sp2-px-ss smartpurge manual - expo technologies · section 1. system specification smartpurge...

60
SP2-PX-ss SmartPurge Manual ML 484 ML484 | v11 08-June-15

Upload: trinhphuc

Post on 12-Jul-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

SP2-PX-ss SmartPurge

Manual

ML 484

ML484 | v11 08-June-15

Page 2: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 1 System Specification .......................................................................................... 1SmartPurge Control Unit Data ........................................................................................... 1Electrical Ratings ............................................................................................................... 2

Section 2 Quick User Guide .................................................................................................. 3Installation.......................................................................................................................... 3Operation of the System .................................................................................................... 3Purge Parameter Setup ..................................................................................................... 4

Section 3 Application Suitability........................................................................................... 5Section 4 Description and Principle of Operation............................................................... 5Section 5 Main Components ................................................................................................. 6

SmartPurge Controller ....................................................................................................... 6Air Supply Unit ................................................................................................................... 6Solenoid Digital Valve for Manual Leakage Compensation – SP2-DV.............................. 6Continuous Flow Control Valve – SP2-CF......................................................................... 6General Safety Warnings................................................................................................... 8Electrical Safety ................................................................................................................. 8Torque for electrical terminals ........................................................................................... 8Compressed Air ................................................................................................................. 8Hazardous area safety....................................................................................................... 8Air Supply Quality .............................................................................................................. 8Purge Outlet Unit ............................................................................................................... 9SmartPurge Controller Unit................................................................................................ 9Non-Intrinsically Safe Terminals ........................................................................................ 9Intrinsically Safe Terminals .............................................................................................. 10SmartPurge Interface Unit (SIU) Signal Isolation............................................................. 10Mounting the SmartPurge and Air Supply Unit ................................................................ 11Remote Control Panel (Optional)..................................................................................... 13Tristate LED (Optional) .................................................................................................... 13

Section 7 Commissioning ..................................................................................... 13Initial Commissioning ....................................................................................................... 13Commissioning ................................................................................................................ 13

Section 8 Configuration....................................................................................................... 15System Configuration....................................................................................................... 15......................................................................................................................................... 15A: Purge System Status................................................................................................... 18B: Language .................................................................................................................... 18C: Settings Display .......................................................................................................... 18D: Passwords................................................................................................................... 18E: Password Override...................................................................................................... 19Operational Strategies ..................................................................................................... 24......................................................................................................................................... 27

Section 9 Maintenance of the System................................................................. 27Routine Maintenance ....................................................................................................... 27Repairs............................................................................................................................. 28

Section 10 Fault Finding......................................................................................... 29Section 11 Recommended Spares List .............................................................................. 30Section 12 Drawings and Diagrams ................................................................................... 30

Section 13 Certificates............................................................................................ 30

ML484 | v11 i

Page 3: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 1. System Specification

SmartPurge Control Unit Data

Model Number

SP2 – ab – c a = P for Purge and Pressurize Control UnitF for Fan Control Unit

b= M for Mains Universal Voltage L for Low Voltage

c = ss for Stainless SteelPurge Flow Range Leakage Compensation: 110 - 540 Nl/min

Continuous FLow 10 - 540 NI/minPurge Time 1-99 minutesLow Pressure Trip Options Immediate Trip, Alarm Only, Delay Trip (Up to 99 mins)Enclosure Pressure 0.8 - 7 mbarg after purgeEnvironmental Protection IP65 316 Stainless Steel EnclosureMounting Position May be mounted in any position external to pressurized enclosureControl Unit Dimensions Stainless steel = 187 x 139 x 107 mm (7.3" x 5.3" x 4.2")Temperature -20 to +60ºCApprovals IECEx

IEC 60079-0 : 2007-10IEC 60079-11 : 2006IEC 60079-18 : 2009IEC 60079-2 : 2007-02IEC 60079-31 : 2008IEC 60079-7 : 2006-07IEC 61241-4 : 2001IECEx FME11.0006Ex e ib mb [p] IIC T4 GbEx tb [pD] IIIC T135ºC Db IP64 -20°C to +60°CATEX

0518 II 2 (2) GD

EN60079-0 : 2009EN60079-2 : 2007EN60079-7 : 2007EN60079-11 : 2007EN60079-18 : 2009EN60079-31 : 2009EN61241-4 : 2006EN60529 : 1991 + A1: 2000FM11ATEX0060 Ex e ib mb [p] IIC T4 GbEx tb [pD] IIIC T135ºC Db IP64 -20°C to +60°C

Page 1 ML484 | v11

Page 4: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Electrical Ratings

SmartPurge Control Unit

Energy limitation parameters:

Remote Panel, energy limitation parameters

USA

ANSI/ISA 60079-0ANSI/ISA 60079-11ANSI/ISA 60079-18ANSI/ISA 60079-2ANSI/ISA 60079-31ANSI/ISA 60079-7ANSI/IEC 60529Class I, Zone 1AEx e ib mb [p] IIC T4 IP64Class I, Zone 21AEx tb [pD] IIIC 135ºC IP64-20º to +60ºCCanada

CAN/CSAE 60079-0CAN/CSAE 60079-11CAN/CSAE 60079-18CAN/CSAE 60079-2Ex e ib m [p] IIC T4 Gb IP64-20ºC to +60ºC

Safety Integrity Level ESC: A127_CT001_(2.0)Weight 4.2kg (9.3lb)

Power Supply (Terminals 1, 2): 90 - 254 Vac: Universal Voltage

11 - 28 Vdc: Low Voltage

Um = 254 Vac

Alarm Contact Ratings:

(Terminals 5, 6 and 7, 8) 240 V, 1 A Fuse type (see Installation of the System section for details

(Terminals 9, 10) 100mA (mains voltage) 500mA (low voltage)Power Switching 2 pole 6A 250V AC1

5A 30V DC1

Terminal TB1 Uo (Vdc) Io (mA) Co (μF) Lo (mH) Po (W)SOV 1, 2 23.58 165.5 0.091 2.9 0.975IP 3,4 23.58 165.5 0.091 2.9 0.975Remote Output 9, 10, 11, 12 8.465 405.1 5.145 0.48 0.857External Alarm 5, 6 5.88 5.9 negligible 0 0.009Override 7, 8 5.88 5.9 negligible 0 0.009

Ui (Vdc) Ii (mA) Ci (μF) Li (mH) Pi (W)8.465 405.1 5.145 0.48 0.857

ML484 | v11 Page 2

Page 5: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 2. Quick User Guide

Installation

The SmartPurge System must be installed by a competent engineer, in accordance with relevant standards, such as IEC / EN 60079-14 and any local codes or practice.

• Fit the appropriate orifice plate to the system if required• Mount the purge system in accordance with the hook-up drawing.• Ensure the system has been installed according to the full instructions in the Installation of the System

section of this manual.• All piping must be clean and free of dirt, condensation and debris prior to connection to the purge system

or pressurized enclosure.Note:It is essential for safety that the installer and user of the Expo system follow these instruc-tions.

Operation of the System

Once installed correctly follow the directions below to make the system operational.

This Quick User Guide is the minimum necessary for the system to operate. Detailed information about system set up can be found in the Configuration section.

When first switched on the system will display the serial number. Check that this corresponds with the system documentation.

The Purge System Status menu will be displayed and it is possible to use and to scroll through the menu to view the current system status, action on alarm and the current pressure sensor readings.

Follow directions on the next page to set up purge parameters.

Once the parameter entry has been completed, switch the air supply on. Slowly increase the pressure inside the pressurized enclosure using the LC valve. When the required minimum pressure is reached, the SmartPurge will initiate the purge cycle.

The elapsed purge time will be shown in the display, once a successful cycle had completed, the power to the electrical equipment in the pressurized enclosure will be connected.

If the system has not performed as expected, check the installation thoroughly and consult the System Configuration and Operation of the System sections.

If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section.

If all checks have been carried out and the system still does not perform as expected, contact your local distributor or Expo Technologies.

Page 3 ML484 | v11

Page 6: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Purge Parameter Setup

End: system isnow ready for

operation

After 30 seconds thedisplay will return to"Purge System Status"

Once High pressure hasbeen set display willreturn to "PurgeParameters menu

Enter "PurgeParameters" sub-menuand change settings tothose on test andinspection sheet.

Scroll throughsub-menu screensuntil you reach "PurgeParameters"Sub-menu

Enter OperatorPassword

Scroll through menuscreens until you reach"Parameter Entry"menu

Start At PurgeSystem Status

Display

Use to scroll

and to enter

menu

Use and to

change numbers and

to enter

Use and to change

numbers and to enter (enter

will also move you to the next

parameter)

use and to scroll

and to enter sub menu

ML484 | v11 Page 4

Page 7: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 3. Application Suitability

SmartPurge systems are certified for use in hazardous locations, where the hazardous location is non-mining (above ground) and the hazard is caused by flammable gasses, vapours or dust. The system may be used in IEC and ATEX Zone 1(21) and Zone 2(22) - Categories 2 and 3 respectively.

Installations in the United State shall comply with the relevant requirements of the National Electrical code®

(ANSI/NFPA-70 NEC).

Installations in Canada shall comply with the relevant requirements of the Canadian Electrical code (CSA C22.1).

SmartPurge systems may be used for hazards of any gas or dust group. Apparatus associated with the SmartPurge system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability.

This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure.

The following materials are used in the construction of SmartPurge systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies ltd for further guidance.

Section 4. Description and Principle of Operation

Purge and pressurization is a method of protection used in Zone 1 (21) and Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a SmartPurge system allows the electrical equipment within the enclosure to be used safely in a hazardous location.

The principle of purge and pressurization is as follows:

• Clean compressed air or inert gas is drawn from a non-hazardous location.• The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust.• This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg above

the external pressure.• Whilst pressurized, flammable gas cannot enter the enclosure from the environment.Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test.

Materials of Construction

Stainless Steel Nylon Acetal

Mild (Carbon) Steel Acrylic Silicone Foam

Brass Polyurethane PVC Foam

Aluminium Polycarbonate

Page 5 ML484 | v11

Page 8: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

The SmartPurge system controls the release of purge air, drawn from a non hazardous location, into the enclosure containing electrical equipment. After the purging cycle, the system connects the power to the equipment to be protected. It then monitors the enclosure pressure to ensure that an overpressure is maintained.

The system is fully automatic in operation, and can be configured by the user to meet the application requirements. If the pressure inside the protected enclosure drops below the minimum threshold the system will either shut down the electrical apparatus and / or give an alarm signal depending on the configuration. The default setting is immediate disconnect of the power.

Section 5. Main Components

SmartPurge Controller

The SmartPurge Control Unit is an electronic unit designed to be used in the hazardous location, it provides the following functions:

•Microprocessor controlled purge and delay timing •Isolation to equipment (2 pole rated 6A @ 230V AC1 duty) •2 Status / Alarm contacts (user configurable) •System status indication via LCD •Delay isolation option •Monitoring and control of purge flow •Monitoring and control of enclosure pressurization •Optional Remote Control Panel duplicates the front panel display andkeypad

Air Supply Unit

The SmartPurge controls the flow of protective gas into the pressurized enclosure through the Air Supply Unit. There are three varieties of unit:

Solenoid Digital Valve for Manual Leakage Compensation – SP2-DV This is designed for leakage compensation purging applications. The flow of gas through the pressurized enclosure is controlled by the SmartPurge Controller. This allows switching between the purging and leakage compensation phases of the purge and pressurization cycle.

Continuous Flow Control Valve – SP2-CFThis is designed for continuous flow purging applications. The air flow through the pressurized enclosure is controlled by a needle valve. Suitable for low flow rate applications, applications where a continuous flow of air is required for cooling or when the dilution of hazardous gases generated inside the enclosure is required.

ML484 | v11 Page 6

Page 9: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Accessories

Remote Control Panel – SP2-RP

This allows the SmartPurge system to be controlled from a remote location. It is an Intrinsically Safe device that duplicates the display and 4 control buttons on the front of the main SmartPurge Unit. The Remote Control Panel is connected to the main unit by means of a shielded 2 twisted pair cable. The cable should not be longer than 50 metres, and have a cross sectional area of at least 0.75 mm2.

It is not possible to perform operations at both keypads simultaneously. The keypad that is in use will “lock-out” operation at the other keypad until the data entry is complete or the display times out and returns to the Purge System Status Display.

An error message is displayed if a key is pressed while another display is being used.

When entering passwords, the password being entered will only show on the control terminal display which is in use. The other display will show “0000” during password entry.

