standby generators

30
18 STANDBY GENERATORS Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-1 contents Generator Features 18-2 – 18-3 Industry Leading System Controls 18-4 Catalog Logic — Easy Order Selection Guide 18-5 NEW—Optimus Series Air Cooled Generators 18-6 Air Cooled Standby Generators 18-7 Liquid Cooled Standby Generators 18-8 – 18-12 Single-Phase Transfer Switches 18-13 – 18-14 Three-Phase Transfer Switches 18-15 Portable Generators 18-16 Generator Ready Load Center 18-17 – 18-18 Manual Transfer Interlock Kits 18-19 – 18-20 Standby Generator Ratings / Maintenance Kits / Accessories 18-21 Cellular Remote Monitoring 18-22 Diesel Generator Introduction 18-23 Protector™ Series Automatic Standby Diesel Generators 18-24 – 18-25 SM & SL Type Transfer Switches 18-26 Accessories for Diesel Generators 18-27 Pre-order checklist 18-28 Easy Order Selection Guide 18-29 Additional Information 18-30 Scan to connect online to the most up-to- date version of this Section of SPEEDFAX. Liquid cooled generator Standard air cooled generator Transfer switch Standby Generators SPEEDFAX TM 2017 Section

Upload: others

Post on 12-Dec-2021

17 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-1

c o n t e n t sGenerator Features 18-2 – 18-3Industry Leading System Controls 18-4Catalog Logic — Easy Order Selection Guide 18-5NEW—Optimus Series Air Cooled Generators 18-6Air Cooled Standby Generators 18-7Liquid Cooled Standby Generators 18-8 – 18-12Single-Phase Transfer Switches 18-13 – 18-14Three-Phase Transfer Switches 18-15Portable Generators 18-16Generator Ready Load Center 18-17 – 18-18Manual Transfer Interlock Kits 18-19 – 18-20Standby Generator Ratings / Maintenance Kits / Accessories 18-21Cellular Remote Monitoring 18-22Diesel Generator Introduction 18-23Protector™ Series Automatic Standby Diesel Generators 18-24 – 18-25SM & SL Type Transfer Switches 18-26Accessories for Diesel Generators 18-27Pre-order checklist 18-28Easy Order Selection Guide 18-29Additional Information 18-30

Scan to connect online to the most up-to-date version of this Section of SPEEDFAX.

Liquid cooled generator

Standard air cooled generator

Transfer switch

Standby Generators SPEEDFAXTM 2017 Section

Page 2: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-2

Standby Power SystemsAir Cooled Generator Features

Generator Features

Generator back view

Fuel line connection

A section of UL or AGA approved flexible fuel line is required to protect the rigid fuel line connections against generator vibration. 1' flexible fuel line connector is included.

New Base Pad

Air cooled units will now be rated for direct-to-dirt mounting.

Wind resistant housing

150 MPH wind resistant design on both steel and aluminum units, ASCE 7 Standards. Electrostatically applied texturedepoxy paint for added durability.

Exhaust enclosure

Verify spacing with local code and inspector, prior to installation. Typically, the generator must be placed awayfrom any opening in the house due to exhaust regulationsfrom NFPA guidelines.

Oil dipstick, low oil switch, high temperature switch,oil filter, oil drain hose

Break in periods are not required on Siemens standby gen-erators to initiate the warranty, but are recommended.

Natural gas/liquid propane fuel setup

The 9-22kW units ship from the factory ready for use with natural gas. The conver-sion to propane is as simple as turning a knob. No tools required!

Substructure

Galvannealed substructure for excellent rust protection.

Snap-in cover plate

Easy access for remote wireless monitor. Refer to page 12 for monitor offering.

Page 3: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-3

Standby Power SystemsAir Cooled Generator Features

Larger battery compartment

Batteries are not included and must be purchased separately.The recommended battery is a 26 frame battery capable of 525-550cca.

Air filter

Prolong the life of your enginethrough routine maintenance and ensure warranty requirements are met.

Maintenance is recommended annually or every 200 hours.

Refer to page 12 for mainte-nance kit offerings.

Electrical connections

All connections available in one single location internally that allows for easy visibility and connection.

Removable side panel

Giving technicians easier access to electrical connections, fuel, and battery installation. Saves consumers time and money.

LED indicator lightsincluded on 8-22 kW• Green = Generator OK• Yellow = Maintenance needed (not on 8-14kW)• Red = Contact dealer

New featuresNew Brighter LED indicator lights

Door improvement with lip to prevent water from leaking in.

Control panelEvolution controller functions include monitoring utility power, triggering the automatic transfer switch, starting and stopping the generator, exercising the generator, and monitoring the generator for any system faults. Combines the voltage regulator, engine control board and battery charger into one single item. Brings more functionality to the generator control for a smarter power solution

Product Activation is required on all Evolution Controlled Models to engage automatic transfer mode. Generator will operate in manual mode until activation code is entered. Easy, one-time activation process can be completed in shop or on-site.

Data label is located inside the generator. Serial number is required for generator activation.

New Optimus Series units will have the following features:n Upgraded battery charger from 3.5

to 5 amp, paired with an updated algorithm to work with an AGM or lead acid battery

n Quiet Test standard on 9-22kW air cooled unitsn 16-22kW units will have lower RPM exercise (1950 RPM) to

facilitate quieter exercisingn LEDs will blink during utility loss

n Will include consumer instructions on screen to reset fault prior to contacting dealer to reduce nuisance service calls

n Improved common alarm connection and usage information

Page 4: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-4

Industry Leading System Controls

Evolution controller for air cooled generators

Standby Power SystemsAir Cooled Generator Controller

Air Cooled Evolution Controller for Optimus Units Orange text indicates a new or changed feature from previous version of Evolution controller

Display Alarms Dealer service features/menus Key miscellaneous

üLCD Display üLED Backlit Membrane Keypad üTime & Date üAlarm Log üRun Log üMaintenance Log & Reminders üSet Exercise via Display üRun Hour Display üBattery Condition üQuad-lingual Display (Portuguese) üQuiet Test Selection üFuel Selection üElimination of "Inspect" prompt üCapture of Dismissal of Maintenance Reminder Prompt üVariable Start Up Delay between 2-1500 seconds üLEDs will blink during utility loss

üGenerator Over Voltage üGenerator Under Voltage üUnderspeed/Fail to Xfer üLow Battery Voltage üHigh Engine Temperature üLow Oil Pressure üOvercrank üOverspeed üRPM Sensor Loss üInternal Fault üLow Fuel Pressure (QT only) üWiring Error üExternal common fault alarm üOverload Warning/Cooldown üLow Battery/Battery Problem üCharger Warning üCharger Missing AC üStepper Over Current üFuse Problem üRadio Signal Indication üImproved common alarm connection and usage information

üImproved smart battery charger, upgraded from 3.5 to 5 amps üBattery Voltage üUSB Port üGenerator Output Voltage üOutput Frequency & RPM üUtility Input Voltage üSoftware & Hardware Version üBoot Loader Version üCommand Status üVoltage Calibration üParameter Group üVotage Code üMaintenance Hard Reset üEdit Run Hours (controller replacement) üMaintenance Schedule üService/Monitoring Port üSerial Number üDebug üUpdateable Firmware Prompts üBrown Out Voltage üWill include consumer instructions on screen to reset fault prior to contacting dealer

üCompatible with Cellular Monitoring üProduct Activation üVoltage Regulator üExercise not set error ü16-22kW will have lower RPM exercise (1950rpm)

•Certain faults will also have an associated E-code after the general message to specifically call out what the exact problem for more exact/quick diagnosis.

Type "E" Evolution Digital LCD ControllerFunctions include monitoring utility power, triggering the automatic transfer switch, starting and stopping the generator, exercising the generator, and monitoring the generator for any system faults.

