submittal data - flexmaster usa · certifications met class 1 air connector, nfpa 90a and 90b,...

53
SUBMITTAL DATA Acoustical Flexible Duct Insulated Technical Data Standard Lengths (ft) 25 ft, Special lengths on request Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20” Inside Bend Radius (in) 1/2 x I.D. (all sizes) Air Friction Loss See Friction Loss Chart for details Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A Test Standard UL181 Tested By Intertek/ETL Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std. Internal Working Pressure (w.g.) 10” w.g. positive 5” w.g. negative thru 16” dia. 1” w.g. negative, 18” & 20” dia. Rated Velocity 5500 F.P.M. Min Burst Pressure 2 1/2 times working pressure Operating Temperature Range -20 0 to +250 0 F Flame/Smoke 25/50 Insulation Thermal Conductance R4.2, R6, R8 Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance. Construction Features The Flexmaster U.S.A.® Type 1B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Connector is fabricated with an acoustically transparent PE inner film, which allows mid-range sound energy to penetrate the duct wall. Duct Fabric A Polyethylene fabric, mechanically locked to the duct helix without the use of adhesives. Duct Helix Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives. Vapor Barrier Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden. Insulation Fiberglass insulation jacket, factory wrapped. Mechanical Lock Helix Fire Retardant Vapor Barrier PE Fabric (Polyethylene) Fiberglass Insulation Metal Helix Overlapping Fabric Folds Filler Flexmaster U.S.A.® 1B Metal Helix 110214 1B Masterduct, Inc. 5235 Ted Street Houston, TX 77040 USA Tel. +1.713.462.7694 Fax + 1.713.939.8441 www.flexmasterusa.com www.masterduct.com

Upload: dinhhanh

Post on 19-Aug-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

SUBMITTAL DATA

Acoustical Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive5” w.g. negative thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 1B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Connector is fabricated with an acoustically transparent PE inner film, which allows mid-range sound energy to penetrate the duct wall.

Duct Fabric

A Polyethylene fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Mechanical Lock Helix

Fire Retardant Vapor Barrier

PE Fabric (Polyethylene)

Fiberglass Insulation

Metal HelixOverlapping Fabric Folds

Filler

Flexmaster U.S.A.® 1B

Metal Helix

110214 1B

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Acoustical Flexible Duct Insulated

110214 1M

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive5” w.g. negative thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 1M is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated with an acoustically transparent PE inner film which allows mid-range sound energy to penetrate the duct wall.

Duct Fabric

A Polyethylene fabric, mechanically locked to the duct helix without the use of adhesives..

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Mechanical Lock Helix

Reinforced Metalized Vapor Barrier PE Fabric

(Polyethylene)

Fiberglass Insulation

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 1M

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Flexible Duct Non-Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive5” w.g. negative thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® type 1NI is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Connector is designed for applications in a low to medium pressure HVAC air distribution system.

Duct Fabric

A Polyethylene fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Mechanical Lock Helix

PE Fabric (Polyethylene)

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 1NI

110214 1NI

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

High Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 20” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative, 14” thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Fire Retardant Vapor Barrier

Trilaminate Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 3B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Connector is designed for applications in a low to high pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 3B

110214 3B

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

High Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 20” w.g. positive10” w.g. positive thru 12” dia.5” w.g. negative, 14” & 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Reinforced Metalized Vapor Barrier

Trilaminate Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 3M is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated for application in a low to high pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 3M

110214 3M

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Flexible Duct Non-Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 20” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative, 14” thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 3NI is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Connector is designed for applications in a low to high pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Mechanical Lock Helix

Trilaminate Fabric

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 3NI

110214 3NI

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

High Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 25” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative, 14” thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Fire Retardant Vapor Barrier

PVC Coated Fiberglass Cloth Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 4B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated for application in a low to high pressure HVAC air distribution system.

Duct Fabric

A heavy, PVC coated, Fiberglass cloth fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 4B

110214 4B

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

High Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 25” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative, 14” thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Reinforced Metalized Vapor Barrier PVC Coated

Fiberglass Cloth Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 4M is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated for application in a low to high pressure HVAC air distribution system.

Duct Fabric

A heavy, PVC coated, Fiberglass cloth fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 4M

110214 4M

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Flexible Duct Non-Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 25” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative, 14” thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 4NI is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 air duct is designed for application in a low to high pressure HVAC air distribution system.

Duct Fabric

A heavy, PVC coated, Fiberglass cloth fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Mechanical Lock Helix

PVC Coated Fiberglass Cloth Fabric

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 4NI

110214 4NI

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Low Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative 14” & 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Fire Retardant Vapor Barrier

TrilaminateFabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 5B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated for application in a low to medium pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 5B

110214 5B

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Low Pressure Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative 14” & 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Reinforced Metalized Vapor Barrier Trilaminate

Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 5M is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated for application in a low to medium pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 5M

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 5M

SUBMITTAL DATA

Flexible Duct Non-Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive10” w.g. negative thru 12” dia.5” w.g. negative 14” & 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 5NI is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Connector is designed for applications in a low to medium pressure HVAC air distribution system.

Duct Fabric

A Trilaminate of Aluminum Foil, Fiberglass and Aluminized Polyester, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Mechanical Lock Helix

TrilaminateFabric

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 5NI

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 5NI

SUBMITTAL DATA

Acoustical Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Connector, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 6” w.g. positive5” w.g. negative thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Fire Retardant Vapor Barrier

Spunbond Nylon Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 6B is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated with an acoustically transparent Spunbond Nylon inner film which allows broadband sound energy to penetrate the duct wall.

Duct Fabric

A Spunbond Nylon fabric, mechanically locked to the duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Black, fire retardant, Polyethylene material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Flexmaster U.S.A.® 6B

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 6B

SUBMITTAL DATA

Acoustical Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 6” w.g. positive5” w.g. negative thru 16” dia.1” w.g. negative, 18” & 20” dia.

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Mechanical Lock Helix

Reinforced Metalized Vapor Barrier Spunbond Nylon

Fabric

Fiberglass Insulation

Construction Features

The Flexmaster U.S.A.® Type 6M is manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated with an acoustically transparent Spunbond Nylon inner film which allows broadband sound energy to penetrate the duct wall.

Duct Fabric

A Spunbond Nylon fabric, mechanically locked to the

duct helix without the use of adhesives.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Flexmaster U.S.A.® 6M

Metal HelixOverlapping Fabric Folds

Filler

Metal Helix

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 6M

SUBMITTAL DATA

Flexible Duct Insulated

Technical DataStandard Lengths (ft) 25 ft, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”, 16”, 18”, 20”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 6” w.g. positive1/2” w.g. negative

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -200 to +2000F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Type 9M is an economy flexible duct that meets the quality standards in strength, permeability and fire resistance required in a flexible air duct. Tested to UL standard 181, this Class 1 Air Duct is fabricated with a double lamination of tough polyester,

which encapsulates a steel wire helix.

Duct Fabric

A double lamination of tough polyester, which

encapsulates a steel wire helix.

Duct Helix

Spring steel galvanized helix.

Vapor Barrier

Fire retardant, reinforced aluminum material. Excellent

strength at low temperatures. Will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Flexmaster U.S.A.® 9M

Double Lamination of Polyester

Reinforced Metalized Vapor Barrier

Fiberglass Insulation

Mechanical Lock Helix

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 9M

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F Extractor:

__450 or __900

F Flange only

F Insulation Guard

F All seams sealed

Damper Options:

F BO1, Build-Out (2”),

shaft extender, cover,

handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

SUBMITTAL DATA

SHEET METAL FITTINGS

Order Size Diameter Cone

DiameterHole Cut Diameter

Length w/ Damper

Length w/o Damper

Extractor

900 450

4” 3 ⅞” 5 ⅞” 5 ¾” 10” 6” 2” 2”

5” 4 ⅞” 6 ⅞” 6 ¾” 10” 6” 2 ½” 2”

6” 5 ⅞” 7 ⅞” 7 ¾” 10” 6” 3 2 ½”

7” 6 ⅞” 8 ⅞” 8 ¾” 10” 6” 3 ½” 3”

8” 7 ⅞” 9 ⅞” 9 ¾” 10” 6” 4 3 ½”

9” 8 ⅞” 10 ⅞” 10 ¾” 10” 6” 4 ½” 4”

10” 9 ⅞” 11 ⅞” 11 ¾” 10” 6” 5 4 ½”

12” 11 ⅞” 13 ⅞” 13 ¾” 10” 6” 6 5”

14” 13 ⅞” 15 ⅞” 15 ¾” 10” 6” 7 6”

15” 14 ⅞” 16 ⅞” 16 ¾” 10” 6” 7 6”

16” 15 ⅞” 17 ⅞” 17 ¾” 10” 6” 8 7”

18” 17 ⅞” 19 ⅞” 19 ¾” 10” 6” 9 8”

20” 19 ⅞” 21 ⅞” 21 ¾” 10” 6” 10 9”

(+/-) 1/8” Tolerance on all Sizes

The Flexmaster U.S.A.® Conical Bellmouth with stick on gasket (CB-SOG) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The CB-SOG is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation.

