sophia - cooper hunter · 2017. 10. 23. · c508 c507 c506 c505 c504 c503 c412 c410 c409 c408 c405...
TRANSCRIPT
-
TROUBLESHOOTING
SPLIT AIR CONDITIONERWITH HEAT PUMP
SOPHIA
-
1.1 Indoor Unit Error Display Operation
lamp Timer lamp Display LED STATUS
☆ 1 time X E0 Indoor unit EEPROM parameter error
☆ 2 times X E1 Indoor / outdoor units communication error
☆ 3 times X E2 Zero-crossing signal detection error
☆ 4 times X E3 Indoor fan speed has been out of control
☆ 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit
☆ 6 times X E5 Evaporator coil temperature sensor T2 open circuit or short circuit ☆ 7 times X EC Refrigerant leakage detection
☆ 1 times O F0 Overload current protection
☆ 2 times O F1 Outdoor ambient temperature sensor T4 open circuit or short circuit
☆ 3 times O F2 Condenser coil temperature sensor T3 open circuit or short circuit
☆ 4 times O F3 Compressor discharge temperature sensor TP open circuit or short circuit ☆ 5 times O F4 Outdoor unit EEPROM parameter error
☆ 6 times O F5 Outdoor fan speed has been out of control
☆ 1 times ☆ P0 IPM malfunction or IGBT over-strong current protection
☆ 2 times ☆ P1 Over voltage or over low voltage protection
☆ 3 times ☆ P2 High temperature protection of IPM module or compressor top ☆ 4 times ☆ P3* Outdoor ambient temperature too low.
☆ 5 times ☆ P4 Inverter compressor drive error
☆ 6 times ☆ P5 Indoor units mode conflict (multi-zone ONLY)
☆ 7 times ☆ P6 Low pressure protection(Only for 36K) O(light) X(off) ☆(flash)
*P3 1) In heating mode, when the outdoor temperature is lower than -25℃ for 1 hour, the indoor unit display error code P3. 2) If the outdoor temperature is higher than -22℃ for 10 minutes and compressor stop for 1 hour or outdoor temperature is higher than -5℃ for 10 minutes, then the unit will return to work. * Fault Symptom: The display board shows a garbled code or a code that is not an error code found in the service manual nor a temperature reading. Trouble shooting: Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be replaced; if the unit does respond, then the display board needs to be replaced
-
1.2 Outdoor unit error display(TBD) For CH-09SPH-115VO, CH-12SPH-115VO, CH-09SPH-230VO, CH-12SPH-230VO,
N
1
17122000019195
1
1
[ 1. 6] 2015-09-30
US- KFR- 35W/ BP3N1- ( 115V+RX62T+41560) . D. 13. WP2- 1
L-IN
N-IN
7805
S
HEAT
14-
WAY
AC-F
ANHE
AT2
Eart
h
DC-F
AN
PMV
TESTPORT
BLACKW
REDV
BLUEU
CN4_1CN4_2 CN4_3CN4_4
REACTOR
CAP
T3T4TP
NN
N
H
L
CN25
CN31
ACAC
+-
BR1
+E2
CN21
RC1
E304
ZR2
+- AC
OUTI N
~~
RY3ASJ-S-112DMG
R191
I C105
CN15
ZR5
ZR4
R628
C618
R118
R123
R122
C324
I C2
R421
R621
D103
C413
C306
C319
I PM301
R176
R175
+
E109
C107
T401
R410
R409
R316
3W- 10m¦ ¡̧ À1%
D407++
C110
R623
R602
C624
RY3
R196
D610
C318
C316 C314
C134
+
E605
E303
E208
E206E30
2
E300
CN50
R523
R522
R521
R520
R519
R518
R517
R323
R322
R321
R320
R319
R318
R317
I C301
C513
C512C511
C323
C321
C320
R426
R314R306
R305R304
R303C311
C310
C309
C308
C307
CN28
CN29
CN30 C520
C1
+E106
C101
D101
C611
R171
D602
I C102
Rdi
D404
D401
CN6
ZR1
RY2
R626
R620
R619
R618
R617
R616
R615
R612R611 R610R608
R607
R605
R603
R601
R528
R516
R513
R508R506
R504
R502
R429
R428
R427
R408
