EXIST AIR CARGO BUILDING SITE EXIST WAREHOUSE AND ADMIN OFFICES TOTAL BUILDING PLUMBING FIXTURE CALCULATION IBC 2009 (Table 2902.1) 49 Total Building Occupants (25 M,24 F) Water Closets (1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50) Lavatories (1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80) Drinking Fountians (1 per 100) Service Sink Male Female Male Female Fixtures Required 1 1 1 1 1 1 Fixtures Provided 1 1 1 1 1 1 DRAWN BY: CHECKED BY: PROJECT NUMBER DATE DWG NO. SHEET TITLE SEAL PROJECT NAME Architecture Planning Interior Design 1500 Union Avenue Memphis, TN 38104 Tel. 901-278-6868 www.anfa.com PROJECT STATUS This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants. All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA. Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced. MEMPHIS INTERNATIONAL AIRPORT 2491 WINCHESTER RD. SUITE 113 MEMPHIS, TENNESSEE 38116-3856 APPROVED BY: SCALE MSCAA NO. G000 COVER SHEET BC DG STAFF SERVICES WAREHOUSE TEMPORARY 14053.016 10/31/16 ISSUED FOR BIDS DG ARCHITECT ANF ARCHITECTS, INC. 2941 WINCHESTERROAD, SUITE 113, MEMPHIS, TN 38116 STAFF SERVICES WAREHOUSE TEMPORARY MEMPHIS - SHELBY COUNTY AIRPORT AUTHORITY INNOVATIVE ENGINEERING SERVICES, LLC MECHANICAL/ ELECTRICAL/ PLUMBING DRAWING LIST G000 COVER SHEET G001 LIFE SAFETY A100 FENCING AND GATE DETAILS A201 FIRST FLOOR PLAN A401 WALL, CANOPY, SITE DETAILS A402 MILLWORK DETAILS, REFLECTED CEILING PLAN A501 ENLARGED PLANS AND INTERIOR ELEVATIONS M1.0 HVAC DETAILS, LEGEND, NOTES & SCHEDULES M1.1 HVAC OVERALL WAREHOUSE FLOOR PLAN M1.2 HVAC A/C WAREHOUSE FLOOR PLAN P1.0 PLUMBING GENERAL NOTES, LEGEND & SCHEDULE P1.1 PLUMBING FLOOR PLAN P1.2 PLUMBING ENLARGED FLOOR PLAN E1.0 ELECTRICAL DETAILS, LEGEND & NOTES E1.1 ELECTRICAL OVERALL FLOOR PLAN E1.2 ELECTRICAL WAREHOUSE ENLARGED LIGHTING PLAN E2.0 ELECTRICAL RISER AND PANEL SCHEDULES Grand total: 17 CODE ANALYSIS - INTERNATIONAL BUILDING CODE 2009 CODE COMMENTS BUILDING DATA CODE SECTION - TABLE JURISDICTION Memphis and Shelby County Construction Code Enforcement APPLICABLE CODES 2009 International Building Code with Local Amendments 2012 International Building Code with Structural Requirements 2012 International Existing Building Code 2009 ANSI A117.1 conjunction with Chapter 11 of 2009 IBC 2008 International Electrical Code 2012 Joint Electrical code 2009 International Mechanical Code 2009 International Gas Code with Local Amendments 2009 International Plumbing Code with Local Amendments 2010 ANSI/ASME Elevator Code - A17.1 2009 International Energy Conservation Code 2010 ADA Standards for Accessible Design OCCUPANCY CLASSIFICATION Business Group B Section 304 TYPE OF CONSTRUCTION Type II, B Table 602.2 Protected or Unprotected Protected Sprinkled or Unsprinkled Sprinkled ACTUAL BUILDING COMPONENTS Area (Gross) Offices 1,140 SF Area (Gross) AC Warehouse 3.520 SF Area (Gross) Warehouse 14,080 SF OCCUPANT LOAD Offices 14 Table 1004.1.1 AC Warehouse 7 Table 1004.1.1 Warehouse 28 Table 1004.1.1 EXITS Maximum Travel Distance 300'-0" Table 1016.1 Exit Capacity for Level Travel 0.20" per person Section 1005.1 Minimum Clear Door Width 32" Section 1008.1.1 Minimum Corridor Width 44" Section 1018.2 Maximum Dead End Corridor 20' - 0" Section 1018.4 REQUIRED RATINGS Occupancy Separation N/A Bearing Walls - Interior N/A Non-Bearing Walls and Partitions - Interior 0 Hour Table 601 Interior Finishes Class B - Corridors, Class C - Rooms and Enclosed Spaces Table 803.9 FIRE PROTECTION Fire Alarm Required Section 907 Standpipe Class I (Existing) Section 905 Emergency Lighting Required Section 1006 Emergency Power Required for corridors and exit enclosures Section 1006.3 Fire Extinguishers Required Section 906.1 HANDICAPPED ELEMENTS Hardware Lever handles throughout Toilet Components Minimum of one per restroom ADAGG Section 213.3.1 N.T.S. 1 VICINITY MAP 14-1379-16-01 REVISIONS NO. DESCRIPTION DATE BY RELOCATION MSCAA PROJECT #: 14-1379-16-01

Upload: nguyenkiet

Post on 23-Feb-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

EXIST AIR CARGOBUILDING SITE

EXIST WAREHOUSEAND ADMIN OFFICES

TOTAL BUILDING PLUMBING FIXTURE CALCULATION IBC 2009 (Table 2902.1)

49 Total Building Occupants (25M,24 F)

Water Closets (1 per 25 for the first50 and 1 per 50 for the remainder

exceeding 50)

Lavatories (1 per 40 for the first80 and 1 per 80 for the

remainder exceeding 80)Drinking

Fountians(1 per 100)

ServiceSinkMale Female Male Female

Fixtures Required 1 1 1 1 1 1Fixtures Provided 1 1 1 1 1 1

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

G000

COVER SHEET

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

ARCHITECT ANF ARCHITECTS, INC.

2941 WINCHESTERROAD, SUITE 113, MEMPHIS, TN 38116

STAFF SERVICES WAREHOUSE TEMPORARYMEMPHIS - SHELBY COUNTY AIRPORT AUTHORITY

INNOVATIVE ENGINEERING SERVICES, LLCMECHANICAL/ELECTRICAL/PLUMBING

DRAWING LISTG000 COVER SHEETG001 LIFE SAFETY

A100 FENCING AND GATE DETAILSA201 FIRST FLOOR PLANA401 WALL, CANOPY, SITE DETAILSA402 MILLWORK DETAILS, REFLECTED CEILING PLANA501 ENLARGED PLANS AND INTERIOR ELEVATIONS

M1.0 HVAC DETAILS, LEGEND, NOTES & SCHEDULESM1.1 HVAC OVERALL WAREHOUSE FLOOR PLANM1.2 HVAC A/C WAREHOUSE FLOOR PLAN

P1.0 PLUMBING GENERAL NOTES, LEGEND & SCHEDULEP1.1 PLUMBING FLOOR PLANP1.2 PLUMBING ENLARGED FLOOR PLAN

E1.0 ELECTRICAL DETAILS, LEGEND & NOTESE1.1 ELECTRICAL OVERALL FLOOR PLANE1.2 ELECTRICAL WAREHOUSE ENLARGED LIGHTING PLANE2.0 ELECTRICAL RISER AND PANEL SCHEDULESGrand total: 17