High Voltage Shutdown Shuts down the generator at >130%

rated voltage for 200 milliseconds or >110% for 5 seconds to better protect home owner appliances or connected items.

n Low Voltage ShutdownShuts down the generator at <60% voltage for 5 seconds to better protect home owners appliances or connected items.

n Internal Fault ShutdownShuts down the generator when a failure is detected within the Evolution Controller for more protection and easier diagnostics.

n Battery Sentinel Monitors the battery and charging system

to indicate that the battery is trending towards failure or that it has failed.

n Event Log All generators 8-22 kW feature a full

event log capable of recording 50 events.

n Smart Battery Charger Only delivers a charge to the battery

when needed. Battery charge depends on ambient air temperature. Upgraded charger from 3.5 to 5 amp; updated algorithm to work with an AGM or lead acid battery.

n Voltage Regulation With the combination into the

Evolution Controller, the voltage regulation delivers an industry leading voltage regulation +/- 1%.

n Product Activation Requires each generator to be

activated via website or phone before automatic function is enabled - Allows a warranty activation start point for every generator sold.

n External Common Fault Alarm The Evolution Controller has a

provision to connect to a set of contacts that will allow for a common alarm when any of the generator shut downs occur- This will allow individuals to connect into security systems, home automation systems or simply drive a different alarm within a home or business.

n Adjustable generator start time When utility fails, the control is factory

set to delay 10 seconds prior to starting the engine. There is also the capability to change the delay time between 2-1500 seconds.

n Incorrect Wiring Error Eliminates the potential of damaging

the Evolution Controller if it is not connected properly, a warning message is displayed that must be corrected before the controller is allowed to be fully operational.

Page 5: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-5

Air Cooled and Liquid Cooled Generators

Standby Power Generators kW ratingsab

Voltage R = 120/240V, 1Ø C = 208/120V, 3Ø J = 240/120V, 3Ø I = 480/277V, 3Ø

Fuel G = Natural Gas P = Liquid Propane Vapor B = Accepts Both

Enclosure A = Aluminum

Speed Left Blank = 3600rpm L = 1800rpm

Emissions Compliant Optioncd E = Catalyst

Air

Co

ole

d

ASGM

9 R B A11 R B A16 R B A20 R B A22 R B A

Liq

uid

Co

ole

d SGE

22 R, C, J B A L25 R, C, J B A27 R, C, J B A L30 R, C, J B A32 R, C, J, I B A L36 R, C, J, I B A38 R, C, J, I B A L45 R, C, J, I B A E48 R, C, J, I B A L E60 R, C, J, I G, P A

SGN*

70 R, C, J, I G, P A L E80 R, C, J, I G, P A

100 R, C, J, I G, P A L E130 R, C, J, I G, P A E150 R, C, J, I G, P A E

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

Transfer Switches

Transfer SwitchesST = Indoor Branch CircuitSL = Outdoor Load Shedding SM = Load Management** Amp

VoltageR = 120/240V, 1ØC = 208/120V, 3ØJ = 240/120V, 3ØI = 480/277V, 3Ø

Service DisconnectBlank = NoD = Yes

Branch Circuits

ST 50 R 10C, 12C

100 R 16C

SL 100 C, J, I

200 C, J, I

400 C, J, I

600 C, J, I

800 C, J, I

SM 100 R Blank, D

150 R D

200 R Blank, D

300 R D

400 R D

600** R

800** R

** Will have Outdoor Load Shedding and Load Management Capabilities

Catalog Logic

a Battery not included for units 60kW and below.b Catalyst option available on 45, 48, and 70kW units,

catalyst factory standard on 100-150kW units.

c All units 30kW and below do not fall under CA/MA emis-sions standards, therefore are not required to have a catalyst.

d All units 32kW and above must contain emissions catalyst in order to be installed in California/Massachusettes (part number ending with “E”).

Standby Power SystemsAir Cooled and Liquid Cooled Generator Catalog Logic

Page 6: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-6

NEW Siemens Optimus Series Air Cooled GeneratorsSiemens is happy to introduce the new Optimus line of air cooled generators, launching in October 2016. This launch introduces an entire new line of air cooled products with several changes that highlight ease of installation, and end-user functionality. A synopsis of these changes can be found below.

Standby Power SystemsAir Cooled Generator Controller

Door Alignment

Updated door alignment making access to the interior of the unit with ease.

Moved pins from side panels to the door, which eliminates the need to lift up and out, vertical removal and reinstallation only

New kW Range

9, 11, 16, 20 and 22kW

Base Changes

Allows for quicker installation, saving our consumers time and money.

Eliminates sinking and allows unit to be placed directly on ground (increased surface area by 9X).

Removable Side Panel

Giving our technicians easier access to all electrical connections, fuel and battery installation. Saving our consumers time and money.

Controller

Includes consumer introductions on screen to reset fault prior to contacting dealer to reduce nuisance service calls.

New design eliminates the external connection box and GFCI. The main breaker is moved inside by the control panel.

Enclosure Changes

Aluminum enclosures to give consumers a clean, rust-free enclosure for the life of their generator.

Fuel System Changes

Integrated Sediment Trap that eliminates the need to build and install it in the field which saves time and money.

Locking System

Improved locking system to prevent interference and less pressure to open. Lock covers to prevent debris and ice intrusion

Electrical Connections

All connections available in one single location for easy visibility and connection.

Page 7: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-7

9, 11, 16, 20, and 22kW Air Cooled Generator, 120/240V, Single phase

Typical load requirementsc

Description kW Description kW

Electric Heat per 1,000 ft.b 12.0 General Receptacles per 1,000 ft.b 1.0

Heat Pump Elements per 1,000 ft.b 7.0 Dishwasher 1.5

Dryer 5.5 Blow Dryer 1.3

Hot Tub 5.0 AC (per ton) 1.0

Range Oven 5.0 Microwave 1.0

Hot Water Heater 4.5 Toasters 1.0

Stove Top Burner 1.5 Lighting per 1,000 ft.b 0.8

Current Catalog Numbers

Catalog Numbera kW Ratingc Enclosure Type

Engine Size Weight (lbs.) Dimensions (in.)

Maintenance Kits

ASGM009RBA 9 Aluminum 410CC 360

48 x 25 x 29

GENMKIT19

ASGM011RBA 11 Aluminum 530CC 428 GENMKIT20

ASGM016RBA 16 Aluminum 992CC 448 GENMKIT21

ASGM020RBA 20 Aluminum 999CC 516 GENMKIT22

ASGM022RBA 22 Aluminum 999CC 526 GENMKIT22

a All units ship ready for use with natural gas, minor adjustments required for liquid propane vapor use.

b Check local code requirements.

c Battery not included with air cooled models 8-22kw. Refer to page 12 for 26R battery.

Standard featuresn UL 2200 Listed

n Four-cycle industrial engines provide durable,reliable, long life

n Operate on either natural gas or propane vapora

n Composite mounting pad approved to eliminateneed to pour concrete padb

n Automatic high temperature, low oil pressure,over speed, and over crank shut down

n Low battery voltage indicator

n Standard safety fuse

n Provided with Type “E” Evolution controller

n Provided with the upgraded Optimus version of the Evolution controller

Standby Power SystemsAir Cooled Generators

Page 8: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-8

1800, 2300, and 3600 RPM Liquid Cooled Generators, Single Phase and 3 Phase

Standard featuresn UL 2200 Listed

n Meets EPA Emission Regulations (units 45kW and above must have emissions catalyst to be used in CA/MA)

n Operate on either natural gas or propane vapor

n Automatic high temperature, low coolant, low oil pressure, and over speed shutdown

n Automatic voltage regulator with over voltage protection

n Isochronous Electronic Governor

n Safety fuse included

n Smart Battery Charger

n Quiet run weekly self test

n Provided with type "E" evolution controller (8-60kW units) or type "N" Nexus controller (70-150kW)

n Compatible with "SE", "SL", and "SM" type automatic transfer switches

Catalog Numbers

Standby Power Generators kW ratingscd

VoltageR =120/240v, 1 phaseC = 208/120v, 3 phaseJ = 240/120v, 3 phaseI = 480/277v, 3 phase

FuelG = Natural GasP = Liquid Propane VaporB = Accepts Both

EnclosureS = SteelA = Aluminum

SpeedBlank = 3600rpm L = 1800rpm

Emissions CompliantOptionab

E = Catalyst

Air

Co

ole

d

ASGM

8 R B A

11 R B A

16 R B A

20 R B A

22 R B A

Liq

uid

Co

ole

d SGE

22 R, C, J B A L

25 R, C, J B S

27 R, C, J B A L

30 R, C, J B A

32 R, C, J, I B A L

36 R, C, J, I B A

38 R, C, J, I B A L

45 R, C, J, I B A E

48 R, C, J, I B A L E

60 R, C, J, I G, P A

SGN*

70 R, C, J, I G, P A L E

80 R, C, J, I G, P A

100 R, C, J, I G, P A L E

130 R, C, J, I G, P A E

150 R, C, J, I G, P A E

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

a All units 38kW and below do not fall under CA/MA emissions standards, therefore are not required to have a catalyst

b All units 45kW and above must contain emissions catalyst to be installed in California/Massachusettes (part no. ending with “E”)

c Battery not included for units 60kW and belowd Catalyst option available on 45, 48, and 70kW units,

catalyst factory standard on 100-150kW units

Denotes speed of 2300RPM

Standby Power SystemsLiquid Cooled Generators

Page 9: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-9

120/240V Single-Phase Liquid Cooled Generators

Catalog Number kW Rating

Fuel Type Enclosure

Engine Size (Liters)

Speed (RPM)

Amp Output

Weight (lbs.) Dimensions (in.)

