the Clean Air Act (42 U.S.C. sections 7411 and 7547) and 40 CFR Part 60, and subject to the terms and conditions prescribed in those provisions, this certificate ofconformity is hereby issued with respect to the test engines which have been found to conform to applicable requirements and which represent the following engines, by engine family, more fully described inthe documentation required by 40 CFR Part 60 and produced in the stated model year.

This certificate of conformity covers only those new compression-ignition engines which conform in all material respects to the design specifications that applied to those engines described in thedocumentation required by 40 CFR Part 60 and which are produced during the model year stated on this certificate of the said manufacturer, as defined in 40 CFR Part 60.

It is a term of this certificate that the manufacturer shall consent to all inspections described in 40 CFR 1068 and authorized in a warrant or court order. Failure to comply with the requirements of such awarrant or court order may lead to revocation or suspension of this certificate for reasons specified in 40 CFR Part 60. It is also a term of this certificate that this certificate may be revoked or suspended orrendered void ab initio for other reasons specified in 40 CFR Part 60.

This certificate does not cover engines sold, offered for sale, or introduced, or delivered for introduction, into commerce in the U.S. prior to the effective date of the certificate.

Page 12: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,
Page 13: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

EMCP 4

LEHE0138-00

EMCP 4.2 GENERATOR SET CONTROLLER Caterpillar is leading the power generation market place with power solutions engineered to deliver unmatched performance, reliability, durability and cost-effectiveness.

FEATURES GENERAL DESCRIPTION The Cat® EMCP 4.2 offers fully featured power metering, protective relaying and engine and generator control and monitoring. Engine and generator controls, diagnostics, and operating information are accessible via the control panel keypads; diagnostics from the EMCP 4 optional modules can be viewed and reset through the EMCP 4.2. FULL RANGE OF ATTACHMENTS • Wide range of system expansion attachments, designed specifically to work with the EMCP 4. • Flexible packaging options for easy and cost effective installation. WORLD WIDE PRODUCT SUPPORT • Cat dealers provide extensive pre and post sale support. • Cat dealers have over 1,600 dealer branch stores operating in 200 countries. FEATURES • A 33 x 132 pixel, 3.8 inch, graphical display denotes text alarm/event descriptions, set points, engine and generator monitoring, and is visible in all lighting conditions. • Textual display with support for 28 languages, including character languages such as Arabic, Chinese, and Japanese. • Advanced engine monitoring is available on systems with an electronic engine control module. • Integration with the Cat Digital Voltage Regulator (CDVR) provides enhanced system performance. • Fully featured power metering, protective relaying, engine and generator parameter viewing, and expanded AC metering are all integrated into this controller.

• Real-time clock allows for date and time stamping of diagnostics and events in the control’s logs as well as service maintenance reminders based on engine operating hours or calendar days. • Up to 40 diagnostic events are stored in the non- volatile memory.

Image shown may not reflect actual package

• Ability to view and reset diagnostics on EMCP 4 optional modules via the control panel removes the need for a separate service tool for troubleshooting. • Set points and software stored in non-volatile memory, preventing loss during a power outage. • Reduced power mode offers a low power state to minimize battery power requirements. • Three levels of security allow for configurable operator privileges. • Selectable units

− Temperature: °C or °F − Pressure: psi, kPa, bar − Fuel Consumption: Gal/hr or Liter/hr

STANDARDS • UL Recognized • CSA C22.2 No.100,14, 94 • Complies with all necessary standards for CE Certification 98/37/EC Machinery Directive – BS EN 60204-1 Safety of Machinery 89/336/EEC EMC Directive – BS EN 50081-1 Emissions Standard – BS EN 50082-2 Immunity Standard 73/23/EEC Low Voltage Directive – EN 50178 LVD Standard • IEC529, IEC60034-5, IEC61131-3 • MIL STND 461

Page 14: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

EMCP 4.2 GENERATOR SET CONTROLLER

LEHE0138-00 2

STANDARD FEATURES

Generator Monitoring

• Voltage (L-L, L-N)• Current (Phase)• Average Volt, Amp, Frequency• kW, kVAr, kVA (Average, Phase, %)• Power Factor (Average, Phase)• kW-hr, kVAr-hr (total)• Excitation voltage and current (with CDVR)• Generator stator and bearing temp (with optional module)

Generator Protection

• Generator phase sequence• Over/Under voltage (27/59)• Over/Under frequency (81 O/U)• Reverse Power (kW) (32)• Reverse Reactive Power (kVAr) (32RV)• Overcurrent (50/51)

Engine Monitoring

• Coolant temperature• Oil pressure• Engine speed (RPM)• Battery voltage• Run hours• Crank attempt and successful start counter• Enhanced engine monitoring (with electronic engines)

Engine Protection

• Control switch not in auto (alarm)• High coolant temp (alarm and shutdown)• Low coolant temp (alarm)• Low coolant level (alarm)• High engine oil temp (alarm and shutdown)• Low, high, and weak battery voltage• Overspeed• Overcrank

Control

• Run / Auto / Stop control• Speed and voltage adjust• Local and remote emergency stop• Remote start/stop• Cycle crank

Inputs & Outputs

• Two dedicated digital inputs• Six programmable digital inputs• Six programmable form A dry contacts• Two programmable form C dry contacts• Two digital outputs

Communications • Primary and accessory CAN data links• RS-485 annunciator data link• Modbus RTU (RS-485 Half duplex)

Language Support

Arabic, Bulgarian, Chinese, Czech, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Icelandic, Italian, Latvian, Lithuanian, Japanese, Norwegian, Polish, Portuguese, Romanian, Russian, Slovak, Slovene, Spanish, Swedish, Turkish

Environmental

• Control module operating temperature: -40°C to 70°C• Display operating temperature: -20°C to 70°C• Humidity: 100% condensing 30°C to 60°C• Storage temperature: -40°C to 85°C• Vibration: Random profile, 24-1000 Hz, 4.3G rms

Low Oil Pressure•

shermae
Sticky Note
Marked set by shermae
Page 15: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

E M C P 4

LEHE0142-01

EMCP 4 RS-485ANNUNCIATOR

The EMCP 4 RS-485 annunciator serves to displaygenerator set system alarm conditions and statusindications. The annunciator has been designedfor use on the EMCP 4 RS-485 annunciator datalink for remote applications, providing customerswith enhanced site flexibility.

The EMCP 4 annunciator is configurable to thestandards of NFPA 99/110 for emergency standbygenerator systems.

FEATURES SPECIFICATIONS

● The EMCP 4 annunciator provides sixteen (16)individual points of annunciation, with two (2)LED’s included for each point.

● An additional pair of LED’s provides statusindication of the RS-485 communication network.

● Includes alarm horn with lamp test and alarm acknowledge pushbuttons.

● Configurable to NFPA 99/110 requirements forlocal and remote annunciation on emergencystandby generator systems.

● Provides custom label kit including software forcustomer’s specific alarms and arrangement

● Designed and tested to meet stringent impulseshock and operating vibration requirements

● Uses high quality shielded twisted-triad cablefor robust remote communications

● Graphic symbols are provided next to each pairto indicate various alarms and events

● The annunciator can be mounted remotelyup to 1200 m (4,000 ft).

● Provides superior visibility of the LED’s in direct sunlight

Technical Data

ElectricalBattery Voltage Functional Range: 9 to 32 VDC

Power ConsumptionMaximum: � 12 watt at 24 VDCStandby: � 5 watt at 24 VDCControl Power: 12-24 VDC

Communication: RS-485Single, 8-pin ConnectorAlarm

Sound Level 80 db

PHYSICAL

Weight 2.5 lb or � 1.13 kg

ENVIRONMENTAL

Operating Temperature –40° C to 70° C–40° F to 158° F

Storage Temperature –50° C to 70° C–58° F to 158° F

Relative Humidity 90%

CERTIFICATIONS

UL Recognized

d100mdo
Text Box
Required Control Wiring: From EMCP4.2 gen set controller to EMCP4 remote annunciator pull the following: (4) #12 stranded wired (1) Belden 9365 communications cable
Page 16: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

E M C P 4

LED COLOR SCHEME

Each pair of LED’s on the annunciator consists oftwo of three colors: green, yellow and red, whichallows for custom configuration of status, warningand shutdown conditions. The available colors and combinations are:

STANDARD LED CONFIGURATION

● Emergency stop shutdown● Overcrank shutdown● Low coolant temperature warning● High coolant temperature warning/shutdown● Low oil pressure warning/shutdown● Overspeed warning/shutdown● Low coolant level warning/shutdown● Low fuel level warning/shutdown● EPS supplying load status● Control switch not in auto warning● High battery voltage warning/shutdown● Low battery voltage warning/shutdown● BATT charger AC failure warning/shutdown● Low cranking voltage● Engine running● Tier 4 SCR

Row LED 1 LED 2

1 Red Yellow

2 Red Yellow

3 Red Yellow

4 Red Yellow

5 Red Yellow

6 Red Green

7 Red Yellow

8 Red Yellow

9 Red Yellow

10 Red Yellow

11 Red Yellow

12 Red Yellow

13 Green Yellow

14 Green Yellow

15 Red Green

16 Red Yellow

Annunciator Dimensions

A 158 mm 6.22 in

B 60 mm 2.37 in

C 288 mm 11.34 in

Information contained in this publication may be considered confidential. Discretion is recommended when distributing. www.Cat-ElectricPower.com

Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” © 2010 Caterpillar

LEHE0142-01 (05-10) trade dress as well as corporate and product identity used herein, are trademarks All rights reserved.of Caterpillar and may not be used without permission. Printed in U.S.A.

Page 17: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

LEHE0827-00 Page 1 of 5

Features

Weather Protective andSound Attenuated EnclosuresD40-2LC to D60-2LC

Picture shown may not reflect actual configuration

Enclosures

Highly Corrosion Resistant Construction• Stainless steel flush-fitting latches and hinges

tested and proven to withstand extreme conditions of corrosion

• Zinc-plated or stainless steel fasteners • Body constructed from 16-gauge steel components treated with polyester powder coating

Excellent Access• Single-side access for service and controls • Overhead door with lift-assist strut on

service side • All non-service sides have removable doors

and/or panels• Radiator fill access• Lube oil and coolant drains piped to the exterior

of the enclosure base• Large cable entry area for installation ease

Transportability• These enclosures are of extremely rugged

construction to withstand outdoor exposure and rough handling common on many construction sites.

• This range of enclosures are designed on modular principles which will aid on-site repair

Security and Safety• Lockable access doors which give full access to

control panel and breaker • Cooling fan and battery-charging alternator fully

guarded• Fuel fill, oil fill, and battery can only be reached

via lockable access• Stub-up area is rodent proof• Externally-mounted emergency stop button

Options• Weather protective enclosure • Sound attenuated enclosure – weather

protective with critical silencer• Caterpillar yellow or white paint• UL listed fuel tanks

Page 18: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Enclosures

Enclosure Sound Pressure Levels (SPL) at 100%

Sound Attenuated Enclosure Cooling Air Flow Rate SPL @ 7 m (23 ft)Model Standby eKW m3/s cfm dBA

D40-2LC 40 1.7 3602 74D50-2LC 50 1.7 3602 74D60-2LC 60 2.1 4450 75

Weather Protective Enclosure Cooling Air Flow Rate SPL @ 7 m (23 ft)Model Standby eKW m3/s cfm dBA

D40-2LC 40 1.7 3602 85D50-2LC 50 1.7 3602 86D60-2LC 60 2.1 4450 87

LEHE0827-00 Page 2 of 5

d100mdo
Rectangle
Page 19: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Enclosures

Component Weights to Calculate Package Weight

Model Standby eKW

Skid Base Weather ProtectiveEnclosure

Sound AttenuatedEnclosure

kg lb kg lb kg lbD40-2LC 40

80 176 121 267 137 302D50-2LC 50D60-2LC 60

Enclosure Dimensions on Skid Bases

LEHE0827-00 Page 3 of 5

EngineModel

Generator Set Rating

eKWEnclosure

Width “W” Length “L” Height “H”

mm in mm in mm in

C4.440

Weather Protective/Sound Attenuated 1075 42.3 1972 77.6 1378 54.350

60

WIDTH (W) LENGTH (L)

HEIGHT (H)

Page 20: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Enclosures

Enclosure Dimensions on UL Listed Sub Base Tanks

EngineModel

Generator Set Rating

eKWEnclosure

137 Gallon Sub Base Tank 255 Gallon Sub Base TankLength “L” Height “H” Length “L” Height “H”mm in mm in mm in mm in

C4.4

40 WeatherProtective/

Sound Attenuated

2503 98.5 1912 75.3 2503 98.5 2241 88.250

60

LEHE0827-00 Page 4 of 5

LENGTH (L)

HEIGHT (H)

WIDTH (W)

Page 21: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Enclosures

LEHE0827-00 (03-15)

www.Cat-ElectricPower.com©2015 Caterpillar

All rights reserved.Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,

the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

Enclosure Dimensions on UL Listed Integral Tanks

EngineModel

Generator Set Rating

eKWEnclosure

137 Gallon Integral Tank 394 Gallon Integral TankLength “L” Height “H” Length “L” Height “H”mm in mm in mm in mm in

C4.4

40 WeatherProtective/

Sound Attenuated

2503 98.5 1712 67.4 2503 98.5 2041 80.450

60

LENGTH (L)

HEIGHT (H)

WIDTH (W)

Page 22: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

LEHE0826-00 Page 1 of 2

Features

C4.4 LC Integral/Sub-base Fuel TanksNewberryDiesel Generator Set40-60 kW 60 Hz

Picture shown may not reflect actual configuration

Attachments

• UL listed for the United States UL142 and Canada ULC-S601

• Compliant with NFPA 30, 37, 110, and B139-09 standards

• Welded, heavy steel gauge construction with a containment basin sized as a minimum 110% of the tank

