sp2-px-ss smartpurge manual - expo technologies · section 1. system specification smartpurge...
TRANSCRIPT
![Page 1: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/1.jpg)
SP2-PX-ss SmartPurge
Manual
ML 484
ML484 | v11 08-June-15
![Page 2: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/2.jpg)
Section 1 System Specification .......................................................................................... 1SmartPurge Control Unit Data ........................................................................................... 1Electrical Ratings ............................................................................................................... 2
Section 2 Quick User Guide .................................................................................................. 3Installation.......................................................................................................................... 3Operation of the System .................................................................................................... 3Purge Parameter Setup ..................................................................................................... 4
Section 3 Application Suitability........................................................................................... 5Section 4 Description and Principle of Operation............................................................... 5Section 5 Main Components ................................................................................................. 6
SmartPurge Controller ....................................................................................................... 6Air Supply Unit ................................................................................................................... 6Solenoid Digital Valve for Manual Leakage Compensation – SP2-DV.............................. 6Continuous Flow Control Valve – SP2-CF......................................................................... 6General Safety Warnings................................................................................................... 8Electrical Safety ................................................................................................................. 8Torque for electrical terminals ........................................................................................... 8Compressed Air ................................................................................................................. 8Hazardous area safety....................................................................................................... 8Air Supply Quality .............................................................................................................. 8Purge Outlet Unit ............................................................................................................... 9SmartPurge Controller Unit................................................................................................ 9Non-Intrinsically Safe Terminals ........................................................................................ 9Intrinsically Safe Terminals .............................................................................................. 10SmartPurge Interface Unit (SIU) Signal Isolation............................................................. 10Mounting the SmartPurge and Air Supply Unit ................................................................ 11Remote Control Panel (Optional)..................................................................................... 13Tristate LED (Optional) .................................................................................................... 13
Section 7 Commissioning ..................................................................................... 13Initial Commissioning ....................................................................................................... 13Commissioning ................................................................................................................ 13
Section 8 Configuration....................................................................................................... 15System Configuration....................................................................................................... 15......................................................................................................................................... 15A: Purge System Status................................................................................................... 18B: Language .................................................................................................................... 18C: Settings Display .......................................................................................................... 18D: Passwords................................................................................................................... 18E: Password Override...................................................................................................... 19Operational Strategies ..................................................................................................... 24......................................................................................................................................... 27
Section 9 Maintenance of the System................................................................. 27Routine Maintenance ....................................................................................................... 27Repairs............................................................................................................................. 28
Section 10 Fault Finding......................................................................................... 29Section 11 Recommended Spares List .............................................................................. 30Section 12 Drawings and Diagrams ................................................................................... 30
Section 13 Certificates............................................................................................ 30
ML484 | v11 i
![Page 3: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/3.jpg)
Section 1. System Specification
SmartPurge Control Unit Data
Model Number
SP2 – ab – c a = P for Purge and Pressurize Control UnitF for Fan Control Unit
b= M for Mains Universal Voltage L for Low Voltage
c = ss for Stainless SteelPurge Flow Range Leakage Compensation: 110 - 540 Nl/min
Continuous FLow 10 - 540 NI/minPurge Time 1-99 minutesLow Pressure Trip Options Immediate Trip, Alarm Only, Delay Trip (Up to 99 mins)Enclosure Pressure 0.8 - 7 mbarg after purgeEnvironmental Protection IP65 316 Stainless Steel EnclosureMounting Position May be mounted in any position external to pressurized enclosureControl Unit Dimensions Stainless steel = 187 x 139 x 107 mm (7.3" x 5.3" x 4.2")Temperature -20 to +60ºCApprovals IECEx
IEC 60079-0 : 2007-10IEC 60079-11 : 2006IEC 60079-18 : 2009IEC 60079-2 : 2007-02IEC 60079-31 : 2008IEC 60079-7 : 2006-07IEC 61241-4 : 2001IECEx FME11.0006Ex e ib mb [p] IIC T4 GbEx tb [pD] IIIC T135ºC Db IP64 -20°C to +60°CATEX
0518 II 2 (2) GD
EN60079-0 : 2009EN60079-2 : 2007EN60079-7 : 2007EN60079-11 : 2007EN60079-18 : 2009EN60079-31 : 2009EN61241-4 : 2006EN60529 : 1991 + A1: 2000FM11ATEX0060 Ex e ib mb [p] IIC T4 GbEx tb [pD] IIIC T135ºC Db IP64 -20°C to +60°C
Page 1 ML484 | v11
![Page 4: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/4.jpg)
Electrical Ratings
SmartPurge Control Unit
Energy limitation parameters:
Remote Panel, energy limitation parameters
USA
ANSI/ISA 60079-0ANSI/ISA 60079-11ANSI/ISA 60079-18ANSI/ISA 60079-2ANSI/ISA 60079-31ANSI/ISA 60079-7ANSI/IEC 60529Class I, Zone 1AEx e ib mb [p] IIC T4 IP64Class I, Zone 21AEx tb [pD] IIIC 135ºC IP64-20º to +60ºCCanada
CAN/CSAE 60079-0CAN/CSAE 60079-11CAN/CSAE 60079-18CAN/CSAE 60079-2Ex e ib m [p] IIC T4 Gb IP64-20ºC to +60ºC
Safety Integrity Level ESC: A127_CT001_(2.0)Weight 4.2kg (9.3lb)
Power Supply (Terminals 1, 2): 90 - 254 Vac: Universal Voltage
11 - 28 Vdc: Low Voltage
Um = 254 Vac
Alarm Contact Ratings:
(Terminals 5, 6 and 7, 8) 240 V, 1 A Fuse type (see Installation of the System section for details
(Terminals 9, 10) 100mA (mains voltage) 500mA (low voltage)Power Switching 2 pole 6A 250V AC1
5A 30V DC1
Terminal TB1 Uo (Vdc) Io (mA) Co (μF) Lo (mH) Po (W)SOV 1, 2 23.58 165.5 0.091 2.9 0.975IP 3,4 23.58 165.5 0.091 2.9 0.975Remote Output 9, 10, 11, 12 8.465 405.1 5.145 0.48 0.857External Alarm 5, 6 5.88 5.9 negligible 0 0.009Override 7, 8 5.88 5.9 negligible 0 0.009
Ui (Vdc) Ii (mA) Ci (μF) Li (mH) Pi (W)8.465 405.1 5.145 0.48 0.857
ML484 | v11 Page 2
![Page 5: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/5.jpg)
Section 2. Quick User Guide
Installation
The SmartPurge System must be installed by a competent engineer, in accordance with relevant standards, such as IEC / EN 60079-14 and any local codes or practice.
• Fit the appropriate orifice plate to the system if required• Mount the purge system in accordance with the hook-up drawing.• Ensure the system has been installed according to the full instructions in the Installation of the System
section of this manual.• All piping must be clean and free of dirt, condensation and debris prior to connection to the purge system
or pressurized enclosure.Note:It is essential for safety that the installer and user of the Expo system follow these instruc-tions.
Operation of the System
Once installed correctly follow the directions below to make the system operational.
This Quick User Guide is the minimum necessary for the system to operate. Detailed information about system set up can be found in the Configuration section.
When first switched on the system will display the serial number. Check that this corresponds with the system documentation.
The Purge System Status menu will be displayed and it is possible to use and to scroll through the menu to view the current system status, action on alarm and the current pressure sensor readings.
Follow directions on the next page to set up purge parameters.
Once the parameter entry has been completed, switch the air supply on. Slowly increase the pressure inside the pressurized enclosure using the LC valve. When the required minimum pressure is reached, the SmartPurge will initiate the purge cycle.
The elapsed purge time will be shown in the display, once a successful cycle had completed, the power to the electrical equipment in the pressurized enclosure will be connected.
If the system has not performed as expected, check the installation thoroughly and consult the System Configuration and Operation of the System sections.
If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section.
If all checks have been carried out and the system still does not perform as expected, contact your local distributor or Expo Technologies.
Page 3 ML484 | v11
![Page 6: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/6.jpg)
Purge Parameter Setup
End: system isnow ready for
operation
After 30 seconds thedisplay will return to"Purge System Status"
Once High pressure hasbeen set display willreturn to "PurgeParameters menu
Enter "PurgeParameters" sub-menuand change settings tothose on test andinspection sheet.
Scroll throughsub-menu screensuntil you reach "PurgeParameters"Sub-menu
Enter OperatorPassword
Scroll through menuscreens until you reach"Parameter Entry"menu
Start At PurgeSystem Status
Display
Use to scroll
and to enter
menu
Use and to
change numbers and
to enter
Use and to change
numbers and to enter (enter
will also move you to the next
parameter)
use and to scroll
and to enter sub menu
ML484 | v11 Page 4
![Page 7: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/7.jpg)
Section 3. Application Suitability
SmartPurge systems are certified for use in hazardous locations, where the hazardous location is non-mining (above ground) and the hazard is caused by flammable gasses, vapours or dust. The system may be used in IEC and ATEX Zone 1(21) and Zone 2(22) - Categories 2 and 3 respectively.
Installations in the United State shall comply with the relevant requirements of the National Electrical code®
(ANSI/NFPA-70 NEC).
Installations in Canada shall comply with the relevant requirements of the Canadian Electrical code (CSA C22.1).
SmartPurge systems may be used for hazards of any gas or dust group. Apparatus associated with the SmartPurge system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability.
This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure.
The following materials are used in the construction of SmartPurge systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies ltd for further guidance.
Section 4. Description and Principle of Operation
Purge and pressurization is a method of protection used in Zone 1 (21) and Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a SmartPurge system allows the electrical equipment within the enclosure to be used safely in a hazardous location.
The principle of purge and pressurization is as follows:
• Clean compressed air or inert gas is drawn from a non-hazardous location.• The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust.• This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg above
the external pressure.• Whilst pressurized, flammable gas cannot enter the enclosure from the environment.Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test.
Materials of Construction
Stainless Steel Nylon Acetal
Mild (Carbon) Steel Acrylic Silicone Foam
Brass Polyurethane PVC Foam
Aluminium Polycarbonate
Page 5 ML484 | v11
![Page 8: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/8.jpg)
The SmartPurge system controls the release of purge air, drawn from a non hazardous location, into the enclosure containing electrical equipment. After the purging cycle, the system connects the power to the equipment to be protected. It then monitors the enclosure pressure to ensure that an overpressure is maintained.
The system is fully automatic in operation, and can be configured by the user to meet the application requirements. If the pressure inside the protected enclosure drops below the minimum threshold the system will either shut down the electrical apparatus and / or give an alarm signal depending on the configuration. The default setting is immediate disconnect of the power.
Section 5. Main Components
SmartPurge Controller
The SmartPurge Control Unit is an electronic unit designed to be used in the hazardous location, it provides the following functions:
•Microprocessor controlled purge and delay timing •Isolation to equipment (2 pole rated 6A @ 230V AC1 duty) •2 Status / Alarm contacts (user configurable) •System status indication via LCD •Delay isolation option •Monitoring and control of purge flow •Monitoring and control of enclosure pressurization •Optional Remote Control Panel duplicates the front panel display andkeypad
Air Supply Unit
The SmartPurge controls the flow of protective gas into the pressurized enclosure through the Air Supply Unit. There are three varieties of unit:
Solenoid Digital Valve for Manual Leakage Compensation – SP2-DV This is designed for leakage compensation purging applications. The flow of gas through the pressurized enclosure is controlled by the SmartPurge Controller. This allows switching between the purging and leakage compensation phases of the purge and pressurization cycle.
Continuous Flow Control Valve – SP2-CFThis is designed for continuous flow purging applications. The air flow through the pressurized enclosure is controlled by a needle valve. Suitable for low flow rate applications, applications where a continuous flow of air is required for cooling or when the dilution of hazardous gases generated inside the enclosure is required.
ML484 | v11 Page 6
![Page 9: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/9.jpg)
Accessories
Remote Control Panel – SP2-RP
This allows the SmartPurge system to be controlled from a remote location. It is an Intrinsically Safe device that duplicates the display and 4 control buttons on the front of the main SmartPurge Unit. The Remote Control Panel is connected to the main unit by means of a shielded 2 twisted pair cable. The cable should not be longer than 50 metres, and have a cross sectional area of at least 0.75 mm2.
It is not possible to perform operations at both keypads simultaneously. The keypad that is in use will “lock-out” operation at the other keypad until the data entry is complete or the display times out and returns to the Purge System Status Display.
An error message is displayed if a key is pressed while another display is being used.
When entering passwords, the password being entered will only show on the control terminal display which is in use. The other display will show “0000” during password entry.
Cable Gland Kit – SP2-GK
An Expo recommended set of cable glands for field wiring. M16 Gland for cable of outer diameter 4 – 8.4 mm and M20 Gland for cable of outer diameter 7.2 – 11.7 mm
Remote LED – SP2-RL
Tri-colour remote indication of purge systems status.
