spca rsb gb - calor · general the spca-rsb series air-cooled water chillers consists of 9 models...
TRANSCRIPT
PACKAGED AIR COOLED WATER CHILLERCOOLING ONLYOUTDOOR INSTALLATIONWITH BUILT IN HYDRAULIC MODULE
Cooling Capacity: 5,8kW - 31,8kWR407c - Scroll
FeaturesOptimized design for R407c refrigerant.Casing:galvanized steel plate with polyesteric coating.
Assemblyfully bolted/welding free.
Built in complete hydraulic module.Compressor:hermetically sealed scroll type.
Air heat exchanger:cross fin coil.internally grooved copper tubes and louvered aluminium fins.
Direct drive propeler fanlow rpm, quiet operation.
Water heat exchangerPlate heat exchanger.
Safety and functional devices- high/low pressure switch.- linear fan speed regulation according to coil temperature.- differential water pressostat.- plate heat exchanger low temperature protection.- electronic microprosessor control with digital display.
The Interklima SPCA - RSB small capacityseries are packaged air cooled water chillersfor cooling applications and outdoorinstallation. They are available in 9 modelswith nominal capacities ranging from 5,8 to31,8 kW.
This series is ideal in combination withInterklima fan coils or air handing units forresidential and light commercial applicationsor for supplying chilled water for smallindustrial applications.
SPCA 001-010RSB
NOMENCLATURE
1 RangeS-small M-mid L-large R-screw-series
2 Packaged Chiller Air-cooledPCA
3 Model number001-002-003-004-005-006-007-010
4 Cool / Heat ModelR-cooling only H-heat pump
5 Compressor typeS-scroll M-tandem scroll R-reciprocatingT-twin screw
6 Refrigerant typeA-R22 B-R407c
7 Electrical Characteristic-1 Single phase -Ommited Three phase
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 3
1. Technical Description
2. Specifications
3. Capacity Tables
4. Available External Water Pressure Curves
5. Operation Range
6. Sound Data
7. Outlook Drawings
8. Refrigerant Circuit Diagrams
9. Wiring Diagrams
10. Installation
11. Guide Specifications
Contents
GeneralThe SPCA-RSB series air-cooled water chillers consists of 9models covering capacities from 5,8 up to 31,8kW.It is the end result of a thorough study, and accurate design byexperienced Interklima research and development teams, todevelop a small size chiller series with compact shape, highperformance, and reliability of the highest quality standards.This series meets the highest levels of aesthetic and technicalrequirements using the latest technological innovations includingenvironmentally friendly R407c refrigerant that is Chlorine-freeand has zero ozone depletion potential. SPCA-RSB units aretherefore ideal for installation in urban environments due to theirelegant design, selected materials and low operating sound levels.
CasingAll units use metal parts fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that guarantees andpreserves the units operation during the years. After fabrication metalparts are degreased, phosphatised, and electrostatically powdercoated with an epoxy-polyester RAL 9002 coating of a thickness of60-70Ì. This fully automatic process ensures superior corrosionresistance against the most aggressive ambient conditions. Thetreatment can successfully withstand a salt spray test of 500 hours,according to ASTM B-117.All components are assembled together using bolts thus avoidingthe need for welding which may harm the galvanization of thesteel, and ensures that the whole assembly can fully withstandadverse weather conditions.The compact footprint of the unit arises from detailed study anddesign by our engineering teams and results in a machine, whichfits easily in restricted areas and is simple and easy to install andmaintain, and has been designed with special fittings for easytransport and lifting.Removable panels with special locks are used to permit access onlyto authorized personnel to internal components of the unit forinspection and maintenance.
CompressorAll units' use low-noise, maintenance free, Hermetic Scrollcompressor with low vibration levels, specially optimized for usewith R407c refrigerant, selected from world class suppliers.They are equipped with a crankcase electrical heater for the oil,and are internally protected against potential overloading orelectrical spikes.The compressors are mounted on special antivibration rubbermounts to eliminate vibration from the unit's operation.
Hydraulic kitAll units are equipped, as standard, with a complete hydraulic kitcomprising of a circulating pump, buffer and expansion tank,automatic fill and make up water valve with manometer, safetyvalve, airvent, water filter, differential water pressure switch, andevacuation valve.
Condenser coil All unit air heat exchangers are manufactured from high quality innergrooved seamless copper tubes according to ASTM B-280, havingan outside diameter of 9,52 mm (3/8"). The fins are manufacturedfrom aluminium and form the secondary extended heat transfersurface. The fins are continuous across the heat exchanger and arefabricated in high precision dedicated press lines. The fin surface iswaffle formed, so as to increase the fin rigidity, and have speciallouvers that help increase heat transfer. The combination ofinternally grooved Copper-tubing and louvered fins has resulted in aheat transfer performance 30% superior to that of a conventionalcoil for this particular application. The assembly of the finned packis achieved by mechanical expansion of the tubes in such a way asto form a perfect mechanical bond with the fins. For this purpose,the fin holes have a peripheral extrusion (collar) of adjustable height.This extrusion serves to define the distance between fins (andconsequently the total heat transfer surface) and to ensure perfectcontact of the fins to the tubes.Alternative fin materials are available upon request such as epoxy- coated aluminium or copper for applications in especiallyaggressive environments.
