Page 1: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Planning Guide DEM 750/950

652 West Ave

South Jersey Elevator

Ocean City, New JerseyOffice 609-545-8512 Fax 609-545-8502

www.SJElevator.com

Page 2: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Phone: 609-545-8512 FAX: 609-545-8502

Elevator Feature

Characteristics

Up to 950 lb capacity (750 lb standard)*40 f.p.m. nominal car speedUp to 6 stops with 50 feet of floor to floor travel*Minimum pit depth of 8 inches required (10” recommended)Minimum overhead clearance of 8’0”required(9’6” recommended)Up to 15 square feet interiors cab sizes available (12 ft standard)*

*Consult SJE for other custom options available

Equipment

1:2 Roped hydraulic drive(2) 3/8” diameter hoist cablesSingle stage hydraulic piston and cylinder with pressure balanced self adjusting sealHeavy duty cantilevered designed car sling withroller guide shoes8 lb per foot steel tee guide rail system220 volt single phase power supplyVibration free submersible pump/motor assemblywith 3 or 5 horsepower motor optionTwo speed control valve with (4) solenoids, start and stop, and constant down speed regulation

Safety Devices

Type “A” instantaneous broken rope car safetyPipe rupture valveUpper and lower terminal limit switchesTop final limit switchSlack cable switchEmergency car lighting in cabEmergency l stop switch in cabEmergency push button alarm in cabAutomatic car re-leveling deviceFloor selectable battery lowering deviceEmergency manual lowering valve Emergency telephone in cabSolid panel cab doors with approved safety switchApproved electro mechanical hoistway doorinterlocksRubber impact bumper below elevator carUL and/or CSA certified electrical and hydraulicdevices

Manufactured in accordance with ASME A17.1 safety code

Manufactured in accordance with ASME A17.1 safety code

South Jersey Elevator

Page 3: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Phone: 410-749-3489 FAX: 410-341-7505

Controls/Push Button Fixtures

Automatic pushbutton controlMicroprocessor based control system with uninterrupted battery back upLight-up pushbuttons in car and hallDigital floor position indicator in carAutomatic in car light with override switch in cabAutomatic indicator light time-out featureAutomatic “Home Park” feature to designated floor“Car Here” indicators in hallLow oil protection timer circuit

Cab Finishes & Accessories

Cambridge series cab available in a wide variety ofplastic laminate choices and other optionsSolid panel accordion cab door available in a wide variety of vinyl laminate choices

36” x 48” x 80” high clear interior cab size with a variety of cab opening configurations

Brushed stainless steel handrail on one side wallBrushed stainless steel cab control panel

Options

St. Michael & Chesapeake Series cabs available ina wide variety of finishes and other options

Accordion cab doors in hardwoods, custom stain and lacquer finish, aluminum, clear or bronze acrylic panels

Recessed telephone cabinetAutomatic car door operatorPolished stainless steel, brushed brass, or polished brass pushbutton faceplate handrail finishes

South Jersey Elevator

Page 4: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Rev. Date 6/10/2009

652 West Ave

WORK DONE BY OTHERS Ocean City, NJ 08226

South Jersey Elevator Residential Hydraulic Elevator Ph: 609-545-8512 Fax: 609-545-8502

www.SJElevator.com

Prior to job site arrival for installation of elevator, SJE requires the following work by others to be completed.

ELEVATOR HOISWAY: Provide an enclosed finished LEGAL hoistway with INSIDE, CLEAN, CLEAR, SQUARE, AND PLUMB (including pit) dimensions recommended to be a minimum of 53 inches wide by 57 inches deep (53” X 57”) (THIS IS AFTER DRYWALL) including blocking, which will provide an interior cab dimension of approximately 12 square feet. Additional Hoistway Plans are available by contacting your local SJE Sales Rep. SJE will build to your specifications if smaller or larger than the above, but only to the smallest dimension inside the clean, clear, square and plumb (including pit) finished drywall hoistway.

Barricades and/or any/all other legal methods required by any jurisdiction to prevent access into shaft shall be required outside each floor landingfor the protection of workmen and all other subcontractors and/or occupants until the elevator is installed completely and turned over to the homeowner. These devices shall be the sole responsibility of GC. GC TO PROVIDE SOLID CORE HOISTWAY/LANDING DOORS WITHHINGES LOCATED ON RAILSIDE.