• Gloss black polyester triglycidyl isocyanurate (TGIC) powder coating

• Dedicated external customer interface area with access to the 4" (101.6 mm) fuel fill, visual level gauge, normal and emergency vents

• Rear electrical stub-up area with removable access panel

• Removable engine supply and return dip tubes • Two additional 1" (25.4 mm) ports for customer

use • Tanks are rated to safely support the weight of

the generator • Standard NPT tank fittings • UL listed emergency vents sized as per UL

standards 3" (76.2 mm) NPT • Normal atmospheric vent 1-1/4" (31.75 mm) • Top-mounted fuel level sensor with control

panel alarms • Top-mounted leak detection switch • Lockable fuel fill cap, 4" (101.6 mm) NPT

Description • Dual wall, secondary containment • Pressure tested to UL requirements • Fuel tank mounts directly below generator

skid base• Sub-base fuel tank mounts directly below

generator skid base• Integral fuel tank is incorporated into the

generator set base frame including linear vibration isolators between tank base, engine, and generator

• Modular tank design is compatible with all factory units open and enclosed

Options • Emergency vent and normal vent extension kits

12' (3.66 m) • 5 gal (18.9 L) spill containment • Overfill prevention valve • Tank riser to allow for visual secondary

containment leak inspection • Drop tube

Page 23: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Attachments

LEHE0826-00 (3-15)

C4.4 LC Sub-base Fuel Tank Dimensions and Capacities

Engine Model

Tank Feature Code

GeneratorSet Rating

ekW

Est.Run Time hrs

Fillable Capacity

Usable Capacity Vent Length ‘L’ Width ‘W’ Height ‘H’ Weight

(Dry)

L gal L gal in mm in mm in mm in kg lb

C4.4

INTFT140SBT140

40 36520 137 508 134 3

2483 97.8 1000 39.4

533 21.0 336 74050 2960 26

INTFT250 SBT250

40 68965 255 952 251 3 864 34.0 466 102750 55

60 49

Note: For reference only – do not use for installation design. Please contact your local dealer for exact dimensions.

www.Cat-ElectricPower.com©2015 Caterpillar

All rights reserved.Materials and specifications are subject to change without notice.

CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate and product identity used

herein, are trademarks of Caterpillar and may not be used without permission.

d100mdo
Rectangle
d100mdo
Rectangle
Page 24: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

C4.4 / C6.6 / C7.1 Circuit Breakers

LEHE0469-01 (05-14)

Manually Operated C4.4, C6.6 & C7.1 Circuit Breakers

Current(A)

Frame

Number of Poles

Interrupting Ratings (kA rms)

Trip Units

Lugs Auxiliary Options

240V 480V 600V

30 T1N 3 50 22 10

ThermalMagnetic

14 AWG-1/0

1 Form C + 1 Bell Alarm

Shunt Trip 12VDC

40 T1N 3 50 22 10

50 T1N 3 50 22 10

60 T1N 3 50 22 10

70 T1N 3 50 22 10

80 T1N 3 50 22 10

90 T1N 3 50 22 10

100 T1N 3 50 22 10

125 T3N 3 50 25 10

4 AWG - 300 kcmil

150 T3N 3 50 25 10

175 T3N 3 50 25 10

200 T3N 3 50 25 10

225 T3N 3 50 25 10

250 T4N 3 65 25 18

Electronic LS/I (S or I)

6 AWG - 350 kcmil 1 Form C + 1

Bell Alarm250VAC/VDC

Shunt Trip 12VDC

400 T5N 3 65 25 18 3/0 - 250 kcmil

600 T6N 3 65 35 20 2/0 - 400 kcmil

800 T6N 3 65 35 20 2/0 - 400 kcmil

d100mdo
Rectangle
d100mdo
Rectangle
Page 25: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Circuit Breakers

LEHE0470-00 (10-13)

Molded Case Circuit Breakers: 30A – 1200A40kW – 600kW Gensets

FeaturesConformity with International Standards

100% UL ListingThermal Magnetic Trip Units (Frames T1N and T3N) Electronic Trip Units (Frames T4N, T5N, T6N & T7S/T7M-S)Double insulationClear indication of breaker status Can be used in normal operation in an ambient of –25° C and +70° CAuxiliary contacts available

reinforced synthetic resinAnti-corrosion treatment on all metal partsOptional Dual Circuit Breakers

The T1N through T6N and T7S/T7M-S Frame Circuit Breakers have been designed to comply with these major standards:

UL 489CSA22.2 No.5IEC 60947-2

Picture shown may not represent actual package

d100mdo
Text Box
Lubna PS Gen Breaker T3N - 150 AMP
Page 26: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Circuit Breakers

LEHE0470-00 (10-13)

Manually Operated Circuit Breakers

Current(A)

Frame

Number of Poles

Interrupting Ratings (kA rms)

Trip Units

240V 480V 600V

30 T1N 3 50 22 10

ThermalMagnetic

40 T1N 3 50 22 10

50 T1N 3 50 22 10

60 T1N 3 50 22 10

70 T1N 3 50 22 10

80 T1N 3 50 22 10

90 T1N 3 50 22 10

100 T1N 3 50 22 10

125 T3N 3 50 25 10

150 T3N 3 50 25 10

175 T3N 3 50 25 10

200 T3N 3 50 25 10

225 T3N 3 50 25 10

250 T4N 3 65 25 18Electronic

LS/I (S or I)

400 T5N 3 65 25 18

600 T6N 3 65 35 20

800 T6N 3 65 35 20

1200 T7S 3 65 50 25

Electrically Operated Circuit Breakers

Current(A)

Frame

Number of Poles

Interrupting Ratings (kA rms)

Trip Units

240V 480V 600V

800 T6N 3 65 35 20Electronic

LSI 1200 T7M-S 3 65 50 25

Electronic LS/I Trip Units offer LS or LI ProtectionL-I Mode

Long Time / Overload Protection, “L“ has an adjustable trip threshold and adjustable time delay Instantaneous Short Circuit Protection, “I“ has an adjustable short circuit trip threshold and once exceeded will cause the circuit breaker to trip instantaneously

L-S ModeLong Time / Overload Protection, “L“ has an adjustable trip threshold and adjustable time delay Short Circuit Protection, “S“ has an adjustable short circuit trip threshold and adjustable time delay if necessary for coordinating with downstream loads Instantaneous Short Circuit Protection, “I“ is still included, but the threshold level is not adjustable and exists at a predetermined level

d100mdo
Rectangle
Page 27: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Circuit Breakers

LEHE0470-00 (10-13)

t [s]

1x I 1

10

10-1

10-2

102

1

10

102

103

104

10-1

125 ÷225A

T3 225 – TMFIn = 125 ÷ 225 A

Page 28: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

G E N E R A T O R S

AVR12 – PERMANENTMAGNET GENERATOR

The permanent magnet generator (PMG) optionupgrades the excitation system of the generatorfrom the standard self-excited system to aseparately-excited system. The PMG couples tothe non-drive end of the generator and providesan independent source of excitation power thatensures initial voltage build-up. The PMG improvesthe voltage response of the generator duringtransient load application, such as motor starting,and provides a sustained short-circuit current forthe operation of protective devices. Isolation ofthe excitation power ensures that regulation isnot affected by non-linear distorting loads.

www.cat-ElectricPower.comMarket: N. America

Information contained in this publication may be considered confidential. © 2005 Caterpillar LEHE4015 (01-05) Discretion is recommended when distributing. All Rights Reserved.

Materials and specifications are subject to change without notice. Printed in U.S.A.

Page 29: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

INTEGRATED VOLTAGEREGULATOR

LEHE0448-00

FEATURESWhen used with an Excitation Module, EMCP 4.3/4.4 and IVR-compatible EMCP 4.1/4.2 controllers o

Automatic Voltage Regulation (AVR)

Programmable stability settings

Soft start control with an adjustable time setting in AVR control mode

Hz) regulation

Three-phase or single-phase generator voltage (RMS) sensing/regulation in AVR mode

Setpoint adjustment from the EMCP display or Cat® ET Service Tool

IVR Operating Status and Voltage Bias Overview screens to provide an enhanced level of user interface

Integrated Voltage Regulator event monitoring

EMCP 4.3/4.4 and IVR-compatible EMCP 4.2 controllers also o

Power Factor Regulation (PF)

Reactive Droop compensation

Line drop compensation

COMPLETE SYSTEM INTEGRATIONFully designed and factory tested to work seamlessly with Cat generators using Self Excitation (SE), Internal Excitation (IE) or Permanent Magnet (PMG) excitation systems and EMCP controls.

INTEGRATED VOLTAGE REGULATOR

The Integrated Voltage Regulator (IVR) is designed to provide robust, precise closed-loop control of the generator voltage, optimized transient performance and industry leading feature specification.

Caterpillar is leading the power generation marketplace with power solutions engineered to deliver unmatc y, expandability, reliability and cost-e iveness.

Generator

Voltage & CurrentSensing

ExcitationCurrent

ExcitationCommand

Genset Controlwith IVR Logic

ExcitationModule

Integrated Voltage Regulator

WORLDWIDE PRODUCT SUPPORT Worldwide parts availability through the Cat dealer network

Over 1,800 dealer branch stores operating in 200 countries

The best product support record in the industry

Cat dealers provide extensive post sale support includingmaintenance and repair agreements

Page 30: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

EMCP 4.1 EMCP 4.2 EMCP 4.3 EMCP 4.4

SPECIFICATIONS

No Load to Full Load Regulation ±0.5% ±0.25% ±0.25% ±0.25%

Regulator Response Time 10 ms 10 ms 5 ms 5 ms

Single and Three Phase Sensing

Voltage Adjustment Range ± 30% ± 30% ± 30% ± 30%

CONTROL

Characteristic

Excitation Enable / Disable Selection

Line Loss (I2R) Compensation –

Reactive Droop Compensation –

Power Factor Control Mode –

PROTECTION / ALARMS

Generator Overvoltage

Generator Undervoltage

Over Excitation

Loss of Sensing

Generator Reverse VARs –

Event Log

METERING

EMCP AC Metering

EMCP Power Metering –

Excitation Command Percentage

Operating Mode Status Indication

INTEGRATED VOLTAGE REGULATOR FEATURE SPECIFICATION

2

INTEGRATED VOLTAGEREGULATOR

LEHE0448-00

d100mdo
Rectangle
Page 31: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

EMCP 4.1 EMCP 4.2 EMCP 4.3 EMCP 4.4

VOLTAGE ADJUSTMENT

EMCP 4 Display Voltage Bias

Digital Input (Raise / Lower) Voltage Bias1

Potentiometer Voltage Bias1

Analog Voltage Bias – Voltage Range1 0V to 5V 0V to 5V -10V to +10V -10V to +10V

Analog Voltage Bias – Current Range1 – – 0mA to 20mA 0mA to 20mA

Analog Voltage Bias – PWM Range1 – – 0% to 100% 0% to 100%

SCADA (Modbus) Voltage Bias –1Requires an available input on the EMCP 4.

INTEGRATED VOLTAGE REGULATOR FEATURE SPECIFICATION (continued)

3

INTEGRATED VOLTAGEREGULATOR

LEHE0448-00

Page 32: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

The Integrated Voltage Regulator consists of an EMCP 4 interfacing with an Excitation Module. There are a range of Excitation Modules available to match Cat generator sets.

EXCITATION MODULE TECHNICAL SPECIFICATION

EM10 EM15

Compatible Generator Excitation Types Self Excitation (SE)Internal Excitation (IE)

Permanent Magnet (PMG)

Nominal Field Current Output 6 Amps 7 Amps

Maximum (forcing) Field Current Output 10 Amps 15 Amps

Maximum AC Voltage Input 180 Vrms 240 Vrms

For more information on the Excitation Module refer to the component spec sheet.

Figure 1: Figure 2:

EM10 Excitation Module EM15 Excitation Module

EXCITATION MODULE SPECIFICATION

4

INTEGRATED VOLTAGEREGULATOR

LEHE0448-00

d100mdo
Rectangle
Page 33: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

INTEGRATED VOLTAGEREGULATOR

Figure 3: IVR Overview Screen

Figure 4: Voltage Bias Overview Screens

Figure 5: IVR Overview Screen Figure 6: Voltage Bias Overview Screen

EMCP 4 DISPLAY

EXAMPLE SCREENS – EMCP 4.1/4.2

EXAMPLE SCREENS – EMCP 4.3/4.4

www.Cat-Electric Power.com©2013 Caterpillar

All rights reserved

Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.

CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the“Power Edge” trade dress, as well as corporate and product

identity used herein, are trademarks of Caterpillar and may not beused without permission.

LEHE0448-00 (08/13)

Page 34: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

A T T A C H M E N T S

LEHE0143-01

UL 10 AMPBATTERY CHARGER

60 Hz Only

This battery charger offers accurate, automatic charging of lead-acid and nickel cadmium batteries. The output voltage automatically adjusts to changing input, load, battery and ambient conditions. This prevents battery over-charging and consequent loss of battery electrolyte.Standard features include AC line compensation, precision voltage regulation, current limiting, automatic 2-rate charging, voltmeter and ammeter, temperature compensation and UL Listing.The user interface is easy to understand with digital metering, NFPA 110 alarms and a battery fault alarm.

Picture shown may not represent actual unit.

Specification FeaturesInput Supply 110-120 V 208-240 V AC and DC Fuses (2 input and 2 output)Output voltage 12VFrequency 60 HzOperating temperature -20°C( -4°F) to +60°C (140°F)Housing constructed of rustproof anodized aluminum.

