stabiliser brochure
DESCRIPTION
SCVS BrochureTRANSCRIPT
Atandra Energy Pvt. Ltd., with years of experience in Power Conditioning & Energy Management, provides innovative solutions to your power conditioning needs. KRYKARD Servo Stabilisers have set the standard in the industry for product design and quality in over 300,000 installations over the years.
Under‐rated stabilisers are cheaper but break down frequently and have shorter useable life ‐ higher downtime, reduced productivity and higher life‐cycle cost
NO under-rating to make it cheaper
– set in relation to the nominal output voltage for compatibility with
– normally set at 110% of rated full load current but can be altered
Options for additional protection features as required by the machine such as phase reversal trip,
• Under / Over voltage tripmachine requirement
• Current sensing for overload tripbased on machine requirement ensuring genuine protection for equipment and stabiliser
• Protection against 1‐phasing, short circuit & spikes• Manual service by‐pass as a standard feature up to 50 kVA•
Earth leakage protection, lightning arrestors
Protection features designed
to PROTECT
• 1 phase Servo Stabilisers• 2 phase Servo Stabilisers• 3 phase in / 1 phase out Servo StabilisersAlso Available
SERVO CONTROLLED VOLTAGE STABILISER
3 phase Residential Servo Stabilisers•
CPRI TESTED
Organisations that value uptime of their critical machines prefer KRYKARD and are regular buyers. Among them are: Engg: Tata Motors, M&M, Hyundai, Sundaram Clayton, Rane EVL; Textile: Gangotri, KG, Lakshmi, Precot, Ramalinga, Tuticorin, Sholinghur, Gokak, GTN, Kallam, Suryavanshi; Garment: Best Intl, DeeCee Exports, JV Group, Leela Scottish, White House, Mudra, Silvercrest; Telecom: Idea, Vodafone; Printing: NPT, RRD, Srinivasa Fine, Ramya Repro; Food Proc: Britannia, Coca‐Cola, Hatsun, Hindustan Lever, Mohan Breweries, Pepsi, Ruchi; Leather: Bachi, Farida; Med/ Edn/ R&D: Apollo, Biocon, Bharathidasan, CRLI
Other Products In Our Range Lighting Energy Savers Isolation Transformers Auto Transformers Portable Load Managers Panel Load Managers
Market Impact
Revision: September 2015. Specifications are subject to change without prior notice.KRYKARD is a registered trademark owned by Atandra Energy Pvt. Ltd.
Atandra Energy Private LimitedNo. 5, Kumaran Street, Pazhavanthangal, Chennai ‐ 600 114
Tel: +91 44 4278 0700 | 4278 0600www.atandra.in | [email protected]
Chennai | Coimbatore | Bengaluru | Hyderabad | Vishakapatnam | Mumbai | Pune
Ahmedabad | New Delhi | Madurai | Kochi | Tirupur
OU
R D
EA
LE
R
Parameter 3 Phase Unbalanced Air cooled 3 Phase Unbalanced Oil cooled
Rating (kVA) 3‐150 3‐2000
Reference Standard IS 9815 (Part 1) : 1994
Type of cooling Air (AN/AF) Oil (ONAN)
Input voltage range (V)
310‐480 310‐480
340‐480 340‐480
360‐460 360‐460
380‐440 380‐440
Output voltage (nominal) 415V LL 415V LL
Alternate Output V settings 360V / 380V / 400V / 440V *
Output V regulation ± 1% of nominal output voltage
Input frequency range 47Hz – 53Hz
Output voltage indicationDigital Voltmeter, accuracy 1% of FS, ±1 digit /
VAF meter / Multi Functional Meter can be provided as optional
LED indicationsFront Panel LED indications for Input ON, Output ON,
Input High/ Low, Output High/ Low Trip, Output overload Trip
Under/ Over Voltage cutoffElectronic cutoff circuit with graded time delay for all models.
Cutoff set @ +5% / ‐10% of the nominal output voltage for 310‐480, 340‐480, 360‐460 input range and +5% / ‐12.5% for 380‐440 input range
Overload cutoffElectronic cutoff circuit with graded time delay
set @ 110% of rated full load current
Short circuit protectionHRC fuse at input (in models up to 200 kVA 3‐phase) /
MCB / MCCB can be provided as optional
Single phasing prevention Provided
Stabiliser bypass Provided as a standard up to 50 kVA 3‐phase / optional for higher ratings
Phase Reversal Trip Optional
Transient protection Spike suppressors (standard) / Surge Arrestors (optional)
Resetting modeAutomatic Restart with time delay of 15 sec (3 mins time delay optional) /
manual mode optional
TECHNICAL SPECIFICATIONS
* Alternate settings will result in shift in Input range (Regulation)