EvaporatorAll units are equiped with a water - refrigerant Plate HeatExchanger, selected from world class manufacturers.It is made of stainless steel plates (AISI 3161.4401) speciallyformed to achieved a large heat transfer surface and assembledby means of an automatic brazing proccess under vaccum.
Condenser fansAll unit fans are of the axial type, single phase, 6 poles, internallyprotected against potential overheating, silent and suitable foroutdoor installation. Due to the sophisticated aerodynamic designof the blades and inlet cones, as well as the perfect static anddynamic balancing, their operation is completely vibration-free. Thefan-motor assembly has a protective grid against accidentalcontact with moving parts, which is designed according to ISOregulations. Fan motors are of the external rotor type,aerodynamically shaped so as not to interfere with the airflow, and
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll4
Technical Description1.
have permanently lubricated bearings that do not require servicing.Continuous linear fan speed regulation control is achievedaccording to coil temperatures including fan silent mode operation.This standard feature for Interklima SPCA units saves energy andreduces sound levels dramatically, optimizing capacity.
Microprocessor controllerAll units are equipped with a sophisticated controller easilyaccessible from outside through a transparent plastic cover thatcombines intelligence with operating simplicity. The controllerconstantly monitors all machine parameters and preciselymanages among others: ñ Automatic compressor control function through return water
temperature.ñ Continuous fan speed control based on coil heat exchanger
temperature.ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Over 150 programmable parameters.ñ Fan motor overload protection.ñ Auto diagnostic stop function due to low water circulation,
high/low operating pressures, and compressor thermaloverload.
ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.
ñ Digital displays of water inlet / outlet as well as coiltemperatures.
ñ Remote on/ off switch.ñ Remote alarm indication capability.ñ Many optional control capabilities (listed in optional
accessories).
Refrigerant circuitAll units have a single refrigerant circuit with one compressor.Thecircuit consists, depending on the size, of either a capillary orthermal expansion valve. Other components fitted are solenoidvalve, and a large capacity filter dryer.Unit protection is provided by a high-pressure switch with manualreset, low-pressure protection is via a low-pressure switch.
Optional accessories
Microprocessor controller optionsñ Remote keyboard.ñ Dynamic set point program via a 4-20ma proportional signalñ BMS module interface kit for Modbus connection.ñ Parallel chiller operation with more than 2 units with optional
controller.ñ Microprocessor parameter reprogramming card.
Other unit accessories/optionñ R407c or R22 refrigerant.ñ Antifreeze protection.ñ Condenser fins made of copper or prepainted aluminum, or
blygold treatment for corrosion protection.ñ Glycol application for chilled water temperature down to -5oC.ñ Pressure relief valve on compressor discharge.ñ High / Low pressure manometers.ñ Phase sequence - phase failure - reverse phase and voltage
monitoring device.ñ Compressor noise reduction jacket.ñ Compressor chamber noise reduction kit.ñ Other custom built options upon request.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 5
2.Technical specifications
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll6
Type
Nominal cooling capacity
Construction
Compressor
Quantity
Absorbed power
Nominal operating current
Maximum operating current
Air heat exchanger
Water heat exchanger
Quantity
Water content
Max. Operating pressure
Connections
Nominal water flow
Water pressure drop
Minimum system water content
Maximum unit operating water pressure
Fan
Quantity
Speed
Total air flow
Absorbed power
Nominal operating current
Maximum operating current
