TECHNICAL DATA& SERVICE MANUAL
OUTDOOR UNIT: GRV180C7TABGRV180L7TAB
SPLIT SYSTEM AIR CONDITIONER
0.8180.297.0 09/2004
387107071GRV180L7TAB
Model No. Product Code No.GRV180C7TAB 387107070
IMPORTANT!Please read before installation
This air conditioning system meets strict safety and operatingstandards.For the installer or service person, it is important to install orservice the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state and national electrical codes. Pay close attention to all warning and caution notices given in
this manual.The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can resultin severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can resultin personal injury or product or property damage.
If necessary, get helpThese instructions are all you need for most installation sites andmaintenance conditions.If you require help for a special problem, contact our sale/serviceoutlet or your certified dealer for additional instructions.
In case of improper installationThe manufacturer shall in no way be responsible for improperinstallation or maintenance service, including failure to follow theinstructions in this document.
SPECIAL PRECAUTIONS
During installation, connect before the refrigerant system andthen the wiring one; proceed in the reverse orden when removingthe units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVEREPERSONAL INJURY OR DEATH. ONLY A QUALIFIED,EXPERIENCED ELECTRICIANS SHOULD ATTEMPTTO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing arecompleted or reconnected and checked, to ensure the grounding.
Highly dangerous electrical voltages are used in this system.Carefully refer to the wiring diagram and these instructions whenwiring.Improper connections and inadequate grounding can causeaccidental injury and death.
Ground the unit following local electrical codes. The Yellow/Green wire cannot be used for any connection
different from the ground connection. Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard. Do not allow wiring to touch the refrigerant tubing, compressor,
or any moving parts of the fan. Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
When transportingBe careful when picking up and moving the indoor and outdoorunits. Get a partner to help, and bend your knees when lifting toreduce strain on your back. Sharp edges or thin aluminium fins onthe air conditioner can cut your fingers.
When installing...... In a ceiling or wallMake sure the ceiling/wall is strong enough to hold the unit-weight.It may be necessary to build a strong wooden or metal frame toprovide added support.
... In a roomProperly insulate any tubing run inside a room to prevent"sweating", which can cause dripping and water damage to wallsand floors.
... In moist or uneven locationsUse a raised concrete base to provide a solid level foundation forthe outdoor unit.This prevents damage and abnormal vibrations.
... In area with strong windsSecurely anchor the outdoor unit down with bolts and a metalframe. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)Install the outdoor unit on a raised platform that is higher thandrifting snow. Provide snow vents.
When connecting refrigerant tubing Keep all tubing runs as short as possible. Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand andthen tighten the nut with a torque wrench for a leak-freeconnection.
Check carefully for leaks before starting the test run.
NOTE:Depending on the system type, liquid and gas lines may be eithernarrow or wide. Therefore, to avoid confusion, the refrigeranttubing for your particular model is specified as narrow tube forliquid, wide tube for gas.
When servicing Turn the power OFF at the main power board before opening
the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after the work, remembering to check that no
metal scraps or bits of wiring have been left inside the unit beingserviced.
Ventilate the room during the installation or testng the refrigerationsystem; make sure that, after the installation, no gas leaks arepresent, because this could produce toxic gas and dangerousif in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
2
Page
1.OPERATING RANGE 4
2. SPECIFICATIONS 52-1 Unit specifications 52-2 Major Component specifications 72-3 Other Component specifications 9
3. DIMENSIONAL DATA 10
4. REFRIGERANT FLOW DIAGRAM 11
5. PERFORMANCE DATA 125-1 Performance Charts 125-2 Cooling Capacity 14
6. ELECTRICAL DATA 166-1 Electrical characteristics 166-2 Electric Wiring Diagram 186-3 System Wiring Diagram 19
Table of Contents
3
1. OPERATING RANGE
Cooling
(*) SCL MODEL : -15C D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
(*)19C D.B.32C D.B. / 23C W.B.19C D.B. / 14C W.B.
43C D.B.
