staircase pressurisation calculation
TRANSCRIPT
-
7/30/2019 Staircase Pressurisation Calculation
1/1
DESCRIPTION
No of Floors 48 Nos
Assuming Gap Between Door and Floor 6 mm
Height of the Door 2500 mm
Length of the Door 1250 mmNo of Doors per Floor 1 Nos
AREA OF LEAKAGE
Area of Leakage (Sq.Mt)= Door Perimeter (mm) x Gap (mm)x 10^-6
Door Perimeter = 7500 mm
Area of leakage 0.045 Sq.Mt
Case -1
When doors Closed
Q = Leakage Air (m3/sec) = 0.839 *Area of Leakage * Sq.root of Pressure Diff
Pressure Difference (Pa) = 50 (Bldg Ht is more than 100 Mt)
Leakage Air (Q) m3/sec = 0.266968165
Leakage Air (Q) CFM / Floor 565.3443499 CFM
Case -2
When Fire Floor Door open
Area of the Door 3.125 Sq.Mt
Area of leakge through Door 33.625 Sq.ft
Air Velocity 100 FPM
Q =Leakage Air Per Floor 3362.5 CFM
No of Doors open at the time of Fire 1 Nos
(Only Fire Floor Door)
Req Air for pressurisation when door open 3362.5 CFM
in Fire Floor
No of Doors closed at the time of Fire 47
Req Air for pressurisation when door closed 26571.184 CFM
Floors
Total Fan capacity Required for Pressurising 29933.684 CFM
the whole staircase
STAIRCASE PRESSURISATION FOR ENNOVA PROJECT