CODE ANALYSIS - INTERNATIONAL BUILDING CODE 2009

CODE COMMENTS BUILDING DATACODE SECTION

- TABLE

JURISDICTIONMemphis and Shelby County Construction Code Enforcement

APPLICABLE CODES2009 International Building Code with Local Amendments2012 International Building Code with Structural Requirements2012 International Existing Building Code2009 ANSI A117.1 conjunction with Chapter 11 of 2009 IBC2008 International Electrical Code2012 Joint Electrical code2009 International Mechanical Code2009 International Gas Code with Local Amendments2009 International Plumbing Code with Local Amendments2010 ANSI/ASME Elevator Code - A17.12009 International Energy Conservation Code2010 ADA Standards for Accessible Design

OCCUPANCY CLASSIFICATIONBusiness Group B Section 304

TYPE OF CONSTRUCTIONType II, B Table 602.2Protected or Unprotected ProtectedSprinkled or Unsprinkled Sprinkled

ACTUAL BUILDING COMPONENTSArea (Gross) Offices 1,140 SFArea (Gross) AC Warehouse 3.520 SFArea (Gross) Warehouse 14,080 SF

OCCUPANT LOADOffices 14 Table 1004.1.1AC Warehouse 7 Table 1004.1.1Warehouse 28 Table 1004.1.1

EXITSMaximum Travel Distance 300'-0" Table 1016.1Exit Capacity for Level Travel 0.20" per person Section 1005.1Minimum Clear Door Width 32" Section 1008.1.1Minimum Corridor Width 44" Section 1018.2Maximum Dead End Corridor 20' - 0" Section 1018.4

REQUIRED RATINGSOccupancy Separation N/ABearing Walls - Interior N/ANon-Bearing Walls and Partitions - Interior 0 Hour Table 601Interior Finishes Class B - Corridors, Class C -

Rooms and Enclosed SpacesTable 803.9

FIRE PROTECTIONFire Alarm Required Section 907Standpipe Class I (Existing) Section 905Emergency Lighting Required Section 1006Emergency Power Required for corridors and exit

enclosuresSection 1006.3

Fire Extinguishers Required Section 906.1

HANDICAPPED ELEMENTSHardware Lever handles throughoutToilet Components Minimum of one per restroom ADAGG Section 213.3.1

N.T.S.1 VICINITY MAP

14-1379-16-01

REVISIONSNO. DESCRIPTION DATE BY

RELOCATION MSCAA PROJECT #: 14-1379-16-01

UP

FE-1

A/CWAREHOUSE

WAREHOUSE

LUGGAGECARTS

EYEWASH

DF

BATTERYCHARGER

HAND TOOLS

EXIST 8" SAN SEWERAPPROX 7' DEEP

EXIST SAN MH

COUNTER WITH2 COMPUTERS

80' -

0"

HVAC UNIT,SEE MECH.

KEEP THISDOOR OPEN

AC WAREHOUSE*STORAGE S-2 OCCUPANCY*GROSS AREA = 3,520 SF*500 SF/OCCUPANT = 7 TOTAL OCCUPANTS*2 EXITS = 4 OCCUPANTS/EXIT

WAREHOUSE*STORAGE S-2 OCCUPANCY*GROSS AREA = 14,020 SF*500 SF/OCCUPANT = 28 TOTAL OCCUPANTS*2 EXITS = 14 OCCUPANTS/EXIT

OFFICES*BUSINESS OCCUPANCY*GROSS AREA = 1,440 SF*100 SF/OCCUPANT = 15 TOTAL OCCUPANTS*2 EXITS = 8 OCCUPANTS/EXIT

PRE-ENGINEEREDMETAL CANOPY

OFFICES

Occ x =Required

( Provided)

8 0.20"1.6"

3' - 0"( 34" Provided )

FE

Occ x =Required

( Provided)

8 0.20"1.6"

3' - 0"( 34" Provided )

Occ x =Required

( Provided)

14 0.20"2.8"

3' - 0"( 34" Provided )

Occ x =Required

( Provided)

14 0.20"2.8"

3' - 0"

Occ x =Required

( Provided)

14 0.20"0.8"

3' - 0"( 34" Provided )( 34" Provided )

FE FE

FE

MAX TRAVEL DISTANCE = 101' -1"

MAX

TR

AVEL

DIS

TAN

CE

= 57

' -4"

LIFE SAFETY LEGEND

REQUIREDWIDTH PEROCCUPANT

NUMBER OFOCCUPANTS

LIFE SAFETY DOOR TAG

Occ x =Required

( Provided)

150 0.20"30.00"3' - 0" PROVIDED

WIDTH

MINIMUMWIDTH

GREATEST TRAVEL DISTANCEEGRESS PATH

BRACKET-MOUNTEDFIRE EXTINGUISHER

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

G001

LIFE SAFETY

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

1/16" = 1'-0"1 FIRST FLOOR PLAN - LIFE SAFETY 14-1379-16-01

REVISIONSNO. DESCRIPTION DATE BY

95' -

6" +

/-

31' -

6" +/-

92' - 0" +/-

148' - 6" +/-21' - 6

" +/-

190' - 0" +/-

6' -0

" FAB

RIC

HEI

GH

T

EXTENSION ARM W/ 3STRANDS OF ZINCCOATED BARB WIRE

LINE POST @ 10' O.C.MAX 4 - 1/2" DIAM. X 33/4" WEDGE ANCHORS

8" X 8" X 1/2" THK PASEPLATE, 1" GROUT BED

EXIST CONC. PAVING

FENCE BASE @ CONC. PAVING

SECURITY FENCE ELEVATION

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

A100

FENCING AND GATEDETAILS

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

1/32" = 1'-0"1 EXISTING WAREHOUSE AND ADMIN OFFICES NEW FENCE PLAN

REVISIONSNO. DESCRIPTION DATE BY

N.T.S.2 FENCE DETAILS14-1379-16-01

UP

A/CWAREHOUSE

WAREHOUSE

LUGGAGECARTS

EYEWASH

DF

BATTERYCHARGER HAND TOOLS

EXIST 8" SAN SEWERAPPROX 7' DEEP

EXIST SAN MH

COUNTER WITH2 COMPUTERS

175' - 4 3/4" 44' - 0"

80' -

0"

60' - 0" 83' - 2"

23' -

6"

15' -

2" HVAC UNIT,

SEE MECH.

KEEP THISDOOR OPEN

PRE-ENGINEEREDMETAL CANOPY

OFFICES

1A401

2A401

A5011

11' -

6"

NOTES:

1. CONTRACTOR SHALL EMPLOY A LICENSED & BONDED CLEANINGCOMPANY TO THOROUGHLY CLEAN THE INSIDE & OUTSIDE OF THISSPACE PRIOR TO MOVING AND SHELVING OR EQUIPMENT.

2. MSCAA WILL BE RESPONSIBLE FOR REMOVING INVENTORY FROMSHELVING BEING RELOCATED AND INSTALLED BY THE CONTRACTOR.

3. THE FOLLOWING ITEMS RELOCATED TO THE SITE BY OTHERSREQUIRE ELECTRICAL CONNECTS PROVIDED BY THE CONTRACTORVERIFY ELECTRICAL REQUIREMENTS. 2 - RESIDENTIALREFRIGERATORS, 1 - COMMERCIAL 2 DOOR FREEZER AND 1 BATTERYCHARGER.

4. BOLT WAREHOUSE SHELVING TO FLOOR AND SEISMIC BRACE.

5. RE-PAINT EXISTING GYP. BD. WALLS WITH 8" HIGH PLYWOODWAINSCOT ON COLUMN LINES 5, 9, AND 10.

6. CONTRACTOR SHALL PROVIDE ALL PERMITS, SEISMIC CALCULATIONSAND SIGNED AND SEALED DRAWINGS REQUIRED FOR INSTALLATIONOF WAREHOUSE SHELVING.