Override Switch – SP2-OS
A panel mounting, key operating switch that bypasses the SmartPurge Controller output signal.
Splash Cover – SP2-SC
A cover to protect the outlet valve from direct water jets.
SmartPurge Interface Unit – SIU
A flameproof interface used for switching higher loads or additional signals.
Page 7 ML484 | v11
![Page 10: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/10.jpg)
Section 6. Installation of the System
The SmartPurge is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.
The SmartPurge system must be installed by a competent person in accordance with relevant standards, such as EN 60079-14, and any local Codes of Practice that are in force.
The SmartPurge control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system display and certification labels are in view. The system should not be subject to vibration. If to be mounted on a surface that may transmit vibrations it is recommend that the SmartPurge control unit is first mounted onto a chassis plate which is mounted via Anti-Vibration (AV) mounts.
General Safety Warnings
The Expo SmartPurge purge and pressurization system must only be used in accordance with the instructions in this manual and for the purpose described earlier.
Failure to comply with the instructions in the manual during operation, installation, commissioning and maintenance may lead to personal injury, damage to property or voiding of the warranty and/or certification of the SmartPurge system.
The use of a certified purge and pressurization system does not guarantee or imply the compliance of the complete enclosure with ATEX or IECEx standards. Such compliance can only be endorsed by an EU Notified Body.
Installation must be carried out in accordance with these instructions in conjunction with any applicable local Codes of Practice or standards. The units should be configured prior to installation using the following guidelines.
Electrical Safety
The system control unit contains components which may be live when powered. Always isolate power from supply to the SmartPurge and the enclosure before opening.
Torque for electrical terminalsIntrinsically safe terminals: 0.22 - 0.25 NmNon-intrinsically safe terminals: 0.4 - 0.5 Nm
Compressed Air
The system uses compressed air.
• Take precautions when connecting or disconnecting compressed air supplies.• Ensure all flexible pipes used are well secured. • Never block compressed air pipes with any part of the body. • Ensure that equipment is maintained in good condition. • The system exhausts air from the compressed air supply into the atmosphere so a clean supply must be
used. Do not allow the exhaust air to be breathed.
Hazardous area safety
The system is designed for use in hazardous areas; correct installation and maintenance are critical for safe operation. Installation and maintenance must only be carried out by qualified and authorized personnel in accordance with local and site regulations.
ML484 | v11 Page 8
![Page 11: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/11.jpg)
No unauthorised modifications to the equipment should be made. Purging should be done in accordance with the relevant standard.
Air Supply Quality
The SmartPurge system should be connected to a protective gas supply, which is suitable for purging and pressurization.
The air supply must be: clean, non-flammable and from a non-hazardous location. It must comply with BS ISO 8573-1: 2001 Class 2.2.1 or equivalent local standards.
This is typically referred to as Instrument Air Quality. Although equipment will operate with lower air quality, the operational life of the system will be adversely affected. The equipment that is being protected by the SmartPurge may also suffer because of poor air quality.
* For applications where Tamb ≤ 0oC, the air supply should be Class 2.1.1 with humidity of -70oC pressure dewpoint.
When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section.
Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe.
A method of controlling the air supply should be incorporated into the supply side to the enclosure.
Purge Outlet Unit
The Purge Outlet Unit is housed within the SmartPurge enclosure and measures flow across an orifice. It is preset to open at an enclosure pressure of 8 - 10 mbarg.
A Spark Arrestor is added to the exhaust point of the Purge Outlet Unit to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure.
SmartPurge Controller Unit
SmartPurge has four M5 mounting points for mounting the unit to a flat surface on the pressurized enclosure, refer to appropriate General Arrangement drawing and connected in accordance with the Hook-Up drawing.
Connections to the SmartPurge must be through the M20 & M16 Ex e cable entries. If cable entries are not going to be used, an Ex e blanking plug must be fitted in place of the cable gland.
Non-Intrinsically Safe Terminals
Terminals 1 – 2 and earth: mains input
The unit must be supplied from a separately switched, labelled circuit with over current protection of not greater than 6 Amps.
Instrument Air Quality
Solid Particles 0.5 μm < particle size ≤ 1 μm, maximum 1000 particles / m3
Humidity -40oC* pressure dewpoint
Oil Content ≤ 0.01 mg / m3 concentration total oil
Page 9 ML484 | v11
![Page 12: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/12.jpg)
The protective earth conductor must be securely attached to the protective earth terminal on the SmartPurge terminal cover plate.
The SmartPurge is housed in and increased safety (Ex e) enclosure. This must be earthed using an earth conductor of minimum 4 mm2, connected to the earth connection on the outside of the unit.
Terminals 3 – 4: mains output
The SmartPurge system provides a switched mains voltage output that can be used to power the protected equipment. It can also be used to drive relays and contactors that provide the necessary switching function.
The load connected to the output from the SmartPurge must not exceed 6 A (AC1). For the Low Voltage version, load must not exceed 5A, 28 Vdc
Terminals 5 – 6 and 7 – 8: alarms
The SmartPurge system provides two volt-free contacts rated 250 V, 1 A AC1. These provide remote indication of the state of the purge system and for the generate alarm signals.
A fuse or other current limiting device must be placed in the circuit connected to these status contacts to limit the current to below that specified. This must have a breaking capacity of 1500 Amps or greater. The fuse or circuit breaker used must have an "F" characteristic to IEC 127 for a fuse, or type B characteristic for a miniature circuit breaker. Where other types of fuse or circuit breaker are used, the user must verify that the switching contacts have not been welded together by the current flowing in the time taken for the fuse to blow or circuit breaker to trip.
The status / alarm outputs must not be used to control the switching of power to the protected equipment.
Terminals 9 – 10: fuse
Fuse connection, See Electrical Ratings for AC and DC versions
Intrinsically Safe Terminals
All connections to these terminals must be made from intrinsically safe circuits in accordance with the Hook-Up drawing.
Terminals 1 – 2: intrinsically safe solenoid valve
1. power supply +2. power supply -Terminals 3 – 4: intrinsically safe I/P converter
4 – 20 mA output:
3. current loop +4. current loop -Terminals 5 – 6 intrinsically safe external alarm
Refer to the wiring diagram for fitting of resistors.
Terminals 7 – 8 intrinsically safe override keyswitch
Refer to the wiring diagram for fitting of resistors.
Terminals 9 – 10 – 11 – 12: remote panel (or tristate LED)
9. power supply + (or common cathode)
ML484 | v11 Page 10
![Page 13: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/13.jpg)
10.data + (or Anode: Green)11.data - (or Anode: Red)12power supply -
SmartPurge Interface Unit (SIU) Signal Isolation
The following signals may need to be considered for isolation by the SmartPurge system:
• Video Signals.• Network cables (e.g. Ethernet, ARCNet, MODBUS)• Current loops• Status signals• 3 phase power supplies
Note: 3 phase and neutral supplies need all 4 wires to be isolated. Earth wires should not beisolated. Take care not to overtighten screws.
Mounting the SmartPurge and Air Supply Unit
Before mounting the SmartPurge, it should be configured for the flow range required. To carry out this configuration, choose the appropriate flow rate from Table 1
Locate the appropriate Orifice Plate and Flow Restrictor (where necessary).
Using the 2 screws supplied, fix the orifice plate in position in the air entry into the SmartPurge. Refer to Figure 1 for guidance.
For systems that are using the SDV (solenoid digital valve) option, screw the brass flow restrictor into the outlet from the SDV. A slot for a screwdriver is provided in the restrictor to assist in this operation.
The SmartPurge settings need to be configured to the new orifice size.
Normally, the SmartPurge and Air Supply Units will be mounted in diagonally opposite corners of the enclosure to be protected.These units may be mounted internally or externally. For internal mounting of the SmartPurge, use an EXPO adaptor plate accessory. Pipe work to and from the air supply unit must be sized to provide adequate airflow with the minimum pressure drop (restrictive pipe fittings should be avoided). The air outlet from the Air Supply Unit should be located or piped to the opposite side of the enclosure to ensure effective purging, unless effective purging can be proved by other means.
It is recommended that all air supply pipe work be a minimum of 10 mm x 1 mm (3/8”)
If adequate air pressure regulation and filtration cannot be assured, it is recommended that a filter regulator set is installed at the air inlet.
Remember that the minimum air supply pressure requirements quoted are those needed during purge. Long pipe runs or restrictive pipes and fittings may cause substantial pressure drops.
Page 11 ML484 | v11
![Page 14: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/14.jpg)
Figure 1:
Note: The minimum air supply requirements shown in the table above are greater than those shown for the certified minimum flow rate. This is to allow for the additional air required to make up for enclosure leakage and the tolerance of the air flow measurement
Store the orifice plate(s) and flow restrictor(s) which are not used so that the unit may be reconfigured if required at a future date. Record the selections made in the maintenance record of this manual and mark the flow range selected on the label with an indelible marker. If required, it may be possible to use a custom inlet
Table 1: Air Supply Requirements
Flow Range
Inlet Flow Restrictor (for
SDV only)Outlet orifice
Certified Minimum Flow
Rate
Minimum Air Supply Requirement Pressure at Flow
Nl/min (scfm) Bar (psi) Nl/min (scfm)
A
Ø2.7mm hole
8 Hole
= 13 mm
150 (5) 3.1 (45) 212 (7.5)
B
Ø4.2mm hole
16 Hole
= 18mm
300 (10) 3.5 (50) 414 (15)
C None None = 25 mm 540 (19) 4.5 (65) 848 (30)
ML484 | v11 Page 12
![Page 15: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/15.jpg)
or outlet flow restrictor in order to achieve satisfactory purge operation. Only standard 8 & 16 hole outlet orifices should be used. SmartPurge allows for custom orifice settings. Consult EXPO for further information..
Remote Control Panel (Optional)
The SmartPurge system may be controlled from a remote location by using the Remote Control Panel.
Refer to the drawings section for the dimensions and connection schematic for the Remote Control Panel.
The case of the Remote Control Panel has an external earth terminal. This must be used to bond the case to earth using a 4mm2 cable minimum.
The remote terminal and the main unit must be installed in an environment where the equipotential bonding system exists over the entire area of the installation.
The keypad and display of the remote terminal is used in exactly the same manner as those on the main unit.
It is not possible to perform operations at both keypads simultaneously. The keypad that is in use will “lock-out” operation at the other keypad until the data entry is complete or the display times out and returns to the Purge System Status Display.
Tristate LED (Optional)
This is a simple remote indication of purge status.
• Purge Complete: Green• Purge in Progress: Amber• Purge Low Flow: Flashing Red / Green• Pressure Fault: RedA stainless steel bezel mounts in a 22 mm hole and is connected to terminals 9 – 10 – 11. The maximum cable length between the SmartPurge Control Unit and the Tritsate LED is 50 m.
This panel can only be used when the remote panel is not present.
Page 13 ML484 | v11
![Page 16: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/16.jpg)
Section 7. Commissioning
Initial Commissioning
Note: The system is pre-set and no adjustments (other than those detailed in this document)should be made without consultation with Expo.
• Ensure the SmartPurge has been correctly installed. • Ensure that all electrical power to the enclosure being protected is isolated.• Check all pipe work and wiring is in accordance with appropriate instructions and wiring diagrams.• Check all doors, inspection covers and other openings in the enclosure are sealed and secure.• Close the leakage compensation valve fully (where fitted).
Commissioning
• Turn on the air supply to the Air Supply Unit.• Turn on the SmartPurge Control Unit. • For leakage compensation systems, slowly open the leakage compensation needle valve until the
enclosure pressure builds up above the lower limit: the Low Pressure Fault message will change toPurge Flow Low. Once this happens, the solenoid valve in the Air Supply Unit will turn on the purge airflow. It may take several seconds before the enclosure pressure reaches the required level. To monitor the pressure on the display panel, press the down arrow once and the pressure in millibars will be shown. Use the pressure display to adjust the setting of the leakage compensation regulator. Typical enclosure pressures:
• To verify that sufficient purge air flow is being detected, ensure that the display on the front of theSmartPurge shows Purge in Progress and a countdown of the purge time or purge volume. A PurgeFlow Low or Purge Flow High message will be displayed if flow is insufficient. if this happens, increaseor decrease the pressure of the air supply to the unit to increase the flow until the Purge in Progressmessage appears. If the purge flow is high enough to cause an overpressure situation, the system will turn off the purge air flow until the pressure falls below the high pressure setting. If this is occurs, reduce the purge flow rate by reducing the supply pressure, and re-start the purge cycle.
• Check that the system continues purging for the correct time or volume. Power will then be connected tothe protected equipment.
