split system heat pump · panels are subjected to our 1,000 hour salt spray test . refrigerant...

45
TAG:______________________________ SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. November 2019 AM-PRQ-A4HP4017A-1B-EN Split System Heat Pump A4HP4017A1000A Note: “Graphics in this document are for representation only. Actual model may differ in appearance.” Submittal

Upload: others

Post on 14-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44001177AA--11BB--EENN

Split System Heat PumpA4HP4017A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 2: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4017A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4017A 1A.2 727 (28–5/8) 600 (23–5/8) 19 (3/4) 41 (1–5/8)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4017A 76 72 66 64 66 71 64 56 47

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 3: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4017A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4017A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 12

MAX. OVERCURRENT PROTECTION 20

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 9 — 56

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 18.06

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 1725

NO. MOTORS— HP 1— 1/12

MOTOR SPEED R.P.M. 810

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.54

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 12.41

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 4 LBS., 2 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 3/4

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 24.9 x 24.9

WEIGHT

SHIPPING (LBS.) 164

NET (LBS.) 142

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 4: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4017A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 5: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4017A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4017A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 6: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44001188AA--11BB--EENN

Split System Heat PumpA4HP4018A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 7: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4018A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4018A 2.2 727 (28–5/8) 651 (25–5/8) 19 (3/4) 41 (1–5/8)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4018A 75 72 66 64 66 71 64 56 47

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 8: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4018A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4018A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 12

MAX. OVERCURRENT PROTECTION 20

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 9 — 56

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 19.1

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 2170

NO. MOTORS— HP 1— 1/12

MOTOR SPEED R.P.M. 810

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.54

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 13.44

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 6 LBS., 1 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 3/4

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 26.9 x 26.9

WEIGHT

SHIPPING (LBS.) 167

NET (LBS.) 143

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 9: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4018A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 10: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4018A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4018A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 11: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44002233AA--11BB--EENN

Split System Heat PumpA4HP4023A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 12: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4023A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4023A 2.2 727 (28–5/8) 651 (25–5/8) 19 (3/4) 41 (1–5/8)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4023A 76 77 72 68 68 69 60 53 47

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 13: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4023A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4023A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 14

MAX. OVERCURRENT PROTECTION 25

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 10.9 — 62.9

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 19.1

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 2610

NO. MOTORS— HP 1— 1/8

MOTOR SPEED R.P.M. 1075

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.64

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 13.44

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 4 LBS., 2 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 3/4

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 26.9 x 26.9

WEIGHT

SHIPPING (LBS.) 167

NET (LBS.) 143

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 14: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4023A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 15: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4023A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4023A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 16: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44002244AA--11BB--EENN

Split System Heat PumpA4HP4024A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 17: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4024A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4024A 3.2 727 (28–5/8) 756 (29–3/4) 19 (3/4) 41 (1–5/8)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4024A 75 77 72 68 68 69 60 53 47

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 18: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4024A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4024A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 14

MAX. OVERCURRENT PROTECTION 25

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 10.9 — 62.9

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 23

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 2700

NO. MOTORS— HP 1— 1/8

MOTOR SPEED R.P.M. 850

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.64

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 15.55

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 6 LBS., 2 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 3/4

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 31.0 x 31.0

WEIGHT

SHIPPING (LBS.) 187

NET (LBS.) 159

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 19: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4024A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 20: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4024A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4024A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 21: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

June 2019 AAMM--PPRRQQ--AA44HHPP44003300AA--11AA--EENN

Split System Heat PumpA4HP4030A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 22: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4030A-1A-EN

Outline Drawing

Model Base A B C D

A4HP4030A 4.2 727 (28–5/8) 870 (34–1/4) 19 (3/4) 41 (1–5/8)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4030A 75 84 73 70 72 73 65 58 50

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 23: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4030A-1A-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4030A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 17

MAX. OVERCURRENT PROTECTION 25

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 12.8 — 67.8

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 27.5

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 3235

NO. MOTORS— HP 1— 1/8

MOTOR SPEED R.P.M. 850

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.74

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 18.03

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 6 LBS., 13 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 3/4

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 8°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 35.5 x 35.5

WEIGHT

SHIPPING (LBS.) 207

NET (LBS.) 177

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) Ameristar outdoor condensing units are factory charged with thesystem charge required for the outdoor condensing unit and 15 feetof tested connecting lines. If connecting line length exceeds 15 feet,then final refrigerant charge adjustment is necessary. Each additionalfoot over 15 feet requires 0.6 ozs of refrigerant. See the Installer’sGuide for full charging instructions.

