Study and Performance Analysis of FACTS-incorporated Transmission Line
Presented ByShahadat Hossain Rashed, ID: 021-113-065
MD Sahbaz Sahria Iqbal Suzon, ID: 021-121-016Abu Sayed Md Rizvi, ID: 021-121-067
MD. Shakwhat Hossain, ID: 021-113-031
Supervised ByMohammad Wahiduzzaman Khan
![Page 2: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/2.jpg)
CONTENTS
• Concept of FACTS and General System • Objectives of FACTS• Benefits of FACTS Technology• Types of FACTS Controllers • Transmission line Parameters & Design
of FACTS Controllers • Conclusion • References
![Page 3: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/3.jpg)
General System
• Designed to operate efficiently
• Various load centers with high reliability
• Located at distant locations
• Environmental and safety reasons
![Page 4: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/4.jpg)
FACTS
• Composed of static equipment
• Enhance controllability
• Increase power transfer capability
• Loaded up to its full thermal limit
• Power electronics-based system
FACTS device and project
of substation
![Page 5: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/5.jpg)
Background Of FACTS
• The shunt-connected Static VAR Compensator was first demonstrated in Nebraska
in 1974
• The first series connected Controller, NGH-SSR Damping Scheme, invented in 1984
(Demonstrated in California)
• Co-author Hingorani and Gyugyi has been at the forefront of such advanced ideas
Nebraskaa California
![Page 6: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/6.jpg)
Objectives Of FACTS
• Solve Power Transfer Limit & Stability Problems
• Increase (control) power transfer capability of a line
• Mitigate sub synchronous resonance
• Power quality improvement
• Load compensation
• Limit short circuit current
• Increase the load ability of the system
![Page 7: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/7.jpg)
Benefits of FACTS Technology
• Environmental benefit
• Increased stability
• Increased quality of supply
• Flexibility and uptime
• Financial benefit
• Reduced maintenance cost
![Page 8: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/8.jpg)
Overview Of System
Source orGeneration
House Industry
Load
SeriesCompens
ation
ShuntCompens
ation
Transmission Line
FACTS Intelligence System
![Page 9: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/9.jpg)
Types of FACTS ControllersFC
FC
FC
FC
FC
Series ControllersLine
LineShunt Controllers
DC LinkFC
Line
Combined series-seriesControllers
Combined series-shuntControllers
Line
![Page 10: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/10.jpg)
FACTS Controllers• Series controllers such as TCSC, TCPST and TCVR• Shunt controllers such as SVC and STATCOM• Combined series-shunt controllers such as UPFC FACTS devices: (a)
SVC. (b) TCVR. (c) TCSC. (d) TCPST. (e) UPFC.
![Page 11: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/11.jpg)
Effects of FACTS devices on variables in active power flow equation.
![Page 12: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/12.jpg)
Series Controllers
• Variable impedance (capacitor, Inductor)
To control
• Frequency
• Subsynchonous and
• Harmonic frequencies
• Inject a voltage
• Supplies or consumes reactive power
• Control of both active and reactive power
Basic module of Thyristor
Controlled Series Capacitor
![Page 13: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/13.jpg)
Series Controllers
• Current control
• Damping Oscillations
• Transient and Dynamic stability
• Voltage stability
• Fault current limiting
• If > 0; The combined reactance is Capacitive. • If < 0; The combined reactance is Inductive.
![Page 14: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/14.jpg)
Shunt compensation
• Variable impedance (capacitor, Inductor)
• Inject a current
• Consumes reactive power
• Involves control of both active and reactive power
• Improves system stabilities and pf
![Page 15: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/15.jpg)
FACTS Implemented On a ModelSpecification:
• Line is 350 Km (218.75 mile)
• Conductor Mallard (ACSR)
• Flat horizontal Spacing is 7.25 m (23.8 ft)
• Frequency is 50 Hz
• Receiving end voltage is 230KV
• Receiving end Power is 138.45MW
• Power Factor is 1 (100%)
== = 30.0 ft
Short = less than about 80 km (50 mile) longMedium = 80 km to 240 km (150 mile) longLong = longer than 240 km long
![Page 16: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/16.jpg)
Calculation of Transmission line Parameters (R, L & C)
Resistance (R)• R60 = 0.127 Ω/mile• R50 = 0.127
Inductance (L)• XL60 = (Xa+ Xd) = (0.393 + 0.4127) = 0.8057 Ω/mile• XL50 = 0.8057• L50 =
Capacitance (C)• XC60 = (Xa+ Xd) = (0.0904 + 0.1009) = 0.1913 Ω/mile• XC50 = 0.1913• C50 =
![Page 17: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/17.jpg)
Performance of Resistive Load without Compensation
![Page 18: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/18.jpg)
Performance of Series Compensation with Resistive Load
![Page 19: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/19.jpg)
Performance of Shunt Compensation with Resistive Load
![Page 20: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/20.jpg)
Results
25 50 75 100 125 138.45 150 175 200 225 2500
50
100
150
200
250
300
350
400 Receiving End Voltage (KV) vs Resistive Load (MW)
Uncompensated Receiving End Voltage (KV) with Resistive Load
Series Compensated Receiving End Voltage (KV) with Resistive Load
Shunt Compensated ReceivingVoltage (KV) with Resistive Load
Load (MW)
Rece
ivin
