specifications - instrumart · 2017-02-02 · • calculation of crest factors for v and a •...

5
www.aemc.com Technical Assistance (800) 343-1391 POWER QUALITY ANALYZERS, METERS & LOGGERS Three-Phase Power Quality Analyzer SD card memory capacity for trend data storage: Up to 50 captured snapshots, 210 captured transients, 1 inrush and 10,000 alarm events PowerPad ® III Model 8435 KIT OPTION INCLUDES Extra large tool bag, accessory pouch, 5 ft USB cable, five 10 ft black voltage leads with alligator clips, 110V US power cord, four water-tight AmpFlex ® 196A-24-BK (included with Cat. #2136.42 only), NiMH battery, SD card, twelve color-coded input ID markers, quick start guide, and a USB stick containing DataView ® software and user manual. 8435 Kit SPECIFICATIONS MODEL 8435 ELECTRICAL Sampling Frequency 256 samples/cycle Data Storage SD card for trend recording; Additional separate 12.5MB partitioned memory for snapshots, transient/inrush & alarms Voltage (TRMS) Phase-to-Phase: 2000V Phase-to-Neutral: 1000V Voltage Ratio: up to 500kV Current (TRMS) MN Clamp: 0 to 6A/120A or 0 to 240A SR Clamp: 0 to 1200A MR Clamp: 0 to 1000AAC, 0 to 1400ADC MiniFlex ® : 10 to 3000A AmpFlex ® : 10 to 10kA (1) SL261 Clamp: 50mA to 100AAC/DC J93: 50 to 3500AAC/DC Current Ratio: 10mA to 50kA Frequency (Hz) 40 to 69Hz Other Measurements kW, kvar, kVA, PF, DPF, kWh, kvarh, kVAh, K-Factor, Flicker Harmonics 1 st to 50 th , Direction, Sequence Power Source 9.6V NiMH rechargeable battery pack (included) External AC supply: 110/230VAC ±10% (50/60Hz) Battery Life 8 hours with display on; 35 hours with display off (record mode) MECHANICAL Communication Port Optically isolated USB Display ¼ VGA (320 x 240) color LCD display with adjustable brightness & contrast Dimensions 10.6 x 9.8 x 7.1" (270 x 250 x 180mm) Weight 8.2 lbs (3.7kg) with batteries Safety Rating EN 61010, 600V CAT IV (2) , 1000V CAT III, Pollution Degree 2 (1) Crest factor at 6500 = 1 (2) When used with SR193 or AmpFlex ® probes. 600V CAT III with MN193 or MR193 probes. Four current and four voltage input terminals FEATURES Measurement of TRMS voltages up to 1000Vrms AC/ DC for two-, three-, four- or five-wire systems Measurement of TRMS currents up to 6500Arms (sensor dependent) Direct measurement of neutral current & voltage Frequency measurement (40 to 69Hz systems) Record and display trend data as fast as once per second for one month for up to 25 variables Transient detection on all V and I inputs (up to 210) Selectable PT and CT ratios Inrush current measurement Calculation of Crest Factors for V and A Calculation of the K-Factor for transformers Calculation of short-term flicker and three-phase voltage unbalance Measures harmonics (referenced to the fundamental or RMS value) for voltage, current or power, up to 50 th harmonic Displays of harmonic sequencing and direction and calculation of overall harmonics Real-time display of phasor diagrams including values and phase angles Measurement of active, reactive and apparent power per phase and their respective sum total Calculation of power factor, displacement power factor and tangent factor Recording, time stamping and characterization of disturbance (swells, sags and interruptions, exceedence of power and harmonic thresholds) 2GB internal Trend Recording memory; Alarm, Snapshot and Transient/Inrush memories are separate Measurement of energy VAh, varh & Wh The Max and Min RMS measurements are calculated every half-period Includes DataView ® software for configuring, real-time display, analysis and report generation 65μs/sample transient recording Special product features 2 G B M E M O R Y C A P T R E T R A N S I E N T S T R E N D R E C O R D I N G ' ' ' ' R A T I N G S A F E T Y IP Rated 67 cover closed 3 3 W A R R A N T Y Y E A R * * Registration must take place within 30 days of purchase cover closed

