southern regional power committee - · pdf filesouthern regional power committee ... a field...

68

Upload: vudung

Post on 06-Mar-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

Minutes of the PSAG-16 Meeting held on 18.07.2016 at Ambewadi SS Page 1

SOUTHERN REGIONAL POWER COMMITTEE

BENGALURU

Minutes of the Meeting of Protection System Analysis Group - 16 (PSAG-16) held

on 18th July, 2016 at 220/110 kV Ambewadi SS of KPTCL

Introduction

The Protection System Analysis Group (PSAG-16) meeting was held on 18th July, 2016 at

Ambewadi Substation of KPTCL. Shri. Harish K. Nayak, Executive Engineer (El), TL & SS Division,

welcomed the members and participants and briefed regarding the Grid Disturbance (GD) that

occurred at Ambewadi on 24.06.2016. The list of participants is enclosed at Annexure-I.

Ambewadi on 220 kV side has six grid-connected feeders including two inter-state lines, [viz.,

220 kV Ambewadi-Nagjhari lines – 1&2, 220 kV Ambewadi-Narendra lines – 1&2, and 220 kV

Ambewadi-Ponda-1 (Xeldem) line, Ambewadi-Ponda-2 (Ponda) line] and 2x100 MVA, 220/110

kV Transformers. On 110 kV side, it has total four feeders, out of which two are connected to

Supa generating station, another feeder connected to Haliyal SS and the other to Kawalwad SS.

It has been observed that even though the substation has been designed for double-bus with

bus-coupler switching scheme, as bus-CVT of one bus is not in healthy condition, the other bus

only is being used by keeping the bus-coupler breaker out of service. Thus, functionally

substation is on Single Bus Operation. The Single Line Diagram and Connectivity Diagram of

Ambewadi SS are enclosed at Annexure-II.

The following issues were deliberated in the meeting:

A. Analysis of the Grid Disturbance that occurred at 220kV Ambewadi SS on 24.06.2016

A.1 Pre-fault Scenario:

There was no generation at Nagjhari PH and Supa PH.

220kV Ambewadi-Ponda line 2 was idle-charged from Ambewadi end.

220kV Ambewadi-Ponda line 1 (Xeldem) was feeding radial loads.

220/110kV Ambewadi ICT-I & II were feeding radial loads (110kV Ambewadi-Kawalwad &

110kV Haliyal-Kawalwad were in open condition).

Auto-reclosure (A/R) scheme was enabled only in 220kV Ambewadi-Ponda line-2 on

23.06.2016 at Ambewadi end. .

A.2 Sequence of occurrence of faults:

A.2.1 Y-B fault in Ambewadi-Ponda line-2 at 20:23 hrs:

R

Y

B

Line tripped (in 3-ph) at 20:23 Hrs on Y-B fault due to DPR, Z1 operation (3000 A; 64 km

from Ambewadi end). From DR, fault was observed to be cleared in-time in about 60ms.

Ambewadi Ponda

Minutes of the PSAG-16 Meeting held on 18.07.2016 at Ambewadi SS Page 2

KPTCL informed that the fault occurred due to Y-ph Jumper cutting (on Ponda side) and

falling on B-phase conductor causing arc between the broken conductor edges. The said

incident was stated to have happened at Location No. 176 in Goa area.

A.2.2 B-E fault in Ambewadi-Ponda line-2 at 20:44 hrs:

R

Y

B

Subsequently, line was attempted to be test-charged at 20:44 hrs but tripped (in B-ph) on

B-E fault due to DPR, Z1 (A/R) operation. Fault was observed to be cleared in-time in

about 100 msec. KPTCL informed that the falling of Y-ph conductor on to B-ph conductor

had caused the B-E fault. It was noted that SOTF protection which was supposed to

operate and give 3-ph trip under these conditions had not operated. Due to this, A/R

operated to open the line in faulty phase (B-ph). It was also noted that SOTF had been

enabled with a comparatively high-setting of I(op) > 3A for Ponda-2 line. For all others

lines it had been kept in disabled condition.

After the dead-time of 1 sec, line tried for auto-reclosure, but remained unsuccessful due

to problem in A/R output contacts of the distance relay. It was noted that Pole

Discrepancy Relay which was supposed to operate under these circumstances remained

ineffective due to the problem B-ph auxiliary switch of the circuit breaker (CB). KPTCL

informed that this was subsequently set-right. It was later found out by the station staff

that the breaker’s close-contact of A/R of Ponda-2 got wedged/ welded during the incident.

This was also confirmed by measuring resistance (which was around 25 ohms) across those

contacts.

Now, after some time, control room personnel observed smoke in Ponda-2 distance Relay,

and immediately switched off the Main DC supply for Ponda-2 line relay panels to prevent

undue damage.

Considering the above sequence of events, and the past history of Ambewadi SS, the

possible reason for smoke and subsequent damage to Ponda-2 distance relay could be

attributed to sudden rise in earth potential of the distance relay panel due to wedging of

A/R contacts facilitated by the poor condition of the existing earth-mat (this issue was

elaborated in various reports as mentioned under Item No. B).

It may be noted that at the time of switching off of DC-supply, B-ph pole was in open

condition, and the other two phase poles (R & Y) of CB were in closed condition.

A.2.3 B-G fault in Ambewadi-Ponda line-2 at 20:57 hrs:

R

Y

B

Ambewadi Ponda

Ambewadi Ponda

Minutes of the PSAG-16 Meeting held on 18.07.2016 at Ambewadi SS Page 3

Now, in order to open the R & Y ph breaker limbs of Ponda-2, the operator had restored

the DC supply at around 20:57 hrs after removing the protection DC fuses in the panel to

avoid further damage.

Immediately, Closing-Pulse from the A/R got extended resulting in closing of B-ph pole.

However, as Close-contact of A/R was already in wedged-condition, this extension of

closing pulse could be attributed to momentary arc formation across the wedged close-

contacts of A/R.

Since DC protection fuses for the relays had already been removed, the back-up

protections at Ambewadi end could not operate during the incident; as a result the fault

was kept feeding from the other lines connected to Ambewadi from the remote ends.

The duration of fault feeding was observed to be around 5.2 sec.

A.3 Reasons for Delayed Fault Clearance:

It was noted that Ambewadi –Ponda (Xeldem) line-1 and 110 kV system were radially fed

from Ambewadi. Further, there was no generation at Supa HEP. Therefore, the only

available sources to feed the fault current were 220kV Ambewadi-Nagjhari and 220kV

Ambewadi- Narendra lines.

However, due to the low magnitude of the fault current involved (around 600 – 800 A),

the fault could not sensed by the remote end distance relays on Narendra and Nagjheri

bound lines. As such, fault was continued to be fed from all the four lines till the back-up

protection at respective ends came into action to trip the lines.

KPTCL informed that 220kV Narendra lines 1& 2 fed the fault for about 5 sec before finally

being tripped on DEF/DOC protection. The fault currents and dip in voltages were

observed to be very less . [However, it may be noted that in Narendra end DR furnished

for both the lines 1 & 2, time-scale was restricted to one second only. Also no EL was

furnished.]

As per DR & EL of Nagjhari line-1 end, the fault was observed to be fed for about 5sec.

In this regard, the Relay settings adopted for all lines connected to Ambewadi SS, and

Nagjheri – Ambewadi lines at Nagjhari PH, and Narendra-Ambewadi lines at Narendra SS

as provided by KPTCL are enclosed at Annexure-V.

B. Status Review of Renovation & Upgradation (R&U) works of Ambewadi SS

220/ 110 kV Ambewadi substation of KPTCL is an inter-regional substation located on the north-

western periphery of Karnataka. The criticality of the substation can be gauged from the fact

that not only does it form an important outlet for evacuation of power from 220 Nagjheri Ph,

but also constitutes the vital link in supplying power to the tune of (100 MW) to the state of Goa

located in the western region. Given its significance, the substation was audited by SRPC team

way back in 2012, which recommended certain actionable measures covering all protection

aspects including reviewing earthing of all equipments, for implementation. Similarly, there was

an internal-audit of the substation conducted by KPTCL in April, 2014 with regard to

strengthening of earth-mat (report enclosed at Annexure–III), which clearly spelt out the need

to go for replacement (for deteriorated conductors) / strengthening of the existing earth-mat

Minutes of the PSAG-16 Meeting held on 18.07.2016 at Ambewadi SS Page 4

immediately to avoid further failure of the equipments & interruptions of power supply to the

consumers. Then in April, 2015, a field visit of the substation was undertaken by CEA team to

ascertain the problems in the transmission lines feeding Goa from Karnataka in Southern Region,

which gave certain protection-specific recommendations to be implemented at Ambewadi SS to

improve export capacity of 220 kV Ambewadi-Ponda lines. (Compliance report of the same as

furnished by KPTCL is given at Annexure–IV). Apart from these, there were also

recommendations specific to Ambewadi SS given by the Protection Coordination Sub-Committee

(PCSC) of SRPC w.r.t. providing bus-bar protection, LBB protection, double-bus operation, and

auto-reclosure on all lines emanating from Ambewadi.

Keeping above in view, inspection of the switchyard and control room was carried out by the

PSAG team to get a first-hand view of the status of the R & U works of Ambewadi SS. The

major observations of the PSAG team were as follows:

Lush-green vegetation (grass) was observed in the entire yard.

Circuit breakers did not seem to be properly maintained and found rusted.

The faulty distance relay of Ponda-2 line was sent to manufacturer for repair, and was

replaced by a spare relay.

CVTs of Bus II had not been commissioned yet; only Bus I (Single bus) was in operation.

Bus-I CVT was being used for protection of all lines.

A/R was not provided for Narendra and Nagjheri bound lines. For Ponda-2 line, A/R,

though provided, was kept out of service after the above grid occurrence. As regards

Ponda-1 (Xeldem) line, KPTCL informed that A/R, which was already commissioned, would

be kept into service soon.

PLCC was available on all lines except Ponda and Xeldem lines. For double circuit line

inter-circuit coupling had been provided. However, only one channel had been provided

for both Protection and Speech.

Auxiliary AC supply change-over was being effected in manual mode.

For 220 V protection DC supply, only one charger was available for two battery sets and

the two battery sets were connected to the same DC load Bus. For 48 V communication

DC supply, only one battery set was available with one charger.

It was generally observed that works relating to complying with the protection audit

recommendations given by SRPC team in 2012 w.r.t. providing Bus bar and LBB

protections, GPS, DG set, Main-II line protection, Redundant DC supply, etc. are yet to

take-off.

When enquired about the same, KPTCL informed that works relating to implementing above

recommendations had been covered under the scope of Renovation & Upgradation (R&U)

works, whose contract was originally awarded to M/s Easun Reyrolle. However, as they could

not complete the works as per contractual agreement, their contract had been terminated, and

a fresh contract for the R&U works had now been awarded to M/s Alstom in December, 2015.

KPTCL also informed that the total contract for R&U works cover 23 stations of KPTCL including

Ambewadi, and M/s Alstom was conducting sub-station wise survey to finalize the purchase of

materials.

Minutes of the PSAG-16 Meeting held on 18.07.2016 at Ambewadi SS Page 5

C. Recommendations:

Reasons for SOTF non-operation during the second fault to be investigated, and if

required, its settings shall be suitably revised for correct operation.

The settings of back-up protections (O/C & E/F relays) at Narendra and Nagjheri ends on

the Ambewadi – Narendra and Ambewadi – Nagjheri lines for a typical fault on 220 kV

lines emanating from Ambewadi shall be suitably revised so that they operate with

minimum possible time allowed by their respective I-t (current-time) characteristics. For

this, the use of IDMT characteristics may be explored to be in the fitness of the things.

To go for immediate replacement (for deteriorated conductors) / strengthening of the

existing earth-mat on war-footing basis to avoid further failure of the equipments &

interruptions of power supply to the consumers as brought out in the KPTCL report dated

19.04.2014.

The R&U works covering LBB protection, Busbar protection, GPS provisision, Main-II

protection to be completed without further delay in the time-lines stipulated by Hon’ble

CERC.

Both the buses (Bus I & Bus II) to be made operational with bus-coupler in service.

Auto-reclose feature to be provided for all 220 kV feeders emanating from Ambewadi SS.

Line CVT’s to be provided in all three phases for all 220 kV lines

Two sets of battery-banks and chargers to be provided for both protection (220 V) and

communication (48 V) applications.

Redundancy in PLCC communication to be provided by providing two channels for both

protection and speech for each circuit.

All breakers and substation equipment to be properly maintained. CB replacement works

may be undertaken wherever required.

