Specification Bulletin 911-31December 19, 2011 ©S&C Electric Company
S&C Cypoxy® InsulatorsIndoor and Outdoor Distribution (4.8 kV through 46 kV)
Conditions of Sale
STANDARD: Seller’s standard conditions of sale set forth in Price Sheet 150 apply.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: S&C Cypoxy Insulators are manufactured utilizing S&C’s proprietary Cypoxy cycloaliphatic epoxy resin system. The Cypoxy material is nontracking, self-scouring, and nonweathering. The standard color for S&C Cypoxy Insulators is gray. No other colors are available.
S&C Cypoxy Insulators are furnished with embedded aluminum inserts, threaded to accommodate standard galvanized bolts. As noted in the appropriate tables on
pages 2 through 6, the sets of inserts at the two ends of S&C Apparatus Insulators are furnished in one of two standard configurations: either in-line or with a 90° offset relative to each other.
EXCLUSIONS: S&C Cypoxy Insulators do not include mounting hardware.
How to Order
1. Obtain the catalog number of the desired Cypoxy Insulator from the tables on pages 2 through 6.
2. Obtain the suffix letter of spacer-adapters, if desired, from the table on page 7.
S&C Cypoxy® Insulators
2 S&C Specification Bulletin 911-31
OUTDOOR STATION POST INSULATORS1
TypeInsert
Configuration
Rating, kV Height, Inches (mm)
Leakage Distance,
Inches (mm)
Creepage Distance, mm/kV2
Cantilever Strength,
Pounds34
Catalog Number
Page Reference for Dimensional InformationNominal BIL
Apparatus
In-Line
4 inserts each end, 30 (76 mm) bolt spacing;
Z\x0–13 3 C\v0 tapped holes
14.4 11010
(254)16M\, (429)
29.8 2000 PA-7252R1 8
25/34.5h 15014
(356)26Z\v (667)
26.7 2000 PA-7253R1 8
34.5 20018
(457)37C\, (949)
27.5 2000 PA-7254R1 8
46 25022
(559)57C\,
(1457)31.7 2000 PA-7255 8
1 S&C Cypoxy station post insulators meet or exceed the electrical and mechanical-strength requirements established in ANSI Standard C29.9 (1983) for porcelain standard-strength station post insulators.
2 Calculated at nominal voltage.
3 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator. Furthermore, the mounting surface must be free of protrusions, such as lumps from galvanizing, to prevent cracking of the insulator when mounting bolts are tightened.
4 These insulators have tapered root diameters. To attain the rated cantilever strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
h Applicable at 34.5 kV where the leakage distance to ground meets user’s requirements.
S&C Cypoxy® Insulators
S&C Specification Bulletin 911-31 3
1 Calculated at nominal voltage.2 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator. Furthermore, the mounting surface must be free of protrusions, such as lumps from galvanizing, to prevent cracking of the insulator when mounting bolts are tightened.l This insulator serves as a blade spacer in S&C Regulator Bypass Switches—Type XL. When used alone its nominal rating is 600 volts.
d This insulator has tapered root diameters. To attain the rated cantile-ver strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.f For indoor use only, when applied at 34.5 kV.
a Supersedes Catalog Number PA-7193. When replacing Insulator Catalog Number PA-7193, specify one Spacer-Adapter Catalog Number S-86542.
INDOOR-OUTDOOR INSULATORS
TypeInsert
Configuration
Rating, kV Height, Inches (mm)
Leakage Distance,
Inches (mm)
Creepage Distance, mm/kV1
Cantilever Strength, Pounds2
Catalog Number
Page Reference for Dimensional InformationNominal BIL
Apparatus
90° Offset
2 inserts each end, 2Z\v0 (57 mm) bolt
spacing; Z\,0–16 3 B\,0 tapped holes
14.4 1106 C\v
(171)14Z\, (359)
24.9 1200 PA-7191d 9
25 15010
(254)24Z\, (613)
24.5 1000 PA-7192d 9
In-Line
4 inserts each end, 30 (76 mm) bolt spacing;
Z\x0–13 3 C\v0 tapped holes
34.5 20014
(356)26Z\v (667)
19.3 2000 PA-7253R1dfa 9
Specialty
In-Line
1 insert each end, centered;
Z\x0–13 3 C\,0 tapped hole
l 452 C\v (70)
2C\v (70)
116.7 600 PA-7188 9
S&C Cypoxy® Insulators
4 S&C Specification Bulletin 911-31
1 Calculated at nominal voltage.2 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator. Furthermore, the mounting surface must be free of protrusions, such as lumps from galvanizing, to prevent cracking of the insulator when mounting bolts are tightened.