Page 24: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4030A-1A-EN

Mechanical Specification Options

GGeenneerraall

The Outdoor Units are fully charged from the factoryfor up to 15 feet of piping. This unit is designed tooperate at outdoor ambient temperatures as high as115°F. Cooling capacities are matched with a wideselection of air handlers and furnace coils that are AHRIcertified. The unit is certified to UL 1995. Exterior isdesigned for outdoor application.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches. A factory supplied, field installed liquid linedrier is standard.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 25: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4030A-1A-EN 24 Jun 2019

Supersedes (New) ©2019 Ingersoll Rand

Page 26: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44003366AA--11BB--EENN

Split System Heat PumpA4HP4036A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 27: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4036A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4036A 4.2 727 (28–5/8) 870 (34–1/4) 22 (7/8) 43 (1–3/4)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4036A 76 84 75 70 72 67 62 57 50

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 28: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4036A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4036A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 19

MAX. OVERCURRENT PROTECTION 30

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 14.7 — 72.2

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 27.5

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 3380

NO. MOTORS— HP 1— 1/8

MOTOR SPEED R.P.M. 850

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.64

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 18.03

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 6 LBS., 12 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 7/8

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 35.5 x 35.5

WEIGHT

SHIPPING (LBS.) 207

NET (LBS.) 177

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 29: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4036A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 30: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4036A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4036A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 31: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44004422AA--11BB--EENN

Split System Heat PumpA4HP4042A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 32: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4042A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4042A 4.2 727 (28–5/8) 870 (34–1/4) 22 (7/8) 43 (1–3/4)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4042A 76 79 70 68 67 64 59 56 51

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 33: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4042A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4042A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 25

MAX. OVERCURRENT PROTECTION 40

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 19.2 — 124

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 27.5

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 3990

NO. MOTORS— HP 1— 1/5

MOTOR SPEED R.P.M. 825

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.93

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 18.03

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 6 LBS., 5 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 7/8

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 31.7 x 35.5 x 35.5

WEIGHT

SHIPPING (LBS.) 227

NET (LBS.) 197

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 34: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4042A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 35: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4042A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4042A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 36: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44004488AA--11BB--EENN

Split System Heat PumpA4HP4048A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 37: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4048A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4048A 4.3 828 (32–5/8) 870 (34–1/4) 22 (7/8) 43 (1–3/4)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4048A 76 81 73 68 72 67 62 57 51

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 38: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4048A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4048A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 25

MAX. OVERCURRENT PROTECTION 45

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 19.6 — 130

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 27.5

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 4180

NO. MOTORS— HP 1— 1/5

MOTOR SPEED R.P.M. 825

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 0.93

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 20.92

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 8 LBS., 13 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 7/8

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 35.7 x 35.5 x 35.5

WEIGHT

SHIPPING (LBS.) 240

NET (LBS.) 210

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 39: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4048A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 40: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4048A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4048A-1A-EN (June 2019) ©2019 Ingersoll Rand

Page 41: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

TAG:______________________________

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.

November 2019 AAMM--PPRRQQ--AA44HHPP44006600AA--11BB--EENN

Split System Heat PumpA4HP4060A1000A

NNoottee:: “Graphics in this document are for representationonly. Actual model may differ in appearance.”

Submittal

Page 42: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

2 AM-PRQ-A4HP4060A-1B-EN

Outline Drawing

Model Base A B C D

A4HP4060A 4.6 1133 (44–5/8) 870 (34–1/4) 22 (7/8) 43 (1–3/4)

SOUND POWER LEVEL

ModelA-Weighted SoundPower Level [dB(A)]

Full Octave Sound Power [dB]

63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzA4HP4060A 76 81 72 68 71 68 64 59 54