4
2. SPECIFICATIONS2-1 Unit SpecificationsGRV180C7TAB
Power source
Voltage rating
Performance * MCAV180C5VAACapacity kW
BTU/hAir circulation (High) m/hMoisture removal (High) Liters/h
Electrical RatingAvailable voltage range VRunning amperes APower input WPower factor %C.O.P. W/WCompressor locked rotor amperes A
FeaturesFan speedCompressorRefrigerant / Amount charged at shipment gRefrigerant controlOperation Sound Hi dB-ARefrigerant tubing connectionsMax. allowable tubing length at shipment mRefrigerant Narrow tube mm(in.)tube diameter Wide tube mm(in.)
Dimensions & WeightUnit dimensions Height mm
Width mmDepth mm
Package dimensions Height mmWidth mmDepth mm
Weight Net kgShipping kg
Shipping volume m3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:Rating conditions are:Cooling: Indoor air temperature 27C D.B. / 19C W.B.
Outdoor air temperature 35C D.B. / 24C W.B.Heating: Indoor air temperature 20C D.B.
Outdoor air temperature 7C D.B. / 6C W.B.
2000
7,5
0,29
400V
9944135257
6,35 (1/4")
830
2,3
Cooling
4,20
760
342 ~ 440
400-415V - 3N - 50Hz
Cooling5,00
17063
713
1(Hi)
630
Rotary (Hermetic)R407C / 1680
12,7(1/2")
Flare type
305
47
2072,521
Capillary tube
5
GRV180L7TAB
Power source
Voltage rating
Performance * MCAV180C5VAACapacity kW
BTU/hAir circulation (High) m/hMoisture removal (High) Liters/h
Electrical RatingAvailable voltage range VRunning amperes APower input WPower factor %C.O.P. W/WCompressor locked rotor amperes A
FeaturesFan speedCompressorRefrigerant / Amount charged at shipment gRefrigerant controlOperation Sound Hi dB-ARefrigerant tubing connectionsMax. allowable tubing length at shipment mRefrigerant Narrow tube mm(in.)tube diameter Wide tube mm(in.)
Dimensions & WeightUnit dimensions Height mm
Width mmDepth mm
Package dimensions Height mmWidth mmDepth mm
Weight Net kgShipping kg
Shipping volume m3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:Rating conditions are:Cooling: Indoor air temperature 27C D.B. / 19C W.B.
Outdoor air temperature 35C D.B. / 24C W.B.Heating: Indoor air temperature 20C D.B.
Outdoor air temperature 7C D.B. / 6C W.B.
* For other INDOOR UNITS' MODELS, please refer to catalogue
400-415V - 3N - 50Hz
400V
Cooling5,00
170637602,3
Cooling342 ~ 440
4,2020002072,521
1(Hi)Rotary (Hermetic)
R407C / 1680Capillary tube
47Flare type
7,56,35 (1/4")12,7(1/2")
6308303057139944135257
0,29
6
2-2 Major Component Specifications
GRV180C7TAB
CompressorTypeCompressor modelNominal output WCompressor oilAmount cc.Coil resistance (Ambient temp. 20C)
Safety devices TypeOverload relayOperating Temp. Open C
Close C
Run capacitor FVAC
Fan & Fan MotorTypeQ'ty . Dia.Fan motor modelQ'tyNo. Of polesrpm (230 V, High)Nominal output WCoil resistance (Ambient temp. 20 C )
Safety devices TypeOperating temp. Open C
Close CRun capacitor F
VAC
Heat Exch. CoilCoilRowsFin pitch mmFace area m2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Operating amp.(Ambient temp.25C)
Rotary (Hermetic)
C-S: 7,21
4JS350PAB (JSM709-051)1700
RB68A or FREOL ALPHA68M 700C-R: 7,1