• PA-7205 has 4 inserts at each end with a 2-inch bolt spacing.d This insulator has tapered root diameters. To attain the rated canti-lever strength, the end with the larger root diameter must be oriented toward the mounting surface.
INDOOR INSULATORS
TypeInsert
Configuration
Rating, kV Height, Inches (mm)
Leakage Distance,
Inches (mm)
Creepage Distance, mm/kV1
Cantilever Strength, Pounds2
Catalog Number
Page Reference for Dimensional InformationNominal BIL
Bus
In-Line
1 insert each end, centered;
Z\x0–13 3 C\,0 tapped hole
4.8 603Z\x (89)
4M\, (124)
25.8 1000 PA-7164d 10
13.8 956
(152)12Z\,
(308)22.3 1250 PA-7163d 10
Apparatus
90° Offset
2 inserts each end, 30 (76 mm) bolt spacing;
Z\x0–13 3 C\v0 tapped holes
4.8 605
(127)7 C\v
(197)41.0 1250 PA-7166 10
13.8 957Z\x
(191)13
(330)23.9 1250 PA-7162d 10
In-Line
2 inserts each end, 20 (51 mm) bolt spacing and
2 inserts each end, 1C\,0 (35 mm) bolt spacing•;
C\,–16 3 B\,0 tapped holes
13.8 956Z\v
(159)12Z\v (311)
22.5 1250 PA-7181 10
25 1257Z\x
(191)18Z\x (470)
18.8 1000 PA-7183 10
25 15010
(254)26Z\, (664)
26.6 1000 PA-7205• 10
TABLE CONTINUED v
S&C Cypoxy® Insulators
S&C Specification Bulletin 911-31 5
1 Calculated at nominal voltage.
2 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator. Furthermore, the mounting surface must be free of protrusions, such as lumps from galvanizing, to prevent cracking of the insulator when mounting bolts are tightened.
3 These insulators have tapered root diameters. To attain the rated cantilever strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
INDOOR INSULATORS—Continued
TypeInsert
Configuration
Rating, kV Height, Inches (mm)
Leakage Distance,
Inches (mm)
Creepage Distance, mm/kV1
Cantilever Strength,
Pounds23
Catalog Number
Page Reference for Dimensional InformationNominal BIL
Apparatus
In-Line
2 inserts, 20 (51 mm) bolt spacing,
C\,0–16 3 B\,0 tapped holes 1 insert, center;
B\,0–11 3 M\,0 tapped hole
4 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes
5 603Z\x (89)
6 (152)
30.5 2000 PA-7310 11
15 956
(152)12Z\v (311)
20.7 1250 PA-7280 11
25 125
7Z\x (191)
18Z\x (470)
18.8 1000 PA-7290 11
8Z\x (216)
22Z\x (572)
22.9 1000 PA-7340 11
In-Line
2 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes 1 insert, center;
B\,0–11 3 M\,0 tapped hole
2 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes
5 603Z\x (89)
6 (152)
30.5 2000 PA-7311 11
15 956
(152)12Z\v (311)
20.7 1250 PA-7281 11
25 125
7Z\x (191)
18Z\x (470)
18.8 1000 PA-7291 11
8Z\x (216)
22Z\x (572)
22.9 1000 PA-7341 11
TABLE CONTINUED v
S&C Cypoxy® Insulators
6 S&C Specification Bulletin 911-31
1 Calculated at nominal voltage.
2 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator. Furthermore, the mounting surface must be free of protrusions, such as lumps from galvanizing, to prevent cracking of the insulator when mounting bolts are tightened.
