spf thermal performance - johns manville
TRANSCRIPT
SPF THERMAL PERFORMANCE
CURRENT TEST METHODS USED TO QUANTIFY THE THERMAL PERFORMANCE OF SPRAY FOAM INSULATION PRODUCTS
ASTM C518: STANDARD TEST METHOD FOR STEADY-STATE THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS:ASTM C518 is a controlled test environment that measures the thermal performance of SPF products.
ASTM C1363: STANDARD TEST METHOD FOR THERMAL PERFORMANCE OF BUILDING MATERIALS AND ENVELOPE ASSEMBLIES BY MEANS OF A HOT BOX APPARATUS:ASTM C1363 measures the actual wall thermal characteristics by using a calibrated hot box (CHB), which quantifies foam performance in a representative wall assembly.
ASTM C518 AND ASTM C1363: WALL ASSEMBLY TESTS Testing of the wall assemblies per ASTM C1363, as well as small-scale ASTM C518 thermal testing, was conducted at the Johns Manville Technical Center at 30-, 90-,180- and 365-day intervals to understand the change in R-value over time of three foam products: JM Corbond III® SPF and two products from leading manufacturers. All samples for both test series were aged at ambient interior Littleton, Colorado, conditions.
ASTM C1363: Interior side of SPF test wall ASTM C1363: Interior side with gypsum wallboard and thermocouple grid
SPF THERMAL PERFORMANCE
THERMAL PERFORMANCE COMPARISON OF THREE 2.0 PCF SPRAY FOAM INSULATION PRODUCTS
TIME (DAYS)
6
7
6.8
6.6
6.4
6.2
5.8
30 90 180 365
INS
ULA
TIO
N R
-VA
LUE
(C
518
)
JM Corbond III SPF
Manufacturer 1
Manufacturer 2
6.6
6.6
6.3
6.5
6.5
6.2
6.5
6.5
6.1
6.3
6.4
5.9
TIME (DAYS)
10.0
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
14.5
15.0
JM Corbond III SPF
Manufacturer 1
Manufacturer 2
13.2
12.8
13.3
13.3
13.3
13.2
12.8
13.2
12.8
12.4
12.6
12.4
TIME (DAYS)
INS
ULA
TIO
N R
-VA
LUE
(C
13
63
)
30 90 180 365
R-value results using the standard small-scale ASTM C518 testing protocol show a small decrease in performance over a 365-day time period (above). The decrease was less than 6 percent for all three foam products with initial values for JM Corbond III® SPF, Manufacturer 1 and Manufacturer 2 of R-6.6, R-6.6 and R-6.3 per inch, respectively. All the samples had densities between 2.1 ± 0.1 pcf. For comparison, published technical datasheets show aged R-values at 1" for JM Corbond III SPF, Manufacturer 1 and Manufacturer 2 as R-6.4, R-7.4 and R-6.7, respectively.
CHB wall assemblies show similar performance for all three foam products at each time tested (above). The initial values for JM Corbond III SPF, Manufacturer 1 and Manufacturer 2 were R-13.2, R-12.8 and R-13.3, respectively. The difference in R-value of the wall assemblies compared to that expected from ASTM C518 results (R-19.5 = R-6.5 per inch x 3 inches) is due to the thermal-bridging losses associated with the 2" x 4" wood stud constructions.
SUMMARY: Regardless of the differences in R-values advertised by each manufacturer, both large-scale and small-scale testing of three 2.0 pcf spray polyurethane foam products (JM Corbond III SPF, Manufacturer 1 and Manufacturer 2) demonstrate similar thermal performance.
The majority of the closed-cell foam products on the market are likely to provide very similar thermal performance in actual field applications.
ASTM C518 ASTM C1363