Care to be taken to maintain proper upkeep of substation by regularly undertaking cutting

of weeds, grass & unwanted vegetation growth, esp. in the switchyard area.

*****

Annexure-I

Annexure-I

Narendra-1 Narendra-2 Ponda-1 Ponda-2 Nagzhari-1 Nagzhari-2

220kV Bus-1

220kV Bus-2

NK-1 NK-2 Supa-1 Supa-2

20 MVA Tfr. -2 20 MVA Tfr. -1

F-10 F-9 F-8 F-7 F-6 F-5 F-4 F-3 F-2 F-1

11Kv Bus

coupler

Breaker

11kV Bank-1

Breaker Proposed to replace age-old 2I

+10F+1B/C 1AP3 5A CTs class-1

accuracy MCVCB by 2I +10F +2AP3

1A C.T secondary PCVCBs at out door

yard with 11kV Bus system & DPs

100MVA

220/110

kV Tfr.-1

100MVA

220/110

kV Tfr.-2

Single Line Diagram of 220kV R/S, Ambewadi Dist. Uttara Kannada

LEGEND

SYMBOL DISCRIPTION

PROPOSED

S F-6 BREAKER

ISOLATOR

CURRENT

TRANSFORMER

LIGHTNING

ARRESTER

EARTH ISOLATOR

11kV Bank-2

Breaker

110kV PT-2

Proposal for replacement of 2X55MVA, 220/110kv Power

transformer by 2X100MVA, 220/110KV is approved in the 28th

TCC meeting. Work under progress. [Replacement of 55MVATfr-2.

By 100MVA Tfr.Work completed & commissioned on 18.08.2014 &

TFR.-1 Replacement Work under progress.

Replacement of 220kV, 3Core CT’s by 5

core, 0.2 class CT’s for 220kV Line: 6 Sets

LBB relays for all 220kV panels. 220kV LT

frs.: 2 Sets LBB bus bar tripping relays for

all 220kV

Proposed for replacing age old

5 Amps system C&R panels for

220/110kV Transformers,

110/11kV Transformers &

110kV line by 1 Amp system.

Strengthening of existing 110 KV single strung bus by double

strung bus

Note: Replacement of back up

OCRs and EFR by main-2

distance relay for 220kV lines is

considered

110kV PT-1

Annexure-II

55+37 Km DC, Drake, 125 MW each

85 km, Drake 9km, Drake

400kV G/S

400kV R/S

220kV R/S

Executive Engineer(El.),TL & SS Division, Sirsi

Kodsalli Power House 3x40MW

15.8 kM

Kaiga NTPCL 4x210MVA, 220/400kV

96 km, Drake

32.4

+22.

1 km

, Moo

se

220kV R/S

SRS Hubli Bidnal R/S

Nagzhari Power House 6x150MW

Ambewdi R/S 220/110kV,2x55MVA 110/11kV,2x20MVA

Ponda S/S

30+3

7km

,DC

, D

rake

400kV R/S, Narendra (PGCIL)Narendra R/S

13.57kMXeldom S/S

Sharavatti Power House 10x103.5MW

Kadra Power House 3x50MW

Karwar R/S 1x100MVA

400kV R/S, Guttur (KPTCL)

54+14 Km DC, Drake, 125 MW each

Esale R/S 1x50MVA

400/220kV Grid connectivity of Generating Stations & Receiving Stations in TL&SS Division, Sirsi

25 k

m,

Dra

ke

30+4

2.9k

m,D

C,

Dra

ke

31.9Km DC, Drake 28.2kM DC, Drake 27.5km Drake

Annexure-II

0.9km, SC, Lynx

NK-1, 7.7+18 HA-1 HK-1

Amb-1 Supa-1 NK-1 NK-1

Amb-2 Supa-2 NK-2 NK-2 (Amb)

17.3km13.715 km, DC, This lines comes under TL&SS Division Hubli

220kV SRS Hubli

NK-2 (Hubli)33.6km, DC, Dog/Coyote NK-2

(Esale)NK-1

(Kirvatti)Kalgatagi

NK-1, 7.7+15

km, Kadankoppa

Supa Power House 220kV Ambewadi R/S Kawalwad

NK-1(Kadankoppa)

110kV Grid Connectivity of TL & SS Division, KPTCL, SirsiToGoa

Anmod 0.9km, SC, LynxSirsi

Jurisdiction 40km, DC,

Lynx One line kept Idle

GMR (PARRY) Haliyal

Ganeshgudi

LILO'd 0.3 kmKU-1

29.3km UK-1

LILO'd 0.05 kmUE-1

28.4 KmEU

EK

ES-2

10Km ES-1

10km

220kV Esale, Sirsi R/S

21.9km, SC, 54km, DC, Lynx

Kiravathi11.887 km

72.4km, DC,Dog/Coyot

UmmachagiEsale-

Kawalwad

30.6 km, NK-2(SE-

2)Kumta-1

HonHon Murd Kumta Kumta-2

Jog-2 Jog-1

4.5km

KumtaLILO'd 0.9km 0.05km

Murdeshwar HonnavarChandragutti

51.25+ 2 km, DC,

Lynx

38.85km Siddapur to Sirsi31.87km, SC, Lynx Siddapur

Ankola12.399 + 2 km, DC, Lynx

, ,Lynx

, , yNK-1 (SE-1)

Kumta Sirsi

,SC, Lynx

Arga

AnkolaLILO'd 0.25km

Karwar

Solaris Chemtech, Binaga

Kadra Power House

5.75 km, DC, Lynx

Karwar

Jog Power House

Arga8.384km, DC, Lynx

27.5km Drake

220kV R/S Karwar

0.05km ,Dc, Lynx

23.154 km, SC, Lynx

Asst. Executive Engineer(Ele.) Executive Engineer(Ele.)TLM Sub-Division KPTCL Sirsi

Karwar

TL & SS Division KPTCL Sirsi

Annexure-II

Annexure-III

Page 1 of 3

Annexure-III

Page 2 of 3

Annexure-III

Page 3 of 3

Annexure-IV

Page 1 of 2

Annexure-IV

Page 2 of 2

Annexure-V

Page 1 of 52

Annexure-V

Page 2 of 52

Annexure-V

Page 3 of 52

Annexure-V

Page 4 of 52

Annexure-V

Page 5 of 52

Annexure-V

Page 6 of 52

Annexure-V

Page 7 of 52

Annexure-V

Page 8 of 52

Annexure-V

Page 9 of 52

Annexure-V

Page 10 of 52

Annexure-V

Page 11 of 52

Annexure-V

Page 12 of 52

Installation:  AMBEWADI L1 D1                           Position:      UCL 4 Device:        PZ1000‐AA*22A**0/X ‐ (FB1004X) Manufacturer:  INGETEAM T&D _____________________________________________________________________________________                   Distance protection (characteristic curve I)                                     ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                              Distance protection features                           MHO features__________________________________________________________________ T1    T2   T3   T4   min  max    inc   Phase‐to‐earth faults zone 1 reach............................................ 3.26  4.15 4.15 4.15 0.01 300.00 0.01  Phase‐to‐earth faults zone 2 reach............................................ 8.52  6.20 6.20 6.20 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 reach............................................ 21.70 7.10 7.10 7.10 0.01 300.00 0.01  Phase‐to‐earth faults zone 4 reach............................................ 1.04  0.52 0.52 0.52 0.01 300.00 0.01  Phase‐to‐phase faults zone 1 reach............................................ 3.26  4.15 4.15 4.15 0.01 300.00 0.01  Phase‐to‐phase faults zone 2 reach............................................ 8.52  6.20 6.20 6.20 0.01 300.00 0.01  Phase‐to‐phase faults zone 3 reach............................................ 21.70 7.10 7.10 7.10 0.01 300.00 0.01  Phase‐to‐phase faults zone 4 reach............................................ 1.04  0.52 0.52 0.52 0.01 300.00 0.01   Quadrilateral features________________________________________________________ T1    T2    T3    T4    min  max    inc   Phase‐to‐earth faults zone 1 reactance........................................ 3.20  4.35  4.35  4.35  0.01 300.00 0.01  Phase‐to‐earth faults zone 1 resistance....................................... 22.94 19.55 19.55 19.55 0.01 300.00 0.01  Phase‐to‐earth faults zone 2 reactance........................................ 8.36  6.40  6.40  6.40  0.01 300.00 0.01  Phase‐to‐earth faults zone 2 resistance....................................... 24.76 34.08 34.08 34.08 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 reactance........................................ 21.28 18.31 18.31 18.31 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 resistance....................................... 28.96 41.22 41.22 41.22 0.01 300.00 0.01  Phase‐to‐earth faults zone 4 reactance........................................ 1.02  0.51  0.51  0.51  0.01 300.00 0.01  Phase‐to‐earth faults zone 4 resistance....................................... 2.00  2.30  2.30  2.30  0.01 300.00 0.01  Phase‐to‐phase faults zone 1 reactance........................................ 3.20  4.35  4.35  4.35  0.01 300.00 0.01  Phase‐to‐phase faults zone 1 resistance....................................... 2.44  2.58  2.58  2.58  0.01 300.00 0.01  Phase‐to‐phase faults zone 2 reactance........................................ 8.36  6.40  6.40  6.40  0.01 300.00 0.01  Phase‐to‐phase faults zone 2 resistance....................................... 3.48  4.29  4.29  4.29  0.01 300.00 0.01  Phase‐to‐phase faults zone 3 reactance........................................ 21.28 18.31 18.31 18.31 0.01 300.00 0.01  Phase‐to‐phase faults zone 3 resistance....................................... 6.08  5.35  5.35  5.35  0.01 300.00 0.01  Phase‐to‐phase faults zone 4 reactance........................................ 1.02  0.51  0.51  0.51  0.01 300.00 0.01  Phase‐to‐phase faults zone 4 resistance....................................... 2.01  0.30  0.30  0.30  0.01 300.00 0.01   Zero sequence compensation____________________________________________________ T1    T2    T3    T4    min  max   inc   Zone 1 zero sequence compensation modulus..................................... 0.70  0.70  0.70  0.70  0.00 50.00 0.01  

Annexure-V

Page 13 of 52

Zone 1 zero sequence compensation angle....................................... 277.9 1.4   1.4   1.4   0.0  359.0 0.1   Other zones zero sequence compensation modulus................................ 0.00  0.20  0.20  0.20  0.00 50.00 0.01  Other zones zero sequence compensation angle.................................. 306.3 349.0 349.0 349.0 0.0  359.0 0.1   Zone 2 constant mutual compensation modulus................................... 0.00  0.70  0.70  0.70  0.00 50.00 0.01  Zone 2 constant mutual compensation angle..................................... 288.6 1.4   1.4   1.4   0.0  359.0 0.1    Mutual compensation___________________________________________________________ T1    T2   T3    T4   min  max   inc   Zone 1 mutual compensation modulus............................................ 0.67  0.00 0.67  0.00 0.00 50.00 0.01  Zone 1 mutual compensation angle.............................................. 357.2 0.0  357.2 0.0  0.0  359.0 0.1   Other zones mutual compensation modulus....................................... 0.20  0.00 0.20  0.00 0.00 50.00 0.01  Other zones mutual compensation angle......................................... 351.3 0.0  351.3 0.0  0.0  359.0 0.1   Zone 2 constant mutual compensation modulus................................... 0.57  0.00 0.57  0.00 0.00 50.00 0.01  Zone 2 constant mutual compensation angle..................................... 357.2 0.0  357.2 0.0  0.0  359.0 0.1    Zone 5 reach__________________________________________________________________ T1    T2    T3    T4    min  max    inc   Phase‐to‐earth forward reactive (ohm)......................................... 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐earth backward reactive (ohm)........................................ 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐earth forward resistive (ohm)........................................ 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐earth backward resistive (ohm)....................................... 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐phase forward reactive (ohm)......................................... 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐phase backward reactive (ohm)........................................ 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐phase forward resistive (ohm)........................................ 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐phase backward resistive (ohm)....................................... 41.26 2.40  2.40  2.40  0.01 300.00 0.01                    Distance protection (characteristic curve II)                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                              Distance protection features                           Overreaching direction zone___________________________________________________ T1       T2       T3       T4        Zone 2 direction.............................................................. Forward  Forward  Forward  Forward   Zone 3 direction.............................................................. Forward  Forward  Forward  Forward   Zone 4 direction.............................................................. Zone OFF Zone OFF Zone OFF Zone OFF  Zone 5........................................................................ Zone OFF Zone OFF Zone OFF Zone OFF   