R-S: 6,86
Propeller
KFG6S-51SB5P - 1
--
WHT-PNK: 201
1. 400
690840
BRN-WHT: 98,5
Acrylic baked-on enamel finish
Internal thermal protector130 5
21,8
0,508
83 152
Aluminium plate fin / Copper tube
440
Internal protector External protector-
- 5A
CLK-15JT40-S622Automatic opening -
Automatic reclosining -
7
GRV180L7TAB
CompressorTypeCompressor modelNominal output WCompressor oilAmount cc.Coil resistance (Ambient temp. 20C)
Safety devices TypeOverload relayOperating Temp. Open C
Close C
Run capacitor FVAC
Fan & Fan MotorTypeQ'ty . Dia.Fan motor modelQ'tyNo. Of polesrpm (230 V, High)Nominal output WCoil resistance (Ambient temp. 20 C )
Safety devices TypeOperating temp. Open C
Close CRun capacitor F
VAC
Heat Exch. CoilCoilRowsFin pitch mmFace area m2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Crank case heater 240 V - 30 W
Rotary (Hermetic)4JS350PAB (JSM709-051)
Automatic opening -
1700RB68A or FREOL ALPHA68M 700
C-R: 7,1C-S: 7,21R-S: 6,86
Internal protector External protector- CLK-15JT40-S622
Automatic reclosining -Operating amp.(Ambient temp.25C) - 5A
-
Propeller
-
1. 400KFG6S-51SB5P - 1
690840
BRN-WHT: 98,5WHT-PNK: 201
Internal thermal protector130 583 15
2440
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube2
1,80,508
8
2-3 Other Component Specifications
GRV180C7TABGRV180L7TAB
Negative Phase RelayTypeRatingContact RatingOperation
Thermostat (Fan Speed Control 23S)TypeSwitching Temp. C high LOW 23.5 +0 / -2.5
C low HIGH 27 +0 / -3
Pressure Transducer (Johnson Control)TypeRange BarFactory Setting Bar
Thermostat (Fan Speed Control 23S)TypeSwitching Temp. C high LOW 23.5 +0 / -2.5
C low HIGH 27 +0 / -3
Pressure Transducer (Johnson Control)TypeRange BarFactory Setting Bar 20
(Only for GRV180L7TAB)
P35 AC14 to 24
MQT5S-27YZJ
(Only for GRV180L7TAB)
(Only for GRV180L7TAB)
MQT5S-27YZJ
CISE131-VAC 380 V, 3-PHASE 50 Hz
AC 250 V , 8 APositive phase: ON
Negative phase: OFF
20(Only for GRV180L7TAB)
P35 AC14 to 24
9
3. DIMENSIONAL DATA Outdoor Unit: GRV180C7TABGRV180L7TAB
Air discharge
Air intake
538 146
307
337
4 12 holes
830
19
630
305
6195
Wide tube service valve 12.7 (1/2")
Narrow tube service valve6.35 (1/4")
Unit : mm
10
4. REFRIGERANT FLOW DIAGRAMIndoor Unit: Outdoor Unit: GRV180C7TAB
Indoor Unit: Outdoor Unit: GRV180L7TAB
11
5. PERFORMANCE DATA
5-1 Performance chartsGRV180C7TAB
Cooling Characteristics
Points of Rating condition
Data referred to MCAV180C5VAA
Overload prevention operates to protect the air conditioner when outdoor ambient temperaturereaches extremely high values in heating mode.
0
1
2
3
4
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (C)
Ope
ratin
gcu
rren
t(A
)
0,00
0,10
0,20
0,30
0,40
0,50
0,60
20 25 30 35 40 45
Outdoor inlet air D.B. (C)
Low
pres
sure
atw
ide
tube
serv
ice
valv
eM
Pa
Indoor inlet airD.B. (C)
32
27
19
3227
19
Indoor inlet airD.B. (C)
12
GRV180L7TAB
Cooling Characteristics
Points of Rating condition
Data referred to MCAV180C5VAA
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reachesextremely high values in heating mode.