SGE022RBAL 22 Both Aluminum 2.4 1800 92 955 62.2 x 30.6 x 38.6

SGE025RBA 25 Both Aluminum 1.5 3600 104 835 62.2 x 30.6 x 38.6

SGE027RBAL 27 Both Aluminum 2.4 1800 113 955 62.2 x 30.6 x 38.6

SGE030RBA 30 Both Aluminum 1.5 3600 125 865 62.2 x 30.6 x 38.6

SGE032RBAL 32 Both Aluminum 2.4 1800 133 1271 76.8 x 35 x 46.1

SGE036RBA 36 Both Aluminum 2.4 3600 150 1202 76.8 x 35 x 46.1

SGE038RBAL 38 Both Aluminum 2.4 1800 158 1271 76.8 x 35 x 46.1

SGE045RBA 45 Both Aluminum 2.4 3600 188 1260 76.8 x 35 x 46.1

SGE045RBAE 45 Both Aluminum 2.4 3600 188 1260 76.8 x 35 x 46.1

SGE048RBAL 48 Both Aluminum 5.4 1800 200 1555 76.8 x 35 x 46.1

SGE048RBALE 48 Both Aluminum 5.4 1800 200 1555 76.8 x 35 x 46.1

SGE060RGA 60 Gas Aluminum 2.4 3600 250 1230 76.8 x 35 x 46.1

SGE060RPA 60 Liquid Propane Aluminum 2.4 3600 250 1230 76.8 x 35 x 46.1

SGN070RGAL 70 Gas Aluminum 6.8 1800 279 2040 97 x 37 x 47

SGN070RGALE 70 Gas Aluminum 6.8 1800 279 2040 97 x 37 x 47

SGN070RPAL 70 Liquid Propane Aluminum 6.8 1800 279 2040 97 x 37 x 47

SGN070RPALE 70 Liquid Propane Aluminum 6.8 1800 279 2040 97 x 37 x 47

SGN080RGA 80 Gas Aluminum 5.4 3600 320 2075 116 x 37 x 55

SGN080RPA 80 Liquid Propane Aluminum 5.4 3600 320 2075 117 x 37 x 55

SGN100RGALE 100 Gas Aluminum 6.8 2300 417 2075 118 x 37 x 55

SGN100RPALE 100 Liquid Propane Aluminum 6.8 2300 417 2075 119 x 37 x 55

SGN130RGAE 130 Gas Aluminum 6.8 3600 542 2699 120 x 37 x 55

SGN130RPAE 130 Liquid Propane Aluminum 6.8 3600 542 2699 121 x 37 x 55

SGN150RGAE 150 Gas Aluminum 6.8 3600 600 2492 122 x 37 x 55

SGN150RPAE 150 Liquid Propane Aluminum 6.8 3600 600 2492 123 x 37 x 55

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

Compatible Transfer SwitchCatalog Number

SM100R

SM100RD

SM150RD

SM200R

SM200RD

SM300RD

SM400R

SM400RD

SM600R

SM800R

Liquid Cooled Generator Specifications/Compatible Transfer Switches

Standby Power SystemsLiquid Cooled Generators, 120/208V 3-Phase

Page 10: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-10

120/208V 3-Phase Liquid Cooled Generators

Catalog Number kW Rating

Fuel Type Enclosure

Engine Size (Liters)

Speed (RPM)

Amp Output

Weight (lbs.) Dimensions (in.)

SGE022CBAL 22 Both Aluminum 2.4 1800 76 955 62.2 x 30.6 x 38.6

SGE025CBA 25 Both Aluminum 1.5 3600 87 835 62.2 x 30.6 x 38.6

SGE027CBAL 27 Both Aluminum 2.4 1800 94 955 62.2 x 30.6 x 38.6

SGE030CBA 30 Both Aluminum 1.5 3600 104 865 62.2 x 30.6 x 38.6

SGE032CBAL 32 Both Aluminum 2.4 1800 111 1271 76.8 x 35 x 46.1

SGE036CBA 36 Both Aluminum 2.4 3600 125 1202 76.8 x 35 x 46.1

SGE038CBAL 38 Both Aluminum 2.4 1800 132 1271 76.8 x 35 x 46.1

SGE045CBA 45 Both Aluminum 2.4 3600 156 1260 76.8 x 35 x 46.1

SGE045CBAE 45 Both Aluminum 2.4 3600 156 1260 76.8 x 35 x 46.1

SGE048CBAL 48 Both Aluminum 5.4 1800 167 1555 76.8 x 35 x 46.1

SGE048CBALE 48 Both Aluminum 5.4 1800 167 1555 76.8 x 35 x 46.1

SGE060CGA 60 Gas Aluminum 2.4 3600 208 1230 76.8 x 35 x 46.1

SGE060CPA 60 Liquid Propane Aluminum 2.4 3600 208 1230 76.8 x 35 x 46.1

SGN070CGAL 70 Gas Aluminum 6.8 1800 243 2040 97 x 37 x 47

SGN070CPAL 70 Gas Aluminum 6.8 1800 243 2040 97 x 37 x 47

SGN070CGALE 70 Liquid Propane Aluminum 6.8 1800 243 2040 97 x 37 x 47

SGN070CPALE 70 Liquid Propane Aluminum 6.8 1800 243 2040 97 x 37 x 47

SGN080CGA 80 Gas Aluminum 5.4 3600 278 2075 116 x 37 x 55

SGN080CPA 80 Liquid Propane Aluminum 5.4 3600 278 2075 117 x 37 x 55

SGN100CGALE 100 Gas Aluminum 6.8 2300 347 2075 118 x 37 x 55

SGN100CPALE 100 Liquid Propane Aluminum 6.8 2300 347 2075 119 x 37 x 55

SGN130CGAE 130 Gas Aluminum 6.8 3600 451 2699 120 x 37 x 55

SGN130CPAE 130 Liquid Propane Aluminum 6.8 3600 451 2699 121 x 37 x 55

SGN150CGAE 150 Gas Aluminum 6.8 3600 520 2492 122 x 37 x 55

SGN150CPAE 150 Liquid Propane Aluminum 6.8 3600 520 2492 123 x 37 x 55

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

Compatible Transfer SwitchCatalog Number

SL100C

SL200C

SL400C

SL600C

SL800C

Liquid Cooled Generator Specifications/Compatible Transfer Switches

Standby Power SystemsLiquid Cooled Generators, 120/208V 3-Phase

Page 11: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-11

120/240V 3-Phase Liquid Cooled Generators

Catalog Number kW Rating

Fuel Type Enclosure

Engine Size (Liters)

Speed (RPM)

Amp Output

Weight (lbs.) Dimensions (in.)