Annexure-V

Page 14 of 52

Trip timing___________________________________________________________________ T1   T2   T3   T4   min  max    inc   Zone 2 timing phase to earth.................................................. 0.30 0.30 0.30 0.30 0.00 100.00 0.01  Zone 2 timing phase to phase.................................................. 0.30 0.30 0.30 0.30 0.00 100.00 0.01  Zone 3 timing phase to earth.................................................. 0.52 0.52 0.52 0.52 0.00 100.00 0.01  Zone 3 timing phase to phase.................................................. 0.52 0.52 0.52 0.52 0.00 100.00 0.01  Zone 4 timing phase to earth.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 4 timing phase to phase.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 1 timing phase to earth.................................................. 0.00 0.00 0.00 0.00 0.00 100.00 0.01  Zone 1 timing phase to phase.................................................. 0.00 0.00 0.00 0.00 0.00 100.00 0.01  Zone 5 timing phase to earth.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 5 timing phase to phase.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01   Zone 1 extension______________________________________________________________ T1   T2   T3   T4   min  max  inc   Enable........................................................................ NO   NO   NO   NO    GND factor.................................................................... 1.00 1.00 1.00 1.00 0.10 3.00 0.01  Phase factor.................................................................. 1.00 1.00 1.00 1.00 0.10 3.00 0.01                            Distance protection logic trip                           V1 memory cycles______________________________________________________________ T1 T2 T3 T4 min max inc  V1 memory cycles.............................................................. 3  3  3  3  3   25  1                                    Protection schema                                                                ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                           Distance protection logic trip                          Logic trip select_____________________________________________________________ T1            T2            T3  T4             Phase‐to‐earth fault units selection type..................................... Quadrilateral Quadrilateral MHO Quadrilateral  Phase‐to‐phase fault units selection type..................................... Quadrilateral Quadrilateral MHO Quadrilateral  Single pole trip.............................................................. YES           YES           YES YES             Protective schemes____________________________________________________________ T1                    T2                    T3                    T4                    min  max   inc   Protective schemes type selection............................................. Permissive underreach Permissive underreach Permissive underreach Permissive underreach  RTP input dropout time (s).................................................... 1.00                  1.00                  1.00                  1.00                  0.00 1.00  0.01  Block additional delay (s).................................................... 0.50                  0.50                  0.50                  0.50                  0.00 1.00  0.01  Loss of guard delay (s)....................................................... 0.15                  0.15                  0.15                  0.15                  0.00 0.15  0.01  ECO enabled................................................................... YES                   YES                   YES                   YES                    

Annexure-V

Page 15 of 52

ECO time delay (s)............................................................ 6.00                  6.00                  6.00                  6.00                  0.00 10.00 0.01  Reverse zone block enabled.................................................... NO                    NO                    NO                    NO                     Reverse zone block delay (s).................................................. 3.00                  3.00                  3.00                  3.00                  0.00 10.00 0.01  Weak infeed enable............................................................ YES                   YES                   YES                   YES                    Direct trip enable............................................................ NO                    NO                    NO                    NO                                        Distance protection (other func. & superv.)                                      ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                               Distance protection features                           Single phase overcurrent supervision__________________________________________ T1   T2   T3   T4   min  max   inc   Single phase overcurrent enable............................................... NO   NO   NO   NO    Single phase overcurrent threshold (A)........................................ 0.8  0.8  0.8  0.8  0.1  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Two phase overcurrent supervision_____________________________________________ T1   T2   T3   T4   min  max   inc   Two phase overcurrent enable.................................................. NO   NO   NO   NO    Two phase overcurrent threshold (A)........................................... 0.8  0.8  0.8  0.8  0.1  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Additional functions__________________________________________________________ T1     T2     T3     T4     min  max   inc   Switch onto fault enable...................................................... YES+Z2 YES+Z2 YES+Z2 YES+Z2  Positive sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   Positive sequence threshold current (A)....................................... 1.0    1.0    1.0    1.0    0.2  30.0  0.1   Fuse failure enable........................................................... YES    YES    YES    YES     Negative sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   Negative sequence threshold current (A)....................................... 0.20   0.20   0.20   0.20   0.02 30.00 0.01  Phase discontinuity enable.................................................... YES    YES    YES    YES     Negative sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   Negative sequence threshold current (A)....................................... 0.2    0.2    0.2    0.2    0.2  30.0  0.1    Land zone mask________________________________________________________________ T1    T2    T3    T4    min  max    inc   Enable........................................................................ NO    NO    NO    NO     Positive sequence current threshold (A)....................................... 1.0   1.0   1.0   1.0   0.2  30.0   0.1   Forward load impredance....................................................... 15.00 15.00 15.00 15.00 0.01 300.00 0.01  Forward load positive angle limit............................................. 45    45    45    45    0    90     1     Forward load negative angle limit............................................. 315   315   315   315   270  359    1     Reverse load impedance........................................................ 15.00 15.00 15.00 15.00 0.01 300.00 0.01  Reverse load positive angle limit............................................. 135   135   135   135   90   180    1     Reverse load negative angle limit............................................. 225   225   225   225   180  270    1     

Annexure-V

Page 16 of 52

 Power oscillation_____________________________________________________________ T1    T2    T3    T4    min   max    inc    Enable........................................................................ YES   NO    NO    NO     Innes zone reactance.......................................................... 23.40 9.09  9.09  9.09  0.01  300.00 0.01   Innes zone resistance......................................................... 41.26 8.15  8.15  8.15  0.01  300.00 0.01   Outes zone reactance.......................................................... 29.25 10.49 10.49 10.49 0.01  300.00 0.01   Outes zone resistance......................................................... 51.58 9.41  9.41  9.41  0.01  300.00 0.01   Positive sequence current threshold (A)....................................... 0.5   0.5   0.5   0.5   0.2   30.0   0.1    Activation time............................................................... 0.030 0.030 0.030 0.030 0.008 0.100  0.001  Maximum current threshold (A)................................................. 1.6   1.6   1.6   1.6   0.2   30.0   0.1    I2/Imax ratio (%)............................................................. 30.0  30.0  30.0  30.0  10.0  50.0   0.1    Zone lock Zone 1 lock................................................................... N     N     N     N      Zone 2 lock................................................................... Y     Y     Y     Y      Zone 3 lock................................................................... Y     Y     Y     Y      Zone 4 lock................................................................... Y     Y     Y     Y      Zone 5 lock................................................................... Y     Y     Y     Y      Oscillation time (s).......................................................... 0.055 0.055 0.055 0.055 0.008 0.100  0.001   Dead line detection___________________________________________________________ T1   T2   T3   T4   min  max   inc  Enabled....................................................................... NO   NO   NO   NO    V min. threshold (V).......................................................... 10.0 10.0 10.0 10.0 10.0 165.0 0.1  I min. threshold (A).......................................................... 0.5  0.5  0.5  0.5  0.1  2.0   0.1                                Backup protection (I)                                                            ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                               Current Protection                                Phase overcurrent time unit unit 1____________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ YES   YES   YES   YES    Pickup tap (A)................................................................ 1.0   1.0   1.0   1.0   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 0.20  0.15  0.15  0.15  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ YES   YES   YES   YES     Neutral overcurrent time unit unit 1__________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ YES   YES   YES   YES    Pickup tap (A)................................................................ 0.2   0.2   0.2   0.2   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 0.25  0.25  0.25  0.25  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ YES   YES   YES   YES     

Annexure-V

Page 17 of 52

Phase overcurrent instantaneous unit 1________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Neutral overcurrent instantaneous unit 1______________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ YES  YES  YES  YES    Directional___________________________________________________________________ T1         T2         T3         T4         min max inc  Phases angle (deg)............................................................ 45         45         45         45         0   359 1    Zero sequence angle........................................................... 45         45         45         45         0   359 1    Directional lock.............................................................. YES Vpol < YES Vpol < YES Vpol < YES Vpol <  Neutral polarization.......................................................... V          V          V          V            Phase overcurrent time unit unit 2____________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 1.6  1.6  1.6  1.6  0.2  4.0   0.1   Response type................................................................. FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (s)............................................................. 5.0  5.0  5.0  5.0  0.0  100.0 0.1   Torque control................................................................ NO   NO   NO   NO     Neutral overcurrent time unit unit 2__________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 1.6  1.6  1.6  1.6  0.2  4.0   0.1   Response type................................................................. FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (s)............................................................. 5.0  5.0  5.0  5.0  0.0  100.0 0.1   Torque control................................................................ NO   NO   NO   NO     Phase overcurrent instantaneous unit 2________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Neutral overcurrent instantaneous unit 2______________________________________ T1   T2   T3   T4   min  max   inc   

Annexure-V

Page 18 of 52

Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Phase unbalance time unit_____________________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ NO    NO    NO    NO     Pickup tap (A)................................................................ 1.6   1.6   1.6   1.6   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 1.00  1.00  1.00  1.00  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ NO    NO    NO    NO      Phase unbalance instantaneous_________________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO                                   Backup protection (II)                                                           ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                              Current Protection                                Stub bus______________________________________________________________________ T1   T2   T3   T4   min  max   inc   Phase enable.................................................................. NO   NO   NO   NO    Phase trip (A)................................................................ 1.0  1.0  1.0  1.0  0.2  30.0  0.1   Phase additional timing (sec)................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Zero sequence enable.......................................................... NO   NO   NO   NO    Zero sequence trip (A)........................................................ 1.0  1.0  1.0  1.0  0.2  30.0  0.1   Zero sequence additional timing (sec)......................................... 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Breaker failure_______________________________________________________________ T1   T2   T3   T4   min  max   inc   Enable breaker failure........................................................ YES  YES  YES  YES   Restore breaker failure phase unit (A)........................................ 0.5  0.5  0.5  0.5  0.1  30.0  0.1   Breaker failure definite time (s)............................................. 0.20 0.20 0.20 0.20 0.05 10.00 0.01   Thermal image_________________________________________________________________ T1  T2  T3  T4  min max inc  Enable........................................................................ NO  NO  NO  NO   Heating constant.............................................................. 3   3   3   3   3   60  1    Cooling constant.............................................................. 10  10  10  10  3   60  1    Alarm threshold (%)........................................................... 60  60  60  60  60  100 1    Current (A)................................................................... 1.0 1.0 1.0 1.0 0.2 2.0 0.1  

Annexure-V

Page 19 of 52

                                Voltage Protection                                 Phases overvoltage____________________________________________________________ T1   T2   T3   T4   min  max   inc   Instantaneous enable.......................................................... NO   NO   NO   NO    Instantaneous pickup tap (V).................................................. 80.0 80.0 80.0 80.0 50.0 165.0 0.1   Instantaneous definite time (sec)............................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Phases undervoltage___________________________________________________________ T1   T2   T3   T4   min  max   inc   Instantaneous enable.......................................................... NO   NO   NO   NO    Instantaneous pickup tap (V).................................................. 50.0 50.0 50.0 50.0 10.0 150.0 0.1   Instantaneous definite time (sec)............................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Overvoltage V0 (time delay)___________________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup (V).................................................................... 80.0 80.0 80.0 80.0 1.0  150.0 0.1   Curve type.................................................................... FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (sec)........................................................... 5.0  5.0  5.0  5.0  0.0  100.0 0.1    Overvoltage V0 (instantaneous)________________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ NO    NO    NO    NO     Pickup (V).................................................................... 100.0 100.0 100.0 100.0 1.0  150.0 0.1   Definite time (sec)........................................................... 0.00  0.00  0.00  0.00  0.00 10.00 0.01                                    Fault Locator                                                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐                                                                     Fault locator                                   Fault locator_________________________________________________________________ T1    T2    T3    T4    min  max     inc   Enabled....................................................................... YES   YES   YES   YES    Zero‐sequence impedance modulus (Ohms)........................................ 12.67 16.22 16.22 16.22 0.01 300.00  0.01  Zero‐sequence impedance angle (Degrees)....................................... 80.01 79.58 79.58 79.58 0.00 359.99  0.01  Forward impedance modulus (Ohms).............................................. 4.08  5.22  5.22  5.22  0.01 300.00  0.01  Forward impedance angle (Degrees)............................................. 78.63 68.83 68.83 68.83 0.00 359.99  0.01  Line length (Kms)............................................................. 25.0  32.0  32.0  32.0  0.1  5000.0  0.1   Positive sequence of line admittance.......................................... 0.0   0.0   0.0   0.0   0.0  50000.0 0.1   Zero‐sequence of line admittance.............................................. 0.0   0.0   0.0   0.0   0.0  50000.0 0.1    