The CB-SOG should be installed using SMACNA installation

standards.

Flexmaster U.S.A.® Conical Bellmouth SOG

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 CB SOG

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F Extractor:

__450 or __900

F Flange with stick on

gasket (SOG)

F Flange only

F Insulation Guard

F All seams sealed

Damper Options:

F BO1, Build-Out (2”),

shaft extender, cover,

handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

SUBMITTAL DATA

SHEET METAL FITTINGS

Order Size Diameter Cone

DiameterHole Cut Diameter

Length w/ Damper

Length w/o Damper

Extractor

900 450

4” 3 ⅞” 5 ⅞” 5 ¾” 10” 6” 2” 2”

5” 4 ⅞” 6 ⅞” 6 ¾” 10” 6” 2 ½” 2”

6” 5 ⅞” 7 ⅞” 7 ¾” 10” 6” 3 2 ½”

7” 6 ⅞” 8 ⅞” 8 ¾” 10” 6” 3 ½” 3”

8” 7 ⅞” 9 ⅞” 9 ¾” 10” 6” 4 3 ½”

9” 8 ⅞” 10 ⅞” 10 ¾” 10” 6” 4 ½” 4”

10” 9 ⅞” 11 ⅞” 11 ¾” 10” 6” 5 4 ½”

12” 11 ⅞” 13 ⅞” 13 ¾” 10” 6” 6 5”

14” 13 ⅞” 15 ⅞” 15 ¾” 10” 6” 7 6”

15” 14 ⅞” 16 ⅞” 16 ¾” 10” 6” 7 6”

16” 15 ⅞” 17 ⅞” 17 ¾” 10” 6” 8 7”

18” 17 ⅞” 19 ⅞” 19 ¾” 10” 6” 9 8”

20” 19 ⅞” 21 ⅞” 21 ¾” 10” 6” 10 9”

(+/-) 1/8” Tolerance on all Sizes

The Flexmaster U.S.A.® Conical Bellmouth (CB) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The CB-SOG should be installed using SMACNA installation

standards.

Flexmaster U.S.A.® Conical Bellmouth

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 CB

LOW LEAKAGE PERFORMANCE DATA

Flexmaster U.S.A.® CBD-BO3 2000G Series

Manufactured to eliminate air loss at the point of assembly, the Flexmaster U.S.A.® CBD-BO3 2000G is a factory sealed fitting, made from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Flexmaster U.S.A.® BO3 damper, with a 2” stool, aluminum rod, nylon bushings and locking quadrant, reduces leakage from the damper barrel to less than 1 cfm at 4 SP (in w.g.)

2” Stool with Locking Quadrant and Handle

Factory Formed 1” Flange with Stick on Gasket

Sealed Seams

0.00

5.00

10.00

15.00

20.00

25.00

30.00

35.00

40.00

0.01 .0 2.03 .0 4.05 .0

CFM

LEA

KAGE 8" CBD 2000 G

12" CBD 2000 G

8" Conical Spin-In

12" Conical Spin-In

Optional Features

Gauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Tested by ORIFLOW Engineering and Testing Services in accordance with

the standards below:

• Relevant sections of ANSI/ASHRAE Standard 126-2008, Method of

Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard Methods for

Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard Methods for

Laboratory Pressure Measurement

Test results available upon request

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 CBD 2000G Leakage Data

SUBMITTAL DATA

Flexmaster U.S.A.® CBD-BO3 2000G Series

SHEET METAL FITTINGS

Order Size Diameter Cone

Diameter Length

6” 5 ⅞” 7 ⅞” 10 ½”

7” 6 ⅞” 8 ⅞” 10 ½”

8” 7 ⅞” 9 ⅞” 10 ½”

9” 8 ⅞” 10 ⅞” 10 ½”

10” 9 ⅞” 11 ⅞” 10 ½”

12” 11 ⅞” 13 ⅞” 10 ½”

14” 13 ⅞” 15 ⅞” 10 ½”

15” 14 ⅞” 16 ⅞” 10 ½”

16” 15 ⅞” 17 ⅞” 10 ½”

18” 17 ⅞” 19 ⅞” 10 ½”

20” 19 ⅞” 21 ⅞” 10 ½”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® 2000 Series Conical Tap

(CBD-BO3 2000G) is a factory sealed fitting, manufactured from

26 gauge, or heavier, galvanized steel to meet SMACNA and UMC

Standards for commercial construction.

The CBD-BO3 2000G, is manufactured with a 1” formed on flange

and Stick on Gasket to provide air-tight installation. It comes with

a 2” stool, aluminum rod, nylon bushings and locking quadrant to

provide easy access and system balancing when installed in a 1 ½”

thick Insulation Wrapped Duct System.

The CBD-BO3 2000G should be installed using current SMACNA

installation standards.

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

2” Stool with Locking Quadrant and Handle

Factory Formed 1” Flange with Stick on Gasket

Sealed Seams

Operating Pressure (w.g.)

Leakage Rate* All sizes (CFM)

.5 .20

1 .30

1.5 .45

2 .50

3 .75

4 .80

*Leakage rate may vary based on installation by mechanical contractor and with added options.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

111405 CBD 2000G

SUBMITTAL DATA

SHEET METAL FITTINGS

Order Size Diameter Cone

Diameter Length

6” 5 ⅞” 7 ⅞” 10 ½”

7” 6 ⅞” 8 ⅞” 10 ½”

8” 7 ⅞” 9 ⅞” 10 ½”

9” 8 ⅞” 10 ⅞” 10 ½”

10” 9 ⅞” 11 ⅞” 10 ½”

12” 11 ⅞” 13 ⅞” 10 ½”

14” 13 ⅞” 15 ⅞” 10 ½”

15” 14 ⅞” 16 ⅞” 10 ½”

16” 15 ⅞” 17 ⅞” 10 ½”

18” 17 ⅞” 19 ⅞” 10 ½”

20” 19 ⅞” 21 ⅞” 10 ½”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® CBD-SOG-BO3 UT fitting is a factory sealed fitting, manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The CBD-SOG-BO3 UT is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation. It comes with Durodyne End Bearings, a 2” stool, aluminum rod, nylon bushings and locking quadrant to provide easy access and system balancing when installed in a 1 ½” thick Insulation Wrapped Duct System.

The CBD-SOG-BO3 UT should be installed using SMACNA instal-

lation standards.