0
1
2
3
4
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (C)
Ope
ratin
gcu
rren
t(A
)
0,00
0,10
0,20
0,30
0,40
0,50
0,60
20 25 30 35 40 45
Outdoor inlet air D.B. (C)
Low
pres
sure
atw
ide
tube
serv
ice
valv
eM
Pa
Indoor inlet airD.B. (C)
32
27
19
32
2719
Indoor inlet airD.B. (C)
13
5-2 Cooling CapacityOUTDOOR UNIT:
GRV180C7TABINDOOR UNIT: MCAV180C5VAA
400-415V - 3N - 50HzRATING CAPACITY 5,00 kW moisture removal 2,3 l/hCOMP. POWER INPUT 1,844 kW max comp input 2,244 kWAIR FLOW RATE 760 m/h
EVAPORATORENT.TEMP. CW.B. D.B. 20 25 30 35 40 43
TC 5,05 4,74 4,60 4,38 4,11 3,79CM 1,30 1,44 1,59 1,73 1,88 2,02
21 SHC 3,50 3,25 3,18 3,08 2,95 2,7923 SHC 3,96 3,68 3,61 3,50 3,37 3,22
15 25 SHC 4,40 4,10 4,02 3,91 3,78 3,6327 SHC 4,85 4,54 4,45 4,34 4,11 3,7929 SHC 5,05 4,74 4,60 4,38 4,11 3,7931 SHC 5,05 4,74 4,60 4,38 4,11 3,79
TC 5,41 5,13 4,93 4,70 4,41 4,07CM 1,35 1,50 1,64 1,79 1,93 2,08
21 SHC 3,02 2,84 2,76 2,65 2,52 2,3623 SHC 3,48 3,27 3,17 3,07 2,93 2,78
17 25 SHC 3,93 3,70 3,60 3,49 3,36 3,2027 SHC 4,39 4,13 4,01 3,90 3,77 3,6229 SHC 4,85 4,56 4,43 4,33 4,20 4,0331 SHC 5,28 4,99 4,85 4,70 4,41 4,07
TC 5,75 5,43 5,25 5,00 4,70 4,33CM 1,41 1,55 1,70 1,84 1,99 2,13
21 SHC 2,54 2,38 2,30 2,20 2,07 1,9123 SHC 2,99 2,80 2,73 2,62 2,49 2,34
19 25 SHC 3,45 3,21 3,14 3,03 2,91 2,7527 SHC 3,88 3,62 3,57 3,39 3,33 3,1729 SHC 4,34 4,02 3,98 3,87 3,75 3,5931 SHC 4,80 4,45 4,40 4,29 4,16 4,01
TC 6,05 5,76 5,57 5,30 4,98 4,59CM 1,67 1,77 1,87 1,98 2,08 2,19
23 SHC 2,48 2,35 2,27 2,16 2,03 1,8821 25 SHC 2,94 2,75 2,68 2,59 2,46 2,30
27 SHC 3,39 3,17 3,11 3,00 2,88 2,7229 SHC 3,85 3,57 3,52 3,42 3,29 3,1431 SHC 4,28 3,99 3,95 3,84 3,72 3,57
TC 6,45 6,09 5,89 5,57 5,21 4,85CM 1,92 1,99 2,05 2,11 2,18 2,24
23 25 SHC 2,42 2,28 2,21 2,09 1,96 1,8327 SHC 2,88 2,67 2,62 2,50 2,37 2,2429 SHC 3,33 3,07 3,04 2,92 2,79 2,6631 SHC 3,79 3,51 3,47 3,34 3,21 3,09
TC: TOTAL COOLING CAPACITY kWSHC: SENSIBLE HEAT CAPACITY kWCM: COMPRESSOR INPUT kW
NOTE: Data referred to MCAV180C5VAA
CONDENSEROUTDOOR AMBIENT TEMP. C
14
OUTDOOR UNIT:GRV180L7TAB
INDOOR UNIT: MCAV180C5VAA
400-415V - 3N - 50HzRATING CAPACITY 5,00 kW moisture removal 2,3 l/hCOMP. POWER INPUT 1,844 kW max comp input 2,244 kWAIR FLOW RATE 760 m/h
EVAPORATORENT.TEMP. CW.B. D.B. 20 25 30 35 40 43
TC 5,05 4,74 4,60 4,38 4,11 3,79CM 1,30 1,44 1,59 1,73 1,88 2,02
21 SHC 3,50 3,25 3,18 3,08 2,95 2,7923 SHC 3,96 3,68 3,61 3,50 3,37 3,22
15 25 SHC 4,40 4,10 4,02 3,91 3,78 3,6327 SHC 4,85 4,54 4,45 4,34 4,11 3,7929 SHC 5,05 4,74 4,60 4,38 4,11 3,7931 SHC 5,05 4,74 4,60 4,38 4,11 3,79