DOORS:

1. CUT OPENING IN EXISTING 1 HR RATIO GYP. BD. AND METAL STUDWALL AND INSTALL A PAIR OF 3' X 7' DOUBLE ACTING, IMPACTDOORS EQUAL TO CHASE-DURUS DURULITE EXTRA HEAVY DUTYGASKTED INDUSTRIAL DOORS W/ 20" X 22" DOUBLE PANE VISIONPANELS AND 24" HIGH BUMPERS.

A4021

5

A

B

C

D

E

6 7 8 9 10 11

B E

F

E E

B

B

B

D

AA FREEZER

1

1

C C C C C C C

CCCCCCC

C C

C

C

C

C

C

C

C

C

LEGENDFURNISHED & INSTALLED BY CONTRACTOR

WAREHOUSE SHELVING - HUSKY WIREWAY IU24420963 - 42" X 96" WELDED UPRIGHT FRAME6 - 96" STEEL TEARDROP RACK BEAM - ORANGE IBX423096G8 - 46" X 42" WIRE MESH DECKING 2500 LB LOAD CAPACITYNASHVILLE WIRE D4246AA3AIP

WAREHOUSE SHELVING - HUSKY WIREWAY41 - 42" X 144" WELDED UPRIGHT FRAME IU24420144136 - 96" STEEL TEARDROP RACK BEAM - ORANGE IBX423096G136 - 46" X 42" WIRE MESH DECKING 2500 LB LOAD CAPACITYNASHVILLE WIRE D4246AA3AIP

STEEL SHELVING - LYON - DOVE GRAY48 - 36" X 24" X 84" STARTER UNITS WITH 6 SHELVES DD82625212 - 36" X 24" X 84" ADD ON LIGHTS W/ 6 SHELVES DD 8262

A

B

SHELVING, APPLIANCE OR STORAGE UNITRELOCATED TO SITE BY OTHERS

WAREHOUSE SHELVING 3' -6" x 8' -0" x 96" HI. WITH 2SHELVES RELOCATED TO SITE BY CONTRACTORD

E

F

WAREHOUSE SHELVING 3' -6" x 8' -0" x 144" HI. WITH2 SHELVES RELOCATED TO SITE BY CONTRACTOR

HEAVY DUTY SHELVING 3' -6" x 12' -0" x 144" HI. WITH3 SHELVES RELOCATED TO SITE BY CONTRACTORC

1/16" = 1'-0"1 FIRST FLOOR PLAN

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

A201

FIRST FLOOR PLAN

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

14-1379-16-01

REVISIONSNO. DESCRIPTION DATE BY

12' -

0"

EXIST DOCKLEVELER

EXIST PIPEBOLLARD

EXIST OVERHEADSECTIONAL DOOR TOREMAIN CLOSED

EXIST METALCANOPY

EXIST ROOF

EXIST CONCSLAB

4" VINYL BASE

1' - 8"

3 1/2" BATTINSULATION

3 5/8" MTL STUDS@ 16" O.C.

5/8" GYP BDPAINTED

SUSP ACOUSTICCLG

6" BATTINSULATION

BRACE TOP OFWALL @ 4' - 0" MAX

EXIST SECTIONALDOOR TRACK

EXIST PRE CASTCONC PANEL

A

INSULATEUNDER SIDE OFDOCK LEVELER

EXIST. PRE CASTCONC. PANEL

SECTIONAL OVERHEADDOOR IN OPEN POSITION

FILL IN DOOR OPENINGW/ SYNTHETIC STUCCOOVER 6" METAL STUDS

EXIST. PIPE BOLLARDS

6" BATT INSULATION

ACOUSTIC CEILING

5/8" GYP. BD

3 5/8" MTL STUDS@ 16" O.C.

BATT INSULATION

4" VINYL BASE

EXIST. CONCSLAB

14' -

0"

12' -

0"

E

NEW MODULARBUILDING

EXISTINGBUILDING

14' - 0"

12' -

0"

2' -

0"

STEEL COLUMNSAND BEAMS

18" DIAM.

3000 PSICONC.

CORE DRILL EXIST. 12"CONC PAVEMEN TOINSTALL FOOTINGS

STANDING SEAMROOF, METAL DECK

NOTE:

PRE-ENGINEERED STANDING SEAM METAL CANOPYSHALL BE FURNINSHED AND ISNTALLED BY PARASOL AWNINGS, LLC; 4834 HICKORY HILLS ROAD;MEMPHIS, TN 38141 (901) 368-4477 OR APPROVEDEQUAL. COLOR TO BE SELECTED FROMMANUFACTURER'S STANDARD COLORS.

STEPS AND BUILDINGBY MODULAR BLDG.MFF

CONTRACTOR TOFLASH ROOF TOBUILDINGS

6"

1' -

0"

9 1/2"

LUBRICATE ONEEND OF DOWEL

SOLID STEEL DOWEL 1"DIAMETER 19" LENGTH,12" SPACING

EXISTINGNEW

1' -

0"8"

6"

DENSELY COMPACTED SUBGRADE

NOTE:REINFORCING FABRIC SHALL BE PROVIDED IN SHEETS.

W6 X W6 - 10" X 10" ONLY INSLABS INDICATED IN CIVIL

CLR

.4"

1' -

0"8"

6"

PORTLAND CEMENT CONCRETE COURSEWITH 28 DAY MODULOUS OF RUPTUREVALUE OF 650 PSI (MIN)

CEMENT TREATED AGGREGATE BASE(CTB) COURSE - P304

EXISTING SOIL CEMENT BASE COURSE(TO 36" NORTH OF EXISTING EDGE ONLY)

INITIAL CUT

1" NOMINAL WIDTHPREFORMEDCOMPRESSION SEALANT t/4

+/-

1/4"

TO B

EC

ON

STR

UC

TED

BY S

AWIN

G

5/8" +/- 3/16"1/4" BEVEL BYSAWCUTTING

NOTE:DEPTH AND WIDTH OF RESERVOR SHALL BE IN ACCORDANCEWITH MANUFACTURER'S RECOMMENDATIONS

15' - 0"

REMOVE AND REPLACESECTION OF CONC. PAVING TOMAKE SEWER CONECTION

W6 X W6 - 10-" X 10"

4" C

LR.

1' -

0"

EXIST 8" SANSEWER DRAIN

7' -

0" +

/-

EXISTING PRE-CASTWALL PANEL

EXIST STL CHANEL

METAL DRIP FLASHING

SMOOTH FINISHSYNTHETIC STUCCOON 5/8" CEMENT BOARD

WATER RESISTIVEBARRIER

5/8" GYP SHEATHING

4" X 20 GA METALSTUDS @ 16" O.C.

SEALANT

SMOOTH FINISH ONSYN 5.8" CEMENTBOARD

EXIST 6" DIAM. PIPEBOLLARD

R-13 BATT INSULATION

5/8" GYP BD, PAINTED

BRACE TOP OFWALL @ 4'-0" O.C.

HEAD

JAMB

HEAD

EXIST 5/8" GYP BD

EXIST 6" METALSTUDS

METAL STUD TRACK

PLYWOOD SHIM

3/8" BENT PLATEFRAME

JAMB

EXIST PLYWOODWAINSCOT

EXIST 5/8" GYP BD

DOUBLE STUDS

PLYWOOD SHIM

3/8" BENT PLATEFRAME

LOWER HINGE

DOUBLE ACTINGDOOR

4"

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

A401

WALL, CANOPY,SITE DETAILS

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

1/4" = 1'-0"2 NORTH SECTION

1/4" = 1'-0"1 SOUTH SECTION

1/4" = 1'-0"3 CANOPY

1" = 1'-0"4 DOWELED JOINT

1" = 1'-0"5 PCC SECTION - AIRSIDE

3" = 1'-0"6 JOINT DETAIL

3/8" = 1'-0"7 SAN SEWER DETAIL

1 1/2" = 1'-0"8 HEAD AND JAMB DETAILS

REVISIONSNO. DESCRIPTION DATE BY

14-1379-16-01

14' - 0"

3' -

0"

PLAN

14' - 0"

3' -

6"

FRONT ELEVATION

13' - 10"

3' -

6"

SIDE ELEVATION SECTION

3' - 0"

6"

3' -

6"

1 1/

2"

WILSONART, OILEDSOAPSTONE, 4882-38

PULLS2' - 0"

DRAWER

ADJUSTABLESHELF

LAMINART #240-T,GRIS STREAMLINE

FLEXCO,03CHARCOAL

MELAMINEINTERIOR

EXIST. FINISHFLOOR

FLEXCO,03CHARCOAL

5/8" GYP BD ON 35/8" MTL STUDS @16" O.C.