R407
R406
R405
R404
R403
R315
R301
R190
R188R187
R186
R185
R182
R181R180
R179
R178
R174
R173 R
170
R169
R168
R165
R157
R155R154
R152
R150
R149
R148
R147
R144
R143
R142R140
R138
R137
R136
R135
R133
R132
R131
R130
R129
R128
R127R126
R125R124
R121
R120
R117
R116
R115
R114 R1
12R1
11
R110
R108
R107
R106
R105
R102
R101
R2
Q101
OSC101
NTC2
+LED101
IC60
3
IC60
2
IC60
1
I C403
I C401
I C1
+
E602
+
E401
+
E108 + E107
+E105
+
E103
+
E102
+
E101
+
E1
+
E3
+
DZ601
DZ304 DZ303 DZ302DZ301
+DZ203
+
DZ202
D406
D402
+
D2
+
D1
1CN505
CN7
C615
C614
C612
C606
C605
C601
C509
C508
C507
C506
C505
C504
C503
C412
C410
C409
C408
C405
C404
C403
C402
C401
C322C312
C305
C303
C302
C274
C273C272
C271
C133
C132
C131
C130C129
C128
C127
C126
C125
C124
C123
C121
C120
C119
C118
C116
C115
C114
C113
C112
C111
C106
C105C104
C103
C102
C16
C11 C10C7 C6
C5
C4
C3
C2
+ E280 +E281
+ E282
+
E283
+
E404
+
E407
PTC1
+
E409D104
R401
R103
C117
R195
R172
+
DZ204 C275
R156R60
4
R104
I C101
I C104
RY4
+
E410
+
E405
FUSE1T20A/ 250VAC
C9A
CN1A
I C404
+
D403
I C103
C613
CN3
CN2
CN1
CN16
+
DZ201
L2L3L4L5
C135
CN17
R21 R23
R158
RY5
21 43
3 4
ON
1 2
ON
SW2
RC2
DSA1
I C405
+
CN60
C8
L1
R1
IPM5
01
C122
CommentComment
RY1
CN507
R606
3W-1
0m¦
¡̧À1%
R2530. 75¦ /̧ 1W
R2540. 75¦ /̧ 1W connect to compressor heaterwhen is on, 100-130V AC outpu
connect to 4-way Valvewhen is on, 100-130VAC OUTPUT
connect to PFC Capacitorwhen is on, 100-130V ACoutput
connect to reactorwhen is on, 100-130V AC output
connect toGround
connect to N-line
(100-130VAC INPUT)
connect to L-line
(100-130VAC INPUT)
connect to indoor unitcommunication
U
V
W
10- 230VAC¡ ̄ ( r unni ng)
0VAC ( st andby)
connect t o DC Mot or
external driver motor
connect to Electric Expansi
pipe temp.sensor& room temp.sensor&Exaust temp. sensor
6 5 4 3
TP T4
RT
RT+5V
DC
+5V
DC
+12V DC pul se wave bet ween (+1) -G
+12V DC pul se wave bet ween (+2) -G+12V DC pul se wave bet ween (+3) -G
+12V DC pul se wave bet ween (+4) -G
+12V DC+12V DC
6 5
4 3
2 1
AC fan motor5
4
3
2
1low speed
N linehigh speed
FAN Starting Capacitor
FAN Starting Capacitor
connect to chassis heaterwhen is on, 100-130VAC OUTPUT
UVW 0VAC(standby)
10-230VAC¡(̄running)
connect tocompressor
connect to PCcommunication
EEPROM ProgrammerPort
Test Port
bridge
IPM for compressor
IPM for DC FAN
P
-
For CH-09SPH-230VO, CH-12SPH-230VO, CH-18SPH-230VO, CH-18SPH-230VO
+
T4TP
T3
N
L
H
NN
RdiHave
Low- Fr e
YESNO
No
U
BLUE
VRED
WBLA
CK
TESTPORT
PMV
DC-F
AN
DR_L
DR_N
Eart
h
HEAT2
AC-F
AN4-
WAY
HEAT
1
S
7805
N-IN
L-IN
KFR- 35W/ BP3N1- ( RX62T+41560) . D. 13. WP2- 1 [ 1. 8] 2015- 12- 31
1 1
17122000002718
1
E304E208
C10
RC3
CN22
ZR4
R696R695
C696
C695
ZR5
C9
IPM5
01
L1
C8
CN60
+
I C405
DAS1
RC2
ON
21
ON
43
341 2
SW2
RY5
R158
R23R21
CN17
CN11
CN10
C135
L5 L4 L3 L2
+
DZ201
L601
CN16
CN1
CN2
CN3
CN3_1
C613
I C103
CN507
+
D403
I C404
CN1A
FUSE1T20A/ 250VAC
E405
E410
RY4
I C104
I C101R1
04
R604
R156
C275
DZ204 R17
2
R195
C117
R103
R401
D104
E409
PTC1
CN32
BR1
E407
E404E283
+ E282+E281
+
E280
RY1
D601
Q601
C2
C3
C4C5
C6
C7
C11
C16
C102
C103
C104C105
C106
C111
C112
C113
C114
C115
C116
C118
C119
C120
C121
C123
C124
C125
C126
C127
C128
C129C130
C131
C132
C133
C271C272
C273
C274
C302