Upload: others

Post on 25-Apr-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SPECIFICATIONS - Instrumart · 2017-02-02 · • Calculation of Crest Factors for V and A • Calculation of the K-Factor for transformers • Calculation of short-term flicker and

www.aemc.com Technical Assistance (800) 343-1391

POWER QUALITY ANALYZERS, METERS & LOGGERS Three-Phase Power Quality Analyzer

SD card memory capacity for trend data storage: Up to 50 captured snapshots, 210 captured transients, 1 inrush and 10,000 alarm events

PowerPad® III Model 8435

KIT OPTION INCLUDES

Extra large tool bag, accessory pouch, 5 ft USB cable, five 10 ft black voltage leads with alligator clips, 110V US power cord, four water-tight AmpFlex® 196A-24-BK (included with Cat. #2136.42 only), NiMH battery, SD card, twelve color-coded input ID markers, quick start guide, and a USB stick containing DataView® software and user manual.

8435 Kit

SPECIFICATIONSMODEL 8435ELECTRICALSampling Frequency 256 samples/cycleData Storage SD card for trend recording;

Additional separate 12.5MB partitioned memory for snapshots, transient/inrush & alarms

Voltage (TRMS) Phase-to-Phase: 2000V Phase-to-Neutral: 1000V

Voltage Ratio: up to 500kVCurrent (TRMS) MN Clamp: 0 to 6A/120A or 0 to 240A

SR Clamp: 0 to 1200AMR Clamp: 0 to 1000Aac, 0 to 1400Adc

MiniFlex®: 10 to 3000A AmpFlex®: 10 to 10kA(1)

SL261 Clamp: 50mA to 100Aac/dc J93: 50 to 3500Aac/dc

Current Ratio: 10mA to 50kA

Frequency (Hz) 40 to 69HzOther Measurements kW, kvar, kVA, PF, DPF, kWh, kvarh, kVAh, K-Factor, FlickerHarmonics 1st to 50th, Direction, SequencePower Source 9.6V NiMH rechargeable battery pack (included)

External AC supply: 110/230Vac ±10% (50/60Hz)Battery Life ≥8 hours with display on; ≤35 hours with display off

(record mode)MECHANICALCommunication Port Optically isolated USBDisplay ¼ VGA (320 x 240) color LCD display with adjustable

brightness & contrastDimensions 10.6 x 9.8 x 7.1" (270 x 250 x 180mm)Weight 8.2 lbs (3.7kg) with batteriesSafety Rating EN 61010, 600V CAT IV(2), 1000V CAT III, Pollution Degree 2

(1)Crest factor at 6500 = 1 (2)When used with SR193 or AmpFlex® probes. 600V CAT III with MN193 or MR193 probes.

Four current and four voltage input terminals

FEATURES• Measurement of TRMS voltages up to 1000Vrms AC/

DC for two-, three-, four- or five-wire systems• Measurement of TRMS currents up to 6500Arms

(sensor dependent)• Direct measurement of neutral current & voltage• Frequency measurement (40 to 69Hz systems)• Record and display trend data as fast as once

per second for one month for up to 25 variables• Transient detection on all V and I inputs (up to 210)• Selectable PT and CT ratios• Inrush current measurement• Calculation of Crest Factors for V and A• Calculation of the K-Factor for transformers• Calculation of short-term flicker and three-phase

voltage unbalance• Measures harmonics (referenced to the fundamental

or RMS value) for voltage, current or power, up to 50th

harmonic• Displays of harmonic sequencing and

direction and calculation of overall harmonics• Real-time display of phasor diagrams

including values and phase angles• Measurement of active, reactive and apparent power

per phase and their respective sum total• Calculation of power factor, displacement power factor

and tangent factor• Recording, time stamping and characterization of

disturbance (swells, sags and interruptions,exceedence of power and harmonic thresholds)

• 2GB internal Trend Recording memory; Alarm,Snapshot and Transient/Inrush memories are separate

• Measurement of energy VAh, varh & Wh• The Max and Min RMS measurements are

calculated every half-period• Includes DataView® software for configuring, real-time

display, analysis and report generation• 65μs/sample transient recording

Special product features

2GB

MEMORY

CAPT

RE TRANSIEN

TS

TRE

ND

RECORDIN

G

''''