“3X5” RULE (Clearance between hoistway/landing doors and gates AND landing sills): DOOR SIDE WALL TO BE OF 2” X 4”CONSTRUCTION. Regardless of construction type EACH DOOR MUST BE RECESSED TO MEET THRESHOLD REQUIREMENTS ASCONTAINED IN THE ANSI A17.1 (3” X 5” SPACING CODE). The distance between the backside of hoistway/landing door, in the closedposition, and the elevator gate(s), in the open position, shall not exceed 5 inches. The distance between the backside of hoistway/landing door, inthe closed position, and landing sill shall not exceed 3 inches. ELEVATOR CANNOT BE OPERATIONAL UNLESS LANDING DOORS ARE IN COMPLIANCE.

THRESHOLD: Contractor shall provide a threshold from each floor to 1” of the elevator platform AFTER the elevator has been installed. Doors shall NOT be centered but installed per SJE specs to allow proper rail side return measurement. Rail Side return measurement of at least 12 inches is required. Hoistway side of landing doorframes shall NOT have casing or door trim that exceed ¼” thickness.

A MINIMUM PIT OF 8” INCHES IS REQUIRED built to withstand 3,900lb maximum load. Minimum 96” overhead clearance is required for6’-8” cabs (108” for 8’-0” cabs).

ANY TRAVEL DISTANCES over 28’ 0” requires a special piston which requires installation during framing stage due to piston length.Contractor to allow DEI four (4) weeks notice to order, deliver and install “Hydraulic Jack” prior to sheetrock.

WOODFRAME HOME BLOCKING REQUIREMENTS: Four (2 sets of 2 ea.) – 2” X 12” yellow pine studs running vertically the entirelength of the hoistway 12” on center on either side of rail wall centerline (centerline of rail wall must be minimum of 28” off inside front wall), 2”X 12” to be face nailed, glued and edged with 2” X 4” for structural integrity. The yellow pine boards shall all be fastened to the wall supports with 3/8” by 2-1/2” lag bolts to support elevator rail system. To insure adequate support in wall for guide rail fastening the blocking should not exceed 10 vertical feet without intermediate horizontal support and shall meet all pertinent building codes.

CONCRETE BLOCK HOME OR HOISTWAY: All dimensions shall remain the same for INSIDE, CLEAN, CLEAR, SQUARE, ANDPLUMB hoistway. Rail sidewall blocks shall filled solid with concrete the entire length of hoistway. One (1) 4’ Knockout shall be provided between hoistway and machine room. All patching, fire caulking, painting/grouting required after installation is the responsibility of GC.

MACHINE ROOM: The contractor shall provide an elevator machine room. UNLESS OTHERWISE SPECIFIED, MACHINE ROOM IS ASSUMED TO BE A LOWEST LEVEL ADJACENT TO ELEVATOR. This area shall be a minimum size of 4’ X 4’ and to meet all electrical codes. Contractor/Owner is responsible for notifying DEI is Machine Room is located within in a Flood Zone and contractor is responsible for building platform or room above Flood Zone per SJE specifications. If machinery is located in attic, a deck must be built to support loads imposed by unit (Contact SJE for Details) height and accessibility for service and installation should be provided minimum height of 60 inches including catwalk to deck area, scuttle hole and attic ladder. Attic not recommend for hydraulic installations. If machine room is remote (not rail side adjacent) contractor is responsible for coordinating the timely installation of ¾’ seamless schedule 80 black pipe. DEI will install, but we must have ample time and access.

ELECTRICAL: Standard 220 Volt 30 Amp dedicated service 10-3 wire with ground and standard 110, 15 Amp single pole circuit breaker (both with eight feet of length from inside machine room wall penetration) and telephone line shall all be located in machine room. PLEASE BE ADVISED THAT POWER ON THE 220V LINE MUST BE A 10-3 WIRE WITH A GROUND AND INSURE THERE IS A DEDICATED NEUTRAL TO THE UNIT. IN ADDITION, ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL 240V-30 AMP DISCONNECT WITH INTERLOCK KIT PLUS 2 EACH 250V RK5 FUSE, AND SINGLE POLE 110V-15A DISCONNECT. Explanation: The 220V feed should have a black, red, white and ground wire coming to the machine room. All electrical contractors will have full knowledge of this requirement. Simply insure they are aware of the requirement. Black and red are powered with 110V each totaling 220V. White is neutral to feed low voltage transformer with 110V. Ground to ground standard. (See SJE Electrical requirements sheet.)