Annexure-V

Page 20 of 52

Other power grid data_________________________________________________________ T1       T2       T3       T4       min  max      inc   Local source forward impedance modulus (Ohms)................................. 5.04     2.03     2.03     2.03     0.01 50000.00 0.01  Local source forward impedance angle (Degrees)................................ 78.00    78.00    78.00    78.00    0.00 359.99   0.01  Remote source forward impedance modulus (Ohms)................................ 8.00     2.51     2.51     2.51     0.01 50000.00 0.01  Remote source forward impedance angle (Degrees)............................... 76.00    76.00    76.00    76.00    0.00 359.99   0.01  Line shunt forward impedance modulus (Ohms)................................... 50000.00 50000.00 50000.00 50000.00 0.01 50000.00 0.01  Line shunt forward impedance angle (Degrees).................................. 90.00    90.00    90.00    90.00    0.00 359.99   0.01   Sensitivities_________________________________________________________________ T1  T2  T3  T4  min max   inc  Phase current sensitivity..................................................... 0.1 0.1 0.1 0.1 0.0 30.0  0.1  Neutral current sensitivity................................................... 0.1 0.1 0.1 0.1 0.0 30.0  0.1  Phase voltage sensitivity..................................................... 0.2 0.2 0.2 0.2 0.0 165.0 0.1   Analogic output_______________________________________________________________ T1 T2 T3 T4 min max  inc  Analogic output steady delay.................................................. 0  0  0  0  0   7201 1     Parallel line_________________________________________________________________ T1     T2     T3     T4     min  max    inc   Line type..................................................................... Double Single Double Single  Mutual impedance modulus (ohm)................................................ 8.72   0.10   11.17  0.01   0.01 300.00 0.01  Mutual impedance angle (deg).................................................. 75.85  0.00   75.85  0.00   0.00 359.99 0.01                                     Synchrocheck                                                                     ‐‐‐‐‐‐‐‐‐‐‐‐                                                                Synchrocheck protection                              Synchrocheck__________________________________________________________________ T1   T2   T3   T4   min  max  inc   Voltage difference between A and B sides unit pickup.......................... 2    2    2    2    2    90   1     Angle difference between A and B sides unit pickup............................ 5    5    5    5    5    50   1     Frequency difference between A and B sides unit pickup........................ 1.00 1.00 1.00 1.00 0.05 2.00 0.01  Undervoltage unit pickup for permission on A side............................. 50   50   50   50   20   165  1     Undervoltage unit pickup for permission on B side............................. 50   50   50   50   20   165  1     Close permission checking time................................................ 5    5    5    5    0    100  1                                 Synchronism authorisations                             

Annexure-V

Page 21 of 52

Synchronism authorisations____________________________________________________ T1    T2    T3    T4    min max  inc  Enable synchrocheck function.................................................. NO    NO    NO    NO     Undervoltage conditions....................................................... NEVER NEVER NEVER NEVER  Enable difference of voltages................................................. NO    NO    NO    NO     Enable difference of frequencies.............................................. NO    NO    NO    NO     Enable difference of phases................................................... NO    NO    NO    NO     Number of cycles close breaker................................................ 0.0   0.0   0.0   0.0   0.0 60.0 0.1                                 Breaker Supervision                                                              ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                               Breaker Supervision                                Breaker Supervision___________________________________________________________ T1    T2    T3    T4    min max   inc  Excessive number of trips..................................................... 200   200   200   200   1   254   1    Time span for counting the excessive number of trips.......................... 300   300   300   300   300 3600  1    Cumulative kI2 alarm for maintenance.......................................... 65000 65000 65000 65000 0   65535 1    Cumulative kI2 start value (setting).......................................... 1000  1000  1000  1000  0   65535 1    Enable trip circuit supervision............................................... NO    NO    NO    NO     Enable closing circuit supervision............................................ NO    NO    NO    NO                                  Breaker operation logic                                                          ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                            Operation logic scheme                              Breaker_______________________________________________________________________ T1   T2   T3   T4   min  max  inc   Trip locking.................................................................. NO   NO   NO   NO    Open failure timing........................................................... 3.00 3.00 3.00 3.00 0.10 5.00 0.01  Closing failure timing........................................................ 3.00 3.00 3.00 3.00 0.10 5.00 0.01                                Breaker failure protection                             Pole discordance______________________________________________________________ T1   T2   T3   T4   min  max    inc   Enable........................................................................ NO   NO   NO   NO    Discordance time (s).......................................................... 3.00 3.00 3.00 3.00 0.03 300.00 0.01                                     Recloser (4)                                                                     ‐‐‐‐‐‐‐‐‐‐‐‐                                                             Distance protection logic trip                          Single/Three pole recloser____________________________________________________ T1         T2              T3              T4              min max   inc  Recloser on‐line.............................................................. NO         NO              NO              NO               

Annexure-V

Page 22 of 52

Reclose type selection........................................................ Three pole Sing/Three pole Sing/Three pole Sing/Three pole  Number of programmed shots.................................................... 1          1               1               1               1   4     1    1st shot time for single pole reclose......................................... 3.0        1.0             1.0             1.0             0.1 20.0  0.1  1st shot time for three pole reclose.......................................... 3.0        1.5             1.5             1.5             0.1 20.0  0.1  2nd shot time reclose......................................................... 5.0        5.0             5.0             5.0             1.0 300.0 0.1  3rd shot time reclose......................................................... 7.0        7.0             7.0             7.0             1.0 300.0 0.1  4th shot time reclose......................................................... 20.0       20.0            20.0            20.0            1.0 300.0 0.1  Security time after single pole closing....................................... 6.0        6.0             6.0             6.0             1.0 300.0 0.1  Security time after three pole closing........................................ 4.0        4.0             4.0             4.0             1.0 300.0 0.1  Reclaim time after manual closing............................................. 10.0       10.0            10.0            10.0            1.0 300.0 0.1  Synchronism time delay........................................................ 10.0       10.0            10.0            10.0            1.0 300.0 0.1  Enabled reclose units Zone 1 trip................................................................... Y          Y               Y               Y                Zone 2 trip................................................................... N          Y               Y               Y                Zone 3 trip................................................................... N          Y               Y               Y                Zone 4 trip................................................................... N          N               N               N                Instantaneous negative sequence overcurrent trip.............................. N          N               N               N                Time delay negative sequence overcurrent trip................................. N          N               N               N                Instantaneous zero sequence overcurrent trip.................................. N          Y               Y               Y                Time delay zero sequence overcurrent trip..................................... N          Y               Y               Y                Locks after single pole trip Neutral instantaneous......................................................... N          N               N               N                Neutral time delay............................................................ N          N               N               N                Unbalance instantaneous....................................................... N          N               N               N                Unbalance time delay.......................................................... N          N               N               N                                  General settings and remote port configuration                                   ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                       General                                      Operation_____________________________________________________________________ T0   Device on‐line................................................................ YES   Configuration_________________________________________________________________ T0     Number of breaker (position).................................................. NA1     

Annexure-V

Page 23 of 52

Current transformers turn ratio_______________________________________________ T0  min max  inc  Phase current turn ratio...................................................... 800 1   3000 1    Neutral current turn ratio.................................................... 800 1   3000 1     Voltage turn ratio____________________________________________________________ T0   min max  inc  Voltage transformers turn ratio............................................... 2000 1   9999 1         Measurements correcting factors and outputs activation timings of outputs      Correcting factors____________________________________________________________ T0    min   max   inc    Active energy counter constant................................................ 1     1     9999  1      Reactive energy counter constant.............................................. 1     1     9999  1      Power constant................................................................ 1.000 0.010 2.000 0.001                                   General settings                                  Phase‐to‐neutral rated voltage (secondary winding)____________________________ T0   min  max   inc  Phase‐to‐neutral rated voltage (secondary winding) (V)........................ 63.5 50.0 165.0 0.1                       Digital and logical inputs configuration                                         ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                       Configuration                                   Digital Inputs________________________________________________________________ T0  Digital inputs layout ED 1............................................ CB 52a Status ED 2............................................ Phase 1 CB 52a Status ED 3............................................ Phase 2 CB 52a Status ED 4............................................ Phase 3 CB 52a Status ED 5............................................ Close Command ED 6............................................ Recloser Block ED 7............................................ Leds Reposition ED 8............................................ Force 3 Phase Trip ED 9............................................ External Protection ED 10........................................... Not Assigned Input ED 11........................................... Not Assigned Input ED 12........................................... Not Assigned Input ED 13........................................... Guard Signal Lost: RPSG ED 14........................................... Teleprotection Received RTPE ED 15........................................... Not Assigned Input ED 16........................................... External Protection                                 Signals Programing                                                               ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                

Annexure-V

Page 24 of 52

                            Programable Logic Signals                             Programable Logic Signals_____________________________________________________ T0     1 ‐ Logic 1                              Delay: 0.0 sec        Pulse width: By logic OR     OR         1‐     Phase Overcurrent Trip       [45]         2‐     Earth Overcurrent Trip       [47]     AND   2 ‐ Logic 2                              Delay: 0.0 sec        Pulse width: 0.2 sec AND     OR         1‐     Start Zone 2 Ph 1‐Earth      [8]         2‐     Start Zone 2 Ph 2‐Earth      [9]         3‐     Start Zone 2 Phe 3‐Earth     [10]         4‐     Start Zone 2 Ph 1‐2          [11]         5‐     Start Zone 2 Ph 2‐3          [12]         6‐     Start Zone 2 Ph 3‐1          [13]         7‐     Start Zone 2 Triphasic       [14]     AND         1‐     Digital Input 14             [93]   3 ‐ Logic 3                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐     Phase 1 Open Failure         [58]         2‐     Phase 2 Open Failure         [66]         3‐     Phase 3 Open Failure         [74]         4‐     Switch Onto Fault            [37]         5‐     Power Swing Trip             [36]         6‐     Digital Input 16             [95]         7‐     Logic 1                      [120]         8‐     Logic 5                      [124]     AND         1‐     Digital Input 9              [88]   4 ‐ Logic 4                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐ NOT Digital Input 10             [89]         2‐ NOT Digital Input 11             [90] 

Annexure-V

Page 25 of 52

        3‐ NOT Digital Input 12             [91]     AND   5 ‐ Logic 5                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐     Zone 1 Trip                  [7]         2‐     Zone 2 Trip                  [15]         3‐     Zone 3 Trip                  [23]         4‐     Zone 4 Trip                  [31]     AND   6 ‐ Logic 6                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐     Output Contact 21            [116]     AND                            Digital outputs configuration                                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Configuration                                   Digital outputs_______________________________________________________________ T0  Digital outputs layout SD 1............................................ Breaker Closing (reclose) SD 2............................................ Phase 1 Fault SD 3............................................ Phase 2 Fault SD 4............................................ Phase 3 Fault SD 5............................................ Not Assigned Output SD 6............................................ Teleprotection ETP Signal SD 7............................................ Triphasic fault SD 8............................................ Logic Signal 3 SD 9............................................ Breaker Failure Trip SD 10........................................... Close Permission SD 11........................................... Recloser Blocked SD 12........................................... Logic Signal 4 SD 13........................................... Logic Signal 5 SD 14........................................... Logic Signal 1 SD 15........................................... Recloser Ongoing Cycle SD 16........................................... Open Phase Alarm SD 17........................................... Switch On Fault SD 18........................................... Fuse Failure SD 19........................................... Power Swing SD 20........................................... Logic Signal 1 SD 21........................................... QUAD Trip 

Annexure-V

Page 26 of 52

SD 22........................................... Not Assigned Output SD 23........................................... Logic Signal 6 SD 24........................................... Logic Signal 2                                 Leds configuration                                                               ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                                  Configuration                                   LEDs__________________________________________________________________________ T0  LEDs layout LED 1........................................... Phase 1 Fault LED 2........................................... Phase 2 Fault LED 3........................................... Phase 3 Fault LED 4........................................... Triphasic Fault LED 5........................................... Zone 1 Trip LED 6........................................... Zone 2 Trip LED 7........................................... Zone 3 Trip LED 8........................................... Zone 4 Trip LED 9........................................... Phase Overcurrent Trip LED 10.......................................... Earth Overcurrent Trip LED 11.......................................... Open Phase Alarm LED 12.......................................... Fuse Failure                                Chronological reports                                                            ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Chronological reports                               Measurements chronological reports____________________________________________ T1    T2    T3    T4     Time span for calculating the mean of samples................................. 1     1     1     1      Chronological report recording time interval.................................. 00:30 01:00 01:00 01:00  Weekdays mask Monday........................................................................ YES   YES   YES   YES    Tuesday....................................................................... YES   YES   YES   YES    Wednesday..................................................................... YES   YES   YES   YES    Thursday...................................................................... YES   YES   YES   YES    Friday........................................................................ YES   YES   YES   YES    Saturday...................................................................... YES   YES   YES   YES    Sunday........................................................................ YES   YES   YES   YES    Calendar mask................................................................. YES   YES   YES   YES    Daily record start time....................................................... 0     0     0     0      Daily record end time......................................................... 23    23    23    23                             Oscillograph record configuration                                                ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                 Oscillograph record configuration                         

