construction type: cavity barriers
1
The purpose-made solution for cavity fire stopping
SP Firestop Systems
AUGUST 2016
construction type: cavity barriers
2
Description
As part of the comprehensive FIREPRO® range of fire protection products, ROCKWOOL SP Firestop Slab is a product specifically designed to form cavity fire stops within buildings.
It may be installed horizontally or vertically and is suitable for cavity widths between 50mm and 400mm, in both masonry and curtain wall constructions.
NB: For cavity widths of 250mm or more, jointsbetween adjacent lengths of firestops should besealed on the top surface with aluminium foil tape.The product has been designed as a one-piece system and allows easy cutting and installation. It provides a unique lateral compression to facilitate tightness of fit.
The product is available in two versions:SP 60 Slab, provides 1 hour fire resistance.SP 120 Slab, provides 2 hours fire resistance.
Benefits
Easytocutandinstall
Ensuressitetolerancesareaccommodated
Independentlytestedtoprovide2hoursoffireresistance
Resiststhepassageofsmoke–aluminiumfoilfacedonbothsides
Suitableforcavitywidthsupto400mm
Easysitestorageandhandling
QualityassuredtoBSENISO9001
SP Firestop Slabs at floor / external wall junctionInternational Patent App. PCT/GB98/01733
SPFirestopSystems
construction type: cavity barriers
3
Dimensions
ROCKWOOLSP60FirestopSlab:1000x650x75mmthickROCKWOOLSP120FirestopSlab:1000x650x90mmthickTheproductsarefacedonbothsideswithreinforcedaluminiumfoiltogiveClassOratingandexcellentsmokeresistance.
Bothslabsaredesignedtobecuton-site,toproducecavityfirestopsof1000mmlengthandinwidthstosuitindividualcavitysizes,asshowninFigure1.
Accessories
ROCKWOOLSPFixingBrackets*arerequiredfortheinstallation(figureB).Theyaresuppliedintwostandardtypes,namelySP/SFixingBracketdesignedforcavitiesupto,andincluding100mmwideandSP/LFixingBracketforcavitiesover100mmandupto400mmwide.
Bracketsaresuppliedincardboardboxes,flatpacked,andaredesignedtobeeasilyre-profiledbyhandonsite.TheSPFixingBracketsshouldbecutonsiteasnecessarytoallowatleast75%penetrationoftheFirestop.
*Pleasenote:Inordertocomplywiththefiretestcertification,onlyROCKWOOLSPFixingBracketsshouldbeusedtoinstalltheproduct.
SP Firestop Slab – direction of cut to produce 1000 mm long Firestop stripsto suit cavity width W
1000
mm
650 mm
W
Figure 1 Cutting method for SP Firestop Slab
Re-profile the bracket by hand to form a Z shape
min. 75% penetration
Break off tab at serration prior to installation
Secure bracket with metal fixings suitable for masonry
Re-profile the bracket by hand to form a Z shape
min. 75% penetration
Break off tab at serration prior to installation
Secure bracket with metal fixings suitable for masonry
Figure 2 SP Firestop Fixing Bracket
Figure 3 Sectional view of Firestop Slab and Bracket
SPFirestopSystems
construction type: cavity barriers
4
Standardsandapprovals
ROCKWOOLSP60andSP120FirestopSlabshavebeentestedandassessedinaccordancewithBS476:Part20:1987andhaveachieved60minutesand120minutesrespectivelyforbothintegrityandinsulation,asdetailedinLPCassessmentCC89697.
ROCKWOOLSP60andSP120FirestopSlabscomplywiththeprovisionsofApprovedDocumentB3ofthe1991buildingRegulations(2002edition).
SPFirestopSystemsarethirdpartyapprovedbytheLossPreventionCouncilCertificationboard(LPCB)forperformanceandqualityandarelistedintheRed Book-certificateno.022b.Certificatescanbeaccessedonlineatwww.rockwool.co.ukorwww.redbooklive.com
Performance
FireThebasemineralwoolofROCKWOOLSP60andSP120FirestopSlabsisinherentlyfiresafeandachievesEuroClassA1.ROCKWOOLproductswillwithstandtemperaturesofupto1000°Cwithoutmelting.
AcousticROCKWOOLproductshaveexcellentacousticproperties,andcansignificantlyreducethelevelsofairbornesoundtransmissionthroughwallandfloorcavities.
Resistance to moistureROCKWOOLSP60andSP120FirestopSlabsarewaterrepellentandunaffectedbythefreeze/thawcycle.
Applications
Fireresistancebetweentheedgeofaconcretefloorslabandcurtainwallingwhichisstableinfire.
ROCKWOOL®SP60andSP120FirestopSlabsprovideoneandtwohoursfireresistancerespectivelyinvoidsupto400mmwide.
Pleasenote:Curtainwallingsystemsshouldbeadequatelyrestrainedtothefloor.
FigureDillustratesatypicalarrangement,usingSPFixingBracketsat500mmcentres.
Masonry wall cavitiesROCKWOOL®SP60andSP120FirestopSlabsprovideoneandtwohoursfireresistancerespectivelyinmasonrywallcavitiesupto400mmwide.Theycanbeusedbothhorizontallyandvertically.