Cable Gland Kit – SP2-GK

An Expo recommended set of cable glands for field wiring. M16 Gland for cable of outer diameter 4 – 8.4 mm and M20 Gland for cable of outer diameter 7.2 – 11.7 mm

Remote LED – SP2-RL

Tri-colour remote indication of purge systems status.

Override Switch – SP2-OS

A panel mounting, key operating switch that bypasses the SmartPurge Controller output signal.

Splash Cover – SP2-SC

A cover to protect the outlet valve from direct water jets.

SmartPurge Interface Unit – SIU

A flameproof interface used for switching higher loads or additional signals.

Page 7 ML484 | v11

Page 10: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 6. Installation of the System

The SmartPurge is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.

The SmartPurge system must be installed by a competent person in accordance with relevant standards, such as EN 60079-14, and any local Codes of Practice that are in force.

The SmartPurge control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system display and certification labels are in view. The system should not be subject to vibration. If to be mounted on a surface that may transmit vibrations it is recommend that the SmartPurge control unit is first mounted onto a chassis plate which is mounted via Anti-Vibration (AV) mounts.

General Safety Warnings

The Expo SmartPurge purge and pressurization system must only be used in accordance with the instructions in this manual and for the purpose described earlier.

Failure to comply with the instructions in the manual during operation, installation, commissioning and maintenance may lead to personal injury, damage to property or voiding of the warranty and/or certification of the SmartPurge system.

The use of a certified purge and pressurization system does not guarantee or imply the compliance of the complete enclosure with ATEX or IECEx standards. Such compliance can only be endorsed by an EU Notified Body.

Installation must be carried out in accordance with these instructions in conjunction with any applicable local Codes of Practice or standards. The units should be configured prior to installation using the following guidelines.

Electrical Safety

The system control unit contains components which may be live when powered. Always isolate power from supply to the SmartPurge and the enclosure before opening.

Torque for electrical terminalsIntrinsically safe terminals: 0.22 - 0.25 NmNon-intrinsically safe terminals: 0.4 - 0.5 Nm

Compressed Air

The system uses compressed air.

• Take precautions when connecting or disconnecting compressed air supplies.• Ensure all flexible pipes used are well secured. • Never block compressed air pipes with any part of the body. • Ensure that equipment is maintained in good condition. • The system exhausts air from the compressed air supply into the atmosphere so a clean supply must be

used. Do not allow the exhaust air to be breathed.

Hazardous area safety

The system is designed for use in hazardous areas; correct installation and maintenance are critical for safe operation. Installation and maintenance must only be carried out by qualified and authorized personnel in accordance with local and site regulations.

ML484 | v11 Page 8

Page 11: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

No unauthorised modifications to the equipment should be made. Purging should be done in accordance with the relevant standard.

Air Supply Quality

The SmartPurge system should be connected to a protective gas supply, which is suitable for purging and pressurization.

The air supply must be: clean, non-flammable and from a non-hazardous location. It must comply with BS ISO 8573-1: 2001 Class 2.2.1 or equivalent local standards.

This is typically referred to as Instrument Air Quality. Although equipment will operate with lower air quality, the operational life of the system will be adversely affected. The equipment that is being protected by the SmartPurge may also suffer because of poor air quality.

* For applications where Tamb ≤ 0oC, the air supply should be Class 2.1.1 with humidity of -70oC pressure dewpoint.

When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section.

Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe.

A method of controlling the air supply should be incorporated into the supply side to the enclosure.

Purge Outlet Unit

The Purge Outlet Unit is housed within the SmartPurge enclosure and measures flow across an orifice. It is preset to open at an enclosure pressure of 8 - 10 mbarg.

A Spark Arrestor is added to the exhaust point of the Purge Outlet Unit to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure.

SmartPurge Controller Unit

SmartPurge has four M5 mounting points for mounting the unit to a flat surface on the pressurized enclosure, refer to appropriate General Arrangement drawing and connected in accordance with the Hook-Up drawing.

Connections to the SmartPurge must be through the M20 & M16 Ex e cable entries. If cable entries are not going to be used, an Ex e blanking plug must be fitted in place of the cable gland.

Non-Intrinsically Safe Terminals

Terminals 1 – 2 and earth: mains input

The unit must be supplied from a separately switched, labelled circuit with over current protection of not greater than 6 Amps.

Instrument Air Quality

Solid Particles 0.5 μm < particle size ≤ 1 μm, maximum 1000 particles / m3

Humidity -40oC* pressure dewpoint

Oil Content ≤ 0.01 mg / m3 concentration total oil

Page 9 ML484 | v11

Page 12: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

The protective earth conductor must be securely attached to the protective earth terminal on the SmartPurge terminal cover plate.

The SmartPurge is housed in and increased safety (Ex e) enclosure. This must be earthed using an earth conductor of minimum 4 mm2, connected to the earth connection on the outside of the unit.

Terminals 3 – 4: mains output

The SmartPurge system provides a switched mains voltage output that can be used to power the protected equipment. It can also be used to drive relays and contactors that provide the necessary switching function.

The load connected to the output from the SmartPurge must not exceed 6 A (AC1). For the Low Voltage version, load must not exceed 5A, 28 Vdc

Terminals 5 – 6 and 7 – 8: alarms

The SmartPurge system provides two volt-free contacts rated 250 V, 1 A AC1. These provide remote indication of the state of the purge system and for the generate alarm signals.

A fuse or other current limiting device must be placed in the circuit connected to these status contacts to limit the current to below that specified. This must have a breaking capacity of 1500 Amps or greater. The fuse or circuit breaker used must have an "F" characteristic to IEC 127 for a fuse, or type B characteristic for a miniature circuit breaker. Where other types of fuse or circuit breaker are used, the user must verify that the switching contacts have not been welded together by the current flowing in the time taken for the fuse to blow or circuit breaker to trip.

The status / alarm outputs must not be used to control the switching of power to the protected equipment.

Terminals 9 – 10: fuse

Fuse connection, See Electrical Ratings for AC and DC versions

Intrinsically Safe Terminals

All connections to these terminals must be made from intrinsically safe circuits in accordance with the Hook-Up drawing.

Terminals 1 – 2: intrinsically safe solenoid valve

1. power supply +2. power supply -Terminals 3 – 4: intrinsically safe I/P converter

4 – 20 mA output:

3. current loop +4. current loop -Terminals 5 – 6 intrinsically safe external alarm

Refer to the wiring diagram for fitting of resistors.

Terminals 7 – 8 intrinsically safe override keyswitch

Refer to the wiring diagram for fitting of resistors.

Terminals 9 – 10 – 11 – 12: remote panel (or tristate LED)

9. power supply + (or common cathode)

ML484 | v11 Page 10

Page 13: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

10.data + (or Anode: Green)11.data - (or Anode: Red)12power supply -

SmartPurge Interface Unit (SIU) Signal Isolation

The following signals may need to be considered for isolation by the SmartPurge system:

• Video Signals.• Network cables (e.g. Ethernet, ARCNet, MODBUS)• Current loops• Status signals• 3 phase power supplies

Note: 3 phase and neutral supplies need all 4 wires to be isolated. Earth wires should not beisolated. Take care not to overtighten screws.

Mounting the SmartPurge and Air Supply Unit

Before mounting the SmartPurge, it should be configured for the flow range required. To carry out this configuration, choose the appropriate flow rate from Table 1

Locate the appropriate Orifice Plate and Flow Restrictor (where necessary).

Using the 2 screws supplied, fix the orifice plate in position in the air entry into the SmartPurge. Refer to Figure 1 for guidance.

For systems that are using the SDV (solenoid digital valve) option, screw the brass flow restrictor into the outlet from the SDV. A slot for a screwdriver is provided in the restrictor to assist in this operation.

The SmartPurge settings need to be configured to the new orifice size.

Normally, the SmartPurge and Air Supply Units will be mounted in diagonally opposite corners of the enclosure to be protected.These units may be mounted internally or externally. For internal mounting of the SmartPurge, use an EXPO adaptor plate accessory. Pipe work to and from the air supply unit must be sized to provide adequate airflow with the minimum pressure drop (restrictive pipe fittings should be avoided). The air outlet from the Air Supply Unit should be located or piped to the opposite side of the enclosure to ensure effective purging, unless effective purging can be proved by other means.

It is recommended that all air supply pipe work be a minimum of 10 mm x 1 mm (3/8”)

If adequate air pressure regulation and filtration cannot be assured, it is recommended that a filter regulator set is installed at the air inlet.

Remember that the minimum air supply pressure requirements quoted are those needed during purge. Long pipe runs or restrictive pipes and fittings may cause substantial pressure drops.

Page 11 ML484 | v11

Page 14: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Figure 1:

Note: The minimum air supply requirements shown in the table above are greater than those shown for the certified minimum flow rate. This is to allow for the additional air required to make up for enclosure leakage and the tolerance of the air flow measurement

Store the orifice plate(s) and flow restrictor(s) which are not used so that the unit may be reconfigured if required at a future date. Record the selections made in the maintenance record of this manual and mark the flow range selected on the label with an indelible marker. If required, it may be possible to use a custom inlet

Table 1: Air Supply Requirements

Flow Range

Inlet Flow Restrictor (for

SDV only)Outlet orifice

Certified Minimum Flow

Rate

Minimum Air Supply Requirement Pressure at Flow

Nl/min (scfm) Bar (psi) Nl/min (scfm)

A

Ø2.7mm hole

8 Hole

= 13 mm

150 (5) 3.1 (45) 212 (7.5)

B

Ø4.2mm hole

16 Hole

= 18mm

300 (10) 3.5 (50) 414 (15)

C None None = 25 mm 540 (19) 4.5 (65) 848 (30)

ML484 | v11 Page 12

Page 15: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

or outlet flow restrictor in order to achieve satisfactory purge operation. Only standard 8 & 16 hole outlet orifices should be used. SmartPurge allows for custom orifice settings. Consult EXPO for further information..

Remote Control Panel (Optional)

The SmartPurge system may be controlled from a remote location by using the Remote Control Panel.

Refer to the drawings section for the dimensions and connection schematic for the Remote Control Panel.

The case of the Remote Control Panel has an external earth terminal. This must be used to bond the case to earth using a 4mm2 cable minimum.

The remote terminal and the main unit must be installed in an environment where the equipotential bonding system exists over the entire area of the installation.

The keypad and display of the remote terminal is used in exactly the same manner as those on the main unit.

It is not possible to perform operations at both keypads simultaneously. The keypad that is in use will “lock-out” operation at the other keypad until the data entry is complete or the display times out and returns to the Purge System Status Display.

Tristate LED (Optional)

This is a simple remote indication of purge status.

• Purge Complete: Green• Purge in Progress: Amber• Purge Low Flow: Flashing Red / Green• Pressure Fault: RedA stainless steel bezel mounts in a 22 mm hole and is connected to terminals 9 – 10 – 11. The maximum cable length between the SmartPurge Control Unit and the Tritsate LED is 50 m.

This panel can only be used when the remote panel is not present.

Page 13 ML484 | v11

Page 16: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 7. Commissioning

Initial Commissioning

Note: The system is pre-set and no adjustments (other than those detailed in this document)should be made without consultation with Expo.

• Ensure the SmartPurge has been correctly installed. • Ensure that all electrical power to the enclosure being protected is isolated.• Check all pipe work and wiring is in accordance with appropriate instructions and wiring diagrams.• Check all doors, inspection covers and other openings in the enclosure are sealed and secure.• Close the leakage compensation valve fully (where fitted).

Commissioning

• Turn on the air supply to the Air Supply Unit.• Turn on the SmartPurge Control Unit. • For leakage compensation systems, slowly open the leakage compensation needle valve until the

enclosure pressure builds up above the lower limit: the Low Pressure Fault message will change toPurge Flow Low. Once this happens, the solenoid valve in the Air Supply Unit will turn on the purge airflow. It may take several seconds before the enclosure pressure reaches the required level. To monitor the pressure on the display panel, press the down arrow once and the pressure in millibars will be shown. Use the pressure display to adjust the setting of the leakage compensation regulator. Typical enclosure pressures:

• To verify that sufficient purge air flow is being detected, ensure that the display on the front of theSmartPurge shows Purge in Progress and a countdown of the purge time or purge volume. A PurgeFlow Low or Purge Flow High message will be displayed if flow is insufficient. if this happens, increaseor decrease the pressure of the air supply to the unit to increase the flow until the Purge in Progressmessage appears. If the purge flow is high enough to cause an overpressure situation, the system will turn off the purge air flow until the pressure falls below the high pressure setting. If this is occurs, reduce the purge flow rate by reducing the supply pressure, and re-start the purge cycle.