Pump
Absorbed power
Maximum operating current
Available external water head
Electrical characteristics
Total absorbed power
Nominal operating current
Maximum operating current
Compressor carter resistance power
Power cables cross section
Fuses
Voltage operating limits
Refrigerant circuit
Number of circuits
Expansion device
Refrigerant type
Noise level at 5m
Dimensions
Shipping weight
kW
RT
Btu/hMaterial/Color
kW
A
A
l
Water side bar
Refrigerant side bar
l/h
kpa
l
bar
rpm
m3/h
kW
A
A
kW
A
Kpa
kW
A
A
W
mm2
A
V
dB(A)
Width mm
Length mm
Heigth mm
kg
SPCA-001-1 SPCA-002-1 SPCA-002 SPCA-003 SPCA-004
5,8
1,6
19.773
6,9
2,0
23.523
6,9
2,0
23.523
8,1
2,3
27.614
12,2
3,5
41.591
1
2,00
9,40
14,80
1
0,57
30
30
3/4"
998
26,5
29
3,0
1
2,40
11,10
17,30
1
0,66
30
30
3/4"
1.187
27,6
35
3,0
1
2,32
4,40
5,60
1
0,66
30
30
3/4"
1.187
27,6
35
3,0
1
2,70
5,00
7,00
1
0,76
30
30
1"
1.393
29,2
41
3,0
1
4,02
7,80
11,00
1
1,14
30
30
1"
2.098
29,9
61
3,0
1
920
2.500
0,12
0,57
0,63
0,13
0,58
35,0
2,3
10,6
16,0
70
4
25
1
45
474
1022
932
100
1
920
2.350
0,12
0,57
0,63
0,13
0,58
32,0
2,7
12,3
18,5
70
4
25
1
45
474
1022
932
108
1
920
2.350
0,12
0,57
0,63
0,13
0,58
32,0
2,6
5,6
6,8
70
2,5
3x16
1
46
474
1022
932
108
1
920
4.000
0,17
0,80
0,90
0,13
0,58
30,0
3,0
6,4
8,5
70
2,5
3x16
1
48
474
1222
982
140
2
920
4.600
0,24
1,14
1,26
0,25
1,1
42,0
4,5
10,0
13,4
70
2,5
3x16
1
48
522
1462
1002
180
Galvanized steel / Light grey-beige (RAL 9002)SCROLL
High capaci ty cross finned coi l wi th internally grooved tubes and louver fins
Brazed plate
Axial type
Capi llary tubes
R407c
230 V/1 ph/50 Hz 400 V/3 ph/50 Hz
360-440 V220-240 V
2.1 SPCA 001-010RSB
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 7
Type
Nominal cooling capacity
Construction
Compressor
Quantity
Absorbed power
Nominal operating current
Maximum operating current
Air heat exchanger
Water heat exchanger
Quantity
Water content
Max. Operating pressure
Connections
Nominal water flow
Water pressure drop
Minimum system water content
Maximum unit operating water pressure
Fan
Quantity
Speed
Total air flow
Absorbed power
Nominal operating current
Maximum operating current
Pump
Absorbed power
Maximum operating current
Available external water head
Electrical characteristics
Total absorbed power
Nominal operating current
Maximum operating current
Compressor carter resistance power
Power cables cross section
Fuses
Voltage operating limits
Refrigerant circuit
Number of circuits
Expansion device
Refrigerant type
Noise level at 5m
Dimensions
Shipping weight
kW
RT
Btu/hMaterial/Color
kW
A
A
l
Water side bar
Refrigerant side bar
l/h
kpa
l
bar
rpm
m3/h
kW
A
A
kW
A
Kpa
kW
A
A
W
mm2
A
V
dB(A)
Width mm
Length mm
Heigth mm
kg
SPCA-005 SPCA-006 SPCA-007 SPCA-010
14,6
4,14
49.773
18,5
5,36
63.068
22,4
6,47
76.364
31,8
9,010
108.409
1
4,70
8,30
13,00
1
1,35
30
30
1"
2.511
34,1
73
3,0
1
6,00
12,20
17,00
1
1,40
30
30
1 1/4"
3.182
34,6
93
3,0
1
7,20
14,50
20,00
1
1,70
30
30
1 1/4"
3.853
45,4
112
3,0
1
10,30
17,80
27,00
1
2,50
30
30
1 1/4"
5.470
24,4
159
3,0
2
920
6.200
0,34
1,60
1,80
0,30
2,00
130,0
5,3
11,9
16,8
70
4
3x25
1
51
522
1612
1002
200
2
920
6.400
0,34
1,60
1,80
0,45
2,70
150,0
6,8
16,5
21,5
70
6
3x25
1
52
605
1732
1202
270
2
920
10.500
0,74
3,40
3,80
0,45
2,70
120,0
8,4
20,6
26,5
70
6
3x32
1
53
800
2020
1202
320
2
920
11.000
0,74
3,40
3,80
0,55
3,50
165,0
11,6
24,7
34,3
70
10
3x40
1
55
800
2020
1202
350
Galvanized steel / Light grey-beige (RAL 9002)SCROLL
High capacity cross finned coil with internally grooved tubes and louver fins
Brazed plate
Axial type
Capi llary tubes Expansion valve / Capi llary tubes
400 V/3 ph/50 Hz
R407c
360-440 V
NOTESNominal conditions are asfollows
entering/leaving chilledwater temperature 12/7oC;ambient 35oC DB
electrical installationspecifications are purelyindicative and non-binding,all connections to thesystem and the electricalinstallation must be in fullaccordance with allapplicable national and localcodes.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll8
Capacity tables3.