TC 5,41 5,13 4,93 4,70 4,41 4,07CM 1,35 1,50 1,64 1,79 1,93 2,08
21 SHC 3,02 2,84 2,76 2,65 2,52 2,3623 SHC 3,48 3,27 3,17 3,07 2,93 2,78
17 25 SHC 3,93 3,70 3,60 3,49 3,36 3,2027 SHC 4,39 4,13 4,01 3,90 3,77 3,6229 SHC 4,85 4,56 4,43 4,33 4,20 4,0331 SHC 5,28 4,99 4,85 4,70 4,41 4,07
TC 5,75 5,43 5,25 5,00 4,70 4,33CM 1,41 1,55 1,70 1,84 1,99 2,13
21 SHC 2,54 2,38 2,30 2,20 2,07 1,9123 SHC 2,99 2,80 2,73 2,62 2,49 2,34
19 25 SHC 3,45 3,21 3,14 3,03 2,91 2,7527 SHC 3,88 3,62 3,57 3,39 3,33 3,1729 SHC 4,34 4,02 3,98 3,87 3,75 3,5931 SHC 4,80 4,45 4,40 4,29 4,16 4,01
TC 6,05 5,76 5,57 5,30 4,98 4,59CM 1,55 1,68 1,81 1,93 2,06 2,19
23 SHC 2,48 2,35 2,27 2,16 2,03 1,8821 25 SHC 2,94 2,75 2,68 2,59 2,46 2,30
27 SHC 3,39 3,17 3,11 3,00 2,88 2,7229 SHC 3,85 3,57 3,52 3,42 3,29 3,1431 SHC 4,28 3,99 3,95 3,84 3,72 3,57
TC 6,45 6,09 5,89 5,57 5,21 4,85CM 1,69 1,80 1,91 2,02 2,13 2,24
23 25 SHC 2,42 2,28 2,21 2,09 1,96 1,8327 SHC 2,88 2,67 2,62 2,50 2,37 2,2429 SHC 3,33 3,07 3,04 2,92 2,79 2,6631 SHC 3,79 3,51 3,47 3,34 3,21 3,09
TC: TOTAL COOLING CAPACITY kWSHC: SENSIBLE HEAT CAPACITY kWCM: COMPRESSOR INPUT kW
NOTE: Data referred to MCAV180C5VAA
CONDENSEROUTDOOR AMBIENT TEMP. C
15
6. ELECTRICAL DATA6-1 Electrical characteristicsOUTDOOR UNIT:
GRV180C7TAB
COOLING
Indoor Unit Complete UnitFan Motor Fan Motor Compressor
performance atRating conditions Running Amps. A 0,37 0,40 3,43 4,2
Power input Kw 0,070 0,086 1,844 2,000Full load conditions Running Amps. A 0,37 0,40 3,83 4,6
Power input Kw 0,070 0,086 2,244 2,400
Rating Conditions: Indoor Air Temperature 27C D.B. / 19C W.B.Outdoor Air Temperature 35C D.B.
Full Load Conditions: Indoor Air Temperature 32C D.B. / 23C W.B.Outdoor Air Temperature 43C D.B.
NOTE: Data referred to indoor unit MCAV180C5VAA model.For other indoor unit models there could be the same differences.
Outdoor unit
230V 1-Phase 50 Hz
16
OUTDOOR UNIT:GRV180L7TAB
COOLING
Indoor Unit Complete UnitFan Motor Fan Motor Compressor
performance atRating conditions Running Amps. A 0,37 0,40 3,4 4,2
Power input Kw 0,070 0,086 1,844 2,000Full load conditions Running Amps. A 0,37 0,40 3,8 4,6
Power input Kw 0,070 0,086 2,244 2,400
Rating Conditions: Indoor Air Temperature 27C D.B. / 19C W.B.Outdoor Air Temperature 35C D.B.
Full Load Conditions: Indoor Air Temperature 32C D.B. / 23C W.B.Outdoor Air Temperature 43C D.B.
NOTE: Data referred to indoor unit MCAV180C5VAA model.For other indoor unit models could be the same difference.
Outdoor unit
230V 1-Phase 50 Hz
17
6-2 Electric Wiring Diagram
OUTDOOR UNIT: GRV180C7TAB
OUTDOOR UNIT: GRV180L7TAB
18
6-3 System Wiring Diagram
19