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Silicone on all Seams Flexmaster

U.S.A.® Quadrant and Handle

Factory Formed 1” Flange with Adhesive Gasket

Flexmaster U.S.A.® CBD-SOG-BO3 UT 3000G

Up Close: Quadrant with Durodyne SB 138 Thru Bearing

Features• Heavy 26 gauge G90 Galvanized Steel Body• Heavy 26 gauge G90 Galvanized Steel Flange• Double Sided Adhesive Gasket on Flange• Extra Heavy 24 gauge G90 Galvanized Steel Blade• 3/8” Square Axle Secured to Blade with U-Bolts (2 U-bolts

used for 8” diameter and larger)• Sealed End Bearings by Durodyne (SB338)• 2” Insulation Build-Out• Locking Hand Quadrant with Flexmaster U.S.A.® Handle• Silicone on all Seams• BO3 Build-Out (2”), 3/8” Square Shaft, U-Bolt, Nylon Bush-

ings, Locking Quadrant, Handle

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110514 CBD UT

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

F Extractor:

__450 or __900

Damper Options:

F BO1, Build-Out (2”),

shaft extender,

cover, handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, Rossi

Everlock locking

quadrant, handle

SUBMITTAL DATA

Flexmaster U.S.A.® Conical Bellmouths for Duct Board

SHEET METAL FITTINGS FOR DUCT BOARD

Order Size Diameter Cone

DiameterTab

Length

Length w/

Damper

Length w/o Damper

Extractor

900 450

4” 3 ⅞” 5 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 2” 2”

5” 4 ⅞” 6 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 2 ½” 2”

6” 5 ⅞” 7 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 3 2 ½”

7” 6 ⅞” 8 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 3 ½” 3”

8” 7 ⅞” 9 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 4 3 ½”

9” 8 ⅞” 10 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 4 ½” 4”

10” 9 ⅞” 11 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 5 4 ½”

12” 11 ⅞” 13 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 6 5”

14” 13 ⅞” 15 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 7 6”

15” 14 ⅞” 16 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 7 6”

16” 15 ⅞” 17 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 8 7”

18” 17 ⅞” 19 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 9 8”

20” 19 ⅞” 21 ⅞” 2 ¼” 9 ⅝” 5 ⅝” 10 9”

(+/-) 1/8” Tolerance on all Sizes

The Flexmaster U.S.A.® Conical Bellmouth Extended Tab fitting for duct board is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Conical Bellmouth Extended Tab fitting is manufactured to fit up to 2 1/4” duct board.

The Conical Bellmouth Extended Tab fitting should be installed using SMACNA installation standards.

Extended Tabs for up to 2 1/4” Duct Board

Fitting Description

DC-ET Extended Tab Conical Fitting, No Damper

DC-DET Extended Tab Conical Fitting, Damper, No Build Out

DC-DB1ET Extended Tab Conical Fitting, Damper, BO1

DC-DB3ET Extended Tab Conical Fitting, Damper, BO3

DC-DB4ET Extended Tab Conical Fitting, Damper, BO4

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 CD Extended Tab

SUBMITTAL DATA

Flex Duct Kits

Technical DataStandard Lengths (ft) 5’, 6’, 7’, Special lengths on request

Inside Diameter (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”, 15”,

16”, 18”, 20”

Inside Bend Radius (in) 1 x I.D. (all sizes)

Vapor Barrier Permeance B - (.10) perm, M - (.05) perm A.S.T.M.

E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B,

BOCA, SBBC, HUD/FHA, MIN Property

Std.

Internal Working Pressure (w.g.) See Liner Spec Sheet

Rated Velocity 5500 F.P.M.

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

Construction Features

The Flexmaster U.S.A.® Flex Duct Kits are manufactured to meet the highest quality standards in strength, permeability and fire resistance required in a flexible air duct. The Flex Duct Kits can be fabricated with a variety of different liners, including acoustical liners, which allow sound energy to penetrate the duct wall. Tested to UL standard 181, all Flex Duct Kit assemblies meet the ETL attachment requirements for flexible duct to sheet metal collars.

Duct Helix

Made from corrosive resistant galvanized steel, the duct helix is mechanically formed to attach the duct fabric without the use of adhesives.

Vapor Barrier

Available in a black polyethylene or reinforced aluminum material. Both are fire retardant, have excellent strength at low temperatures, and will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Metal HelixOverlapping Fabric Folds

Filler

Flexmaster U.S.A.® Flex Duct Kits

Metal Helix

110414 FDK

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

(B) Black Polyethylene Vapor Barrier

(M) Reinforced Metalized Vapor Barrier

Optional FeaturesLiner Options:

FF Type 1

FF Type 3

FF Type 4

FF Type 5

FF Type 6

Vapor Barrier Options:

F (B) Black Polyethylene

F (M) Reinforced Metalized

Insulation Options:

F R4.2

F R6.0

F R8.0

Collar Options: standard 26 gauge

F Male

F Female

F Worm Gear

F Other

End A End B_____ _____

_____ _____

_____ _____

_____ _____

SUBMITTAL DATA

Flexmaster U.S.A.® FL & CB Options

SHEET METAL FITTINGS FOR DUCT BOARD

1” Flange, 26 ga., Galvanized

1” Insulation Guard, 26 ga., Galvanized

1” Flange with Gasket

Standard 26 gauge, Galvanized

Available Options:•24, 22 or 20 gauge•Stainless Steel or Aluminum

Damper Options for all Fittings:

•2” Build-out

BO1

•2” Build-out•3/8” Square Steel

Shaft•Locking Quadrant•Nylon Bushing

BO3

•Rossi (Everlock) 2” Build-out•3/8” Square Steel Shaft•Locking Quadrant•Nylon Bushing

BO4

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 FL CB Options

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

F Extractor:

__450 or __900

Damper Options:

F BO1, Build-Out (2”),

shaft extender,

cover, handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, Rossi

Everlock locking

quadrant, handle

SUBMITTAL DATA

Flexmaster U.S.A.® Straight Collar for Duct Board

SHEET METAL FITTINGS FOR DUCT BOARD

Order Size Diameter Tab

Length

Length w/

Damper

Length w/o Damper

Extractor

900 450

4” 3 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 2” 2”

5” 4 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 2 ½” 2”

6” 5 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 3 2 ½”

7” 6 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 3 ½” 3”

8” 7 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 4 3 ½”

9” 8 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 4 ½” 4”

10” 9 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 5 4 ½”

12” 11 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 6 5”

14” 13 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 7 6”

15” 14 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 7 6”

16” 15 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 8 7”

18” 17 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 9 8”

20” 19 ⅞” 2 ¼” 6 ⅝” 2 ⅝” 10 9”

(+/-) 1/8” Tolerance on all Sizes

The Flexmaster U.S.A.® Straight Collar Extended Tab fitting for duct board is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Straight Collar Extended Tab fitting is manufactured to fit up to 2 1/4” duct board.

The Straight Collar Extended Tab fitting should be installed using SMACNA installation standards.

Extended Tabs for up to 2 1/4” Duct Board

Fitting Description

DB-ET Extended Tab Straight Collar Fitting, No Damper

DB-DET Extended Tab Straight Collar Fitting, Damper, No Build Out

DB-DB1ET Extended Tab Straight Collar Fitting, Damper, BO1

DB-DB3ET Extended Tab Straight Collar Fitting, Damper, BO3

DB-DB4ET Extended Tab Straight Collar Fitting, Damper, BO4

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110414 FL Extended Tab

SUBMITTAL DATA

Flexmaster U.S.A.® Straight Collar SOG

SHEET METAL FITTINGS

Order Size Diameter Length w/ Damper

Length w/o Damper

4” 3 ⅞” 6 ½” 3 ½”

5” 4 ⅞” 6 ½” 3 ½”

6” 5 ⅞” 6 ½” 3 ½”

7” 6 ⅞” 6 ½” 3 ½”

8” 7 ⅞” 6 ½” 3 ½”

9” 8 ⅞” 6 ½” 3 ½”

10” 9 ⅞” 6 ½” 3 ½”

12” 11 ⅞” 6 ½” 3 ½”

14” 13 ⅞” 6 ½” 3 ½”

15” 14 ⅞” 6 ½” 3 ½”

16” 15 ⅞” 6 ½” 3 ½”

18” 17 ⅞” 6 ½” 3 ½”

20” 19 ⅞” 6 ½” 3 ½”

(+/-) 1/8” Tolerance on all Sizes

The Flexmaster U.S.A.® Straight Collar with stick on gasket (FL-SOG) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The FL-SOG is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation.

The FL-SOG should be installed using SMACNA installation

standards.

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F Extractor:

__450 or __900

F Flange only

F Insulation Guard

F All seams sealed

Damper Options:

F BO1, Build-Out (2”),

shaft extender, cover,

handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 FL SOG

SUBMITTAL DATA

Flexmaster U.S.A.® Straight Collar

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Straight Collar (FL) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The FL should be installed using SMACNA installation standards.