SGE022JBAL 22 Both Aluminum 2.4 1800 66 955 62.2 x 30.6 x 38.6

SGE025JBA 25 Both Aluminum 1.5 3600 75 835 62.2 x 30.6 x 38.6

SGE027JBAL 27 Both Aluminum 2.4 1800 81 955 62.2 x 30.6 x 38.6

SGE030JBA 30 Both Aluminum 1.5 3600 90 865 62.2 x 30.6 x 38.6

SGE032JBAL 32 Both Aluminum 2.4 1800 96 1271 76.8 x 35 x 46.1

SGE036JBA 36 Both Aluminum 2.4 3600 108 1202 76.8 x 35 x 46.1

SGE038JBAL 38 Both Aluminum 2.4 1800 114 1271 76.8 x 35 x 46.1

SGE045JBA 45 Both Aluminum 2.4 3600 135 1260 76.8 x 35 x 46.1

SGE045JBAE 45 Both Aluminum 2.4 3600 135 1260 76.8 x 35 x 46.1

SGE048JBAL 48 Both Aluminum 5.4 1800 144 1555 76.8 x 35 x 46.1

SGE048JBALE 48 Both Aluminum 5.4 1800 144 1555 76.8 x 35 x 46.1

SGE060JGA 60 Gas Aluminum 2.4 3600 180 1230 76.8 x 35 x 46.1

SGE060JPA 60 Liquid Propane Aluminum 2.4 3600 180 1230 76.8 x 35 x 46.1

SGN070JGAL 70 Gas Aluminum 6.8 1800 210 2040 97 x 37 x 47

SGN070JPAL 70 Gas Aluminum 6.8 1800 210 2040 97 x 37 x 47

SGN070JGALE 70 Liquid Propane Aluminum 6.8 1800 210 2040 97 x 37 x 47

SGN070JPALE 70 Liquid Propane Aluminum 6.8 1800 210 2040 97 x 37 x 47

SGN080JGA 80 Gas Aluminum 5.4 3600 249 2075 116 x 37 x 55

SGN080JPA 80 Liquid Propane Aluminum 5.4 3600 249 2075 117 x 37 x 55

SGN100JGALE 100 Gas Aluminum 6.8 2300 301 2075 118 x 37 x 55

SGN100JPALE 100 Liquid Propane Aluminum 6.8 2300 301 2075 119 x 37 x 55

SGN130JGAE 130 Gas Aluminum 6.8 3600 391 2699 120 x 37 x 55

SGN130JPAE 130 Liquid Propane Aluminum 6.8 3600 391 2699 121 x 37 x 55

SGN150JGAE 150 Gas Aluminum 6.8 3600 451 2492 122 x 37 x 55

SGN150JPAE 150 Liquid Propane Aluminum 6.8 3600 451 2492 123 x 37 x 55

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

Compatible Transfer SwitchCatalog Number

SL100J

SL200J

SL400J

SL600J

SL800J

Liquid Cooled Generator Specifications/Compatible Transfer Switches

Standby Power SystemsLiquid Cooled Generators, 120/240V 3-Phase

Page 12: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-12

277/480V 3-Phase Liquid Cooled Generators

Catalog Number kW Rating

Fuel Type Enclosure

Engine Size (Liters)

Speed (RPM)

Amp Output

Weight (lbs.) Dimensions (in.)

SGE032IBAL 32 Both Aluminum 2.4 1800 48 1271 76.8 x 35 x 46.1

SGE036IBA 36 Both Aluminum 2.4 3600 54 1202 76.8 x 35 x 46.1

SGE038IBAL 38 Both Aluminum 2.4 1800 57 1271 76.8 x 35 x 46.1

SGE045IBA 45 Both Aluminum 2.4 3600 68 1260 76.8 x 35 x 46.1

SGE045IBAE 45 Both Aluminum 2.4 3600 68 1260 76.8 x 35 x 46.1

SGE048IBAL 48 Both Aluminum 5.4 1800 72 1555 76.8 x 35 x 46.1

SGE048IBALE 48 Both Aluminum 5.4 1800 72 1555 76.8 x 35 x 46.1

SGE060IGA 60 Gas Aluminum 2.4 3600 90 1230 76.8 x 35 x 46.1

SGE060IPA 60 Liquid Propane Aluminum 2.4 3600 90 1230 76.8 x 35 x 46.1

SGN070IGAL 70 Gas Aluminum 6.8 1800 105 2040 97 x 37 x 47

SGN070IPAL 70 Gas Aluminum 6.8 1800 105 2040 97 x 37 x 47

SGN070IGALE 70 Liquid Propane Aluminum 6.8 1800 105 2040 97 x 37 x 47

SGN070IPALE 70 Liquid Propane Aluminum 6.8 1800 105 2040 97 x 37 x 47

SGN080IGA 80 Gas Aluminum 5.4 3600 120 2075 116 x 37 x 55

SGN080IPA 80 Liquid Propane Aluminum 5.4 3600 120 2075 117 x 37 x 55

SGN100IGALE 100 Gas Aluminum 6.8 2300 150 2075 118 x 37 x 55

SGN100IPALE 100 Liquid Propane Aluminum 6.8 2300 150 2075 119 x 37 x 55

SGN130IGAE 130 Gas Aluminum 6.8 3600 195 2699 120 x 37 x 55

SGN130IPAE 130 Liquid Propane Aluminum 6.8 3600 195 2699 121 x 37 x 55

SGN150IGAE 150 Gas Aluminum 6.8 3600 225 2492 122 x 37 x 55

SGN150IPAE 150 Liquid Propane Aluminum 6.8 3600 225 2492 123 x 37 x 55

*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018

Compatible Transfer SwitchCatalog Number

SL100I

SL200I

SL400I

SL600I

SL800I

Liquid Cooled Generator Specifications/Compatible Transfer Switches

Standby Power SystemsLiquid Cooled Generators, 277/480V 3-Phase

Page 13: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-13

SM Type transfer switches

SM Type Transfer Switches

Catalog Number Amp

Branch Circuits

KA Rating (in Amps)

Weight (lbs.) Dimensions (in.) Enclosure Type

SM100R100

10,000

20 20 x 14.6 x 7.09 Aluminum

SM100RD 23 21 x 14.6 x 7.09 Aluminum

SM150RD 150 39 30 x 13.5 x 6.3 Aluminum

SM200R200

20 20 x 14.6 x 7.09 Aluminum

SM200RD 39 30 x 13.5 x 6.3 Aluminum

SM300RD 300

22,000

140 48 x 21.82 x 10.06 Aluminum

SM400R400

133 36 x 24 x 10.6 Aluminum

SM400RD 140 48 x 21.82 x 10.06 Aluminum

* kW rating is from 8 to 20kW on each switch listed/NEMA 3 rating for each.

Features and ratingsn 100-400A

n Open transition

n Cover more circuits with a smaller generator

n Cover every circuit when paired with a higher kW generator

n Outdoor NEMA 3R aluminum enclosure

n Service rated and non-service rated

n Compatible with Evolution and NEXUS controllers

n Add additional PMM modules (6186) and manage up to four more large loads on single phase SE type transfer switches

Transfer switches provide the mechanism for transferring power between utility and generator service. Engineered with Digital Power Management (DPM) technology. 100-400A single phase SM Type transfer switches have the ability to cycle on and off two air conditioners without adding additional components, allowing for a smaller generator to cover more circuits than when paired with a standard transfer switch.

Transfer SwitchesSM Type Single-Phase

SM modelsSMD models

(service rated)

Page 14: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-14

*Disconnect included

ST Type Transfer Switches

Catalog Number Amp

kW rating

Branch circuits

KA rating (Amp)

Weight (lbs.) Dimensions (in.)

NEMA rating Enclosure

ST050R10C 50

8 10

10,000

5722.5 x 15.4 x 3.8

1 ST

ST050R12C 11 12 61 1 ST

ST100R16C 100 16 16 68 29.25 x 12.5 x 7 1 ST

ST Type transfer switchesST type transfer switches are compatible with the Evolution and NEXUS controllers. The controller senses power outages and initiates the transfer of power to the generator via the automatic transfer switch.

Features and ratingsn 30 ft. pre-wired conduit for connecting

the transfer switch to the external connection box

n 2 ft. pre-wired conduit for moving circuits from the main panel to the transfer switch

n Pre-wired external connection box with a weatherproof conduit for generator connections

n Compatible with Evolution and NEXUS controllers

n Electrically operated, mechanically contacts for fast, positive connections

n Rated for all classes of load,100%

equipment rated, both inductive and resistive

n 160 millisecond transfer time

n 50 amps = 10 & 12 circuit, single coil design, flush mountable

n 100 amps = 14 & 16 circuit, dual coil design

n Main contacts are silver plated or silver alloy to resist welding and sticking

n Suitable for use only on air cooled products (8–17 kW)

n Open transition

n Express install kit included

Transfer SwitchesST Type Single-Phase

Page 15: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-15

Features and ratingsn 100–800A

n Outdoor NEMA 3R aluminum enclosure

n Open transition

n Compatible with Nexus controllers

n Cover more circuits with a smaller generator

n Service rated and non-service rated

n Add additional individual DLM modules (5937) and manage up to four more large loads on single phase SL type transfer switches. See page 18-19

n Cover every circuit when paired with a higher kW generator

SL Type Transfer Switches

Catalog number Amp Phase

Withstand rating (Amps)

Weight (lb.) Dimensions (in.)