Figure5illustratestypicalapplications,withtheproductfittedtightlybetweenmasonryleaves.Whenitisnotpossibletobuildthebracketsintoaleaf,thefixingscanbere-profiledasnecessaryandmechanicallyfixedtothefaceofthemasonry.
TheapplicationofROCKWOOLSPFirestopSlabsistheresponsibilityofthesiteoperator.Fixingsequenceinstructionsareshownclearlyoneachpackaswellascuttingguidelinesonthesurfaceofeachslab.
External claddingWhereusedinconjunctionwithprofiledmetalcladding,cuttheROCKWOOL®SPFirestopSlabtosuittheprofile.
Suitable for cavity widths up to 400mm*
Sitework
ROCKWOOLSPFirestopSlabsaredesignedforcuttingonsitewithasharpknifeorsawandastraightedge.ThecavitytobefirestoppedshouldbemeasuredandtheROCKWOOLSPFirestopSlabcuttosuitthisdimension,usingonepieceonlypergapwidth–seeFigures4and5.
Foreasycompressionfittingandtoaccommodatethefixingpattern,cuttingshouldbealongthe1000mmwidthasindicatedinfigure1.
TheSPFixingBracketsarethenre-profiledbyhandandcutasnecessarytoallowatleast75%penetrationofthefirestopmaterial.
Theyshouldbeplacedasshowninthediagrams,orfixedbyothersuitablemechanicalmeans.
SPFirestopSystems
construction type: cavity barriers
5
Thefixingsequenceisasfollows:
CuttheROCKWOOLSPFirestopSlaballowinganadditional3–5mmforcompressionwhenfitted.
TheROCKWOOLSP60orSP120FirestopSlabisimpaledontotheSPFixingBracketsattherateof2per1000mmlength,fixedat500mm±10mmcentres,asshowninFigureD.TheSPFixingBracketsshouldbeplaced250mm±10mminfromeachendoftheROCKWOOLSPFirestopSlab.
Theproductshouldthenbefittedsecurelyintothevoid,andtightlybuttedtotheadjacentROCKWOOLSPFirestopSlab.
OncetheROCKWOOLSPFirestopSlabhasbeenaccuratelyfitted,theSPFixingBracketsmustthenbemechanicallyfixedtotheedgeofthefloorslabwithmetalfixingssuitableformasonry.
Masonry wall cavitiesThefixingsequenceisasfollows:
CuttheROCKWOOLSPFirestopSlabtosuitthecavitysize,ensuringatightfit.
Aftersuitablyre-profilingtheSPFixingBrackets,theycanbebuiltintothebedjointsoftheinternalleafat500mm±10mmcentres.Alternatively,theSPFixingBracketsmaybere-profiledbyhandintoan‘L’shapeandmechanicallyfixedtothefaceoftheinnerleaf.
TheROCKWOOLSPFirestopSlabisthenimpaledontotheSPFixingBracketafterthenextliftofinnerleafmasonry.
Workonbothleavescanthenbecontinuedandmustincludeeitheraverticaldampproofcourseoracavitytray,installedovertheROCKWOOLSPFirestopSlabasshowninFigure5.
500m
m
Y
concrete floor slab
curtain wall
Vertical section
Plan view
Dimension Y is 75mm (SP 60) or 90mm (SP 120)
Cavitytray
ROCKWOOL®SPFixingBrackets
ROCKWOOL®SPFixingBrackets
Verticaldpc
Horizontalinstallation
Verticalinstallation
Figure 4 ROCKWOOL® SP Firestop Slab between floor and curtain wall
Figure 5 ROCKWOOL® SP Firestop Slab between masonry leaves
*Pleasenote:Forcavitywidthsof250mmormore,jointsbetweenadjacentlengthsoffirestopsshouldbesealedonthetopsurfacewithaluminiumfoiltape.
SPFirestopSystems
construction type: cavity barriers
6
Siteuse
Storage and handlingROCKWOOLSPFirestopSlabsarelightandeasytohandle.Theyaresuppliedincompressionwrappedpolyethylene,whichwillprovideshorttermprotection.Forlongtermstoragetheymustbeprotectedbyawaterproofcovering.
Estimating quantitiesThechartbelowindicatestheusageofROCKWOOL®SPFirestopSlabsandfixings,assumingaccuratesitecuttingpractices.
Typicalspecifications
Curtain WallingThecavityfirestopbetweentheedgeoftheconcretefloorslabandcurtainwallingistobeROCKWOOL®SP60orSP120FirestopSlabasmanufacturedbyROCKWOOLLimited,Pencoed,BridgendCF356NYtoprovide1houror2hourfireresistanceforbothintegrityandinsulationcriteria(LPCassessmentCC89697).FixingsareROCKWOOLSP/SorSP/LFixingBrackets,fixedinaccordancewiththedetailsgiveninthethisdatasheet.
Slabsshouldbecuttosuitthewidthoftheas-builtcavity,allowinganadditional3–5mmforcompression,andsecurelyfittedintothevoid.Alljointsaretobetightlybutted.Referto*CurtainWallingandExternalCladdingSystems,below.