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F Extractor:

__450 or __900

F Flange only

F Insulation Guard

F All seams sealed

Damper Options:

F BO1, Build-Out (2”),

shaft extender, cover,

handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

Order Size Diameter Hole Cut

DiameterLength w/ Damper

Length w/o Damper

Extractor

900 450

4” 3 ⅞” 5 ¾” 6 ½” 3 ½” 2” 2”

5” 4 ⅞” 6 ¾” 6 ½” 3 ½” 2 ½” 2”

6” 5 ⅞” 7 ¾” 6 ½” 3 ½” 3 2 ½”

7” 6 ⅞” 8 ¾” 6 ½” 3 ½” 3 ½” 3”

8” 7 ⅞” 9 ¾” 6 ½” 3 ½” 4 3 ½”

9” 8 ⅞” 10 ¾” 6 ½” 3 ½” 4 ½” 4”

10” 9 ⅞” 11 ¾” 6 ½” 3 ½” 5 4 ½”

12” 11 ⅞” 13 ¾” 6 ½” 3 ½” 6 5”

14” 13 ⅞” 15 ¾” 6 ½” 3 ½” 7 6”

15” 14 ⅞” 16 ¾” 6 ½” 3 ½” 7 6”

16” 15 ⅞” 17 ¾” 6 ½” 3 ½” 8 7”

18” 17 ⅞” 19 ¾” 6 ½” 3 ½” 9 8”

20” 19 ⅞” 21 ¾” 6 ½” 3 ½” 10 9”

(+/-) 1/8” Tolerance on all Sizes

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 FL

SUBMITTAL DATA

Flexmaster U.S.A.® FLD-BO3 2000G Series

SHEET METAL FITTINGS

Order Size Diameter Length

6” 5 ⅞” 6 ½”

7” 6 ⅞” 6 ½”

8” 7 ⅞” 6 ½”

9” 8 ⅞” 6 ½”

10” 9 ⅞” 6 ½”

12” 11 ⅞” 6 ½”

14” 13 ⅞” 6 ½”

15” 14 ⅞” 6 ½”

16” 15 ⅞” 6 ½”

18” 17 ⅞” 6 ½”

20” 19 ⅞” 6 ½”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® 2000 Series low leakage spin collar (FLD-BO3 2000G) is a factory sealed fitting, manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The FLD-BO3 2000G, is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation. It comes with a 2” stool, aluminum rod, nylon bushings and locking quadrant to provide easy access and system balancing when installed in a 1 ½” thick Insulation Wrapped Duct System.

The FLD-BO3 2000G should be installed using current SMACNA

installation standards.

2” Stool with Locking Quadrant and HandleFactory

Formed 1” Flange with Stick on Gasket

Sealed Seams

Operating Pressure (w.g.)

Leakage Rate* All sizes (CFM)

.5 .20

1 .30

1.5 .45

2 .50

3 .75

4 .80

*Leakage rate may vary based on installation by mechanical contractor and with added options.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 FLD 2000G

SUBMITTAL DATA

FlexRight® Elbow Item #41650

Flexmaster U.S.A.® FlexRight® Elbow

Designed to form flexible duct into highly efficient 90 degree elbows.

Universal Mount, 1 piece fully adjustable radius forming brace to support 4” inch (102-mm) through 16” inch (406mm) diameter flexible air ducts.

Nylon cable ties secure duct to duct support, (purchased separately and available from Flexmaster U.S.A.®)

Made from 100% recycled material (copolymer polypropylene)

UL 2043 Listed. http://flexright.net/docs/specifications.php

Meets ASHRAE’s Advanced Energy Design Guides for Schools, warehouses, office and retail buildings.

The FlexRight® flexible duct elbow is manufactured by Build Right Products. Please see their website www.flexright.net for further details.

1. Install flexible duct over air device per flexible duct manufacturer’s installation instructions.

2. Thread cable ties through both FlexRight® Elbow saddle bands. Cable ties not included.

3. Position one end of FlexRight® Elbow around neck of air device and the other under the flexible duct to form 900 elbow. For best results, keep duct insulation out from under cable tie as it is tightened.

4. Using cable tie tensioning tool, fasten cable tie around neck of air device to secure FlexRight® Elbow.

5. Fasten second cable tie around flexible duct. Do not over-tighten, as to crush the flexible duct.

6. Cut-off and discard excess from both cable tie ends.

110214 FlexRight Elbow

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Quick Release Stainless Steel Clamp

Clamp Flex Size Clamp Min. Dia. Max. LengthLS-88 4 2.06 6.00 20”

LS-88 5 2.06 6.00 20”

LS-104 6 1.75 7.00 23”

LS-152 8 2.00 10.00 32”

LS-152 9 2.00 10.00 32”

LS-188 10 2.06 12.31 40”

LS-232 12 10.19 14.00 48”

LS-258 14 10.00 16.00 52”

*LS-280 16 14.25 18.00 58”

LS-312 18 14.00 20.00 64”

LS-344 20 16.00 22.00 73”

*Can only be used on stated size.

All materials used in the manufacture of the subject clamp are certified by our suppliers to meet our material specifications. The band is made from AISI 201 stainless steel. The housing is made from AISI 201 stainless steel. The screw is made of AISI 1018 carbon steel. The bridge is made from AISI 410 stainless steel neutral hardened and drawn.

Clamps meet the Maximum Concentration Values (MCV) requirements of the following material: European Directive 2002/95/EC also known as the ROHS Directive. Therefore the clamps are ROHS compliant.

Flexmaster U.S.A.® Quick Release LS Series Clamp

Slide clamp into position

Slide band through housing

Snap screw down for

engagement

Easy On...Easy Off...in 3 Simple Steps!Reverse procedure for quick release and removal.

No need to disassemble connection.

110214 LS Series Clamps

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Medical Grade Insulated Acoustical Duct

Technical DataStandard Lengths (ft) 5’, 6’, 7’

Inside Diameter (in) 6”, 8”, 10”, 12”, 14”, 16”

Inside Bend Radius (in) 1/2 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 6” w.g. positive2” w.g. negative

Rated Velocity 5500 F.P.M.

Min Burst Pressure 15” w.g. positive

Operating Temperature Range -400 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R6

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

The Flexmaster U.S.A.® Medical Grade Acoustical Triple Lock Ductwork, starts with an all aluminum perforated flexible core, with a free open area of 20-25%. The semi rigid and lightweight air duct is manufactured by using a dead soft aluminum strip which is spirally wound, perforated and mechanically locked for strength and durability. The fiberglass blanket is totally isolated from the air stream by UL approved acoustically transparent seamless polyethylene liner. Available options of a black fire retardant polyethylene (MGA-TLB) or metallized polyester film (MGA-TLM). A minimum bend radius to center line is recommended at 1.5 diameters. End fittings can be provided to accommodate job conditions.

Flexmaster U.S.A.® MGA Triple Lock

MGA TLB MGA TLM MGA TLD

Flexmaster U.S.A.® MGA

Acoustical Triple LockHERTZ 125 250 500 1K 2K 4K

MGA TLB R6 12.2 23.2 22.9 27.8 21.4 11.2

MGA TLM R6 15.8 24.6 25.8 27.9 18.2 10.0

Noise reduction dB (6 ft length, 10” dia.)

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 MGA TL

SUBMITTAL DATA

Triple Lock Non-Insulated

Technical DataStandard Lengths (ft) 8 ft, Special lengths on request up to 10 ft

Inside Diameter (in) 3”, 4”, 5”, 6”, 8”, 10”, 12”, 14”, 16”, 18”

Inside Bend Radius (in) Min. one dia.

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 0 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive thru 16”6” w.g. positive, 18”12” w.g. negative thru 16” dia.4” w.g. negative, 18”

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -600 to +6000F

Flame/Smoke Less than 0

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

The Flexmaster U.S.A.® Triple Lock Aluminum ducting is an all metal flexible duct that is constructed entirely without the use of adhesives. The Triple Lock mechanical joint makes an air tight seam, while the circumferential corrugations provide excellent strength and flexibility. Minimum bend radius to center line is one diameter. However, our recommended radius is 1 ½ diameters in accordance with accepted practice. Triple Lock Aluminum ducting may be easily cut to size and hand formed into elbows or offsets to suit job conditions without subsequent sagging or droop. Triple Lock has much lower pressure loss than conventional cloth ducts due to the small but consistent corrugations that provide both strength and flexibility.