• Check that the system continues purging for the correct time or volume. Power will then be connected tothe protected equipment.

• To allow for variations in temperature and air supply pressure, open the leakage compensation valve andincrease the air supply pressure by approximately 5% of the value. Observe the pressure display toascertain when the appropriate pressure is reached. This gives sufficient flow to trigger the flow sensorduring purge.

• Record the air supply pressure and observed purge time in the maintenance record section of thishandbook.

• All the critical settings of the purge parameters are protected from unauthorised modification by means ofa password access to the settings areas of the SmartPurge Menu System. Once the system is configured,change the password from the default setting of 0000 to prevent modification by unauthorisedpersonnel.

• Check function of alarm contacts when pressure drop below 0.5 mbar occurs.• If correct operation is not observed refer to the fault finding section of this handbook.

Normal Operation: 2.5 mbargDuring Purge: 9 mbargMinimum Pressure: 1 mbargMaximum Pressure: 14 mbarg

ML484 | v11 Page 14

Page 17: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 8. Configuration

System Configuration

Once the SmartPurge Controller has been installed it must be configured and settings such as the low pressure, purge flow method and orifice diameter must be set up. The SmartPurge controller is configured using the operators and a two-line display. Refer to the icons below for name and description of each button.

The Test and Inspection Sheet supplied with the unit will show the factory set parameters.

To aid the user in configuring the system to their requirements the Settings sheet should be completed.

The default screen for the SmartPurge displays Purge System Status, which provides information related to the current state of the purge system.

The top line of the display will give a general message, such as Purge System Status and the bottom line will give supplementary information, such as an alarm message. Pressing the Up or Down buttons will cycle the bottom line through any supplementary messages that may be relevant.

Only prompts and parameters appropriate to selected purge method are shown on the menu system.Options that cannot be combined will not be shown.

Pressing the menu button enters the menu system. Each press of the menu button moves the system on to the next menu item, until the display returns to the Purge System Status display.

To change numbers for passwords or settings use or to increase or decrease the flashing number 0-9.Then press to accept entry.

Once accepted the next digit will be highlighted for change or the complete entry will be accepted.

To scroll through sub-menus use or Then press to choose menu.

Once accepted the next menu will be highlighted for change or the complete entry will be accepted.

Some menus will request confirmation by displaying Confirm? Y / N. Press for Yes and for No.

Menu Button This moves to the next menu item

Up ButtonThis allows the user to scroll to the previous menu, confirm Yes, display last parameter or increase digit

Down ButtonThis allows the user to scroll to the next menu, confirm No, display next parameter or decrease digit.

Enter Button This allows the user to scroll to select menu item or entry.

Page 15 ML484 | v11

Page 18: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Me

nu

E:

Pa

ssw

ord

Ove

rrid

e

Pu

rge

Sta

rtA

uto

Man

ual

Pu

rge

Pa

ram

ete

rsEn

clos

ure

Vol

ume

Vol

ume

Cha

nges

Purg

e A

ir V

olum

eO

rific

e D

iam

eter

Min

imum

Flo

w R

ate

Max

imum

Flo

w R

ate

Purg

e Ti

me

Del

ay T

ime

Low

Pre

ssur

eLo

w P

ress

ure

Pre-

Ala

rmH

igh

Pres

sure

Encl

osur

e Ta

rget

Pre

ssur

eM

inim

um D

iluti

on R

ate

Ala

rm 2

Fu

nct

ion

Gen

eral

Ala

rmPr

essu

re C

orre

ctPr

essu

re N

ot C

orre

ctPu

rge

In P

rogr

ess

Low

Pre

ssur

e al

arm

Rea

dy t

o Pu

rge

Ala

rm 1

Fu

nct

ion

Gen

eral

Ala

rmPr

essu

re C

orre

ctPr

essu

re N

ot C

orre

ctPu

rge

In P

rogr

ess

Low

Pre

ssur

e al

arm

Rea

dy t

o Pu

rge

Ex

tern

al

Ala

rmPo

wer

Off

Sys

tem

Tri

pPu

rge

Sta

rt

Tri

p F

un

ctio

nIm

med

iate

Tri

pA

larm

Onl

y an

d R

e-Pu

rge

Del

ay T

rip

and

Re-

Purg

eA

larm

Onl

yD

elay

Tri

pPu

rge

Flo

w M

eth

od

Con

tinu

ous

Flow

2-C

on F

low

(IS

DV

)2-C

on F

low

(I/

P co

nv)

Leak

age

Com

pens

atio

n (I

S D

V)

Leak

age

Com

pens

atio

n (I

/P c

onv)

Pu

rge

Tim

ing

Me

tho

dEl

apse

d Ti

me

Ada

ptiv

e Fl

ow

F

: P

ara

me

ter

En

try

*

Zer

o S

enso

rsR

e-ze

ro f

low

and

pre

ss E

nter

key

to

set

Res

et P

assw

ords

Ente

r ke

y to

set

Sen

sor

Full

Sca

le25

mba

r

Vol

tage

Mon

itor

*M

: x.

xxV

S

: x.

xxVOri

fice

13 m

m18

mm

25 m

mC

usto

mdp

Flo

w

Pres

sure

25

mba

rC

al P

ress

ure

25 m

bar,

Ent

er k

ey t

o se

t

Pres

sure

Zer

oC

al P

ress

ure

Zer

o, E

nter

key

to

set

D

: P

ass

wo

rds

Ch

an

ge

Op

era

tor

Pa

ssw

ord

Ch

an

ge

Ove

rrid

e P

ass

wo

rdS

en

sor

Ca

lib

rati

on

C

: S

ett

ing

s D

isp

lay

*E

ncl

osu

re V

olu

me

Vo

lum

e C

ha

ng

es

Pu

rge

Air

Vo

lum

eM

inim

um

Flo

w R

ate

Pu

rge

Sta

rtP

urg

e T

ime

De

lay

Tim

eLo

w P

ress

ure

Low

Pre

ssu

re P

re-a

larm

En

clo

sure

Ta

rge

t P

ress

ure

Hig

h P

ress

ure

Tri

p F

un

ctio

nE

xt

Ala

rm F

un

ctio

nP

urg

e F

low

Me

tho

dP

urg

e T

imin

g M

eth

od

Ori

fice

Dia

me

ter

Ala

rm 1

Fu

nct

ion

Ala

rm 2

Fu

nct

ion

Se

ria

l N

um

be

r

B:

Lan

gu

ag

eE

ng

lish

En

Fra

nça

is F

De

uts

chE

spa

ño

l E

Ita

lia

no

No

rsk

A:

Pu

rge

Sy

ste

m S

tatu

s *

* D

isp

lay

on

ly.

On

ly p

rom

pts

an

d p

ara

me

ters

rele

va

nt

to t

he

se

lec

ted

pu

rge

me

tho

d a

res

ho

wn

.

ML484 | v11 Page 16

Page 19: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

A: Purge System Status

This screen is the default display for the system and it shows information about the status of the system. Using the arrow keys to scroll through the menu will display: enclosure pressure, purge flow rate and trip mode.

The bottom line of this display will revert to its default of trip mode after 30 seconds. The display can be fixed on other parameters using the Enter key. After this, the arrow keys can be used to change the display and the 30 second time out will resume.

B: Language

This menu is used to change the language used to display menu items.

Selection of this display will show the language currently in use. Scroll through the options using the up and down arrow keys and press enter to select once the desired language is displayed.

The operator password will be required to change the language.

Languages available are English (default), French, German, Spanish, Italian and Norwegian.

C: Settings Display

The Settings Display menu is used to give the operator a view of all the parameters that have been set up for the purge system in its present configuration. This for display only, it is not possible to change settings in this menu.

Press the Enter key to select this menu, then use the Up and Down arrow keys to view the settings.

D: Passwords

The passwords menu allows the user to change the passwords used by the system to control access to various parts of the system. The system uses 3 passwords:

• The Operator Password: required to access the language menu and to modify any of the purging parameters.

• The Override Password: required to turn on the system override or by-pass function allowing power to be connected to the protected equipment regardless of the state of the purge system.

• The Maintenance Password is fixed by Expo, and is not available to general users, as this password controls access to the pressure sensor and flow rate calibration system.

Passwords consist of a 4-digit number, 0000 to 9999. The default value of the Operator and Override passwords is 0000.

When you are prompted to enter a password, a group of 4 0's will appear on the bottom line of the display. The first 0 will be flashing. Use the Up and Down keys to change this character to the appropriate value. Press the Enter key to move on to the next digit. If you make an error, it is possible to “Backspace” by pressing the Up and Down keys simultaneously.

When changing a password, you will first be prompted to enter the current Password.

You will then be prompted to enter the new password. You will then be asked to confirm the new password. If the confirmation succeeds, a confirmation message will be displayed, if it fails, an error message will be displayed, and it will be necessary to repeat the process.

Page 17 ML484 | v11

Page 20: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

E: Password Override

This is a software version of a manual override keyswitch. It allows user to switch on the power to the protected equipment, regardless of the status of the purge system.

This must only be used when the area is known to be hazard free, and typically will require the use of a Hot Work Permit or similar. You should follow your local work instructions and regulations for such matters.

If a manual override keyswitch is fitted to the system, this will take precedence over the password override.

• If the password override has been used and the manual override is activated, the override can only be removed manually. It is not possible to use the password in this case.

• All override is cancelled when the Keyswitch override is turned off

• If the Keyswitch override is in use, the password override menu is not available, and a warning message is shown.

Press Enter to select the Password Override menu. A message will be displayed asking whether the override should be turned On or Off, depending on the present state of the override. Use the Up key to respond “Yes” and the Down key to respond "No".

If you are turning the Override On, then you will be prompted to enter the Override Password. Successful entry of the password will turn the override On.

The password is not required to turn the Override Off.

It is possible to remove the Password Override option from the main menu, by setting the Override Password to “9999” in the Passwords menu.

Pressing the Menu key will move the user along to the next menu item.

F: Parameter Entry

Requires Operator password to be entered before sub-menu can be accessed.

The Parameter Entry menu allows the user to configure the system to the specific application.

Purge Timing Method

The first sub-menu in the Parameter Entry menu allows the choice of purge timing methods.

Elapsed Time This option is the traditional timing method. The purge flow is maintained above a minimum for a set period of time measured in minutes. If the flow drops below the minimum, the purge time is reset and the purge time will restart.

Adaptive Flow This method is a cumulative values of true flow rate measured over time. The system will take into account the time that the flow rate is above the minimum but below the maximum specified flow rate. If the flow rate falls below minimum the accumulation of purge volume will stop but the total is not reset. Flow rate above the maximum is accumulated at the maximum rate. the accumulation is only reset when the pressure exceeds the limits for the low or high pressure alarms.

ML484 | v11 Page 18

Page 21: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Purge Flow Method

The second sub-menu in the Parameter Entry menu allows the choice between how the flow of purge gas is to be controlled.

Trip Function

The third sub-menu in the Parameter Entry menu allows the choice of action to be taken by the system if the pressure goes out of the specified range.

External Alarm

The fourth sub-menu configures the action taken by the system in response to the External Alarm. This is an IS (Intrinsically Safe Circuit),

The default condition is “Purge Start”

Continuous Flow: There is no control by the system over the flow of purge air. After the purge has completed, the system checks for flow above the minimum dilution rate.

Continuous Flow High Purge, IS Digital Valve control

A boost is provided by means of an intrinsically safe solenoid valve to allow a higher flow rate during purging.

Leakage Compensation with IS Digital Valve

The purge flow is controlled by an intrinsically safe solenoid valve, and leakage compensation controlled manually by means of a leakage compensation needle valve.

Immediate Trip This option will disconnect the power to the protected equipment as soon as the enclosure pressure goes out of bounds.

Alarm Only & Repurge

Alarm Only does not disconnect the power to the protected equipment, but will activate the appropriate alarm signals. It is possible to turn the power to the protected equipment off by pressing the Down button on the keypad. A message will be displayed to ask for confirmation that the power is to be turned off.

Delay Trip & Repurge

Delay Trip will disconnect the power to the protected equipment after a pre-set period of time has elapsed after the enclosure pressure goes out of limits. As with the Alarms Only option, the appropriate alarm signals are activated, and it is possible to manually turn the power to the protected equipment off by pressing the Down button on the keypad.

Alarm Only This will prevent the enclosure being re-purged once pressure is restored after pressurization failure.

Delay Trip This will prevent the enclosure being re-purged once pressure is restored after pressurization failure.