Annexure-V

Page 27 of 52

Oscillograph record configuration_____________________________________________ T0      min max inc  Digital signals recorded in each channel Channel Nº 0.................................... Phase 3 Trip Channel Nº 1.................................... Zone 1 Ph 2‐Earth Start Channel Nº 2.................................... Zone 1 Ph 3‐Earth Start Channel Nº 3.................................... Zone 1 Ph 1‐2 Start Channel Nº 4.................................... Zone 1 Ph 2‐3 Start Channel Nº 5.................................... Zone 1 Ph 3‐1 Start Channel Nº 6.................................... Phase 1 Trip Channel Nº 7.................................... Phase 2 Trip Channel Nº 8.................................... Phase 3 Trip Channel Nº 9.................................... Fuse Failure Channel Nº 10................................... Zone 2 Start Channel Nº 11................................... Zone 2 Activation Channel Nº 12................................... Zone 3 Start Channel Nº 13................................... Zone 3 Activation Channel Nº 14................................... Zone 4 Start Channel Nº 15................................... Zone 4 Activation Pickup causing digital signals Digital Input 1................................. Yes Digital Input 2................................. No Digital Input 3................................. No Digital Input 4................................. No Digital Input 5................................. Yes Digital Input 6................................. Yes Digital Input 7................................. No Digital Input 8................................. Yes Digital Input 9................................. Yes Digital Input 10................................ No Digital Input 11................................ No Digital Input 12................................ No Digital Input 13................................ Yes Digital Input 14................................ Yes Digital Input 15................................ No Digital Input 16................................ Yes Three Phase Trip................................ Yes Phase 1 Trip.................................... Yes Phase 2 Trip.................................... Yes Phase 3 Trip.................................... Yes I1 Instantaneous Trip........................... Yes I2 Instantaneous Trip........................... Yes I3 Instantaneous Trip........................... No I Earth Instantaneous Trip...................... No I1 Time Delay Trip.............................. No I2 Time Delay Trip.............................. No I3 Time Delay Trip.............................. No I Earth Time Delay Trip......................... No 

Annexure-V

Page 28 of 52

V1 Overvoltage Trip............................. No V2 Overvoltage Trip............................. No V3 Overvoltage Trip............................. No V1 Undervoltage Trip............................ No V2 Undervoltage Trip............................ No V3 Undervoltage Trip............................ No I1 Instantaneous Start.......................... No I2 Instantaneous Start.......................... No I3 Instantaneous Start.......................... No I Earth Instantaneous Start..................... No I1 Time Delay Start............................. No I2 Time Delay Start............................. No I3 Time Delay Start............................. No I Earth Time Delay Start........................ No V1 Overvoltage Start............................ No V2 Overvoltage Start............................ No V3 Overvoltage Start............................ No V1 Undervoltage Start........................... No V2 Undervoltage Start........................... No V3 Undervoltage Start........................... No Zone 1 Ph 1‐Earth Start......................... No Zone 1 Ph 2‐Earth Start......................... No Zone 1 Ph 3‐Earth Start......................... No Zone 1 Ph 1‐2 Start............................. No Zone 1 Ph 2‐3 Start............................. No Zone 1 Ph 3‐1 Start............................. No Zone 2 Ph 1‐Earth Start......................... No Zone 2 Ph 2‐Earth Start......................... No Zone 2 Ph 3‐Earth Start......................... No Zone 2 Ph 1‐2 Start............................. No Zone 2 Ph 2‐3 Start............................. No Zone 2 Ph 3‐1 Start............................. No Zone 3 Ph 1‐Earth Start......................... No Zone 3 Ph 2‐Earth Start......................... No Zone 3 Ph 3‐Earth Start......................... No Zone 3 Ph 1‐2 Start............................. No Zone 3 Ph 2‐3 Start............................. No Zone 3 Ph 3‐1 Start............................. No Zone 4 Ph 1‐Earth Start......................... No Zone 4 Ph 2‐Earth Start......................... No Zone 4 Ph 3‐Earth Start......................... No Zone 4 Ph 1‐2 Start............................. No Zone 4 Ph 2‐3 Start............................. No Zone 4 Ph 3‐1 Start............................. No Zone 2 Ph 1‐Earth Activation.................... No Zone 2 Ph 2‐Earth Activation.................... No Zone 2 Ph 3‐Earth Activation.................... No Zone 2 Ph 1‐2 Activation........................ No 

Annexure-V

Page 29 of 52

Zone 2 Ph 2‐3 Activation........................ No Zone 2 Ph 3‐1 Activation........................ No Zone 3 Ph 1‐Earth Activation.................... No Zone 3 Ph 2‐Earth Activation.................... No Zone 3 Ph 3‐Earth Activation.................... No Zone 3 Ph 1‐2 Activation........................ No Zone 3 Ph 2‐3 Activation........................ No Zone 3 Ph 3‐1 Activation........................ No Directional..................................... No Fuse Failure.................................... Yes Load Encroachment............................... No Power Swing..................................... Yes Switch On Fault................................. Yes Open Phase Alarm................................ Yes Phase Instantaneous Start....................... No Phase Time delay Start.......................... No Overvoltage Trip................................ No Undervoltage Trip............................... No Phase Instantaneous Trip........................ No Phase Time delay Trip........................... No Overvoltage Start............................... No Undervoltage Start.............................. No Zone 1 Start.................................... No Zone 2 Start.................................... Yes Zone 3 Start.................................... Yes Zone 4 Start.................................... Yes Zone 2 Activation............................... Yes Zone 3 Activation............................... Yes Zone 4 Activation............................... Yes Power Swing Trip................................ No Logic Signal 1.................................. No Logic Signal 2.................................. No Logic Signal 3.................................. No Logic Signal 4.................................. No Logic Signal 5.................................. No Logic Signal 6.................................. No I Unbalance Time Delay Start.................... Yes I Unbalance Instantaneous St.................... No Thermal Start................................... Yes V0 Time Delay Start............................. Yes V0 Instantaneous Start.......................... No I Unbalance Time Delay Trip..................... No I Unbalance Instantaneous Tr.................... Yes Thermal Trip.................................... Yes V0 Time Delay Trip.............................. No V0 Instantaneous Trip........................... No Phase 1 Dead Line............................... No Phase 2 Dead Line............................... No 

Annexure-V

Page 30 of 52

Phase 3 Dead Line............................... No Phase 1 52BF.................................... No Phase 2 52BF.................................... No Phase 3 52BF.................................... No Zone 5 Ph 1‐Earth Start......................... Yes Zone 5 Ph 2‐Earth Start......................... No Zone 5 Ph 3‐Earth Start......................... No Zone 5 Ph 1‐2 Start............................. No Zone 5 Ph 2‐3 Start............................. No Zone 5 Ph 3‐1 Start............................. No Zone 5 Ph 1‐Earth Activation.................... No Zone 5 Ph 2‐Earth Activation.................... No Zone 5 Ph 3‐Earth Activation.................... No Zone 5 Ph 1‐2 Activation........................ No Zone 5 Ph 2‐3 Activation........................ No Zone 5 Ph 3‐1 Activation........................ No Zone 5 Start.................................... No Zone 5 Activation............................... No CT supervision.................................. Yes Samples per message........................................................... Maximum  Total number of oscillograph stored cycles.................................... 30       Number of stored pre‐fault cycles............................................. 4       1   60  1                                Control Measures Selection                                                       ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Control Measures                                 Control Measures Selection____________________________________________________ T0  Control Measures Selection MEASURE 1....................................... V Phase 1 MEASURE 2....................................... V Phase 2 MEASURE 3....................................... V Phase 3 MEASURE 4....................................... Average V MEASURE 5....................................... V Phase 1‐2 MEASURE 6....................................... V Phase 2‐3 MEASURE 7....................................... V Phase 3‐1 MEASURE 8....................................... Average V Phase‐Phase MEASURE 9....................................... I Phase 1 MEASURE 10...................................... I Phase 2 MEASURE 11...................................... I Phase 3 MEASURE 12...................................... Average I MEASURE 13...................................... Maximum I MEASURE 14...................................... Real Power P MEASURE 15...................................... Reactive Power Q MEASURE 16...................................... Frequency MEASURE 17...................................... Power Factor Phase 1 MEASURE 18...................................... Power Factor Phase 2 MEASURE 19...................................... Power Factor Phase 3 

Annexure-V

Page 31 of 52

MEASURE 20...................................... Average Power Factor MEASURE 21...................................... Fault Distance (%)  ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐***‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ Installation:  AMBEWADI L2 D2                           Position:      UCL 4 Device:        PZ1000‐AA*22A**0/X ‐ (FB1004X) Manufacturer:  INGETEAM T&D __________________________________________________________________________________________________________________________________                     Distance protection (characteristic curve I)                                     ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                              Distance protection features                           MHO features__________________________________________________________________ T1    T2   T3   T4   min  max    inc   Phase‐to‐earth faults zone 1 reach............................................ 3.26  4.15 4.15 4.15 0.01 300.00 0.01  Phase‐to‐earth faults zone 2 reach............................................ 8.52  6.20 6.20 6.20 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 reach............................................ 21.70 7.10 7.10 7.10 0.01 300.00 0.01  Phase‐to‐earth faults zone 4 reach............................................ 1.04  0.52 0.52 0.52 0.01 300.00 0.01  Phase‐to‐phase faults zone 1 reach............................................ 3.26  4.15 4.15 4.15 0.01 300.00 0.01  Phase‐to‐phase faults zone 2 reach............................................ 8.52  6.20 6.20 6.20 0.01 300.00 0.01  Phase‐to‐phase faults zone 3 reach............................................ 21.70 7.10 7.10 7.10 0.01 300.00 0.01  Phase‐to‐phase faults zone 4 reach............................................ 1.04  0.52 0.52 0.52 0.01 300.00 0.01   Quadrilateral features________________________________________________________ T1    T2    T3    T4    min  max    inc   Phase‐to‐earth faults zone 1 reactance........................................ 3.20  4.35  4.35  4.35  0.01 300.00 0.01  Phase‐to‐earth faults zone 1 resistance....................................... 22.94 19.55 19.55 19.55 0.01 300.00 0.01  Phase‐to‐earth faults zone 2 reactance........................................ 8.36  6.40  6.40  6.40  0.01 300.00 0.01  Phase‐to‐earth faults zone 2 resistance....................................... 24.76 34.08 34.08 34.08 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 reactance........................................ 21.28 18.31 18.31 18.31 0.01 300.00 0.01  Phase‐to‐earth faults zone 3 resistance....................................... 28.96 41.22 41.22 41.22 0.01 300.00 0.01  Phase‐to‐earth faults zone 4 reactance........................................ 1.02  0.51  0.51  0.51  0.01 300.00 0.01  Phase‐to‐earth faults zone 4 resistance....................................... 2.00  2.30  2.30  2.30  0.01 300.00 0.01  Phase‐to‐phase faults zone 1 reactance........................................ 3.20  4.35  4.35  4.35  0.01 300.00 0.01  Phase‐to‐phase faults zone 1 resistance....................................... 2.44  2.58  2.58  2.58  0.01 300.00 0.01  Phase‐to‐phase faults zone 2 reactance........................................ 8.36  6.40  6.40  6.40  0.01 300.00 0.01  Phase‐to‐phase faults zone 2 resistance....................................... 3.48  4.29  4.29  4.29  0.01 300.00 0.01  Phase‐to‐phase faults zone 3 reactance........................................ 21.28 18.31 18.31 18.31 0.01 300.00 0.01  Phase‐to‐phase faults zone 3 resistance....................................... 6.08  5.35  5.35  5.35  0.01 300.00 0.01  