• To allow for variations in temperature and air supply pressure, open the leakage compensation valve andincrease the air supply pressure by approximately 5% of the value. Observe the pressure display toascertain when the appropriate pressure is reached. This gives sufficient flow to trigger the flow sensorduring purge.
• Record the air supply pressure and observed purge time in the maintenance record section of thishandbook.
• All the critical settings of the purge parameters are protected from unauthorised modification by means ofa password access to the settings areas of the SmartPurge Menu System. Once the system is configured,change the password from the default setting of 0000 to prevent modification by unauthorisedpersonnel.
• Check function of alarm contacts when pressure drop below 0.5 mbar occurs.• If correct operation is not observed refer to the fault finding section of this handbook.
Normal Operation: 2.5 mbargDuring Purge: 9 mbargMinimum Pressure: 1 mbargMaximum Pressure: 14 mbarg
ML484 | v11 Page 14
![Page 17: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/17.jpg)
Section 8. Configuration
System Configuration
Once the SmartPurge Controller has been installed it must be configured and settings such as the low pressure, purge flow method and orifice diameter must be set up. The SmartPurge controller is configured using the operators and a two-line display. Refer to the icons below for name and description of each button.
The Test and Inspection Sheet supplied with the unit will show the factory set parameters.
To aid the user in configuring the system to their requirements the Settings sheet should be completed.
The default screen for the SmartPurge displays Purge System Status, which provides information related to the current state of the purge system.
The top line of the display will give a general message, such as Purge System Status and the bottom line will give supplementary information, such as an alarm message. Pressing the Up or Down buttons will cycle the bottom line through any supplementary messages that may be relevant.
Only prompts and parameters appropriate to selected purge method are shown on the menu system.Options that cannot be combined will not be shown.
Pressing the menu button enters the menu system. Each press of the menu button moves the system on to the next menu item, until the display returns to the Purge System Status display.
To change numbers for passwords or settings use or to increase or decrease the flashing number 0-9.Then press to accept entry.
Once accepted the next digit will be highlighted for change or the complete entry will be accepted.
To scroll through sub-menus use or Then press to choose menu.
Once accepted the next menu will be highlighted for change or the complete entry will be accepted.
Some menus will request confirmation by displaying Confirm? Y / N. Press for Yes and for No.
Menu Button This moves to the next menu item
Up ButtonThis allows the user to scroll to the previous menu, confirm Yes, display last parameter or increase digit
Down ButtonThis allows the user to scroll to the next menu, confirm No, display next parameter or decrease digit.
Enter Button This allows the user to scroll to select menu item or entry.
Page 15 ML484 | v11
![Page 18: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/18.jpg)
Me
nu
E:
Pa
ssw
ord
Ove
rrid
e
Pu
rge
Sta
rtA
uto
Man
ual
Pu
rge
Pa
ram
ete
rsEn
clos
ure
Vol
ume
Vol
ume
Cha
nges
Purg
e A
ir V
olum
eO
rific
e D
iam
eter
Min
imum
Flo
w R
ate
Max
imum
Flo
w R
ate
Purg
e Ti
me
Del
ay T
ime
Low
Pre
ssur
eLo
w P
ress
ure
Pre-
Ala
rmH
igh
Pres
sure
Encl
osur
e Ta
rget
Pre
ssur
eM
inim
um D
iluti
on R
ate
Ala
rm 2
Fu
nct
ion
Gen
eral
Ala
rmPr
essu
re C
orre
ctPr
essu
re N
ot C
orre
ctPu
rge
In P
rogr
ess
Low
Pre
ssur
e al
arm
Rea
dy t
o Pu
rge
Ala
rm 1
Fu
nct
ion
Gen
eral
Ala
rmPr
essu
re C
orre
ctPr
essu
re N
ot C
orre
ctPu
rge
In P
rogr
ess
Low
Pre
ssur
e al
arm
Rea
dy t
o Pu
rge
Ex
tern
al
Ala
rmPo
wer
Off
Sys
tem
Tri
pPu
rge
Sta
rt
Tri
p F
un
ctio
nIm
med
iate
Tri
pA
larm
Onl
y an
d R
e-Pu
rge
Del
ay T
rip
and
Re-
Purg
eA
larm
Onl
yD
elay
Tri
pPu
rge
Flo
w M
eth
od
Con
tinu
ous
Flow
2-C
on F
low
(IS
DV
)2-C
on F
low
(I/
P co
nv)
Leak
age
Com
pens
atio
n (I
S D
V)
Leak
age
Com
pens
atio
n (I
/P c
onv)
Pu
rge
Tim
ing
Me
tho
dEl
apse
d Ti
me
Ada
ptiv
e Fl
ow
F
: P
ara
me
ter
En
try
*
Zer
o S
enso
rsR
e-ze
ro f
low
and
pre
ss E
nter
key
to
set
Res
et P
assw
ords
Ente
r ke
y to
set
Sen
sor
Full
Sca
le25
mba
r
Vol
tage
Mon
itor
*M
: x.
xxV
S
: x.
xxVOri
fice
13 m
m18
mm
25 m
mC
usto
mdp
Flo
w
Pres
sure
25
mba
rC
al P
ress
ure
25 m
bar,
Ent
er k
ey t
o se
t
Pres
sure
Zer
oC
al P
ress
ure
Zer
o, E
nter
key
to
set
D
: P
ass
wo
rds
Ch
an
ge
Op
era
tor
Pa
ssw
ord
Ch
an
ge
Ove
rrid
e P
ass
wo
rdS
en
sor
Ca
lib
rati
on
C
: S
ett
ing
s D
isp
lay
*E
ncl
osu
re V
olu
me
Vo
lum
e C
ha
ng
es
Pu
rge
Air
Vo
lum
eM
inim
um
Flo
w R
ate
Pu
rge
Sta
rtP
urg
e T
ime
De
lay
Tim
eLo
w P
ress
ure
Low
Pre
ssu
re P
re-a
larm
En
clo
sure
Ta
rge
t P
ress
ure
Hig
h P
ress
ure
Tri
p F
un
ctio
nE
xt
Ala
rm F
un
ctio
nP
urg
e F
low
Me
tho
dP
urg
e T
imin
g M
eth
od
Ori
fice
Dia
me
ter
Ala
rm 1
Fu
nct
ion
Ala
rm 2
Fu
nct
ion
Se
ria
l N
um
be
r
B:
Lan
gu
ag
eE
ng
lish
En
Fra
nça
is F
De
uts
chE
spa
ño
l E
Ita
lia
no
No
rsk
A:
Pu
rge
Sy
ste
m S
tatu
s *
* D
isp
lay
on
ly.
On
ly p
rom
pts
an
d p
ara
me
ters
rele
va
nt
to t
he
se
lec
ted
pu
rge
me
tho
d a
res
ho
wn
.
ML484 | v11 Page 16
![Page 19: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/19.jpg)
A: Purge System Status
This screen is the default display for the system and it shows information about the status of the system. Using the arrow keys to scroll through the menu will display: enclosure pressure, purge flow rate and trip mode.
The bottom line of this display will revert to its default of trip mode after 30 seconds. The display can be fixed on other parameters using the Enter key. After this, the arrow keys can be used to change the display and the 30 second time out will resume.
B: Language
This menu is used to change the language used to display menu items.
Selection of this display will show the language currently in use. Scroll through the options using the up and down arrow keys and press enter to select once the desired language is displayed.
The operator password will be required to change the language.
Languages available are English (default), French, German, Spanish, Italian and Norwegian.
C: Settings Display
The Settings Display menu is used to give the operator a view of all the parameters that have been set up for the purge system in its present configuration. This for display only, it is not possible to change settings in this menu.
Press the Enter key to select this menu, then use the Up and Down arrow keys to view the settings.
D: Passwords
The passwords menu allows the user to change the passwords used by the system to control access to various parts of the system. The system uses 3 passwords:
• The Operator Password: required to access the language menu and to modify any of the purging parameters.
• The Override Password: required to turn on the system override or by-pass function allowing power to be connected to the protected equipment regardless of the state of the purge system.
• The Maintenance Password is fixed by Expo, and is not available to general users, as this password controls access to the pressure sensor and flow rate calibration system.
Passwords consist of a 4-digit number, 0000 to 9999. The default value of the Operator and Override passwords is 0000.
When you are prompted to enter a password, a group of 4 0's will appear on the bottom line of the display. The first 0 will be flashing. Use the Up and Down keys to change this character to the appropriate value. Press the Enter key to move on to the next digit. If you make an error, it is possible to “Backspace” by pressing the Up and Down keys simultaneously.
When changing a password, you will first be prompted to enter the current Password.
You will then be prompted to enter the new password. You will then be asked to confirm the new password. If the confirmation succeeds, a confirmation message will be displayed, if it fails, an error message will be displayed, and it will be necessary to repeat the process.
Page 17 ML484 | v11
![Page 20: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/20.jpg)
E: Password Override
This is a software version of a manual override keyswitch. It allows user to switch on the power to the protected equipment, regardless of the status of the purge system.
This must only be used when the area is known to be hazard free, and typically will require the use of a Hot Work Permit or similar. You should follow your local work instructions and regulations for such matters.
If a manual override keyswitch is fitted to the system, this will take precedence over the password override.
• If the password override has been used and the manual override is activated, the override can only be removed manually. It is not possible to use the password in this case.
• All override is cancelled when the Keyswitch override is turned off
• If the Keyswitch override is in use, the password override menu is not available, and a warning message is shown.
Press Enter to select the Password Override menu. A message will be displayed asking whether the override should be turned On or Off, depending on the present state of the override. Use the Up key to respond “Yes” and the Down key to respond "No".
If you are turning the Override On, then you will be prompted to enter the Override Password. Successful entry of the password will turn the override On.
The password is not required to turn the Override Off.
It is possible to remove the Password Override option from the main menu, by setting the Override Password to “9999” in the Passwords menu.
Pressing the Menu key will move the user along to the next menu item.
F: Parameter Entry
Requires Operator password to be entered before sub-menu can be accessed.
The Parameter Entry menu allows the user to configure the system to the specific application.
Purge Timing Method
The first sub-menu in the Parameter Entry menu allows the choice of purge timing methods.
Elapsed Time This option is the traditional timing method. The purge flow is maintained above a minimum for a set period of time measured in minutes. If the flow drops below the minimum, the purge time is reset and the purge time will restart.
Adaptive Flow This method is a cumulative values of true flow rate measured over time. The system will take into account the time that the flow rate is above the minimum but below the maximum specified flow rate. If the flow rate falls below minimum the accumulation of purge volume will stop but the total is not reset. Flow rate above the maximum is accumulated at the maximum rate. the accumulation is only reset when the pressure exceeds the limits for the low or high pressure alarms.
ML484 | v11 Page 18
![Page 21: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/21.jpg)
Purge Flow Method
The second sub-menu in the Parameter Entry menu allows the choice between how the flow of purge gas is to be controlled.
Trip Function
The third sub-menu in the Parameter Entry menu allows the choice of action to be taken by the system if the pressure goes out of the specified range.
External Alarm
The fourth sub-menu configures the action taken by the system in response to the External Alarm. This is an IS (Intrinsically Safe Circuit),
The default condition is “Purge Start”
Continuous Flow: There is no control by the system over the flow of purge air. After the purge has completed, the system checks for flow above the minimum dilution rate.
Continuous Flow High Purge, IS Digital Valve control
A boost is provided by means of an intrinsically safe solenoid valve to allow a higher flow rate during purging.
Leakage Compensation with IS Digital Valve
The purge flow is controlled by an intrinsically safe solenoid valve, and leakage compensation controlled manually by means of a leakage compensation needle valve.
Immediate Trip This option will disconnect the power to the protected equipment as soon as the enclosure pressure goes out of bounds.
Alarm Only & Repurge
Alarm Only does not disconnect the power to the protected equipment, but will activate the appropriate alarm signals. It is possible to turn the power to the protected equipment off by pressing the Down button on the keypad. A message will be displayed to ask for confirmation that the power is to be turned off.
Delay Trip & Repurge
Delay Trip will disconnect the power to the protected equipment after a pre-set period of time has elapsed after the enclosure pressure goes out of limits. As with the Alarms Only option, the appropriate alarm signals are activated, and it is possible to manually turn the power to the protected equipment off by pressing the Down button on the keypad.
Alarm Only This will prevent the enclosure being re-purged once pressure is restored after pressurization failure.
Delay Trip This will prevent the enclosure being re-purged once pressure is restored after pressurization failure.
Power Off Choosing power off will cause the system to remove power from the protected enclosure when the external alarm input is activated. For example, this option could be used with a thermostat, to prevent over-heating.
System Trip Choosing system trip will cause the system to act as if a pressure fault had been detected. The system will trip in accordance with the currently selected trip mode. For example, this option would be chosen when the input is used to connect additional pressure switches monitoring the pressurization.