SL100C

100

120/208V, 3Ø 10,000 20 24.1 x 20.2 x 7.1

SL100J 120/240V, 3Ø 14,000 53 24.1 x 20.2 x 7.1

SL100I 277/480V, 3Ø 14,000 105 36.1 x 24 x 10

SL200C

200

120/208V, 3Ø 10,000 20 24.1 x 20.2 x 7.1

SL200J 120/240V, 3Ø 25,000 53 24.1 x 20.2 x 7.1

SL200I 277/480V, 3Ø 25,000 105 48.1 x 30.1 x 13.1

SL400C

400

120/208V, 3Ø 18,000 133 36.1 x 24 x 10

SL400J 120/240V, 3Ø 18,000 133 36.1 x 24 x 10

SL400I 277/480V, 3Ø 18,000 133 36.1 x 24 x 10

SL600C

600

120/208V, 3Ø 42,000 439 66 x 36 x 21

SL600J 120/240V, 3Ø 42,000 439 66 x 36 x 21

SL600I 277/480V, 3Ø 42,000 439 66 x 36 x 21

SL800C

800

120/208V, 3Ø 65,000 469 66 x 36 x 21

SL800J 120/240V, 3Ø 65,000 469 66 x 36 x 21

SL800I 277/480V, 3Ø 65,000 469 66 x 36 x 21

SL Type transfer switchesTransfer switches provide themechanism for transferring powerbetween utility and generator service.Engineered with Digital LoadManagement (DLM) technology, 100-400A single phase SL Type transferswitches have the ability to cycle onand off two air conditioners withoutadding additional components, allowingfor a smaller generator to covermore circuits than when paired witha standard transfer switch.

Three-Phase Transfer Switches

Three phase transfer switch

Catalog Number Amp Phase

Withstand rating (Amps)

Weight (lb.) Dimensions

RTSW100G3 100 120/208V 3Ø 14,000 49 24 x 20 x 7.3

RTSW100J3 100 120/240V 3Ø 14,000 49 24 x 20 x 7.3

RTSW100K3 100 277/480V 3Ø 14,000 49 24 x 20 x 7.3

RTSW200G3 200 120/208V 3Ø 18,000 49 24 x 20 x 7.3

RTSW200J3 200 120/240V 3Ø 18,000 49 24 x 20 x 7.3

RTSW200K3 200 277/480V 3Ø 18,000 49 24 x 20 x 7.3

Page 16: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-16

Portable Generators: 5.5, 6.5, 7.5, 8, 15, 17.5 kWFeatures and ratingsn Ideal for residential emergency and

job-site power

n Gasoline powered, OHV engine

n Include handles and wheels for easy movement

n Hour meter included

n Large variety of outlets

n Low noise muffler

n 2 year residential warranty

n Easily integrated into home electrical systems with Siemens breaker interlock kits (pictured below)

Portable Accessories: 5715 - Lifting Beam Kit; 6.5 kW & 8.0 kW

Refer to page 12 for Portable Maintenance Kits

Portable Generator Catalog Numbers

PG0055 PG0065 PG0075Ea PG0080Ea PG015a PG017a

Rated Power 5.5 kW 6.5 kW 7.5 kW 8 kW 15 kW 17.5 kW

Surge 6.875 kW 8 kW 9.37 kW 10 kW 22.5 kW 26.2 kW

Rated Amps @ 60Hz 120/240, 1Ø, 1.0 pf 22.9 27.1 31.2 33.3 62.5 73

Engine RPM 3600 3600 3600 3600 3600 3600

Fuel Capacity (gallons) 6.6 6.6 8 8 16 16

Dimensions (inches) 34 x 26.5 x 27.5 34 x 27 x 28 28.75 x 26.75 x 26 34 x 27 x 28 39 x 31 x 49 39 x 31 x 49

Weight (lbs) 180 172 201 192 450 475

�a Manual Electric Starter

Standby Power SystemsPortable Generators

Page 17: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-17

Features:n NEMA 3R / Indoor Type 1

n 225A max rated

n Flush or surface mounting

n Fits between standard stud centers

n Tin plated copper bus bars

n 22 kAIC rated

n 120/240V, 1 Phase

n Main lug – convertible to main breaker with addition of MBK150A, MBK200A, or MBK225A

n Installation of transfer mechanism can be performed at time of generator installation

A

B

D

E

F

C

S

A

BD

EF

CSS

Traditional Installation Generator Ready Load Center with Portable Generator installation

Generator Ready Load Center with Automatic Standby generator installation

The Siemens Generator Ready Load Center can save thousands of dollars in future generator installation expenses while keeping initial expenses to a minimum. Works with an automatic standby generator or a portable generator.

Catalog No.ECSBPK01 (mechanical interlock for manual or portable generation installation)

GENTFRSWTCH (auto transfer switch for automatic standby generation installation)

Automatic Transfer Switch features:n UL Listed

n Operates automatically when connected to generator

n Transfers load from utility to generator and back to utility

n Includes: Q215 and Q2125S needed for installation

NOTE:GENTFRSWTCH is sold separately from Gen ready panel!

Generator Ready Load Center

Standby Power SystemsGenerator Ready Load Center

Page 18: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-18

Generator Ready Load Centers

Amp Rating

No. of Spaces

No. of Circuits Catalog No.

Dimensions (inches)

Height Width Depth

Indoor Enclosure – NEMA Type 1

200 30 42 G3042B1200GEN 42.00 14.25 4.00

225 30 42 G3042L1225GEN 42.00 14.25 4.00

200 42 54 G4254B1200GEN 44.0 14.25 4.00

225 42 54 G4254L1225GEN 44.0 14.25 4.00

Outdoor Enclosure – NEMA Type 3R200 30 42 W3042B1200GEN 42.00 14.63 4.00

225 30 42 W3042L1225GEN 42.00 14.63 4.00

G3042L1225GEN

Install ECSBPK01for portablegenerators

Install GENTFRSWTCH for automatic standby generators

Standby Power SystemsGenerator Ready Load Center

NOTE:GENTFRSWTCH is sold separately from Gen ready panel!

Page 19: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-19

Panels in which the bussing or wire forms from the meter socket land on main lugs are not acceptable for use in standby systems because turning the main breaker to “OFF” does not prevent feedback to the utility power lines. Examples of such panels include catalog numbers that start with the following letters.

MC0606L1200*MM0406L1*MC1212L1200*

Standard featuresn UL listed for use in most Siemens

load centers and meter combinations

n Suitable for use with optional standby systems in accordance with article 702 of the National Electric Code

n Corrosion resistant finish

n Easy assembly requiring no modifications to the load center or meter combination

n Remains attached to the main breakers when load center cover

Wire formsor bussing

Acceptable usage of Interlock Kits by load center/meter combination catalog numbers

Siemens Meter CombinationsMC0816B1150RTH 5 7 MC2040B1200 5 7

MC0816B1150T 5 7 MC2040B1200R 5 7

MC0816B1150TH 5 7 MC2442B1200FEC 2

MC0816B1200FCTM 2 MC2442B1200SEC 2

MC0816B1200RT 5 7 MC3040B1200SECW 5 7

MC0816B1200RTB 5 7 MC3042B1200FED 3

MC0816B1200RTH 5 7 MC3042B1200SED 3

MC0816B1200SCTM 2 MC3042B1225FED 3

MC0816B1200T 7 MC3042B1225SED 3

MC0816B1200TH 5 7 MC4040B1200SECW 5 7

MC0816B1350RLTM 5 7 MC0816B1200RJBT 8

MC0816B1400RLTM 5 7 MC0816B1150RJBT 8

MC1224B1100FEC 2 MC0816B1200RCT 8

MC1224B1100SEC 2 MC0816B1150RCT 8

MC1224B1125 1 2 MC0816B1200CT 8

MC1224B1125FEC 2 MC0816B1150CT 8

MC1224B1125SEC 2 MC2040B1150RCT 9

MC1632B1100SEC 2 MC2040B1150CT 9

MC1632B1125FEC 2 MC2040B1200RCT 9

MC2040B1150 5 7 MC2040B1200CT 9

Numbers 1 through 9 in these tables represent the last digit in each interlock kit catalog number. Example: 1 = ECSBPK01

When used in horizontal positions as typical in most load centers, ECSBPK07 is recommended for use only with QNR type circuit breakers.