Power Off Choosing power off will cause the system to remove power from the protected enclosure when the external alarm input is activated. For example, this option could be used with a thermostat, to prevent over-heating.

System Trip Choosing system trip will cause the system to act as if a pressure fault had been detected. The system will trip in accordance with the currently selected trip mode. For example, this option would be chosen when the input is used to connect additional pressure switches monitoring the pressurization.

Purge Start Choosing purge start will inhibit the start of a purge cycle if an external alarm input is present.

Page 19 ML484 | v11

Page 22: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Alarm 1 & Alarm 2

There are two normally open volt free contacts (Alarm 1 and Alarm 2) that may be configured to give a number of indications

Purge Parameters

The seventh sub-menu will allow the user to enter all the specific details needed to fully configure the SmartPurge System to the application.

To change the setting use to select number, then press when number is correct, this will move you onto the next setting. Backspace is achieved by pressing the Up and Down buttons simultaneously.

Once the last setting has been set the display will default back to Purge Parameters menu.

Wait 30 seconds or Press this will return you to the Purge System Status.

The user can escape early from the parameter entry menu after the desired item has been changed by pressing . Early escape is only possible provided all the parameters remain consistent with correct operation.

Note: Not all of the parameters listed below will be relevant to the purging method selected.

in this section the system will suggest some values based on the parameters entered earlier. Where values are suggested, these values may be adjusted by the user, but only in an upward direction. You cannot use a value smaller than that suggested by the system.

General Alarm This is the default function of Alarm 1, and is active whenever the enclosure is not in a pressurized condition. The contacts close when the enclosure is purged and pressurized.

Pressure Correct The status relay is closed when the enclosure pressure is within limits

Pressure NOT Correct

The status relay is closed when the enclosure pressure is NOT within limits.

Purge In Progress The status contact closes when the purge flow is above the minimum level. This is the default function of Alarm 2.

Low Press Pre-Alarm

The status relay closes when the enclosure pressure falls below the low pressure pre-alarm setting, giving an early warning of impending loss of pressurization.

Ready to Purge When the External Alarm option Purge Start has been chosen this Alarm contact will close to inform the user that purge has not started. This will either be because the Purge Start signal has not been received or there is insufficient Purge Flow being measured in the purge air exit valve.

Enclosure Volume Enter the volume of the purged enclosure. The volume may be between 1 and 99999 litres.

Number of Vol. Changes

Enter the number of times you wish the enclosure volume to be changed. The number of times may be between 1 and 10.

Where the purge air volume has been evaluated by testing, set the number of changes to 1. The default value is 10.

ML484 | v11 Page 20

Page 23: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Notes on air volume and purge time parameters:

• The enclosure volume must be larger than 10 litres and smaller than 99999 litres

• The number of purge volume changes must be between 1 and 10.

• The Purge Air Volume is automatically calculated by the system as the enclosure volume x number of volume changes.

• The user may amend the Purge Air Volume, but only to a larger volume. The maximum volume is 99999 litres.

• The user may select an orifice size from the 3 standard sizes or from the Custom Size, if one has been configured.

Purge Air Volume The system will suggest a purge air volume based on the Enclosure Volume x Number of Volume. Changes.

Where the purge air volume has been measured by testing, enter the desired volume here.

Orifice Diameter It is possible to select 3 different orifice sizes in order to change the range of flow rates measured by the system. The default value for orifice diameter is 25mm, and corresponds to a maximum flow rate during purge of 540 litres per minute.

Two smaller orifice plates are supplied, and are fitted over the air entry into the SmartPurge. The orifice is secured by two screws. Refer to Table 1

For systems that have been specially factory-configured, an extra orifice diameter may be selected in this menu. Details of the flow rate for this orifice size will be recorded in the project specific information section of the manual. Standard systems will only offer the 3 sizes as detailed in Table 1

Purge Time Enter the desired purge time, in minutes. A value will be suggested, based on the purge air volume / minimum purge flow rate.

Minimum Flow Rate Enter the minimum purge flow rate. The default value suggested will depend upon the orifice diameter selected.

Maximum Flow Rate Enter here the maximum purge flow rate. A default value will be suggested, based on the orifice diameter. (Adaptive Flow Purge Timing only)

Minimum Dilution Rate

Enter here the minimum dilution rate for the purge flow after the main purge has completed. (Continuous Flow High Purge methods only)

Low Pressure Enter the lowest acceptable pressure within the enclosure.

The function of this is to shut power off to the pressurized enclosure due to a loss of pressure that may allow the entry of hazardous gas or particles.

High Pressure Enter the highest acceptable pressure within the enclosure.

Enclosures should have a maximum test pressure and it is advised that the High Pressure is set a below this point.

This will warn the user that higher than expected pressure is present inside the enclosure.

Low Pressure Pre-Alarm

Enter the pressure which is above the Low Pressure and below the expected normal operation pressure of the enclosure. The function of this alarm is to warn the user that the enclosure pressure is falling to allow for preventative maintenance to occur.

Enclosure Target Pressure

Where an I/P supply valve is used the Enclosure Target Pressure is maintained by the valve after purge complete.

Page 21 ML484 | v11

Page 24: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

• The minimum flow rate is automatically calculated as 40% of the maximum flow rate available for the selected orifice.

• The maximum flow rate is automatically calculated as 80% of the maximum flow rate available for the selected orifice.

• The user may amend the maximum and minimum flow rates. The system will check that the value for minimum flow rate is always lower than the value for maximum flow rate. The maximum flow rate cannot be larger than the maximum flow rate available for the selected orifice.

• The purge time is automatically calculated by the system by dividing the purge air volume by the minimum flow rate.

• The purge time has a minimum value of 1 minute.

The user can amend the purge time to a larger value than the one calculated by the system.

ML484 | v11 Page 22

Page 25: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Operational Strategies

Page 23 ML484 | v11

Page 26: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 24

Page 27: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Page 25 ML484 | v11

Page 28: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Notes:

Note 1:

• In elapsed time mode, purge is controlled by the timer

• In adaptive flow mode, purge is controlled by the number of litres of air used

Note 2:

• Purge acknowledge only applies when the parameter Purge Start is set to manual. This message prompts the user to initiate the purge cycle by pressing the enter button.

Section 9. Maintenance of the System

The maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice.

Routine Maintenance

It is recommended that these tasks are carried out annually.

• The system should be checked to ensure that the system generates an alarm when the enclosure pressure drops below 0.5 mbar minimum.

• The condition of the connections and cable glands should be checked by suitably qualified personnel. This may be required more frequently depending on environment.

• Re-zeroing of the flow and pressure sensors should be carried out according to the instructions in this manual.

Re-zeroing of the Flow and Pressure Sensors

If the SmartPurge display shows the error message Pressure Mismatch the zero point of the flow and pressure sensors must be reset. It is essential to the correct operation of this function that the enclosure is not pressurized. It is suggested that the best way to ensure this is to perform this operation with the enclosure door open and the air supply turned off

Carry out re-zeroing as follows:

ML484 | v11 Page 26

Page 29: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Repairs

If the SmartPurge needs repairs, these should be carried out by an Expo Service Person.

Start

Display reads"Passwords"

Display reads"Chg Operator

Passw'd" Press

Press until Display reads

"Zero Sensors"

Display reads"Operator Password

0000"

Enter operatorpassword

Display reads"Re-Zero flow andpress enter key to

set"

Press 3 times

Press

Press key to

re-zero sensors

(press to cancel)

Press 4 times

to return to main

menu

End

Page 27 ML484 | v11

Page 30: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 10. Fault Finding

Symptom Fault Solution

No display on the Control Unit

Check power to Control Unit.Check fuse in Control Unit.If ambient temperature is below -20oC the display may not be visible.

Low pressure fault. No Pressure OK indication

No air supply Check air supply is on.Defective wiring between SmartPurge and Air Supply Unit.

Excessive leakage Check that all enclosure doors, covers and conduit or cable entries are sealed and that the enclosure is of an airtight construction. Improve sealing using closed cell foam strip or suitable sealant.

Low air supply pressure Open leakage compensation valve (where fitted) to provide more leakage compensation air flowIncrease the air supply pressureEnsure atmospheric pressure is referenced.

No Purge in Progress indication

Insufficient air supply Check that when the purge is flowing that the pressure at the air inlet is greater than the value shown in Table 1.Check air supply and piping for correct sizing and excessive restrictions.

Excessive enclosure leakage during purging

Seal leaks as above

Purge timer does not time out

Elapsed Time Purging:Purge flow drops during purge sequence (the purge timer resets to zero if purge flow is lost at any time during purge). Check air supply capacity. Increase air supply pressure or select a lower minimum flow threshold.Adaptive Flow Purging:The purge accumulation process will stop if the purge flow drops below the minimum setting. Increase the air supply pressure, or select a lower minimum purge flow threshold.

High pressure fault indication

SmartPurge air outlet is restricted or blocked.

Unblock

Purge flow is too high Reduce supply pressure.

ML484 | v11 Page 28

Page 31: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Section 11. Recommended Spares List

Section 12. Drawings and Diagrams

Section 13 Certificates

Part Number Description

SP2-DV Intrinsically safe solenoid valve, switches between the purge flow and leakage compensation flow rate.

Title Drawing Number Sheet Numbers

Control Unit Drawing XMA-STD0-001 1

External Mounting Dimensions 2

Remote Panel Mounting 3

SmartPurge 2 Internal Components 4

Line Fault Detection Connector assembly 5

SmartPurge 2 Wiring Layout 6

SmartPurge2 SDV Assembly 7

SmartPurge2 Assembly and Cutouts 8

SmartPurge 2 controller and Digital Valve Cutout 9

SmartPurge 2 Hook up 10

SmartPurge 2 Intrinsically Safe Control Drawing USS

SD8112 11

SmartPurge 2 Intrinsically Safety Control Drawing Canada

SD8113 12

Component Certificate Number

SmartPurge Control Unit IECEx IECEx FME 11.0006

ATEX FM11ATEX0060

FM (USA) 3036907

FM (Canada) 3036907C

SIL 2 Rating ESC A127_CT001_(2.0)

IS SOV IECEx IECEx INE 10 0002X - 0

ATEX INNERIS-03--ATEX-0249-X

Page 29 ML484 | v11

Page 32: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

����

�����

���

���

���

�����

��� ��

�������

���

����

����

������

��������

���

���

���

���������

��� ����������

���

�����������

���������

��

��������

���� !

"#$%

&

��������

����

���'�(

����

����

����

������������

��������)*++��,��

�������++���

��

����

�����

����

����

'�!�� ��

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

��

���-����

���

����

����+

+

UN

ITE

D K

ING

DO

M

���.�

� )

����

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

SU

RR

EY

K

T7

0R

H����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

����

����

��;�)�

� �

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8��# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

����

����

��;�)�

������

�����

�.��������

�,�

���

����������.�

���=���

�=��

��

��,

> �'�)?+

+����

���.� ����

���>

���@�

��@�

��@.

����

����

����

��;�)?

,������

������

����*�

� ����

���.�����

>

����

������������������

�����

�)�������,��,

������

����

�.��������

���

� ���

��������.�����

.�� ���������

�����

���

���*)���

�����������,

������ ���

��

')������

���������������

�������

�)

����

�����

���

�������� ��

�������

���� �

����������

��

������

����������

��

������

����������

��

����

������

���

��������

�� ��

���

����

����

��������

ML484 | v11 Page 30

Page 33: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

����

�A*���*BC�

���D�AD)'(BC�

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

��������

����

���'�(

,������

������

����*�

� ����

������

�����

�.�����

���

�,�

����

�������

�����

����

����

���=���

�=��

��

��,

> �'�)?+

+����

���.� ����

���>

���@�

��@�

��@.

����

��

��������

���� !

"#$%

&

���.�����

>

����������

���������

���?�

++���������

���

������

���

��������

���������

��'?�AE)�?BC�

��'*

�A?)��

BC�

��(�A�)(�BC�

Page 31 ML484 | v11

Page 34: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

�?��A�BC�

���'

�A*)*?

BC�

���0�

?�A��?BC�������

����A')�?BC�

���?

�A*)E�

BC�

�?��A�)��BC�

����

����

�����

�������

��������

��F�

�(G

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8��# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

��

����

������

���

�������������

���

���

�������

����

���=���

�=��

��

'

��,

> �'���.� ����

���>

���@�

��@�

��@.

����

��

��������

���� !

"#$%

&

���.�����

>

ML484 | v11 Page 32

Page 35: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

'�

��

*

D?