3' -

6"

3' - 0"

FLEXCO,03CHARCOAL

PAINTED GYP BD

WILSONART, OILEDSOAPSTONE, 4882-38

BACK ELEVATION

OPEN OPEN

WILSONART, OILEDSOAPSTONE, 4882-38

LAMINART #240-T, GRIS STREAMLINE

2" DIAMETER GROMMETS

NOTE:

PAINTED GYP BD TO BE SUBMITTEDFOR APPROVAL BY MSCAA, TYP.

NOTE:

CEILING TILE TO BEARMSTRONG 2' X 4', CORTEGASECOND LOOK (2765)

CEILING GRID TO BEARMSTRONG PRELUDEMAINS: 73004' T'S: XL73482' T'S: XL7328WALL MOLD: 7800

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

A402

MILLWORKDETAILS,

REFLECTEDCEILING PLAN

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

3/4" = 1'-0"1 MILLWORK DETAILS

1/8" = 1'-0"2 A/C WAREHOUSE REFLECTED CEILING

REVISIONSNO. DESCRIPTION DATE BY

14-1379-16-01

E

HVAC UNIT,SEE MECH.PRE-ENGINEERED METAL

CANOPY

11' -

6"

24' - 0" +/-

STEPS & RAMPS BYMODULAR BUILDINGVENDOR

EXIST SAN SEWER MANHOLE EXIST 8" SEWER(APPROX 7' DEEP)

SAW CUT, REMOVE, AND REPOUR12" THICK CONC. PAVEMENT ASNEEDED TO CONNECT MODULARBLDG DRAIN TO SEWER. SEEDETAILS ON SHEET A401

RAMP DOWN

DF

MOPSINK

10' -

9"

5' - 0" 10' - 0" 2" 7' - 3" 3' - 5" 2" 3' - 5" 7' - 3" 2" 9' - 0" 5' - 0"

2' - 8" 7' - 0" 2" 7' - 0" 2' - 8" 2" 8' - 0"

7' -

10"

FEREF

14' - 0"

15' -

2"

23' -

6"

NOTES:

1. CONTRACTOR SHALL LEASE AND INSTALL MODULAROFFICE BUILDING. AT THE END OF THE FIRST YEAR THELEASE WILL BE TURNED OVER TO MSCAA FOR A MINIMUMOF TWO ADDITIONAL YEARS. MSCAA SHALL BERESPONSIBLE FOR REMOVAL OF THE BUILDING.

2. MODULAR BUILDING SHALL MEET ALL STATE OFTENNESSEE BUILDING CODES. VENDOR SHALL PROVIDESHOP DRAWINGS SIGNED AND SEALED BY A DESIGNPROFESSIONAL REGISTERED IN THE STATE OFTENNESSEE.

3. CONTRACTOR SHALL PROVIDE SKIRT, SKIRT VENTILATION,AND ACCESS DOOR.

4. OFFICE CUBICLE TO BE LEASED WITH THE MODULARBUILDING.

5. REFRIGERATOR TO BE PROVIDED BY OWNER. INSTALLEDBY OTHERS.

6. TABLES, CHAIRS, BOOKCASES, FILE CABINETS, ETC. WILLBE INSTALLED BY OTHERS.

7. FREE STANDING , PRE-ENGINEERED METAL CANOPYINCLUDING ATTACHMENT TO EXISTING CONCRETEPAVEMENT, METAL ROOF, STEEL FRAMING, ROOF DRAINS,FASCIAS, AND ACCESSORIES SHALL BE FURNISHED BYMANUFACTURER EQUAL TO AUSTIN MOWHAWK MARQUE/OVERHEAD ENTRANCE CANOPY MANUFACTURER SHALLPROVIDE COMPLETE SHOP DRAWINGS SIGNED ANDSEALED BY A TENNESSEE REGISTERED ENGINEER.

8. FOR GSA APPROVED MODULAR BUILDING SUPPLIERCONTACT CORTNEY VIGLIETTI WITH WILLIAMS SCOTMAN5012 MALONE ROAD MEMPHIS, TN 38118.(OFFICE: 901-366-1433, CELL: 901-486-4605)

REF. FREEZER FREEZER REF.

THIS DOOR TO REMAIN OPENCONTRACTOR TO PROVIDEELECTRICAL FOR THESEAPPLIANCES. APPLIANCESWILL BE INSTALLED BYOTHERS.

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

A501

ENLARGED PLANSAND INTERIORELEVATIONS

BC

DG

STAFF SERVICESWAREHOUSETEMPORARY

14053.016

10/31/16

ISSUED FOR BIDS

DG

1/4" = 1'-0"1 FIRST FLOOR PLAN

REVISIONSNO. DESCRIPTION DATE BY

14-1379-16-01

TYPICAL CEILING DIFFUSER DETAIL

VD

MIN R/D = 10

R

SUPPLY DIFFUSER

PROVIDE INSULATEDBACKPAN

CEILING-REFER TOREFLECTED CEILINGPLANS FOR CEILINGTYPE AND DIFFUSERLOCATION

ROUND OR RECTANGULARDUCT AS SHOWN ON PLANS

INSULATED FLEXIBLE DUCT(6'-0" MAX LENGTH)

TRANSITIONAS REQUIRED

DUCT HANGER(TYP)

AIR FLOW

DUCT0002.rvt

AIR FLOW

MAIN DUCT

BRANCH

SPIN-IN FITTINGWITH DAMPERFOR ROUNDBRANCH DUCT12"Ø AND BELOW

MAN. VOLUME DAMPER(ALL RECTANGULARDUCT SIZES)

GENERAL PROJECT NOTES :

1. COORDINATE INSTALLATION OF DUCTWORK WITH OTHER DIVISIONS.2. ALL DUCTWORK ASSOCIATED WITH THE MECHANICAL SYSTEMS SHALL BE INSTALLED

AND SECURED PER APPLICABLE BUILDING CODES. PROVIDE ACCESS PANELS FOR ALLMECHANICAL EQUIPMENT INSTALLED ABOVE HARD CEILINGS OR IN FURRED CHASESREQUIRING ACCESS, SUCH AS VOLUME DAMPERS, PIPING VALVES, ETC.

3. MECHANICAL CONTRACTOR SHALL INSTALL VOLUME DAMPERS IN AIR DUCTS TO NEWSUPPLY, RETURN, AND EXHAUST GRILLES, AS APPLICABLE. VOLUME DAMPERS SHALL BELOCATED FOR ACCESS FROM LAY-IN CEILINGS OR ACCESS DOORS.

4. THERMOSTAT HEIGHT SHALL BE 4'-0" ABOVE FINISHED FLOOR AND SHALL BE ALIGNEDWITH LIGHT SWITCH WHERE SHOWN AT THE SAME LOCATION.