R AT I N G

SAFETYIP

Rated67

cover closed

33WARRANT

Y

YEAR*

* Registration must take place within 30 days of purchase

Original

cover closed

Page 2: SPECIFICATIONS - Instrumart · 2017-02-02 · • Calculation of Crest Factors for V and A • Calculation of the K-Factor for transformers • Calculation of short-term flicker and

Technical Assistance (800) 343-1391 www.aemc.com

CATALOG NO. DESCRIPTION

2136.41 PowerPad® III Model 8435 (No Sensors - Waterproof IP67)2136.42 PowerPad® III Model 8435 w/4 A196-24-BK (AmpFlex® - Waterproof IP67)Accessories (Optional)2133.73 Extra Large Classic Tool Bag2140.72 Replacement accessory pouch (accessories not included)2140.19 Replacement – Battery 9.6V NiMH2140.28 AC Current Probe Model MR193-BK2140.32 AC Current Probe Model MN93-BK2140.33 AC Current Probe Model SR193-BK2140.35 AmpFlex® Sensor 36" Model 193-36-BK2140.36 AC Current Probe Model MN193-BK 2140.45 Replacement – Set of 12, Color-coded Input ID Markers2140.46 Replacement – 5 ft USB Cable2140.48 MiniFlex® Sensor 10" Model MA193-10-BK2140.49 AC/DC Current Probe Model J93-BK

2140.73 Lead – One 10 ft (3M) Black Lead (Waterproof cap) [Rated 1000V CAT IV] & one Black Alligator Clip [Rated 1000V CAT IV, 15A,UL]

2140.75 AmpFlex® Sensor 24" (waterproof - IP67) Model A196-24-BK

Configuration

Inrush Peak

Trend Analyze

Phasor Diagram

Harmonics Mode

Transient Mode

PowerPad® III Model 8435

Large Color Functional DisplaysInstallation of the Leads and Current SensorsColor-coded ID markers are supplied with the PowerPad® III to identify the leads and input terminals.

Cat. #5000.63

Cat. #2140.73

Cat. #2140.75 (For Cat. #2136.42 only)

The voltage and current inputs, as well as the

power cord connection are constructed with screw on, watertight connectors rated to

IP67.

Page 3: SPECIFICATIONS - Instrumart · 2017-02-02 · • Calculation of Crest Factors for V and A • Calculation of the K-Factor for transformers • Calculation of short-term flicker and

www.aemc.com Technical Assistance (800) 343-1391

POWER QUALITY ANALYZERS, METERS & LOGGERS Optional Accessories

SENSOR TYPE CURRENT RANGE ACCURACY (TYPICAL)

TYPICAL ERROR

ON Φ AT 50/60HZ

MAX CONDUCTOR

SIZE

USED WITH MODEL

LIMITED RANGE IF

USED WITH MODEL

CATALOG NUMBER

MiniFlex® MA193-BK *

100mA to 3000Aac ±1% 0° 2.75" (70mm)

PEL 102 PEL 103 PEL 105

8333 8336

8220 8230 8435

2140.48 (10" sensor)

2140.50 (14" sensor)

MR193-BK

1 to 1000Aac

1 to 1300Adc±2.5% -0.80° 1.6"

(41mm)

8220 8230

PEL 102 PEL 103 PEL 105

8333 8336 8435

N/A 2140.28

SR193-BK

1 to 1200Aac ±0.3% 0.2° 2.05" (52mm)

8220 8230

PEL 102 PEL 103 PEL 105

8333 8336 8435

N/A 2140.33

AmpFlex® 193-BK *

100mA to 12,000Aac ±1% 0°

7.64" (190mm)

or11.46"

(290mm)

PEL 102 PEL 103 PEL 105

8333 8336

8220 8230 8435

2140.34 (24" sensor)

2140.35 (36" sensor)

AmpFlex® A196

10 to 10,000Aac ±2% 0° 5.73" (145mm)

PEL 105 8435 N/A 2140.75

(24" sensor)

* Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.