E

(

����

��)

���

������

H��

�������

�� ������

� ���

��

����

���

.��

����

�����

'����� ��

���F��������

����

�����

��G

*

*��

� ��������������

��������

���

?��

������

��������

�������������������

(��

����

�������

�����

�����

D������

�� ������������ ����

�����������

�������

���

�����

E��

���

����

����������

'

������������

��

��������

����

���������

��

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

��������

����

���'�(

,������

������

����*�

� ����

������

�����

�.��������

�,�

�������

�� �������

��������

���

���=���

�=��

�>? *

��,

> �'�)?+

+����

���.� ����

���>

���@�

��@�

��@.

����

��

��������

���� !

"#$%

&

���.�����

>

Page 33 ML484 | v11

Page 36: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

D

�E

�(

��

�����

�I�����

����

������

��������

����

��

D�������������������

������

������

����������

�����E�

�����

��������F���

��*)D��G���

����

����

��������������������� ���������

����

��

?=(J

��D=�J

���

�����������'����*����?�����(����D���������E�����

����������

����

������������

��������)*++��,��

�������++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

�� �������

�������

�������

��������

���=���

�=��

��

?

��,

> �'�

���.� ����

���>

���@�

��@�

��@.

����

��

��������

���� !

"#$%

&

���.�����

>

����

�,��

������������

�������

���.

���

���

�������

�)*�.

���

�?K��

���������

����

��

��H

�����

������

����

���������

����.������

�,��

��������

��.��������������

�������

����

.��

�������

���������

�������,��

�����

���

��.�������������H

�����

5��������

����

���

������.�F����

��G���������������������

� �����)

�����

��������

� �

���

�����

����

����

����

���

���

��

���

��

�� ���

���

��

�,��

�����

���

��.���

�)�)�������������

? ( D �

����

��)

���

������

H��

)

����� ���.

�������������

')?+

+�����

������

�����

����

������)*.����

*�

�����

����

�����

��)*.����

*�

ML484 | v11 Page 34

Page 37: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

12

34

56

78

910

1112

6 5 4 3 2 1

10

- -

+ +

+

0V

D-

D+

RE

MO

TE

PA

NE

L

OV

ER

RID

E K

EY

SW

ITC

H

EX

TE

RN

AL

AL

AR

M

AL

AR

M C

IRC

UIT

1

AL

AR

M C

IRC

UIT

2

987

SO

LE

NO

ID V

AL

VE

I/P

CO

NV

. 4

/20

mA

CA

UT

ION

!IN

TR

INS

ICA

LL

YS

AF

E C

IRC

UIT

S

FU

SE

NL

EE

LN

N.O

. C

ON

TA

CT

1A

25

0A

AC

1 M

AX

.R

EF

ER

TO

HA

ND

BO

OK

FO

R A

LA

RM

CO

NF

IGU

RA

TIO

N

TB

1

SM

AR

T P

UR

GE

CO

NT

RO

L U

NIT

(OP

TIO

NA

L)

(OP

TIO

NA

L)

SE

E N

OT

E 1

(SE

E N

OT

E 2

)

(SE

E N

OT

E 3

)

PO

WE

R T

O P

RO

TE

CT

ED

EQ

UIP

ME

NT

:6

A A

C1

MA

X.

LO

AD

FO

R 9

0 -

25

4V

ac

SU

PP

LY

5A

MA

X F

OR

11

-28

Vd

c S

UP

PL

Y

PO

WE

R S

UP

PL

Y9

0 -

25

4 V

ac

50

- 6

0 H

zO

R1

1-2

8 V

dc

PR

OT

EC

TIV

E

EA

RT

H

TE

RM

INA

LS

EX

TE

RN

AL

E

AR

TH

NO

TE

S:-

FU

SE

RA

TIN

G:

AC

SU

PP

LY

: 1

00

mA

D

C S

UP

PL

Y 5

00

mA

FIT

10

K 0

.25

W R

ES

IST

OR

IN

PL

AC

E O

F O

VE

RR

IDE

SW

ITC

H W

HE

N N

OT

RE

QU

IRE

D.

FIT

1K

0.2

5W

RE

SIS

TO

R I

N P

LA

CE

OF

EX

TE

RN

AL

AL

AR

M W

HE

N N

OT

RE

QU

IRE

D.

CO

ND

UC

TO

RS

OF

IN

TR

INS

ICA

LL

Y S

AF

E C

IRC

UIT

S S

HA

LL

NO

T B

E C

AR

RIE

D I

N T

HE

S

AM

E C

AB

LE

AS

CO

ND

UC

TO

RS

OF

CIR

CU

ITS

WH

ICH

AR

E N

OT

IN

TR

INS

ICA

LL

Y S

AF

E.

TH

E R

AD

IAL

TH

ICK

NE

SS

OF

TH

E C

ON

DU

CT

OR

IN

SU

LA

TIO

N S

HA

LL

BE

AP

PR

OP

RIA

TE

T

O T

HE

CO

ND

UC

TO

R D

IAM

ET

ER

AN

D T

HE

NA

TU

RE

OF

TH

E I

NS

UL

AT

ION

. T

HE

M

INIM

UM

RA

DIA

L T

HIC

KN

ES

S S

HA

LL

BE

0,2

mm

.

TH

E C

ON

DU

CT

OR

IN

SU

LA

TIO

N S

HA

LL

BE

SU

CH

TH

AT

IT

WIL

L B

E C

AP

AB

LE

OF

W

ITH

ST

AN

DIN

G A

N R

.M.S

. A

.C.

TE

ST

VO

LT

AG

E O

F T

WIC

E T

HE

NO

MIN

AL

VO

LT

AG

E O

F

TH

E I

NT

RIN

SIC

AL

LY

SA

FE

CIR

CU

IT W

ITH

A M

INIM

UM

OF

50

0 V

.

TH

E D

IST

AN

CE

BE

TW

EE

N T

HE

CO

ND

UC

TO

RS

OF

AN

Y C

OR

E O

F A

N I

NT

RIN

SIC

AL

LY

S

AF

E C

IRC

UIT

AN

D T

HA

T O

F A

NY

CO

RE

OF

A N

ON

-IN

TR

INS

ICA

LL

Y S

AF

E C

IRC

UIT

S

HA

LL

BE

IN

AC

CO

RD

AN

CE

WIT

H I

EC

60

07

9-1

1 T

AB

LE

5 C

OL

UM

N 4

(F

OR

37

5V

TH

IS

WIL

L B

E 1

.0 m

m)

EX

CE

PT

WH

EN

ON

E O

F T

HE

FO

LL

OW

ING

AP

PL

Y:

- T

HE

CO

RE

S O

F E

ITH

ER

TH

E I

NT

RIN

SIC

AL

LY

SA

FE

OR

TH

E N

ON

-IN

TR

INS

ICA

LL

Y S

AF

E

CIR

CU

IT A

RE

EN

CL

OS

ED

IN

AN

EA

RT

H S

CR

EE

N,

OR

- T

HE

IN

SU

LA

TIO

N O

F T

HE

IN

TR

INS

ICA

LL

Y S

AF

E C

OR

ES

IS

CA

PA

BL

E O

F

WIT

HS

TA

ND

ING

AN

R.M

.S.

A.C

. T

ES

T V

OL

TA

GE

OF

20

00

V

TE

RM

INA

L B

LO

CK

S T

ER

MIN

AL

TIG

HT

EN

ING

TO

RQ

UE

S:

N

ON

IN

TR

INS

ICA

LL

Y S

AF

E:

0

.4 -

0.5

Nm

IN

TR

INS

ICA

LL

Y S

AF

E T

B1

:

0.2

2 -

0.2

5 N

m

RE

MO

TE

PA

NE

L C

AN

BE

RE

PL

AC

ED

BY

SM

AR

T P

UR

GE

2 R

EM

OT

E L

ED

AS

SE

MB

LY

. R

EF

DR

AW

ING

SD

79

97

TH

E E

LE

CT

RIC

AL

CO

NN

EC

TIO

NS

AR

E D

ET

AIL

ED

ON

TH

IS

DR

AW

ING

1.

2.

3. 4. 5.

6.

7. 8.

(SE

E N

OT

E 9

)

9.

���.�����

>

�� !

"#$%

&

��������

��

����

��

��@.

��@�

���@�

���.� ����

���>

�'��,

>

�>�

���=���

�=��

���������

� ����.��� �����

��

��

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

���.�

� )

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

����

����

�� )

�����

������

Exp

o T

ech

no

log

ies

Lim

ited

���

����

����+

+

����������

'�!�� ��

���-����

����

����

����

�����

����

����

����

������������

��������)*++��,��

������

�++���

��

Page 35 ML484 | v11

Page 38: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

��������

�������

��*B�����

������

��-����

���,��,

������ ������

������

���

������������

�����

��,��,

�D��A�)�*BC�

�D��A�)D(BC�

����AD��BC�

���E�A*)��BC�

�'D�A�)*DBC�

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

�� ���������

� ������,������

���

���=���

�=��

��

(

��,

> �'�

���.� ����

���>

���@�

��@�

��@.

����

��

��

��������

���� !

"#$%

&

���.�����

>

ML484 | v11 Page 36

Page 39: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

�������

��

����

�������

,�

����

���

������ ���,����

�����

�������������

���

�����������

��)�

���

�������������

�����������

��E�A'�*BC���E�A'�*BC�

���

?)?�AD�'�BC�������

��'

�A''

�(*BC������

����AD��BC�

���

�����.��

�������

��

����

��E�A'�*BC� ��E�A'�*BC�

��'

�A''

�(*BC������

���

�A�?

�'�BC������

�?)?�AD�'�BC������

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

�� ���������

� ������,��

���� �

����������

���=���

�=��

)�)�) D

��,

> �'�

���.� ����

���>

���@�

��@�

��@.

����

����

��������

���� !

"#$%

&

���.�����

>

���

���

������ ���,����

�����

�������

,���

�����������

���

�����.��

��,����

���

������ ���=���

��,���

�����

������ ���=���

�'

Page 37 ML484 | v11

Page 40: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

�J���A')�BCJ�

���(�A*)E(BC�

���*

�A�)*BC�

���*

�A�BC�

�*()��A�)��BC�

������

?)?�A�)�BC�������

�������?)��A�)�E

(BC����

���

�������

(��A�)'(

C������

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

����

��,

�����

����

���

����

�����

����

��

����=���

�=��

�>�

E

��,

> �''+

+�����'?�

E���.� ����

���>

���@�

��@�

��@.

���

���

��������

���� !

"#$%

&

���.�����

>

���

������,���=�������

����

�����

��� ���D

���������������������������

�'

ML484 | v11 Page 38

Page 41: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

�����

��

��

����

��.��

����

�H�����

����

�����������

��������

�����������

��.��

�����

��

����

����

� ���

���

�����

����

��� ����������

���

����.

��� ����

����������

��� ���

����

������������

��������)*++��,��

������

�++���

��

����

�����

����

����

����

����

'�!�� ��

���-����

���

����

����+

+

����������

Exp

o T

ech

no

log

ies

Lim

ited

�����

����

��

�����

�� )

����

SU

RR

EY

K

T7

0R

HU

NIT

ED

KIN

GD

OM

���.�

� )

����

�1��# &$�&

$4� /�$1%4�!�69%&3���!

#"+�&

$�6��� �

7�%31$�:

��0� ���

#1&

2 3%�4��%+

%$�!)���1

�7�6���$ �8�

�$��6$�!

�64�# &/%!�&

$%62�

6&!�6�����$"�&68

2��"�

&���<"

�4$)���1

�7�6���& $�$ �8�

�# �

%�!� ��# +

+"&

%#6$�!

�%&��6�$� ��%&

�91

2��9%$1

"$�9�%$$�&

�# &

4�&$�

/� +

��0� ���

#1&

2 3%�4��%+

%$�!5�&�%$1���6���$1�

7�$ �8��"4�!

�%&�6&7

�967�636

%&4$� "��%&

$���4$4)

����

����

��;�)?

����

����

��;�)�

����

����

��;�)�

� �

��������

����

���'�(

,������

������

����*�

� ����

������

�����

�.��������

�,�

�������

�� ��������=�

��

���=���

�=��

)�)�) ��

��,

> �'�)?+

+����

���.� ����

���>

���@�

��@�

��@.

���

���

��������

���� !