3 These insulators have tapered root diameters. To attain the rated cantilever strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
INDOOR INSULATORS—Continued
TypeInsert
Configuration
Rating, kV Height, Inches (mm)
Leakage Distance,
Inches (mm)
Creepage Distance, mm/kV1
Cantilever Strength,
Pounds23
Catalog Number
Page Reference for Dimensional InformationNominal BIL
Apparatus
In-Line
2 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes
4 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes
5 603Z\x (89)
6 (152)
30.5 2000 PA-7312 11
15 956
(152)12Z\v (311)
20.7 1250 PA-7282 11
25 125
7Z\x (191)
18Z\x (470)
18.8 1000 PA-7292 11
8Z\x (216)
22Z\x (572)
22.9 1000 PA-7342 11
In-Line
4 inserts, 20 (51 mm) bolt spacing;
C\,0–16 3 B\,0 tapped holes
4 inserts, 20 (51 mm) bolt spacing;
C\,–16 3 B\,0 tapped holes
5 603Z\x (89)
6 (152)
30.5 2000 PA-7313 11
15 956
(152)12Z\v (311)
20.7 1250 PA-7283 11
25 125
7Z\x (191)
18Z\x (470)
18.8 1000 PA-7293 11
8Z\x (216)
22Z\x (572)
22.9 1000 PA-7343 11
S&C Cypoxy® Insulators
S&C Specification Bulletin 911-31 7
SPACER-ADAPTERS
Illustration DescriptionHeight, Inches (mm)
For use with Insulator
Catalog NumberCatalog Number
Galvanized stamped steel—for use in adapting 30 (76 mm) insulator-bolt spacing (for Z\x0–13 bolts) to 2Z\v0 (57 mm) bolt spacing (holes at 2Z\v0 [57 mm] bolt spacing are tapped for C\,0–16 bolts)
ZB\zn (24)
PA-7166
PA-7162
PA-7193
S-82274-1
Galvanized stamped steel—for use in adapting 2Z\v0 (57 mm) insulator-bolt spacing (for C\,0–16 bolts) to 30 (76 mm) bolt spacing (for Z\x0–13 bolts)
ZB\zn (24)
PA-7191
PA-7192S-82274-2
Galvanized stamped steel—for use in adapting 20 (51 mm) insulator-bolt spacing (for C\,0–16 bolts) to 30 (76 mm) bolt spacing (for Z\x0–13 bolts)
ZB\zn (24)
PA-7181
PA-7183S-82274-3
Galvanized stamped steel—for use in adapting 1C\,0 (35 mm) insulator-bolt spacing (for C\,0–16 bolts) to 30 (76 mm) bolt spacing (for Z\x0–13 bolts)
ZB\zn (24)
PA-7181
PA-7183S-82274-4
Cast aluminum alloy—for use in adapting 1C\,0 (35 mm) insulator-bolt spacing and 20 (51 mm) insulator-bolt spacing (for C\,0–16 bolts) to 30 (76 mm) bolt spacing (holes at 30 [76 mm] bolt spacing are tapped for Z\x0–13 bolts)
C\v (19)
PA-7181
PA-7183S-86016
Outdoor Station Post Insulators
S&C Cypoxy® Insulators
8 S&C Specification Bulletin 911-31
1 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator.
2 These insulators have tapered root diameters. To attain the rated cantilever strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
Type
Ratings
Leakage Distance,
Inches (mm)
Dry Arcing
Distance, Inches (mm)
Mechanical Strength Rating, Pounds
Catalog Number
T.R. Number
(for corre- sponding porcelain
station post
insulator)
Dimensions in Inches (mm)
Net Weight,
Lbs. (Kg.)Nom. BIL
Low Fre-
quency With- stand, 1 Min.
Dry
Low Fre-
quency With- stand, 10 Sec.
Wet
Canti- lever12 Tensile
Com- pression
H D1
Apparatus
14.4
25
34.5
46
110
150
200
250
70
95
95
120
60
80
80
100
16M\, (429)
26Z\v (667)
37C\, (949)
57C\, (1457)
10 (254)
14 (356)
18 (457)
22 (559)
2000
2000
2000
2000
10 000
10 000
12 000
14 000
20 000
20 000
20 000
20 000
PA-7252R1
PA-7253R1
PA-7254R1
PA-7255
205
208
210
214
10 (254)
14 (356)
18 (457)
22 (559)
5 (127)
5Z\v (133)
6 (152)
6Z\x (165)
10 (4.5)
15 (6.8)
21 (9.5)
32 (14.4)
3 (76)
4C\,(111)
C\v (19)
3(76)
3(76)
3 (76)
CATALOG NUMBERSPA-7252R1, PA-7253R1, AND PA-7254R1
Dimensions in inches (mm)
Indoor-Outdoor Insulators
S&C Cypoxy® Insulators
S&C Specification Bulletin 911-31 9
1 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator.
l This insulator serves as a blade spacer in S&C Regulator Bypass Switches—Type XL. When used alone its nominal rating is 600 volts.
d This insulator has tapered root diameters. To attain the rated cantile-ver strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
f For indoor use only, when applied at 34.5 kV.h Tapped oversize for galvanized steel hardware.
