staircase pressurisation calculation

Upload: mohammed-faisal-siddiqui

Post on 14-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Staircase Pressurisation Calculation

    1/1

    DESCRIPTION

    No of Floors 48 Nos

    Assuming Gap Between Door and Floor 6 mm

    Height of the Door 2500 mm

    Length of the Door 1250 mmNo of Doors per Floor 1 Nos

    AREA OF LEAKAGE

    Area of Leakage (Sq.Mt)= Door Perimeter (mm) x Gap (mm)x 10^-6

    Door Perimeter = 7500 mm

    Area of leakage 0.045 Sq.Mt

    Case -1

    When doors Closed

    Q = Leakage Air (m3/sec) = 0.839 *Area of Leakage * Sq.root of Pressure Diff

    Pressure Difference (Pa) = 50 (Bldg Ht is more than 100 Mt)

    Leakage Air (Q) m3/sec = 0.266968165

    Leakage Air (Q) CFM / Floor 565.3443499 CFM

    Case -2

    When Fire Floor Door open

    Area of the Door 3.125 Sq.Mt

    Area of leakge through Door 33.625 Sq.ft

    Air Velocity 100 FPM

    Q =Leakage Air Per Floor 3362.5 CFM

    No of Doors open at the time of Fire 1 Nos

    (Only Fire Floor Door)

    Req Air for pressurisation when door open 3362.5 CFM

    in Fire Floor

    No of Doors closed at the time of Fire 47

    Req Air for pressurisation when door closed 26571.184 CFM

    Floors

    Total Fan capacity Required for Pressurising 29933.684 CFM

    the whole staircase

    STAIRCASE PRESSURISATION FOR ENNOVA PROJECT