SPCA-001-1
SPCA-002-1
SPCA-002
SPCA-003
SPCA-004
SPCA-005
SPCA-006
SPCA-007
SPCA-010
Water outlet ÆC
Coolingcapacity
kW
Absorbedpower
kWCurrent
A
Absorbedpower
kWCurrent
A
Coolingcapacity
kW
Absorbedpower
kWCurrent
A
Coolingcapacity
kW
Absorbedpower
kWCurrent
A
Coolingcapacity
kW
Absorbedpower
kW
25 30 35 40 45
CurrentA
Coolingcapacity
kW
5
7
10
5
7
10
5
7
10
5
7
10
5
7
10
5
7
10
5
7
10
5
7
10
5
7
10
6.1
6.7
7.5
7.3
8.0
8.9
7.2
7.9
8.8
8.5
9.2
10.4
12.8
14.0
15.7
15.4
16.7
18.7
19.3
21.0
23.6
23.5
25.4
28.4
33.4
36.1
40.4
1.6
1.6
1.6
1.9
1.9
1.8
1.8
1.8
1.8
2.1
2.1
2.1
3.2
3.2
3.2
3.7
3.7
3.7
4.7
4.7
4.7
5.7
5.7
5.7
8.1
8.1
8.2
7.5
7.5
7.4
8.9
8.8
8.7
3.8
3.7
3.7
4.3
4.3
4.3
6.9
6.9
6.9
6.9
6.9
7.0
10.9
10.9
10.9
13.0
13.0
13.0
15.1
15.2
15.2
5.8
6.2
7.0
6.9
7.5
8.4
6.8
7.4
8.3
8.0
8.7
9.8
12.1
13.1
14.8
14.5
15.6
17.5
18.2
19.7
22.2
22.1
23.9
26.8
31.5
34.0
38.1
1.8
1.8
1.8
2.1
2.1
2.1
2.1
2.0
2.0
2.4
2.4
2.4
3.6
3.6
3.6
4.1
4.1
4.1
5.3
5.3
5.3
6.4
6.4
6.4
9.1
9.1
9.1
8.4
8.3
8.2
9.9
9.9
9.8
4.1
4.0
4.0
4.7
4.6
4.6
7.3
7.3
7.3
7.6
7.6
7.6
11.5
11.5
11.5
13.7
13.7
13.6
16.3
16.3
16.4
5.4
5.8
6.6
6.4
6.9
7.8
6.3
6.9
7.8
7.4
8.1
9.2
11.2
12.2
13.9
13.5
14.6
16.4
17.0
18.5
20.8
20.7
22.4
25.2
29.5
31.8
35.7
2.0
2.0
2.0
2.4
2.4
2.3
2.3
2.3
2.3
2.7
2.7
2.7
4.0
4.0
4.0
4.7
4.7
4.7
6.0
6.0
5.9
7.2
7.2
7.2
10.2
10.3
10.3
9.4
9.4
9.2
11.1
11.1
10.9
4.4
4.4
4.4
5.1
5.0
5.0
7.7
7.8
7.8
8.3
8.3
8.3
12.2
12.2
12.2
14.5
14.5
14.5
17.7
17.8
17.8
4.9
5.4
6.1
5.9
6.4
7.2
5.8
6.4
7.2
6.9
7.5
8.5
10.4
11.3
12.9
12.5
13.6
15.2
15.8
17.2
19.5
19.3
20.9
23.5
27.4
29.6
33.3
2.3
2.3
2.3
2.7
2.7
2.7
2.7
2.6
2.6
3.1
3.1
3.1
4.5
4.5
4.5
5.2
5.2
5.2
6.8
6.8
6.7
8.0
8.0
8.1
11.5
11.5
11.6
10.6
10.6
10.4
12.6
12.5
12.4
4.8
4.8
4.8
5.5
5.5
5.5
8.3
8.3
8.3
9.2
9.2
9.2
13.1
13.1
13.1
15.5
15.5
15.5
19.4
19.4
19.4
4.5
4.9
5.5
5.3
5.8
6.6
5.3
5.8
6.6
6.3
6.8
7.8
9.5
10.4
11.8
11.5
12.5
14.1
14.7
16.0
18.1
17.9
19.4
21.9
25.3
27.4
30.8
2.6
2.6
2.6
3.1
3.1
3.0
3.0
3.0
3.0
3.5
3.5
3.5
5.0
5.0
5.0
5.9
5.9
5.9
7.7
7.7
7.7
9.0
9.0
9.0
13.0
13.0
13.0
12.1
12.0
11.9
14.3
14.2
14.1
5.3
5.3
5.3
6.1
6.1
6.0
8.9
8.9
9.0
10.2
10.2
10.2
14.1
14.1
14.1
16.6
16.6
16.6
21.3
21.3
21.4
Type
Ambient temperature oC
Cooling capacity table for SPCA 001-010RSB
NOTESBold values show nominal cooling capacitiesAbsorbed power and current refers to the compressorAbove figures are valid for water ¢t = 5oC
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 9
90
80
70
60
50
40
30
20
10
00 500 1.000 2.000 3.0001.500 2.500 3.500 WF
PD
kpa
l/h
l/h
80
100120
140
160180
200220
240260280
300320340360
604020
00 500 1,000 2.000 3.0001,500 2.500 3.500 4.000 4.500 5.000 6.0005.500 WF
PD
kpa
001
002003
004
005
006
007
010
Available external water pressure curves4.
SPCA 001-010RSB
NOTESPD: pressure dropWF: water flow rate1. SPCA 001-002RSB2. SPCA 003RSB3. SPCA 004RSB4. SPCA 005RSB5. SPCA 006RSB6. SPCA 007-010RSB
% ETHYLENE GLYCOL BY VOLUME
Freezing point
Output duty
Input pow er
Equivalent Flow rate
Equivalent Pressure drop
ETHYLENE GLYCOL CORRECTION FACTORSUNIT 10oC
kW
kW
L/H
kPa
-4
0,99
0,99
1,02
1,06
20
-9
0,98
0,98
1,04
1,12
30
-15
0,97
0,98
1,08
1,18
40
-23
0,96
0,97
1,13
1,25
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll10
Operation range5.
Sound data6.