Standby power interlock kits are not intended for use with AFCI, GFCI, 3-pole or 1/2” frame circuit breakers and 4 space, 125 amp load centers.

Siemens type EQ load centers using a “4-pole” main breaker do not have a kit available to interlock this main to branch circuits. Branch circuit positions can be interlocked.

Convert load centers or meter combinations into standby power panels

ES Series Load Centers can utilize interlock kits: 1, 2, 5, 6, 7. Kits 3 and 4 can also be used on main breaker panels.

PL Series Load Centers can utilize interlock kits: 1, 2, 3, 4, 5, 6, 7.

To activate standby power the utility main breaker must be in the “OFF” position to prevent dangerous feedback between the power sources.

Utility main breaker

Standby power main breaker

Standby Power SystemsManual Transfer Interlock Kits

Page 20: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-20

Standby Power SystemsManual Transfer Interlock Kits

Prevents dangerous feedback between two sources of power

a Manual breaker interlock kits are attached to the break-ers not the trim of the load center.

b These kits take up 2 spaces adjacent to the 2 pole breaker being interlocked. Those spaces cannot accommodate filler plates.

Manual Transfer Interlock Kitsa

Catalognumber

UsageInformation

Utility mainbreaker types

Standby mainbreaker types

InterlockNumber

ECSBPK01 For use on load centers or meter combinations that will accept 2-pole circuit breakers oppositeone another as shown.

QP, QPH, HQPH QP, QPH, HQPH 1

ECSBPK02 For use on load centers or meter combinations that will accept 2- or 4-pole next to a 2-pole circuit breaker side by side as shown.

QP, QPH, HQPH QP, QPH, HQPH 2

ECSBPK03b For use on UltimateTM and RockSolid load centers, 150 amp andhigher, to connect the main breakerto a 2-pole circuit breaker.

MBK150A,MBK200A, OR MBK225A

QP, QPH, HQPH 3

ECSBPK04b For use on Ultimate and Rock Solidload centers, 125 amp and lower,to connect the main breaker to a 2-pole circuit breaker.

MBK100A orMBK125A

QP, QPH, HQPH 4

ECSBPK05 For use on load centers or meter meter combinations that will accept a QNR (MD-TR) frame circuit breaker next to a 2-pole circuit breaker as shown.

QNR, QNRH, HQNR QP, QPH, HQPH 5

ECSBPK06b For use on load centers or meter combinations that will accept a QN (MD-T) frame circuit breaker next to a 2-pole circuit breaker as shown.

QN, QNH, HQN QP, QPH, HQPH 6

ECSBPK07 For use on load centers or meter combinations that will accept two QNR (MD--TR) circuit breakers side by side as shown OR will accept two QN (MD--T) circuit breakers side by side as shown.

QNR, QNRH, HQNR, QN, QNH, HQN

QNR, QNRH, HQNR QN,QNH, HQN

7

ECSBPK08b For use on 8 space, over/under,OH/UG feed meter combinations as shown. Limited application to specific catalog numbers.

QPP, QPPH QP, QPH, HQPH 8

ECSBPK09b For use on 20 space, over/under, OH/UG feed meter combinations as shown. Limited application to specific catalog numbers.

QPP, QPPH QP, QPH, HQPH 9

Page 21: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-21

Generator Ratings

kW Rating(LP/NG) Rated Amps

Engine RPM at full load

Natural gas fuelconsumption(ft^3/hr)

Liquid propane vapor consumptionN(gal/hr)

Propane vaporconsumptionft^3/ft

Sound level atnormal load

Sound levelat exercise

8/7 35 3600 118.9 1.47 51.4 62 N/A

11/10 50 3600 160.3 2.08 72.7 63 N/A

16/16 65 3600 312 3.57 130 66 60

20/18 90 3600 303.4 3.99 139.5 66 60

22/19.5 100 3600 281 3.68 127 67 58

for Btu content, multiply ft^3/hr x 2520 (LP) or ft^3/hr x 1000

AccessoriesCatalog No. Usage

5621 Auxiliary Transfer Switch Contact

GENPAINT Gray Touch Up Paint for 2007 units

GENPAINT2 Generator Spray Paint Gray Textured

GENSHELL2 Display Shell, gray color

7101 Battery Pad Warmer

7102 Oil Warmer

7103 Breather Box Warmer

68730Smart Management Module - load management system that operates autonomously

6424 Brown Out Kit

5928 Standard Wireless Remote in Home Monitor

GENCART

The Generator Transport Cart is designed to allow a single individual to move and position any of the air-cooled generators without the need for additional people or equipment. By attaching the cart to the generator through the lifting holes, the generator is lifted from the pallet by leverage and is easily wheeled to the appropriate location for final setting

5666

The pad skirt snaps together around the bottom of the new 20kW generators. This offers a sleek, contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base. Available in grey, the pad skirt fits 20kW generators manufactured after 4/2008.

6510E-stop allows for immediate fuel shutoff and generator shutdown in the event of an emergency.

Maintenance KitsJust like an engine in an automobile, generator engines require routine main-tenance. Service kits, which include oil and air filters, are available and are selected based on engine size. Touch up paint is also provided to help cover minor scratches.

Oil and Air Filter KitsASGE ASGN

Catalog No. Usage Catalog No. Usage

GENMKIT19 8 kW 410cc GENMKIT10 8 kW 410cc

GENMKIT20 11 kW 530cc GENMKIT2 10 kW 530cc

GENMKIT21 14,16 kW 992cc GENMKIT3 14, 17 kW 990cc

GENMKIT22 20, 22 kW 999cc GENMKIT11 20 kW 990cc

PORTMKIT1 Portable 15, 17.5 kW

PORTMKIT2 Portable 5, 6.5 kW

PORTMKIT3 Portable 8 kW

Cold Weather Kits

Generator Size (kW)

Cold Weather Kit Part no.

Extreme Cold Weather Kit Part No.

9 7101, 7102, 7103 n/a11 7101, 7102, 7103 n/a16 7101, 7102, 7103 n/a20 7101, 7102, 7103 n/a22 (Air Cooled) 7101, 7102, 7103 n/a22 (Liquid Cooled) 5630 561625 6175 617427 5630 561630 6175 617432 5630 561636 5630 561638 5630 561645 5630 561648 5632 620460 5630 561670 5632 562080 5632 7088

100 5633 5620130 5633 5620150 5632 5667

Extreme cold weather kit

Standby Power SystemsRatings / Maintenance Kits / Accessories / Cold Weather Kits

Page 22: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-22

6463 – Mobile Link6478 – Liquid-Cooled Extension CableNote: this cable is required with Mobile Link for all liquid-cooled units.

Compatibility:Mobile Link is designed for use with a generator equipped with an LCD display. Mobile Link is compatible with most 2008-and-newer air-cooled standby generators and 2010-and-newer liquid-cooled standby generators.Note: Please ensure you have cellular service in your area before purchasing.

Email or Text Notifications:StandbyStatus.com provides over 40 different notifications, including successful exercise, maintenance reminders, change in status, low battery, fault alert and more:

n When maintenance is required or fault conditions occur, StanbyStatus.com automatically sends out alerts

n Dealer gets accurate data and can respond quickly and efficiently to problems

n Customers designate up to 4 different accounts to receive email and text notifications, including their dealer, so that they can discuss options with the customer to address the generator’s issues.

n Notifications drive regular, timely communication with the customer

StandbyStatus.com:StandbyStatus.com features a user-friendly dashboard that allows the customer to check their generator’s status anytime, anywhere:n View current generator status and upcoming maintenance needs

n Remotely set exercise schedule

n Review run and maintenance history

n Get local weather updates

n Change messaging settings

Mobile Link: Cellular remote monitoring system for your generator

How does it work?

Standby Power SystemsCellular Monitor

Page 23: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-23

All the conveniences of modern living—heat, central air, refrigeration, communication—are nothing without power. When the power supply is disrupted, our lives and businesses can come to a sudden halt. An automatic standby generator protects you from power failures, restoring power within seconds of an outage, so you can have peace of mind and the power you need.