5. MANUAL BALANCING DAMPERS SHALL BE LOCATED WHERE OPERATORS AREACCESSIBLE.

6. DUCT SIZES SHOWN ARE NET DIMENSIONS MEASURED FROM THE INSIDE (UNLESSOTHERWISE NOTED).

7. PROVIDE FLEXIBLE CONNECTIONS TO DUCTWORK AT ALL INDOOR UNITS, ASAPPLICABLE.

8. COORDINATE EXACT LOCATION OF ALL PIPING AND DUCT PENETRATIONS OF WALLSWITH STRUCTURAL BRACING.

9. WHERE PIPING IS ROUTED THROUGH EXTERIOR WALL OF BUILDING PROVIDE "LINKSEAL" AND SLEEVES FOR PENETRATION OF WALL.

10. DUCT LOCATIONS THROUGH MASONRY PARTITIONS AND BEARING WALLS MUST BECOORDINATED WITH OTHER OPENINGS AND WALL REINFORCING REQUIREMENTS SOTHAT STRENGTH OF WALL IS NOT IMPAIRED.

11. EVERY APPLIANCE SHALL BE LOCATED WITH RESPECT TO BUILDING CONSTRUCTIONAND OTHER EQUIPMENT SO AS TO PERMIT ACCESS AND SERVICE PER ALL THEREQUIREMENTS OF 2009 IMC INCLUDING, BUT NOT LIMITED TO, SECTIONS 303 AND 304.

12. EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE TERMS OFTHEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING, THEMANUFACTURER'S INSTALLATION INSTRUCTIONS, AND THE 2009 IMC. MANUFACTURER'SINSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB SITE AT THE TIME OFINSPECTION PER 2009 IMC, SECTION 304.1. WHERE CONFLICTS EXIST BETWEEN THEDRAWINGS, 2009 IMC, AND THE CONDITIONS OF THE LISTING OR THE MANUFACTURER'SINSTALLATION INSTRUCTIONS, THE PROVISIONS OF 2009 IMC SHALL APPLY. WHERE ACODE PROVISION IS LESS RESTRICTIVE THAN THE CONDITIONS OF THE LISTING OF THEEQUIPMENT OR APPLIANCE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, THECONDITIONS OF THE LISTING AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONSSHALL APPLY.

13. PERMITS SHALL BE APPLIED FOR BY A LICENSED MECHANICAL, GAS OR FIREPROTECTION CONTRACTOR.

14. PROTECTION OF HVAC SYSTEM DURING CONSTRUCTION: ALL HVAC EQUIPMENT SHALLBE PROTECTED FROM DUST AND OTHER PARTICULATE MATTER. ALL SITE AND/ORINSTALLED ABSORPTIVE MATERIALS SHALL BE PROTECTED FROM MOISTURE DAMAGE.ALL DUCT AND EQUIPMENT OPENINGS SHALL BE PROPERLY SEALED.

15. THE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL MECHANICAL LAYOUTS FORBIDDING PURPOSES ONLY. DRAWINGS ARE NOT SHOP DRAWINGS. THE ABOVECEILING SPACE IS LIMITED WITH MANY TRADES WORKING IN THE SAME AREA. WORKMUST BE COORDINATED IN DETAIL WITH OTHER TRADES AND EXISTING CONDITIONS TOAVOID CONFLICTS. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TOPREPARE DETAILED SHOP DRAWINGS, FIELD VERIFY ALL EXISTING CONDITIONS,CONFIRM SPACE ALLOCATIONS, AND COORDINATE WITH THE WORK OF OTHERTRADES. MINOR ADJUSTMENTS SHALL BE MADE TO NEW PIPE, DUCT, AND EQUIPMENTLOCATIONS AND SIZES TO MATCH ACTUAL FIELD CONDITIONS SUCH THAT COMPONENTSFIT ABOVE FINISHED CEILINGS IN THE AVAILABLE SPACE. FIELD VERIFY CONDITIONS ANDDIMENSIONS, AS NEEDED, PRIOR TO PREPARING SHOP DRAWINGS, ORDERINGEQUIPMENT, OR BEGINNING WORK. WHERE A CONFLICT WILL EXIST (FIT, FORM, ORFUNCTION), CONTRACTOR SHALL IMMEDIATELY NOTIFY DESIGN ENGINEER PRIOR TOPROCEEDING WITH WORK.

16. WHERE APPLIANCES ARE INSTALLED ABOVE A DROP CEILING AND HAVE THEIR LOWESTPOINT AT AN ELEVATION OF 10 FT. A.F.F. OR MORE, A WORK SURFACE WITH A NON-COMBUSTIBLE MATERIAL SHALL BE CONSTRUCTED ON THE SERVICE SIDE OF THEEQUIPMENT.

1-1/2" MIN TO 3" MAX INSTALLED.6" NOMINAL WITH MATERIAL TAUT

ALTERNATE POSITION OF BOLT

1" FLANGE AND HEM

BOLT ON 4" CENTERS

1"x1/8" BAND IRON

FLEXIBLEMATERIAL ASSPECIFIED

WASHER

FLANGEDCONNECTIONON FAN SIDE

SHEET METALAS SPECIFIEDFOR DUCTWORK

DUCT

1-1/2" POCKET SLIP

SHEET METAL ASSPECIFIED FORDUCTWORK

CONNECTION TO EQUIPMENT,INSTALL PER LOCAL CODES

UNION

GAS LINEFROMMAIN

6" DIRT LEG WITHREMOVABLE CAP

GASCOCK

12" LONG, S.S. BRAIDED HOSE,FLEX. CONN. EQUAL TO MASONMODEL CSAMN (CSA APPROVED)

T

#

FLEXIBLE DUCTWORK

W x H

MANUAL VOLUME DAMPER

RECTANGULAR DUCTW=WIDTH H=HEIGHT

90 DEGREE ELBOW WITH TURNINGVANES

CAPPED PIPE

NATURAL GAS PIPINGNG

NEW PLAN KEY NOTE

THERMOSTAT (48" A.F.F.)

FIRE DAMPER

#

X

X Ø ROUND DUCTX=DIAMETER

DESCRIPTIONSYMBOL

MECHANICAL EQUIPMENT TAGX=ABBREVIATION X=UNIT NUMBER

HVAC LEGEND

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

M1.0

HVAC DETAILS,LEGEND, NOTES &

SCHEDULES

JAG

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

JAG

N.T.S.1 SUPPLY DIFFUSER W/ FLEXIBLE DUCT

N.T.S.2 SUPPLY DUCT BRANCH DETAIL

1/8" = 1'-0"3 GENERAL PROJECT NOTES

N.T.S.4 FLEXIBLE RECT. DUCT CONNECTION

N.T.S.5 NATURAL GAS PIPE CONNECTION

1/8" = 1'-0"6 PROJECT LEGEND

PACKAGED DX UNIT SCHEDULE (GAS HEAT)

UNITMARK NO.

SUPPLY FANEAT °F,

DbEAT °F,

WbLAT °F,

DbLAT °F,

Wb

COOLING DATA @96.7°F AMBIENT HEATING DATA ELECTRICAL DATA (@

460/3Ø/60)IEER

(AHRI 360)EQUAL TO

MANUFACTURER MODEL NO.COND.DRAIN(I.P.S.)

WEIGHTW/CURB (LBS) REMARKS

CFM MIN. O.S.A.CFM

EXT.S.P. IN.

W.G.

SENSIBLEBTUH

TOTALBTUH TYPE INPUT

MBHOUTPUT

MBH MCA MOCP SUPPLY FANHP

GMU 1 6870 CFM 200 CFM 1 75.6 62.9 58.0 55.3 155,400 132,400 NG 300 240 31.8 40 7.5 17.5 DAIKIN APPLIED DPS015 1-1/4" 2,330 SINGLEZONE VAV

AIR DISTRIBUTION SCHEDULE

MARK FACE SIZE O.B.V.D. PRICEMODEL NO. REMARKS

A YesB No

NOTES:

1. EQUAL DEVICES BY NAILOR, TITUS, KRUEGER & METALAIRE ARE ACCEPTABLE.2. COORDINATE CEILING DEVICES WITH ARCHITECTURAL GRID AND LIGHTING.3. COORDINATE FINISH WITH ARCHITECT.