"#$%

&

���.�����

>

����

���

��������

����,

���

���

��������

����,

��������

�������

��*B����

Page 39 ML484 | v11

Page 42: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

)cdV( iU

)Am( iI

( iC)F

)H

m( iL)

W( iP

564.81.504

541.584.0

758.0

VOS

PI LA

NRETXEMRALA

EDIR- REV

O T

UO

MERT

UPTU

O

LANI

MRET1BT

2,14,3

6,58,7

21,11,01,9

)cdV( oU

85.3285.32

88.588.5

564.8

)Am( oI

5.5615.561

9.59.5

1.504

( oC)F

190.0190.0

541.5

)H

m( oL9.2

9.20

084.0

)W( oP

579.0579.0

900.0900.0

758.0

DE

DLEIHS

REVO S

RIAP DETSI

WT 2 EZIS

ROT

CU

DN

OC

NIM

mm57.0

51 EC

NED

NEPMI P

OOL XA

M

DN

UO

RG

OT DET

CEN

NO

C DLEI

HSELB A

C FO S

DNE

HTOB TA

SERTE

M 05 SI HT

GNEL

MU

MIXAM ELBA

C

ELBI

GILGE

NELBI

GILGE

N

LAITNET

OPIU

QEG

NID

NOB

HTRAE

LANRETXE

HTRAE LA

NRETXEHTRAE

MRALA LANRETXE

)TUP

NI(

TCATN

OC EERF TLOV

DEILPPUS RES

U() 21 ET

ON EES

EDIR-REV

O

)TUP

NI(

TCATN

OC EERF TLOV

DEILPPUS RES

U()21 ET

ON EES

EVLAV DI

ONEL

OS

)VOS(

DEILPP

US RESU(

)21 ETO

N EES

LAN

OITROP

OR PEVLAV

)PI(

DEILPPUS RES

U()21 ET

ON EES

DEIFITREC

2

TIN

U LORT

NO

C 2 EGR

UP TRAMS

SRETEMARAP

NOITATI

MIL YGRE

NEXX-XX-2PS

LENAP ET

OMER 2 E

GRUP TRA

MSSRETE

MARAP N

OITATIMIL Y

GRENE

LENAP ET

OME

R R

OF PR-2PS4

DNA 3 ,2 ,1 SLA

NIMRET

μ

μ

3102/80/31deti

miLseigolonhceT

opxE

505

CEN

REP

SA

1ENOZ

ISSAL

C

D'PPAD'K

HC

NWAR

D

:RE

MOT

SU

C.o

N TEEH

SF

O

ELA

CS

BD5

61WT

YE

RR

US

MO

DG

NIK

DETI

NU

LAI

RETA

M

ELG

NA dr3

NOIT

CEJO

RP

:oN

BOJ

HSI

NIFELTIT

.oN

GNI

WA

RD

:SUTATS

GNI

WAR

D

:ETAD

NWA

RD

mm

NI S

NOI

SNE

MID

ELA

CS T

ON

OD

laitnedifnoc sa detaert eb ot era yehT .detimiL seigolonhceT opxE

© thgirypoC era tne

mucod / gniward siht fo stnetnoc ehT

tnesnoc nettirw tuohti

w elohw ni ro trap ni detacinu

mmoc ro deipoc eb ot ton era yehT .tseuqer nopu elbanruter era dna

.stseretni ruo tsniaga yaw yna ni desu eb ot yeht era rehtien ,deti

miL seigolonhceT opxE morf

:VER

NM

HM

HM

NOIT

ACOL

)DEIFI

SSAL

C(SUODRAZ

AH

11

DEIFICEP

SN

USE

CN

AREL

OT5.0

± EC

ALP CE

D O

N2.0

± EC

ALP CE

D 11.0

± EC

ALP CE

D 2HT

GNEL

mm001 Y

NA

REV

O m

m4.0 N

AHT

SSEL E

B OT

SSE

NTALF

2 EGR

UP TRAMS

GNI

WARD L

ORTN

OC Y TEFAS CISNIRT

NI2118

DS

1:210

;oL ro aL< )elbacL

+ spool lla fo iL( ;oC ro a

C< )elbac

C ro spool lla fo iC( ;tl

> il ro xaml;tV

>iU ro xa

mV.1

oP>iP ro xa

mP.t pecno

C ytitnE rednu devorppA

MF eb tsum sutarappA detaicos sa fo noitarugifnoc ehT

.2.devorppA

MF eb tsum tne

mpiuqE .S.I.3

.devorppa si ti hcihw rof noitacol )deifissal

C( suodrazaH eht nihti

w dellatsni eb yam tne

mpiuqE .S.I.4

eb tsum sgni

ward lortnoc s'rerutcafunam sutarappa pool noitacol suodrazah dna tne

mpiuqE ro reirraB .S.I.5

.metsys a gnillatsni neh

w dewollof

.cdV ro s

mrV 052 naht erom etareneg ton tsu

m sutarappA detaicossA eht ot detcennoc tne

mpiuqe lortnoC

.6 s

metsys efas yllacisinirtnI fo noitallatsnI" 10.60.21PR ASI/IS

NA htiw ecnadrocca ni eb dluohs noitallatsnI

.7)07

APFN/IS

NA(

®edoC lacirtcelE lanoita

N eht dna "snoitacoL )deifissalC( suodraza

H rof.lavorpp

A MF tuohti

w dettimrep si gni

war d siht ot noisiver oN

.8 ,I ssal

C ton dna snoitacoL )deifissalC( suodraza

H 1 enoZ I ssalC ot gnitcennoc rof ylno elbatius si ']bi[' xEA

.9.snoitacoL )deifissal

C( suodrazaH 1 noisivi

D ,I ssalC ro ,0 enoZ

.aera suodrazah 1 enoZ I ssalC ni dellatsni tne

mpiuqE llA.01

yllacisnirtni eht fo noitalusni eht ro neercs htrae na ni rehtie era stiucric efas yllacisnirtni eht fo seroc ehT.11

V 0002 fo egatlov tset .C.A S.

M.R na gnidnatshti

w fo elbapac si seroc efas.devorppa

MF eb llahs tnempiuqe deilppus res

U.21

.VERREB

MUN

DO

MET

AD

DEVORPP

ADEV

ORPPA

10N

WAR

D3102/01/41

HM

ML484 | v11 Page 40

Page 43: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

)cdV(iU

)Am(iI

(iC)F

)H

m(iL)

W(iP

564.81.504

541.584.0

758.0

VOS

PILA

NRETXEMRALA

EDIR-REV

OT

UO

MERT

UPTU

O

LANI

MRET1BT

2,14,3

6,58,7

21,11,01,9

)cdV(o

U85.32

85.3288.5

88.5564.8

)Am(

oI5.561

5.5619.5

9.51.504

(oC

)F190.0

190.0541.5

)H

m(oL

9.29.2

00

84.0

)W(

oP579.0

579.0900.0

900.0758.0

LAN RETXE

HTRAE

DE

DLEIHS REVO SRI

AP EZIS R

OTCU

DN

OC

NIM

mm57.0

51 E

CNE

DNEP

MI PO

OL XA

M T

A D

NUOR

G OT

DETCE

NN

OC

DLEIHSELB

AC F

O SD

NE HTOB

SERTEM05 SI HT

GNEL

MUMIX

AM ELB

AC

DETSI

WT 2

;oLro

aL<

)elbacL+

spoolllafoiL(

;oC

roa

C<

)elbacC

rospoollla

foiC(

;tl>il

roxa

ml;tV>i

Uro

xam

V.1

oP>iP

roxa

mPadana

Cni

dellatsnineh

wdeifitre

CA

SC

rodevorppA

MFeb

tsum

sutarappAdetaicossa

fonoitarugifnoc

ehT.2

.tpecnoC

ytitnErednu

.devorppasi

tihcih

wrof

noitacolsuodraza

Heht

nihtiw

dellatsnieb

yaM

2egruP

tram

S.3

,1traP

,1 .22C

ASC

,edoClacirtcelE

naidanaC

ehthti

wecnadrocca

nieb

dluohsadana

Cni

noitallat snI.4

.FxidneppA

.lavor ppA

MFtuohti

wdetti

mrepsi

gniward

sihtot

noisivero

N.5

.devorppasi

tihcih

wrof

noitacolsuodraza

Heht

nihtiw

dellatsnieb

yam

tnempiuqE

.S.I.6

ebtsu

msgni

wardlortnocs'rerutcafuna

msutarappa

poolnoitacol

suodrazahdna

tnempiuqE

roreirraB

.S.I.7

.metsys

agnillatsni

nehw

dewollof

aerasuodrazah

1enoZ

Issal

Cni

dellatsnisi

tnempiuqEll

A.8

yllacisnirtnieht

fonoitalusni

ehtro

neercshtrae

nani

rehtieera

stiucricefas

yllacisnirtnieht

foseroc

ehT.9

V0002

foegatlov

tset.

C.AS.

M.R

nagnidnatshti

wfo

elbapacsi

serocefas

deifitrecA

SC

rodevorppa

MFebllahs

tnempiuqe

deilppusres

U.01

ELBIGIL

GEN

ELBI

GILGE

N

MRALALA

NRETXE

)TUP

NI(

TCATN

OCEERF

TLOV

DEILPPUS

RESU(

)01ET

ON

EES

LAN

OITROP

ORPEVLAV

)PI(

DEILPPUS

RESU(

)01ET

ON

EES

EVLAVDI

ONEL

OS

)VOS(

DEILPPUS

RESU(

)01ET

ON

EESLAIT

NETOPI

UQE

GNI

DN

OBHTRAE

LANRETXE

HTRAEE

DIR-REVO

)TUP

NI(

TCATN

OCEERF

TLOV

DEILPPUS

RESU(

)01ET

ON

EES

DEIFITREC

2

TIN

UL

ORTN

OC2

EGR

UPT

RAMS

SRETEMARAP

NOITATI

MILY

GRENE

XX-XX-2PS

LENAP

ETO

MER2

EG

RUP

TRA

MSS

RETEMARAP

NOITATI

MILY

GRENE

LENAP

ETO

MERR

OFPR-2PS

4D

NA3

,2,1

SLANI

MRET

μμ

3102/90/42deti

miLseigolonhceT

opxE

CEC

REP

SA

1ENOZ

ISSAL

C

D'PPAD'K

HC

NWAR

D

:RE

MOT

SU

C.o

NTEE

HS

FO

ELA

CS

BD5

61WT

YE

RR

US

MO

DG

NIK

DETI

NU

LAI

RETA

M

E LG

NA

dr3N

OITCEJ

ORP

:oN

BOJ

HSI

NIFELTIT

.oN

GNI

WA

RD

:SUTATS

GNI

WAR

D

:ETAD

NWA

RD

mm

NIS

NOI

SNE

MID

ELA

CS

TO

NO

D

laitnedifnocsa

detaerteb

otera

yehT.deti

miLseigolonhceT

opxE©

thgirypoC

eratne

mucod/

gniward

sihtfo

stnetnocehT

tnesnocnettir

wtuohti

weloh

wni

rotrap

nidetacinu

mmoc

rodeipoc

ebot

tonera

yehT.tseuqer

nopuelbanruter

eradna

.stseretniruo

tsniagaya

wyna

nidesu

ebot

yehtera

rehtien,deti

miLseigolonhceT

opxEmorf

:VER

NM

PM

HM

NOIT

ACOL

SUODRAZ

AH

11

DEIFICEP

SN

USE

CN

AREL

OT5.0

±E

CALP

CED

ON

2.0±

EC

ALPCE

D1

1.0±

EC

ALPCE

D2

HTG

NELm

m001Y

NA

REV

Om

m4.0N

AHT

SSEL

EB

OTS

SENT

ALF

2E

GRUP

TRAMS

GNI

WARD

LORT

NOC

YTEFASCIS

NIRTNI

3118DS

1:2E

.VERREB

MUN

DO

MET

AD

DEVORPP

ADEV

ORPPA

Page 41 ML484 | v11

Page 44: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 42

Page 45: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

F)L o

(mH

)P o

(W)

SOV

1, 2

23.5

816

5.5

0.09

12.

90.

975

IP3,

423

.58

165.

50.

091

2.9

0.97

5R

emot

e O

utpu

t9,

10,

11,

12

8.46

540

5.1

5.14

50.

480.

857

Exte

rnal

ala

rm5,

65.

885.

9N

eglig

ible

00.

009

Ove

r-rid

e7,

85.

885.

9N

eglig

ible

00.

009

Ui (V

dc)

I i (mA)

Ci (

F)L i (m

H)

P i (W)

8.46

540

5.1

5.14

50.

480.

857

Page 43 ML484 | v11

Page 46: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 44

Page 47: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Nic

hola

s Lu

dlam

D

eput

y C

ertif

icat

ion

Man

ager

, FM

App

rova

ls L

td.