General contractor and/or Owner shall Indemnify and hold SJE harmless for all claims subject to this “Work Done By Others”. Cancellation fees apply. See SJE representative for details. ANY WORK DONE BY OTHERS HEREIN NOT FULLY COMPLETE PRIOR TO TIME OF INSTALLATION SHALL RESULT IN A REMOBILIZATION FEE OF $750. NOTE: INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE.

Page 5: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 6: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 7: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 8: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Part 1: General

1.1 Description of WorkTo furnish all labor and materials required tocover a complete installation of (one) ropedhydraulic residential elevator. The elevator is to be installed in a first class workmanlike mannerin accordance with the specification anddrawings provided.

1.2 Work By OthersThe following preparatory work to accommodate the elevator installation is to be done by othersand is part of work of other sections.A. Hoistway

1.A finished plumb hoistway of proper sizeand construction conforming to ASMEA17.1 all applicable building codes, andthe elevator layout drawings.

2.Adequate supports shall be provided forfastening rail brackets as indicated on thelayout drawings. Supports must withstandrail forces indicated.

3.A poured pit conforming to all applicablecodes, ASME A17.1, and to thedimensions indicated on the layoutdrawings must be provided. The pit mustbe designed for the impact load indicatedand must be guaranteed dry and levelfrom wall to wall.

4.Knock-out in walls between the machineroom and elevator hoistway for routinghydraulic and electrical lines and for hallbuttons shall be coordinated with theelevator contractor.

5.All wall patching, painting, and grouting byothers.

6.Hoistway doors, frames, entrances, sills,and associated framing to be providedand installed by purchaser or generalcontractor.

B. Machine Room1. An adjacent machine room built to

conform to the layout drawings, NFPA70, ASME A17.1, and all applicablebuilding code requirements. It shall havesuitable access, a lockable door, aconvenience outlet, and light switch.Machine roon temperature must be maintained between 60 and 100degrees. Relative humidity not toexceed 95%.

2. A telephone line to the machine roomand tied into the elevator controller asper ANSI/AMSE A17.1 code.

3. Machine room vents as required by localcode.

C. Electrical Requirements1. A 220 VAC, single phase service, with

neutral, to a lockable safety disconnectswitch, fused with time delay fuses shall be furnished in the machine room inaccordance with NFPA 70. A normally open electric interlock contact isrequired in the switch for batteryisolation.

2. A 120 VAC, single phase, 15 AMPservice to a lockable disconnect switch,or circuit breaker, located in themachine room shall be provided for thecab lighting in accordance with NFPA70.

1.3 Quality AssuranceThe elevator shall be designed, manufactured,installed, and inspected in accordance withANSI/ASME A17.1 standards and all applicableregulations of federal, state, and local agencieshaving jurisdiction.A. References

1. American National Standards Institute(ANSI)

2. American Society of MechanicalEngineers (AMSE)

3. National Electric Code (NFPA 70)4. CSA B44.1/ASME A17.1, elevator and

escalator electrical equipment requirements.

B. QualificationsThe installation shall be performed by acompany with no less than (5) years ofsuccessful experience in the assembly anderection of similar type elevators and whohas adequate product liability insurance.

C. Regulatory RequirementsThe elevator installer shall verifyrequirements of the local authority havingjurisdiction and shall obtain and pay fornecessary municipal and state permits and inspections as required, and make tests as called for by the regulations of suchauthorities.

Part 2: Submittals

2.1 Product DataSubmit manufacturer literature including productdata, cab design, color charts, signal fixtures andspecification.

2.2 Layout Drawings

South Jersey Elevator652 West Ave Ocean City, NJ 08226

Phone: 609-545-8512 FAX: 609-545-8502

Layout drawings shall be submitted showing thegeneral arrangement of the elevator equipment including dimensions, clearances, location ofmachine equipment, and all loads and reactionsimposed on pit and building structure.

Page 9: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Part 3: Product

3.1 ManufacturerThe roped hydraulic residential elevator shall bemanufactured by Delaware ElevatorManufacturing Co., 27685 Rockawalkin RidgeRoad, Salisbury, MD 21801. U.S. Toll Free 1-800-787-0436 or Fax 410-341-7505

3.2 CharacteristicsType: Roped 2:1 HydraulicCapacity: 750 lbs.Car Speed: 40 FPMOperation: SAPB/Single Button CollectiveTravel:Number of Stops:Number of Openings:Inside Car Dimensions: 36” x 48” x 80” highPower Supply: 220 Volt, single phase, 60 Hz.Cab Design:Push Button Faceplatesand Handrail Finish:

3.3. EquipmentA. Operations

Operation of the elevator shall be singleautomatic push button or single buttoncollective (field programmable); momentary pressure on any button will call or send theelevator to the corresponding landingproviding all doors are closed.