Type
Ratings
Leakage Distance,
Inches (mm)
Dry Arcing
Distance, Inches (mm)
Mechanical Strength Rating, Pounds
Catalog Number
Dimensions in Inches (mm)
Insert Thread
Size
Net Weight,
Lbs. (Kg.)Nom. BIL
Low Fre-
quency With- stand, 1 Min.
Dry
Low Fre-
quency With- stand, 10 Sec.
Wet
Canti- lever1 Tensile
Com- pression
H R S
Apparatus
14.4
25
34.5
110
150
200
50
70
95
45
60
80
14Z\, (359)
24Z\, (613)
26Z\v (667)
6C\v (171)
10 (254)
14 (356)
1200
1000
2000
5 000
5 000
10 000
20 000
20 000
20 000
PA-7191d
PA-7192d
PA-7253R1df
6C\v (171)
10 (254)
14 (356)
Z\v (6)
Z\v (6)
—
B\,
(16)
B\,
(16)
C\v (19)
C\,0–16 h
C\,0–16 h
Z\x0–13 h
4Z\x (2.0)
7 (3.2)
15 (6.8)
Specialty l 45 15 —2C\v (70)
2Z\v (57)
600 3 000 20 000 PA-71882C\v (70)
—C\v
(19)Z\x0–13
1 (0.5)
3 (76)
1B\,(41)
4(102)
4C\, (111)
2Z\v (57)
2Z\v(57)
3(76)
3(76)
5Z\v (133)
3 (76)
Dimensions in inches (mm)
Indoor Insulators
S&C Cypoxy® Insulators
10 S&C Specification Bulletin 911-31
1 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator.d This insulator has tapered root diameters. To attain the rated cantile-
ver strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.f Tapped oversize for galvanized steel hardware.
Type
Ratings
Leakage Distance,
Inches (mm)
Dry Arcing
Distance, Inches (mm)
Mechanical Strength Rating, Pounds
Catalog Number
Dimensions in Inches (mm)
Insert Thread
Size
Net Wt, Lbs. (Kg.)Nom. BIL
Low Fre-
quency With- stand, 1 Min.
Dry
Low Fre-
quency With- stand, 10 Sec.
Wet
Canti- lever1 Tensile
Com- pression
H D1 D2 R S
Bus 4.8
13.8
60
95
19
36
15
26
4M\, (124)12Z\, (308)
3Z\x (89)
6 (152)
1000
1250
2000
3000
20 000
20 000
PA-7164d
PA-7163d
3Z\x (89)
6 (152)
3 (76)3Z\v (83)
2Z\x (64)2C\v (70)
Z\v (6)C\,
(10)
C\v (19)C\v
(19)
Z\x0–13 f
Z\x0–13 f
1Z\x (0.7)2Z\x
(1.1)
Apparatus
4.8
13.8
13.8
25
25
60
95
95
125
150
19
36
36
60
60
15
26
26
40
40
7C\v (197)
13 (330)12Z\v (311)18Z\x (470)26Z\, (664)
5 (127)7Z\x
(191)6Z\v
(159)7Z\x
(191)10
(254)
1250
1250
1250
1000
1000
3000
3000
3000
3000
5000
20 000
20 000
20 000
20 000
20 000
PA-7166
PA-7162d
PA-7181
PA-7183
PA-7205
5 (127)7Z\x
(191)6Z\v
(159)7Z\x
(191)10
(254)
4C\, (111)4C\,
(111)3C\v
(95)4
(102)4
(102)
—
—
—
—
—
Z\, (3)Z\, (3)Z\v (6)Z\v (6)Z\v (6)
C\v (19)C\v
(19)B\,
(16)B\,
(16)B\,
(16)
Z\x0–13 f
Z\x0–13 f
C\,0–16 f
C\,0–16 f
C\,0–16
4Z\v (1.9)5C\v
(2.6)4
(1.8)4M\,
(2.2)6Z\x
(2.9)
3(76)
2(51)
2(51)
2 (51)
3 (76)
2 (51)
1C\,(35)
2(51)
2(51)
1C\,(35)
Dimensions in inches (mm)
Indoor Insulators—Continued
S&C Cypoxy® Insulators
S&C Specification Bulletin 911-31 11
1 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator.