45
-5
0
6 15
Outdoor Temperature ( CDB)O
Leaving water temperature(oC)
4
47
NOTESProtect the water circuit against freezing
- The accompanying operating limits are for general guidance only.It may be possible for certain units to operate outside the confinesof the graph. Please contact Interklima if further clarification isrequired.
- For operation with leaving water temperature below 6 oC it isrequired to confirm with Interklima at the time of order and theaddition of glycol into the system.
SPCA - 001
SPCA - 002
SPCA - 003
SPCA - 004
SPCA - 005
SPCA - 006
SPCA - 007
SPCA - 010
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
dB(A)
66
58
39
67
59
39
68
60
40
70
62
42
71
64
44
74
66
46
75
67
47
77
69
49
63
49
41
21
49
41
21
51
43
23
52
44
24
54
46
26
54
46
26
54
46
26
54
46
26
125
55
47
27
55
47
27
56
48
28
58
50
30
59
51
31
59
51
31
60
52
32
60
52
32
250
56
48
28
56
48
28
57
49
29
59
51
31
60
52
32
61
53
33
60
52
32
61
53
33
500
58
50
30
58
50
30
59
51
31
61
53
33
61
53
33
69
61
41
69
61
41
70
62
42
1000
62
54
34
62
56
36
64
56
36
65
57
37
67
59
39
68
60
40
68
60
40
69
61
41
2000
59
51
31
61
55
35
62
54
34
63
55
35
64
56
36
67
59
39
70
62
42
73
65
45
4000
54
46
26
58
53
33
58
50
30
58
50
30
65
57
37
63
55
35
65
57
37
70
62
42
8000
49
41
21
48
42
22
49
41
21
50
42
22
53
45
25
50
42
22
50
42
22
57
49
29
Type Octave band center frequency (Hz)
491000
10221008
474460
932
450
474460
12221208
120051450
981
1440
14481462522
508
1002
500
1002
500
508522 1612
1598
1590
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 11
Outlook drawings7.
7.1 SPCA 001-002RSB
7.2 SPCA 003RSB
7.3 SPCA 004RSB
7.4 SPCA 005RSB
519
ma
t ie
ef
u b
.1
mm
0x
rhni s c
Ea
Germany
Mulfingen
R
th ep D
1
re
. xm
a
w
0m
m
sf
co
ma
t ie
ef
u b
.1
mm
0x
rhni s c
Ea
Germany
Mulfingen
R
th ep D
1
re
. xm
a
w
0m
m
sf
co
1202
17401754
173260540
50
137
40 2020800
1202
20282042
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll12
7.5 SPCA 006RSB
7.6 SPCA 007-010RSB
3
4
2
1
5.1
1
2
6
4
5.2
3 3
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 13
8.1 SPCA 001-005RSB
8.2 SPCA 006-010RSB
Refrigerant circuit diagrams8.
NOTES1. Compressor2. Plate heat exchanger3. Condenser coil
4. Filter dryer5.1 Capillary5.2 Thermal expansion valve6. Solenoid valve
VC
VC
C1
FM1
F
CCf1
CC PM
CC
CM
PE
L2
L1
L3
NF 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CP
CP
PM
C
FM2
Cf2
C1
FM1
F
CCf1
C1
FM1
F
CCf1
C2CC
VC
VC
CC
CM
PE
L2
L1
L3
NF 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
PMCM
CC
PE
L
N
C
C1
FM1
F
CCf1
CC
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll14
Wiring diagrams9.
9.1 SPCA 001-002RSB-1
9.2 SPCA 002-003RSB
9.3 SPCA 004-005RSB
CP
CP
PMSV
CC
T
C
C
FM2
Cf2
C1
FM1
F
CCf1
CC
C2VC
VC
CC
CM
PE
L2
L1
L3
NF 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 15
CP
CP
PMC2
SV
CC
CF 22 3334
F124
C
FM2
Cf2
C1
FM1
F
CCf1
T
C
FAN SPEEDCONTROLLER
VC
VC
CC
CM
PE
L2
L1
L3
NF 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
9.4 SPCA 006RSB
OFFON AL AL
SM1 GENERAL CIRCUIT BREAKER CC COMPRESSOR CONTACTOR CH COMPRESSOR CRANKCASE HEATER TR TRANSFORMER 220/2x12VAC HP HIGH PRESSURE PRESSOSTAT LP LOW PRESSURE PRESSOSTAT F CONTROL CIRCUIT BREAKER (2A) C1,2 COND, FANS 1, 2 CAPACITORS FS WATER DIFFERENTIAL PRESSOSTAT TC COMPRESSOR THERMAL PROTECTION
S1 ENTERING WATER SENSOR S2 LEAVING WATER SENSOR S3 CONDENSER COIL TEMPERATURE SENSOR A COMMAND 220VAC FOR ELECTRICAL HEATERS (OPTIONAL) CP PUMP CONTACTOR PM PUMP CM COMPRESSOR VC VOLTAGE SURVEYOR (OPTIONAL) SV LIQUID SOLENOID VALVE
ALARM
LEGEND
FIELD CONNECTIONS
ON -OFF REMOTE SWITCH (DRY CONTACT)AL-AL ALARM 12 V AC
E00:E01:E02:E03:
E05:E06:E07:E41:
REMOTE ON/OFF IN POSITION OFFHIGH PRESSURELOW PRESSURECOMPRESSOR THERMAL PROTECTION*(*ONLY FOR SPCA 006-010RSB)ANTIFREEZEPROBE ST2 FAULTPROBE ST3 FAULTWATER DIFFERENTIAL PRESSOSTAT
9.5 SPCA 007-010RSB
The SPCA-RSB unit should be installed in a location that meets thefollowing requirements:1. The foundation is strong enough to support the weight of the unit,
and the floor is flat to prevent vibration and noise generation.2. The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. If severalunits are being installed side by side in parallel, the minimumservice space between them must be taken into account
3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in
case it drips out the unit.5. Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind willdisturb the operation of the unit. If necessary, use awindscreen to block the wind.