C303
C305
C312C322
C401C402
C403
C404
C405
C408
C409
C410
C503
C504
C505
C506
C507
C508
C509
C601
C605
C606
C612
C614
C615
CN7
CN9
CN31
CN505
D1D2
D402
D406
DZ202
DZ203
DZ301DZ302DZ303DZ304
DZ601
E1
E2
E101
E102
E103
E105
E107
E108
E401
E602
I C1
I C401I C403
IC60
1
I C602
IC60
3
LED101
NTC2
OSC101
Q101
R2
R3
R101
R102
R105
R106
R107
R108
R110
R111R112
R114
R115
R116
R117
R120
R121
R124R125
R126R127
R128
R129
R130
R131
R132
R133
R135
R136
R137
R138
R140R142
R143
R144
R147R148R149
R150
R152
R154R155
R157
R165
R168
R169
R170
R173
R174
R178
R179
R180R181
R182
R185R186
R187
R188
R189
R190
R301
R315
R403
R404
R405
R406
R407
R408
R427
R428
R429
R502
R504R506R508
R513
R516
R528
R601
R603
R605
R607
R608R610R611
R612
R615
R616
R617
R618
R619
R620
R626
RY2
ZR1
CN6
D401
D404
Rdi
I C102
D602
R171
C611
D101
C101
E106
C1
C520
ZR3
CN30
CN29
CN28
C307
C308
C309
C310
C311R303
R304R305
R306R314
R426
C320
C321
C323
C511 C512
C513
I C301
R317
R318
R319
R320
R321
R322
R323
R517
R518
R519
R520
R521
R522
R523
CN50
E206
E605
C134
C314C316
C318
CN25
D610
R196
RY3
C624
R602
R623
C110
C122
D407
R316
3W- 10m| ??¨ ¤1%
R409
R410
R6063W
-10m
1%
T401
C107
E109
R175
R176
I PM301
C319
C306
C413
D103
R621
R421
I C2
C324
R122
R123
R118
C618
R628
CN15
I C105
R191
RY3A
ZR2
RC1
CN21
R1
C412
E300
E302
E303
C330
C331
C332
C333C334
connect t o t he t er mi nal208- 230V ACpower suppl y
connect to earth
CN60connect to 4-way valve
when 4- way i s ON, out put 208- 230VAC
connect t o compr essor heat er
power suppl y
CN17
AC fan motor
L low speed
N ground
H high speed
CN21/CN22exhaust temp. sensor& pipetemp.sensor& room temp.sensor
6 5 4 3 2 1
TP T4 T3
RT
RT
+5VDCRT
+5VDC
+5VDC
connect to Electric Expansion Valve
+12V
DC
puls
e wa
ve b
etwe
en (
+1)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+2)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+3)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+4)-
GND
+12V
DC
+12V
DC
6 5 4 3 2 1
connect to indoor unit communication
HEAT2connect to chassis heaterwhen is on, 208-230VAC OUTPUT
U
V
W
10- 200VAC¡ ̄ ( r unni ng)
0VAC ( st andby)
connect t o t he DC compr essor
Test PortConnect to PCcommunication
EEPROM Programmer Port
FUSE1 20A/250VAC
U
V
W
10- 200VAC¡ ̄ ( r unni ng)
0VAC ( st andby)
connect t o DC Mot or
External driver motor
slow flicker:standby(0.5Hz)quick flicker:error(2Hz)continuous light: normally running
Connect to reactor
IPM for
compressor
IGBT
FRD
when heater is ON, output 208-230V AC
BR
P
N
-
For CH-24SPH-230VO,
Suct i on
Exhaust
+
17122200000309
Hui Qi
Test
Port
1
1
HEAT
4- WAY
W
BLUE
BLACK
REDVU
TP T3T4
No
NO
NOYES
Low- Fr e
No
Have
YESHaveTemp- Pr o
Rdi
Ri pm
11PMV
44
15V17V
[ V1. 8] 2015- 01- 16
7815
22
1
34
REACTOR
311 TEST
7805
N- I N
DC-F
ANAC
-FAN
L- I N
S
KFR- 72W/ BP2- ( 311+0515+6061HD+PSS30S92F6-AG+6822+HEAT) . D. 13. WP2. 1
12V 5V
CN3DSA1
K
A
K
D5
R18
R46
R107A
R515A
R316A
R18A
IC40
3
D4
C21
R54
R55
R68
R69 R56
R90
C14
J4
R16
R52
J5
+LE
D1
R78
R142
R141
R155
R154
R153
R152
R151
R150
C3
R108
R107
RC2
RC4
RC1
RC3C1
FUSE1
65T 250V30A
ZR1
ZR2
CN30
R109
R58 R6
1
R60
R59
C301
C76
C312
R315
C83
C85
C86
C91
R156R158
R169
R170
R171
R172
I C34
D11
R157
R159
C310
C306