2 This insulator has tapered root diameters. To attain the rated cantile-ver strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
Type
Ratings
Leakage Distance,
Inches (mm)
Dry Arcing
Distance, Inches (mm)
Mechanical Strength Rating, Pounds
Catalog Number
Dimensions in Inches (mm)
Insert Thread
Size
Net Wt, Lbs. (Kg.)Nom. BIL
Low Fre-
quency With- stand, 1 Min.
Dry
Low Fre-
quency With- stand, 10 Sec.
Wet
Canti- lever 12
Tensile Com- pression D1 D2 H R S
Appar- atus
5 60 19 15 6 (152)
3Z\x (89) 2000 2000 20 000
PA-7310PA-7311
3B\, (92)
3C\, (86)
3Z\x (89)
Center insert: Z\v (6)
20 bolt spacing inserts; Z\v (6)
Center insert: M\, (22)
20 bolt spacing inserts; B\, (16 )
Center insert:
B\,0– (11 )
20 bolt spacing inserts; C\,0 (16 )
2Z\, (1.0)
15 95 36 26 12Z\v (311)
6 (152) 1250 3000 20 000
PA-7280PA-7281
3M\, (98)
3C\v
(95)6
(152)3Z\x
(1.6)
25 125 60 40
18Z\x (470)
7Z\x (191) 1000 3000 20 000
PA-7290PA-7291
4 (102)
4 (102)
7Z\x (191)
4M\, (2.2)
22Z\x (572)
8Z\x (216) 1000 3000 20 000
PA-7340PA-7341
4 (102)
4 (102)
8Z\x (216)
5Z\, (2.3)
2 (51)
2 (51)
D1
D2
2 (51)
H
D1
D2
2 (51)
H
CATALOG NUMBERS PA-7280, PA-7290,
PA-7310, AND PA-7340
CATALOG NUMBERS PA-7281, PA-7291, PA-7311, AND 7341
2 (51)
CATALOG NUMBERSPA-7280, PA-7290,
PA-7310, AND PA-7340
CATALOG NUMBERSPA-7281, PA-7291,
PA-7311, AND PA-7341
Dimensions in inches (mm)
Indoor Insulators—Continued
S&C Cypoxy® Insulators
12 S&C Specification Bulletin 911-31
1 To attain their rated cantilever strengths, Cypoxy Insulators must be mounted on a flat surface that is at least as wide as the diameter of the base of the insulator.
2 This insulator has tapered root diameters. To attain the rated cantile-ver strength, the end with the larger root diameter (marked “Base”) must be oriented toward the mounting surface.
Type
Ratings
Leakage Distance,
Inches (mm)
Dry Arcing
Distance, Inches (mm)
Mechanical Strength Rating, Pounds
Catalog Number
Dimensions in Inches (mm)
Insert Thread
Size
Net Wt, Lbs. (Kg.)Nom. BIL
Low Fre-
quency With- stand,
1 Min. Dry
Low Fre-
quency With- stand, 10 Sec.
Wet
Canti- lever 12
TensileCom-
pressionD1 D2 H
Apparatus
5 60 19 15 6 (152)
3Z\x (89) 2000 2000 20 000
PA-7312PA-7313
3B\, (92)
3C\, (86)
3Z\x (89)
C\,0– (16 )
2Z\, (1.0)
15 95 36 26 12Z\v (311)
6 (152) 1250 3000 20 000
PA-7282PA-7283
3M\, (98)
3C\v
(95)6
(152)3Z\x
(1.6)
25 125 60 40
18Z\x (470)
7Z\x (191) 1000 3000 20 000
PA-7292PA-7293
4 (102)
4 (102)
7Z\x (191)
4M\, (2.2)
22Z\x (572)
8Z\x (216) 1000 3000 20 000
PA-7342PA-7343
4 (102)
4 (102)
8Z\x (216)
5Z\, (2.3)
CATALOG NUMBERSPA-7282, PA-7292,
PA-7312, AND PA-7342
CATALOG NUMBERSPA-7283, PA-7293,
PA-7313, AND PA-7343
Dimensions in inches (mm)