6. In heavy snowfall areas, select an installation site where snowwill not affect operation of the unit.
7. Make sure that the unit mounting base can be fixed directly onconcrete.
8. In order to avoid the transmission of vibration from theoperating unit to its carrying structure, the use of antivibrationmaterial to install under the supports of the unit isrecommended. It is suggested to install a rubber pad betweenthe points of support and the base of the unit, or springantivibration mounts under each point of support of the unit.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll16
Installation10.
10.1 Selection of location - service space
10.2 Centre of gravity
400mm
500mm
500mm (1500mm for 006-010 models)
500mm
800mm
420
175 390
SPCA 001-002RSB
420
175 490
SPCA 003RSB
570200
420
SPCA 004RSB
200 620
420
SPCA 005RSB
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 17
ñ All units are equipped with a complete hydraulic kit as shownin the figure below.
ñ All field connections must be carried out by a licensedtechnician and must comply with the applicable local andnational codes.
ñ Evaporator water connections should be made in accordancewith the unit outlook respecting the water inlet and outlets.
ñ Connect a fresh water line to the water make up connection.The units are equipped with a automatic make up valve tofacilitate water make up.
ñ It is advisable to connect flexible water inlet and outlet tubesto avoid vibration transmission.
ñ The unit is operating in closed circuit. Avoid frequentunnecessary water evacuation.
ñ It is essential to install a thermometer in the water inlet/outletpipe to check temperatures.
ñ Provide heat insulation with suitable vapour barrier around thechilled water piping to prevent condensation and capacity loss.
ñ Provide drain connections at all low points of the system topermit complete drainage for maintenance and/ or shutdown.
ñ Air vents should be provided at all high points in the systemlocated where they are easily accessible for servicing. Thewater inlet pipe is specially designed to obtain a complete airpurge of the evaporator.
ñ To avoid frequent on/off operation of the compressor, aminimum water volume is required in the system (table 10.4)
ñ To assure proper operation of the unit, the water quality throughthe evaporator must be within the specified limits in (table 10.4).
10.3 Recomendations concerning the hydraulic circuit
590
250 650
SPCA 006RSB
590
350 750
SPCA 007-010RSB
NOTES1. Pump2. Plate heat exchanger3. Automatic make up water
valve with manometer4. Buffer tank (water accumulation)5. Expansion tank6. Airvent7. Pressure relief valve8. Differential water pressure switch9. Water filter
3,5-4 bar
17-19 bar
4-5 bar
21-23 bar
5,5-6 bar
24-26 bar
low pressure
high pressure
Minimum(outdoor temp. 15ÔCDB) (leaving water temp 6ÔC)
Nominal(outdoor temp. 35ÔCDB)(leaving water temp, 7ÔC)
Maximum(outdoor temp. 38ÔCDB)
(leaving water temp, 25ÔC)
Cooling mode(region)
To ensure proper operation of the unit, a minimum water volumeis required in the system and the water flow must be within theoperation range as specified in the table.
It is important to check the high and low pressure of therefrigerant circuit to ensure the proper operation of the unit andto guarantee that the rated output will be obtained.
Attention:The pressures measured will vary between a maximum and minimum value, depending on the water and ambient temperatures at the moment of measurement.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll18
