steam

6
Steam Control and Condensate Drainage for Heat Exchangers Bulletin FHD-206 General Heat transfer units that use steam to pro- duce hot water are known as indirect heaters. They are often shell and tube type heat exchangers and are generally referred to as converters, hot water gen- erators, and instantaneous heaters. The ASME Code for Unfired Pressure Vessels is the nationally recognized authority pre- scribing their construction for given tem- peratures and pressures. The term used varies with the heating medium and the manner of application. When these heaters use steam as the heat source they are usually called steam to water converters. In steam heated converters, the water to be heated circulates through the tubes and steam circulates in the shell sur- rounding the outside of the tubes. This results in condensate draining to the bottom of the heat exchanger shell as the steam gives up its latent heat. Steam to Water Heat Exchangers The operation of the shell and tube heat exchanger is as follows. Steam enters the heat exchanger shell through the top vapor opening and surrounds the outside of the tubes. As energy is transferred through the tubes it heats the water inside the tubes. The heat transfer condenses steam inside the shell forming condensate that drops to the bottom of the heat exchanger shell. The condensate flows through the bottom condensate outlet and into a steam trap. The steam pressure in the heat exchanger shell has a direct correlation to the tem- perature of the condensate formed in the shell. The properties of saturated steam are such that the steam temperature varies with steam pressure (See Table 1 on next page). When the latent heat of vaporiza- tion is removed, the resulting condensate will be close to the saturation tempera- ture. Depending on the system load, slight sub-cooling may occur from the bottom of the heat exchanger and the inlet piping to the steam trap. The heat exchanger should be selected to operate at the minimum possible steam pressure. This allows the lowest possible condensate temperature to discharge from the steam trap and reduces the amount of flash steam in the return system. When heating fluids up to 200°F, the heat exchanger should be selected based on 2 psig steam pressure in the shell for the most efficient system operation. This may require a slightly larger heat exchanger than one operating at higher pressure, however it will result in a smaller less expensive low pressure steam trap and a smaller steam regulating valve. The low pressure selection will also limit the maximum temperature that can occur inside the tubes, should the temper- ature controller fail in an open position. TIP: When heating fluids up to 200°F, select heat exchanger with 2 psi steam pressure in shell for best efficiency. SERIES 415C Y-STRAINER SU 84-2 HEAT EXCHANGER with OPTIONAL “K” HEAD GT610-IP ELECTRO-PNEUMATIC TRANSDUCER AIR-PRV MODEL 62 VACUUM BREAKER SERIES 2000 PRESSURE TEMPERATURE REGULATOR SERIES 415C Y-STRAINER MODEL AP-1A AIR PILOT SERIES C FLOAT AND THERMOSTATIC STEAM TRAP CB CONDENSATE UNIT SERIES 1 INLINE FLOAT AND THERMOSTATIC STEAM TRAP SERIES 415C Y-STRAINER STEAM SUPPLY

Upload: joquispe

Post on 23-Oct-2015

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Steam

Steam Control andCondensate Drainage for

Heat Exchangers

Bulletin FHD-206

GeneralHeat transfer units that use steam to pro-duce hot water are known as indirectheaters. They are often shell and tubetype heat exchangers and are generallyreferred to as converters, hot water gen-erators,and instantaneous heaters. TheASME Code for Unfired Pressure Vesselsis the nationally recognized authority pre-scribing their construction for given tem-peratures and pressures. The term usedvaries with the heating medium and themanner of application. When these heatersuse steam as the heat source they areusually called steam to water converters.

In steam heated converters, the water to be heated circulates through the tubesand steam circulates in the shell sur-rounding the outside of the tubes. Thisresults in condensate draining to the bottom of the heat exchanger shell as the steam gives up its latent heat.

Steam to Water Heat ExchangersThe operation of the shell and tube heatexchanger is as follows. Steam enters theheat exchanger shell through the topvapor opening and surrounds the outsideof the tubes. As energy is transferredthrough the tubes it heats the water insidethe tubes. The heat transfer condensessteam inside the shell forming condensatethat drops to the bottom of the heatexchanger shell. The condensate flowsthrough the bottom condensate outlet andinto a steam trap.

The steam pressure in the heat exchangershell has a direct correlation to the tem-perature of the condensate formed in theshell. The properties of saturated steamare such that the steam temperature varieswith steam pressure (See Table 1 on nextpage). When the latent heat of vaporiza-tion is removed, the resulting condensatewill be close to the saturation tempera-ture. Depending on the system load,slight sub-cooling may occur from the bottom of the heat exchanger and theinlet piping to the steam trap.