Siemens’ new Protector™ Series diesel generators raise the bar for residential and light commercial diesel generators. Building and zoning codes can vary wildly from one region to another. In the past, the only answer was to order expensive, custom-configured solutions.

Protector™ Series Automatic Standby Diesel Generator

Until now.

Siemens’ diesel-powered Protector Series features Code Ready, a set of popular preconfigured options and a range of code-driven accessories, so you can feel confident that your generator will be able to conform to the required local codes. The Protector Series is versatile, adaptable, meets UL requirements, and is an affordable optional standby diesel generator for your backup power needs.

Standby Power SystemsDiesel Generators

Page 24: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-24

Diesel Generator Specifications

15 kW 20 kW 30 kW 48 / 50 kWCatalog Number RD015 RD020 RD030 RD048* / RD050

Engine/Alternator RPM 1800/1800

Engine In-line 4-cylinder

Fuel Type Diesel

Output Voltage 120/240 V, 1Ø, 1.0 pf 62 83 125 200

Output Voltage 120/208 V, 3Ø, 0.8 pf 52 69 104 173

Output Voltage 120/240 V, 3Ø, 0.8 pf 45 60 90 150

Output Voltage 277/480 V, 3Ø, 0.8 pf n/a n/a 45 75

Fuel Consumption @ 1/2 load - gal/hr (L/hr) 0.79 (2.99) 1.05 (3.97) 1.45 (5.5) 2.3 (8.71)

Fuel Consumption @ full load - gal/hr (L/hr) 1.48 (5.58) 1.98 (7.48) 2.74 (10.4) 4.3 (16.36)

Quiet-Test Mode Yes

db(A) at exercise 65

db(A) at normal operating load 70

Enclosure Steel

Enclosure Color Gray

Warranty 5-year limited

Dimensions (L” x W” x H”) 49.4 x 80.8 x 30.55 55.4 x 95.4 x 35

Weight (lbs.) 1474 1574 1755 2114

EPA Emission Regulations Yes

*1Ø only

Diesel Generators:Siemens diesel generators are fully configured and tested. A fully configured diesel generator means you receive the generator and the fuel tank together. Our generators are prototyped tested, system torsional tested, NEMA MG1-22 evaluation, and motor starting ability tested. The prototype testing includes total commitment to component testing, reli-ability testing, environmental testing, destruction and life test-ing, plus testing to applicable CSA, NEMA, EGSA, and other standers. All models also come standard with a state of the art power maximizing regulation system. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque matching the surge loads to the engine and digital regulated

the voltage at +-1%. All this allows you to choose a Siemens diesel generator with confidence that these systems will pro-vide superior performance.

If you need assistance in ordering your diesel system please see our preorder check list and easy order selection guide on pages 7 and 8.

If you have any further questions please reference page 9 to contact our Siemens Tech Support line/email box that is dedi-cated for generators.

Standby Power SystemsProtector™ Series Automatic Standby Diesel Generators 15 - 50 kW

Page 25: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-25

Diesel Generator Catalog Logic

Catalog No.

Catalog logic Generator information

Diesel

kW Size015 = 15kW020 = 20kW030 = 30kW048 = 48kW050 = 50kW

Engine Size in Liters23 = 2.3L24 = 2.4L34 = 3.4L

Voltage & PhaseADAE = 120/240V, 1ØGDAE = 120/208V, 3ØJDAE = 120/240V, 3ØKDAE = 277/480V, 3Ø Enclosure Speed

Weight (lbs.) Dimensions (in.)

db(A) at exercise / full load

RD01523ADAE RD 015 23L ADAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70

RD01523GDAE RD 015 23L GDAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70

RD01523JDAE RD 015 23L JDAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70

RD02023ADAE RD 020 23L ADAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70

RD02023GDAE RD 020 23L GDAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70

RD02023JDAE RD 020 23L JDAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70

RD03024ADAE RD 030 24L ADAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70

RD03024GDAE RD 030 24L GDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70

RD03024JDAE RD 030 24L JDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70

RD03024KDAE RD 030 24L KDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70

RD04834ADAE RD 048 34L ADAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70

RD05034GDAE RD 050 34L GDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70

RD05034JDAE RD 050 34L JDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70

RD05034KDAE RD 050 34L KDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70

Featuresn Two line LCD multilingual digital Evolution

Controller (English, Spanish, French, Portuguese) with external viewing window for easy indication of generator status and breaker position.

n Isochronous Electronic Governor

n Sound Attenuated Enclosure

n Smart Battery Charger

n UV/Ozone Resistant Hoses

n +-1 % Voltage Regulation

n Integrated Base Tank provides 24 hour run time minimum at ½ load

n UL/CUL2200/UL 142 Listed

n Meets code requirements for External Vent and Fill

Please read all additional information located in the following pages before purchasing a diesel generator.

Standby Power SystemsProtector™ Series Automatic Standby Diesel Generators 15 - 50 kW

Page 26: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-26

SM & SL Type Transfer SwitchesTransfer switches provide the mechanism for transferring power between utility and generator service. Engineered with Digital Power Management (DPM) technology. 100-400A single phase SM & SL type transfer switches have the ability to cycle on and off 2 air conditioners without adding additional components, allowing for a smaller generator to cover more circuits than when paired with a standard transfer switch. Diesel units are compatible with the same transfer switches as natural gas/propane units.

SM and SL Transfer Switches

Catalog Number Amp

KA rating (Amp) Weight (lbs.) Dimensions (in.)

Disconnect included

Single PhaseSM100R 100 10,000 20 20 x 14.6 x 7.09 NoSM100RD 100 10,000 23 20 x 14.6 x 7.09 YesSM150RD 150 10,000 39 30 x 13.5 x 6.3 YesSM200R 200 10,000 20 20 x 14.6 x 7.09 NoSM200RD 200 10,000 39 30 x 13.5 x 6.3 YesSM300RD 300 22,000 145 48 x 21.82 x 10.06 YesSM400R 400 22,000 141 36 x 24 x 10.6 NoSM400RD 400 22,000 145 48 x 21.82 x 10.06 Yes

Three PhaseSL100C 100 10,000 65 24.1 x 20.2 x 7.1 NoSL100J 100 14,000 57 24.1 x 20.2 x 7.1 NoSL100I 100 14,000 135 36.1 x 24 x 10 NoSL200C 200 10,000 48 24.1 x 20.2 x 7.0 NoSL200J 200 25,000 65 24.1 x 20.2 x 7.0 NoSL200I 200 25,000 105 48.1 x 30.1 x 13.1 NoSL400C 400 18,000 160 36.1 x 24 x 10 NoSL400J 400 18,000 133 36.1 x 24 x 10 NoSL400I 400 18,000 133 48.1 x 30.1 x 13.1 NoSL600R 600 42,000 439 66 x 36 x 21 NoSL600C 600 42,000 439 66 x 36 x 21 NoSL600J 600 42,000 439 66 x 36 x 21 NoSL600I 600 42,000 439 66 x 36 x 21 NoSL800R 800 65,000 469 66 x 36 x 21 NoSL800C 800 65,000 469 66 x 36 x 21 NoSL800J 800 65,000 469 66 x 36 x 21 NoSL800I 800 65,000 469 66 x 36 x 21 No

Featuresn 100 – 800A

n Outdoor NEMA 3R AL enclosure

n Open transition

n Compatible with Evolution and Nexus controllers

n Cover more circuits with a smaller generator

n Service rated and non-service rated

n Add additional individual SMM Modules (68730) and manage up to 4 additional large loads on a single SM transfer switch

n Cover every circuit when paired with a higher kW generator

Transfer SwitchesSM Type Single Phase and SL Type Three-Phase

Page 27: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-27

Diesel Generator Accessories

Model # Product Description

6502 Spill Box The 5-gallon spill box screws into the existing fuel fill port of the base tank. It captures and contains fuel if over fueling or spilling occurs during the fill process.

6504 90% Fuel Level Alarm The 90% fuel level alarm alerts the fuel fill operator when the tank reaches a 90% fill level by sounding an audible alarm and triggering an LED warning light.

6505 – 15 & 20 kW6506 – 30 & 50 kW Tank Risers Tank risers are required in some municipalities to help avoid potential base tank

corrosion caused by mounting on rough surfaces.