Annexure-V

Page 32 of 52

Phase‐to‐phase faults zone 4 reactance........................................ 1.02  0.51  0.51  0.51  0.01 300.00 0.01  Phase‐to‐phase faults zone 4 resistance....................................... 2.01  0.30  0.30  0.30  0.01 300.00 0.01   Zero sequence compensation____________________________________________________ T1   T2    T3    T4    min  max   inc   Zone 1 zero sequence compensation modulus..................................... 0.70 0.70  0.70  0.70  0.00 50.00 0.01  Zone 1 zero sequence compensation angle....................................... 1.4  1.4   1.4   1.4   0.0  359.0 0.1   Other zones zero sequence compensation modulus................................ 0.00 0.20  0.20  0.20  0.00 50.00 0.01  Other zones zero sequence compensation angle.................................. 1.4  349.0 349.0 349.0 0.0  359.0 0.1   Zone 2 constant mutual compensation modulus................................... 0.00 0.70  0.70  0.70  0.00 50.00 0.01  Zone 2 constant mutual compensation angle..................................... 1.4  1.4   1.4   1.4   0.0  359.0 0.1    Mutual compensation___________________________________________________________ T1    T2   T3    T4   min  max   inc   Zone 1 mutual compensation modulus............................................ 0.67  0.00 0.67  0.00 0.00 50.00 0.01  Zone 1 mutual compensation angle.............................................. 357.2 0.0  357.2 0.0  0.0  359.0 0.1   Other zones mutual compensation modulus....................................... 0.20  0.00 0.20  0.00 0.00 50.00 0.01  Other zones mutual compensation angle......................................... 351.3 0.0  351.3 0.0  0.0  359.0 0.1   Zone 2 constant mutual compensation modulus................................... 0.57  0.00 0.57  0.00 0.00 50.00 0.01  Zone 2 constant mutual compensation angle..................................... 357.2 0.0  357.2 0.0  0.0  359.0 0.1    Zone 5 reach__________________________________________________________________ T1    T2    T3    T4    min  max    inc   Phase‐to‐earth forward reactive (ohm)......................................... 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐earth backward reactive (ohm)........................................ 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐earth forward resistive (ohm)........................................ 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐earth backward resistive (ohm)....................................... 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐phase forward reactive (ohm)......................................... 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐phase backward reactive (ohm)........................................ 23.40 13.75 13.75 13.75 0.01 300.00 0.01  Phase‐to‐phase forward resistive (ohm)........................................ 41.26 2.40  2.40  2.40  0.01 300.00 0.01  Phase‐to‐phase backward resistive (ohm)....................................... 41.26 2.40  2.40  2.40  0.01 300.00 0.01                      Distance protection (characteristic curve II)                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                   

Annexure-V

Page 33 of 52

                           Distance protection features                           Overreaching direction zone___________________________________________________ T1       T2       T3       T4        Zone 2 direction.............................................................. Forward  Forward  Forward  Forward   Zone 3 direction.............................................................. Forward  Forward  Forward  Forward   Zone 4 direction.............................................................. Zone OFF Zone OFF Zone OFF Zone OFF  Zone 5........................................................................ Zone OFF Zone OFF Zone OFF Zone OFF   Trip timing___________________________________________________________________ T1   T2   T3   T4   min  max    inc   Zone 2 timing phase to earth.................................................. 0.30 0.30 0.30 0.30 0.00 100.00 0.01  Zone 2 timing phase to phase.................................................. 0.30 0.30 0.30 0.30 0.00 100.00 0.01  Zone 3 timing phase to earth.................................................. 0.52 0.52 0.52 0.52 0.00 100.00 0.01  Zone 3 timing phase to phase.................................................. 0.52 0.52 0.52 0.52 0.00 100.00 0.01  Zone 4 timing phase to earth.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 4 timing phase to phase.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 1 timing phase to earth.................................................. 0.00 0.00 0.00 0.00 0.00 100.00 0.01  Zone 1 timing phase to phase.................................................. 0.00 0.00 0.00 0.00 0.00 100.00 0.01  Zone 5 timing phase to earth.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01  Zone 5 timing phase to phase.................................................. 2.00 2.00 2.00 2.00 0.00 100.00 0.01   Zone 1 extension______________________________________________________________ T1   T2   T3   T4   min  max  inc   Enable........................................................................ NO   NO   NO   NO    GND factor.................................................................... 1.00 1.00 1.00 1.00 0.10 3.00 0.01  Phase factor.................................................................. 1.00 1.00 1.00 1.00 0.10 3.00 0.01                              Distance protection logic trip                           V1 memory cycles______________________________________________________________ T1 T2 T3 T4 min max inc  V1 memory cycles.............................................................. 3  3  3  3  3   25  1                                      Protection schema                                                                ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                           Distance protection logic trip                          Logic trip select_____________________________________________________________ T1            T2            T3  T4             Phase‐to‐earth fault units selection type..................................... Quadrilateral Quadrilateral MHO Quadrilateral  Phase‐to‐phase fault units selection type..................................... Quadrilateral Quadrilateral MHO Quadrilateral  

Annexure-V

Page 34 of 52

Single pole trip.............................................................. YES           YES           YES YES             Protective schemes____________________________________________________________ T1                    T2                    T3                    T4                    min  max   inc   Protective schemes type selection............................................. Permissive underreach Permissive underreach Permissive underreach Permissive underreach  RTP input dropout time (s).................................................... 1.00                  1.00                  1.00                  1.00                  0.00 1.00  0.01  Block additional delay (s).................................................... 0.50                  0.50                  0.50                  0.50                  0.00 1.00  0.01  Loss of guard delay (s)....................................................... 0.15                  0.15                  0.15                  0.15                  0.00 0.15  0.01  ECO enabled................................................................... YES                   YES                   YES                   YES                    ECO time delay (s)............................................................ 6.00                  6.00                  6.00                  6.00                  0.00 10.00 0.01  Reverse zone block enabled.................................................... NO                    NO                    NO                    NO                     Reverse zone block delay (s).................................................. 3.00                  3.00                  3.00                  3.00                  0.00 10.00 0.01  Weak infeed enable............................................................ YES                   YES                   YES                   YES                    Direct trip enable............................................................ NO                    NO                    NO                    NO                                          Distance protection (other func. & superv.)                                      ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                               Distance protection features                           Single phase overcurrent supervision__________________________________________ T1   T2   T3   T4   min  max   inc   Single phase overcurrent enable............................................... NO   NO   NO   NO    Single phase overcurrent threshold (A)........................................ 0.8  0.8  0.8  0.8  0.1  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Two phase overcurrent supervision_____________________________________________ T1   T2   T3   T4   min  max   inc   Two phase overcurrent enable.................................................. NO   NO   NO   NO    Two phase overcurrent threshold (A)........................................... 0.8  0.8  0.8  0.8  0.1  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Additional functions__________________________________________________________ T1     T2     T3     T4     min  max   inc   Switch onto fault enable...................................................... YES+Z2 YES+Z2 YES+Z2 YES+Z2  Positive sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   Positive sequence threshold current (A)....................................... 1.0    1.0    1.0    1.0    0.2  30.0  0.1   Fuse failure enable........................................................... YES    YES    YES    YES     Negative sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   

Annexure-V

Page 35 of 52

Negative sequence threshold current (A)....................................... 0.20   0.20   0.20   0.20   0.02 30.00 0.01  Phase discontinuity enable.................................................... YES    YES    YES    YES     Negative sequence threshold voltage (V)....................................... 10.0   10.0   10.0   10.0   10.0 165.0 0.1   Negative sequence threshold current (A)....................................... 0.2    0.2    0.2    0.2    0.2  30.0  0.1    Land zone mask________________________________________________________________ T1    T2    T3    T4    min  max    inc   Enable........................................................................ NO    NO    NO    NO     Positive sequence current threshold (A)....................................... 1.0   1.0   1.0   1.0   0.2  30.0   0.1   Forward load impredance....................................................... 15.00 15.00 15.00 15.00 0.01 300.00 0.01  Forward load positive angle limit............................................. 45    45    45    45    0    90     1     Forward load negative angle limit............................................. 315   315   315   315   270  359    1     Reverse load impedance........................................................ 15.00 15.00 15.00 15.00 0.01 300.00 0.01  Reverse load positive angle limit............................................. 135   135   135   135   90   180    1     Reverse load negative angle limit............................................. 225   225   225   225   180  270    1      Power oscillation_____________________________________________________________ T1    T2    T3    T4    min   max    inc    Enable........................................................................ NO    NO    NO    NO     Innes zone reactance.......................................................... 23.40 9.09  9.09  9.09  0.01  300.00 0.01   Innes zone resistance......................................................... 41.26 8.15  8.15  8.15  0.01  300.00 0.01   Outes zone reactance.......................................................... 29.25 10.49 10.49 10.49 0.01  300.00 0.01   Outes zone resistance......................................................... 51.58 9.41  9.41  9.41  0.01  300.00 0.01   Positive sequence current threshold (A)....................................... 0.5   0.5   0.5   0.5   0.2   30.0   0.1    Activation time............................................................... 0.030 0.030 0.030 0.030 0.008 0.100  0.001  Maximum current threshold (A)................................................. 1.6   1.6   1.6   1.6   0.2   30.0   0.1    I2/Imax ratio (%)............................................................. 30.0  30.0  30.0  30.0  10.0  50.0   0.1    Zone lock Zone 1 lock................................................................... N     N     N     N      Zone 2 lock................................................................... Y     Y     Y     Y      Zone 3 lock................................................................... Y     Y     Y     Y      Zone 4 lock................................................................... Y     Y     Y     Y      Zone 5 lock................................................................... Y     Y     Y     Y      Oscillation time (s).......................................................... 0.055 0.055 0.055 0.055 0.008 0.100  0.001   Dead line detection___________________________________________________________ T1   T2   T3   T4   min  max   inc  Enabled....................................................................... NO   NO   NO   NO    V min. threshold (V).......................................................... 10.0 10.0 10.0 10.0 10.0 165.0 0.1  I min. threshold (A).......................................................... 0.5  0.5  0.5  0.5  0.1  2.0   0.1                                  Backup protection (I)                                                            ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                               Current Protection                                

Annexure-V

Page 36 of 52

Phase overcurrent time unit unit 1____________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ YES   YES   YES   YES    Pickup tap (A)................................................................ 1.0   1.0   1.0   1.0   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 0.20  0.15  0.15  0.15  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ YES   YES   YES   YES     Neutral overcurrent time unit unit 1__________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ YES   YES   YES   YES    Pickup tap (A)................................................................ 0.2   0.2   0.2   0.2   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 0.25  0.25  0.25  0.25  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ YES   YES   YES   YES     Phase overcurrent instantaneous unit 1________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Neutral overcurrent instantaneous unit 1______________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ YES  YES  YES  YES    Directional___________________________________________________________________ T1         T2         T3         T4         min max inc  Phases angle (deg)............................................................ 45         45         45         45         0   359 1    Zero sequence angle........................................................... 45         45         45         45         0   359 1    Directional lock.............................................................. YES Vpol < YES Vpol < YES Vpol < YES Vpol <  Neutral polarization.......................................................... V          V          V          V            Phase overcurrent time unit unit 2____________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 1.6  1.6  1.6  1.6  0.2  4.0   0.1   Response type................................................................. FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (s)............................................................. 5.0  5.0  5.0  5.0  0.0  100.0 0.1   Torque control................................................................ NO   NO   NO   NO     

Annexure-V

Page 37 of 52

Neutral overcurrent time unit unit 2__________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 1.6  1.6  1.6  1.6  0.2  4.0   0.1   Response type................................................................. FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (s)............................................................. 5.0  5.0  5.0  5.0  0.0  100.0 0.1   Torque control................................................................ NO   NO   NO   NO     Phase overcurrent instantaneous unit 2________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Neutral overcurrent instantaneous unit 2______________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO     Phase unbalance time unit_____________________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ NO    NO    NO    NO     Pickup tap (A)................................................................ 1.6   1.6   1.6   1.6   0.2  4.0   0.1   Response type................................................................. I BSC I BSC I BSC I BSC  Time dial..................................................................... 1.00  1.00  1.00  1.00  0.05 30.00 0.01  Definite time (s)............................................................. 5.0   5.0   5.0   5.0   0.0  100.0 0.1   Torque control................................................................ NO    NO    NO    NO      Phase unbalance instantaneous_________________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup tap (A)................................................................ 2.0  2.0  2.0  2.0  0.2  30.0  0.1   Definite time (s)............................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Torque control................................................................ NO   NO   NO   NO                                    Backup protection (II)                                                           ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                              Current Protection                                Stub bus______________________________________________________________________ T1   T2   T3   T4   min  max   inc   Phase enable.................................................................. NO   NO   NO   NO    