The heat exchanger should be selected tooperate at the minimum possible steampressure. This allows the lowest possiblecondensate temperature to discharge fromthe steam trap and reduces the amount offlash steam in the return system. When

heating fluids up to 200°F, the heatexchanger should be selected based on2 psig steam pressure in the shell for themost efficient system operation.

This may require a slightly larger heatexchanger than one operating at higherpressure, however it will result in asmaller less expensive low pressuresteam trap and a smaller steam regulatingvalve. The low pressure selection will alsolimit the maximum temperature that canoccur inside the tubes, should the temper-ature controller fail in an open position.

TIP: When heating fluids up to 200°F, select heat exchanger with 2 psi steam pressure in shell for best efficiency.

SERIES 415CY-STRAINER

SU 84-2 HEAT EXCHANGERwith OPTIONAL “K” HEAD

GT610-IPELECTRO-PNEUMATIC

TRANSDUCER

AIR-PRV

MODEL 62 VACUUM BREAKER

SERIES 2000PRESSURE

TEMPERATUREREGULATOR

SERIES 415CY-STRAINER

MODEL AP-1AAIR PILOT

SERIES CFLOAT AND THERMOSTATIC

STEAM TRAP

CB CONDENSATE UNIT

SERIES 1INLINE FLOAT

AND THERMOSTATICSTEAM TRAP

SERIES 415CY-STRAINER

STEAMSUPPLY

Page 2: Steam

It is standard practice to add a fouling factor in the heat exchanger selection.This fouling factor adds additional tubesurface area to assure adequate heatingafter normal scale and corrosion depositson the tube surfaces. A standard .0005fouling factor will add 20 to 25% addi-tional tube surface area. When the heatexchanger is new and the tubes are cleanand shiny, the heat exchanger will operateat lower than design pressure even at fullsystem load. For example, a new heatexchanger designed for 15 psi steam toheat water to 160 degrees will generallyheat the full system load with 0 psi steamin the heat exchanger shell.

Table 1Properties of Saturated Steam

Heat Exchanger SelectionThe heat exchanger should be selectedfor operation at the minimum pressure toprovide the most efficient operation. Theproperties of saturated steam tables showa larger amount of the latent heat is avail-able at low pressure. Less energy remainsin the condensate reducing the flashsteam losses. A reasonable guide would

be to select a steam pressure that has asaturation temperature approximately30°F higher than the required outlet tem-perature of the fluid being heated in thetubes. For fluid temperatures up to 200°F,2 psig steam is recommended.

When a high steam pressure source isused, the pressure should be reduced byinstalling a steam pressure regulatingvalve or by using a combination temper-ature pressure regulator.

After selecting the heat exchanger, thenext step should be planning the installa-tion. The heat exchanger should bemounted high enough to allow gravitydrainage of the condensate from thesteam trap into a vented gravity returnline. If a gravity return line is not avail-able, a condensate pump should beinstalled. The heat exchanger should be mounted with a pitch toward the condensate outlet. A minimum 1/2 inchpitch per 10 foot length should be provided. The heat exchanger shouldalso be located such that removal of the tube bundle is possible.

Steam TrapsThe steam trap must be capable of com-pletely draining the condensate from theheat exchanger shell under all operatingconditions. On a heat exchanger using amodulating temperature regulator to heatfluids under 212°F, the steam pressure inthe shell can be 0 psig. To assure conden-sate drainage, the steam trap must bemounted below the heat exchanger outlettapping and it must drain by gravity intoa vented condensate return unit. Whenpossible, the trap should be located 15inches below the heat exchanger outlet.The 15 inches static head to the trap inletwill provide 1/2 psig static inlet pressure tothe trap when the shell steam pressure isat 0 psig.

The trap should be sized based on this 1/2 psig differential pressure. A safetyfactor of 1.5 times the calculated fullload capacity should be used to handleunusual start up loads. A float and thermostatic trap is normally the bestselection for a heat exchanger. The thermostatic element quickly vents the

air from the heat exchanger shell. Themodulating float element provides continuous condensate drainage equal tothe system condensing rate.

Failure to provide complete condensatedrainage will lead to poor temperaturecontrol and possible water hammer. Anylift in the condensate return piping afterthe trap discharge requires a positivepressure to develop in the heat exchangershell to provide condensate drainage. Forthis to occur, condensate must back up in the heat exchanger shell until enoughtube surface is covered by condensate tobuild a positive steam pressure. Whenthe positive steam pressure develops tomove the condensate through the steamtrap and up the vertical return line, overheating can occur on the tube side of theheat exchanger due to the positive steampressure remaining in the shell. Thisresults in a wide range of outlet fluidtemperatures from the heat exchanger.

A lift in the return line as shown aboveshould be avoided on heat exchangersusing a modulating control valve. (Forcorrect configurations, see diagram at top of page 4.)