C308
C311 C3
07
C309
R110
E305
C302
+DZ301Q3
R75
R84
C103
CN28
CN29
CN6-1
CN6
CN13
CN12
CN2
CN8
CN7
CN22DR
CN21DR
R102
J6
PTC1
CN414
R127 C105
+
E5
IPM2
C501
C503
C507
C508
C509
C510
C511
C512
C517
+DZ501 R501
R502
R503
R504
R505
R506
R509
R510
R511
R512
R513R5
14
R523
C502
C505
+
DZ502
R515
R522
+
DZ50
4
C504
R316
~ ~
I NAC-
+
R101R100
R71
C42
CN20
RY5
CN16
CN18
NTC4
C8
C513
C514
C515
C516
R516R517
R518R519
R520
R521
C27
I C7 24LC512
3349
17
1
IC9
R53
IC10
1
R160
+
E4
+
E3
R83
R82R81
R80
R79
R50
C47
C20
R322R321R3
20Q2
I C405
+
E10
R120
R167
R166
R32
+
E1
R12 +LED3
R412
R413
R414
R415
Rdi
Ripm
R13
CN24
R72
R8
R87R74
J3
I C17
+
E24
D2
R124
C2
J2 J1
C77
ACAC
+-
BR1
C13
D3
R7
RY3
RY4
RY2
CN5
R23
R24
R25
R26
R27
C74
C75
RY1
+
E14 C9
C17
C18
C19
C23
C24
C26
C32
C33
C35
C36
C37
C39
C43
C48
C49
C52
C65
C67
C78
C87
C89
C90
C92
C147
C153
C25
CN9
CN23
CN39
+
E17
+
E23
+
E28
I C824LC08
I C1224LC08
I C14
+
LED2
OSC1
R5R30
R31
R40
R41
R42
R48
R49
R62
R64
R65
R66
R70
R73
R76R77
R86
R92
R97
R161
R162
R163
R164
R165
R176
R177
R419
X1
C58
+ +
E405
I C404
R45
Q1
C15
C22
R21
R22
R28
R29
R33
+
E22
R3R4
R121
C5
+E6
R10
C28
C4
CN38
I C10
C79
C80
D7
C6
R148
R63
C506
R507
R508
+
E11
R106C73
I C21 PC817
I C31PC817
R175
R178
C409
I C402
C403
I C11
+
E402
D401
C401 R40
3
C411
C40
C50
D403
R401
R405
R406
R404
+
E404
D402
D404
C408
C402
+
E403R407
R408
C404
C110
+
E409
+E401
R402
C405
10
9
7
65
4
3
1
T401
C406
C407
D13
D14
+
E406
+
E407
+
E408
+
E502
+
E503
+
E504
+
DZ50
3
CN25
R6R9
CN60
I C406
I C407
C7
D1
R1
R137
I C2PC851
I C1PC817
R2
R126R125
R123R122
R119
R118R117
R15
R14
C99
C98
C97
C96C95
C94
C93
C66
D20
R17
CN17
CN10
CN1
C41
R38
C45
C44
R136
R135
R134
R104
D12
D10
C54
+
D8
D9
R57
R20
C242
C243
C244
R89
E2
R67
C84
C10
C11
I C4
C12
C38
R34
R47R88
IC32
R39
R35
R36
R19
+
DZ6
R37
C46
C51
C53
CN19
+DZ2
+
E27
I C3 PC8
17
I C5PC817
Q8
R43
R44
R85
R91
R93
R95R96
R99
D15
R51
+E410
+
E8
C60
C61
E302
E303
E304 C62
VN1
VP1
U
P
VUB
U+
W
V+
VW+
U-
VVB
VWB
FO
W-V-
NVNW
NU
VNCCIN
I PM1
+DZ304
+ DZ303
+ DZ302 C314
C316
C318
C30
C34
C31
ZR3
ZR4
C82
L1
R11
R140
CN27
E301
R168
I GBT1
connect to the DR moduleconnect to earth
fuse 250V 30Aconnect to reactance
290-330VDC standby210-300VDC running
power supply 208-230V AC connect to the terminal
connect to 4-way val vewhen 4-way is on, output 208-230V AC
AC FAN mototr
connect to compressor heaterwhen heater is on, output 208-230V AC
1 low speed
2 hign speed
3 ground
external drive motorconnect to DC motor0V AC standby10~200V AC’ running
UVW
connect to electric expansion valve
6 5 4 3 2 1
+12VDC
+12VDC
+12V DC pulse wave between( +4)-GND
+12V DC pulse wave between( +3)-GND
+12V DC pulse wave between( +2)-GND
+12V DC pulse wave between( +1)-GND
EEPROM Programmer Port
reserve
test port
Connect to PCcommunication
V
U
W
connect to PC communication test port
LED: status light(yellow)
CN5/CN4 connect to chassis heaterwhen heater is on, output 208-230V AC
connect to DC motor
0V AC standby
10~200V AC’ running
bridge
IGBT
fast recovery diode(FRD)
IPM for compressor
IPM for DC FAN
reserve
P
N
-
After power on, LED3(Green color) and LED2(Red color) will be flash if the unit has some problems.