• Electronically current limited at 105% of rated output

• Alarm system• Digital Display• Lightning and voltage transient protection• Protection of connected equipment against load

dump protection• Constant voltage, current limited, 4-rate automatic

equalization• IP20 housing• AC isolated from DC• Temperature compensation• On board temperature sensor with remote port

Standards• C-UL listed to UL 1236• NFPA 70, NFPA 110• CSA 22.2 No 107 certified• UL 1564• CE DOC to EN 60335• IBC Seismic Certification

Page 35: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

A T T A C H M E N T S

LEHE0143-01

Information contained in this publication may be considered confidential.Discretion is recommended when distributing.

Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress, as well as corporate and product identity used herein, are trademarks

of Caterpillar and may not be used without permission.

www.Cat-ElectricPower.com

© 2014 CaterpillarAll Rights Reserved.

Printed in U.S.A.

LED IndicationIn normal operation, the four circuit board LEDs indicate operating status: fault conditions, charge mode, temperature compensation and AC supply.

LED Operation Status

Red on Fault condition (except AC supply & battery connection errors)

flashing slow AC Supply not available (DC connected)

flashing fast Battery connection error

off No fault conditions

Yellow on In float mode

flashing slow In autoboost mode

flashing fast In AutoBoost extension mode / boost decay

off Output off / output to nominal

Blue on Temperature compensation active

flashing slow Temperature compensation auto disabled due to external fault

flashing fast Temperature compensation at absolute limit I.e. <-10ºC or >+50ºC

off Temperature compensation disabled

Green on AC supply available, charge output on

flashing slow AC supply available, charge output off

flashing fast Boost decay or battery missing (if red LED is also on)

off AC supply not available

Output Input

Amps Volts Hz Volts

10 12 60 110 - 120208 - 240

Width Depth Height Weight

165mm (6.5 in) 125 mm (4.9 in) 300 mm (11.8 in) 2.1 kg (4.6 lb)

Feature Code

PBC10NU

d100mdo
Rectangle
Page 36: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

A T T A C H M E N T S

LEHE4035-06

FEATURES

l Molded from Polyphenylene Sulphide l Rust free, corrosion resistant with exceptional tensile

strength l Vibration and shock tested to extreme limits to ensure

durabilityl Compatible with all coolant additives l Incoloy element for longer service life

COOLANT HEATERWHH

Appropriate when the generator set is to be sited in a low ambient environment, the heater maintains the engine coolant at a temperature [typically 38°C (100°F)] which facilitates rapid starting and load acceptance. The heater assembly uses UL compliant components (to UL1030) and has CSA certification which is to both CSA and UL Standards.

The heater itself is powered by a 110/120 volt (VAC 120) AC auxiliary supply protected by a safeguard breaker inside the main control panel. A thermostatic controller is included to regulate the output temperature to within safe limits. When the generator set is not running the heater is automatically connected to the AC supply through a power relay mounted in the control panel. Upon receiving a start signal the AC supply is automatically disconnected by the power relay and automatically reconnected when the start signal is removed and the engine has stopped.

Page 37: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

A T T A C H M E N T S

LEHE4035-06 (06/14)

www.Cat-ElectricPower.com

© 2014 CaterpillarAll rights reserved.

Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.

CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the“Power Edge” trade dress, as well as corporate and product

identity used herein, are trademarks of Caterpillar and may not be used without permission.

VAC 120

Diesel Generator Set ModelsNominal Coolant Heater Power

Consumption (Watts)

3 Phase

XQ20, XQ30, XQ45, XQ60, XQ80, XQ100 1000

D40-6, D50-6, D60-6, D80-6, D100-6 1000

D125-6, D150-8, D175-2, D200-2 1800

Single Phase

D40-6S, D50-6S, D60-8S, D80-2S, D100-6S 1000

d100mdo
Rectangle
d100mdo
Text Box
D40-2LC
Page 38: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

TOWN OF CHRISTIANSBURG

-LUBNA PUMP STATION

Automatic Transfer Switch

Customer: Carter Machinery Submittal Date: June 9, 2015

Submittals for Approval Tel. # 571-313-8041

ASCO Power Technologies L.P Baltimore / Washington Sales Office

12310 Pinecrest Rd. Suite 204 Reston, VA 20191

Page 39: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

We Keep Your Power On June 9, 2015 ASCO POWER TECHNOLOGIES L.P, BALTIMORE/MARYLAND SALES OFFICE 12310 PINECREST RD SUITE 204 RESTON, VA 20190 TEL # 571-313-8041 FAX # 703-342-0391

Automatic Transfer Switch Bill of Material TOWN OF CHRISTIANSBURG – LUBNA PUMP STATION

Note: Standard Lead Time: 4 weeks after final release

ATS DESIGNATION

QTY

AMPS/ POLES

BYPASS

TRANSITION

CATALOG NUMBER

OPTIONAL ACC.

ENCL. DRG.

WIRING DRG. BOM

- 1 260/3 NO OPEN E03ATSA30260CG0G STANDARD FEATURES 978732-001 978743 1083070

Page 40: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO Order Voltage Confirmation Sheet To ensure the accuracy of your order, it is important that we confirm the voltages for all line items. This confirmation should be independent of the voltage shown in the ASCO proposal. Please check the box for each line to confirm the information shown is accurate. Please initial and date at the bottom of this form to acknowledge your approval. Customer: ___________________________ Location: ______________________ P.O. #: ___________________________ Project Name: ______________________ Item #1: Cat. #: _________________________________ Voltage:________ V Item #2: Cat. #: _________________________________ Voltage:________ V Item #3: Cat. #: _________________________________ Voltage:________ V Item #4: Cat. #: _________________________________ Voltage:________ V Item #5: Cat. #: _________________________________ Voltage:________ V _______________________________ __________ ____________ Customer Name (printed) Initial Date

Page 41: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

06/09/15

Town of Christiansburg – Lubna Pump Station ATS Detailed Information

# 1

ATS

AMPS : 0260

QTY : 1

Bulletin Number : Series 3ATS Transfer Switches Catalog Number : E03ATSA30260CG0C

Service Voltage / Hz : 208V/60Hz Optional Accessories :

By-pass Isolation : Not Applicable Product Description : Open Transition Series 3ATS No. of Switched Poles : 3

Neutral Configuration : Solid [A]

Withstand Rating : See WCR table below

Frame = E, Switch Rating = 0260, Series = 300

No. of Cables & Lug : 1, #4 AWG to 600 MCM or (2) 1/0 Size AWG to 250 MCM

Enclosure : 1(C)-UL Type 1 enclosure Service : Three Phase, 4-wire

DRAWINGS FOR APPROVAL

Drawing Number Description

978732-001 Composite Enclosure Outline and Mounting Diagram

978743 Three-Phase Wiring Diagram

Page 42: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

ASCO®

Page 43: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

ASCO ®

ENGINE CONTROL CONTACTS

LOAD DISCONNECT FEATURE

COMMON ALARM & NOT IN AUTO SIGNALING FEATURES

INPHASE TRANSFER FEATURE FOR LOAD TRANSFER

SOURCE AVAILABILITY SIGNALS

EXTERNAL POWER SUPPLY COMPATIBILITY

LOAD CURRENT METERING

NON-AUTOMATIC (MANUAL) OPERATION

FOUR-FUNCTION SOFTWARE BUNDLE

REMOTE CONTROL FEATURES

ASCO®

Page 44: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

Page 45: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

Page 46: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

Page 47: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

Page 48: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

ASCO®

Page 49: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,
Page 50: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

2

24-hour protection no matter when trouble strikes

generator and an automatic transfer switch (ATS) which transfers the load from the utility to the generator. An ATS with built-in control logic monitors your normal power supply, senses interruptions and unacceptable abnormalities. When the utility power fails, the ATS automatically starts the engine and transfers the load after the generator has reached proper voltage and frequency. This happens in a matter of seconds after the power failure occurs. When the utility power has been restored, the ATS will automatically switch the load back, and after a time delay, it will shut down the engine. With an Automatic Transfer Switch, you are protected 24 hours a day, seven days a week.

Where would you be without a constant flow of electrical power? We often take for granted that power will always be around when we need it. In reality, power failures are very common. And when the power goes out, your business suffers. Power failures are unpredict-able. They can occur at any time and for any number of reasons—a bolt of lightning, a power surge, a blackout, an accident or even equip-ment failure. They come without warning and often at the most inconvenient times. It’s for this reason that many businesses and other entities have invested in emergency power backup systems. Typically, the sys-tem consists of an engine

ASCO Series 300Power Transfer Switches for Power Outage Protection

Page 51: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

3

Typical Applications

Telecom In the telecommunications industry, providing a high level of service and dependability is crucial. Lost power means an interruption in service for your customers and lost business for your company. For instance, with cell sites scattered across a wide geographical region and in many remote areas, the chances of an interruption in power are increased, making Automatic Transfer Switches a valuable resource at each location. To maintain dependable service, each cell site must be monitored 24 hours a day. This can be very difficult without some type of remote monitoring and testing capability. The SerieS 300 Transfer Switch, combined with ASCO’s monitoring and control management system, is a cost-effective, packaged solution which can help meet both of these challenging objectives without a major investment at each cell site. With ASCO’s connectivity solutions you can remotely monitor and control numerous sites from around the corner or around the world.

AgricultureMaintaining electrical power is vital to an agriculture opera-tion. If the flow of power is interrupted, your operation could be at risk unless the backup generator is quickly activated. A prolonged power outage can affect numerous aspects of the operation, from housing and feeding livestock to processing and produc-ing the end product. With an ASCO SerieS 300 Transfer Switch, power will automatical-ly be transferred over to your backup generator, eliminating the need to manually switch from utility to generator. When power is restored, the ASCO SerieS 300 Transfer Switch will, after an adjustable time delay to allow for utility stabilization, automatically switch the load back to the utility service.

Commercial / Retail, Light IndustrialThe retail industry is very com-petitive. An electrical power failure can have a dramatic impact on a retailer’s bottom line. If power is interrupted during peak shopping times, the effect could be extremely damaging to present and future business. A power inter-ruption will not only suspend shopping, it can also create safety problems, result in lost transaction data, lost account information and damage to data collection equipment. In addition, retailers who rely on controlled climates to protect valuable inventory could suffer even greater losses, especially if the power failure occurs at a time when no one is avail-able to rectify the situation. To avoid any of these power out-age problems, simply install a backup generator with an ASCO SerieS 300 Transfer Switch and power outage concerns will be a thing of the past.

Municipal The ASCO SerieS 300 Transfer Switch can be a critical com-ponent of a municipal gov-ernment’s emergency power backup system. Residents of townships, cities and counties rely on police, fire, ambu-lance/first aid and other critical public sector services. An inter-ruption in power would affect the ability of emergency ser-vices to effectively respond to the needs of the community. When time is a critical factor, such as when responding to a fire alarm or an emergency call, an ASCO SerieS 300 Transfer Switch can be a lifesaver, switching power to the backup generator. While not all munic-ipal services are a matter of life and death, they are always expected to be there.

Page 52: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

30 through 3000 amps in a compact design. Available to 600 VAC, single or three phase. True double-throw operation: The single solenoid design is inherently inter-locked and prevents contacts from being in contact with both sources at the same time.

There’s no danger of the SerieS 300 ATS transferring loads to a dead source because the unique ASCO single-solenoid operator derives power to operate from the source to which the load is being transferred. Easy to navigate 128x64 graphical LCD display with keypad provides LED indicators for switch position, source availability, not in auto, and alert condition. Integrated multilingual user interface for configuration and monitoring. Delayed transition operation is now available (Dual Operator Configuration). Relay expansion module with extra relays for accessory outputs (Optional). Includes soft keys for test function and time delay bypass as standard features. Historical event log (Optional). Statistical ATS system monitoring information. Diagnostic Functions. Password protection to prevent unauthorized tampering of settings. Adjustable time-delay feature prevents switch from being activated due to momentary utility power outages and generator dips.

Supplied with solid neutral termination. Optional switched neutral pole available.

Field modification accessory kits available. Available for immediate delivery.

UL Listed Withstand & Close-On Ratings

Maximum Reliability & Excellent ValueWith a SerieS 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually every major technological advance in the Transfer Switch industry.

The ASCO SerieS 300 was designed for one purpose–to automatically transfer critical loads in the event of a power outage. Each and every standard component was designed by ASCO engineers for this purpose. The SerieS 300 incorporates the Group G controller with enhanced capabilities for dependable operation in any environment. A user friendly control interface with a 128x64 graphical LCD display and intuitive symbols allow for ease of operation while visual LED indicators verify transfer switch status. Operating parameters and feature settings can be adjusted without opening enclosure door.

The rugged construction and proven performance of the ASCO SerieS 300 assure the user of many years of complete reliability. The SerieS 300 is even designed to handle the extraordinary demands placed on the switch when switching stalled motors and high inrush loads.

ASCO’s SerieS 300 modular, compact design makes it easy to install, inspect and maintain. All parts are accessible from the front so switch contacts can be easily inspected.

Features The SerieS 300 is listed to UL 1008 standard for total system loads and CSA standard C22.2 for automatic transfer switches. Meets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) Articles 700, 701 and 702. Controller is RoHS compliant (Restriction of Hazardous Substances).