10.4 Watercharge, flow and quality
10.5 Operating pressure of the refrigerant circuit.
29
35
35
41
61
73
93
112
159
SPCA-001-1RSB
SPCA-002-1RSB
SPCA-002RSB
SPCA-003RSB
SPCA-004RSB
SPCA-005RSB
SPCA-006RSB
SPCA-007RSB
SPCA-010RSB
Minimumwater
volume (l)
948
1127
1127
1324
1993
2386
3023
3660
5196
Minimumwater flow
(l/h)
997
1187
1187
1393
2098
2511
3182
3853
5469
Nominalwater flow
(l/h)
1097
1305
1305
1533
2308
2762
3500
4238
6017
Maximumwater flow
(l/h)
Items to be controlled:
PH AT 25ÔC
∂lectrical conduct (mS/m) at 25ÔC
Chloride ion (mg CI-/I)
Sulfate ion (mg SO 2/4/I
M-alkalinity (ph 4.8) (mg SO3/I)
Total hardness (mg CaCO3/I )
Calcium hardness (mg CaCO3/I)
Silica ion (mg SiO2/I
Items to be referred to:
Iron (mg Fe/I)
Copper (mg Cu/I)
Sulfide ion (mg S2-/I)
Amonium ion (mg NH+4/I
Remaining chloride (mg CI/I)
Free carbide (mg SO2/I)
Stability index
6.8 - 8.0
below 30
below 50
below 50
below 50
below 70
below 50
below 30
below 1.0
below 1.0
Not detectable
below 0.3
below 0.25
below 0.4
-
6.8 - 8.0
below 30
below 200
below 50
below 50
below 70
below 50
below 30
below 0.3
below 0.1
Not detectable
below 0.1
below 0.3
below 4.0
-
7.0 - 8.0
below 30
below 30
below 30
below 50
below 70
below 50
below 30
below 1.0
below 1.0
Not detectable
below 0.1
below 0.1
below 0.4
-
7.0 - 8.0
below 30
below 30
below 30
below 50
below 70
below 50
below 30
below 0.3
below 1.0
Not detectable
below 0.1
below 0.3
below 4.0
-
ItemsCirculatingwater 20C Supply water Circulating
water 20C-60C Supply water
Tendencyif out of criteria
Evaporator water Heated water
corrosion + scale
corrosion + scale
corrosion
corrosion
scale
scale
scale
scale
corrosion + scale
corrosion
corrosion
corrosion
corrosion
corrosion
corrosion + scale
Be sure the water quality is in accordance with the specificationsbelow
NOTESThe above tables are purelyindicative and non binding
User interface SPCA 001-010RSBThe interface on the front panel can be used to carry out all theoperations connected to the use of the instrument, and inparticular to:
Set operating mode Check the state of resourcesRespond to alarm situations
10.6.1 KeysSelects operating mode: (Heating /Defrostrefers only to SPCA Heat pump series)
If the heating mode is enabled, each time thekey is pressed the following sequence occurs:Stand-by cooling heating stand by
If cooling mode is enabled:heating stand by cooling heating stand by In menu mode, this key acts as a SCROLL UPor UP key (increasing value).
Resets alarms, and turns the instrument onand off. Press once to reset all manually resetalarms not currently active.
Hold down the key for 2 seconds to turn theinstrument from on to off or vice versa. When it isoff, only the decimal point remains on the display.In menu mode this key acts as a SCROLL DOWNor DOWN key (decreasing value).
Pressing the “mode” and “on-off” keys at thesame time.
If you press both keys at the same time andthen release within 2 seconds, you will moveone level deeper in the display menu. If you press both keys for more than 2 secondsyou will move one level up.If you are currently viewing the lowest level inthe menu and you press both keys and releasewithin 2 seconds, you will go up one level.
10.6.2.2 LedLed 1 compressor 1(step 1)ON if compressor 1 is activeOFF if compressor 1 is offRapid BLINK if safety timing is in progressSlow BLINK if compressor is currently set to defrost (heatpump version)Power step 2 led
Not used
Defrost led (heat pump version)ON if defrosting is in progressOFF if defrosting is disabled or has been completedBLINK if timing is in progress (defrost interval)
Electrical heater/boiler ledON if the internal anti-freeze electrical heater or boiler is onOFF if the internal anti-freeze electrical heater or boiler is off
Heating led (heat pump version)ON if the device is in heating mode
Cooling ledON if the controller is in cooling mode
If neither the HEATING led nor the COOLING led is on, thecontroller is in STAND-BY mode
10.6.2 Displays10.6.2.1 DisplayNormal display shows:
ñ Regulation temperature in tenths of degreescelsius with a decimal point, or in degreesfahrenheit without a decimal point.
ñ The alarm code, if at least one alarm is active. Ifmultiple alarms are active, the one with greaterpriority will be displayed, according to the Tableof Alarms.
ñ If temperature control is not analogue anddepends on the status of a digital input (ST1 orST2 configured as digital inputs), the “On” or“Off” label will be displayed, depending onwhether temperature control is active or not.
ñ When in menu mode, the display depends on thecurrent position; labels and codes are used tohelp the user identify the current function.
ñ Decimal point: when displaying hours of operation,indicates that the value must be multiplied x 100.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 19
10.6 Digital controler
Front panel of the instrument
1 2
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll20
24
Blue
Conn. A
Remote keyboard
Connection
Back side
Conn. B
Red
Blac
k
26
25
The remote keyboard on the display is an exact copy of theinformation displayed on the instrument, with the same leds;
Connection with the controller is illustrated below:
It performs exactly the same functions as those described in thedisplay section.The only difference is in use of the UP and DOWNkeys (to increase and decrease value), which are separate fromthe MODE and ON/OFF keys.
10.7 Remote keyboard
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll 21
The supply, transport to jobsite, installation, commissioning andstart up of an air cooled water chiller with the following technicalcharacteristics.The unit shall be factory assembled, charged with R407Crefrigerant and factory tested.The capacity of the unit shall be no less than: kW
Ambient air temperature (DB) ÆCEntering water temperature ÆCLeaving water temperature ÆC
The unit shall operate unhindered within 6 to 15ÆC water outlettemperature, 3.5 to 7ÆC water temperature difference and 5 up to45ÆC ambient air temperature.