Triple Lock Standard Aluminum Duct

Flexmaster U.S.A.® NI-TL

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 NITL

SUBMITTAL DATA

Nylon Clamp

Flexmaster U.S.A.® UL 181B-C Clamp

Part Number

Max Dia. Formed

Length (L)

Width (W) Thickness Avg. Loop

TensileStd. Pkg.

Qty.UL 181B-C 11.0 (279.4) 37.1 (942.8) .340 (8.610) .090 (2.300) 175 (778) 50

*NOTE: Clamps adjustable for DUCT diameters 4” thru 10”; for larger diameters, join two or more clamps together. Can be used for both high and low pressure flexible duct.

UL 181 listed under file MH29946.

The Nylon clamps are manufactured by Bay State Cable Ties. Please see their website at www.baystatecableties.com for further information.

Material6/6 Nylon

ColorNatural Nylon

Temp Range-400F to 1850F

FlammabilityU.L. 94V-2

ATBLess than 5 sec. per ASTM D635

110214 Nylon Clamp

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

Optional FeaturesGauge Options: standard 24 ga

FF 22 ga

FF 20 ga

Damper Options:

F BO1, Build-Out (2”), shaft

extender, cover, handle

F BO3, Build-Out (2”), 3/8”

square shaft, U-bolt,

nylon bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

Material Options:

F Aluminum

F Stainless steel

F Paint grip

SUBMITTAL DATA

Flexmaster U.S.A.® Saddle Taps

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Saddle Tap fittings are manufactured from 24 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Saddle Tap fittings are sized for flex duct and can be made to fit up to 24” spiral pipe. The Saddle Tap fittings can be ordered as straight FL, straight FL 450 or our high efficiency STO in the 900, 450 or Center model.

The Saddle Tap fittings should be installed using SMACNA

installation standards.

STO ST 450 STO ST 900 STOC ST

FL ST FL ST 450

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 Saddle Taps

Optional FeaturesConstruction Options:

Stick on Gasket (SOG)

Single Pane Viewport

Double Pane Viewport

Cable

Insulation Options:

R4.2 R6

SUBMITTAL DATA

Flexmaster U.S.A.® “INSPECTOR SERIES” SDSM-SPIN DOORHIGH PRESSURE ACCESS DOOR FOR SHEET METALLow Leakage • Quick Installation • Safe Entry and Exit

Nominal Door Size* (in.)

Hole Cut for SDSM Frame* (in.)

Cams Per Door

8 7 3/16 2

10 9 3/16 3

12 11 3/16 3

18 17 3/16 5

24 23 3/16 5

*Tolerance + 1/32”

The Flexmaster U.S.A.® Inspector Series Spin Door is manufactured with heavy gauge galvanized steel to meet the highest quality standards required in a high pressure access door. This insulated and gasketed access door is designed for applications in a low to high pressure HVAC air distribution system.

The Inspector Series Spin Door’s frame is made of 22-gauge galvanized steel, rolled and double hemmed. The inner door is made of 24-gauge galvanized steel, rolled and triple hemmed. No raw edges are exposed, and, therefore, a safe entry and exit is ensured.

The Inspector Series Spin Door is installed using SMACNA installation guidelines for spin in fittings.

Operating Pressure (w.g.)

Leakage Rate* All door sizes (CFM)

1 0

2 .5

3 1

4 1

6 1.5

10 2

*Leakage rate may vary based on installation by mechanical contractor and with added options, such as port and SOG.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

110214 SDSM

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Flexmaster U.S.A.® Side Inlet Diffuser Box

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Side Inlet Diffuser Box (SIDB) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The SIDB is manufactured for plenum sizes 6” x 6” up to 24” x 24”, and outlet sizes 4” up to 20”. Custom sizes are available upon request.

The SIDB should be installed using SMACNA installation

standards.

Standard Features• 26 Gauge G-90 Galvanized Steel

• Plenum Sizes: 6” x 6” up to 24” x 24”

• Outlet Sizes: 4” up to 20”

• 1/8” Tolerance

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F 26 ga, Black interior

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F Flange with stick on

gasket (SOG)

F Flange only

F Insulation guard

F All seams sealed

F Oval outlet

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 SIDB

SUBMITTAL DATA

Flexmaster U.S.A.® Connecting Sleeve

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Connecting Sleeve (SL) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The SL should be installed using SMACNA installation standards.

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Damper Options:

F BO1, Build-Out (2”),

shaft extender, cover,

handle

F BO3, Build-Out

(2”), 3/8” square

shaft, U-bolt, nylon

bushings, locking

quadrant, handle

F BO4, Build-Out (2”),

3/8” square shaft,

U-bolt, nylon bushings,

Rossi Everlock locking

quadrant, handle

Order Size Diameter Hole Cut Diameter

Length w/ and w/o Damper

4” 3 ⅞” 5 ¾” 7 ½”

5” 4 ⅞” 6 ¾” 7 ½”

6” 5 ⅞” 7 ¾” 7 ½”

7” 6 ⅞” 8 ¾” 7 ½”

8” 7 ⅞” 9 ¾” 7 ½”

9” 8 ⅞” 10 ¾” 7 ½”

10” 9 ⅞” 11 ¾” 7 ½”

12” 11 ⅞” 13 ¾” 7 ½”

14” 13 ⅞” 15 ¾” 7 ½”

15” 14 ⅞” 16 ¾” 7 ½”

16” 15 ⅞” 17 ¾” 7 ½”

18” 17 ⅞” 19 ¾” 7 ½”

20” 19 ⅞” 21 ¾” 7 ½”

(+/-) 1/8” Tolerance on all Sizes

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 SL

LOW LEAKAGE PERFORMANCE DATA

Flexmaster U.S.A.® SLD-BO3 2000G Series

Manufactured to eliminate air loss at the point of assembly, the Flexmaster U.S.A.® SLD-BO3 2000G is a factory sealed fitting, made from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Flexmaster U.S.A.® BO3 damper, with a 2” stool, aluminum rod, nylon bushings and locking quadrant, reduces leakage from the damper barrel to less than 1 cfm at 2 SP (in w.g.)

Optional Features

Gauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

2” Stool with Locking Quadrant and Handle

Sealed Seams

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

0.0 1.0 2.0 3.0 4.0 5.0

CFM

LEA

KAGE

8" SLD 2000 G

12" SLD 2000 G

SP (in w.g.)

Tested by ORIFLOW Engineering and Testing Services in accordance with the

standards below:

• Relevant sections of ANSI/ASHRAE Standard 126-2008, Method of Testing

HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard Methods for

Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard Methods for

Laboratory Pressure Measurement

Test results available upon request

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 SLD 2000G Leakage Data

SUBMITTAL DATA

Flexmaster U.S.A.® SLD-BO3 2000G Series

SHEET METAL FITTINGS

Order Size Diameter Length

6” 5 ⅞” 7 ½”

7” 6 ⅞” 7 ½”

8” 7 ⅞” 7 ½”

9” 8 ⅞” 7 ½”

10” 9 ⅞” 7 ½”

12” 11 ⅞” 7 ½”

14” 13 ⅞” 7 ½”

15” 14 ⅞” 7 ½”

16” 15 ⅞” 7 ½”

18” 17 ⅞” 7 ½”

20” 19 ⅞” 7 ½”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® 2000 Series low leakage volume damper (SLD-BO3 2000G) is a factory sealed fitting, manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The SLD-BO3 2000G, is manufactured to provide air-tight installation. It comes with a 2” stool, aluminum rod, nylon bushings and locking quadrant to provide easy access and system balancing when installed in a 1 ½” thick Insulation Wrapped Duct System.

The SLD-BO3 2000G should be installed using current SMACNA

installation standards.

2” Stool with Locking Quadrant and Handle

Improved Nylon Bushings

Sealed Seams

Operating Pressure (w.g.)

Leakage Rate* All sizes (CFM)

.5 .20

1 .30

1.5 .45

2 .50

3 .75

4 .80

*Leakage rate may vary based on installation by mechanical contractor and with added options.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 SLD 2000G

SUBMITTAL DATA

Stainless Steel Clamp

Bridging over helix allows for better contact of clamp to duct thus lowering leakage.