4

30 100,000 480v/60Hz 10,000 70 - 200 200,000 480v/60Hz 22,000 230 100,000 480v/60Hz 22,000 260, 400 200,000 480v/60Hz 42,000 150, 200, 230 200,000 600v/60hz 42,000 260, 400 200,000 480v/60Hz 50,000 Series 3ADTS only 200,000 240v/60Hz 65,000 600 200,000 600v/60Hz 42,000 600 200,000 480v/60Hz 50,000 600 200,000 240v/60Hz 65,000 800,1000,1200 200,000 600v/60Hz 65,000 1600, 2000 200,000 600v/60Hz 85,000 2600, 3000 200,000 600v/60Hz 100,000

Switch RatingsAmps

Available Symmetrical Amperes RMS

When Used With Current

Limiting Fuses

Maximum Voltage

When Used With Specific

Circuit Breakers

Notes: 1. Current limiting fuse should be class J type through 400 amps: use Class L type above 300 - amp fuse rating Current limiting fuse for 3ADTS only 150 - 400 amp should be Class L type

2. Refer to publication 1128 for specific manufacturer ’s breakers

series 300 Power Transfer Switches

Fig. 1: ASCO Power Transfer Switch rated 200 amperes

Page 53: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Designed to Fit AnywhereThe ASCO SerieS 300 product line represents the most compact design of automatic power transfer switches in the industry. With space in electrical closets being at a premium, the use of wall or floor-mounted ASCO Power Transfer Switches assures designers optimum utilization of space.

All transfer switches through 2000 amps are designed to be completely front accessible. This permits the enclosures to be installed flush to the wall and still allows installation of all power cabling and connections from the front of the switch. Cable entrance plates are also standard on the 1600 and 2000 amp units to install optional side-mounted pull boxes for additional cable bending space.

5

series 300 Power Transfer Switches

Fig. 2: ASCO Power Transfer Switch rated 200 amperes

Fig. 3: ASCO Power Transfer Switch rated 400 amperes

Fig. 5: ASCO Power Transfer Switch rated 1000 amperes

Fig. 6: ASCO Power Transfer Switch rated 2000 amperes shown in Type 3R enclosure

Fig. 7: ASCO Power Transfer Switch rated 3000 amperes

Fig. 4: ASCO Power Transfer Switch rated 600 Amperes

Page 54: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

The ASCO Service Entrance Power Transfer Switch combines automatic power switching with the necessary disconnecting, grounding, and bonding required for use as service entrance equipment. The power transfer switch meets all National Electrical Code requirements for service entrance use. Transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source.

ASCO SerieS 300SE products use two types of construction.

Products 400 amperes or less, utilize a single enclosure including a service (utility source) disconnect circuit breaker, as well as the power transfer switch, grounding and bonding provisions.

Products 600 amperes and above, utilize a multi-section switchboard construction including a service equipment section containing the service (utility source) disconnect circuit breaker, grounding, and bonding provisions. A second section contains the power transfer switch.

Fig. 16: ASCO SerieS 300 SE Rated 800 amperes Type

1 enclosure with Service Entrance Equipment

Fig. 17: ASCO SerieS 300 SE rated 200 amperes in Type 1 enclosure with single source

breakers

Product Features: Suitable for use as service entrance equipment. Listed to UL 891 (standard for switchboards) for 600 - 3000 amps, sizes and UL 1008 (standard for panel-boards) for 70 - 400 amps. Automatic Transfer Switch is listed to UL 1008 for total system loads Sizes available from 70 - 3000 amps, 600 VAC, 50 or 60 Hz, single or three phase Silver plated copper ground and neutral bus solderless screw type terminals Ground fault trip protection provided on sizes 1000 amps and above Available with solid or switched neutral

series 300SE Power Transfer Switch

+ + + + + + +B

3AUS

4003 N 1 X C + + 240 V/60

2 poles, 1Ø

3 poles, 3Ø

A3

B3

CDEFHJKLMNQR

1 Insert “X” If optional

accessories are required

Product

B1

Switched Neutral

NeutralCode

PhasePoles

AmperesContinuous

Rating

VoltageCode

Controller

11BG Programmable Engine

Exerciser

14AA/14BA Auxiliary Contacts

(2 sets)

44G Strip Heater

w/Thermostat

72A

Serial Module

72E Connectivity Module

73A Surge Suppressor

Optional Accessories

This information is necessary

to allow correct control

settings prior to shipment

Specific Volt & Freq

Options EnclosureBlank Open Type

11CD

115120208220230240380400415440460480575600

To order an ASCO series 300SE Power Transfer Switch, complete the following catalog number:

Notes: 1. Specify neutral code “C” for 250 and 400 amperes only. 2. Available 70-1000 ampacity. Use Type 3R for 1200-3000 amp applications. 3. 115-120 volt available 150-400 amps only. 4. A solid neutral is standard on 3AUS. 5. For switch sizes 70 - 225 amperes only.

3AUS

70, 100,150, 2006, 2256, 250, 400, 600,

800, 1000, 1200, 1600,

20002500, 3000

series 300SE Transfer Switch Ordering Information

6. 200, 225 amp rated switch suitable for use with copper cable only.7. Type 316 Stainless Steel is standard. It provides an improved reduction in corrosion of salt and some chemicals. It is the preferred choice for marine environments.8. Available only on switches rated 1200, 2000, 2600, and 3000 Amps.

12

70 - 400 Amp Construction

600 - 3000 Amp Construction

Type 1 (Standard)

Type 3R

Type 42

Type 4X

Type 122

Type 3R Secure

Type 4 Secure

Type 4X6

SecureDouble Door SS

Type 3RX7,8 SecureDouble Door SS

C

F G

L M

N

H

P

R

Cristina.DelaCruz
Rectangle
Page 55: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Control and Display Panel Easy to navigate 128x64 graphical LCD display

with keypad provides LED indicators for switch position, source availability, not in auto, and alert condition. It also includes test and time delay bypass soft keys.

Voltage & Frequency Sensing 3 — Phase under and over voltage settings on normal and

single phase sensing on emergency source. Under and over frequency settings on normal and emergency. True RMS Voltage Sensing with +/-1% accuracy

Frequency Sensing Accuracy is +/- 0.1Hz Voltage and Frequency parameters adjustable in 1% increments Selecting settings : single or three phase voltage sensing on normal, and single phase sensing on emergency; 50 or 60 Hz Load current sensing card (Optional)

Time Delays Engine start time delay – delays engine starting signal to

override momentary normal source outages – adjustable to 0 to 6 seconds (Feature 1C)

Transfer to emergency time delay – adjustable 0 to 60 minutes (Feature 2B) Emergency source stabilization time delay to ignore momentary transients during initial generator set loading – adjustable 0 to 4 seconds (Feature 1F) Re-transfer to normal time delay – adjustable 0 to 10 hours (Feature 3A) Unloaded running time delay for engine cooldown – adjustable 0 to 60 minutes (Feature 2E) Pre and post signal time delay for selective load disconnect with a programmable bypass on source failures – adjustable 0 to 5 minutes (specify ASCO Optional accessory 31Z) Optional fully programmable engine exerciser with seven independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi weekly or monthly basis (Specify ASCO optional accessory feature bundle 11BE) Delay transition load disconnect time delay – adjustable 0 to 5 minutes.

Standard Selectable Features Inphase monitor to transfer motor loads, without any

intentional off time, to prevent inrush currents from exceeding normal starting levels.

Engine exerciser to automatically test backup generator each week—with or without load 20 minutes not adjustable. Commit to transfer. Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and re-transfer. 60Hz or 50Hz selectable switch. Three – phase/single - phase selectable switch.

Remote Control FeaturesExternal Inputs for connecting: Remote test switch. Remote contact for test or for peak shaving applications.

If emergency source fails, switch will automatically transfer back to normal source if acceptable. Inhibit transfer to emergency Remote time delay bypass switch emergency to normal

Fig. 8: ASCO SerieS 300 Microprocessor Controller

The SerieS 300’s incorporate the group “G” controller with enhanced capabilities for dependable operation in any environment.

Controller/TSInterface Plug

Battery to Maintain Engine Exerciser

Clock Settings

Dip Switches forVoltage/Frequency

and Feature Functions

Customer ControlInterface

2) SE and ER Relay

Performance Features 600 volt spacing per UL and CSA standards. Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).

IEEE C37.90

IEC 61000 – 4 - 2 Electrostatic Discharge Immunity IEC 61000 – 4 - 3 Radiated RF Field Immunity

IEC 61000 – 4 - 4 Electrical Fast Transient/Burst Immunity

IEC 61000 – 4 - 5 Surge Immunity

IEC 61000 – 4 - 6 Conducted RF Immunity

CISPR 11 – Conducted RF Emissions and Radiated RF Emissions

Control PowerTransformers

Mounting Locationfor Accessory Dongle

NR Relay

Mounting Locationfor Current Sensing Card

RS 485 Port (Optional)Enabled with Feature

Bundle 11BE

CAN Bus Port

485 Configuration Dip Switches

Power Supply Jumper Card

6

series 300 New Microprocessor Controller

Page 56: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

7

series 300 Group G Offers Sophisticated Functionality

Status

Data Logging

Fig. 9: Door-Mounted Control & Display Panel

Alarms Source

SettingsCommunication

Gen Status Engine Exerciser

The new Group G controller offers an intuitive, easy to navigate 128*64 graphical LCD display with soft keypad and provides (6) LED indica-tors

The ASCO group “G” controller is self contained with an integrated display

(no other components are required for efficient operation). The controller allows for open or delayed transition transfer operation (both au-tomatic, and non automatic configurations).

Integrated multilingual user interface for configuration and monitoring (this design

•Switch Position (green for normal, red for emergency LED)

• Source Availability (green for normal, red for emergency LED) • “Not In Auto” (amber LED)

• Common Alarm (amber LED)

approach allows greater application flexibility). Multiple source sensing capabilities of volt-age, frequency (under frequency sensing on normal and emergency sources), and optional current card, single and three phase (Does not require an external me-tering device).

6

54

3

2

1

1

LED Source Availability and Switch Position IndicatorsTransfer / Time Delay Override control pushbutton

2

Escape Key

3

4

5 Enter Key

Scroll, Up/Down Arrows

Common Alarm

6

Not In Auto Indicator

Page 57: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Fig. 13: Programmable Engine Exerciser

Fig. 10: Strip Heater Kit(Accessory 44G)

series 300 ATS Optional Accessories

Accessory 1UPUPS back up power to allow controller to run with LCD display for 30 seconds without AC power

Accessory 11BE Feature Bundle Consists of:A fully programmable engine exerciser with seven independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi – weekly or monthly basis. Engine exerciser setting can be displayed and changed from the user interface keypad. Event Log display shows the event number, time and date of event, event type, and event reason (if applicable). A maximum of 300 events can be stored. RS 485 Communications Port Enabled Common Alarm Output Contact

Accessory 18RXRelay expansion module (REX) provides for some commonly used accessory relays, includes one form C contact for source availability of normal (18G), and one contact for availability of emergency (18B) (contact rating 5 amps @ 30Vdc or @125 Vac resistive). Additional output relay is provided, the default is to indicate a common alarm. (See operator’s manual for configurable options).

Accessory 23GA1 (Single Phase), and 23GB (Three Phase) Load current metering card, measures either single or three phase load current Note1: This feature is not available with a Power Meter Option (135L)

Accessory 14AA/14BA Auxiliary contacts to indicate position of main contacts. Two (2) for normal and two (2) for emergency position (one set is standard).

Accessory 44AStrip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.

Accessory 44GStrip Heater with thermostat, wired to load terminals: 208-240, 360-380, 460-480, 550-600 volts. Contains wiring harnesses for all transfer switch sizes.

8

Field Conversion Kits for series 300 Transfer SwitchesKit No. Description

935147 Feature Bundle Includes Engine Exerciser/Event Log/RS 485/ Common Alarm Output Contact (Acc. 11BE) Dongle

935148 REX Module with Source Availability Contacts (Acc. 18RX)

935149 UPS to allow controller to run for 3 minutes minimum with AC Power935150 1/3 Phase load current sensing card only (Acc. 23GA/GB)

K613127-001 Strip Heater (125 watt) 120 volt (Acc.44A)K613127-002 Strip Heater (125 watt) 208 - 480 volt (Acc.44G) 948551 Quad - Ethernet Module (Acc. 72EE) K60927 Cable Pull Box (1600 - 2000 amp)

Accessory 72EEConnectivity Module, enabling remote monitoring and control capabilities (Pages 12-14)

Accessory 31ZSelective load disconnect circuit to provide a pre – transfer and/or post transfer signal when transferring from emergency to normal and/or normal to emergency. Accessory 73Surge Suppressor (TVSS) Rated 65kA Accessory 62WAudible alarm with silencing feature to signal each time switch transfers to emergency (City of Chicago requirement) Accessory 37B6’ Extension harness for units shipped open type to accommodate customer mounting of controls and switch Accessory 37C9’ Extension harness for units shipped open type to accommodate customer mounting of controls and switch

Accessory 135L2

Power Meter on load side (Includes shorting block and CT’s)Note2: This feature is not available with Load Current Metering Option (23GA, or 23GB)

Accessory 30AA3

Load – shedding circuit initiated by opening of a customer – supplied contact

Accessory 30BA3

Load – shedding circuit initiated by removal of customer – supplied voltage (* Specify voltage) Note3: Accessory 30AA, and 30BA are only available for 3ADTS (Automatic Delayed Transition Transfer Switch )

Fig. 11: Relay Expansion Module (Accessory 18RX)

Fig. 12: Load CurrentCard (Accessory 23GA/GB)

Fig. 14: Accessory 1UPUPS Backup Power

Page 58: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Series 300 Non-Automatic Transfer Switching (3NTS)ASCO non-automatic transfer switches are generally used in applications where operating personnel are available and the load is not an emergency type requiring automatic transfer of power. They can also be arranged for remote control via ASCO’s connectivity products.

