What is a fire ?
• A fire is a chemical process out of
control where flammable material
supported by oxygen decompose to
combustion gases and ashes during
heat development
![Page 3: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/3.jpg)
Fire triangle
• The Fire triangle illustrate the three ingredients needed for a fire
![Page 4: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/4.jpg)
SUBLIMATION
HEAT
SOLID
VAPORIZATION
HEAT
MELTING LIQUID
VAPOUR
HEAT
GAS
OXYGEN
EMBER
HEAT SMOKE/GASSES
ASHES
FIRE
FLAMES
OXYGEN
![Page 5: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/5.jpg)
Fire Class NFPA ISO
A Ordinary combustible A
B Flammable liquids B
- Gasses C
C Dry electrical equipment -
D Metals D
![Page 6: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/6.jpg)
Stages of A - Fire
Application: Ordinary combustibles
Ignition: Flame/Heat
Ignition Smoke Flame Heat
Fire build up Time - Hours
![Page 7: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/7.jpg)
Stages of B - FireApplication: Flammable liquids
Ignition: Flame/Spark/Heat
Ignition Flame Heat Smoke
Fire build up Time - Seconds to minutes
![Page 8: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/8.jpg)
Stages of C - Fire (NFPA)
Application: Telecom, Computers i.e.
Ignition: Overheated componentsIgnition Smoke Flame Heat
Fire build up Time - Hours
![Page 9: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/9.jpg)
Stages of C - Fire (NFPA)
Application: Electrical installation
Ignition: Overheated components/Short circuit
Ignition Smoke Flame Heat
Fire build up Time - Minutes to hour
![Page 10: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/10.jpg)
Stages of C - Fire (NFPA)
Application: High power electricity
Ignition: Short circuit/Overheated equipment
Ignition Flame Heat Smoke
Fire build up Time - Seconds to minutes
![Page 11: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/11.jpg)
Stages of A-B-C - Fire (NFPA)
Application: Process industry
Ignition: Flame/Spark/Heat/Short circuit
Ignition Flame Heat Smoke
Fire build up Time - Minutes
![Page 12: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/12.jpg)
Fire Detection
• Heat Fixed - Rate of rise - cable
• Smoke Optical - Ionisation
• HSSD Laser based aspiration
• Beam Sender - Receiver
• Flame UV - IR
![Page 13: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/13.jpg)
Controls
•Conventional Loop identification•Addressable Item identification•Release Double knock
- 2 x Loops- 2 x Addresses- 1 x Loop + 1 x HSSD- 1 x Address +1 x HSSD- Single knock
![Page 14: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/14.jpg)
Extinguishants• Water
• Foam
• Inert Gas
(e.g. Argonite)
• Carbon Dioxide
• Powder
• Halocarbon
![Page 15: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/15.jpg)
Water as Extinguishants
• Water Mist / Fog– Flammable liquids
– Spray fires
– Cooling
– Effective on high Temperature fire
– Local application
– Not suitable for telecommunications,
computer, control rooms, etc
![Page 16: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/16.jpg)
Foam as Extinguishants
• Low expansion– Liquid pool fires
• Medium expansion– Liquid pool fires
• High expansion– Total flooding– Risk of suffocation– Very poor visibility
![Page 17: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/17.jpg)
Argonite as Extinguishants
• Total flooding• Non toxic
• Change O2 level
• No residues • No ozone
depletion• No global warming• Recommended for
occupied area
![Page 18: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/18.jpg)
CO2 as Extinguishants
• Total flooding• Local application• Change of O2 level• “Toxic”• “No residues” • No ozone depletion• Global Warming Potential of 1• Not recommended for occupied area
![Page 19: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/19.jpg)
Powder as Extinguishants
• Flammable liquids
• Spray fires
• Local application
• Stop combustion
• Chemical toxic
• Not clean
• Not recommended for occupied area
![Page 20: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/20.jpg)
FM200 as Extinguishants
• Total flooding• Chemical reaction• Potentially toxic• Chemical residue• No ozone depletion• Global warming potential 2900• Atmospheric lifetime 37 years• Acceptable for occupied area
![Page 21: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/21.jpg)
Survey of Fire ClassClass Materials Primary
ExtinguishantSecondaryExtinguishant
Applications
A Fire in ordinaryCombustionmaterial(Wood, paper, etc.)