Flexmaster U.S.A.® Quick Release SC Series Clamp

Clamp SC04 SC05 SC06 SC07 SC08 SC09 SC10 SC12 SC14 SC16 SC18 SC20Flex Size 4” 5” 6” 7” 8” 9” 10” 12” 14” 16” 18” 20”

All materials used in the manufacture of the subject clamp are certified by our suppliers to meet our material specifications. The band is made from AISI 201 stainless steel. The housing is made from AISI 201 stainless steel. The screw is made of AISI 1018 carbon steel. The bridge is made from AISI 410 stainless steel neutral hardened and drawn.

Clamps meet the Maximum Concentration Values (MCV) requirements of the following material: European Directive 2002/95/EC also known as the ROHS Directive. Therefore the clamps are ROHS compliant.

110214 Spin Clamp

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

Optional FeaturesGauge Options: standard 26 ga, black interior not available

FF 24 ga

FF 22 ga

FF 20 ga

Corner Options:

F Open

F Closed

Construction Options:

F All seams sealed

Material Options: black interior not available

F Aluminum

F Stainless steel

F Paint grip

Size Options:

F 2” Oversized

SUBMITTAL DATA

Flexmaster U.S.A.® Square to Round Adapters

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Square to Round Adapter is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Square to Round Adapter is manufactured with a standard black interior, depths of 2”, 3” and 4” with an open or closed corner. Custom sizes are available upon request.

The Square to Round Adapter should be installed using SMACNA installation standards.

Fitting Description

F2SO 2” Depth, Square, Open Corner

F2SC 2” Depth, Square, Closed Corner

F3SO 3” Depth, Square, Open Corner

F3SC 3” Depth, Square, Closed Corner

F4SO 4” Depth, Square, Open Corner

F4SC 4” Depth, Square, Closed Corner

(+/-) 1/8” Tolerance on all Sizes

Square to Round 2” Oversized Square to Round

Black Interior

Standard Features• Black Interior

• 26 Gauge Primed G-90 Galvanized Steel

• 1/8” Tolerance

• Standard Depth Size: 2”, 3”, 4”

• Open or Closed Corners

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 Sq to Rd

SUBMITTAL DATA

Triple Lock Stainless Steel Non-Insulated

Technical DataStandard Lengths (ft) 8 ft, Special lengths on request up to 10 ft

Inside Diameter (in) 3”, 4”, 5”, 6”, 8”, 10”, 12”, 14”, 16”, 18”

Inside Bend Radius (in) Min. one dia.

Air Friction Loss See Friction Loss Chart for details

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 0 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 12” w.g. positive 12” w.g. negative

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -600 to +15000F

Flame/Smoke Less than 0

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

The Flexmaster U.S.A.® Triple Lock 316 Stainless steel ducting is an all metal flexible duct that is constructed entirely without the use of adhesives. The Triple Lock mechanical joint makes an air tight seam, while the circumferential corrugations provide excellent strength and flexibility. Minimum bend radius to center line is one diameter. However, our recommended radius is 1 ½ diameters in accordance with accepted practice. Triple Lock stainless steel ducting may be easily cut to size and hand formed into elbows or offsets to suit job conditions without subsequent sagging or droop. Triple Lock has much lower pressure loss than conventional cloth ducts due to the small but consistent corrugations that provide both strength and flexibility.

Triple Lock Standard Stainless Steel Duct

Flexmaster U.S.A.® SS-NI-TL

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 SSNITL

SUBMITTAL DATA

Flexmaster U.S.A.® Side Takeoff for Duct Board

SHEET METAL FITTINGS FOR DUCT BOARD

Order Size

Diameter (D)

Length (L) w/ and w/o

Damper

Height (H)

Width (W)

5” 4 ⅞” 13” 5” 9”

6” 5 ⅞” 13” 5” 9”

7” 6 ⅞” 13” 5” 11”

8” 7 ⅞” 13” 6” 12”

9” 8 ⅞” 13” 7” 13”

10” 9 ⅞” 13” 8” 14”

12” 11 ⅞” 13” 10” 16”

14” 13 ⅞” 13” 12” 18”

15” 14 ⅞” 13” 13” 19”

16” 15 ⅞” 13” 14” 20”

18” 17 ⅞” 13” 16” 22”

20” 19 ⅞” 13” 18” 24”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® Side Takeoff (STO) Extended Tab fitting for duct board is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Side Takeoff Extended Tab fitting is manufactured to fit up to 2 1/4” duct board.

The Side Takeoff Extended Tab fitting should be installed using

SMACNA installation standards.

Standard Features• 26 gauge G90 Galvanized Steel• 1” Flange with Unique Corner Clips for Extra Strength• Prepunched Mounting Holes• Double Sided Adhesive Gasket for Minimal Leakage• 2 1/4” Extended Tab for Duct board

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

Damper Options:

F BO1, Build-Out (2”), shaft

extender, cover, handle

F BO3, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, locking quadrant,

handle

F BO4, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, Rossi Everlock

locking quadrant, handle

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110414 STO Extended Tab

Fitting Description

DSC-ET Extended Tab STO, No Damper

DSC-DET Extended Tab STO, Damper, No Build Out

DSC-DB1ET Extended Tab STO, Damper, BO1

DSC-DB3ET Extended Tab STO, Damper, BO3

DSC-DB4ET Extended Tab STO, Damper, BO4

SUBMITTAL DATA

Flexmaster U.S.A.® Side Takeoff 450

SHEET METAL FITTINGS

Order Size A B C D E F G H I

5” 4 ⅞” 12” 2” 7 ½” 9” 9” 11” 5” 7”

6” 5 ⅞” 12” 2” 7 ½” 9” 9” 11” 5” 7”

7” 6 ⅞” 12” 2” 7 ½” 10” 11” 13” 5” 7”

8” 7 ⅞” 13” 2” 7 ½” 10” 12” 14” 6” 8”

9” 8 ⅞” 13” 2” 7 ½” 11” 13” 15” 7” 9”

10” 9 ⅞” 14” 2” 7 ½” 12” 14” 16” 8” 10”

12” 11 ⅞” 15” 2” 7 ½” 13” 16” 18” 10” 12”

14” 13 ⅞” 16” 2” 7 ½” 15” 18” 20” 12” 14”

16” 15 ⅞” 17” 2” 7 ½” 16” 20” 22” 14” 16”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® Side Takeoff 450 (STO45) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Side Takeoff is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation.

The Side Takeoff should be installed using SMACNA installation standards.

Standard Features• 26 gauge G90 Galvanized Steel• 4” w.g. construction• 1” Flange with Unique Corner Clips for Extra Strength• Prepunched Mounting Holes• Double Sided Adhesive Gasket for Minimal Leakage

A

B

C

D

E

F

GH

IOptional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

Damper Options:

F BO1, Build-Out (2”), shaft

extender, cover, handle

F BO3, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, locking quadrant,

handle

F BO4, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, Rossi Everlock

locking quadrant, handle

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 STO45

SUBMITTAL DATA

Flexmaster U.S.A.® Side Takeoff 900

SHEET METAL FITTINGS

Order Size

Diameter (D)

Length (L) w/ and w/o

Damper

Height (H)

Width (W)

5” 4 ⅞” 13” 5” 9”

6” 5 ⅞” 13” 5” 9”

7” 6 ⅞” 13” 5” 11”

8” 7 ⅞” 13” 6” 12”

9” 8 ⅞” 13” 7” 13”

10” 9 ⅞” 13” 8” 14”

12” 11 ⅞” 13” 10” 16”

14” 13 ⅞” 13” 12” 18”

15” 14 ⅞” 13” 13” 19”

16” 15 ⅞” 13” 14” 20”

18” 17 ⅞” 13” 16” 22”

20” 19 ⅞” 13” 18” 24”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® Side Takeoff (STO) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Side Takeoff is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation.

The Side Takeoff should be installed using SMACNA installation standards.