Fig. 15: ASCO 3NTS 400 AmpType 1 Enclosure

3NTS Features: ASCO Non-Automatic Transfer Switches are electrically held, manually initiated via soft keys on the user interface panel. Non-automatic operation can be selected using the key pad without opening enclosure door. Sizes from 30 through 3000 amps. Microprocessor based controller provides for addition of optional accessories. Controller prevents inadvertent operation under low voltage condition. Source acceptability lights inform operator if sources are available to accept load. Source inphase monitor to transfer motor loads between live sources. One auxiliary contact closed when transfer switch is connected to normal and one closed on Emergency standard feature 14A/14B

series 300 Power Transfer Switches

9

3ADTS/3NDTS Features: Sizes from 150 through 3000 amps. Reliable field proven dual solenoid operating mechanisms. Mechanical interlocks to prevent direct connection of both sources. Adjustable time delay for load disconnect (0 to 5 minutes). Available in manual operation configuration (3NDTS). Available with optional load shed feature for 3ADTS.

Series 300 Delayed Transition Transfer Switching (3ADTS/3NDTS)ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time.

Fig. 16: ASCO 3ADTS/3NDTS 400 AmpType 1 Enclosure

Page 59: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

series 300 Transfer Switch Ordering Information

10

Extended Warranties for series 300 Transfer Switches (3ATS/3NTS/3ADTS) Catalog No. Description

3EXW300 Three-Year Extended Warranty (Parts & Labor)

4EXW300 Four-Year Extended Warranty (Parts & Labor)

5EXW300 Five-Year Extended Warranty (Parts & Labor)

series 300 External Power ConnectionsSizes UL-Listed Solderless Screw-Type Terminals

Notes: 1. All SerieS 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. 2. 200 and 230 amp rated switches for use with copper cable only. Refer to paragraph 310.15 of the NEC for additional information. 3. Use wire rated 75oC minimum for all power connections.

Switch Rating(Amps)

Ranges of AL-CU Wire Sizes(Unless Specified Copper Only)

One #14 to 4/0 AWG

Two 1/0 AWG to 250 MCM or One #4 AWG to 600 MCM

Two 2/0 AWG to 600 MCM

Four 1/0 to 600 MCM

Six 1/0 to 600 MCM

Twelve 3/0 to 600 MCM

30 - 2302

260, 400

600

800, 1000, 1200

1600, 2000

2600, 3000

Notes: 1. Specify neutral code “C” for 260 and 400 amperes only for 3ATS/3DTS 2. Available 30-600 ampere size switches available in non - secure type enclosures 3. 115-120 volt available 30-400 amps only. For other voltages contact ASCO.

4. 200 and 230 amp rated switches for use with copper cable only. 5. Switch sizes 800 - 3000 ampere, and 150 - 400 ampere

3ADTS/3NDTS provided in secure type outdoor enclosures when required.

6. Use 3R for 1200, 2000, 2600, and 3000 7. Type 304 stainless steel is standard. Suitable for indoor

or outdoor use where there may be caustic or alkali chemicals in use. To provide an improved reduction in corrosion of salt and some

chemicals, optional type 316 stainless steel is recommended. This is the preferred choice for marine environments.

+ + + + + +A

A

N

ATS 3 600 N + + C

TS

DTS

G GX

Optional Accessories

Type 1 (Standard)

Type 3R Non-Secure2

Type 42

Non-Secure

Type 4X2

Non-Secure

Type 122

Non-Secure

Type 3R Secure

Type 4 Secure Type 4X Secure

Double Door 304 SS

Type 12 Secure

Double Door Type 3RX7,8

Secure Double Door 304 SS

Automatic

Non- Automatic

Product Neutral Code

Phase Poles

Controller Code

Enclosure

C

F

G

H

L

M

N P

Q

R

GX

To order an ASCO series 300 Power Transfer Switch, complete the following catalog number:

3

Conventional 2 Position

Delayed Transition

A

B1

Solid Neutral

Switched Neutral

2 Poles 1

3 Poles 3

o

o

Amperes

Continuousrating

302, 702, 1042, 1505, 2004,5,

2302,4,5, 2602,5,4002,5, 6005, 8005, 10005,

12005, 16005, 20005, 26005,

30005

A3

B3

CDEFHJKLMNQR

VoltageCode

115120208220230240380400415440460480575600

8. Available on switches rated 1200, 2000, 2600, and 3000 amps. 9. When temperatures below 32oF can be experienced, special precautions should be taken, such as the inclusion of strip heaters,

to prevent condensation and freezing of this condensation. This is particularly important when environmental (Type 3R,4) are

ordered for installation outdoors. 10. Extra shelter protection should be considered for wind blown rain

and snow, since ventilated type 3R enclosures due not protect against these conditions.

Page 60: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

UL Type 1 Enclosure1,2,3,4,5

Switch RatingAmps

Phase Poles

Neutral Code

Dimensions, In. (mm)Width Height Depth

Approx. ShippingWeight Lb. (kg)

2233223322332233223322333333

304,704,1004*,1044

1504, 2004

2303, 260, 400

150,200,230, 260,400

SerieS 3ADTS/3NTS only

600

800, 1000

1200

1600, 20001

2600, 30002

ABABA

B3 or CA

B3 or CABABAB AB ABABABABABAB

18(457)18(457)18(457)18(457)18 (457)18 (457)18 (457)18 (457)24(610)24(610)24(610)24(610)24 (610)24 (610)24 (610)24 (610)34 (864)34 (864)34 (864)34 (864)38 (965)38 (965)38 (965)38 (965)38 (965)38 (965)38 (965)38 (965)

31 (787)31 (787)31 (787)31 (787)

48 (1219)48 (1219)48 (1219)48 (1219)56(1422)56(1422)56(1422)56(1422)63 (1600)63 (1600)63 (1600)63 (1600)72 (1829)72 (1829)72 (1829)72 (1829)87 (2210)87 (2210)87 (2210)87 (2210)87 (2210)87 (2210)91 (2311)91 (2311)

13 (330)13 (330)13 (330)13 (330)13 (330)13 (330)13 (330)13 (330)14(356)14(356)14(356)14(356)17 (432)17 (432)17 (432)17 (432)20 (508)20 (508)20 (508)20 (508)23 (584)23 (584)23 (584)23 (584)23 (584)23 (584)

60 (1524)60 (1524)

*SerieS 3NTS only

69 (32)72 (33)72 (33)75 (34)

117 (53)125 (57)125 (57)133 (61)196 (89)202 (92)202 (92)208 (94)

316 (143)324 (147)324 (147)332 (150)431 (196)460 (209)460 (209)489 (222)581 (264)611 (277)611 (277)639 (290)

1160 (525)1160 (525)1430 (649)1495 (679)

Notes:1. Unit is designed for top cable

entry of emergency & load and bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional accessory kit #K609027). Not required for type 3R, 4X & 12 enclosures where available.

2. Enclosures for 2600, 3000 amps are free-standing with removable top, sides & back.

3. Neutral Code “B” for 230 amperes only.4. Dimensions for 30-200 amperes when furnished with a power meter, 18"W - 41"H - 13"D5. Dimensional data is approximate and subject to change. Certified dimensions available upon request.

series 300 Transfer Switch Dimensions and Shipping Weights

11

UL Type 3R, 4 or 12 Enclosure1,2,3,4,5

Switch RatingAmps

Phase Poles

Neutral Code

Dimensions, In. (mm)Width Height Depth

Approx. ShippingWeight Lb. (kg)

2233223322332233223322333333

303,703,1003*,1043

1503, 2003

(Non Secure Enclosure)

2302, 260, 400

(Non Secure Enclosure)

150, 200, 230260, 400

(Non Secure Enclosure)

600(Non Secure Enclosure)

800, 1000 (Non Secure Enclosure)

12006

(Non Secure Enclosure)

1600, 20002

(Non Secure Enclosure)

2600, 3000(Non Secure Enclosure)

ABABA

B3 or CA

B3 or CABABAB AB ABABABABABAB

17 1/2 (445)17 1/2 (445)17 1/2 (445)17 1/2 (445)

18 (458)18 (458)18 (458)18 (458)24 (607)24 (607)24 (607)24 (607)24 (607)24 (607)24 (607)24 (607)34 (859)34 (859)34 (859)34 (859)

41 (1037)41 (1037)41 (1037)41 (1037)41 (1037)41 (1037)41 (1037)41 (1037)

35 (886)35 (886)35 (886)35 (886)

50 1/2 (1284)50 1/2 (1284)50 1/2 (1284)50 1/2 (1284)

63 (1593)63 (1593)63 (1593)63 (1593)63 (1593)63 (1593)63 (1593)63 (1593)72 (1821)72 (1821)72 (1821)72 (1821)

95 1/2 (2415)95 1/2 (2415)95 1/2 (2415)95 1/2 (2415)95 1/2 (2415)95 1/2 (2415)

96 (2429)96 (2429)

11 5/8 (295)11 5/8 (295)11 5/8 (295)11 5/8 (295)14 1/3 (364)14 1/3 (364)14 1/3 (364)14 1/3 (364)18 1/5 (468)18 1/5 (468)18 1/5 (468)18 1/5 (468)18 1/5 (468)18 1/5 (468)18 1/5 (468)18 1/5 (468)

20 (506)20 (506)20 (506)20 (506)

33 1/2 (848)33 1/2 (848)33 1/2 (848)33 1/2 (848)

62 (1569)62 (1569)74 (1872)74 (1872)

*SerieS 3NTS only

84 (38)87 (40)87 (40)90 (41)

132 (60)140 (63)140 (63)148 (67)

234 (106)241 (109)241 (109)246 (112)320 (145)328 (148)328 (148)336 (152)519 (236)543 (246)543 (246)565 (257)

1131 (513)1160 (526)1160 (526)1189 (539)1705 (775)1830 (832)2150 (976)

2230 (1012)

Notes:1. When climate conditions at in- stallation site present condensa- tion risk, special precautions should be taken, such as the inclusion of space heaters, to prevent interior condensation and freezing of this condensation.2. Neutral code “B” for 230 amperes only.3. Dimensions for 30 - 200 ampere when furnished with a power meter 18"W - 48"H - 13"D4. 30-1000 ampere switches are available in secure type enclosures, contact ASCO for details5. Dimensional data is approximate and subject to change. Certified dimensions available upon request.

*SerieS 3ADTS/3NDTS only

Page 61: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

12

300 ATS with 72EE Engine Generator Utility

Facility

Wifi

Tablet Mobile Device Desktop72EE enables basic local or remote monitoring for ASCO Series 300 Transfer Switches.

series 300 72EE Monitoring and Control

ASCO 5700 CPMS

72EE FeaturesControl Features

ATS Transfer/Re-transfer

ATS Timer Bypass

Generator Start

Generator Test

Connectivity Features

Modbus (over Ethernet or Serial)

SNMP Protocol

AES 128 Bit Encryption

Four Port Ethernet Switch

72EE Also Enables Enhanced PowerQuest CPMS Functionality

5310 SerieS Single Channel Annunciator

5350 SerieS Eight Channel Annunciator

5700 Critical Power Management Systems

Sample drawing for demonstration purposes only.Consult ASCO for exact connection specifications.

Monitoring Features

ATS and Generator Stats

Alarms

Voltage and Frequency

Statistics and Activity

Email Notifications

Event Log (300 Events)

Optional Monitoring Features

— Energy Consumption,

Acc 135L Required

— Power Demand,

Acc 135L Required

Page 62: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

13

series 300 72EE Monitoring Screens

Fig. 17: 72EE Home Page Dashboard

Fig. 20: Configuration

Fig. 18: Power Metering Screen

Fig. 19: Events Screen

Fig. 21: About

Content rich monitoring screens enable real time information for power metering, event logs, voltages, time delays and alerts. The 72EE also allows for switch transfer remotely.

Page 63: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

14

Additional Optional PowerQuest Components

5310, 5350Annunciators

5210, 5220Power Manager

5710, 5750, 5790 Display Terminals

ASCO 5210 (left) and 5220 (right) Power Meters measure, displays and provides single- or 3-phase Energy and Power information

5700 Critical Power Management Systems (5790 shown)provides various levels of monitoring, control and management capability of power equipment. It seamlessly monitors ASCO transfer switches as well as generators, breakers, paralleling buss, panel boards and other power equip-ment via a 5221 PMU. It consists of servers and touch screen interfaces.

ASCO 5310(left) and 5350(right) ATS Remote Annunciators provide distributed monitoring of transfer switch position and source availability as well as transfer test and re-transfer control.

ASCO 5221 Power Manager Unit

ASCO 5221 Power Manager Unit (PMU) is used to enable power measure-ment, discrete inputs for status and output relays for control of generators, breakers and other power equipment via 5700 Series CPMS solutions.

5160Connectivity Module

The ASCO 5160 Remote Connectivity Unit (RCU) provides 10 Ethernet and Dual-Fiber Optic connections in a NEMA 3R enclosure.

series 300 72EE Connectivity Module

The ASCO 72EE Connectivity Module offers remote monitoring for SerieS 300 ATS's and 5210 Power Meter. For the ATS, the optional accessory 72EE provides remote ATS and Generator Control, Monitoring and Connectivity Features via inte-grated web page dashboards. Once connected to an Ethernet, Wifi or Cellular connection, the dashboards can easily be pulled up by any mobile or desktop device on the network by multiple users.

Control

The control capabilities allows remote transfer and retransfer of the ATS, while allowing you to view time delays and bypass functions. The generators can also be called to start and stop for emergency situations as well as for testing and maintenance. Running the generator periodically ensures that the battery is charged for power anomalies and increases reliability. Generator Pick-up and drop-out setpoints are also viewable for comprehensive understanding of control events.