A lift or back pressure in the steam trap return piping can flood the heatexchanger shell and cause severe waterhammer as steam enters the flooded shell.The resulting water hammer can damagethe steam trap, the steam regulatingvalve, the heat exchanger tubes and causethe gasket in the heat exchanger and trapto fail.

Trap InstallationThe trap should be located below theheat exchanger shell to allow free flowof condensate into the trap. A strainercomplete with a screen blow down valveshould be installed ahead of the steamtrap. A shut off valve should be providedin the trap discharge return line to isolatethe unit for service. Unions should beprovided to allow trap service or replace-

2

HEATED FLUIDOUTLET

FLUIDTO BEHEATED

STEAM REGULATOR

STEAM SUPPLY

HEAT EXCHANGER

STEAM TRAP

CONDENSATEOUTLET

15 in.

Typical Steam to WaterHeat Exchanger Installation

TIP: Fouling factor assures adequateheating. A .0005 fouling factor adds 20-25% additional tube surface.

Gage Sensible Latent SpecificReading Saturation Heat in Heat of Volumeat Sea Temp. Water Vaporation of 1 lb. FlashLevel – Degree B.T.U. B.T.U. Steam Steam

psi °F per lb. per lb. cu.ft. %

2 219 187 966 24 0.6

5 227 195 960 20 1.6

15 250 219 945 14 3.9

30 274 243 920 9 6.5

50 298 268 912 8 9.0

100 338 309 881 4 13.2

125 353 325 868 3 14.8

TIP: Steam temperature should beselected 30°F over heat exchangeroutlet temperature.

TIP: Trap should be located at least 15inches below heat exchanger outlet.

Heat Exchanger withModulating Control Valve

Lift

Page 3: Steam

ment. The return line from the trap discharge should be pitched into a vented condensate return unit.

Vacuum BreakersMost steam to water heat exchangersprovide a tapping in the shell to allowinstallation of a vacuum breaker. Thevacuum breaker allows air to enter theshell when a induced vacuum occurs.Failure to install a vacuum breaker willallow the heat exchanger shell to operateat a negative pressure which may causecondensate to be held up in the shell.During light load, the heat exchanger willhave a layer of steam at the top and airunder the steam to provide just the rightamount of heat. The vacuum breakershould be mounted on a vertical pipe 6 to 10” above the topping to provide a cooling leg. This will protect the vacuum breaker from dirt and extremetemperatures.

Steam RegulatorThe choice of the temperature regulatingvalve includes self contained temperatureregulators, pilot operated regulators andpneumatic regulators.

The steam inlet pressure to the regulatormust be higher than the required heatexchanger operating pressure to allowflow. The available steam pressure shouldbe at least two times the heat exchangeroperating pressure to provide modulationof the regulator for good temperaturecontrol. This will also provide the smallest size steam regulator.

The steam regulator should be sizedbased on the maximum lb./hr. of steamrequired by the heat exchanger. To prop-erly size the regulator, the available inletsteam pressure and the heat exchangerdesign operating pressure must be known.The steam regulator should not be over-sized. Oversizing the regulator may causethe temperature to overshoot and the regulator will hunt more than a properlysized regulator. The steam regulator isnormally smaller than the connectinginlet and outlet steam piping.

Regulator InstallationA steam drip trap should be installed in the steam piping ahead of all steamregulating valves. Failure to install a drip trap will allow condensate to collect in the steam piping ahead of the regulator. As the regulator opens, the mix of condensate and steam passing through the regulator may causewater hammer that can destroy thediaphragms or bellows used to operatethe regulator.

A steam strainer should also be installedahead of the regulators to prevent dirtfrom entering the valve. Dirt can depositon the valve seat and not allow it to close tight. The steam strainer should beinstalled with the screen pocket horizon-tally. Installation with the screen down,as commonly piped for water service,will allow a condensate pocket to form in the steam line. This condensate pocketcan carry into the main valve and causewater hammer or sluggish operation.

Shut off valves, pressure gauges, a manual bypass and unions should beinstalled to allow proper servicing of thevalves and strainers. When possible referto the manufacturer’s installation manualfor proper installation.

The temperature sensing bulb should beinstalled as close as possible to the heatexchanger outlet. It is important that thefull length of the temperature sensingbulb be inserted in the system piping.Any portion of the bulb installed in a no flow area will reduce the accuracy of temperature control. When the sensingbulb is installed in a separable well, heattransfer compound must be installedbetween the well and the sensing bulb to aid heat transfer. The tube side of theheat exchanger should have a continuousrunning recirculation pump to providecontinuous flow past the sensing bulb. A minimum 20% recirculation should be provided.