No. Problems LED3 (Green) LED2 (Red) IU display
1 standby for normal O X 2 Operation normally X O 3 IPM malfunction or IGBT over-strong current protection ☆ X P0
4 Over voltage or too low voltage protection O O P1
5 EEPROM parameter error O ☆ E5
6 Inverter compressor drive error X ☆ P4
7 Inverter compressor drive error ☆ O P4
8 Inverter compressor drive error ☆ ☆ P4
O(light) X(off) ☆(2.5Hz flash)
-
For CH-S30FTXW-SV, CH-S36FTXW-SV,
N L
SHOW/ SW
EARTH
[ 1. 4] 2014. 06. 26
EU- KFR105W/ BP3T5N1- 350S. D. 13. WP1- 1
L- OUT
N- OUT
CONNECT TO INVERTER driver
HIGH
LOW
T2B-E T2B-DT2B-C T2B-BT2B-A
TP
T4T3
S- E
S- D
S- C
S- B
S- AFAN_OUT
FAN_I NABCDE
202302141206
CN19
CN10
N
CN9
S
CN44
HEAT
2
CN43FAN
CN42 C
CN41
C
CN40
HEAT
1
CN34
CN33
CN30
CN29
CN28
CN27
CN26
CN22
4-WA
Y
CN20CN18 CN17
CN16
CN14
Comp
Top
CN12 CN11
CN8
CN6
CN5
CN4
N
CN3
N
CN2N- I N
CN1L- I N
CN23
CN7
CN13
P- 1
CN35
N
CN37FAN-L
CN36
FAN-
H
CN21
Electric ExpansionValue B
Electric ExpansionValue E
Electric ExpansionValue D
Electric ExpansionValue C
Electric ExpansionValue A
485communication
testPortconnect to detector external drive DC fan
motor input terminal
external drive DC fanmotor ouput terminal
current loopcommunication A
current loopcommunication B
current loopcommunication C
current loopcommunication D
current loopcommunication E
digital display
FuseT30A/250V
connect to high and lowpressure sensor
connect totrmp. sensor
Fuse 5A/250V
connect to earth
CN23 reserve
digital display button
test reportconnect to detector
CN43-5,CN43-1/CN41,CN42AC fan motor capacitorconnector
CN43-4/CN37 CONNECT TOAC FAN MOTOR(LOW SPEED)
CN43-3/CN36AC fan motor low speedconnectorCN43-2/CN35AV fan motor N phase
current loopcommunication C
Signal wire
24VDC Pulse wave
connect to the terminal
connect to the terminal
208-230V AC
power supply
room temp sensor
pipe temp sensor
(3.3V)
(3.3V)
high pressure sensor
low pressure sensor
Connect to the Indoor evap.pipeout temp. sensor
T2B-A、T2B-B、T2B-C、T2B-D、T2B-E
+12V
DC
puls
e wa
ve b
etwe
en (
+1)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+2)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+3)-
GND
+12V
DC
puls
e wa
ve b
etwe
en (
+4)-
GND
+12V
DC
+12V
DC
6 5 4 3 2 1
when 4-way is ON, output 208-230VACconnect to the 4-WAY
when heater is ON, output 208-230V AC
connect to compressor heater
CN44 LCN10 N
CN40 LCN4 N
CN22 LCN3 N
connect to exhausttemp. sensor
connect to the terminal
208-230V AC
external drive DC fanmotor connector
T3
T4
electricheater1
electricheater 2
-
IPM board,
202302141237
PFC-
L2
[ 1. 6] 2014. 10. 16
EU- KFR105W/ BP2T3N1- 350( 767) . D. 13. MP2- 1
PFC- L1 EARTH
+
CN55
TO-M
AIN
W
V
U
I PM2
I PM1
IC14
24C0
8
CN54L-I N2
N-IN
2
OUTF
AN(D
C)
I C1
CN53power suppl y
connect t o t he t er mi nal208- 230V AC
CN54CN51CN52
PFC
inductanceterminal
CN58EATTH
-+
210- 300VDC ( Runni ng)
CAPACI TOR Vol t age290- 330VDC ( st andby)
CN55TO MAI N
CN19
connect to DC fan motor
U
V
W
10- 200VAC ( r unni ng)0VAC ( st andby)
connect t o t he compr essor
U
V
W10- 200VAC ( r unni ng)0VAC ( st andby)
-
1.3 Diagnosis and Solution
1.3.1 EEPROM parameter error diagnosis and solution(E0/F4) Error Code E0/F4
Malfunction decision conditions
Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Supposed causes ● Installation mistake ● PCB faulty
Trouble shooting:
Yes
Replace the indoor/outdoor main PCB.
Power off, then restart the unit 2 minutes later.
EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos.
Indoor PCB Outdoor PCB
Note: The two photos above are only for reference, it’s may be not same totally with the ones on your side.
-
1.3.2 Indoor / outdoor unit’s communication diagnosis and solution(E1) Error Code E1
Malfunction decision conditions
Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.
Supposed causes ● Wiring mistake ● Indoor or outdoor PCB faulty
Trouble shooting:
Measure Vs. Is the voltage moving alternately between -25V to 25V?Measure Vs. Is the voltage moving alternately between -25V to 25V?
Yes
Power off, then restart the unit 2 minutes later. Is the error extinguished?
Power off, then restart the unit 2 minutes later. Is the error extinguished?
No
Replace the outdoor main PCB.Power on. Is the error
extinguished?
Replace the outdoor main PCB.Power on. Is the error
extinguished?
Check the outdoor wiring connection。Is the wiring correctly?
Check the outdoor wiring connection。Is the wiring correctly?
Replace the indoor main PCB.Power on. Is the error
extinguished?
Replace the indoor main PCB.Power on. Is the error
extinguished?
Yes
Replace the outdoor main PCB.Replace the outdoor main PCB.
No
Replace the indoor main PCB.Replace the indoor main PCB.
No
Check the indoor wiring connection。Is the wiring correctly?
Check the indoor wiring connection。Is the wiring correctly?
Yes
No
Check whether reactor is normal?Check whether reactor is normal?
Yes
Replace the reactorReplace the reactor No
-
Remark: Use a multimeter to test the DC voltage between 2 port and 3 port of outdoor unit. The red pin of multimeter connects with 2 port while the black pin is for 3 port. When AC is normal running, the voltage will move alternately between -25V to 25V. If the outdoor unit has malfunction, the voltage will move alternately with positive value. While if the indoor unit has malfunction, the voltage will be a certain value.
Remark: Use a multimeter to test the resistance of the reactor which does not connect with capacitor. The normal value should be around zero ohm. Otherwise, the reactor must have malfunction.
-
1.3.3 Zero crossing detection error diagnosis and solution (E2) Error Code E2
Malfunction decision conditions
When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.
Supposed causes ● Connection mistake ● PCB faulty
Trouble shooting:
Check if the connections and power supply is normal?
Correct the connections. Turn on the unit when the power supply is good.No
Yes
Indoor main PCB is defective. Replace indoor
main PCB.
-
1.3.4 Fan speed has been out of control diagnosis and solution(E3) Error Code E3/F5
Malfunction decision conditions
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.
Supposed causes ● Wiring mistake ● Fan ass’y faulty ● Fan motor faulty ● PCB faulty
Trouble shooting:
Power off, then restart the unit 2 minutes later
Shut off the power supply, Rotate the fan by hand.
The unit operates normally.