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

Page 43: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

AM-PRQ-A4HP4060A-1B-EN 3

Product Specifications

OUTDOOR UNIT (a) (b) A4HP4060A1000A

POWER CONNS.— V/PH/HZ (c) 208/230/1/60

MIN. CIR. AMPACITY 32

MAX. OVERCURRENT PROTECTION 50

COMPRESSOR SCROLL

NO. USED— NO. STAGES 1 — 1

VOLTS/PH/HZ 208/230/1/60

R.L. AMPS (d)— L.R. AMPS 24.4 — 144

FACTORY INSTALLED

START COMPONENTS (e) NO

INSULATION/SOUND BLANKET NO

COMPRESSOR HEAT NO

OUTDOOR FAN PROPELLER

DIA. (IN.) — NO. USED 27.5

TYPE DRIVE — NO. SPEEDS DIRECT— 1

CFM@ 0.0 IN. W.G. (f) 4410

NO. MOTORS— HP 1— 1/5

MOTOR SPEED R.P.M. 825

VOLTS/PH/HZ 208/230/1/60

F.L. AMPS 1.05

OUTDOOR COIL — TYPE ALL ALUMINUM

ROWS— F.P.I. 1 — 24

FACE AREA (SQ. FT.) 29.31

TUBE SIZE (IN.) 3/8

REFRIGERANT CONTROL EXPANSION VALVE

REFRIGERANT

LBS.— R-410A (O.D. UNIT) (g) 10 LBS., 12 OZ

FACTORY SUPPLIED YES

LINE SIZE — IN. O.D. GAS (h) (i) 7/8

LINE SIZE — IN. O.D. LIQ. 3/8

CHARGING SPECIFICATIONS

SUBCOOLING 10°F

DIMENSIONS H XW X D

CRATED (IN.) 47.7 x 35.5 x 35.5

WEIGHT

SHIPPING (LBS.) 283

NET (LBS.) 252

(a) Certified in accordance with the Air-Source Unitary Air-conditionerEquipment certification program, which is based on AHRI standard210/240.

(b) Rated in accordance with AHRI standard 270.(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR

circuit breakers or fuses.(d) This value shown for compressor RLA on the unit nameplate and on

this specification sheet is used to compute minimum branch circuitampacity and max. fuse size. The value shown is the branch circuitselection current.

(e) No means no start components. Yes means quick start kitcomponents. PTCmeans positive temperature coefficient starter.Optional kit shown.

(f) Standard Air — Dry Coil — Outdoor(g) This value approximate. For more precise value see unit nameplate.(h) Reference the outdoor unit ship-with literature for refrigerant piping

length and lift guidelines. Reference the refrigerant piping softwarepub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denoteslatest revision).

(i) The outdoor condensing units are factory charged with the systemcharge required for the outdoor condensing unit, ten (10) feet oftested connecting line, and the smallest rated indoor evaporative coilmatch. Always verify proper system charge via subcooling (TXV/EEV)or superheat (fixed orifice) per the unit nameplate.

Page 44: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

4 AM-PRQ-A4HP4060A-1B-EN

Mechanical Specification Options

GGeenneerraall

The outdoor condensing units are factory charged withthe system charge required for the outdoor condensingunit, ten (10) feet of tested connecting line, and thesmallest rated indoor evaporative coil match. This unitis designed to operate at outdoor ambienttemperatures as high as 115°F. Cooling capacities arematched with a wide selection of air handlers andfurnace coils that are AHRI certified. The unit is certifiedto UL 1995. Exterior is designed for outdoorapplication.

CCaassiinngg

Unit casing is constructed of heavy gauge, galvanizedsteel and painted with a weather-resistant powderpaint finish. The corner panels are prepainted. Allpanels are subjected to our 1,000 hour salt spray test .

RReeffrriiggeerraanntt CCoonnttrroollss

Refrigeration system controls include condenser fan,compressor contactor and low and high pressureswitches.

CCoommpprreessssoorr

The compressor features internal over temperature andpressure protection. Other features include: Centrifugaloil pump and low vibration and noise.

CCoonnddeennsseerr CCooiill

The outdoor coil provides low airflow resistance andefficient heat transfer. The coil is protected on all foursides by louvered panels.

LLooww AAmmbbiieenntt CCoooolliinngg

As manufactured, this system has a cooling capacity to55°F. The addition of an evaporator defrost controlpermits operation to 40°F. The addition of anevaporator defrost control with TXV permits lowambient cooling to 30°F.

The addition of the BAYLOAM107A low ambient kitpermits ambient cooling to 20°F.

TThheerrmmoossttaattss—Cooling only and heat/cooling (manualand automatic change over). Sub-base to matchthermostat and locking thermostat cover.

Page 45: Split System Heat Pump · panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

ingersollrand.com

The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products,go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.

AM-PRQ-A4HP4060A-1B-EN 12 Nov 2019

Supersedes AM-PRQ-A4HP4060A-1A-EN (June 2019) ©2019 Ingersoll Rand