6507 Fuel Fill Drop Tube

A powder coat painted, steel fuel fill drop tube is required in some municipalities to prevent sparking due to static electricity buildup, which can be caused by the fuel dropping into the tank from the fill area. Using a drop tube also results in submerged filling, which increases the fuel delivery flow rate and reduces vapors, foam and potential tank evaporation.

6513 – 15 & 20 kW6517 – 30 kW6516 – 50 kW

Stainless Steel Fuel LinesSome municipalities require the use of stainless steel fuel lines instead of the standard hoses provided with the diesel generator products. These stainless steel lines are fire resistant for additional safety.

6510 E-Stop E-stop allows for immediate fuel shutoff and generator shutdown in the event of and emergency.

6511 Spill Box Drainback Kit The spill box drainback kit allows fuel that was captured in the 5-gallon spill box to be drained directly back into the fuel tank to avoid vapors.

6512 Lockable Fuel Cap The cast iron, lockable fuel cap provides the ability to lock the fuel system to prevent unwanted fuel tampering or fuel siphoning.

6572 – 15 & 20 kW6571 – 30 kW 6570 – 50 kW

Maintenance Kits The Protector Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac Protector generators.

6560 – 15 & 20 kW6559 – 30 kW6558 – 50 kW

Cold Weather KitsRecommended for generators installed in regions where the temperature regularly falls below 32 °F (0 °C). The Cold Weather Kits consist of a block heater with all necessary mounting hardware and a battery warmer with a thermostat built into the battery wrap.

6576 Fuel Maintenance Kit The Fuel Maintenance Kit contains everything needed to maintain and clean a diesel fuel system.

5704 Paint KitIf the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure.

5928 Basic Wireless Remote Completely wireless and battery powered, Generac’s wireless remote monitor provides you with instant status information without ever leaving the house.

5951 Advanced Wireless Remote Remotely control generator functions with the advanced model’s LCD display. In addition to remote testing of the generator, set the exercise cycle and maintenance interval reminders.

6199 PMM Starter Kit

The PMM Starter Kit consists of a 24 VAC, field installed transformer that enables the use of the 24 VAC Power Management Modules (PMMs) and one PMM. The standard controller (without starter kit) can control two HVAC loads with no additional hardware. Not compatible with pre-wired switches.

6186 Power Management Module (50 Amps)

Power Management Modules are used in conjunction with the Smart Switch to increase its power management capabilities. It gives the Smart Switch additional power management flexibility not found in any other transfer switch. Not compatible with pre-wired switches. Note: PMM Starter Kit required.

6588 Vent Extension Support Kit

The Vent extension support kit consists of 2 aluminum plates with the appropriate pipe cutouts to secure the bent extension pipes coming through the top of the generatorenclosure. It helps to minimize stress on the NPT fittings integrated on the tank and also helps protect against pests.

6463 Mobile Link Mobile Link is designed for use with a generator equipped with an LCD display. Mobile Link sends status updates to StandbyStatus.com.

6478 Extension Cable An extension cable to connect Mobile Link to the Diesel Generators.

Standby Power SystemsAccessories for 15, 20, 30, 48, 50 kW Diesel Generators

Page 28: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-28

Pre-order checklist

Item Description Catalog no. Required

Emergency Stop Switch 6510 Yes No

90% Fuel Level Alarm 6504 Yes No

Five Gallon Spill Box 6502 Yes No

Spill Box Drain Back 6511 Yes No

Anti-Static Fuel Fill Tube 6507 Yes No

Fuel Tank Support Risers6505 (15 & 20 kW)6506 (30 & 50 kW)

Yes No

Stainless Steel Fuel Lines6513 (15 & 20 kW)6517 (30 kW)6516 (50 kW)

Yes No

The local fire marshal has confirmed that the generator must be located a minimum of ________ feet from a house or other structure.

NOTE: A minimum clearance of five feet is recommended.

The local AHJ has advised me regarding the requirements for electrical and/or building permits, as well as those regulations relating to emissions and fuel storage.

I have been advised of the local requirements for construction of a concrete base pad, and whether anchoring requirements are needed for installation on a flood plain.

I have confirmed with the appropriate authorities that the generator must be located a minimum of ________ feet from a property line.

I have been advised whether the local fire marshal (or other third party) is required to be present at start up.

I have confirmed that the installation site is applicable to optional standby only and does not require an NFPA 110 capable generator.

The local fire marshal has confirmed that I am required to extend the fuel tank vents ________ feet above the surrounding grade.

The local fire marshal has confirmed that local codes require installation of the diesel product safety accessories designated below.

Standby Power SystemsDiesel Generators

Page 29: Standby Generators

18

STAN

DB

Y G

ENERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-29

Easy Order Selection Guide

To determine the correct product codes for a diesel generator and transfer switch follow the steps below. A product code is required to order. To place an order, e-mail or fax the product

Transfer Switches Selection GuideStep 1 Step 2 Step 3 Step 4

Selection Criteria Transfer Switch used with Generator ControllerSL = 3 PhaseSM = 1 Phase

Amp Ratinge.g. (200 Amp = 200)

VoltageR = 120/208V, 1 ØC = 120/208V, 3 ØJ = 120/240V, 3 ØI = 277/480V, 3 Ø

Service Disconnect Rated*Blank = NoD = Yes

For Standby Generators 8 - 150 kW

SL 100, 150, 200, 300, 400, 600, 800

R, C, J, I D

Product Number (Enter on Order Form)

NOTE: There are no returns, changes or cancellations on Siemens DIESEL orders.This equipment is built -to-order once payment is received.

* Service rated switches only available for single phase units, with the exception of 100 and 200 amp options that will remain Generac branded - these can be found in the table on page 18-15.

Diesel Generator Selection GuideStep 1 Step 2 Step 3 Step 4 Step 5 Step 6

All diesel product codes begin with RD

kW Ratings e.g. (15 kW = 015)

Engine e.g. (2.3L = 23)

VoltageA = 120/240 1ØG = 120/208 3ØJ = 120/240 3ØK = 277/480 3Ø

Fuel D = Diesel

Enclosure A = Aluminum

Tank E = Extended Tank

015020030048*050*

2.3L @1800 RPM2.3L @ 1800 RPM2.4L @ 1800 RPM3.4L @ 1800 RPM3.4L @ 1800 RPM

A, G, JA, G, J

A, G, J, KA*, G, J, KA, G, J, K

DDDDD

AAAAA

EEEEE

Product Number (Enter on Order Form)* = 48kW in single phase configuration only. 50kW in three phase configuation only.

codes to your inside sales representative or place your order online. If you have questions, call 1-888-Generac. Freight is FOB factory. Charges will be determined at the time of order.

Standby Power SystemsDiesel Product - U.S. and Canada

R D 0 3 0 2 4 G D S E

R D

S M 2 0 0 R DSample

Sample

Page 30: Standby Generators

18

STA

ND

BY

GEN

ERA

TORS

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-30

Additional Information

n These units are not available with ALL enclosures.

n MUST USE A CERTIFIED GENERAC WARRANTY DEALER TO DO ANY AND ALL WARRANTY WORK ON THESE UNITS. A technician will be required to go through certification training prior to being able to file a warranty claim for diesel product.

n This product is currently NOT compatible with Mobile Link™.

n Extended warranties are currently NOT available for these units.

n These units will not ship with a battery. Battery requirements are Group 27F, 700 CCA for 15kW – 50kW.

n If you must connect your diesel generator to a day tank it is possible. THIS WILL VOID YOUR WARRANTY and Generac will not support the connection to a day tank.

n These are standby only, and will not have a limited prime rating.

n These units are NOT LIFE SAFETY RATED.

n These units CANNOT run on heating oil.

n MUST GET LOCAL FIRE MARSHAL’S APPROVAL BEFORE INSTALLATION. Fire Marshal is required for Diesel generator installations with tanks. Diesel cannot be added to the tank without approval and or witness by the fire marshal. It is also important to check with all other local, regional, and/or state codes that are required for installation. If diesel is added to the tank without the proper authority’s approval, the unit can be flagged for hazardous material. This will result in an expensive removal process that the customer will be responsible for.

n NON RETURNABLE.

n Compatible with single and three phase SL and SM series automatic transfer switches.

n Cold weather kits are necessary when the temp regularly falls below 32°F.

Standby Power SystemsDiesel Generators