Find out the cause and have it solved
Check the wiring of fan motor
No
Yes
No
Correct the connections.No
NoReplace the fan motor
Yes
Yes
Measure the voltage for the fan motor from the main
PCB refer to the Appendix 1
Yes
Replace the main PCBNo
-
Index 1:
1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must has
problems and need to be replaced.
DC motor voltage input and output(voltage: 220-240V~)
NO. Color Signal Voltage 1 Red Vs/Vm 280V~380V 2 --- --- --- 3 Black GND 0V 4 White Vcc 14-17.5V 5 Yellow Vsp 0~5.6V 6 Blue FG 14-17.5V
DC motor voltage input and output(voltage :115V~)
NO. Color Signal Voltage 1 Red Vs/Vm 140V~190V 2 --- --- --- 3 Black GND 0V 4 White Vcc 14-17.5V 5 Yellow Vsp 0~5.6V 6 Blue FG 14-17.5V
2. Outdoor DC Fan Motor (control chip is in outdoor PCB)
Power on ,and check if the fan can run normally, if the fan can run normally, the PCB must has
problems and need to be replaced, If the fan can’t run normally, measure the resistance of each two
pins. If the resistance is not equal to each other, the fan motor must have problems and need to be
replaced, otherwise the PCB must has problems and need to be replaced.
3. Indoor AC Fan Motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds,
measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power
supply)or 50V(115V power supply), the PCB must has problems and need to be replaced.
-
1.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5) Error Code E4/E5/F1/F2/F3
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Supposed causes ● Wiring mistake ● Sensor faulty ● PCB faulty
Trouble shooting:
Check the connection between temperature
sensor and PCB.Correct the connectionNo
Yes
Replace indoor or outdoor main PCB
Measure the resistance value of the sensor Repalce the sensorNo
Yes
-
1.3.6 Refrigerant Leakage Detection diagnosis and solution(EC) Error Code EC
Malfunction decision conditions
Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 <Tcool-2°C(Tcool-35.6°F) does not keep continuous 4 seconds and this situation happens 3 times, the display area will show “EC” and AC will turn off.
Supposed causes ● T2 sensor faulty ● Indoor PCB faulty ● System problems, such as leakage or blocking.
Trouble shooting:
Is there cool air blowing out from indoor air outlet?
Yes
Yes
Check if T2 sensor is well fixed. Correct the installation or replace T2 sensor. Does the problem remain again?
No
Is there any leakage? Especially the connection parts, such as the gas valve and the liquid valve.
No
Shut off the power supply and turn it on 2 minutes later. Is it still displaying the error code?
Replace indoor PCB.
Yes
Repair the leakage and recharge the refrigerant.
Yes
Clear the blocking.
Yes
Is there any block i n g ? (Such as the capillary or the welded points of the pipes.)
-
1.3.6 Overload current protection diagnosis and solution(F0) Error Code F0
Malfunction decision conditions
An abnormal current rise is detected by checking the specified current detection circuit.
Supposed causes ● Power supply problems. ● System blockage ● PCB faulty ● Wiring mistake ● Compressor malfunction
Trouble shooting:
Check the power supply. Is it normal?
Check the connections and wires .Is it well connection?
Stop the unit. Check the power supplyNo
Yes
No Correct the connections or replace the wires.
Yes
Replace the outdoor main PCB
Yes
Check the reactor .Is it normal? No Replace the reactor
Is there any blocking?
No
Yes Clear the blockage
Check the compressor resistance values refer to the
[Compressor checking]. Is it normal?
Yes
No Replace the compressor
-
1.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0) Error Code P0
Malfunction decision conditions
When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes ● Wiring mistake ● IPM malfunction ● Outdoor fan ass’y faulty ● Compressor malfunction ● Outdoor PCB faulty
Trouble shooting: For 9K~24K:
Check if the wiring between main PCB and compressor . If the wires and connectors are broken?
Correct the connection or replace the wires and connectors.Yes
No
IPM continuity check. Check if the IPM terminal resistance values are uniform.
Replace the IPM board or replace the main PCB if the IPM board and main
PCB are integrated together.No
Check if the outdoor fan runs properly or the outdoor unit
ventilation is good.
Yes
No Please refer to the solution of 【Fan Speed Has Been Out Of Control】malfunction
Yes
Check if the compressor resistance values are uniform . No Replace the compressor.
Yes
Replace the outdoor main PCB if the main PCB and IPM are separate.
-
For example:
P-U
P-V
Note: The photos below are only for reference, it’s may be not same totally with the ones on your side.