Standard Features• 26 gauge G90 Galvanized Steel• 4” w.g. construction• 1” Flange with Unique Corner Clips for Extra Strength• Prepunched Mounting Holes• Double Sided Adhesive Gasket for Minimal Leakage

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

Damper Options:

F BO1, Build-Out (2”), shaft

extender, cover, handle

F BO3, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, locking quadrant,

handle

F BO4, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, Rossi Everlock

locking quadrant, handle

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110214 STO90

SUBMITTAL DATA

Flexmaster U.S.A.® Side Takeoff Center

SHEET METAL FITTINGS

The Flexmaster U.S.A.® Side Takeoff (STOC) is manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The Side Takeoff is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation.

The Side Takeoff should be installed using SMACNA installation standards.

Standard Features• 26 gauge G90 Galvanized Steel• 4” w.g. construction• 1” Flange with Unique Corner Clips for Extra Strength• Prepunched Mounting Holes• Double Sided Adhesive Gasket for Minimal Leakage

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Construction Options:

F All seams sealed

Damper Options:

F BO1, Build-Out (2”), shaft

extender, cover, handle

F BO3, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, locking quadrant,

handle

F BO4, Build-Out (2”), 3/8”

square shaft, U-bolt, nylon

bushings, Rossi Everlock

locking quadrant, handle

^ ^

_

`

a

bcd e

Order Size A B C D E F G H

5” 4 ⅞” 13” 5 ½” 7 ½” 5” 9” 11” 7”

6” 5 ⅞” 13” 5 ½” 7 ½” 5” 9” 11” 7”

7” 6 ⅞” 13” 5 ½” 7 ½” 5” 11” 13” 7”

8” 7 ⅞” 13” 5 ½” 7 ½” 6” 12” 14” 8”

9” 8 ⅞” 13” 5 ½” 7 ½” 7” 13” 15” 9”

10” 9 ⅞” 13” 5 ½” 7 ½” 8” 14” 16” 10”

12” 11 ⅞” 13” 5 ½” 7 ½” 10” 16” 18” 12”

14” 13 ⅞” 13” 5 ½” 7 ½” 12” 18” 20” 14”

15” 14 ⅞” 13” 5 ½” 7 ½” 13” 19” 21” 15”

16” 15 ⅞” 13” 5 ½” 7 ½” 14” 20” 22” 16”

18” 17 ⅞” 13” 5 ½” 7 ½” 16” 22” 24” 18”

20” 19 ⅞” 13” 5 ½” 7 ½” 18” 24” 26” 20”

(+/-) 1/8” Tolerance on all Sizes.

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110414 STOC

SUBMITTAL DATA

Flexmaster U.S.A.® STOD-BO3 2000G Series

SHEET METAL FITTINGS

Order Size Diameter Length Height Width

6” 5 ⅞” 13” 5” 9”

7” 6 ⅞” 13” 5” 11”

8” 7 ⅞” 13” 6” 12”

9” 8 ⅞” 13” 7” 13”

10” 9 ⅞” 13” 8” 14”

12” 11 ⅞” 13” 10” 16”

14” 13 ⅞” 13” 12” 18”

15” 14 ⅞” 13” 13” 19”

16” 15 ⅞” 13” 14” 20”

18” 17 ⅞” 13” 16” 22”

20” 19 ⅞” 13” 18” 24”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® 2000 Series Side Takeoff (STOD-BO3 2000G) is a factory sealed fitting, manufactured from 26 gauge, or heavier, galvanized steel to meet SMACNA and UMC Standards for commercial construction.

The STOD-BO3 2000G, is manufactured with a 1” formed on flange and Stick on Gasket to provide air-tight installation. It comes with a 2” stool, aluminum rod, nylon bushings and locking quadrant to provide easy access and system balancing when installed in a 1 ½” thick Insulation Wrapped Duct System.

The STOD-BO3 2000G should be installed using current SMACNA

installation standards.

2” Stool with Locking Quadrant and Handle

Factory Formed 1” Flange with Stick on Gasket

Sealed Seams

Operating Pressure (w.g.)

Leakage Rate* All sizes (CFM)

.5 .20

1 .30

1.5 .45

2 .50

3 .75

4 .80

*Leakage rate may vary based on installation by mechanical contractor and with added options.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

Optional FeaturesGauge Options: standard 26 ga

FF 24 ga

FF 22 ga

FF 20 ga

Material Options:

F Aluminum

F Stainless steel

F Paint grip

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

111404 STOD 2000G

Optional FeaturesGauge Options: standard 24 ga body/ 22 ga damper

FF 22 ga

FF 20 ga

Damper Options:

F No Damper

F BO3, Build-Out (2”), 3/8” square

shaft, U-bolt, nylon bushings,

locking quadrant, handle

F Aluminum Shaft, No Locking

Quadrant for Regulator

Axis Options:

F Y Axis Left

F Standard X Axis

F Y Axis Right

SUBMITTAL DATA

Flexmaster U.S.A.® LDS Side Takeoff Series

SHEET METAL FITTINGS

Order Size Diameter Length Height Width

6” 5 ⅞” 13” 5” 9”

7” 6 ⅞” 13” 5” 11”

8” 7 ⅞” 13” 6” 12”

9” 8 ⅞” 13” 7” 13”

10” 9 ⅞” 13” 8” 14”

12” 11 ⅞” 13” 10” 16”

14” 13 ⅞” 13” 12” 18”

15” 14 ⅞” 13” 13” 19”

16” 15 ⅞” 13” 14” 20”

18” 17 ⅞” 13” 16” 22”

20” 19 ⅞” 13” 18” 24”

(+/-) 1/8” Tolerance on all Sizes.

The Flexmaster U.S.A.® LDS Side Takeoff(STO-LDS, STOD-LDS) is a factory sealed fitting, manufactured with a 24 gauge body and a 22 gauge damper, galvanized steel, to meet SMACNA and UMC Standards for commercial construction.

The LDS Side Takeoff, is manufactured with a 1” formed on flange with unique corner clips for extra strength and Stick on Gasket to provide air-tight installation. It comes with prepunched mounting holes, and a 2” stool, aluminum rod, nylon bushings and locking quadrant to provide easy access and system balancing when installed in a 1 ½” thick Insulation Wrapped Duct System.

The LDS Side Takeoff should be installed using SMACNA installa-tion standards.

Flexmaster U.S.A.® Quadrant and Handle

Factory Formed 1” Flange with Adhesive Gasket

Features• Heavy 24 gauge G90 Galvanized Steel Body• Extra Heavy 22 gauge G90 Galvanized Steel Damper• 4” w.g. construction• 1” Flange with Unique Corner Clips for Extra Strength• Prepunched Mounting Holes• Double Sided Adhesive Gasket for Minimal Leakage• 3/8” Square Axle Secured to Blade with U-Bolts (2 U-bolts

used for 8” diameter and larger)• 2” Insulation Build-Out• Locking Hand Quadrant with Flexmaster U.S.A.® Handle• BO3 Build-Out (2”), 3/8” Square Shaft, U-Bolt, Nylon

Bushings, Locking Quadrant, Handle

Y Axis Left

StandardX Axis

Y Axis Right

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110414 STOD LDS

Optional FeaturesMaterial Options:

Aluminum

Stainless Steel

Paint Grip

Construction Options:

Stick on Gasket (SOG)

Single Pane Viewport

Double Pane Viewport

Cable

Extended Tab for Ductboard

Insulation Options:

R4.2 R6

Options:

Cam Hinge

Handle Options: Ventlok handles substitute for each Cam

Ventlok 100

Ventlok 140

Ventlok 260

SUBMITTAL DATA

Flexmaster U.S.A.® “INSPECTOR SERIES” TBSM-TAB DOORACCESS DOORS FOR SHEET METAL

Nominal Door Size* (in.)

Duct Cut Sizes* (in.)

Cams Per Door

Hinge Cam

6x6 5 ¼ x 5 ¼ 1 2

8x8 7 ¼ x 7 ¼ 1 2

10x10 9 ¼ x 9 ¼ 1 2

12x12 11 ¼ x 11 ¼ 1 2

14x14 13 ¼ x 13 ¼ 2 4

16x16 15 ¼ x 15 ¼ 2 4

18x18 17 ¼ x 17 ¼ 2 4

20x20 19 ¼ x 19 ¼ 2 4

24x24 23 ¼ x 23 ¼ 2 4

*Tolerance + 1/32”

The Flexmaster U.S.A.® Inspector Series Tab Door is manufactured with heavy gauge galvanized steel to meet the highest quality standards required in a low pressure access door. This insulated and gasketed access door is designed for applications in a low pressure HVAC air distribution system.