ASPD SUPPLY DIFFUSER24x24630 LOUVERED RETURN GRILLESEE PLANS

NOTES:

1. ENTERING AIR CONDITIONS BASED ON 96.7° DB / 77.8°F WB (OSA SUMMER) AND 10°F DB (OSA WINTER).2. PROVIDE WALL-MOUNTED THERMOSTAT WHERE SHOWN ON PLANS. THERMOSTAT SHALL BE 7-DAY PROGRAMMABLE WITH 5°F DEADBAND AND

SETBACK CONTROLS CAPABLE OF TEMPORARILY OPERATING THE SYSTEM DOWN TO 55°F (WINTER) OR UP TO 85°F (SUMMER).3. FURNISH WITH DRY BULB ECONOMIZER AND BAROMETRIC RELIEF.4. START-UP SHALL BE PROVIDED BY A FACTORY AUTHORIZED TECHNICIAN.5. FURNISH WITH CONDENSER COIL HAIL GUARDS, SMOKE DETECTOR IN SUPPLY/RETURN, AND SS HEAT EXCHANGER.6. PROVIDE 10-YR HEAT EXHANGER AND 5-YR COMPRESSOR WARRANTIES.7. FURNISH WITH SPACE HUMIDITY SENSOR AND HOT GAS REHEAT FOR HUMIDITY CONTROL. INSTALL SENSOR NEXT TO THERMOSTAT SHOWN ON PLANS.

REVISIONSNO. DESCRIPTION DATE BY

A/CWAREHOUSE

WAREHOUSET

GMU

1

M1.22

111

2 2 2 2 2 2 2 2

22221

2222

3 3 3 3

5 6 7 8 9 1110

A

B

C

D

E

4 4 4 4 4 4 4 4 4 44

NG

NG

NG

N.I.C.

N.I.C.

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

M1.1

HVAC OVERALLWAREHOUSEFLOOR PLAN

JAG

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

JAG

3/32" = 1'-0"1 WAREHOUSE OVERALL FLOOR PLAN

Keynote Legend

Key Value Keynote Text

1 LEAVE EXISTING ROOF-MOUNTEDEXHAUST FAN.

2 LEAVE EXISTING GAS-FIRED IR TUBEHEATER.

3 LEAVE EXISTING TUBE HEATER PIPES ANDTAILPIPE (TYP. OF ALL).

4 LEAVE EXISTING 48x48 STORM-PROOFLOUVER.

GENERAL NOTES:

1. REFERENCE SHEET M1.0 FOR HVAC DETAILS,LEGEND, NOTES & SCHEDULES.

REVISIONSNO. DESCRIPTION DATE BY

16"ø

26"x20" 30"x24" 36"x24"

CONCRETE PAD 6"OUTSIDE OF GMU-1;COORDINATE W/ARCHITECT.

TO GMU-1

36"X24" SUPPLY DUCTUP TO A.F.F. 16'-0"

REQUIREDCLEARANCELINES (TYP.)

12"øA570

12"øA575

12"øA570

12"øA570

12"øA575

12"øA575

12"øA575

12"øA570

12"øA570

12"øA575

12"øA 57012"øA 570

12"øA 575

30"x24"B6670

12"ø

12"ø

12"ø

12"ø

12"ø

16"ø

16"ø

16"ø

12"ø

12"ø

12"ø

12"ø

12"ø

12"ø

12"ø

12"ø

18"ø

1

2

2

1

1

9

10

A B C D E

3

T

1

4

4

4

4

NG

30"x24"

36"x24"

NGNG

NG

1"ø

1"ø1"ø

5 3/4"ø

N.I.C.

(300 CFH)

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

M1.2

HVAC A/CWAREHOUSEFLOOR PLAN

JAG

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

JAG

1/4" = 1'-0"1 A/C WAREHOUSE PLAN

Keynote Legend

Key Value Keynote Text

1 LEAVE EXISTING GAS-FIRED IR TUBEHEATER. DISCONNECT POWER.

2 LEAVE EXISTING TUBE HEATER PIPES ANDTAILPIPE (TYP. OF ALL).

3 LEAVE EXISTING ROOF-MOUNTEDEXHAUST FAN. DISCONNECT POWER.

4 LEAVE EXISTING 48x48 STORM-PROOFLOUVER. TEMPORARILY BLOCK OFFOPENING.

5 PRESSURE REGULATING VALVE. REDUCEFROM 2 PSI TO 7" W.C.

GENERAL NOTES:

1. REFERENCE SHEET M1.0 FOR HVAC DETAILS,LEGEND, NOTES & SCHEDULES.

REVISIONSNO. DESCRIPTION DATE BY

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of the

Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as a

work product shall be regarded as priveleged information, not to be

released to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes your

understanding of, and commitment to, providing adequate control of

the materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr., Suite 101

Bartlett, Tennessee 38134

901-379-0500

www.innovativees-llc.com

14-1379-16-01

1/16" = 1'-0"

P1.0

PLUMBING

GENERAL NOTES,

LEGEND, DETAILS

AND SCHEDULES

PTH

JEW

14053.16

JEW

REVISIONS

NO. DESCRIPTION DATE BY

10/31/16

LOCKING NUT

HANGER ROD

CLEVIS HANGER

SUPPORT NUT

PIPE

10'

8'

9'

7'

12'

15"

11'

MAX. ALLOWABLE SPACING

HANGER ROD SPACING

1"

5/8"

7/8"

3/4"

PIPE SIZE

4" AND 5"

6" THRU 8"

UP TO 2"

12"

1/2" DIA.

3/8" DIA.

ROD SIZE

HANGER ROD SCHEDULE

1-1/4"

1-1/2"

3" THRU 8"

10" & 12"

2-1/2"

PIPE SIZE

2"

PIPE

HANGER ROD

2 1/2" THRU 3"

INSULATION SHIELD,

12" LONG FOR PIPES

INSULATION 12" LONG

3" AND LARGER

HIGH DENSITY

CLEVIS HANGER

LOCKING NUT

SUPPORT NUT

INSULATION

PLUMBING/FIRE PROTECTION

PIPE HANGER INSTALLATION

NTS

1

STAFF SERVICES

WAREHOUSE

TEMPORARY

WAREHOUSE

PLUMBING ISOMETRIC PLAN

NTS

3

MODULAR TRAILER CONNECTION

PLUMBING ISOMETRIC PLAN

NTS

4

LOCATION OF SPRINKLER

HEAD IN CEILING TILE

NTS

2

A/C

WAREHOUSE

WAREHOUSE

1/16" = 1'-0"

1

PLUMBING FIRST FLOOR PLAN

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of the

Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as a

work product shall be regarded as priveleged information, not to be

released to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes your

understanding of, and commitment to, providing adequate control of

the materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr., Suite 101

Bartlett, Tennessee 38134

901-379-0500

www.innovativees-llc.com

1/16" = 1'-0"

P1.1

PLUMBING

FIRST FLOOR PLAN

PTH

JEW

STAFF SERVICES

WAREHOUSE

TEMPORARY

14053.16

JEW

REVISIONS

NO. DESCRIPTION DATE BY

14-1379-16-01

10/28/16

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of the

Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as a

work product shall be regarded as priveleged information, not to be

released to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes your

understanding of, and commitment to, providing adequate control of

the materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr., Suite 101

Bartlett, Tennessee 38134

901-379-0500

www.innovativees-llc.com

1/4" = 1'-0"

P1.2

PLUMBING

ENLARGED PLANS

PTH

JEW

STAFF SERVICE

WAREHOUSE

TEMPORARY

14053.16

JEW

1/4" = 1'-0"