1.Battery Lowering: In the event of apower failure, the elevator shallautomatically descend to the nextlanding, and can proceed to thebottom landing while monitoring all safety circuits If the elevator isequipped with a power car door(s)option, the car door(s) shall open andclose automatically. Batteries are to have an automatic charging system.

2. Emergency car lighting: In the eventof a power failure, the car lights shallautomatically transfer to batterypower.

3. Homepark Feature: The elevator shallautomatically return to a field ofprogrammable designated landingafter one minute without use. (perpreference)

4. Automatic two-way leveling: theleveling device shall automatically

South Jersey Elevator652 West Ave Ocean City, NJ 08226

Phone: 609-545-8512 FAX: 609-545-8502

stop and maintain the car within ½inch of the landing regardless ofchange in load.

5. Low oil control: A low oil controlfeature shall be provided designed toautomatically cause an up travel car to descend to the lowest terminal if theelevator should fail to reach a landing in a predetermined time or if the system does not have a sufficientreservoir of oil.

B. Control SystemsA microprocessor based control systemcertified and labels to the requirements of CAN/CSA-B44.1/AMSE A17.1 shall beprovided. It shall include a motor starter with a potential relay, motor overload device, an uninterrupted power supplywith battery charging circuit, and externalrelay redundancy circuits to preventdangerous conditions as a result of a single contact failure. All circuits shall befuse protected. All to be enclosed in asingle NEMA 1 cabinet.

C. Hydraulic Power UnitThe hydraulic power unit shall include a submersible motor, rotary screw typepump, two-speed control valve and oil reservoir with an oil level gauge. The control valve shall include safety check valve, up and down acceleration,deceleration, leveling and soft stopadjustments, pressure relief valve, manual lowering valve, constant down speed regulation, pressure gauge with shutoff,negative pressure switch and manualshutoff valve all mounted and enclosed in a compact unit assembly with a key lockable cover.

D. Plunger and CylinderThe cylinder shall be constructed of steelpipe with a steel bulkplate welded to thelower end and a cylinder head welded to theupper end which houses the self adjustingpacking bearings wiper, are bleeder, andleach line hose. The plunger shall bemanufactured from accurately ground andpolished tubing fitted with a steel stop ringwelded to the bottom to prevent the plungerform leaving the cylinder in the up direction.

E. Pipe Rupture ValveAn automatic shut off valve at the cylinderinlet shall be provided to stop and hold theelevator in the event of a main oil line failureor if the elevator should overspeed in thedown direction.

Page 10: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

The car frame shall be fabricated fromstructural and formed steel members,welded and bolted construction, of thecantilevered design.

G. Car SuspensionThe elevator car frame shall be suspendedby (2) 3/8” diameter, 6 x19, traction steelcables. The cables shall dead end to the pitsteel on one end, pass a “U” groove sheave,and attach to the car safety device with approved type wedge sockets.

H. Guide RailsThe car guide rails shall consist of (2) machined steel “tee” sections, no less than 8lb. per foot, securely fastened to the hoistway structure with steel brackets. Allrail end sections shall be tongue & grovetype joined with steel splice plates.

I. Car Operating PanelCar operating panel shall consist of metallens call push button with red LED halolighting for each landing, an alarm buton,emergency stop button, light switch, and adigital car position indicator with cardirection arrows all mounted onto a brushedstainless steel faceplate (brass optional)Digital C.P.I. shall be field programmable.

J. Landing ControlsLanding controls stations shall consist of a metal lens cal button and a “car here”indicator with red LED halo lighting mountedonto a brushed stainless steel faceplate(brass optional).

K. Hoistway DoorsThe general contractor or owner is to furnish(elevator contractor may opt to furnish) andinstall hoistway doors, frames, hinges, and passage sets at each landing. The type andinstallation of the doors and frames mustcomply with ASME A17.1, all state and localcodes and as per manufacturer’s layoutdrawings.

L. Car Door(s)The car door(s) shall be solid panelconstruction accordion type folding door(s)that prevent a person’s hands or feet fromextending through openings. Finish shall bevinyl laminate chosen from the manufacturer’s standards color selection(hardwood, visifold, and alumifold optional). Car poor shall be equipped with a positivecontact switch to prevent elevator operationwith the car door(s) open (power car door(s)optional).