Purge Start Choosing purge start will inhibit the start of a purge cycle if an external alarm input is present.
Page 19 ML484 | v11
![Page 22: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/22.jpg)
Alarm 1 & Alarm 2
There are two normally open volt free contacts (Alarm 1 and Alarm 2) that may be configured to give a number of indications
Purge Parameters
The seventh sub-menu will allow the user to enter all the specific details needed to fully configure the SmartPurge System to the application.
To change the setting use to select number, then press when number is correct, this will move you onto the next setting. Backspace is achieved by pressing the Up and Down buttons simultaneously.
Once the last setting has been set the display will default back to Purge Parameters menu.
Wait 30 seconds or Press this will return you to the Purge System Status.
The user can escape early from the parameter entry menu after the desired item has been changed by pressing . Early escape is only possible provided all the parameters remain consistent with correct operation.
Note: Not all of the parameters listed below will be relevant to the purging method selected.
in this section the system will suggest some values based on the parameters entered earlier. Where values are suggested, these values may be adjusted by the user, but only in an upward direction. You cannot use a value smaller than that suggested by the system.
General Alarm This is the default function of Alarm 1, and is active whenever the enclosure is not in a pressurized condition. The contacts close when the enclosure is purged and pressurized.
Pressure Correct The status relay is closed when the enclosure pressure is within limits
Pressure NOT Correct
The status relay is closed when the enclosure pressure is NOT within limits.
Purge In Progress The status contact closes when the purge flow is above the minimum level. This is the default function of Alarm 2.
Low Press Pre-Alarm
The status relay closes when the enclosure pressure falls below the low pressure pre-alarm setting, giving an early warning of impending loss of pressurization.
Ready to Purge When the External Alarm option Purge Start has been chosen this Alarm contact will close to inform the user that purge has not started. This will either be because the Purge Start signal has not been received or there is insufficient Purge Flow being measured in the purge air exit valve.
Enclosure Volume Enter the volume of the purged enclosure. The volume may be between 1 and 99999 litres.
Number of Vol. Changes
Enter the number of times you wish the enclosure volume to be changed. The number of times may be between 1 and 10.
Where the purge air volume has been evaluated by testing, set the number of changes to 1. The default value is 10.
ML484 | v11 Page 20
![Page 23: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/23.jpg)
Notes on air volume and purge time parameters:
• The enclosure volume must be larger than 10 litres and smaller than 99999 litres
• The number of purge volume changes must be between 1 and 10.
• The Purge Air Volume is automatically calculated by the system as the enclosure volume x number of volume changes.
• The user may amend the Purge Air Volume, but only to a larger volume. The maximum volume is 99999 litres.
• The user may select an orifice size from the 3 standard sizes or from the Custom Size, if one has been configured.
Purge Air Volume The system will suggest a purge air volume based on the Enclosure Volume x Number of Volume. Changes.
Where the purge air volume has been measured by testing, enter the desired volume here.
Orifice Diameter It is possible to select 3 different orifice sizes in order to change the range of flow rates measured by the system. The default value for orifice diameter is 25mm, and corresponds to a maximum flow rate during purge of 540 litres per minute.
Two smaller orifice plates are supplied, and are fitted over the air entry into the SmartPurge. The orifice is secured by two screws. Refer to Table 1
For systems that have been specially factory-configured, an extra orifice diameter may be selected in this menu. Details of the flow rate for this orifice size will be recorded in the project specific information section of the manual. Standard systems will only offer the 3 sizes as detailed in Table 1
Purge Time Enter the desired purge time, in minutes. A value will be suggested, based on the purge air volume / minimum purge flow rate.
Minimum Flow Rate Enter the minimum purge flow rate. The default value suggested will depend upon the orifice diameter selected.
Maximum Flow Rate Enter here the maximum purge flow rate. A default value will be suggested, based on the orifice diameter. (Adaptive Flow Purge Timing only)
Minimum Dilution Rate
Enter here the minimum dilution rate for the purge flow after the main purge has completed. (Continuous Flow High Purge methods only)
Low Pressure Enter the lowest acceptable pressure within the enclosure.
The function of this is to shut power off to the pressurized enclosure due to a loss of pressure that may allow the entry of hazardous gas or particles.
High Pressure Enter the highest acceptable pressure within the enclosure.
Enclosures should have a maximum test pressure and it is advised that the High Pressure is set a below this point.
This will warn the user that higher than expected pressure is present inside the enclosure.
Low Pressure Pre-Alarm
Enter the pressure which is above the Low Pressure and below the expected normal operation pressure of the enclosure. The function of this alarm is to warn the user that the enclosure pressure is falling to allow for preventative maintenance to occur.
Enclosure Target Pressure
Where an I/P supply valve is used the Enclosure Target Pressure is maintained by the valve after purge complete.
Page 21 ML484 | v11
![Page 24: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/24.jpg)
• The minimum flow rate is automatically calculated as 40% of the maximum flow rate available for the selected orifice.
• The maximum flow rate is automatically calculated as 80% of the maximum flow rate available for the selected orifice.
• The user may amend the maximum and minimum flow rates. The system will check that the value for minimum flow rate is always lower than the value for maximum flow rate. The maximum flow rate cannot be larger than the maximum flow rate available for the selected orifice.
• The purge time is automatically calculated by the system by dividing the purge air volume by the minimum flow rate.
• The purge time has a minimum value of 1 minute.
The user can amend the purge time to a larger value than the one calculated by the system.
ML484 | v11 Page 22
![Page 25: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/25.jpg)
Operational Strategies
Page 23 ML484 | v11
![Page 26: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/26.jpg)
ML484 | v11 Page 24
![Page 27: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/27.jpg)
Page 25 ML484 | v11
![Page 28: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/28.jpg)
Notes:
Note 1:
• In elapsed time mode, purge is controlled by the timer
• In adaptive flow mode, purge is controlled by the number of litres of air used
Note 2:
• Purge acknowledge only applies when the parameter Purge Start is set to manual. This message prompts the user to initiate the purge cycle by pressing the enter button.
Section 9. Maintenance of the System
The maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice.
Routine Maintenance
It is recommended that these tasks are carried out annually.
• The system should be checked to ensure that the system generates an alarm when the enclosure pressure drops below 0.5 mbar minimum.
• The condition of the connections and cable glands should be checked by suitably qualified personnel. This may be required more frequently depending on environment.
• Re-zeroing of the flow and pressure sensors should be carried out according to the instructions in this manual.
Re-zeroing of the Flow and Pressure Sensors
If the SmartPurge display shows the error message Pressure Mismatch the zero point of the flow and pressure sensors must be reset. It is essential to the correct operation of this function that the enclosure is not pressurized. It is suggested that the best way to ensure this is to perform this operation with the enclosure door open and the air supply turned off
Carry out re-zeroing as follows:
ML484 | v11 Page 26
![Page 29: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/29.jpg)
Repairs
If the SmartPurge needs repairs, these should be carried out by an Expo Service Person.
Start
Display reads"Passwords"
Display reads"Chg Operator
Passw'd" Press
Press until Display reads
"Zero Sensors"
Display reads"Operator Password
0000"
Enter operatorpassword
Display reads"Re-Zero flow andpress enter key to
set"
Press 3 times
Press
Press key to
re-zero sensors
(press to cancel)
Press 4 times
to return to main
menu
End
Page 27 ML484 | v11
![Page 30: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/30.jpg)
Section 10. Fault Finding
Symptom Fault Solution
No display on the Control Unit
Check power to Control Unit.Check fuse in Control Unit.If ambient temperature is below -20oC the display may not be visible.
Low pressure fault. No Pressure OK indication
No air supply Check air supply is on.Defective wiring between SmartPurge and Air Supply Unit.
Excessive leakage Check that all enclosure doors, covers and conduit or cable entries are sealed and that the enclosure is of an airtight construction. Improve sealing using closed cell foam strip or suitable sealant.
Low air supply pressure Open leakage compensation valve (where fitted) to provide more leakage compensation air flowIncrease the air supply pressureEnsure atmospheric pressure is referenced.
No Purge in Progress indication
Insufficient air supply Check that when the purge is flowing that the pressure at the air inlet is greater than the value shown in Table 1.Check air supply and piping for correct sizing and excessive restrictions.
Excessive enclosure leakage during purging
Seal leaks as above
Purge timer does not time out
Elapsed Time Purging:Purge flow drops during purge sequence (the purge timer resets to zero if purge flow is lost at any time during purge). Check air supply capacity. Increase air supply pressure or select a lower minimum flow threshold.Adaptive Flow Purging:The purge accumulation process will stop if the purge flow drops below the minimum setting. Increase the air supply pressure, or select a lower minimum purge flow threshold.
High pressure fault indication
SmartPurge air outlet is restricted or blocked.
Unblock
Purge flow is too high Reduce supply pressure.
ML484 | v11 Page 28
![Page 31: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/31.jpg)
Section 11. Recommended Spares List
Section 12. Drawings and Diagrams
Section 13 Certificates
Part Number Description
SP2-DV Intrinsically safe solenoid valve, switches between the purge flow and leakage compensation flow rate.
Title Drawing Number Sheet Numbers
Control Unit Drawing XMA-STD0-001 1
External Mounting Dimensions 2
Remote Panel Mounting 3
SmartPurge 2 Internal Components 4
Line Fault Detection Connector assembly 5
SmartPurge 2 Wiring Layout 6
SmartPurge2 SDV Assembly 7
SmartPurge2 Assembly and Cutouts 8
SmartPurge 2 controller and Digital Valve Cutout 9
SmartPurge 2 Hook up 10
SmartPurge 2 Intrinsically Safe Control Drawing USS
SD8112 11
SmartPurge 2 Intrinsically Safety Control Drawing Canada
SD8113 12
Component Certificate Number
SmartPurge Control Unit IECEx IECEx FME 11.0006
ATEX FM11ATEX0060
FM (USA) 3036907
FM (Canada) 3036907C
SIL 2 Rating ESC A127_CT001_(2.0)
IS SOV IECEx IECEx INE 10 0002X - 0
ATEX INNERIS-03--ATEX-0249-X
Page 29 ML484 | v11
![Page 32: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/32.jpg)
����
�����
���
���
�
���
�����
��� ��
�������
�
���
����
����
������
��������
���
���
���
�
���������
��� ����������
���
�����������
���������
��
��������
���� !
"#$%
&
�
��������
����
���'�(
����
����
����
������������
��������)*++��,��
�������++���
��
����
�����
����
����
'�!�� ��
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
��
���-����
���
����
����+
+
UN
ITE
D K
ING
DO
M
���.�
� )
����
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
SU
RR
EY
K
T7
0R
H����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
����
����
��;�)�
� �
�
�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8��# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
����
����
��;�)�
������
�����
�.��������
�,�
�
���
����������.�
���=���
�=��
�
��
�
��,
> �'�)?+
+����
���.� ����
���>
���@�
��@�
��@.
����
����
����
��;�)?
,������
������
����*�
� ����
���.�����
>
����
������������������
�����
�)�������,��,
������
����
�.��������
���
� ���
��������.�����
.�� ���������
�����
���
���*)���
�����������,
������ ���
��
')������
���������������
�������
�)
����
�����
���
�������� ��
�������
���� �
����������
��
������
����������
��
������
����������
��
����
������
���
��������
�� ��
���
����
����
��������
�
ML484 | v11 Page 30
![Page 33: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/33.jpg)
����
�A*���*BC�
���D�AD)'(BC�
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�
��������
����
���'�(
,������
������
����*�
� ����
������
�����
�.�����
���
�,�
�
����
�������
�����
����
����
�
���=���
�=��
�
��
�
��,
> �'�)?+
+����
���.� ����
���>
���@�
��@�
��@.
����
��
�
��������
���� !
"#$%
&
���.�����
>
����������
���������
���?�
++���������
���
������
���
��������
���������
��'?�AE)�?BC�
��'*
�A?)��
BC�
��(�A�)(�BC�
Page 31 ML484 | v11
![Page 34: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/34.jpg)
�?��A�BC�
���'
�A*)*?
BC�
���0�
?�A��?BC�������
����A')�?BC�
���?
�A*)E�
BC�
�?��A�)��BC�
����
����
�����
�������
��������
��F�
�(G
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8��# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�
��
����
������
���
�������������
���
���
�������
����
���=���
�=��
�
��
'
��,
> �'���.� ����
���>
���@�
��@�
��@.
����
��
�
��������
���� !
"#$%
&
���.�����
>
ML484 | v11 Page 32
![Page 35: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/35.jpg)
'�
��
*
D?