1

PLUMBING ENLARGED MODULAR TRAILER PLAN

REVISIONS

NO. DESCRIPTION DATE BY

10/31/16

14-1319-16-01

MANUAL MOTOR STARTER SWITCHSINGLE-POLE, SINGLE-THROW (S.P.S.T.) WALL SWITCH

KEYED WALL SWITCH

SINGLE-POLE, DOUBLE-THROW (S.P.D.T.) WALL SWITCH

SINGLE RECEPTACLE IN WALL (NEMA 5-20R)DUPLEX RECEPTACLE IN WALL (NEMA 5-20R)

DUPLEX RECEPTACLE IN FLOOR (NEMA 5-20R)DUPLEX RECEPTACLE IN WALL, EMERGENCY CIRCUIT (NEMA 5-20R)

ELECTRIC METER

LIGHTING CONTACTOR

BASIC MATERIALS

LOW VOLTAGE WIRING RUN IN CONDUIT

JUNCTION BOX

PUSHBUTTON

THERMOSTAT

CIRCUIT BREAKER

PHOTOCELL

EQUIPMENT ELECTRICAL CONNECTION

DISCONNECT SWITCH (FUSED AS REQUIRED)

MOTOR CONNECTION

BRANCH CIRCUIT PANEL

DISTRIBUTION PANEL

SERVICE AND DISTRIBUTION

(SPECIFIED IN OTHER THAN DIV. 16)MOTOR CONTROLLER

(SPECIFIED IN OTHER THAN DIV. 16)EQUIPMENT NOT FURNISHED UNDER DIV. 16

COMBINATION MOTOR CONTROLLER & DISCONNECT SWITCH(SPECIFIED IN OTHER THAN DIV. 16)

AMMETER

SWITCHBOARD

TRANSFORMER

GENERATOR CONNECTION

INCANDESCENT OR FLUORESCENT EMERGENCY LIGHTING FIXT URE

FLUORESCENT LIGHTING FIXTURE - DUAL SWITCHED

(LETTER REFERENCES FIXTURE SCHEDULE)FLUORESCENT LIGHTING FIXTURE

FLUORESCENT EMERGENCY LIGHTING FIXTURE

(LETTER REFERENCES FIXTURE SCHEDULE)INCANDESCENT, FLUORESCENT OR H.I.D. LIGHTING FIXTURE

POLE MOUNTED LIGHTING FIXTURE

EXIT SIGN (FURNISH WITH DUAL FACES AND DIRECTIONAL ARROWS

EMERGENCY LIGHTING UNIT

LIGHTING

WHERE INDICATED)

REMOTE EMERGENCY TWIN LIGHTING HEAD

RELAY

A

A

LV

J

G

T

3S

KS

S

MS

T

A

M

R

CB

LC

PC

DOUBLE DUPLEX RECEPTACLE IN WALL (NEMA 5-20R)

WALL MOUNTED LIGHTING FIXTURE

WIRE & CONDUIT RUN EXPOSED

WIRE & CONDUIT RUN IN OR UNDER FLOOR

UNDERGROUND ELECTRICAL DUCTBANK OR CONDUIT

1 BRANCH CIRCUIT WIRE & CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING,HOME RUN TO PANELBOARD. A NUMERAL, IF PRESENT AT A RROW HEAD,INDICATESCIRCUIT NUMBER. ANY BRANCH CIRCUIT SHOWN WITHOUT S LASH MARKSINDICATES A CONDUIT CONTAINING (3) #12 AWG CONDUCTO RS (HOT, NEUTRAL &GROUND). SLASH MARKS, IF PRESENT, INDICATE THE FOL LOWING:

GROUND CONDUCTOR

NEUTRAL CONDUCTOR

HOT (ENERGIZED) CONDUCTOR

WIRE & CONDUIT TURNED DOWN

WIRE & CONDUIT TURNED UP

UE

G.F.I. TYPE DUPLEX RECEPTACLE IN WALL 44" A.F.F. (N EMA 5-20R)

SD WALL BOX DIMMER CONTROL

ELECTRICAL LEGENDSYMBOL DESCRIPTION

ELECTRICAL CONNECTION REQUIRED

EXISTING LIGHT FIXTURE OR ELECTRICAL DEVICE BE REMOVED AND/ORRELOCATEDAND CIRCUITRY MADE CONTINUOUS WHERE REQUIRED. UNO, LINE TYPE TYPICALFOR ALL DEVICES TO BE REMOVED AND/OR RELOCATED.

FIRE ALARM HORN & ADA SIGNAL LIGHT (80" MH)

FIRE ALARM

FIRE ALARM SPEAKER & ADA SIGNAL LIGHT (80" MH)

FIRE ALARM CHIME & ADA SIGNAL LIGHT (80" MH)

F

F

F

FIRE ALARM ADA VISUAL SIGNAL LIGHT (80" MH)L

CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHTFS

CEILING MOUNTED FIRE ALARM HORN & SIGNAL LIGHTFS

CEILING MOUNTED FIRE ALARM SPEAKERF

CEILING MOUNTED FIRE ALARM ADA VISUAL SIGNALING LIG HTL

FIRE ALARM SIGNAL PULL STATION (46" MH)F

CEILING MOUNTED SMOKE DETECTORS

CEILING MOUNTED HEAT DETECTORH

DUCT MOUNTED SMOKE DETECTORS

DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATORLIGHT,WALL MOUNTED AT 80" MH, UNLESS NOTED OTHERWISE.

SR

ELECTROMAGNETIC DOOR HOLDER (WALL MOUNTED)D

FIRE ALARM CONTROLLED PROGRAMMABLE RELAYR

VALVE TAMPER SWITCHV

SMOKE DAMPERSD

FIRE SHUTTERFS

SYMBOL DESCRIPTION

TELEPHONE OUTLET WITH 3/4" CONDUIT TO

DATA OUTLET WITH 3/4" CONDUIT TO NEAREST ACCESSIBLE

COMMUNICATIONS

TO NEAREST ACCESSIBLE CEILING SPACE

CEILING SPACE

30/3

XFMR

30 AMPERE, 3-POLE

TRANSFORMER

CB CIRCUIT BREAKER

MCP MOTOR CIRCUIT PROTECTOR

WP

VFD

VA

V

UGESOWB

PFPA

NEC

MLO

VARIABLE FREQUENCY DRIVE

SPACE ONLY WITH BUS

WEATHERPROOF

VOLT-AMPERES

VOLT

UNDERGROUND ELECTRICAL

NATIONAL ELECTRIC CODE

POWER FACTORPUBLIC ADDRESS

MAIN LUGS ONLY

KVA

MCC

KW

KCMIL

HZ

FLA

GFI

G

EDF

DISC

CT

MOTOR CONTROL CENTER

THOUSAND CIRCULAR MILS

KILOVOLT-AMPERE

KILOWATT

HERTZ

GROUND FAULT CIRCUIT-INTERRUPTER

ELECTRIC DRINKING FOUNTAIN

CURRENT TRANSFORMER

FULL LOAD AMPS

GROUND

DISCONNECT

AWG

AUX

C

ANNAIC

AFG

AFF

A

AMERICAN WIRE GAUGE

AMPERES INTERRUPTING CURRENT

AUXILIARY

CONDUIT

ANNUNICIATOR

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

ABBREVIATIONS

AMPERE

CU COPPER

FACP FIRE ALARM CONTROL PANEL

3P THREE POLE

3PH THREE PHASE

4W FOUR WIRE

LIGHT EMITTING DIODELED

CKT CIRCUIT

NEUTRALN

SYMBOL DESCRIPTION

GFCI

G.F.I. TYPE DUPLEX RECEPTACLE OUTDOORS (WEATHER PRO OF)WP

FAAP FIRE ALARM ANNUNCIATOR PANEL

DISCONNECT SWITCH

ANNUNCIATOR PANELANNP

GENERAL REFERENCE NOTES:

1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH DI VISION 16 SPECIFICATIONS,NATIONAL ELECTRICAL CODE, AND ALL OTHER APPLICABLE STANDARDS AND REGULATIONSAS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

2. ALL ABOVE GROUND EXPOSED CONDUIT SHALL BE GALVANI ZED RIGID STEEL CONDUIT WITHCORROSION RESISTANT FITTINGS, CLAMPS AND SUPPORTS.

3. IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, CODES ANDREGULATIONS. NOTIFY THE ARCHITECT IN WRITING FOR ENGINEER OF RECORD'S OPINIONPRIOR TO INSTALLATION.

4. SHOP DRAWINGS SHALL BE SUBMITTED TO THE CODE ENFO RCEMENT OFFICE FOR APPROVALAND TO THE ENGINEER FOR REVIEW.

5. SMACNA SEISMIC RESTRAINT MANUAL, SECOND EDITION, OR LATEST REVISION MAY BE USEDAS A GUIDE FOR GENERAL SEISMIC SUPPORT DETAIL AND S UPPORT SPACINGRECOMMENDATIONS.

6. COORDINATE LOCATION OF ALL LIGHTING FIXTURES, MEC HANICAL EQUIPMENT AND ACCESSPANELS WITH ARCHITECTURAL REFLECTED CEILING PLANS P RIOR TO ROUGH-IN.

7. REPLACE PARABOLIC LENS WITH ACRYLIC LENS FOR FIXT URES IN AREAS WHERE FIXTURESARE RE-USED.

8. WHILE GREAT EFFORT HAS BEEN MADE TO IDENTIFY CIRC UITS THAT MAY BE MODIFIED ORREMOVED, THE INFORMATION MAY NOT BE ACCURATE. ELEC TRICAL CONTRACTOR SHALLVERIFY CIRCUITS FOR ALL NEW DEVICES AND EXISTING DE VICES THAT ARE REMOVED ORMODIFIED.

1

E200

CONDUCTOR

GROUNDING

WIRE NUT

FACE SCREW

GROUNDING

HEAD, WASHERSLOTTED HEXAGONSCREW #10

TAPPED HOLE

SIMILAR FOR LIGHT SWITCHES

GROUNDRECEPTACLE

SCREW

CONDUIT

(GREEN)

(TYPICAL)

IN BOX

� N G

OUTLET BOX

RECEPTACLE BONDING DETAILNO SCALE

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

E1.0

ELECTRICALGENERAL NOTES

PTH

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

RJH

REVISIONSNO. DESCRIPTION DATE BY

A/CWAREHOUSE

WAREHOUSE

3

33

3F

F

F FF

F

F

F

FF F

F

F

X2

X2

X2

F

F

X1 X1X2X2

X2

X1

X1 X1

F

F

X2F

A1A1A1

A1A1A1

A1A1A1

A1 A1

A1A1

A1 A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

5 6 7 8 9 10

A

B

C

D

E

N.I.C.

A A A A A

A A A A A

A A A A A

AAAAA

A A A A A

HE10.1-13

HE10.1-15

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

E1.1

ELECTRICALWAREHOUSE

LIGHTING FLOORPLAN

PTH

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

RJH

1/8" = 1'-0"1 WAREHOUSE LIGHTING FLOOR PLAN

GENERAL NOTES:

1. NEW LIGHT FIXTURE "A" SHALL BE LITHONIA MODEL 2GTL 4 48L A19 EZ1 LP835,LED TROFFER, 4800 LUMENS, 3500k OR APPROVED EQUAL.

2. EXISTING METAL HALIDE LIGHTS IN THE WAREHOUSE SHALL REMAIN.3. ALL EXIT LIGHTS, EMERGENCY LIGHTS, AND FAIRE ALARM DEVICES SHALL BE

MOVED BELOW THE NEW CEILING IN THE BAY BETWEEN COLUMNS 9&10.4. EACH LIGHTING CIRCUIT SHALL HAVE A MINIMUM OF FOUR CEILING MOUNTED

OCCUPANCY SENSORS CAPABLE OF DIMMING THE LIGHTS DOWN TO 30% WHENNOT OCCUPIED. THREE WAY SWITCHES SHALL SWEEP LIGHTS ON OR OFF.

REVISIONSNO. DESCRIPTION DATE BY

A/CWAREHOUSE

WAREHOUSE

WPWPWPWPWPWP WP WP

WP WP WP

WP WP WP

J J J J J

GF

CI

J

WP

WP WP WP

WP WP

J

LCP8

LE6

TE6

WPIUAT ROOF

HE8

LE8

TE8

LCP10.1

HE8

HE8 - 25,27,29

LE8 - 7

LE10.1-21

LE10.1 - 20

LE10.1-22

LE8 - 33LE8 - 35

LE8 - 36

HE10.1 - 7,9,11

NEWTE8.1

LE10.1

TE10.1

HE10.1

NEW LE8.1(PROVIDED ON TRAILER)

5 6 7 8 9 10

A

B

C

D

E

SECURITY CAMERA(TYPICAL)

LE10.1-23(HEAT TRACE)

N.I.C.

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

E1.2

ELECTRICALWAREHOUSE

POWER FLOORPLAN

PTH

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

RJH

1/8" = 1'-0"1 WAREHOUSE POWER FLOOR PLAN

GENERAL NOTES:

1. EXISTING CIRCUITS SHALL REMAIN IN TACT.2. NEW CIRCUITS SHALL GENERALLY ORIGINATE FROM THE BAY IN WHICH THEY

RESIDE.3. THE NEW GMU-1 SHALL BE POWERED FROM HE10.1. CHANGE THE CIRCUIT

BREAKER TO 40A 480/3.4. THIS DESIGN IS BASED ON THE NEW TRAILER BEING EQUIPPED WITH A 200A PANEL.

THAT PANEL SHALL BE FED FROM A NEW 45KVA 480/3 TO 240/120/1 TRANSFORMER.THE TRANSFORMER SHALL BE FED FROM PANEL HE8 WITH A NEW 70A/3P BREAKER.

5. TWO DOUBLE DATA PORTS OUTLETS SHALL BE INSTALLED IN THE COUNTER AREA.

REVISIONSNO. DESCRIPTION DATE BY

4 #3/0 AWG, #6G, 2" C.

TE8.145KVA

480V

240/120V

LE8.1200A120/240/1

3 #4 AWG, #8G, 1" C.

DRAWN BY:

CHECKED BY:

PROJECT NUMBER

DATE DWG NO.

SHEET TITLE

SEAL

PROJECT NAME

ArchitecturePlanningInterior Design

1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com

PROJECT STATUS

This information is released solely for its use in the interest of theMemphis-Shelby County Airport Authority (MSCAA) or its Tenants.

All drawings received from MSCAA or produced for MSCAA as awork product shall be regarded as priveleged information, not to bereleased to others without the express written permission of MSCAA.

Your acceptance of the released materials establishes yourunderstanding of, and commitment to, providing adequate control ofthe materials issued and produced.

MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113

MEMPHIS, TENNESSEE38116-3856

APPROVED BY:

SCALE

MSCAA NO.

2787 Stage Center Dr. Suite 101Bartlett, Tennessee 38134

O: 901-319-0500www.inovativees-llc.com

14-1379-16-01

E2.0

ELECTRICAL RISERDIAGRAM

PTH

RJH

STAFF SERVICESWAREHOUSETEMPORARY

14053.16

10/31/16

ISSUED FOR BIDS

RJH

N. T. S.ELECTRICAL ONE LINE

1

REVISIONSNO. DESCRIPTION DATE BY