Water Powder,Argonite, CO2,Foam, AquaSafe
FabricationIndustry, Stocks,Offices
B Fire in flammableliquids
Foam, AquaSafe Powder,Argonite, CO2,
PetrochemicalIndustry, Stocks
B Fire in flammablegases
Powder,AquaSafe
Argonite, CO2, Natural gasManufacturers,Stocks, GasStations
C Fire in electricalcunductioninstallation
Argonite, CO2 Water Computer rooms,Electrical board,Board room,Archive
D Metal fires Dry sand,Powder
Machine Industry
![Page 22: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/22.jpg)
Selecting Fire Detection
• Time of detection
• Type of combustion
• Adaption to application
• Avoid nuisance alarms
• Response / Activity
• Authorities
![Page 23: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/23.jpg)
Time of Detection
• Alarm level– Smoke– Flame– Heat
• Value of application– Stop not accepted– Reestablishment– Insurance policy
Flame Heat Smoke
![Page 24: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/24.jpg)
Type of Combustion
• Smoke level
• Flame damage
• Heat damage
![Page 25: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/25.jpg)
Adaption to Application
• Process
• Employee habit
• Surrounding
![Page 26: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/26.jpg)
Avoid Nuisance Alarms
• Detection principle
• Installation principle
• System training
• Update employees
![Page 27: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/27.jpg)
Response / Activitity
• Fire instruction plan
• Designated persons
• Training
• Drill
![Page 28: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/28.jpg)
Authorities
• Standards
• Approvals
• Approving bodies
• Fire brigade
![Page 29: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/29.jpg)
Selecting Fire Suppression
• Fire fighting effectiveness
• Discharge damage/effect on equipment
• Installation issues
• Hazards for occupants
• Environmental acceptability
![Page 30: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/30.jpg)
Fire Fighting Effectiveness
• Speed of fire suppression
• Suitability for the fire hazard
• Ability to permeate
• Post-fire hold time
• Risk of re-ignition
![Page 31: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/31.jpg)
Discharge Damage/Effect on Equipment
• Clean up
• Water damage
• Decomposition products and corrosion
• Condensation
• Thermal shock
![Page 32: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/32.jpg)
Installation Issues
• Floor space/weight
• Pipework
• Ease of maintenance
• Refill cost
• Availability of extinguishant
![Page 33: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/33.jpg)
Hazards for Occupants
• Toxicity
• Visibility
• Inhalation
• Safety with live electrical equipment
• Thermal decomposition products
![Page 34: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/34.jpg)
Environmental Acceptability
• Ozone Depletion
• Global Warming
• Atmospheric Lifetime
![Page 35: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/35.jpg)
www.ginge-kerr.dk
www.argonite.com
![Page 36: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/36.jpg)
www.dti.gov.uk/access/ozone.htm
http://ctan.unsw.edu.au/pub/archive/hc/news/wpafb/humanhal.pdf
References
![Page 37: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/37.jpg)
References
www.epa.gov/ozone/snap/fire/lists/
flood.html
www.Harc.org
![Page 38: Stages of Fire Detections and Extinguishants From Ginge-Kerr Danmark A/s & BMTT Corporation S/B (www. ginge-kerr.com)](https://reader030.vdocuments.us/reader030/viewer/2022033103/56649cea5503460f949b59c8/html5/thumbnails/38.jpg)
References
www.mst.dk-
choose english version
then choose publication
and then choose point 4
publication database in all data
in - including keywords write 301
in Danish EPA publication series -
choose