Annexure-V

Page 38 of 52

Phase trip (A)................................................................ 1.0  1.0  1.0  1.0  0.2  30.0  0.1   Phase additional timing (sec)................................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01  Zero sequence enable.......................................................... NO   NO   NO   NO    Zero sequence trip (A)........................................................ 1.0  1.0  1.0  1.0  0.2  30.0  0.1   Zero sequence additional timing (sec)......................................... 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Breaker failure_______________________________________________________________ T1   T2   T3   T4   min  max   inc   Enable breaker failure........................................................ YES  YES  YES  YES   Restore breaker failure phase unit (A)........................................ 0.5  0.5  0.5  0.5  0.1  30.0  0.1   Breaker failure definite time (s)............................................. 0.20 0.20 0.20 0.20 0.05 10.00 0.01   Thermal image_________________________________________________________________ T1  T2  T3  T4  min max inc  Enable........................................................................ NO  NO  NO  NO   Heating constant.............................................................. 3   3   3   3   3   60  1    Cooling constant.............................................................. 10  10  10  10  3   60  1    Alarm threshold (%)........................................................... 60  60  60  60  60  100 1    Current (A)................................................................... 1.0 1.0 1.0 1.0 0.2 2.0 0.1                                    Voltage Protection                                 Phases overvoltage____________________________________________________________ T1   T2   T3   T4   min  max   inc   Instantaneous enable.......................................................... NO   NO   NO   NO    Instantaneous pickup tap (V).................................................. 80.0 80.0 80.0 80.0 50.0 165.0 0.1   Instantaneous definite time (sec)............................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Phases undervoltage___________________________________________________________ T1   T2   T3   T4   min  max   inc   Instantaneous enable.......................................................... NO   NO   NO   NO    Instantaneous pickup tap (V).................................................. 50.0 50.0 50.0 50.0 10.0 150.0 0.1   Instantaneous definite time (sec)............................................. 0.00 0.00 0.00 0.00 0.00 10.00 0.01   Overvoltage V0 (time delay)___________________________________________________ T1   T2   T3   T4   min  max   inc   Enable........................................................................ NO   NO   NO   NO    Pickup (V).................................................................... 80.0 80.0 80.0 80.0 1.0  150.0 0.1   Curve type.................................................................... FT   FT   FT   FT    Time dial..................................................................... 1.00 1.00 1.00 1.00 0.05 30.00 0.01  Definite time (sec)........................................................... 5.0  5.0  5.0  5.0  0.0  100.0 0.1    Overvoltage V0 (instantaneous)________________________________________________ T1    T2    T3    T4    min  max   inc   Enable........................................................................ NO    NO    NO    NO     Pickup (V).................................................................... 100.0 100.0 100.0 100.0 1.0  150.0 0.1   

Annexure-V

Page 39 of 52

Definite time (sec)........................................................... 0.00  0.00  0.00  0.00  0.00 10.00 0.01                                      Fault Locator                                                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐                                                                     Fault locator                                   Fault locator_________________________________________________________________ T1    T2    T3    T4    min  max     inc   Enabled....................................................................... YES   YES   YES   YES    Zero‐sequence impedance modulus (Ohms)........................................ 12.67 16.22 16.22 16.22 0.01 300.00  0.01  Zero‐sequence impedance angle (Degrees)....................................... 80.01 79.58 79.58 79.58 0.00 359.99  0.01  Forward impedance modulus (Ohms).............................................. 4.08  5.22  5.22  5.22  0.01 300.00  0.01  Forward impedance angle (Degrees)............................................. 78.63 68.83 68.83 68.83 0.00 359.99  0.01  Line length (Kms)............................................................. 25.0  32.0  32.0  32.0  0.1  5000.0  0.1   Positive sequence of line admittance.......................................... 0.0   0.0   0.0   0.0   0.0  50000.0 0.1   Zero‐sequence of line admittance.............................................. 0.0   0.0   0.0   0.0   0.0  50000.0 0.1    Other power grid data_________________________________________________________ T1       T2       T3       T4       min  max      inc   Local source forward impedance modulus (Ohms)................................. 5.04     2.03     2.03     2.03     0.01 50000.00 0.01  Local source forward impedance angle (Degrees)................................ 78.00    78.00    78.00    78.00    0.00 359.99   0.01  Remote source forward impedance modulus (Ohms)................................ 8.00     2.51     2.51     2.51     0.01 50000.00 0.01  Remote source forward impedance angle (Degrees)............................... 76.00    76.00    76.00    76.00    0.00 359.99   0.01  Line shunt forward impedance modulus (Ohms)................................... 50000.00 50000.00 50000.00 50000.00 0.01 50000.00 0.01  Line shunt forward impedance angle (Degrees).................................. 90.00    90.00    90.00    90.00    0.00 359.99   0.01   Sensitivities_________________________________________________________________ T1  T2  T3  T4  min max   inc  Phase current sensitivity..................................................... 0.1 0.1 0.1 0.1 0.0 30.0  0.1  Neutral current sensitivity................................................... 0.1 0.1 0.1 0.1 0.0 30.0  0.1  Phase voltage sensitivity..................................................... 0.2 0.2 0.2 0.2 0.0 165.0 0.1   Analogic output_______________________________________________________________ T1 T2 T3 T4 min max  inc  Analogic output steady delay.................................................. 0  0  0  0  0   7201 1     

Annexure-V

Page 40 of 52

Parallel line_________________________________________________________________ T1     T2     T3     T4     min  max    inc   Line type..................................................................... Double Single Double Single  Mutual impedance modulus (ohm)................................................ 300.00 0.10   11.17  0.01   0.01 300.00 0.01  Mutual impedance angle (deg).................................................. 300.00 0.00   75.85  0.00   0.00 359.99 0.01                                       Synchrocheck                                                                     ‐‐‐‐‐‐‐‐‐‐‐‐                                                                Synchrocheck protection                              Synchrocheck__________________________________________________________________ T1   T2   T3   T4   min  max  inc   Voltage difference between A and B sides unit pickup.......................... 2    2    2    2    2    90   1     Angle difference between A and B sides unit pickup............................ 5    5    5    5    5    50   1     Frequency difference between A and B sides unit pickup........................ 1.00 1.00 1.00 1.00 0.05 2.00 0.01  Undervoltage unit pickup for permission on A side............................. 50   50   50   50   20   165  1     Undervoltage unit pickup for permission on B side............................. 50   50   50   50   20   165  1     Close permission checking time................................................ 5    5    5    5    0    100  1                                   Synchronism authorisations                             Synchronism authorisations____________________________________________________ T1    T2    T3    T4    min max  inc  Enable synchrocheck function.................................................. NO    NO    NO    NO     Undervoltage conditions....................................................... NEVER NEVER NEVER NEVER  Enable difference of voltages................................................. NO    NO    NO    NO     Enable difference of frequencies.............................................. NO    NO    NO    NO     Enable difference of phases................................................... NO    NO    NO    NO     Number of cycles close breaker................................................ 0.0   0.0   0.0   0.0   0.0 60.0 0.1                                   Breaker Supervision                                                              ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                               Breaker Supervision                                Breaker Supervision___________________________________________________________ T1    T2    T3    T4    min max   inc  Excessive number of trips..................................................... 200   200   200   200   1   254   1    Time span for counting the excessive number of trips.......................... 300   300   300   300   300 3600  1    Cumulative kI2 alarm for maintenance.......................................... 65000 65000 65000 65000 0   65535 1    

Annexure-V

Page 41 of 52

Cumulative kI2 start value (setting).......................................... 1000  1000  1000  1000  0   65535 1    Enable trip circuit supervision............................................... NO    NO    NO    NO     Enable closing circuit supervision............................................ NO    NO    NO    NO                                    Breaker operation logic                                                          ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                            Operation logic scheme                              Breaker_______________________________________________________________________ T1   T2   T3   T4   min  max  inc   Trip locking.................................................................. NO   NO   NO   NO    Open failure timing........................................................... 3.00 3.00 3.00 3.00 0.10 5.00 0.01  Closing failure timing........................................................ 3.00 3.00 3.00 3.00 0.10 5.00 0.01                                Breaker failure protection                             Pole discordance______________________________________________________________ T1   T2   T3   T4   min  max    inc   Enable........................................................................ NO   NO   NO   NO    Discordance time (s).......................................................... 3.00 3.00 3.00 3.00 0.03 300.00 0.01                                       Recloser (4)                                                                     ‐‐‐‐‐‐‐‐‐‐‐‐                                                             Distance protection logic trip                          Single/Three pole recloser____________________________________________________ T1         T2              T3              T4              min max   inc  Recloser on‐line.............................................................. NO         NO              NO              NO               Reclose type selection........................................................ Three pole Sing/Three pole Sing/Three pole Sing/Three pole  Number of programmed shots.................................................... 1          1               1               1               1   4     1    1st shot time for single pole reclose......................................... 1.0        1.0             1.0             1.0             0.1 20.0  0.1  1st shot time for three pole reclose.......................................... 1.5        1.5             1.5             1.5             0.1 20.0  0.1  2nd shot time reclose......................................................... 5.0        5.0             5.0             5.0             1.0 300.0 0.1  3rd shot time reclose......................................................... 7.0        7.0             7.0             7.0             1.0 300.0 0.1  4th shot time reclose......................................................... 20.0       20.0            20.0            20.0            1.0 300.0 0.1  

Annexure-V

Page 42 of 52

Security time after single pole closing....................................... 6.0        6.0             6.0             6.0             1.0 300.0 0.1  Security time after three pole closing........................................ 4.0        4.0             4.0             4.0             1.0 300.0 0.1  Reclaim time after manual closing............................................. 10.0       10.0            10.0            10.0            1.0 300.0 0.1  Synchronism time delay........................................................ 10.0       10.0            10.0            10.0            1.0 300.0 0.1  Enabled reclose units Zone 1 trip................................................................... Y          Y               Y               Y                Zone 2 trip................................................................... Y          Y               Y               Y                Zone 3 trip................................................................... Y          Y               Y               Y                Zone 4 trip................................................................... N          N               N               N                Instantaneous negative sequence overcurrent trip.............................. N          N               N               N                Time delay negative sequence overcurrent trip................................. N          N               N               N                Instantaneous zero sequence overcurrent trip.................................. Y          Y               Y               Y                Time delay zero sequence overcurrent trip..................................... Y          Y               Y               Y                Locks after single pole trip Neutral instantaneous......................................................... N          N               N               N                Neutral time delay............................................................ N          N               N               N                Unbalance instantaneous....................................................... N          N               N               N                Unbalance time delay.......................................................... N          N               N               N                                    General settings and remote port configuration                                   ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                       General                                      Operation_____________________________________________________________________ T0   Device on‐line................................................................ YES   Configuration_________________________________________________________________ T0     Number of breaker (position).................................................. NA1     Current transformers turn ratio_______________________________________________ T0  min max  inc  Phase current turn ratio...................................................... 800 1   3000 1    Neutral current turn ratio.................................................... 800 1   3000 1     Voltage turn ratio____________________________________________________________ T0   min max  inc  Voltage transformers turn ratio............................................... 2000 1   9999 1          Measurements correcting factors and outputs activation timings of outputs      

Annexure-V

Page 43 of 52

Correcting factors____________________________________________________________ T0    min   max   inc    Active energy counter constant................................................ 1     1     9999  1      Reactive energy counter constant.............................................. 1     1     9999  1      Power constant................................................................ 1.000 0.010 2.000 0.001                                     General settings                                  Phase‐to‐neutral rated voltage (secondary winding)____________________________ T0   min  max   inc  Phase‐to‐neutral rated voltage (secondary winding) (V)........................ 63.5 50.0 165.0 0.1                         Digital and logical inputs configuration                                         ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                       Configuration                                   Digital Inputs________________________________________________________________ T0  Digital inputs layout ED 1............................................ CB 52a Status ED 2............................................ Phase 1 CB 52a Status ED 3............................................ Phase 2 CB 52a Status ED 4............................................ Phase 3 CB 52a Status ED 5............................................ Close Command ED 6............................................ Recloser Block ED 7............................................ Leds Reposition ED 8............................................ Force 3 Phase Trip ED 9............................................ External Protection ED 10........................................... Not Assigned Input ED 11........................................... Not Assigned Input ED 12........................................... Not Assigned Input ED 13........................................... Guard Signal Lost: RPSG ED 14........................................... Teleprotection Received RTPE ED 15........................................... Not Assigned Input ED 16........................................... External Protection                                   Signals Programing                                                               ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                            Programable Logic Signals                             Programable Logic Signals_____________________________________________________ T0     