�
�
E
(
����
��)
���
������
H��
�������
�� ������
� ���
��
����
�
���
.��
����
�����
�
'����� ��
���F��������
����
�����
��G
*
*��
� ��������������
��������
���
�
?��
������
��������
�������������������
�
(��
����
�������
�����
�����
�
D������
�� ������������ ����
�
�����������
�������
���
�����
�
E��
���
����
����������
'
������������
��
��������
����
���������
��
�
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�
��������
����
���'�(
,������
������
����*�
� ����
������
�����
�.��������
�,�
�������
�� �������
��������
�
���
���=���
�=��
�
�>? *
��,
> �'�)?+
+����
���.� ����
���>
���@�
��@�
��@.
����
��
�
��������
���� !
"#$%
&
���.�����
>
Page 33 ML484 | v11
![Page 36: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/36.jpg)
�
D
�
�E
�(
��
�����
�I�����
����
������
��������
����
��
D�������������������
������
������
����������
�
�����E�
�����
��������F���
��*)D��G���
����
����
�
��������������������� ���������
����
��
?=(J
��D=�J
���
�����������'����*����?�����(����D���������E�����
����������
����
������������
��������)*++��,��
�������++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�� �������
�������
�������
��������
�
���=���
�=��
�
��
?
��,
> �'�
���.� ����
���>
���@�
��@�
��@.
����
��
�
��������
���� !
"#$%
&
���.�����
>
����
�,��
������������
�������
���.
���
���
�������
�)*�.
���
�?K��
���������
����
��
��H
�����
������
����
���������
����.������
�,��
��������
��.��������������
�������
����
.��
�������
���������
�������,��
�����
���
��.�������������H
�����
5��������
����
���
������.�F����
��G���������������������
� �����)
�����
��������
� �
���
�����
����
����
����
���
���
��
���
��
�� ���
���
��
�,��
�����
���
��.���
�)�)�������������
? ( D �
����
��)
���
������
H��
)
����� ���.
�������������
')?+
+�����
������
�
�
�����
����
������)*.����
*�
�����
����
�����
��)*.����
*�
ML484 | v11 Page 34
![Page 37: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/37.jpg)
12
34
56
78
910
1112
6 5 4 3 2 1
10
- -
+ +
+
0V
D-
D+
RE
MO
TE
PA
NE
L
OV
ER
RID
E K
EY
SW
ITC
H
EX
TE
RN
AL
AL
AR
M
AL
AR
M C
IRC
UIT
1
AL
AR
M C
IRC
UIT
2
987
SO
LE
NO
ID V
AL
VE
I/P
CO
NV
. 4
/20
mA
CA
UT
ION
!IN
TR
INS
ICA
LL
YS
AF
E C
IRC
UIT
S
FU
SE
NL
EE
LN
N.O
. C
ON
TA
CT
1A
25
0A
AC
1 M
AX
.R
EF
ER
TO
HA
ND
BO
OK
FO
R A
LA
RM
CO
NF
IGU
RA
TIO
N
TB
1
SM
AR
T P
UR
GE
CO
NT
RO
L U
NIT
(OP
TIO
NA
L)
(OP
TIO
NA
L)
SE
E N
OT
E 1
(SE
E N
OT
E 2
)
(SE
E N
OT
E 3
)
PO
WE
R T
O P
RO
TE
CT
ED
EQ
UIP
ME
NT
:6
A A
C1
MA
X.
LO
AD
FO
R 9
0 -
25
4V
ac
SU
PP
LY
5A
MA
X F
OR
11
-28
Vd
c S
UP
PL
Y
PO
WE
R S
UP
PL
Y9
0 -
25
4 V
ac
50
- 6
0 H
zO
R1
1-2
8 V
dc
PR
OT
EC
TIV
E
EA
RT
H
TE
RM
INA
LS
EX
TE
RN
AL
E
AR
TH
NO
TE
S:-
FU
SE
RA
TIN
G:
AC
SU
PP
LY
: 1
00
mA
D
C S
UP
PL
Y 5
00
mA
FIT
10
K 0
.25
W R
ES
IST
OR
IN
PL
AC
E O
F O
VE
RR
IDE
SW
ITC
H W
HE
N N
OT
RE
QU
IRE
D.
FIT
1K
0.2
5W
RE
SIS
TO
R I
N P
LA
CE
OF
EX
TE
RN
AL
AL
AR
M W
HE
N N
OT
RE
QU
IRE
D.
CO
ND
UC
TO
RS
OF
IN
TR
INS
ICA
LL
Y S
AF
E C
IRC
UIT
S S
HA
LL
NO
T B
E C
AR
RIE
D I
N T
HE
S
AM
E C
AB
LE
AS
CO
ND
UC
TO
RS
OF
CIR
CU
ITS
WH
ICH
AR
E N
OT
IN
TR
INS
ICA
LL
Y S
AF
E.
TH
E R
AD
IAL
TH
ICK
NE
SS
OF
TH
E C
ON
DU
CT
OR
IN
SU
LA
TIO
N S
HA
LL
BE
AP
PR
OP
RIA
TE
T
O T
HE
CO
ND
UC
TO
R D
IAM
ET
ER
AN
D T
HE
NA
TU
RE
OF
TH
E I
NS
UL
AT
ION
. T
HE
M
INIM
UM
RA
DIA
L T
HIC
KN
ES
S S
HA
LL
BE
0,2
mm
.
TH
E C
ON
DU
CT
OR
IN
SU
LA
TIO
N S
HA
LL
BE
SU
CH
TH
AT
IT
WIL
L B
E C
AP
AB
LE
OF
W
ITH
ST
AN
DIN
G A
N R
.M.S
. A
.C.
TE
ST
VO
LT
AG
E O
F T
WIC
E T
HE
NO
MIN
AL
VO
LT
AG
E O
F
TH
E I
NT
RIN
SIC
AL
LY
SA
FE
CIR
CU
IT W
ITH
A M
INIM
UM
OF
50
0 V
.
TH
E D
IST
AN
CE
BE
TW
EE
N T
HE
CO
ND
UC
TO
RS
OF
AN
Y C
OR
E O
F A
N I
NT
RIN
SIC
AL
LY
S
AF
E C
IRC
UIT
AN
D T
HA
T O
F A
NY
CO
RE
OF
A N
ON
-IN
TR
INS
ICA
LL
Y S
AF
E C
IRC
UIT
S
HA
LL
BE
IN
AC
CO
RD
AN
CE
WIT
H I
EC
60
07
9-1
1 T
AB
LE
5 C
OL
UM
N 4
(F
OR
37
5V
TH
IS
WIL
L B
E 1
.0 m
m)
EX
CE
PT
WH
EN
ON
E O
F T
HE
FO
LL
OW
ING
AP
PL
Y:
- T
HE
CO
RE
S O
F E
ITH
ER
TH
E I
NT
RIN
SIC
AL
LY
SA
FE
OR
TH
E N
ON
-IN
TR
INS
ICA
LL
Y S
AF
E
CIR
CU
IT A
RE
EN
CL
OS
ED
IN
AN
EA
RT
H S
CR
EE
N,
OR
- T
HE
IN
SU
LA
TIO
N O
F T
HE
IN
TR
INS
ICA
LL
Y S
AF
E C
OR
ES
IS
CA
PA
BL
E O
F
WIT
HS
TA
ND
ING
AN
R.M
.S.
A.C
. T
ES
T V
OL
TA
GE
OF
20
00
V
TE
RM
INA
L B
LO
CK
S T
ER
MIN
AL
TIG
HT
EN
ING
TO
RQ
UE
S:
N
ON
IN
TR
INS
ICA
LL
Y S
AF
E:
0
.4 -
0.5
Nm
IN
TR
INS
ICA
LL
Y S
AF
E T
B1
:
0.2
2 -
0.2
5 N
m
RE
MO
TE
PA
NE
L C
AN
BE
RE
PL
AC
ED
BY
SM
AR
T P
UR
GE
2 R
EM
OT
E L
ED
AS
SE
MB
LY
. R
EF
DR
AW
ING
SD
79
97
TH
E E
LE
CT
RIC
AL
CO
NN
EC
TIO
NS
AR
E D
ET
AIL
ED
ON
TH
IS
DR
AW
ING
1.
2.
3. 4. 5.
6.
7. 8.
(SE
E N
OT
E 9
)
9.
���.�����
>
�� !
"#$%
&
��������
��
�
����
��
��@.
��@�
���@�
���.� ����
���>
�'��,
>
�
�>�
���=���
�=��
���������
� ����.��� �����
��
�
�
��
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
���.�
� )
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
����
����
�� )
�
�����
������
�
Exp
o T
ech
no
log
ies
Lim
ited
���
����
����+
+
����������
'�!�� ��
���-����
����
����
����
�����
����
����
����
������������
��������)*++��,��
������
�++���
��
Page 35 ML484 | v11
![Page 38: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/38.jpg)
��������
�������
��*B�����
������
��-����
���,��,
������ ������
������
���
������������
�����
��,��,
�
�D��A�)�*BC�
�D��A�)D(BC�
����AD��BC�
���E�A*)��BC�
�'D�A�)*DBC�
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
�
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�� ���������
� ������,������
���
���=���
�=��
�
��
(
��,
> �'�
���.� ����
���>
���@�
��@�
��@.
����
��
��
��������
���� !
"#$%
&
���.�����
>
ML484 | v11 Page 36
![Page 39: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/39.jpg)
�������
��
����
�������
,�
����
���
������ ���,����
�����
�������������
���
�����������
��)�
���
�������������
�����������
��E�A'�*BC���E�A'�*BC�
���
?)?�AD�'�BC�������
��'
�A''
�(*BC������
����AD��BC�
���
�����.��
�
�������
��
����
��E�A'�*BC� ��E�A'�*BC�
��'
�A''
�(*BC������
���
�A�?
�'�BC������
�?)?�AD�'�BC������
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�� ���������
� ������,��
���� �
����������
���=���
�=��
�
)�)�) D
��,
> �'�
���.� ����
���>
���@�
��@�
��@.
����
����
��������
���� !
"#$%
&
���.�����
>
���
���
������ ���,����
�����
�������
,���
�����������
���
�����.��
�
��,����
���
������ ���=���
��,���
�����
������ ���=���
�'
Page 37 ML484 | v11
![Page 40: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/40.jpg)
�J���A')�BCJ�
���(�A*)E(BC�
���*
�A�)*BC�
���*
�A�BC�
�*()��A�)��BC�
������
?)?�A�)�BC�������
�������?)��A�)�E
(BC����
���
�������
(��A�)'(
C������
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
�
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�
����
��,
�����
����
���
����
�����
����
��
����=���
�=��
�
�>�
E
��,
> �''+
+�����'?�
E���.� ����
���>
���@�
��@�
��@.
���
���
�
��������
���� !
"#$%
&
���.�����
>
���
������,���=�������
����
�����
��� ���D
���������������������������
�'
ML484 | v11 Page 38
![Page 41: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/41.jpg)
�����
��
��
����
�
��.��
����
�H�����
�
����
�����������
�
��������
�����������
��.��
�����
��
����
����
� ���
���
�����
����
��� ����������
���
����.
��� ����
����������
��� ���
����
������������
��������)*++��,��
������
�++���
��
����
�����
����
����
����
����
'�!�� ��
���-����
���
����
����+
+
����������
Exp
o T
ech
no
log
ies
Lim
ited
�
�����
����
��
�����
�� )
����
SU
RR
EY
K
T7
0R
HU
NIT
ED
KIN
GD
OM
���.�
� )
����
�1��# &$�&
$4� /�$1%4�!�69%&3���!
#"+�&
$�6��� �
7�%31$�:
��0� ���
#1&
2 3%�4��%+
%$�!)���1
�7�6���$ �8�
�$��6$�!
�64�# &/%!�&
$%62�
6&!�6�����$"�&68
2��"�
&���<"
�4$)���1
�7�6���& $�$ �8�
�# �
%�!� ��# +
+"&
%#6$�!
�%&��6�$� ��%&
�91
2��9%$1
"$�9�%$$�&
�# &
4�&$�
/� +
��0� ���
#1&
2 3%�4��%+
%$�!5�&�%$1���6���$1�
7�$ �8��"4�!
�%&�6&7
�967�636
%&4$� "��%&
$���4$4)
����
����
��;�)?
����
����
��;�)�
����
����
��;�)�
� �
�
�
��������
����
���'�(
,������
������
����*�
� ����
������
�����
�.��������
�,�
�������
�� ��������=�
��
���=���
�=��
�
)�)�) ��
��,
> �'�)?+
+����
���.� ����
���>
���@�
��@�
��@.
���
���
�
��������
���� !
