stored energy calculation

4
Absolute atmospheric pressure P a Test Pressure P t Absolute test pressure P at Test medium Ratio of Specific Heats for test medium k Diameter of pipe under testing D Length of piping segment under testing L Volume of Piping segement under testing V P Voume of equipment(s) included in testing V e Total Volume of system under testing V Stored Energy E TNT Equivalent TNT Penumatic Testi

Upload: aauppal

Post on 13-Apr-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Stored Energy Calculation

7/27/2019 Stored Energy Calculation

http://slidepdf.com/reader/full/stored-energy-calculation 1/4

Absolute atmospheric pressure Pa

Test Pressure Pt

Absolute test pressure Pat

Test medium

Ratio of Specific Heats for test medium k

Diameter of pipe under testing D

Length of piping segment under testing L

Volume of Piping segement under testing VP

Voume of equipment(s) included in testing Ve

Total Volume of system under testing V

Stored Energy E

TNT Equivalent TNT

Penumatic Testi

Page 2: Stored Energy Calculation

7/27/2019 Stored Energy Calculation

http://slidepdf.com/reader/full/stored-energy-calculation 2/4

14.70 psi 1 bar 101325 Pa

111.72 7.6 bar 770070 Pa

126.42 psi 8.6 bar 871395 Pa

Air

1.4

6.33 ft. 76 in. 1.93 m

3323.49 ft. 1013 m 1013.00 m

104700.82 ft3

2964.80 m3

18051.97 ft3

511.175 m3

511.18 m3

122752.79 ft3

3475.97 m3

2,567,487,867.44  ft-lb 3480086779 J

1725 lb 815.60 Kg

  ng - Stored Energy Calculation

Page 3: Stored Energy Calculation

7/27/2019 Stored Energy Calculation

http://slidepdf.com/reader/full/stored-energy-calculation 3/4

Absolute atmospheric pressure Pa

Test Pressure Pt

Absolute test pressure Pat

Test medium

Ratio of Specific Heats for test medium k

1/(k-1)

(k-1)/k

Diameter of pipe under testing D

Length of piping segment under testing L

Volume of Piping segement under testing VP

Voume of equipment(s) included in testing Ve

Total Volume of system under testing V

Stored Energy E

TNT Equivalent TNT

Scaled Consequence Factor Rscaled

Minimum Safe Distance R

Penumatic Te

Page 4: Stored Energy Calculation

7/27/2019 Stored Energy Calculation

http://slidepdf.com/reader/full/stored-energy-calculation 4/4

14.70 psi 1 bar 101325 Pa

111.72 7.6 bar 770070 Pa

126.42 psi 8.6 bar 871395 Pa

Air Air

1.4 1.4

2.5 2.5

0.29 0.29

76.00 in. 76 in. 1.93 m

39881.89 ft. 1013 m 1013.00 m

180923012.41 in3

2964.80 m3

0.00 in3

m3

0.00 m3

180923012.41 in3 2964.80 m3

2,188,330,506.70  ft-lb 2,966,160,098.06  J

1470 lb 695.15 Kg

50

569 ft. 173 m

  sting - Stored Energy Calculation