Annexure-V

Page 44 of 52

1 ‐ Logic 1                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐     Phase Overcurrent Trip       [45]         2‐     Earth Overcurrent Trip       [47]     AND   2 ‐ Logic 2                              Delay: 0.0 sec        Pulse width: 0.2 sec AND     OR         1‐     Start Zone 2 Ph 1‐Earth      [8]         2‐     Start Zone 2 Ph 2‐Earth      [9]         3‐     Start Zone 2 Phe 3‐Earth     [10]         4‐     Start Zone 2 Ph 1‐2          [11]         5‐     Start Zone 2 Ph 2‐3          [12]         6‐     Start Zone 2 Ph 3‐1          [13]         7‐     Start Zone 2 Triphasic       [14]     AND         1‐     Digital Input 14             [93]   3 ‐ Logic 3                              Delay: 0.0 sec        Pulse width: 0.2 sec OR     OR         1‐     Phase 1 Open Failure         [58]         2‐     Phase 2 Open Failure         [66]         3‐     Phase 3 Open Failure         [74]         4‐     Digital Input 16             [95]         5‐     Logic 1                      [120]         6‐     Logic 5                      [124]         7‐     Switch Onto Fault            [37]         8‐     Power Swing Trip             [36]     AND         1‐     Digital Input 9              [88]   4 ‐ Logic 4                              Delay: 0.0 sec        Pulse width: By logic OR     OR         1‐ NOT Digital Input 10             [89]         2‐ NOT Digital Input 11             [90]         3‐ NOT Digital Input 12             [91]     AND   5 ‐ Logic 5                              Delay: 0.0 sec        Pulse width: 0.2 sec OR 

Annexure-V

Page 45 of 52

    OR         1‐     Zone 1 Trip                  [7]         2‐     Zone 2 Trip                  [15]         3‐     Zone 3 Trip                  [23]         4‐     Zone 4 Trip                  [31]     AND   6 ‐ Logic 6                              Delay: 0.0 sec        Pulse width: 25.0 sec OR     OR         1‐     Output Contact 21            [116]     AND                             Digital outputs configuration                                                    ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Configuration                                   Digital outputs_______________________________________________________________ T0  Digital outputs layout SD 1............................................ Breaker Closing (reclose) SD 2............................................ Phase 1 Fault SD 3............................................ Phase 2 Fault SD 4............................................ Phase 3 Fault SD 5............................................ Not Assigned Output SD 6............................................ Teleprotection ETP Signal SD 7............................................ Triphasic fault SD 8............................................ Logic Signal 3 SD 9............................................ Breaker Failure Trip SD 10........................................... Close Permission SD 11........................................... Recloser Blocked SD 12........................................... Logic Signal 4 SD 13........................................... Logic Signal 5 SD 14........................................... Logic Signal 1 SD 15........................................... Recloser Ongoing Cycle SD 16........................................... Open Phase Alarm SD 17........................................... Switch On Fault SD 18........................................... Fuse Failure SD 19........................................... Power Swing SD 20........................................... Logic Signal 1 SD 21........................................... Teleprotection ETP Signal SD 22........................................... Not Assigned Output SD 23........................................... Logic Signal 6 SD 24........................................... Logic Signal 2   

Annexure-V

Page 46 of 52

                                Leds configuration                                                               ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                                  Configuration                                   LEDs__________________________________________________________________________ T0  LEDs layout LED 1........................................... Phase 1 Fault LED 2........................................... Phase 2 Fault LED 3........................................... Phase 3 Fault LED 4........................................... Triphasic Fault LED 5........................................... Zone 1 Trip LED 6........................................... Zone 2 Trip LED 7........................................... Zone 3 Trip LED 8........................................... Zone 4 Trip LED 9........................................... Phase Overcurrent Trip LED 10.......................................... Earth Overcurrent Trip LED 11.......................................... Open Phase Alarm LED 12.......................................... Fuse Failure                                 Chronological reports                                                            ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Chronological reports                               Measurements chronological reports____________________________________________ T1    T2    T3    T4     Time span for calculating the mean of samples................................. 1     1     1     1      Chronological report recording time interval.................................. 00:30 01:00 01:00 01:00  Weekdays mask Monday........................................................................ YES   YES   YES   YES    Tuesday....................................................................... YES   YES   YES   YES    Wednesday..................................................................... YES   YES   YES   YES    Thursday...................................................................... YES   YES   YES   YES    Friday........................................................................ YES   YES   YES   YES    Saturday...................................................................... YES   YES   YES   YES    Sunday........................................................................ YES   YES   YES   YES    Calendar mask................................................................. YES   YES   YES   YES    Daily record start time....................................................... 0     0     0     0      Daily record end time......................................................... 23    23    23    23                               Oscillograph record configuration                                                ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                 Oscillograph record configuration                         

Annexure-V

Page 47 of 52

Oscillograph record configuration_____________________________________________ T0      min max inc  Digital signals recorded in each channel Channel Nº 0.................................... Phase 3 Trip Channel Nº 1.................................... Zone 1 Ph 2‐Earth Start Channel Nº 2.................................... Zone 1 Ph 3‐Earth Start Channel Nº 3.................................... Zone 1 Ph 1‐2 Start Channel Nº 4.................................... Zone 1 Ph 2‐3 Start Channel Nº 5.................................... Zone 1 Ph 3‐1 Start Channel Nº 6.................................... Phase 1 Trip Channel Nº 7.................................... Phase 2 Trip Channel Nº 8.................................... Phase 3 Trip Channel Nº 9.................................... Fuse Failure Channel Nº 10................................... Zone 2 Start Channel Nº 11................................... Zone 2 Activation Channel Nº 12................................... Zone 3 Start Channel Nº 13................................... Zone 3 Activation Channel Nº 14................................... Zone 4 Start Channel Nº 15................................... Zone 4 Activation Pickup causing digital signals Digital Input 1................................. Yes Digital Input 2................................. No Digital Input 3................................. No Digital Input 4................................. No Digital Input 5................................. Yes Digital Input 6................................. Yes Digital Input 7................................. No Digital Input 8................................. Yes Digital Input 9................................. Yes Digital Input 10................................ No Digital Input 11................................ No Digital Input 12................................ No Digital Input 13................................ Yes Digital Input 14................................ Yes Digital Input 15................................ No Digital Input 16................................ Yes Three Phase Trip................................ Yes Phase 1 Trip.................................... Yes Phase 2 Trip.................................... Yes Phase 3 Trip.................................... Yes I1 Instantaneous Trip........................... Yes I2 Instantaneous Trip........................... Yes I3 Instantaneous Trip........................... No I Earth Instantaneous Trip...................... No I1 Time Delay Trip.............................. No I2 Time Delay Trip.............................. No I3 Time Delay Trip.............................. No I Earth Time Delay Trip......................... No 

Annexure-V

Page 48 of 52

V1 Overvoltage Trip............................. No V2 Overvoltage Trip............................. No V3 Overvoltage Trip............................. No V1 Undervoltage Trip............................ No V2 Undervoltage Trip............................ No V3 Undervoltage Trip............................ No I1 Instantaneous Start.......................... No I2 Instantaneous Start.......................... No I3 Instantaneous Start.......................... No I Earth Instantaneous Start..................... No I1 Time Delay Start............................. No I2 Time Delay Start............................. No I3 Time Delay Start............................. No I Earth Time Delay Start........................ No V1 Overvoltage Start............................ No V2 Overvoltage Start............................ No V3 Overvoltage Start............................ No V1 Undervoltage Start........................... No V2 Undervoltage Start........................... No V3 Undervoltage Start........................... No Zone 1 Ph 1‐Earth Start......................... No Zone 1 Ph 2‐Earth Start......................... No Zone 1 Ph 3‐Earth Start......................... No Zone 1 Ph 1‐2 Start............................. No Zone 1 Ph 2‐3 Start............................. No Zone 1 Ph 3‐1 Start............................. No Zone 2 Ph 1‐Earth Start......................... No Zone 2 Ph 2‐Earth Start......................... No Zone 2 Ph 3‐Earth Start......................... No Zone 2 Ph 1‐2 Start............................. No Zone 2 Ph 2‐3 Start............................. No Zone 2 Ph 3‐1 Start............................. No Zone 3 Ph 1‐Earth Start......................... No Zone 3 Ph 2‐Earth Start......................... No Zone 3 Ph 3‐Earth Start......................... No Zone 3 Ph 1‐2 Start............................. No Zone 3 Ph 2‐3 Start............................. No Zone 3 Ph 3‐1 Start............................. No Zone 4 Ph 1‐Earth Start......................... No Zone 4 Ph 2‐Earth Start......................... No Zone 4 Ph 3‐Earth Start......................... No Zone 4 Ph 1‐2 Start............................. No Zone 4 Ph 2‐3 Start............................. No Zone 4 Ph 3‐1 Start............................. No Zone 2 Ph 1‐Earth Activation.................... No Zone 2 Ph 2‐Earth Activation.................... No Zone 2 Ph 3‐Earth Activation.................... No Zone 2 Ph 1‐2 Activation........................ No 

Annexure-V

Page 49 of 52

Zone 2 Ph 2‐3 Activation........................ No Zone 2 Ph 3‐1 Activation........................ No Zone 3 Ph 1‐Earth Activation.................... No Zone 3 Ph 2‐Earth Activation.................... No Zone 3 Ph 3‐Earth Activation.................... No Zone 3 Ph 1‐2 Activation........................ No Zone 3 Ph 2‐3 Activation........................ No Zone 3 Ph 3‐1 Activation........................ No Directional..................................... No Fuse Failure.................................... Yes Load Encroachment............................... No Power Swing..................................... Yes Switch On Fault................................. Yes Open Phase Alarm................................ Yes Phase Instantaneous Start....................... No Phase Time delay Start.......................... No Overvoltage Trip................................ No Undervoltage Trip............................... No Phase Instantaneous Trip........................ No Phase Time delay Trip........................... No Overvoltage Start............................... No Undervoltage Start.............................. No Zone 1 Start.................................... No Zone 2 Start.................................... Yes Zone 3 Start.................................... Yes Zone 4 Start.................................... Yes Zone 2 Activation............................... Yes Zone 3 Activation............................... Yes Zone 4 Activation............................... Yes Power Swing Trip................................ No Logic Signal 1.................................. No Logic Signal 2.................................. No Logic Signal 3.................................. No Logic Signal 4.................................. No Logic Signal 5.................................. No Logic Signal 6.................................. No I Unbalance Time Delay Start.................... Yes I Unbalance Instantaneous St.................... No Thermal Start................................... Yes V0 Time Delay Start............................. Yes V0 Instantaneous Start.......................... No I Unbalance Time Delay Trip..................... No I Unbalance Instantaneous Tr.................... Yes Thermal Trip.................................... Yes V0 Time Delay Trip.............................. No V0 Instantaneous Trip........................... No Phase 1 Dead Line............................... No Phase 2 Dead Line............................... No 

Annexure-V

Page 50 of 52

Phase 3 Dead Line............................... No Phase 1 52BF.................................... No Phase 2 52BF.................................... No Phase 3 52BF.................................... No Zone 5 Ph 1‐Earth Start......................... Yes Zone 5 Ph 2‐Earth Start......................... No Zone 5 Ph 3‐Earth Start......................... No Zone 5 Ph 1‐2 Start............................. No Zone 5 Ph 2‐3 Start............................. No Zone 5 Ph 3‐1 Start............................. No Zone 5 Ph 1‐Earth Activation.................... No Zone 5 Ph 2‐Earth Activation.................... No Zone 5 Ph 3‐Earth Activation.................... No Zone 5 Ph 1‐2 Activation........................ No Zone 5 Ph 2‐3 Activation........................ No Zone 5 Ph 3‐1 Activation........................ No Zone 5 Start.................................... No Zone 5 Activation............................... No CT supervision.................................. Yes Samples per message........................................................... Maximum  Total number of oscillograph stored cycles.................................... 30       Number of stored pre‐fault cycles............................................. 4       1   60  1                                  Control Measures Selection                                                       ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐                                                             Control Measures                                 Control Measures Selection____________________________________________________ T0  Control Measures Selection MEASURE 1....................................... V Phase 1 MEASURE 2....................................... V Phase 2 MEASURE 3....................................... V Phase 3 MEASURE 4....................................... Average V MEASURE 5....................................... V Phase 1‐2 MEASURE 6....................................... V Phase 2‐3 MEASURE 7....................................... V Phase 3‐1 MEASURE 8....................................... Average V Phase‐Phase MEASURE 9....................................... I Phase 1 MEASURE 10...................................... I Phase 2 MEASURE 11...................................... I Phase 3 MEASURE 12...................................... Average I MEASURE 13...................................... Maximum I MEASURE 14...................................... Real Power P MEASURE 15...................................... Reactive Power Q MEASURE 16...................................... Frequency MEASURE 17...................................... Power Factor Phase 1 

Annexure-V

Page 51 of 52

MEASURE 18...................................... Power Factor Phase 2 MEASURE 19...................................... Power Factor Phase 3 MEASURE 20...................................... Average Power Factor MEASURE 21...................................... Fault Distance (%) 

Annexure-V

Page 52 of 52