Pilot operated regulators with a pressurepilot require a downstream pressure sensing line. The pressure sensing lineconnection should be connected in a non-turbulent area downstream of the mainvalve; a minimum 10 pipe diametersdownstream of the main valve is recom-mended. The steam pressure sensingconnection can also be connected directly to the heat exchanger shell.

Condensate CoolersWhen heat exchangers operate at highpressure, consideration should be givento the addition of a condensate cooler.The justification will be depend on thesize of the heat exchanger and the actualnumber of hours per day the unit will bein operation.

With a condensate cooler, the dischargefrom the steam trap on the steam heatexchanger outlet is piped through a water-to-water heat exchanger. A second trap isthen installed on the discharge of thewater-to-water heat exchanger to maintainsaturation pressure and prevent flashingand water hammer from occurring in the condensate cooler. A separate thermo-static trap is installed to allow direct airventing of the steam heat exchanger intothe vented return line downstream of thecondensate cooler.

The water-to-water heat exchanger designdiffers from a steam heat exchanger. The water-to-water heat exchanger hasinternal baffles to direct the water flowacross the tubes to improve heat transfer.Water-to-waterheat exchangers areexternally distinguishable as the shellinlet and outlet tappings are the samesize; steam heat exchangers have a large vapor opening in the top of theshell and a smaller condensate outlet inthe bottom.

The fluid in the condensate cooler tubes may be the inlet water to the steam heat exchanger tubes. When the initialtemperature of the fluid is too high tocool the condensate below 212°F, a separate fluid may be heated. Preheatingdomestic hot water or preheating boilermake up water are two possibilities.

3

TIP: Install a vacuum breaker on allsteam converters.

TIP: For good control, take at least a50% pressure drop across the controlvalve.

THERMOSTATICTRAP

REGULATOR STEAM SUPPLY

HEAT EXCHANGER

COND.OUTLET

TRAP

COOLER

TRAP

Installation withCondensate Cooler

Page 4: Steam

STEAM INLET

HEAT EXCHANGER

CONDENSATE COOLERPUMPED DISCHARGE

CONDENSATEPUMP

THERMOSTATICTRAP

4

Heat exchanger installations depending on operating pressures and the of type of return pump.

Low Pressure (2 psig or less) with Standard Condensate Unit

STEAM INLET

CONDENSATEPUMP

HEAT EXCHANGER F&T TRAPHeat exchangers operating at 2 psig or lesscan be drained into a standard low costfloor mounted condensate returned pump.

High Pressure with Flash Tank and Low NPSH Condensate Unit

STEAM INLET

ELEVATED CONDENSATEUNIT WITH LOW NPSHPUMP

HEAT EXCHANGERF&T TRAP

FLASH TANK

Heat exchangers operating at higher pres-sure require a flash tank to vent the flashsteam. An elevated condensate pump unitequipped with 2-foot NPSH pumps are re-quired to handle the condensate at satura-tion temperature.

High Pressure with Condensate Cooler and Standard Condensate Unit

When it is necessary to operate a heatexchanger at high pressure (above 15 psig)a condensate cooler can be added to sub-cool the condensate below 212°F. Theillustration shows the proper steam trap-ping for a condensate cooler. The incom-ing fluid to the steam heat exchanger maybe used to sub-cool if the temperature islow enough. A separate cooling sourcemay also be used.

Page 5: Steam

5

Heat exchanger installations depending on operating pressures and the of type of return pump.

Low Pressure and Pressure Powered Pump

HEAT EXCHANGER

RESERVOIR TANK

PRESSURE POWEREDPUMP

PUMPED DISCHARGE

DRIP TRAP

STEAM SUPPLY

STEAM SUPPLY

DRIP TRAP

F&T TRAP

A pressure powered pump unit may also beused to return condensate. The installationshown would be used on low pressure heatexchangers. The receiver tank is vented toatmosphere on this unit.

High Pressure and Pressure Powered Pump

HEAT EXCHANGER

THERMOSTATIC VENT

STEAM SUPPLY

STEAM SUPPLY

DRIP TRAP

TO RETURN LINE

PRESSURE POWERED PUMP

RESERVOIRTANK

PUMPDISCHARGE

F&T TRAP

Heat exchangers operating at higher pres-sures may use a closed pressure poweredpump system. The installation shown willallow condensate to discharge directlythrough the steam trap when the pressureon the heat exchanger is higher than thereturn line pressure. When the heatexchanger pressure is not sufficient, thepressure powered pump receiver will filland operate to discharge condensate.

The F&T steam trap can be sized based onthe differential pressure from the pressurepowered pump discharge pressure less thereturn line back pressure.

For additional information or assistance in selecting components,contact your Fluid Handling “Steam Team” representative.

Page 6: Steam