"#$%
&
���.�����
>
����
���
��������
����,
���
���
��������
����,
��������
�������
��*B����
�
Page 39 ML484 | v11
![Page 42: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/42.jpg)
)cdV( iU
)Am( iI
( iC)F
)H
m( iL)
W( iP
564.81.504
541.584.0
758.0
VOS
PI LA
NRETXEMRALA
EDIR- REV
O T
UO
MERT
UPTU
O
LANI
MRET1BT
2,14,3
6,58,7
21,11,01,9
)cdV( oU
85.3285.32
88.588.5
564.8
)Am( oI
5.5615.561
9.59.5
1.504
( oC)F
190.0190.0
541.5
)H
m( oL9.2
9.20
084.0
)W( oP
579.0579.0
900.0900.0
758.0
DE
DLEIHS
REVO S
RIAP DETSI
WT 2 EZIS
ROT
CU
DN
OC
NIM
mm57.0
51 EC
NED
NEPMI P
OOL XA
M
DN
UO
RG
OT DET
CEN
NO
C DLEI
HSELB A
C FO S
DNE
HTOB TA
SERTE
M 05 SI HT
GNEL
MU
MIXAM ELBA
C
ELBI
GILGE
NELBI
GILGE
N
LAITNET
OPIU
QEG
NID
NOB
HTRAE
LANRETXE
HTRAE LA
NRETXEHTRAE
MRALA LANRETXE
)TUP
NI(
TCATN
OC EERF TLOV
DEILPPUS RES
U() 21 ET
ON EES
EDIR-REV
O
)TUP
NI(
TCATN
OC EERF TLOV
DEILPPUS RES
U()21 ET
ON EES
EVLAV DI
ONEL
OS
)VOS(
DEILPP
US RESU(
)21 ETO
N EES
LAN
OITROP
OR PEVLAV
)PI(
DEILPPUS RES
U()21 ET
ON EES
DEIFITREC
2
TIN
U LORT
NO
C 2 EGR
UP TRAMS
SRETEMARAP
NOITATI
MIL YGRE
NEXX-XX-2PS
LENAP ET
OMER 2 E
GRUP TRA
MSSRETE
MARAP N
OITATIMIL Y
GRENE
LENAP ET
OME
R R
OF PR-2PS4
DNA 3 ,2 ,1 SLA
NIMRET
μ
μ
3102/80/31deti
miLseigolonhceT
opxE
505
CEN
REP
SA
1ENOZ
ISSAL
C
D'PPAD'K
HC
NWAR
D
:RE
MOT
SU
C.o
N TEEH
SF
O
ELA
CS
BD5
61WT
YE
RR
US
MO
DG
NIK
DETI
NU
LAI
RETA
M
ELG
NA dr3
NOIT
CEJO
RP
:oN
BOJ
HSI
NIFELTIT
.oN
GNI
WA
RD
:SUTATS
GNI
WAR
D
:ETAD
NWA
RD
mm
NI S
NOI
SNE
MID
ELA
CS T
ON
OD
laitnedifnoc sa detaert eb ot era yehT .detimiL seigolonhceT opxE
© thgirypoC era tne
mucod / gniward siht fo stnetnoc ehT
tnesnoc nettirw tuohti
w elohw ni ro trap ni detacinu
mmoc ro deipoc eb ot ton era yehT .tseuqer nopu elbanruter era dna
.stseretni ruo tsniaga yaw yna ni desu eb ot yeht era rehtien ,deti
miL seigolonhceT opxE morf
:VER
NM
HM
HM
NOIT
ACOL
)DEIFI
SSAL
C(SUODRAZ
AH
11
DEIFICEP
SN
USE
CN
AREL
OT5.0
± EC
ALP CE
D O
N2.0
± EC
ALP CE
D 11.0
± EC
ALP CE
D 2HT
GNEL
mm001 Y
NA
REV
O m
m4.0 N
AHT
SSEL E
B OT
SSE
NTALF
2 EGR
UP TRAMS
GNI
WARD L
ORTN
OC Y TEFAS CISNIRT
NI2118
DS
1:210
;oL ro aL< )elbacL
+ spool lla fo iL( ;oC ro a
C< )elbac
C ro spool lla fo iC( ;tl
> il ro xaml;tV
>iU ro xa
mV.1
oP>iP ro xa
mP.t pecno
C ytitnE rednu devorppA
MF eb tsum sutarappA detaicos sa fo noitarugifnoc ehT
.2.devorppA
MF eb tsum tne
mpiuqE .S.I.3
.devorppa si ti hcihw rof noitacol )deifissal
C( suodrazaH eht nihti
w dellatsni eb yam tne
mpiuqE .S.I.4
eb tsum sgni
ward lortnoc s'rerutcafunam sutarappa pool noitacol suodrazah dna tne
mpiuqE ro reirraB .S.I.5
.metsys a gnillatsni neh
w dewollof
.cdV ro s
mrV 052 naht erom etareneg ton tsu
m sutarappA detaicossA eht ot detcennoc tne
mpiuqe lortnoC
.6 s
metsys efas yllacisinirtnI fo noitallatsnI" 10.60.21PR ASI/IS
NA htiw ecnadrocca ni eb dluohs noitallatsnI
.7)07
APFN/IS
NA(
®edoC lacirtcelE lanoita
N eht dna "snoitacoL )deifissalC( suodraza
H rof.lavorpp
A MF tuohti
w dettimrep si gni
war d siht ot noisiver oN
.8 ,I ssal
C ton dna snoitacoL )deifissalC( suodraza
H 1 enoZ I ssalC ot gnitcennoc rof ylno elbatius si ']bi[' xEA
.9.snoitacoL )deifissal
C( suodrazaH 1 noisivi
D ,I ssalC ro ,0 enoZ
.aera suodrazah 1 enoZ I ssalC ni dellatsni tne
mpiuqE llA.01
yllacisnirtni eht fo noitalusni eht ro neercs htrae na ni rehtie era stiucric efas yllacisnirtni eht fo seroc ehT.11
V 0002 fo egatlov tset .C.A S.
M.R na gnidnatshti
w fo elbapac si seroc efas.devorppa
MF eb llahs tnempiuqe deilppus res
U.21
.VERREB
MUN
DO
MET
AD
DEVORPP
ADEV
ORPPA
10N
WAR
D3102/01/41
HM
ML484 | v11 Page 40
![Page 43: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/43.jpg)
)cdV(iU
)Am(iI
(iC)F
)H
m(iL)
W(iP
564.81.504
541.584.0
758.0
VOS
PILA
NRETXEMRALA
EDIR-REV
OT
UO
MERT
UPTU
O
LANI
MRET1BT
2,14,3
6,58,7
21,11,01,9
)cdV(o
U85.32
85.3288.5
88.5564.8
)Am(
oI5.561
5.5619.5
9.51.504
(oC
)F190.0
190.0541.5
)H
m(oL
9.29.2
00
84.0
)W(
oP579.0
579.0900.0
900.0758.0
LAN RETXE
HTRAE
DE
DLEIHS REVO SRI
AP EZIS R
OTCU
DN
OC
NIM
mm57.0
51 E
CNE
DNEP
MI PO
OL XA
M T
A D
NUOR
G OT
DETCE
NN
OC
DLEIHSELB
AC F
O SD
NE HTOB
SERTEM05 SI HT
GNEL
MUMIX
AM ELB
AC
DETSI
WT 2
;oLro
aL<
)elbacL+
spoolllafoiL(
;oC
roa
C<
)elbacC
rospoollla
foiC(
;tl>il
roxa
ml;tV>i
Uro
xam
V.1
oP>iP
roxa
mPadana
Cni
dellatsnineh
wdeifitre
CA
SC
rodevorppA
MFeb
tsum
sutarappAdetaicossa
fonoitarugifnoc
ehT.2
.tpecnoC
ytitnErednu
.devorppasi
tihcih
wrof
noitacolsuodraza
Heht
nihtiw
dellatsnieb
yaM
2egruP
tram
S.3
,1traP
,1 .22C
ASC
,edoClacirtcelE
naidanaC
ehthti
wecnadrocca
nieb
dluohsadana
Cni
noitallat snI.4
.FxidneppA
.lavor ppA
MFtuohti
wdetti
mrepsi
gniward
sihtot
noisivero
N.5
.devorppasi
tihcih
wrof
noitacolsuodraza
Heht
nihtiw
dellatsnieb
yam
tnempiuqE
.S.I.6
ebtsu
msgni
wardlortnocs'rerutcafuna
msutarappa
poolnoitacol
suodrazahdna
tnempiuqE
roreirraB
.S.I.7
.metsys
agnillatsni
nehw
dewollof
aerasuodrazah
1enoZ
Issal
Cni
dellatsnisi
tnempiuqEll
A.8
yllacisnirtnieht
fonoitalusni
ehtro
neercshtrae
nani
rehtieera
stiucricefas
yllacisnirtnieht
foseroc
ehT.9
V0002
foegatlov
tset.
C.AS.
M.R
nagnidnatshti
wfo
elbapacsi
serocefas
deifitrecA
SC
rodevorppa
MFebllahs
tnempiuqe
deilppusres
U.01
ELBIGIL
GEN
ELBI
GILGE
N
MRALALA
NRETXE
)TUP
NI(
TCATN
OCEERF
TLOV
DEILPPUS
RESU(
)01ET
ON
EES
LAN
OITROP
ORPEVLAV
)PI(
DEILPPUS
RESU(
)01ET
ON
EES
EVLAVDI
ONEL
OS
)VOS(
DEILPPUS
RESU(
)01ET
ON
EESLAIT
NETOPI
UQE
GNI
DN
OBHTRAE
LANRETXE
HTRAEE
DIR-REVO
)TUP
NI(
TCATN
OCEERF
TLOV
DEILPPUS
RESU(
)01ET
ON
EES
DEIFITREC
2
TIN
UL
ORTN
OC2
EGR
UPT
RAMS
SRETEMARAP
NOITATI
MILY
GRENE
XX-XX-2PS
LENAP
ETO
MER2
EG
RUP
TRA
MSS
RETEMARAP
NOITATI
MILY
GRENE
LENAP
ETO
MERR
OFPR-2PS
4D
NA3
,2,1
SLANI
MRET
μμ
3102/90/42deti
miLseigolonhceT
opxE
CEC
REP
SA
1ENOZ
ISSAL
C
D'PPAD'K
HC
NWAR
D
:RE
MOT
SU
C.o
NTEE
HS
FO
ELA
CS
BD5
61WT
YE
RR
US
MO
DG
NIK
DETI
NU
LAI
RETA
M
E LG
NA
dr3N
OITCEJ
ORP
:oN
BOJ
HSI
NIFELTIT
.oN
GNI
WA
RD
:SUTATS
GNI
WAR
D
:ETAD
NWA
RD
mm
NIS
NOI
SNE
MID
ELA
CS
TO
NO
D
laitnedifnocsa
detaerteb
otera
yehT.deti
miLseigolonhceT
opxE©
thgirypoC
eratne
mucod/
gniward
sihtfo
stnetnocehT
tnesnocnettir
wtuohti
weloh
wni
rotrap
nidetacinu
mmoc
rodeipoc
ebot
tonera
yehT.tseuqer
nopuelbanruter
eradna
.stseretniruo
tsniagaya
wyna
nidesu
ebot
yehtera
rehtien,deti
miLseigolonhceT
opxEmorf
:VER
NM
PM
HM
NOIT
ACOL
SUODRAZ
AH
11
DEIFICEP
SN
USE
CN
AREL
OT5.0
±E
CALP
CED
ON
2.0±
EC
ALPCE
D1
1.0±
EC
ALPCE
D2
HTG
NELm
m001Y
NA
REV
Om
m4.0N
AHT
SSEL
EB
OTS
SENT
ALF
2E
GRUP
TRAMS
GNI
WARD
LORT
NOC
YTEFASCIS
NIRTNI
3118DS
1:2E
.VERREB
MUN
DO
MET
AD
DEVORPP
ADEV
ORPPA
Page 41 ML484 | v11
![Page 44: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/44.jpg)
ML484 | v11 Page 42
![Page 45: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/45.jpg)
F)L o
(mH
)P o
(W)
SOV
1, 2
23.5
816
5.5
0.09
12.
90.
975
IP3,
423
.58
165.
50.
091
2.9
0.97
5R
emot
e O
utpu
t9,
10,
11,
12
8.46
540
5.1
5.14
50.
480.
857
Exte
rnal
ala
rm5,
65.
885.
9N
eglig
ible
00.
009
Ove
r-rid
e7,
85.
885.
9N
eglig
ible
00.
009
Ui (V
dc)
I i (mA)
Ci (
F)L i (m
H)
P i (W)
8.46
540
5.1
5.14
50.
480.
857
Page 43 ML484 | v11
![Page 46: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/46.jpg)
ML484 | v11 Page 44
![Page 47: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/47.jpg)
Nic
hola
s Lu
dlam
D
eput
y C
ertif
icat
ion
Man
ager
, FM
App
rova
ls L
td.