Monitoring

Monitor transfer switch and genera-tor health, system state, metering and review calculated transfer statis-tics and activity. Active control timer information allows the operator to anticipate an automated control ac-tion, such as, generator start or ATS transfer. The device can also interface

Fig. 22:Accessory

72EE

to an email server to keep users up-to-date on alarms and critical power events with alerts.

In addition the 72EE can interface to an optional 5210 Power Meter, (stand alone - or with the ATS Acc. 135L). for enhanced monitoring features, such as, power metering, demand and energy usage.

Connectivity

Connect and extract ATS and meter-ing data using industry standard open protocols, such as, Modbus and SNMP. An integrated four port Eth-ernet Switch maximizes connectivity options and flexibility. Embedded password protection will only allow access to appropriate users, while utilizing AES 128-bit encryption for enhanced data security per National Institute of Standards and Technol-ogy (NIST).

Page 64: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

15

FULFILL YOUR NEED

Drill down for a closer look - Each transfer switch, generator, breaker and any other power equip-ment has its own dedicated screens.

The PowerQuest® family is the most comprehensive communication, monitor-ing and control solution ever offered by Emerson Network Power. It empowers you. It provides the ability to test, manage loads, optimize the bus bar, remotely monitor and otherwise be aware of the status of your facility's utility source and on-site power. It provides reports for events, tests, energy use or settings and gets data directly from generators and transfer switches.

Whether user's require stan-dard monitoring and control, or a comprehensive Critical Power Management System, PowerQuest can satisfy your needs.

Hardware. Software. Installa-tion and testing. Service. And upgrades and technology refreshes. A truly complete solution for all your communication, monitoring and control needs.

This web enabled manage-ment system is based on open protocols. As com-munications amongst equipment improve, so does the performance of critical power systems.

ASCO PowerQuest® Power Monitoring and Control Systems

PowerQuest provides monitoring, alarming and control of Critical Power Management Systems, which comprise transfer switches, paralleling control switchgear, gensets, circuit breakers, UPS, loadbanks, distribution and other gear. It also integrates with building management systems.

BE EMPOWERED

PowerQuest can enable you to: • Monitor and control power transfer switches,

paralleling control switchgear, gensets, breakers, UPS, bus bars and other equipment

• Monitor normal and emergency voltages and frequency and their settings

• Know transfer switch position and source availability

• Transfer and re-transfer loads for system testing • View and adjust transfer switch time-delay settings • Receive automatic alerts or selected system alarms

on system operation via E-mail or pager • View transfer switch event log and know the

transfer switch test schedule• Generate reports for alarms, energy consumption,

settings, historical logs and code mandated tests

Remote Display

Terminal

Critical Power Management System (CPMS)

Static Transfer Switches

Transfer Switches

Paralleling Control Switchgear

Generators

CPMS Display

Terminal

HVAC

Security

Fire Alarm Monitoring

Building Management System (BMS)

Internet

UPS

For more PowerQuestproduct informationsee publication 3245

Page 65: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

www.EmersonNetworkPower.com/ASCO

Emerson Network Power - Global Headquarters1050 Dearborn Drive

Columbus, OH 43085Tel: +1 614 888 0246

ASCO Power Technologies - Global Headquarters50 Hanover Road

Florham Park, NJ 07932800-800-ASCO

www.ascoapu.com

Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2013 Emerson Electric Co. All rights reserved.Publication 1195 R15 © October, 2013 Printed in the U.S.A.

Page 66: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

4

480V

Max.

600V

Max.

Max

Size, AClass

240V

Max.

480V

Max.

600V

Max.

Time

(sec)

240V

Max.

480V

Max.

600V

Max..1 .13 .3 .5 .1 .13 .3 .5

D 30 - 100kA - 60 J 22kA 22kA 10kA 0.025 10kA 10kA 10kA

35kA 35kA 200 RK1

200kA 35kA 200 J

35kA 35kA 200 RK1

200kA 35kA 200 J

D 200 - 200kA - 200 J 65kA 25kA - 0.025 10kA 10kA -

D 230 - 100kA - 300 J 65kA 25kA - 0.025 10kA 10kA -

E 260, 400 - 200kA - 600 J 65kA 42kA 35kA 0.05 35kA 35kA 22kA

J150

7, 200

7,

2307, 260, 400

1507, 200

7,

2307, 260, 400

200kA 200kA 600 J 50kA 50kA 42kA 0.05 65kA 42kA5 35kA

J 600 600 200kA 200kA 800 L 50kA 50kA 42kA 0.05 65kA 42kA5 35kA

H 600 600 200kA 200kA 800 L 65kA 65kA 65kA 0.05 50kA 50kA 50kA - -

P 600 600 200kA 200kA 800 L 65kA 65kA 65kA 0.05 50kA 50kA 50kA 30kA -

P 800 800 - 1200 200kA 200kA 1600 L 65kA 65kA 65kA 0.05 50kA 50kA 50kA 30kA -

H 800 - 1200 800 - 1200 200kA 200kA 1600 L 65kA 65kA 65kA 0.05 50kA 50kA 50kA - -

Q 600-1600 600-1600 200kA 200kA 2000 L 65kA 65kA 65kA 0.05 65kA 65kA 65kA

S 800 - 1200 800 - 1200 200kA 200kA 2500 L 100kA 100kA 65kA 0.05 100kA 100kA 65kA

G 1000 - 1200 1000 - 1200 200kA 200kA 2000 L 85kA 85kA 85kA 0.05 85kA 85kA 85kA

G 1600 - 20004 - 200kA 200kA 2500 L 85kA

4 85kA

4 85kA

4 0.05 85kA4

85kA4

85kA4

G 1600 - 2000 1600 - 2000 200kA 200kA 3000 L 125kA8

125kA8 100kA 0.05 100kA 100kA 100kA - -

S 1600 - 2000 1600 - 2000 200kA 200kA 2500 L 100kA 100kA 85kA 0.05 100kA 100kA 85kA 65kA 65kA

G 2600 - 3000 2600 -3000 200kA 200kA 4000 L 100kA 100kA 100kA 0.05 100kA 100kA 100kA - -

G 3200 - 200kA - 4000 L 100kA 100kA - 0.05 100kA 100kA -

G 4000 4000 200kA 200kA 5000 L 100kA 100kA 100kA 0.05 100kA 100kA 100kA

U 2600 - 4000 2600 - 4000 200kA 200kA 5000 L 125kA9

125kA9

125kA9 0.06 125kA

9 125kA

9 125kA

9

Notes: 1) All WCR values indicated are tested in accordance with the requirements of UL 1008, 7th Edition. See ASCO Pub. 1128 for more WCR information

2) Application requirements may permit higher WCR for certain switch sizes.

3) Short Time ratings are provided for applications involving circuit breakers that utilize trip delay settings for system selective coordination

4) Optional front connected service (Accy 40MY and 40NY) limits WCR on 1600 and 2000A G Frame switches

5) Switches utilizing overlapping neutral (code "C") have 35kA, 0.050 Sec time based rating at 480V Max

6) 3000A ratings are for Transfer Switch configurations only

7) J150, 200, 230 Amp available in 7ACTS, 7ADTS, 7ASLS, & All 7000 Bypass Switches only

8) Rating shown is for Bypass switches only, Transfer Switch rating is 100kA

9) Service Entrance Switches rating is 100kA

85KA 65kA 65kA

100kA 100kA

42kA 42kA6

- -

85kA 85kA

36kA 36kA

36kA 36kA

36kA 36kA

36kA 36kA

50kA 50kA

65kA

-

- -

- -

Specific Breaker

- -

10kA - -

Frame

Switch Rating (Amps)Current Limiting Fuses

Transfer

Switches

Bypass

Switches

7000 Series

Time BasedShort Time Ratings

3 (sec)

480V Max. 600V Max.

Table II. ASCO UL1008 Withstand and Close On Ratings 1,2

D 70, 100 - 22kA 10kA 0.025 10kA 10kA42kA

- -

300, 4000 & 7000 Series 4000 & 7000 Series

10kA

(RMS Symmetrical Amps)

42kA 42kA

10kA 0.025 10kA 10kA

65kA

- -

- -

- -

- -

-

D 150 - 65kA 25kA

Page 67: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

Form ASCO T&C 3827 - Rev. 5/1/12

TERMS AND CONDITIONS OF SALE

ASCO Power Technologies, L.P. is herein referred to as the "Seller" and the customer or person or entity purchasing goods and/or services ("Goods") and/or licensing software and/or firmware, which are preloaded, or to be used with Goods ("Software") from Seller is referred to as the "Buyer." These Terms and Conditions, any price list or schedule, quotation, acknowledgment, Seller’s scope of work, or invoice from Seller relevant to the sale of the Goods and licensing of Software and all documents incorporated by specific reference herein or therein, constitute the complete and exclusive statement of the terms of the agreement governing the sale of Goods and/or license of Software by Seller to Buyer. Seller’s acceptance of Buyer’s purchase order is expressly conditional on Buyer’s assent to all of Seller’s terms and conditions of sale, including terms and conditions that are different from or additional to the terms and conditions of Buyer’s purchase order. Buyer's acceptance of the Goods and/or Software will manifest Buyer's assent to these Terms and Conditions. Seller reserves the right in its sole discretion to refuse orders. 1. PRICES: Unless otherwise specified in writing by Seller, the price quoted or specified by Seller for the Goods and/or Software shall remain in effect for thirty (30) days after the date of Seller's quotation provided an unconditional authorization from Buyer for the shipment of the Goods and/or Software is received and accepted by Seller within such time period. If such authorization is not received by Seller within such thirty (30) day period, Seller shall have the right to change the price for the Goods and/or Software to Seller's price for the Goods and/or Software at the time of shipment. All prices and licensee fees are exclusive of taxes, transportation and insurance, which are to be borne by Buyer. 2. TAXES: Any current or future tax or governmental charge (or increase in same) affecting Seller's costs of production, sale, or delivery or shipment, or which Seller is otherwise required to pay or collect in connection with the sale, purchase, delivery, storage, processing, use or consumption of Goods and/or Software, shall be for Buyer's account and shall be added to the price or billed to Buyer separately, at Seller’s election.. 3. TERMS OF PAYMENT: Unless otherwise specified by Seller, terms are net thirty (30) days from date of Seller's invoice in U.S. currency. Seller shall have the right, among other remedies, either to terminate this agreement or to suspend further performance under this and/or other agreements with Buyer in the event Buyer fails to make any payment when due, which other agreements Buyer and Seller hereby amend accordingly. Buyer shall be liable for all expenses, including attorneys' fees, relating to the collection of past due amounts. If any payment owed to Seller is not paid when due, it shall bear interest, at a rate to be determined by Seller, which shall not exceed the maximum rate permitted by law, from the date on which it is due until it is paid. Should Buyer's financial responsibility become unsatisfactory to Seller, cash payments or security satisfactory to Seller may be required by Seller for future deliveries of Goods and/or Software. If such cash payment or security is not provided, in addition to Seller's other rights and remedies, Seller may discontinue deliveries. Buyer hereby grants Seller a security interest in all Goods and/or Software sold to Buyer by Seller, which security interest shall continue until all such Goods and/or Software are fully paid for, and Buyer, upon Seller's demand, will execute and deliver to Seller such instruments as Seller requests to protect and perfect such security interest. 4. SHIPMENT AND DELIVERY: While Seller will use all reasonable commercial efforts to maintain the delivery date(s) and/or performance dates acknowledged or quoted by Seller, all shipping dates and/or performance dates are approximate and not guaranteed. Seller reserves the right to make partial shipments. Seller, at its option, shall not be bound to tender delivery of any Goods, Parts, and/or Software for which Buyer has not provided shipping instructions and other required information. If the shipment of the Goods, Parts, and/or Software is postponed or delayed by Buyer for any reason, Buyer agrees to reimburse Seller for any and all storage costs and other additional expenses resulting therefrom. For sales in which Buyer’s ship to address for the Goods, Parts, and/or Software is outside of the United States, risk of loss and legal title to the Goods, Parts, and/or Software shall transfer to Buyer immediately after the Goods, Parts, and/or Software have passed beyond the territorial limits of the United States. In all other instances risk of loss and legal title to the Goods, Parts, and/or Software shall transfer from Seller to Buyer immediately upon shipment from the FCA Seller’s Shipping Point. All shipments of Goods, Parts, and/or Software are made on a Free Carrier (FCA) Seller’s Shipping Point basis, per Incoterms 2010, with Buyer responsible for all official export formalities, authorizations, risks and expenses as may be applicable for export from the country of shipment. Any claims for shortages or damages suffered in transit are the responsibility of Buyer and shall be submitted by Buyer directly to the carrier. Shortages or damages must be identified and signed for at the time of delivery. 5. LIMITED WARRANTY: Subject to the limitations of Section 6, Seller's standard warranty that is applicable to the Goods and/or Software at the time of purchase is the only warranty applicable to the sale of Seller's Goods and/or Software and its terms, conditions and limitations are incorporated by reference herein. THE WARRANTY SET FORTH IN THIS SECTION 5 AND THE WARRANTY SET FORTH IN SECTION 7 ARE THE SOLE AND EXCLUSIVE WARRANTIES GIVEN BY SELLER WITH RESPECT TO THE GOODS AND/OR SOFTWARE AND ARE IN LIEU OF AND EXCLUDE ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, ARISING BY OPERATION OF LAW OR OTHERWISE, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHETHER OR NOT THE PURPOSE OR USE HAS BEEN DISCLOSED TO SELLER IN SPECIFICATIONS, DRAWINGS OR OTHERWISE, AND WHETHER OR NOT SELLER'S PRODUCTS ARE SPECIFICALLY DESIGNED AND/OR MANUFACTURED BY SELLER FOR BUYER'S USE OR PURPOSE. SELLER'S WARRANTY EXTENDS ONLY TO PURCHASERS WHO BUY FOR INDUSTRIAL OR COMMERCIAL USE. This warranty does not extend to any losses or damages due to misuse, accident, abuse, neglect, normal wear and tear, negligence (other than Seller's), unauthorized modification or alteration, use beyond rated capacity, unsuitable power sources or environmental conditions, improper installation, repair, handling, maintenance or application or any other cause not the fault of Seller. To the extent that Buyer or its agents have supplied specifications, information, representation of operating conditions or other data to Seller in the selection or design of the Goods and/or Software and the preparation of Seller's quotation, and in the event that actual operating conditions or other conditions differ from those represented by Buyer, any warranties or other provisions contained herein that are affected by such conditions shall be null and void. Buyer assumes all other responsibility for any loss, damage, or injury to persons or property arising out of, connected with, or resulting from the use of Goods and/or Software, either alone or in combination with other products/components. 6. LIMITATION OF REMEDY AND LIABILITY: THE SOLE AND EXCLUSIVE REMEDY FOR BREACH OF ANY WARRANTY HEREUNDER (OTHER THAN THE WARRANTY PROVIDED UNDER SECTION 7) SHALL BE LIMITED TO REPAIR, CORRECTION OR REPLACEMENT, OR REFUND OF THE PURCHASE PRICE UNDER SECTION 5. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN PERFORMANCE AND THE REMEDIES OF BUYER SET FORTH IN THIS AGREEMENT ARE EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR OTHERWISE), SHALL SELLER'S LIABILITY TO BUYER AND/OR ITS CUSTOMERS EXCEED THE PRICE PAID BY BUYER FOR THE SPECIFIC GOODS AND/OR SOFTWARE PROVIDED BY SELLER GIVING RISE TO THE CLAIM OR CAUSE OF ACTION. BUYER AGREES THAT SELLER'S LIABILITY TO BUYER AND/OR ITS CUSTOMERS SHALL NOT EXTEND TO INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES. The term "consequential damages" shall include, but not be limited to, loss of anticipated profits, business interruption, loss of use, revenue, reputation and data, costs incurred, including without limitation, for capital, fuel, power and loss or damage to property or equipment. Buyer expressly acknowledges and agrees that Seller has set its prices and entered into this Agreement in reliance upon the limitations of liability, insurance and other terms and conditions specified herein, which allocate the risk between Seller and Buyer and form a basis of this bargain between the parties. It is expressly understood that any technical advice furnished by Seller with respect to the use of the Goods and/or Software is given without charge, and Seller assumes no obligation or liability for the advice given, or results obtained, all such advice being given and accepted at Buyer's risk. 7. PATENTS AND COPYRIGHTS: Subject to the limitations of the second paragraph of Section 6, Seller warrants that the Goods and/or Software sold, except as are made specifically for Buyer according to Buyer's specifications, do not infringe any valid U.S. patent or copyright in existence as of the date of shipment. This warranty is given upon the condition that Buyer promptly notify Seller of any claim or suit involving Buyer in which such infringement is alleged and cooperate fully with Seller and permit Seller to control completely the defense, settlement or compromise of any such allegation of infringement. Seller's warranty as to utility patents only applies to infringement arising solely out of the inherent operation according to Seller's specifications and instructions of such Goods and/or Software. In the event (i) such Goods and/or Software are held to infringe such a U.S. patent or copyright in such suit, and the use of such Goods and/or Software is enjoined, or (ii)a compromise or settlement is made by Seller, Seller shall have the right, at its option and expense, to procure for Buyer the right to continue using such Goods and/or Software, or replace them with non-infringing Goods and/or Software, or modify same to become non-infringing, or grant Buyer a credit for the depreciated value of such Goods and/or Software and accept return of them. In the event of the foregoing, Seller may also, at its option, cancel the agreement as to future deliveries of such Goods and/or Software, without liability. 8. INSURANCE: Seller shall maintain the following insurance or self-insurance coverage: Worker’s Compensation in accordance with the statutory requirements of the state in which work is performed. Employer’s Liability with a limit of liability of $2,000,000 per occurrence for bodily injury by accident or bodily injury by disease. Commercial General Liability (CGL) for bodily injury and property damage with a limit of $2,000,000 per occurrence and aggregate. CGL includes Contractual Liability. CGL does not include Products and Completed Operations coverage, which is self-insured. Automobile Liability insurance that covers usage of all owned, non-owned and leased vehicles and which is subject to a combined single limit per occurrence of $2,000,000. Automobile Liability insurance includes Contractual Liability and Cross Liability, but no special endorsements. Additional information related to the insurance coverage provided by Seller can be found at http://www.marsh.com/moi?client=0900.