Masonry wall cavityThecavitybarrierisROCKWOOLSP60orSP120FirestopSlabtoprovide1houror2hourfireresistanceforbothintegrityandinsulationcriteria(LPCassessmentCC89697).
FixingsareROCKWOOLSP/SorSP/LFixingBrackets,fixedinaccordancewiththedetailsgiveninthisdatasheet.Adampproofmembraneorcavitytrayistobeinstalledduringtheconstructionoftheouterleaf.Slabsshouldbecuttosuitthewidthoftheas-builtcavityandsecurelyfitted.Alljointsaretobetightlybutted.
*Curtain walling and external cladding systemsROCKWOOLSPFireStopSlabswillprovidefirestoppinginconjunctionwithastable,externalfaçadesystem.Duringafire,ifthebehaviourofthefacadepaneloritsfixingissuchthatagapdevelopsbetweentheROCKWOOLSPFireStopSlabandthepanelallowingfiretopassthrough,ROCKWOOLLimitedcannotacceptliabilityforfailure.Specifiersshouldensurethatthechoiceofthecurtainwallingcomponentswillnotdiminishfirestoppingrequirements.
Curtainwallingsystemsaremanufacturedfromawiderangeofmaterialswhichreactdifferentlyinfire.LargescaleindependentUKinvestigationshaveshownthatsomeglazedoraluminiumexternalcladdingsystemsareliabletointegrityfailureunderattack,withinshortperiodsoftime-5and20minutesrespectively.
Steelfacedcompositepanelsfilledwithcombustibleinsulationcanbeunstableunderfireattack.Curtainwallingsystemsincorporatingfire-sensitivepanelsmaysufferseveremovementandbuckling,resultingingapsformingbetweenthepanelandtheROCKWOOLSPFireStopSlab.
Ordering
Thereare4slabsperstandardpack.PleasequoteROCKWOOLSP60orSP120FirestopSlabandthenumberofpacksandbracketsrequired.
Cavity width(mm)
Linear metres per slab (m)
Linear metres per pack (m2)
Number of fixings required per pack
50 12 48 96
55 11 44 88
60 10 40 80
65 9 36 72
70-75 8 32 64
80-85 7 28 56
90-105 6 24 48
110-125 5 20 40
130-155 4 16 32
160-210 3 12 24
215-320 2 8 16
325-400 1 4 8
SPFirestopSystems
construction type: cavity barriers
7
Note
Thisproductdatasheetcoversbasicinstructionsforproductapplicationanddoesnotrelieveusersoftheirresponsibilityforworkinginaccordancewithgoodconstructionpractices,methodsofthermalinsulationworkandOHSregulations.ROCKWOOLguaranteesandshallbeliablefortheproductquality.However,itcannotcontrolthemethodsorconditionsinwhichtheproductisused.Alltechnicaldatawasmeasuredinaverageconditionsi.e.airtemperature:+20°C,airhumidity:60%.
Incaseofotherconditionsthedryingtimemayvary.
Caution
Irritant.Containscement.Contactwithwaterproducesalcaicreaction.Protectskin,eyesandrespiratorytract.Donotinhale.Keepoutofreachofchildren.Incaseofcontactwitheyes,immediatelyrinsewithplentyofwaterandseekmedicalattention.
HealthandSafety
InaccordancewithREACHhealthandenvironmentregulations,therearenohazardousclassificationsassociatedwithROCKWOOLstonewoolinrespecttophysical,healthandenvironmentalconsiderations.
Moreinformation
ROCKWOOLLimitedreservestherighttoalteroramendthespecificationofproductswithoutnoticeasourpolicyisoneofconstantimprovement.Theinformationcontainedinthisdatasheetisbelievedtobecorrectatthedateofpublication.
Interested?
ForfurtherinformationonanyoftheROCKWOOLsystemsinthisbrochure,contactoursupportteam.
Email:[email protected]:01656868445
Visitwww.rockwool.co.uktoviewourcompleterangeofproductsandservices.
CopyrightROCKWOOLAugust2016
ROCKWOOLLimitedreservestherighttoalteroramendthespecificationofproductswithoutnoticeasourpolicyisoneofconstantimprovement.Theinformationcontainedinthisdatasheetisbelievedtobecorrectatthedateofpublication.WhilstROCKWOOLwillendeavourtokeepitspublicationsuptodate,readerswillappreciatethatbetweenpublicationstheremaybepertinentchangesinthelaw,orotherdevelopmentsaffectingtheaccuracyoftheinformationcontainedinthisdatasheet.TheaboveapplicationsdonotnecessarilyrepresentanexhaustivelistofapplicationsforSPFirestopSystems.ROCKWOOLLimiteddoesnotacceptresponsibilityfortheconsequencesofusingSPFirestopSystemsinapplicationsdifferentfromthosedescribedwithinthisdatasheet.Expertadviceshouldbesoughtwheresuchdifferentapplicationsarecontemplated,orwheretheextentofanylistedapplicationisindoubt.