The structural requirements shall be the following:
UNIT HOUSINGThe unit housing shall be fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that shallguarantee and preserve the unit operation during the years. Allmetal parts after fabrication shall be degreased phosphatized, andelectrostatically powder coated with epoxy- polyester RAL 9002coating of a thickness of 60 - 70 Ì. The corrosion resistancetreatment must successfully withstand a salt spray test of 500hours, according to ASTM B- 117. All components shall beassembled exclusively together using bolts, without welding. Theunit shall have removable access panels, designed in such amanner as to permit easy access to internal compartments onlyby authorized personnel.
COMPRESSORShall be of the hermetic scroll type, with low noise and vibrationlevels, specially optimized for use with R407c refrigerant. It shallbe equipped with a crank case electrical heater, to separaterefrigerant and oil when the unit is not operating. It shall alsoinclude internal protection against overloading or electrical spikes.The compressor shall be mounted on special anti vibration rubbermounts to absorb and eliminate any vibration that can begenerated from the unit base.
HYDRAULIC KITThe unit shall be equipped with a complete hydraulic kit,comprising of a circulating pump, buffer and expansion tank,automatic fill / make up water valve with manometer, safety valve,air vent, water filter and differential water pressure switch.
AIR HEAT EXCHANGERThe air hear exchanger shall be manufactured from seamlesscopper tubes having an outside diameter of 9.52mm (3/8'') of highquality according to ASTM B 280. The tubes shall be internallygrooved to achieve optimized heat transfer between refrigerant andtube. The fins shall be manufactured from aluminium. The fins shallbe continuous across the heat exchanger and the fin surface shallbe waffle formed and louvered so as to increase the fin rigidity andheat transfer. The combination of internally grooved copper tubingand louvered fins must result in a heat transfer performance 30%superior to that of a conventional coil.The assembly of the finned pack shall be achieved by mechanicalexpansion in such a way as to form a perfect mechanical bondwith the fins. For this purpose, the fin holes shall have a peripheralextrusion (collar).
WATER HEAT EXCHANGERThe water heat exchanger shall be of the plate heat exchangertype, selected from world-class manufacturers and made ofstainless steel plates (AISI 3161.4401) specially formed toachieve optimized heat transfer. The plates shall be assembled bymeans of an automatic brazing process, under vaccum.
CONDENSER FANS The unit shall be equipped with axial type fans, single phase, and6 poles, internally protected against potential overheating,noiseless and suitable for outdoor installation. The design of theblades and inlet cones shall be aerodynamic, and the fan motorassembly shall be perfectly statically and dinamically balancedallowing a completely vibration free operation. The fan motorassembly shall have a protective grid against accidental contactwith moving parts according to ISO. The fan motor shall be of theexternal rotor type with permanently lubricated bearings that donot require servicing. The motor shall be aerodynamically shapedso as not to interfere with the airflow. The unit shall be equippedwith a continuous linear fan speed regulation control according tocoil temperature.
CONTROL SYSTEM WITH MICROPROCESSOR CONTROLLER The control system shall possess a sophisticated controller thatshall constantly monitor all machine parameters and particullarlymanage among others: ñ Automatic compressor control function through return water
temperature.ñ Continuous fan speed control based on coil heat exchanger
temperature.
Guide specifications11.
SPCA 001-010RSB
ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Compressor running time records.ñ Over 150 programmable parameters. ñ Fan motors overload protection.ñ Auto diagnostic stop function due to low water circulation,
high / low operating pressures and compressor thermaloverload.
ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.
ñ Digital displays of inlet/ outlet as well as condensingtemperatures.
ñ Remote on / off selection.ñ Various other optional control capabilities (listed in options).
REFRIGERANT CIRCUITThe unit shall have a single refrigerant circuit with onecompressor. The circuit shall consist of a filter dryer, expansiondevice, solenoid valve, high and low pressure switch with manualreset.
NOTEThe consultant may if required add the below mentioned optionalaccessories / functions.ñ Remote keyboard.ñ Dynamic set point program via a 4 20 mA proportional
signal.ñ BMS module interface kit for modbus connection.ñ Parallel chiller operation with more than 2 units with optional
controller. ñ Microprocessor parameters reprogramming card.ñ Condenser fins made of prepainted aluminum or copper, and
blygold treatment for additional corrosion protection.ñ Plate exchanger-freezing protection for low chilled water
temperature controlled by microprocessor.ñ Glycol for low chilled water temperatures.ñ Pressure relief valve on compressor discharge.ñ High / low pressure manometers.ñ Phase sequence phase failure - reverse phase and voltage
monitoring device.
Interklima Hydronic systemsSPCA 001-010RSB ñ R407c/Scroll22
Products are manufactured in ISO 9001:2000certified factories. ISO 9001:2000 pertains to quality
assurance regarding design, development,manufacturing and installation of products
as well as to services related to the product.
INTERKLIMA PRODUCTS ARE DISTRIBUTED BY:
EG
B-B
-3-1
-05/
06
Specifications subject to change without notice
Interklima units comply with the European regulations thatguarantee the safety of the product
Engineering Data 2006