9. EXCUSE OF PERFORMANCE: Seller shall not be liable for delays in performance or for non-performance due to acts of God; acts of Buyer; war; epidemic; fire; flood; weather; sabotage; strikes or labor disputes; civil disturbances or riots; governmental requests, restrictions, allocations, laws, regulations, orders or actions; unavailability of or delays in transportation; default of suppliers; or unforeseen circumstances or any events or causes beyond Seller's reasonable control. Deliveries or other performance may be suspended for an appropriate period of time or canceled by Seller upon notice to Buyer in the event of any of the foregoing, but the balance of the agreement shall otherwise remain unaffected as a result of the foregoing. If Seller determines that its ability to supply the total demand for the Goods and/or Software, or to obtain material used directly or indirectly in the manufacture of the Goods and/or Software, is hindered, limited or made impracticable due to causes set forth in the preceding paragraph, Seller may allocate its available supply of the Goods, Software, and/or such material (without obligation to acquire other supplies of any such Goods, Software, or material) among its purchasers on such basis as Seller determines to be equitable without liability for any failure of performance which may result therefrom. 10. CANCELLATION/CHANGES: Buyer may cancel orders only upon reasonable advance written notice and upon payment to Seller of Seller's cancellation charges which include, among other things, all costs and expenses incurred, and, to cover commitments made, by the Seller and a reasonable profit thereon. Seller's determination of such cancellation charges shall be conclusive. Buyer may request changes or additions to the Goods and/or Software consistent with Seller's specifications and criteria. In the event such changes or additions are accepted by Seller, Seller may revise the price, license fees, and dates of delivery and/or performance dates. Seller reserves the right to change designs and specifications for the Goods and/or Software without prior notice to Buyer, except with respect to Goods and/or Software being made-to-order for Buyer. Seller shall have no obligation to install or make such change in any Goods and/or Software manufactured prior to the date of such change. 11. NUCLEAR/MEDICAL: GOODS AND SOFTWARE SOLD HEREUNDER ARE NOT FOR USE IN THE CONTROL AREA OR ANY REACTOR CONNECTED OR SAFETY APPLICATIONS OR WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR FOR INTEGRATION INTO MEDICAL DEVICES. Buyer accepts Goods and Software with the foregoing understanding, agrees to communicate the same in writing to any subsequent purchasers or users and to defend, indemnify and hold harmless Seller from any claims, losses, suits, judgments and damages, including incidental and consequential damages, arising from such use, whether the cause of action be based in tort, contract or otherwise, including allegations that the Seller’s liability is based on negligence or strict liability. 12. SOFTWARE: Notwithstanding any other provision herein to the contrary, Seller or applicable third party licensor to Seller shall retain all rights of ownership and title in its respective Software, including without limitation all rights of ownership and title in its respective copies of such Software. Except as otherwise provided herein, Buyer is hereby granted a nonexclusive, non-transferable royalty free license to use the Software incorporated into the Goods solely for purposes of Buyer properly utilizing such Goods purchased from Seller. All other Software shall be furnished to, and used by, Buyer subject to Seller's (or the licensor’s) applicable standard license agreement, the terms of which are incorporated herein by reference. 13. TOOLING: Tool, die, and pattern charges, if any, are in addition to the price of the Goods and are due and payable upon completion of the tooling. All such tools, dies and patterns shall be and remain the property of Seller. Charges for tools, dies, and patterns do not convey to Buyer, title, ownership interest in, or rights to possession or removal, or prevent their use by Seller for other purchasers, except as otherwise expressly provided by Seller and Buyer in writing with reference to this provision. 14. INSPECTION/TESTING/INSTALLATION: Buyer, at its option and expense, may observe the inspection and testing by Seller of the Goods and/or Software for compliance with Seller's standard test procedures prior to shipment, which inspection and testing shall be conducted at Seller's plant at such reasonable time as is specified by Seller. Any rejection of the Goods and/or Software must be made promptly by Buyer before shipment. Tests shall be deemed to be satisfactorily completed and the test fully met when the Goods and/or Software meet Seller's criteria for such procedures. If Buyer does not inspect the Goods and/or Software at Seller's plant as provided herein, Buyer shall have ten (10) days from (i) the date of delivery of goods and/or Software and (ii) from the date of completion of each portion of the services to inspect the Goods and/or Software, and in the event of any non-conformity, Buyer must give written notice to Seller within said period stating why the Goods and/or Software are not conforming. Failure by Buyer to give such notice constitutes unqualified acceptance of the Goods and/or Software. Buyer’s sole remedy for non-conforming services shall be correct performance of services incorrectly performed by Seller. Buyer shall be responsible for receiving, inspecting, testing, storing, installing, starting up (unless included in Seller’s proposal) and maintaining all Goods. 15. RETURNED GOODS: Advance written permission to return Goods and/or Software must be obtained from Seller in accordance with Seller’s then current Return Material Authorization (RMA) procedures and a return authorization number issued. Such Goods and/or Software must be (i) current, unused Goods and/or Software, (ii) free of all liens, encumbrances, or other claims, and (iii) shipped, transportation prepaid, to Seller’s specified location. Returns made without proper written permission will not be accepted by Seller. Seller reserves the right to inspect Goods and/or Software prior to authorizing return. 16. BILLABLE SERVICES: Additional charges will be billed to Buyer at Seller’s then prevailing labor rates for any of the following: (a) any services not specified in Seller’s quotation, Seller’s order acknowledgement, or other documents referenced herein and therein; (b) any services performed at times other than Seller’s normal service hours; (c) if reasonable site and/or equipment access is denied the Seller service representative; and (d) if it is necessary, due to local circumstances, to use union labor or hire an outside contractor, Seller service personnel will provide supervision only and the cost of such union or contract labor will be charged to Buyer. 17. DOCUMENTATION/BUYER SUPPLIED DATA: Seller shall provide Buyer with that data/documentation which is specifically identified in Seller's quotation. If additional copies of data/documentation are to be provided by Seller, it shall be provided to Buyer at Seller's applicable prices then in effect. Seller's prints and drawings (including without limitation, the underlying technology) furnished by Seller to Buyer in connection with this agreement are the property of Seller and Seller retains all rights, including without limitation, exclusive rights of use, licensing and sale. Possession of such prints or drawings does not convey to Buyer any rights or license, and Buyer shall return all copies (in whatever medium) of such prints or drawings to Seller immediately upon request therefor. To the extent that Seller has been provided by, or on behalf of, Buyer any specifications, description of operating conditions or other data and information in connection with the selection or design of the Goods and/or Software, and/or the provision of Services, and the actual operating conditions or other circumstances differ from those provided by Buyer and relied upon by Seller, any warranties or other provisions contained herein which are affected by such conditions shall be null and void. 18. EXPORT/IMPORT: Buyer agrees that all applicable import and export control laws, regulations, orders and requirements, including without limitation those of the United States, and the jurisdictions in which the Seller and Buyer are established or from which Goods, Software, and Services may be supplied, will apply to their receipt and use. In no event shall Buyer use, transfer, release, import, export, Goods or Software in violation of such applicable laws, regulations, orders or requirements. 19. GENERAL PROVISIONS: These terms and conditions supersede all other communications, negotiations and prior oral or written statements regarding the subject matter of these terms and conditions. No change, modification, rescission, discharge, abandonment, or waiver of these terms and conditions shall be binding upon the Seller unless made in writing and signed on its behalf by a duly authorized representative of Seller. No conditions, usage of trade, course of dealing or performance, understanding or agreement purporting to modify, vary, explain, or supplement these terms and conditions shall be binding unless hereafter made in writing and signed by the party to be bound, and no modification or additional terms shall be applicable to this agreement by Seller's receipt, acknowledgment, or acceptance of purchase orders, shipping instruction forms, or other documentation containing terms at variance with or in addition to those set forth herein. Any such modifications or additional terms are specifically rejected and deemed a material alteration hereof. If this document shall be deemed an acceptance of a prior offer by Buyer, such acceptance is expressly conditional upon Buyer’s assent to any additional or different terms set forth herein. No waiver by either party with respect to any breach or default or of any right or remedy, and no course of dealing, shall be deemed to constitute a continuing waiver of any other breach or default or of any other right or remedy, unless such waiver be expressed in writing and signed by the party to be bound. All typographical or clerical errors made by Seller in any quotation, acknowledgment or publication are subject to correction. Buyer shall not assign its rights or delegate its duties hereunder or any interest herein without the prior written consent of Seller, and any such assignment, without such consent, shall be void. The validity, performance, and all other matters relating to the interpretation and effect of this agreement shall be governed by the law of the state of New Jersey without regard to its conflict of laws principles. Buyer and Seller agree that the proper venue for all actions arising in connection herewith shall be only in New Jersey and the parties agree to submit to such jurisdiction. No action, regardless of form, arising out of transactions relating to this contract, may be brought by either party more than two (2) years after the cause of action has accrued. The U.N. Convention on Contracts for the International Sales of Goods shall not apply to this agreement. Buyer shall not solicit, directly or indirectly, or employ any employee of Seller during the period any Goods are being provided to Buyer and for a period of one (1) year after the last provision of Goods. 20. INDEMNITY: Each party shall indemnify and hold the other party harmless from loss, damage, liability or expense resulting from damage to personal property of a third party, or injuries, including death, to third parties to the extent caused by a negligent act or omission of the party providing indemnification or a party’s subcontractors, agents or employees during performance of services hereunder. Such indemnification shall be reduced to the extent damage or injuries are attributable to others. The indemnifying party shall defend the other party in accordance with and to the extent of the above indemnification, provided that the indemnifying party is: (i) promptly notified by the other party, in writing, of any claims, demands or suits for such damages or injuries; (ii) given all reasonable information and assistance by the other party; (iii) given full control over any resulting negotiation, arbitration or litigation, including the right to choose counsel and settle claims, or the indemnifying party’s obligations herein shall be deemed waived.