Issu

e da

te: 2

nd A

pril,

201

3

THIS

CER

TIFI

CA

TE M

AY

ON

LY B

E R

EPR

OD

UC

ED IN

ITS

ENTI

RET

Y A

ND

WIT

HO

UT

CH

AN

GE

FM A

ppro

vals

Ltd

. 1 W

inds

or D

ials

, Win

dsor

, Ber

kshi

re, U

K. S

L4 1

RS

T: +

44 (0

) 175

3 75

0 00

0 F

: +44

(0) 1

753

868

700

E-m

ail:

atex

@fm

appr

oval

s.co

m w

ww

.fmap

prov

als.

com

F AT

EX 0

20 (M

ay/1

2)

Page

1 o

f 3

1

EC-T

YPE

EXA

MIN

ATI

ON

CER

TIFI

CA

TE2

Equi

pmen

t or P

rote

ctiv

e sy

stem

s in

tend

ed fo

r use

in P

oten

tially

Expl

osiv

e A

tmos

pher

es -

Dire

ctiv

e 94

/9/E

C

3 EC

-Typ

e Ex

amin

atio

n C

ertif

icat

e N

o:

FM11

ATE

X006

0 4

Equi

pmen

t or p

rote

ctiv

e sy

stem

: (T

ype

Ref

eren

ce a

nd N

ame)

Sm

artP

urge

2 Pu

rge

Con

trol

Uni

t

5 N

ame

of A

pplic

ant:

Ex

po T

echn

olog

ies

Lim

ited

6 A

ddre

ss o

f App

lican

t: U

nit 2

, The

Sum

mit,

H

anw

orth

Roa

d,

Sunb

ury

on T

ham

es,

Surr

ey, T

W16

5D

B, U

nite

d K

ingd

om

7 Th

is e

quip

men

t or p

rote

ctiv

e sy

stem

and

any

acc

epta

ble

varia

tion

ther

eto

is s

peci

fied

in th

e sc

hedu

le to

this

ce

rtific

ate

and

docu

men

ts th

erei

n re

ferre

d to

.

8 FM

App

rova

ls L

td, n

otifi

ed b

ody

num

ber 1

725

in a

ccor

danc

e w

ith A

rticl

e 9

of D

irect

ive

94/9

/EC

of 2

3 M

arch

19

94, c

ertif

ies

that

this

equ

ipm

ent h

as b

een

foun

d to

com

ply

with

the

Esse

ntia

l Hea

lth a

nd S

afet

y R

equi

rem

ents

re

latin

g to

the

desi

gn a

nd c

onst

ruct

ion

of e

quip

men

t int

ende

d fo

r use

in p

oten

tially

exp

losi

ve a

tmos

pher

es g

iven

in

Ann

ex II

to th

e D

irect

ive.

Th

e ex

amin

atio

n an

d te

st re

sults

are

reco

rded

in c

onfid

entia

l rep

ort n

umbe

r:

3041

589E

C d

ated

23

Mar

ch 2

012

9

Com

plia

nce

with

the

Esse

ntia

l Hea

lth a

nd S

afet

y R

equi

rem

ents

, with

the

exce

ptio

n of

thos

e id

entif

ied

in it

em 1

5 of

the

sche

dule

to th

is c

ertif

icat

e, h

as b

een

asse

ssed

by

com

plia

nce

with

the

follo

win

g do

cum

ents

:

EN60

079-

0:20

09, E

N60

079-

2:20

07, E

N60

079-

7:20

07, E

N60

079-

11:2

007,

EN

6007

9-18

:200

9,

EN60

079-

31:2

009,

EN

6124

1-4:

2006

and

EN

6052

9:19

91 +

A1:

2000

10

If th

e si

gn �X

� is

plac

ed a

fter

the

certi

ficat

e nu

mbe

r, it

indi

cate

s th

at t

he e

quip

men

t is

sub

ject

to

spec

ial

cond

ition

s fo

r saf

e us

e sp

ecifi

ed in

the

sche

dule

to th

is c

ertif

icat

e.

11

Th

is E

C-T

ype

Exam

inat

ion

certi

ficat

e re

late

s on

ly t

o th

e de

sign

, ex

amin

atio

n an

d te

sts

of t

he s

peci

fied

equi

pmen

t or p

rote

ctiv

e sy

stem

in a

ccor

danc

e to

the

dire

ctiv

e 94

/9/E

C. F

urth

er re

quire

men

ts o

f the

Dire

ctiv

e ap

ply

to th

e m

anuf

actu

ring

proc

ess

and

supp

ly o

f thi

s eq

uipm

ent o

r pro

tect

ive

syst

em. T

hese

are

not

cov

ered

by

this

cer

tific

ate.

12

The

mar

king

of t

he e

quip

men

t or p

rote

ctiv

e sy

stem

sha

ll in

clud

e:

Smar

tPur

ge2

Purg

e C

ontr

ol U

nit

II 2

(2) G

Ex

e ib

mb

[p] I

IC T

4 -2

0°C

T

a 6

0°C

II 2

(2) D

Ex

tb [p

D] I

IIC 1

35°C

-20°

C

Ta

60°

C

Smar

tPur

ge 2

Rem

ote

Con

trol

Ter

min

al

II 2

G E

x ib

IIC

T4

-20°

C

Ta

60°

C

D

igita

lly si

gned

by

Nic

hola

s Lud

lam

D

N: c

n=N

icho

las L

udla

m, o

=Dep

uty

Cert

ifica

tion

Man

ager

, ou=

FM A

ppro

vals

, em

ail=

nich

olas

.ludl

am@

fmap

prov

als.c

om

, c=G

B D

ate:

201

3.04

.02

15:4

0:09

+01

'00'

SCH

EDU

LE

to

EC

-Typ

e E

xam

inat

ion

Cer

tific

ate

No.

FM

11A

TEX

0060

THIS

CER

TIFI

CA

TE M

AY

ON

LY B

E R

EPR

OD

UC

ED IN

ITS

ENTI

RET

Y A

ND

WIT

HO

UT

CH

AN

GE

FM

App

rova

ls L

td. 1

Win

dsor

Dia

ls, W

inds

or, B

erks

hire

, UK

. SL4

1R

S

T: +

44 (0

) 175

3 75

0 00

0 F

: +44

(0) 1

753

868

700

E-m

ail:

atex

@fm

appr

oval

s.co

m w

ww

.fmap

prov

als.

com

F

ATE

X 0

20 (M

ay/1

2)

Pag

e 2

of 3

13

Des

crip

tion

of E

quip

men

t or P

rote

ctiv

e Sy

stem

:

Th

e S

mar

tPur

ge 2

(SP

2) is

an

elec

troni

c pu

rge

and

pres

suriz

atio

n co

ntro

l sys

tem

con

sist

ing

of a

Con

trol

Uni

t con

tain

ing

the

follo

win

g: a

pow

er s

uppl

y an

d sw

itchi

ng m

odul

e, a

flow

and

pre

ssur

e m

easu

ring

unit

and

an e

lect

roni

c co

ntro

l uni

t. A

dis

play

is p

rovi

ded

for m

onito

ring

the

stat

us a

nd fo

r use

dur

ing

set-u

p.

Two

vers

ions

of t

he S

mar

tPur

ge2

are

avai

labl

e, a

s a

purg

e an

d pr

essu

rize

cont

rol u

nit (

P) a

nd a

s a

fan

cont

rol u

nit (

F). B

oth

thes

e ve

rsio

ns a

re a

vaila

ble

with

eith

er s

tain

less

ste

el (s

s) o

r alu

min

ium

enc

losu

res

(al)

and

with

a u

nive

rsal

vol

tage

(M) o

r a lo

w v

olta

ge (L

) pow

er s

uppl

y.

The

syst

em c

an b

e co

nnec

ted

to a

n op

tiona

l Rem

ote

Pan

el w

hich

is h

ouse

d in

an

alum

iniu

m e

nclo

sure

. Th

e m

axim

um s

ervi

ce te

mpe

ratu

re is

60°

C.

SP2-

ab-c

Sm

artP

urge

2 Pu

rge

Con

trol

Uni

t a

=

P, o

r F

b =

M, o

r L

c =

ss, o

r al

Pow

er S

uppl

y (T

erm

inal

s 1,

2):

90-2

54 V

ac o

r 11-

28 V

dc;

Um

= 2

54 V

ac

Ala

rm C

onta

ct ra

tings

(Ter

min

als

5, 6

and

7, 8

): 2

50V

, 1A

Fu

se ty

pe (T

erm

inal

s 9,

10)

:

10

0mA

(whe

n b

= M

)

50

0mA

(whe

n b

= L)

E

nerg

y Li

mita

tion

Par

amet

ers

Te

rmin

al T

B1

Uo

(Vdc

) Io

(mA

) C

o (

F)

Lo (m

H)

Po

(W)

SO

V

1, 2

23

.58

165.

5 0.

091

2.9

0.97

5 IP

3,

4

23.5

8 16

5.5

0.09

1 2.

9 0.

975

Rem

ote

Out

put

9, 1

0, 1

1, 1

2 8.

465

405.

1 5.

145

0.48

0.

857

Ext

erna

l ala

rm

5, 6

5.

88

5.9

Neg

ligib

le

0 0.

009

Ove

r-rid

e 7,

8

5.88

5.

9 N

eglig

ible

0

0.00

9

Smar

tPur

ge2

Purg

e R

emot

e Pa

nel

SR

P-2

E

nerg

y Li

mita

tion

Par

amet

ers

Ui (

Vdc

) Ii

(mA

) C

i (F)

Li

(mH

) P

i (W

) 8.

465

405.

1 5.

145

0.48

0.

857

14

Sp

ecifi

c C

ondi

tions

of U

se:

N

one

15

Esse

ntia

l Hea

lth a

nd S

afet

y R

equi

rem

ents

:

Th

e re

leva

nt E

HS

Rs

that

hav

e no

t bee

n ad

dres

sed

by th

e st

anda

rds

liste

d in

this

cer

tific

ate

have

bee

n id

entif

ied

and

asse

ssed

in th

e co

nfid

entia

l rep

ort i

dent

ified

in it

em 8

.

Page 45 ML484 | v11

Page 48: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

��������������� ����������������������� �����������������������������������������

������������� ����!�"##���$%#��$�&�'�(��!���)�*��+, -,������������!�...,��+, -,����

Certificate of Conformity to IEC 61508 Safety Integrity Level (SIL) 2

Functional Safety of Safety-Related Programmable Electronic Systems

The ‘SmartPurge ATEX Certified Intelligent Purge and Pressurise

System SP2’

Designed and manufactured by

Expo Technologies Ltd Summer Road, Thames Ditton, Surrey, KT7 0RH, UK

The above system has been assessed and is considered capable for use in a SIL2 high demand safety function. The assessment was based on the assumptions and data provided in:

• ESC Ltd Report No. A127_SV001_(2.0)

The system assessed comprises of the following modules in full redundant configuration:

• Pressure Transmitter

• Logic Board

• Relay

With the output normally energised, de-energise to safe state, the estimated frequency of dangerous failure per hour is 2.2E-7 (providing a minimum proof test interval of 1 year); The assessment was carried out to determine compliance with IEC 61508 with regards to:

• Random Hardware Failures;

• Minimum Architecture.

Managing Director: Kenneth G L Simpson

Member of IEC61508 and IEC 61511 committees Assessment Date: August 2011

[Certificate: A127_CT001_(2.0)]

ML484 | v11 Page 46

Page 49: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Page 47 ML484 | v11

Page 50: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 48

Page 51: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Page 49 ML484 | v11

Page 52: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 50

Page 53: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Page 51 ML484 | v11

Page 54: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

ML484 | v11 Page 52

Page 55: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Page 53 ML484 | v11

Page 56: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

To v

erify

the

avai

labi

lity

of th

e Ap

prov

ed p

rodu

ct, p

leas

e re

fer t

o ww

w.ap

prov

algu

ide.

com

FM

App

rova

ls H

LC 5

/13

3047

764

Pa

ge 1

of 3

F

M A

ppro

vals

1151

Bos

ton

Prov

iden

ce T

urnp

ike

P.O

. Box

910

2 N

orwo

od, M

A 0

2062

USA

T:

781

762

430

0 F

: 781

-762

-937

5 ww

w.fm

appr

oval

s.com

CER

TIFI

CATE

OF

COM

PLIA

NCE

HAZA

RDO

US (

CLAS

SIFI

ED)

LOCA

TIO

N EL

ECTR

ICAL

EQ

UIPM

ENT

This

certi

ficat

e is

issue

d fo

r the

follo

wing

equ

ipm

ent:

SP

2-ab

-c S

mar

tPur

ge2

Purg

e Co

ntro

l Uni

t I/1

/AEx

e ib

mb

[p] I

IC T

4 -2

0°C ≤

Ta ≤

60°

C; -

SD81

12; E

ntity

; IP6

4 21

/AEx

tb [p

D] II

IC T

135°

C -2

0°C ≤

Ta ≤

60°

C; -

SD81

12; E

ntity

; IP6

4 a

= P

or F

, Sys

tem

type

b

= M

or L

, Sup

ply

volta

ge

c =

ss o

r al,

Enclo

sure

mat

eria

l

Entit

y pa

ram

eter

s

Term

inal

TB

1 U 0

(V

dc)

I 0 (m

A)

C 0 (

μF)

L 0 (m

H)

P 0 (

W)

SOV

1,2

23.5

8 16

5.5

0.09

1 2.