Issu
e da
te: 2
nd A
pril,
201
3
THIS
CER
TIFI
CA
TE M
AY
ON
LY B
E R
EPR
OD
UC
ED IN
ITS
ENTI
RET
Y A
ND
WIT
HO
UT
CH
AN
GE
FM A
ppro
vals
Ltd
. 1 W
inds
or D
ials
, Win
dsor
, Ber
kshi
re, U
K. S
L4 1
RS
T: +
44 (0
) 175
3 75
0 00
0 F
: +44
(0) 1
753
868
700
E-m
ail:
atex
@fm
appr
oval
s.co
m w
ww
.fmap
prov
als.
com
F AT
EX 0
20 (M
ay/1
2)
Page
1 o
f 3
1
EC-T
YPE
EXA
MIN
ATI
ON
CER
TIFI
CA
TE2
Equi
pmen
t or P
rote
ctiv
e sy
stem
s in
tend
ed fo
r use
in P
oten
tially
Expl
osiv
e A
tmos
pher
es -
Dire
ctiv
e 94
/9/E
C
3 EC
-Typ
e Ex
amin
atio
n C
ertif
icat
e N
o:
FM11
ATE
X006
0 4
Equi
pmen
t or p
rote
ctiv
e sy
stem
: (T
ype
Ref
eren
ce a
nd N
ame)
Sm
artP
urge
2 Pu
rge
Con
trol
Uni
t
5 N
ame
of A
pplic
ant:
Ex
po T
echn
olog
ies
Lim
ited
6 A
ddre
ss o
f App
lican
t: U
nit 2
, The
Sum
mit,
H
anw
orth
Roa
d,
Sunb
ury
on T
ham
es,
Surr
ey, T
W16
5D
B, U
nite
d K
ingd
om
7 Th
is e
quip
men
t or p
rote
ctiv
e sy
stem
and
any
acc
epta
ble
varia
tion
ther
eto
is s
peci
fied
in th
e sc
hedu
le to
this
ce
rtific
ate
and
docu
men
ts th
erei
n re
ferre
d to
.
8 FM
App
rova
ls L
td, n
otifi
ed b
ody
num
ber 1
725
in a
ccor
danc
e w
ith A
rticl
e 9
of D
irect
ive
94/9
/EC
of 2
3 M
arch
19
94, c
ertif
ies
that
this
equ
ipm
ent h
as b
een
foun
d to
com
ply
with
the
Esse
ntia
l Hea
lth a
nd S
afet
y R
equi
rem
ents
re
latin
g to
the
desi
gn a
nd c
onst
ruct
ion
of e
quip
men
t int
ende
d fo
r use
in p
oten
tially
exp
losi
ve a
tmos
pher
es g
iven
in
Ann
ex II
to th
e D
irect
ive.
Th
e ex
amin
atio
n an
d te
st re
sults
are
reco
rded
in c
onfid
entia
l rep
ort n
umbe
r:
3041
589E
C d
ated
23
Mar
ch 2
012
9
Com
plia
nce
with
the
Esse
ntia
l Hea
lth a
nd S
afet
y R
equi
rem
ents
, with
the
exce
ptio
n of
thos
e id
entif
ied
in it
em 1
5 of
the
sche
dule
to th
is c
ertif
icat
e, h
as b
een
asse
ssed
by
com
plia
nce
with
the
follo
win
g do
cum
ents
:
EN60
079-
0:20
09, E
N60
079-
2:20
07, E
N60
079-
7:20
07, E
N60
079-
11:2
007,
EN
6007
9-18
:200
9,
EN60
079-
31:2
009,
EN
6124
1-4:
2006
and
EN
6052
9:19
91 +
A1:
2000
10
If th
e si
gn �X
� is
plac
ed a
fter
the
certi
ficat
e nu
mbe
r, it
indi
cate
s th
at t
he e
quip
men
t is
sub
ject
to
spec
ial
cond
ition
s fo
r saf
e us
e sp
ecifi
ed in
the
sche
dule
to th
is c
ertif
icat
e.
11
Th
is E
C-T
ype
Exam
inat
ion
certi
ficat
e re
late
s on
ly t
o th
e de
sign
, ex
amin
atio
n an
d te
sts
of t
he s
peci
fied
equi
pmen
t or p
rote
ctiv
e sy
stem
in a
ccor
danc
e to
the
dire
ctiv
e 94
/9/E
C. F
urth
er re
quire
men
ts o
f the
Dire
ctiv
e ap
ply
to th
e m
anuf
actu
ring
proc
ess
and
supp
ly o
f thi
s eq
uipm
ent o
r pro
tect
ive
syst
em. T
hese
are
not
cov
ered
by
this
cer
tific
ate.
12
The
mar
king
of t
he e
quip
men
t or p
rote
ctiv
e sy
stem
sha
ll in
clud
e:
Smar
tPur
ge2
Purg
e C
ontr
ol U
nit
II 2
(2) G
Ex
e ib
mb
[p] I
IC T
4 -2
0°C
T
a 6
0°C
II 2
(2) D
Ex
tb [p
D] I
IIC 1
35°C
-20°
C
Ta
60°
C
Smar
tPur
ge 2
Rem
ote
Con
trol
Ter
min
al
II 2
G E
x ib
IIC
T4
-20°
C
Ta
60°
C
D
igita
lly si
gned
by
Nic
hola
s Lud
lam
D
N: c
n=N
icho
las L
udla
m, o
=Dep
uty
Cert
ifica
tion
Man
ager
, ou=
FM A
ppro
vals
, em
ail=
nich
olas
.ludl
am@
fmap
prov
als.c
om
, c=G
B D
ate:
201
3.04
.02
15:4
0:09
+01
'00'
SCH
EDU
LE
to
EC
-Typ
e E
xam
inat
ion
Cer
tific
ate
No.
FM
11A
TEX
0060
THIS
CER
TIFI
CA
TE M
AY
ON
LY B
E R
EPR
OD
UC
ED IN
ITS
ENTI
RET
Y A
ND
WIT
HO
UT
CH
AN
GE
FM
App
rova
ls L
td. 1
Win
dsor
Dia
ls, W
inds
or, B
erks
hire
, UK
. SL4
1R
S
T: +
44 (0
) 175
3 75
0 00
0 F
: +44
(0) 1
753
868
700
E-m
ail:
atex
@fm
appr
oval
s.co
m w
ww
.fmap
prov
als.
com
F
ATE
X 0
20 (M
ay/1
2)
Pag
e 2
of 3
13
Des
crip
tion
of E
quip
men
t or P
rote
ctiv
e Sy
stem
:
Th
e S
mar
tPur
ge 2
(SP
2) is
an
elec
troni
c pu
rge
and
pres
suriz
atio
n co
ntro
l sys
tem
con
sist
ing
of a
Con
trol
Uni
t con
tain
ing
the
follo
win
g: a
pow
er s
uppl
y an
d sw
itchi
ng m
odul
e, a
flow
and
pre
ssur
e m
easu
ring
unit
and
an e
lect
roni
c co
ntro
l uni
t. A
dis
play
is p
rovi
ded
for m
onito
ring
the
stat
us a
nd fo
r use
dur
ing
set-u
p.
Two
vers
ions
of t
he S
mar
tPur
ge2
are
avai
labl
e, a
s a
purg
e an
d pr
essu
rize
cont
rol u
nit (
P) a
nd a
s a
fan
cont
rol u
nit (
F). B
oth
thes
e ve
rsio
ns a
re a
vaila
ble
with
eith
er s
tain
less
ste
el (s
s) o
r alu
min
ium
enc
losu
res
(al)
and
with
a u
nive
rsal
vol
tage
(M) o
r a lo
w v
olta
ge (L
) pow
er s
uppl
y.
The
syst
em c
an b
e co
nnec
ted
to a
n op
tiona
l Rem
ote
Pan
el w
hich
is h
ouse
d in
an
alum
iniu
m e
nclo
sure
. Th
e m
axim
um s
ervi
ce te
mpe
ratu
re is
60°
C.
SP2-
ab-c
Sm
artP
urge
2 Pu
rge
Con
trol
Uni
t a
=
P, o
r F
b =
M, o
r L
c =
ss, o
r al
Pow
er S
uppl
y (T
erm
inal
s 1,
2):
90-2
54 V
ac o
r 11-
28 V
dc;
Um
= 2
54 V
ac
Ala
rm C
onta
ct ra
tings
(Ter
min
als
5, 6
and
7, 8
): 2
50V
, 1A
Fu
se ty
pe (T
erm
inal
s 9,
10)
:
10
0mA
(whe
n b
= M
)
50
0mA
(whe
n b
= L)
E
nerg
y Li
mita
tion
Par
amet
ers
Te
rmin
al T
B1
Uo
(Vdc
) Io
(mA
) C
o (
F)
Lo (m
H)
Po
(W)
SO
V
1, 2
23
.58
165.
5 0.
091
2.9
0.97
5 IP
3,
4
23.5
8 16
5.5
0.09
1 2.
9 0.
975
Rem
ote
Out
put
9, 1
0, 1
1, 1
2 8.
465
405.
1 5.
145
0.48
0.
857
Ext
erna
l ala
rm
5, 6
5.
88
5.9
Neg
ligib
le
0 0.
009
Ove
r-rid
e 7,
8
5.88
5.
9 N
eglig
ible
0
0.00
9
Smar
tPur
ge2
Purg
e R
emot
e Pa
nel
SR
P-2
E
nerg
y Li
mita
tion
Par
amet
ers
Ui (
Vdc
) Ii
(mA
) C
i (F)
Li
(mH
) P
i (W
) 8.
465
405.
1 5.
145
0.48
0.
857
14
Sp
ecifi
c C
ondi
tions
of U
se:
N
one
15
Esse
ntia
l Hea
lth a
nd S
afet
y R
equi
rem
ents
:
Th
e re
leva
nt E
HS
Rs
that
hav
e no
t bee
n ad
dres
sed
by th
e st
anda
rds
liste
d in
this
cer
tific
ate
have
bee
n id
entif
ied
and
asse
ssed
in th
e co
nfid
entia
l rep
ort i
dent
ified
in it
em 8
.
Page 45 ML484 | v11
![Page 48: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/48.jpg)
�
��������������� ����������������������� �����������������������������������������
������������� ����!�"##���$%#��$�&�'�(��!���)�*��+, -,������������!�...,��+, -,����
Certificate of Conformity to IEC 61508 Safety Integrity Level (SIL) 2
Functional Safety of Safety-Related Programmable Electronic Systems
The ‘SmartPurge ATEX Certified Intelligent Purge and Pressurise
System SP2’
Designed and manufactured by
Expo Technologies Ltd Summer Road, Thames Ditton, Surrey, KT7 0RH, UK
The above system has been assessed and is considered capable for use in a SIL2 high demand safety function. The assessment was based on the assumptions and data provided in:
• ESC Ltd Report No. A127_SV001_(2.0)
The system assessed comprises of the following modules in full redundant configuration:
• Pressure Transmitter
• Logic Board
• Relay
With the output normally energised, de-energise to safe state, the estimated frequency of dangerous failure per hour is 2.2E-7 (providing a minimum proof test interval of 1 year); The assessment was carried out to determine compliance with IEC 61508 with regards to:
• Random Hardware Failures;
• Minimum Architecture.
Managing Director: Kenneth G L Simpson
Member of IEC61508 and IEC 61511 committees Assessment Date: August 2011
[Certificate: A127_CT001_(2.0)]
ML484 | v11 Page 46
![Page 49: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/49.jpg)
Page 47 ML484 | v11
![Page 50: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/50.jpg)
ML484 | v11 Page 48
![Page 51: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/51.jpg)
Page 49 ML484 | v11
![Page 52: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/52.jpg)
ML484 | v11 Page 50
![Page 53: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/53.jpg)
Page 51 ML484 | v11
![Page 54: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/54.jpg)
ML484 | v11 Page 52
![Page 55: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/55.jpg)
Page 53 ML484 | v11
![Page 56: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/56.jpg)
To v
erify
the
avai
labi
lity
of th
e Ap
prov
ed p
rodu
ct, p
leas
e re
fer t
o ww
w.ap
prov
algu
ide.
com
FM
App
rova
ls H
LC 5
/13
3047
764
Pa
ge 1
of 3
F
M A
ppro
vals
1151
Bos
ton
Prov
iden
ce T
urnp
ike
P.O
. Box
910
2 N
orwo
od, M
A 0
2062
USA
T:
781
762
430
0 F
: 781
-762
-937
5 ww
w.fm
appr
oval
s.com
CER
TIFI
CATE
OF
COM
PLIA
NCE
HAZA
RDO
US (
CLAS
SIFI
ED)
LOCA
TIO
N EL
ECTR
ICAL
EQ
UIPM
ENT
This
certi
ficat
e is
issue
d fo
r the
follo
wing
equ
ipm
ent:
SP
2-ab
-c S
mar
tPur
ge2
Purg
e Co
ntro
l Uni
t I/1
/AEx
e ib
mb
[p] I
IC T
4 -2
0°C ≤
Ta ≤
60°
C; -
SD81
12; E
ntity
; IP6
4 21
/AEx
tb [p
D] II
IC T
135°
C -2
0°C ≤
Ta ≤
60°
C; -
SD81
12; E
ntity
; IP6
4 a
= P
or F
, Sys
tem
type
b
= M
or L
, Sup
ply
volta
ge
c =
ss o
r al,
Enclo
sure
mat
eria
l
Entit
y pa
ram
eter
s
Term
inal
TB
1 U 0
(V
dc)
I 0 (m
A)
C 0 (
μF)
L 0 (m
H)
P 0 (
W)
SOV
1,2
23.5
8 16
5.5
0.09
1 2.