The Inspector Series Tab Door’s frame is made of 22-gauge galvanized steel that is formed, notched and hemmed. The double sided insulated inner door is made of 24-gauge galvanized steel that is formed, hemmed and available with various options.

The Inspector Series Tab Door is installed using SMACNA installation guidelines.

Operating Pressure (w.g.)

Leakage Rate* All door sizes (CFM)

.5 0

1 1

1.5 2

2 3

3 6

4 14

*Leakage rate may vary based on installation by mechanical contractor and with added options, such as port and SOG.

Tested in accordance with:

• Relevant sections of ANSI/ASHRAE Standard 126-2008,

Method of Testing HVAC Air Ducts and Fittings

• Relevant sections of ANSI/ASHRAE 41.2-2006, Standard

Methods for Laboratory Airflow Measurement

• Relevant sections of ANSI/ASHRAE 41.3-1989, Standard

Methods for Laboratory Pressure Measurement

TBSM-H TBSM-Port TBSM-SOG TBSM-Extended Tabfor Ductboard

110214 TBSM

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

SUBMITTAL DATA

Thermo Sleeve

Technical DataStandard Lengths (ft) 25’, Special lengths on request

Made to Cover Flexible Duct Diameters (in) 3”, 4”, 5”, 6”, 7”, 8”, 9”, 10”, 12”, 14”,

15”, 16”, 18”, 20”

Vapor Barrier Permeance B - (.10) perm, A.S.T.M. E96,

Procedure A

M - (.05) perm, A.S.T.M. E96,

Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met NFPA 90A and 90B, BOCA, SBBC,

HUD/FHA, MIN Property Std.

Rated Velocity 5500 F.P.M.

Operating Temperature Range -200 to +2500F

Flame/Smoke 25/50

Construction Features

The Flexmaster U.S.A.® Thermo Sleeve contains the insulation and outer jacket only. It is made to easily slip over flexible air duct.

Vapor Barrier

Available in a black polyethylene or reinforced aluminum material. Both are fire retardant, have excellent strength at low temperatures, and will not age harden.

Insulation

Fiberglass insulation jacket, factory wrapped.

Flexmaster U.S.A.® Thermo Sleeve

110414 Thermo Sleeves

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

Optional FeaturesVapor Barrier Options:

F (B) Black Polyethylene

F (M) Reinforced Metalized

Insulation Options:

F R4.2

F R6.0

F R8.0

(B) Black Polyethylene Vapor Barrier

(M) Reinforced Metalized Vapor Barrier

Standard lengths (feet) 5 ft

Inside Diameter (inch) 6”, 8”, 10”, 12”, 14”, 16”

Inside Bend Radius (inches) 1.5 x I.D. (all sizes)

Air Friction Loss See Friction Loss Chart

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (W.G.)

10” w.g. positive, 12” w.g. negative

Rated Velocity 5500 F.P.M.

Minimum Burst Pressure 2 ½ times working pressure

Operating Temperature Range -60o to +250oF

Flame Spread Less than 25

Smoke Developed Less than 50

Thermal Conductance R8

Product FPM 125 250 500 1K 2K 4K 8K

SA-TLD5 10” 0 31 39 42 41 32 22 20

2500 29 38 40 40 31 22 20

Product FPM 125 250 500 1K 2K 4K 8K

SA-TLD5 6"

-2500 12 25 >44 44 34 21 14

0 10 24 44 46 34 21 14

2500 10 25 >41 >42 34 21 13

SA-TLD5 10"

-2500 7 18 31 38 25 16 12

0 6 18 31 37 25 16 11

2500 6 17 29 36 25 16 11

SA-TLD5 14"

-2500 9 15 25 28 15 12 8

0 5 11 24 26 16 13 7

2500 7 13 23 26 16 13 6

°

Product FPM 125 250 500 1K 2K 4K 8K

SA-TLD5 6"

-2500 10 24 45 46 35 23 14

0 10 22 44 47 34 21 14

2500 8 24 42 44 35 23 13

SA-TLD5 10"

-2500 5 19 30 38 25 15 11

0 4 15 31 36 26 14 9

2500 4 18 28 36 25 15 10

SA-TLD5 14"

-2500 7 12 24 32 16 12 8

0 3 9 22 28 16 12 5

2500 6 11 22 30 17 13 6

°

°

SUBMITTAL DATA

Triple Lock Insulated

Technical DataStandard Lengths (ft) 8 ft, Special lengths on request up to 10 ft

Inside Diameter (in) 3”, 4”, 5”, 6”, 8”, 10”, 12”, 14”, 16”, 18”

Inside Bend Radius (in) Min. one dia.

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.10) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive thru 16”6” w.g. positive, 18”12” w.g. negative thru 16” dia.4” w.g. negative, 18”

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -400 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

The Flexmaster U.S.A.® Triple Lock Aluminum ducting is an all metal flexible duct that is constructed entirely without the use of adhesives. The Triple Lock mechanical joint makes an air tight seam, while the circumferential corrugations provide excellent strength and flexibility. Minimum bend radius to center line is one diameter. However, our recommended radius is 1 ½ diameters in accordance with accepted practice. Triple Lock Aluminum ducting may be easily cut to size and hand formed into elbows or offsets to suit job conditions without subsequent sagging or droop. Triple Lock has much lower pressure loss than conventional cloth ducts due to the small but consistent corrugations that provide both strength and flexibility.

Flexmaster U.S.A.® TL-B

Fire Retardant Vapor Barrier

Triple Lock Standard Aluminum Duct

Fiberglass Insulation

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110514 TLB

SUBMITTAL DATA

Triple Lock Insulated

Technical DataStandard Lengths (ft) 8 ft, Special lengths on request up to 10 ft

Inside Diameter (in) 3”, 4”, 5”, 6”, 8”, 10”, 12”, 14”, 16”, 18”

Inside Bend Radius (in) Min. one dia.

Air Friction Loss See Friction Loss Chart for details

Vapor Barrier Permeance (.05) perm A.S.T.M. E96, Procedure A

Test Standard UL181

Tested By Intertek/ETL

Certifications Met Class 1 Air Duct, NFPA 90A and 90B, BOCA, SBBC, HUD/FHA, MIN Property Std.

Internal Working Pressure (w.g.) 10” w.g. positive thru 16”6” w.g. positive, 18”12” w.g. negative thru 16” dia.4” w.g. negative, 18”

Rated Velocity 5500 F.P.M.

Min Burst Pressure 2 1/2 times working pressure

Operating Temperature Range -400 to +2500F

Flame/Smoke 25/50

Insulation Thermal Conductance R4.2, R6, R8

Like the UL Mark, the ETL Listed Mark shows that our product has been independently tested by a Nationally Recognized Testing Laboratory (NRTL). It shows that it has met the requirements of widely accepted product safety standards and that we have agreed to periodic follow-up inspections to verify continued compliance.

The Flexmaster U.S.A.® Triple Lock Aluminum ducting is an all metal flexible duct that is constructed entirely without the use of adhesives. The Triple Lock mechanical joint makes an air tight seam, while the circumferential corrugations provide excellent strength and flexibility. Minimum bend radius to center line is one diameter. However, our recommended radius is 1 ½ diameters in accordance with accepted practice. Triple Lock Aluminum ducting may be easily cut to size and hand formed into elbows or offsets to suit job conditions without subsequent sagging or droop. Triple Lock has much lower pressure loss than conventional cloth ducts due to the small but consistent corrugations that provide both strength and flexibility.

Flexmaster U.S.A.® TL-M

Reinforced Metalized Vapor Barrier

Triple Lock Standard Aluminum Duct

Fiberglass Insulation

Masterduct, Inc.5235 Ted StreetHouston, TX 77040USATel. +1.713.462.7694Fax + 1.713.939.8441www.flexmasterusa.comwww.masterduct.com

110514 TLM