Page 68: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

SELF5611-01

Effective with sales to the first user on or after August 1, 2014

CATERPILLAR LIMITED WARRANTYIndustrial, Petroleum, Locomotive, and Agriculture Engine Products and Electric Power

Generation ProductsWorldwide

Caterpillar Inc. or any of its subsidiaries (“Caterpillar”) warrants new and remanufactured engines and electric power generation products sold by it (including any products of other manufacturers packaged and sold by Caterpillar), to be free from defects in material and workmanship.

This warranty does not apply engines sold for use in on-highway vehicle or marine applications; engines in machines manufactured by or for Caterpillar; C175, 3500 and 3600 series engines used in locomotive applications; 3000 Family engines, C0.5 through C4.4 and ACERT™ (C6.6, C7, C7.1, C9, C9.3, C11, C13, C15, C18, C27, and C32) engines used in industrial, mobile agriculture and locomotive applications; or Cat® batteries. These products are covered by other Caterpillar warranties.

This warranty is subject to the following:

Warranty Period

• For industrial engines, engines in a petroleum applications or Petroleum Power Systems (excluding petroleum fire pump application), or engines in a Locomotive application, or Uninterruptible Power Supply (UPS) systems, the warranty period is 12 months after date of delivery to the first user.

• For engines used in petroleum fire pump and mobile agriculture applications the warranty period is 24 months after date of delivery to the first user.

• For controls only (EPIC), configurable and custom switchgear products, and automatic transfer switch products, the warranty period is 24 months after date of delivery to the first user.

• For new CG132, CG170 and CG260 series power generation products the warranty period is 24 months/16,000 hours, whichever comes first, after date of delivery to first user.

• For electric power generation products other than CG132, CG170 and CG260 series in prime or continuous applications the warranty period is 12 months. For standby applications the warranty period is 24 months/1000 hours. For emergency standby applications the warranty period is 24 months/400 hours. All terms begin after date of delivery to the first user.

• For all other applications the warranty period is 12 months after date of delivery to the first user.

Caterpillar Responsibilities

If a defect in material or workmanship is found during the warranty period, Caterpillar will, during normal working hours and at a place of business of a Cat dealer or other source approved by Caterpillar:

• Provide (at Caterpillar’s choice) new, Remanufactured, or Caterpillar approved repaired parts or assembled components needed to correct the defect.

Note: New, remanufactured, or Caterpillar approved repaired parts or assembled components provided under the terms of this warranty are warranted for the remainder of the warranty period applicable to the product in which installed as if such parts were original components of that product. Items replaced under this warranty become the property of Caterpillar.

• Replace lubricating oil, filters, coolant, and other service items made unusable by the defect.

• Provide reasonable and customary labor needed to correct the defect, including labor to disconnect the product from and reconnect the product to its attached equipment, mounting, and support systems, if required.

For new 3114, 3116, and 3126 engines and electric power generation products (including any new products of other manufacturers packaged and sold by Caterpillar):

• Provide travel labor, up to four hours round trip, if in the opinion of Caterpillar, the product cannot reasonably be transported to a place of business of a Cat dealer or other source approved by Caterpillar (travel labor in excess of four hours round trip, and any meals, mileage, lodging, etc. is the user’s responsibility).

For all other products:

• Provide reasonable travel expenses for authorized mechanics, including meals, mileage, and lodging, when Caterpillar chooses to make the repair on-site.

User Responsibilities

The user is responsible for:

• Providing proof of the delivery date to the first user.

• Labor costs, except as stated under “Caterpillar Responsibilities,” including costs beyond those required to disconnect the product from and reconnect the product to its attached equipment, mounting, and support systems.

• Travel or transporting costs, except as stated under “Caterpillar Responsibilities.”

• Premium or overtime labor costs.

• Parts shipping charges in excess of those that are usual and customary.

• Local taxes, if applicable.

• Costs to investigate complaints, unless the problem is caused by a defect in Caterpillar material or workmanship.

• Giving timely notice of a warrantable failure and promptly making the product available for repair.

• Performance of the required maintenance (including use of proper fuel, oil, lubricants, and coolant) and items replaced due to normal wear and tear.

• Allowing Caterpillar access to all electronically stored data.

Limitations

Caterpillar is not responsible for:

• Failures resulting from any use or installation that Caterpillar judges improper.

• Failures resulting from attachments, accessory items, and parts not sold or approved by Caterpillar.

• Failures resulting from abuse, neglect, and/or improper repair.

• Failures resulting from user’s delay in making the product available after being notified of a potential product problem.

• Failures resulting from unauthorized repairs or adjustments, and unauthorized fuel setting changes.

• Damage to parts, fixtures, housings, attachments, and accessory items that are not part of the engine, Cat Selective Catalytic Reduction System or electric power generation product (including any products of other manufacturers packaged and sold by Caterpillar).

• Repair of components sold by Caterpillar that is warranted directly to the user by their respective manufacturer. Depending on type of application, certain exclusions may apply. Consult your Cat dealer for more information.

(Continued on reverse side…)

Page 69: Submittal Data For: Caterpillar Model D40-LC2, Enclosed …peed-bortz.com/projects/Christiansburg/Lubna Booster Station Cat... · Submittal Data For: Caterpillar Model D40-LC2,

SELF5611-01

This warranty covers every major component of the products. Claims under this warranty should be submitted to a place of business of a Cat dealer or other source approved by Caterpillar. For further information concerning either the location to submit claims or Caterpillar as the issuer of this warranty, write Caterpillar Inc., 100 N. E. Adams St., Peoria, IL USA 61629.

Caterpillar’s obligations under this Limited Warranty are subject to, and shall not apply in contravention of, the laws, rules, regulations, directives, ordinances, orders, or statutes of the United States, or of any other applicable jurisdiction, without recourse or liability with respect to Caterpillar.

A) For products operating outside of Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:

NEITHER THE FOREGOING EXPRESS WARRANTY NOR ANY OTHER WARRANTY BY CATERPILLAR, EXPRESS OR IMPLIED, IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER.

THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, EXCEPT CATERPILLAR EMISSION-RELATED COMPONENTS WARRANTIES FOR NEW ENGINES, WHERE APPLICABLE. REMEDIES UNDER THIS WARRANTY ARE LIMITED TO THE PROVISION OF MATERIAL AND SERVICES, AS SPECIFIED HEREIN.

CATERPILLAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.

IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE OF GOODS IS EXCLUDED IN ITS ENTIRETY.

For personal or family use engines or electric power generation products, operating in the USA, its territories and possessions, some states do not allow limitations on how long an implied warranty may last nor allow the exclusion or limitation of incidental or consequential damages. Therefore, the previously expressed exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights, which vary by jurisdiction. To find the location of the nearest Cat dealer or other authorized repair facility, call (800) 447-4986. If you have questions concerning this warranty or its applications, call or write:

In USA and Canada: Caterpillar Inc., Engine Division, P. O. Box 610, Mossville, IL 61552-0610, Attention: Customer Service Manager, Telephone (800) 447-4986. Outside the USA and Canada: Contact your Cat dealer.

B) For products operating in Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:

THIS WARRANTY IS IN ADDITION TO WARRANTIES AND CONDITIONS IMPLIED BY STATUTE AND OTHER STATUTORY RIGHTS AND OBLIGATIONS THAT BY ANY APPLICABLE LAW CANNOT BE EXCLUDED, RESTRICTED OR MODIFIED (“MANDATORY RIGHTS”). ALL OTHER WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED (BY STATUTE OR OTHERWISE), ARE EXCLUDED. WITHOUT LIMITING THE FOREGOING PROVISIONS OF THIS PARAGRAPH, WHERE A PRODUCT IS SUPPLIED FOR BUSINESS PURPOSES, THE CONSUMER GUARANTEES UNDER THE CONSUMER GUARANTEES ACT 1993 (NZ) WILL NOT APPLY.

NEITHER THIS WARRANTY NOR ANY OTHER CONDITION OR WARRANTY BY CATERPILLAR, EXPRESS OR IMPLIED (SUBJECT ONLY TO THE MANDATORY RIGHTS), IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER.

IF THE MANDATORY RIGHTS MAKE CATERPILLAR LIABLE IN CONNECTION WITH SERVICES OR GOODS, THEN TO THE EXTENT PERMITTED UNDER THE MANDATORY RIGHTS, THAT LIABILITY SHALL BE LIMITED AT CATERPILLAR’S OPTION TO (a) IN THE CASE OF SERVICES, THE SUPPLY OF THE SERVICES AGAIN OR THE PAYMENT OF THE COST OF HAVING THE SERVICES SUPPLIED AGAIN AND (b) IN THE CASE OF GOODS, THE REPAIR OR REPLACEMENT OF THE GOODS, THE SUPPLY OF EQUIVALENT GOODS, THE PAYMENT OF THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION OF EQUIVALENT GOODS.

CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.

CATERPILLAR IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES UNLESS IMPOSED UNDER MANDATORY RIGHTS.

IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE OF GOODS IS EXCLUDED IN ITS ENTIRETY.

C) For products supplied in Australia:

IF THE PRODUCTS TO WHICH THIS WARRANTY APPLIES ARE:

I. PRODUCTS OF A KIND ORDINARILY ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE OR CONSUMPTION; OR

II. PRODUCTS THAT COST AUD 40,000 OR LESS,

WHERE THOSE PRODUCTS WERE NOT ACQUIRED FOR THE PURPOSE OF RE-SUPPLY OR FOR THE PURPOSE OF USING THEM UP OR TRANSFORMING THEM IN THE COURSE OF PRODUCTION OR MANUFACTURE OR IN THE COURSE OF REPAIRING OTHER GOODS OR FIXTURES, THEN THIS SECTION C APPLIES.

THE FOLLOWING MANDATORY TEXT IS INCLUDED PURSUANT TO THE AUSTRALIAN CONSUMER LAW AND INCLUDES REFERENCES TO RIGHTS THE USER MAY HAVE AGAINST THE DIRECT SUPPLIER OF THE PRODUCTS: OUR GOODS COME WITH GUARANTEES THAT CANNOT BE EXCLUDED UNDER THE AUSTRALIAN CONSUMER LAW. YOU ARE ENTITLED TO A REPLACEMENT OR REFUND FOR A MAJOR FAILURE AND COMPENSATION FOR ANY OTHER REASONABLY FORESEEABLE LOSS OR DAMAGE. YOU ARE ALSO ENTITLED TO HAVE THE GOODS REPAIRED OR REPLACED IF THE GOODS FAIL TO BE OF ACCEPTABLE QUALITY AND THE FAILURE DOES NOT AMOUNT TO A MAJOR FAILURE. THE INCLUSION OF THIS TEXT DOES NOT CONSTITUTE ANY REPRESENTATION OR ACCEPTANCE BY CATERPILLAR OF LIABILITY TO THE USER OR ANY OTHER PERSON IN ADDITION TO THAT WHICH CATERPILLAR MAY HAVE UNDER THE AUSTRALIAN CONSUMER LAW.

TO THE EXTENT THE PRODUCTS FALL WITHIN THIS SECTION C BUT ARE NOT OF A KIND ORDINARILY ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE OR CONSUMPTION, CATERPILLAR LIMITS ITS LIABILITY TO THE EXTENT IT IS PERMITTED TO DO SO UNDER THE AUSTRALIAN CONSUMER LAW TO, AT ITS OPTION, THE REPAIR OR REPLACEMENT OF THE PRODUCTS, THE SUPPLY OF EQUIVALENT PRODUCTS, OR THE PAYMENT OF THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION OF EQUIVALENT PRODUCTS.

THE WARRANTY SET OUT IN THIS DOCUMENT IS GIVEN BY CATERPILLAR INC. OR ANY OF ITS SUBSIDIARIES, 100 N. E. ADAMS ST, PEORIA, IL USA 61629, TELEPHONE 1 309 675 1000, THE USER IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH MAKING A CLAIM UNDER THE WARRANTY SET OUT IN THIS DOCUMENT, EXCEPT AS EXPRESSLY STATED OTHERWISE IN THIS DOCUMENT, AND THE USER IS REFERRED TO THE BALANCE OF THE DOCUMENT TERMS CONCERNING CLAIM PROCEDURES, CATERPILLAR RESPONSIBILITIES AND USER RESPONSIBILITIES.

TO THE EXTENT PERMISSIBLE BY LAW, THE TERMS SET OUT IN THE REMAINDER OF THIS WARRANTY DOCUMENT (INCLUDING SECTION B) CONTINUE TO APPLY TO PRODUCTS TO WHICH THIS SECTION C APPLIES.

©2014 Caterpillar All Rights Reserved.CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow" the "Power Edge" trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.