Battery operated

10" or 14" sensor

24" or 36" sensor

24" sensor IP67

Page 4: SPECIFICATIONS - Instrumart · 2017-02-02 · • Calculation of Crest Factors for V and A • Calculation of the K-Factor for transformers • Calculation of short-term flicker and

Technical Assistance (800) 343-1391 www.aemc.com

POWER QUALITY ANALYZERS, METERS & LOGGERS Optional Accessories

SENSOR TYPE CURRENT RANGE ACCURACY (TYPICAL)

TYPICAL ERROR

ON Φ AT 50/60HZ

MAX CONDUCTOR

SIZE

USED WITH MODEL

LIMITED RANGE IF

USED WITH MODEL

CATALOG NUMBER

MN93-BK

0.5 to 240Aac ±1% 0.8° 0.78" (20mm)

PEL 102 PEL 103 PEL 105

8333 8336 8435

8220 8230 2140.32

MN193-BK

100A 200mA to 120Aac ±1% 0.75°

0.78" (20mm)

8220 8230

PEL 102 PEL 103 PEL 105

8333 8336 8435

N/A 2140.36

5A 5mA to 6Aac ±1% 1.7°

SL261 **

100A 5 to 100Aac/dc ±4% ±0.5°

0.46" (11.8mm)

8220 8230

PEL 102 PEL 103 PEL 105

8333 8336 8435

N/A 1201.51

10A 50mA to 10Aac/dc ±3% ±1°

J93

50 to 3500Aac

50 to 5000Adc±1% ±1°

2.83" (72mm)

Busbar: 5 x 1.69"

(127 x 43mm)

PEL 102 PEL 103 PEL 105

8333 8336 8435

N/A 2140.49

Note: Refer to the Power Meter’s product user manual for complete specifications.

All current sensors can be used with the Models 8435 and PEL 105. However, only the A196 flexible sensors are waterproof.

** AC/DC Current Probe BNC Adapter for Model SL261 only Catalog #2140.40

Battery operated

Battery operated

CATALOG NO. DESCRIPTION

1201.51 AC/DC Current Probe Model SL261 (BNC)

2140.37 Adapter – US 110V Power Adapter (eliminates need for batteries) 8220 & 8230 only

2140.28 AC/DC Current Probe Model MR193-BK

2140.32 AC Current Probe Model MN93-BK

2140.33 AC Current Probe Model SR193-BK

2140.34 AmpFlex® Sensor 24" Model 193-24-BK

2140.35 AmpFlex® Sensor 36" Model 193-36-BK

2140.36 AC Current Probe Model MN193-BK

2140.48 MiniFlex® Sensor 10" Model MA193-10-BK

2140.49 AC/DC Current Probe Model J93-BK

2140.50 MiniFlex® Sensor 14" Model MA193-14-BK

2140.75 AmpFlex® Sensor 24" (waterproof - IP67) Model A196-24-BK

Page 5: SPECIFICATIONS - Instrumart · 2017-02-02 · • Calculation of Crest Factors for V and A • Calculation of the K-Factor for transformers • Calculation of short-term flicker and

www.aemc.com Technical Assistance (800) 343-1391

Data Analysis and Reporting Software

DATAVIEW® Software for Power & Energy Loggers

Configure all functions of the Power & Energy Loggers

• Display and analyze real-time data on your PC

• Configure functions and parameters from your PC

• Customize views, templates and reports to your exact needs

• Create and store a complete library of configurations thatcan be uploaded as needed

• Zoom in and out and pan through sections of the graph to analyze the data

• Download, display and analyze recorded data

• Display waveforms, trend graphs, harmonic spectrums,text summaries, transients, event logs and stored alarms

• Print reports using standard or custom templates you design• Free updates are available on our website www.aemc.com

Typical DataView® Functional, Digital & Graphical Displays

Clear and easy setup of all functions from one tabbed dialog box.

Display power and energy parameters – both instantaneous and total.

Display harmonics in a text table from harmonic 0 (DC) through the 50th.Display real-time Phasor diagrams.

Includes unbalance for both voltage and current.

Display real-time waveforms by phase, parameter or total.

Display all harmonics from 1st to 50th in bar graph form for voltage, current and power.