9 0.
975
IP
3,4
23.5
8 16
5.5
0.09
1 2.
9 0.
975
Rem
ote
Out
put
9,10
,11,
12
8.46
5 40
5.1
5.14
5 0.
48
0.85
7
Exte
rnal
al
arm
5,
6 5.
88
5.9
Negl
igib
le
0 0.
009
Ove
r-rid
e 7,
8 5.
88
5.9
Negl
igib
le
0 0.
009
SP
2-RP
Sm
artP
urge
2 Re
mot
e Co
ntro
l Ter
min
al
I/1/A
Ex ib
IIC
T4 -2
0°C ≤
Ta ≤
60°
C; -
SD81
12; E
ntity
Entit
y pa
ram
eter
s Ui
(Vdc
) Ii(
mA)
Ci
(μF
) Li
(mH)
Pi
(W
) 8.
465
405.
1 5.
145
0.48
0.
857
Equi
pmen
t Rat
ings
: Th
e Sm
artP
urge
2 Pu
rge
Cont
rol U
nit i
s FM
App
rove
d fo
r Cla
ss I,
Zon
e 1,
AEx
e ib
mb
[p] I
IC
and
Zone
21,
AEx
tb[p
d] II
IC h
azar
dous
(cla
ssifie
d) lo
catio
ns. (
indo
ors/
outd
oors
; IP
64) f
or th
e Un
ited
Stat
es w
hen
inst
alle
d as
per
con
trol d
rawi
ng S
D811
2. T
he S
mar
tPur
ge2
Rem
ote
Cont
rol T
erm
inal
is F
M A
ppro
ved
for C
lass
I, Z
one
1, A
Ex ib
IIC
T4 H
azar
dous
(Cla
ssifie
d)
Loca
tions
. (in
door
s/ou
tdoo
rs; I
P64)
for t
he U
nite
d St
ates
whe
n in
stal
led
as p
er c
ontro
l dra
wing
SD
8112
.
FM
App
rove
d fo
r:
Expo
Tec
hnol
ogie
s Lt
d Su
nbur
y on
Tha
mes
, Sur
rey
Unite
d Ki
ngdo
m
ML484 | v11 Page 54
![Page 57: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/57.jpg)
To v
erify
the
avai
labi
lity
of th
e Ap
prov
ed p
rodu
ct, p
leas
e re
fer t
o ww
w.ap
prov
algu
ide.
com
FM
App
rova
ls H
LC 5
/13
3047
764
Pa
ge 3
of 3
This
cer
tifie
s th
at th
e eq
uipm
ent d
escr
ibed
has
bee
n fo
und
to c
ompl
y wi
th th
e fo
llowi
ng
Appr
oval
Sta
ndar
ds a
nd o
ther
doc
umen
ts:
Cl
ass
3620
20
11
Cl
ass
3810
20
05
AN
SI/IS
A 61
010-
1 20
04
AN
SI/IE
C 60
529
2004
ANSI
/ISA
6007
9-0
2009
ANSI
/ISA
6007
9-2
2010
ANSI
/ISA
6007
9-7
2008
ANSI
/ISA
6007
9-11
20
09
AN
SI/IS
A 60
079-
18
2009
ANSI
/ISA
6007
9-31
20
09
O
rigin
al P
roje
ct ID
: 30
4776
4 Ap
prov
al G
rant
ed:
Janu
ary
10, 2
014
Subs
eque
nt R
evis
ion
Repo
rts /
Date
App
rova
l Am
ende
d
Repo
rt Nu
mbe
r Da
te
Repo
rt Nu
mbe
r Da
te
FM
App
rova
ls L
LC
10
Jan
uary
201
4
J.E.
Mar
qued
ant
Gro
up M
anag
er, E
lect
rical
Date
To v
erify
the
avai
labi
lity
of th
e Ap
prov
ed p
rodu
ct, p
leas
e re
fer t
o ww
w.ap
prov
algu
ide.
com
FM
App
rova
ls H
LC 5
/13
3047
764C
Page
1 o
f 3
F
M A
ppro
vals
1151
Bos
ton
Prov
iden
ce T
urnp
ike
P.O
. Box
910
2 N
orwo
od, M
A 0
2062
USA
T:
781
762
430
0 F
: 781
-762
-937
5 ww
w.fm
appr
oval
s.com
CER
TIFI
CATE
OF
COM
PLIA
NCE
HAZA
RDO
US L
OCA
TIO
N EL
ECTR
ICAL
EQ
UIPM
ENT
PER
CANA
DIAN
REQ
UIRE
MEN
TS
This
certi
ficat
e is
issue
d fo
r the
follo
wing
equ
ipm
ent:
SP
2-ab
-c S
mar
tPur
ge2
Purg
e Co
ntro
l Uni
t I/1
/Ex
e ib
m [p
] IIC
T4
-20°
C ≤
Ta ≤
60°
C;-S
D811
3; E
ntity
; IP6
4 a
= P
or F
, Sys
tem
type
b
= M
or L
, Sup
ply
volta
ge
c =
ss o
r al,
Enclo
sure
mat
eria
l
Entit
y pa
ram
eter
s
Te
rmin
al
TB1
U 0
(Vdc
) I 0
(mA)
C 0
(μF
) L 0
(mH)
P 0
(W
)
SOV
1,2
23.5
8 16
5.5
0.09
1 2.
9 0.
975
IP
3,4
23.5
8 16
5.5
0.09
1 2.
9 0.
975
Rem
ote
Out
put
9,10
,11,
12
8.46
5 40
5.1
5.14
5 0.
48
0.85
7
Exte
rnal
al
arm
5,
6 5.
88
5.9
Negl
igib
le
0 0.
009
Ove
r-rid
e 7,
8 5.
88
5.9
Negl
igib
le
0 0.
009
Page 55 ML484 | v11
![Page 58: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/58.jpg)
To v
erify
the
avai
labi
lity
of th
e Ap
prov
ed p
rodu
ct, p
leas
e re
fer t
o ww
w.ap
prov
algu
ide.
com
FM
App
rova
ls HL
C 5/
13
3047
764C
Page
2 o
f 3
SP2-
RP S
mar
tPur
ge2
Rem
ote
Pane
l I/1
/Ex
ib II
C T4
-20°
C ≤
Ta ≤
60°
C;- S
D811
3; E
ntity
Entit
y pa
ram
eter
s Ui
(Vdc
) Ii(
mA)
Ci
(μF
) Li
(mH)
Pi
(W
) 8.
465
405.
1 5.
145
0.48
0.
857
Equi
pmen
t Rat
ings
: Th
e Sm
artP
urge
2 Pu
rge
Cont
rol U
nit i
s FM
App
rove
d fo
r Cla
ss I,
Zon
e 1,
Ex
e ib
m [p
] IIC
Ha
zard
ous
Loca
tions
(ind
oors
/out
door
s; IP
64) f
or C
anad
a wh
en in
stal
led
as p
er c
ontro
l dra
wing
SD
8113
. Th
e Sm
artP
urge
2 Re
mot
e Co
ntro
l Ter
min
al is
FM
App
rove
d fo
r Cla
ss I,
Zon
e 1,
Ex
ib
IIC T
4 Ha
zard
ous
Loca
tions
for C
anad
a wh
en in
stal
led
as p
er c
ontro
l dra
wing
SD8
113.
FM
App
rove
d fo
r:
Expo
Tec
hnol
ogie
s Lt
d Su
nbur
y on
Tha
mes
, Sur
rey
Unite
d Ki
ngdo
m
To v
erify
the
avai
labi
lity
of th
e Ap
prov
ed p
rodu
ct, p
leas
e re
fer t
o ww
w.ap
prov
algu
ide.
com
FM
App
rova
ls HL
C 5/
13
3047
764C
Page
3 o
f 3
This
certi
fies
that
the
equi
pmen
t des
crib
ed h
as b
een
foun
d to
com
ply
with
the
follo
wing
Ap
prov
al S
tand
ards
and
oth
er d
ocum
ents
:
CSA
C22.
2 N
o.10
10.1
20
04
CS
A C2
2.2
No.
6052
9 20
10
CA
N/C
SA E
6007
9-0
2011
CAN/
CSA
E60
079-
2 20
12
CA
N/C
SA E
6007
9-7
2012
CAN/
CSA
E60
079-
11
2011
CAN/
CSA
E 6
0079
-18
2012
O
rigin
al P
roje
ct ID
: 30
4776
4C
Appr
oval
Gra
nted
: Ja
nuar
y 10
, 201
4
Subs
eque
nt R
evisi
on R
epor
ts /
Date
App
rova
l Am
ende
d
Repo
rt Nu
mbe
r Da
te
Repo
rt Nu
mbe
r Da
te
FM
App
rova
ls LL
C
10
Jan
uary
201
4
J.E.
Mar
qued
ant
Gro
up M
anag
er, E
lect
rical
Date
ML484 | v11 Page 56
![Page 59: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/59.jpg)
Smartpurge2 CE SC029 Iss 4.Docx3
Declaration of Conformity
WithEuropeanDirectives
Expo Technologies Ltd Unit 2, The Summit, Hanworth Road Sunbury on Thames TW16 5DB UK
This document confirms that the SmartPurge 2 Purge Control Unit
manufactured by Expo Technologies Ltd conforms, as described, to the following European Directives and standards:
Product description The SmartPurge 2 (SP2) is an electronic purge and pressurization control system consisting of a Control Unit containing the following: a power supply and switching module, a flow and pressure measuring unit and an electronic control unit. A display is provided for monitoring the status and for use during set-up. Two versions of the SmartPurge2 are available, as a purge and pressurize control unit and as a fan control unit. Both these versions are available with either stainless steel or aluminium enclosures and with a universal voltage or a low voltage power supply. Directive 2004/108/EC Electromagnetic Compatibility (EMC) The SmartPurge 2 system described above is in conformity with Directive 2004/108/EC. Intertek technical report EM11055661 shows compliance with the essential requirements of the directive. Directive 2011/65/EC Restriction of the use of certain hazardous substances (RoHS) The SmartPurge 2 system described above is in conformity with Directive 2011/65/EU. All electrical or electronic components used by Expo Technologies Ltd or our suppliers are RoHS compliant. Directive 94/9/EC Equipment for explosive atmospheres (ATEX) The SmartPurge 2 system described above is designed in conformity with ATEX Directive 94/9/EC, in compliance with:
EN 60079-0:2012+A11:2013 EN 60079-2:2014 EN 60079-7:2007 EN 60079-11:2012 EN 60079-18:2009 EN 60079-31:2014
EN 60529:1992+A2:2013 The SmartPurge 2 is certified by FM Approvals Ltd, Windsor, Berkshire, UK. SL4 1RS, under EC Type Examination Certificate FM11ATEX0060, in compliance with:
EN 60079-0:2009 EN 60079-2:2007 EN 60079-7:2007 EN 60079-11:2007 EN 60079-18:2009 EN 60079-31:2009
EN61241-4:2006 EN 60529:1991 + A1:2000 SmartPurge systems are manufactured under Product Quality Assurance Notification SIRA 99 ATEX M043, issued by SIRA Certification Service, Notified Body No. 0518. Signed Date 29/05/2015 Managing Director Confidential Assessment file reference SC029
Page 57 ML484 | v11
![Page 60: SP2-PX-ss SmartPurge Manual - Expo Technologies · Section 1. System Specification SmartPurge Control Unit Data Model Number SP2 – ab – c a = P for Purge and Pressurize Control](https://reader031.vdocuments.us/reader031/viewer/2022021801/5b4764577f8b9a501f8cc6f6/html5/thumbnails/60.jpg)
Expo Technologies Ltd.
Unit 2 The SummitHanworth RoadSunbury on ThamesTW16 5DBUK
Tel:Fax:E-mail:
+44(0)20 8398 8011+44(0)20 8398 8014 [email protected]
Expo Technologies Inc.
9140 Ravenna Road Unit #3TwinsburgOH 44087USA
Tel:Fax:E-mail:
+1 (440) 247 5314+1 (330) 487 [email protected]
www.expoworldwide.com