F. Car Frame and Platform

laminate or wood veneers with wood trimaccents as selected from the manufacturer’sstandard designs. A brushed stainless steelhandrail (brass optional) shall be located onone wall. A telephone shall be furnished inthe elevator cab for emergency communication. Cab ceiling shall be aminimum of ¾” thick substrate with at least a (2) bulb light fixture as selected from themanufacture’s standard ceiling designs.Finished flooring covering is to be furnishedby others.

N. Electrical WiringAll wiring and electoral materials shallconform to NFPA 70 and with all applicablecodes. Insulated wiring shall have flameretardant and moisture proof outer coveringand shall be run in conduit or electricalwireways as required. Traveling cables shall be flexible and suitable suspended to relievestrain.

Part 4: EXECUTION

4.1 ExaminationElevator installer shall verify dimensions ofhoistway, pit, machine room, and inspectcondition of supports and structure prior toinstallation.

4.2 InstallationThe elevator shall be installed in accordance withthe manufacturer’s instructions and shall conformto ASME A17.1 and all state and local coderequirements.

4.3 Operating InstructionsUpon completion of the installation, the ownershall be instructed on the elevator’s operation,safety precautions, and maintenancerequirements. The owner will be supplied with anowner’s manual to retain for reference.

4.4 MaintenanceThe elevator shall be maintained in accordancewith the manufacturer’s recommendations and all applicable codes

4.5 WarrantyThe elevator shall have a (1) year limited partswarranty.

M. Car EnclosureThe cab walls shall be constructed of ¾”minimum substrates faced with plastic

South Jersey Elevator 652 West Ave Ocean City, NJ 08226 Phone: 609-545-8512 FAX: 609-545-8502

Page 11: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

Minimum Requirements for Hydraulic Elevators

1. 52” x 56” clear inside hoistway dimensions when using an accordion style solid gate.

2. 8” minimum pit built to withstand a 3,900 lb load.

3. 96” clear hoistway overheard for 6’-8” cab.

4. 11” minimum return on rail side wall. If this cannot be obtained, contact office forapproval.

5. If masonry construction, rail wall needs to have inserts sold by Delaware Elevator.

6. Rail side blocking for wood frame hoistways must be two 2 x 12’s sandwichedtogether, running vertically the entire length of the hoistway 12” on center of eitherside of the rail wall centerline. (Please see rail wall structural drawing.) Build same asa header.

7. Any travel distances over 28’-0” will incur a special order charge for larger pistontravel. (Add approximately one month to the standard delivery time.)

8. Machine room to be located adjacent to rail wall on first floor.

9. Remote machine rooms to be approved by office.

10. Machine room to be 48” x 48” or large enough to accommodate pump controllerwithout restricting access, and as per code.

South Jersey Elevator 652 West Ave Ocean City, NJ 08226 Phone: 609-545-8512 FAX: 609-545-8502

Page 12: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall

South Jersey Elevator PRE-INSTALLATION CHECK LIST

Each of the below generic items is required to be fully complete prior to South Jersey Elevator, Inc. scheduling an installation crew. Please see WORK DONE BY OTHERS for specific requirements or the CONTRACT ADDENDUM for

this particular job specification requirement.

ITEM COMPLETEDYes/No

COMPLETEDDate

REMAINING NOTES

Legal Machine Room Per Specs

Dedicated 120V/20A Circuit

Dedicated 230V/30A Circuit

Proper Disconnect 110V Per Specs

Proper Disconnect 230V Per Specs

Telephone Line to Machine Room Space

Hoistway Measurements Per Specs

Legal Hoistway Clean, Clear, Square & Plumb

Pit Depth Complete, Plumb, & Square with Hoistway

Rail Side Blocking Complete

Rail Side Return Per Specs

Hoistway Solid Core Doors and Frames

Drywall and / or grouting patching done

Overhead Measurement Per Spec

Electrical Box at Each FloorPlaced for Hall Station

Permanent Power To Machine Room

Temporary Power to Machine Room

Hydraulic Pumping Unit Platform

For questions or concerns, please contact South Jersey Elevator at

609-545-8512.

Elevator Model: JOB NAME:

Signature:

Page 13: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 14: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 15: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 16: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 17: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 18: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 19: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 20: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 21: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 22: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 23: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 24: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 25: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 26: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 27: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 28: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 29: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 30: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 31: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall
Page 32: South Jersey Elevatorsjelevator.com/files/2016/03/SJE-planning-Guide.pdf · South Jersey Elevator Ocean City, ... xRubber impact bumper below elevator car ... and landing sill shall