g En
d V
olta
ge(K
V))
![Page 21: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/21.jpg)
Results
25 50 75 100 125 138.45 150 175 200 225 2500
0.2
0.4
0.6
0.8
1
1.2 Sending End pf vs Resistive Load (MW)
Uncompensated Sending End pf with Resistive Load
Series Compensated Sending End pf with Resistive Load
Shunt Compensated Sending End pf with Resistive Load
Load (MW)
Send
ing
End
pf
![Page 22: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/22.jpg)
Performance of Resistive and Inductive Load without Compensation
![Page 23: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/23.jpg)
Performance of Series Compensation with Resistive and Inductive Load
![Page 24: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/24.jpg)
Performance of Shunt Compensation with Resistive and Inductive Load
![Page 25: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/25.jpg)
Results
25 50 75 100 125 138.45 150 175 200 225 2500
50
100
150
200
250
300
350 Recieving End Voltage (KV) vs R-L Load (MW)
Uncompensated Receiving End Voltage (KV) with R-L Load
Series Compensated Receiv-ing End Voltage (KV) with R-L Load
Shunt Compensated Receiv-ing End Voltage (KV) with R-L Load
Load (MW)
Rece
ivin
g En
d V
olta
ge(K
V)
![Page 26: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/26.jpg)
Results
25 50 75 100 125 138.45 150 175 200 225 2500
0.2
0.4
0.6
0.8
1
1.2 Recieving End pf vs R-L Load (MW)
Uncompensated Sending End pf with R-L Load
Series Compensated Sending End pf with R-L Load
Shunt Compensated Sending pf with R-L Load
Load (MW)
Reci
evin
g En
d pf
![Page 27: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/27.jpg)
Static Var Compensator• Operate at both inductive and capacitive compensation• The device provides reactive power• In capacitive case it absorbs reactive power
![Page 28: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/28.jpg)
One Line Diagrams
![Page 29: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/29.jpg)
Transmission line parametersFrom To Resistance per
KmReactance per
Km
Bus 1A Bus 2A 0.066 0.52Bus 1A Bus 2B 0.066 0.52Bus 2A Bus 3A 0.066 0.52Bus 2A Bus 3B 0.066 0.52Bus 2B Bus 3C 0.066 0.52Bus 2B Bus 3D 0.066 0.52Bus 3A Bus 4A 0.066 0.52Bus 3B Bus 4B 0.066 0.52Bus 3C Bus 4C 0.066 0.52Bus 3D Bus 4D 0.066 0.52
Transformer parameters
Transformer Primary Voltage (KV)
Secondary Voltage (KV)
MVA
Trans 1 11 230 5
Trans 2 11 230 5
Trans 3 230 0.230 200
Trans 4 230 0.230 100
Trans 5 230 0.230 50
Trans 6 230 0.230 25
![Page 30: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/30.jpg)
Results of Load Flow
![Page 31: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/31.jpg)
Results
1 2 3 4 5 6 7 8 9 10 1198.6
98.8
99
99.2
99.4
99.6
99.8
100
100.2 Voltage Profile Improvement by SVC
Without SVCVoltage Profile (%)
With SVCVoltage Profile (%)
Bus Number
Volta
ge P
rofil
e (%
)
![Page 32: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/32.jpg)
Results
1 2 3 4 5 6 7 8 9 10 110
10
20
30
40
50
60
70
80
90 Performance Active Power
Without SVCActive power (KW)
With SVCActive power (KW)
Bus Number
Activ
e po
wer
(KW
)
![Page 33: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/33.jpg)
The benefits of SVC to power transmission
• Stabilized voltages in weak systems
• Reduced transmission losses
• Increased transmission capacity, to reduce, defer or eliminate the need for
new lines
• Higher transient stability limit
• Increased damping of minor disturbances
• Greater voltage control and stability
• Better adjustment of line loadings
![Page 34: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/34.jpg)
Conclusion
• Application of power electronics
• Makes a system ‘flexible’
• Play important role in active and reactive power control
• Helps to improve the capacity of an existing system
• Improve the power quality and stability
• The most viable and secure option to meet the power demand optimally.
![Page 35: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/35.jpg)
Reference• Facts controllers in power transmission and distribution by k. R. Padiyar
• Understanding FACTS: concepts and technology of flexible AC transmission systems by Narain G. Hingorani, Laszlo Gyugyi.
• Flexible Ac Transmission Systems (FACTS) by Yong-Hua Song, Allan Johns
• IET Generation, Transmission, and Distribution “Long-term economic model for allocation of FACTS devices in restructured power systems integrating
wind generation” by Akram Elmitwally, Abdelfattah Eladi, John Morrow
• FACTS: Modelling and Simulation in Power Networks by John Wiley & Sons
• W.N. Chang and C.J. Wu, “Developing static reactive power compensator in a power system” ,IEEE Trans. on Power Systems
• K.R. Padiyar and R.K. Varma, “Damping torque analysis of static VAR system controllers”,
• N.G. Hingorani , “Flexible ac transmission”,
• Power Semiconductor Devices and Circuits, Brown Boveri symposia series, Baden Datettwil
• Proposed terms and definitions for flexible AC transmission system(FACTS).
• Hingorani, N.G., "High Power Electronics and Flexible AC Transmission System
• L. Gyugyi, IEE Proceedings C, Generation, Transmission and Distribution 139(4), 323 (1992).
• Y.-H. Song, T. A. Johns, Flexible AC Transmission Systems (FACTS.
• Transmission System Application Requirements for FACTS Controllers, A Special Publication for System Planners.
![Page 36: Study and Performance Analysis of FACTS-incorporated Transmission Line](https://reader036.vdocuments.us/reader036/viewer/2022062823/5878eb8c1a28abfa038b69eb/html5/thumbnails/36.jpg)