9 0.

975

IP

3,4

23.5

8 16

5.5

0.09

1 2.

9 0.

975

Rem

ote

Out

put

9,10

,11,

12

8.46

5 40

5.1

5.14

5 0.

48

0.85

7

Exte

rnal

al

arm

5,

6 5.

88

5.9

Negl

igib

le

0 0.

009

Ove

r-rid

e 7,

8 5.

88

5.9

Negl

igib

le

0 0.

009

SP

2-RP

Sm

artP

urge

2 Re

mot

e Co

ntro

l Ter

min

al

I/1/A

Ex ib

IIC

T4 -2

0°C ≤

Ta ≤

60°

C; -

SD81

12; E

ntity

Entit

y pa

ram

eter

s Ui

(Vdc

) Ii(

mA)

Ci

(μF

) Li

(mH)

Pi

(W

) 8.

465

405.

1 5.

145

0.48

0.

857

Equi

pmen

t Rat

ings

: Th

e Sm

artP

urge

2 Pu

rge

Cont

rol U

nit i

s FM

App

rove

d fo

r Cla

ss I,

Zon

e 1,

AEx

e ib

mb

[p] I

IC

and

Zone

21,

AEx

tb[p

d] II

IC h

azar

dous

(cla

ssifie

d) lo

catio

ns. (

indo

ors/

outd

oors

; IP

64) f

or th

e Un

ited

Stat

es w

hen

inst

alle

d as

per

con

trol d

rawi

ng S

D811

2. T

he S

mar

tPur

ge2

Rem

ote

Cont

rol T

erm

inal

is F

M A

ppro

ved

for C

lass

I, Z

one

1, A

Ex ib

IIC

T4 H

azar

dous

(Cla

ssifie

d)

Loca

tions

. (in

door

s/ou

tdoo

rs; I

P64)

for t

he U

nite

d St

ates

whe

n in

stal

led

as p

er c

ontro

l dra

wing

SD

8112

.

FM

App

rove

d fo

r:

Expo

Tec

hnol

ogie

s Lt

d Su

nbur

y on

Tha

mes

, Sur

rey

Unite

d Ki

ngdo

m

ML484 | v11 Page 54

Page 57: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

To v

erify

the

avai

labi

lity

of th

e Ap

prov

ed p

rodu

ct, p

leas

e re

fer t

o ww

w.ap

prov

algu

ide.

com

FM

App

rova

ls H

LC 5

/13

3047

764

Pa

ge 3

of 3

This

cer

tifie

s th

at th

e eq

uipm

ent d

escr

ibed

has

bee

n fo

und

to c

ompl

y wi

th th

e fo

llowi

ng

Appr

oval

Sta

ndar

ds a

nd o

ther

doc

umen

ts:

Cl

ass

3620

20

11

Cl

ass

3810

20

05

AN

SI/IS

A 61

010-

1 20

04

AN

SI/IE

C 60

529

2004

ANSI

/ISA

6007

9-0

2009

ANSI

/ISA

6007

9-2

2010

ANSI

/ISA

6007

9-7

2008

ANSI

/ISA

6007

9-11

20

09

AN

SI/IS

A 60

079-

18

2009

ANSI

/ISA

6007

9-31

20

09

O

rigin

al P

roje

ct ID

: 30

4776

4 Ap

prov

al G

rant

ed:

Janu

ary

10, 2

014

Subs

eque

nt R

evis

ion

Repo

rts /

Date

App

rova

l Am

ende

d

Repo

rt Nu

mbe

r Da

te

Repo

rt Nu

mbe

r Da

te

FM

App

rova

ls L

LC

10

Jan

uary

201

4

J.E.

Mar

qued

ant

Gro

up M

anag

er, E

lect

rical

Date

To v

erify

the

avai

labi

lity

of th

e Ap

prov

ed p

rodu

ct, p

leas

e re

fer t

o ww

w.ap

prov

algu

ide.

com

FM

App

rova

ls H

LC 5

/13

3047

764C

Page

1 o

f 3

F

M A

ppro

vals

1151

Bos

ton

Prov

iden

ce T

urnp

ike

P.O

. Box

910

2 N

orwo

od, M

A 0

2062

USA

T:

781

762

430

0 F

: 781

-762

-937

5 ww

w.fm

appr

oval

s.com

CER

TIFI

CATE

OF

COM

PLIA

NCE

HAZA

RDO

US L

OCA

TIO

N EL

ECTR

ICAL

EQ

UIPM

ENT

PER

CANA

DIAN

REQ

UIRE

MEN

TS

This

certi

ficat

e is

issue

d fo

r the

follo

wing

equ

ipm

ent:

SP

2-ab

-c S

mar

tPur

ge2

Purg

e Co

ntro

l Uni

t I/1

/Ex

e ib

m [p

] IIC

T4

-20°

C ≤

Ta ≤

60°

C;-S

D811

3; E

ntity

; IP6

4 a

= P

or F

, Sys

tem

type

b

= M

or L

, Sup

ply

volta

ge

c =

ss o

r al,

Enclo

sure

mat

eria

l

Entit

y pa

ram

eter

s

Te

rmin

al

TB1

U 0

(Vdc

) I 0

(mA)

C 0

(μF

) L 0

(mH)

P 0

(W

)

SOV

1,2

23.5

8 16

5.5

0.09

1 2.

9 0.

975

IP

3,4

23.5

8 16

5.5

0.09

1 2.

9 0.

975

Rem

ote

Out

put

9,10

,11,

12

8.46

5 40

5.1

5.14

5 0.

48

0.85

7

Exte

rnal

al

arm

5,

6 5.

88

5.9

Negl

igib

le

0 0.

009

Ove

r-rid

e 7,

8 5.

88

5.9

Negl

igib

le

0 0.

009

Page 55 ML484 | v11

Page 58: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

To v

erify

the

avai

labi

lity

of th

e Ap

prov

ed p

rodu

ct, p

leas

e re

fer t

o ww

w.ap

prov

algu

ide.

com

FM

App

rova

ls HL

C 5/

13

3047

764C

Page

2 o

f 3

SP2-

RP S

mar

tPur

ge2

Rem

ote

Pane

l I/1

/Ex

ib II

C T4

-20°

C ≤

Ta ≤

60°

C;- S

D811

3; E

ntity

Entit

y pa

ram

eter

s Ui

(Vdc

) Ii(

mA)

Ci

(μF

) Li

(mH)

Pi

(W

) 8.

465

405.

1 5.

145

0.48

0.

857

Equi

pmen

t Rat

ings

: Th

e Sm

artP

urge

2 Pu

rge

Cont

rol U

nit i

s FM

App

rove

d fo

r Cla

ss I,

Zon

e 1,

Ex

e ib

m [p

] IIC

Ha

zard

ous

Loca

tions

(ind

oors

/out

door

s; IP

64) f

or C

anad

a wh

en in

stal

led

as p

er c

ontro

l dra

wing

SD

8113

. Th

e Sm

artP

urge

2 Re

mot

e Co

ntro

l Ter

min

al is

FM

App

rove

d fo

r Cla

ss I,

Zon

e 1,

Ex

ib

IIC T

4 Ha

zard

ous

Loca

tions

for C

anad

a wh

en in

stal

led

as p

er c

ontro

l dra

wing

SD8

113.

FM

App

rove

d fo

r:

Expo

Tec

hnol

ogie

s Lt

d Su

nbur

y on

Tha

mes

, Sur

rey

Unite

d Ki

ngdo

m

To v

erify

the

avai

labi

lity

of th

e Ap

prov

ed p

rodu

ct, p

leas

e re

fer t

o ww

w.ap

prov

algu

ide.

com

FM

App

rova

ls HL

C 5/

13

3047

764C

Page

3 o

f 3

This

certi

fies

that

the

equi

pmen

t des

crib

ed h

as b

een

foun

d to

com

ply

with

the

follo

wing

Ap

prov

al S

tand

ards

and

oth

er d

ocum

ents

:

CSA

C22.

2 N

o.10

10.1

20

04

CS

A C2

2.2

No.

6052

9 20

10

CA

N/C

SA E

6007

9-0

2011

CAN/

CSA

E60

079-

2 20

12

CA

N/C

SA E

6007

9-7

2012

CAN/

CSA

E60

079-

11

2011

CAN/

CSA

E 6

0079

-18

2012

O

rigin

al P

roje

ct ID

: 30

4776

4C

Appr

oval

Gra

nted

: Ja

nuar

y 10

, 201

4

Subs

eque

nt R

evisi

on R

epor

ts /

Date

App

rova

l Am

ende

d

Repo

rt Nu

mbe

r Da

te

Repo

rt Nu

mbe

r Da

te

FM

App

rova

ls LL

C

10

Jan

uary

201

4

J.E.

Mar

qued

ant

Gro

up M

anag

er, E

lect

rical

Date

ML484 | v11 Page 56

Page 59: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Smartpurge2 CE SC029 Iss 4.Docx3

Declaration of Conformity

WithEuropeanDirectives

Expo Technologies Ltd Unit 2, The Summit, Hanworth Road Sunbury on Thames TW16 5DB UK

This document confirms that the SmartPurge 2 Purge Control Unit

manufactured by Expo Technologies Ltd conforms, as described, to the following European Directives and standards:

Product description The SmartPurge 2 (SP2) is an electronic purge and pressurization control system consisting of a Control Unit containing the following: a power supply and switching module, a flow and pressure measuring unit and an electronic control unit. A display is provided for monitoring the status and for use during set-up. Two versions of the SmartPurge2 are available, as a purge and pressurize control unit and as a fan control unit. Both these versions are available with either stainless steel or aluminium enclosures and with a universal voltage or a low voltage power supply. Directive 2004/108/EC Electromagnetic Compatibility (EMC) The SmartPurge 2 system described above is in conformity with Directive 2004/108/EC. Intertek technical report EM11055661 shows compliance with the essential requirements of the directive. Directive 2011/65/EC Restriction of the use of certain hazardous substances (RoHS) The SmartPurge 2 system described above is in conformity with Directive 2011/65/EU. All electrical or electronic components used by Expo Technologies Ltd or our suppliers are RoHS compliant. Directive 94/9/EC Equipment for explosive atmospheres (ATEX) The SmartPurge 2 system described above is designed in conformity with ATEX Directive 94/9/EC, in compliance with:

EN 60079-0:2012+A11:2013 EN 60079-2:2014 EN 60079-7:2007 EN 60079-11:2012 EN 60079-18:2009 EN 60079-31:2014

EN 60529:1992+A2:2013 The SmartPurge 2 is certified by FM Approvals Ltd, Windsor, Berkshire, UK. SL4 1RS, under EC Type Examination Certificate FM11ATEX0060, in compliance with:

EN 60079-0:2009 EN 60079-2:2007 EN 60079-7:2007 EN 60079-11:2007 EN 60079-18:2009 EN 60079-31:2009

EN61241-4:2006 EN 60529:1991 + A1:2000 SmartPurge systems are manufactured under Product Quality Assurance Notification SIRA 99 ATEX M043, issued by SIRA Certification Service, Notified Body No. 0518. Signed Date 29/05/2015 Managing Director Confidential Assessment file reference SC029

Page 57 ML484 | v11

Page 60: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control

Expo Technologies Ltd.

Unit 2 The SummitHanworth RoadSunbury on ThamesTW16 5DBUK

Tel:Fax:E-mail:

+44(0)20 8398 8011+44(0)20 8398 8014 [email protected]

Expo Technologies Inc.

9140 Ravenna Road Unit #3TwinsburgOH 44087USA

Tel:Fax:E-mail:

+1 (440) 247 5314+1 (330) 487 [email protected]

www.expoworldwide.com