-
P-W
N-U
-
N-V
N-W
-
For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below:
Yes
Check whether the power voltage is normal.
Check whether the power voltage is normal.
Measure whether outdoor terminal voltage is normal?
Measure whether outdoor terminal voltage is normal?
Restart the unit when the power supply gets normal
Restart the unit when the power supply gets normalNo
Yes
No Reconnect it wellReconnect it well
Yes
Measure whether the voltage between L and N is normal?Measure whether the voltage between L and N is normal?
Yes
Measure whether input voltage of bridge rectifier is normal?
Measure whether input voltage of bridge rectifier is normal?
No
No
Check the wiring of power wires well or
correctly
Check the wiring of power wires well or
correctly
Reconnect it wellReconnect it wellCheck the wiring of L and N well or correctlyCheck the wiring of L and N well or correctly
Reconnect it wellReconnect it well Check the wiring of
bridge rectifier well or correctly
Check the wiring of bridge rectifier well or
correctly
No
Yes
Replace the PFC module(If has)Replace the PFC module(If has)
No
Measure whether the voltage between P and N is normal
refer to the Appendix 4?
Measure whether the voltage between P and N is normal
refer to the Appendix 4?Replace the bridge rectifierReplace the bridge rectifierNoCheck whether bridge
rectifier is normalCheck whether bridge
rectifier is normal
Check the wiring of reactor or inductance
Check the wiring of reactor or inductance Reconnect the wiring Reconnect the wiring No
Check whether reactor or inductance is normal
Check whether reactor or inductance is normal
Yes
Replace reactor or inductance
Replace reactor or inductanceNo
Check whether the connecting wire between main board and the
IPM board is connected tightly
Check whether the connecting wire between main board and the
IPM board is connected tightlyReconnect it wellReconnect it wellNo
Check if the outdoor unit ventilation is good
Check if the outdoor unit ventilation is good
Yes
Make the outdoor unit ventilate wellMake the outdoor unit ventilate well
Check whether the refrigerant system is okCheck whether the refrigerant system is ok
No
Check if the outdoor fan runs properly
Check if the outdoor fan runs properly
please refer to the solution of [fan speed has been out of control malfunction] . Find out the cause and have it solved.
please refer to the solution of [fan speed has been out of control malfunction] . Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is normal
Check the compress is normal
Yes
Replace the compressorReplace the compressorNo
Replace IPM board Replace IPM board
Replace the outdoor main PCB Replace the outdoor main PCB
No
Check whether the connecting wire of the compressor is
connected correctly or tightly
Check whether the connecting wire of the compressor is
connected correctly or tightlyReconnect it wellReconnect it wellNo
Yes
Yes
-
1.3.8 Over voltage or too low voltage protection diagnosis and solution(P1) Error Code P1
Malfunction decision conditions
An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Supposed causes ● Power supply problems. ● System leakage or block ● PCB faulty
Trouble shooting:
Check the power supply
Check the connections and wires
Stop the unitNo
Yes
No Correct the connections or replace the wires.
Yes
Replace the reactor
Yes
No Replace the IPM board Check the voltage between P
and N
Check the reactor
Yes
No Replace outdoor main PCB
Remark: Measure the DC voltage between P and N port. The normal value should be around 310V.
P N
-
1.3.9 High temperature protection of IPM module or compressor top diagnosis and solution(P2) Error Code P2
Malfunction decision conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes ● Installation mistake ● Power supply problems. ● System leakage or block ● PCB faulty
Trouble shooting: For 18K,24K,
Yes
Tighten the screws and apply silicon grease.
Tighten the screws and apply silicon grease.
Replace the outdoor control PCB.Replace the outdoor control PCB.
No
Check if the Fastening screws on the PCB and IPM radiator
are fixed tightly.
For other models,
Check if the air flow system of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat exchanger of indoor and outdoor units.Yes
No
Yes
Yes
Turn off the power supply and turn it on 10 minutes later.
Check if the temperature of compressor Top
Is more than 90℃?No
Check if the refrigerant system
is normal?
Repair the refrigerant system .Replace the outdoor control PCB.
Yes
Check if all the connection, especially the connection of OLP (Over Load
Protector) sensor is good.Correct the connection.No
Measure the resistance between the two ports of the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.YesNo
-
1.3.10 Inverter compressor drive error diagnosis and solution(P4) Error Code P4
Malfunction decision conditions
An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
Supposed causes ● Wiring mistake ● IPM malfunction ● Outdoor fan ass’y faulty ● Compressor malfunction ● Outdoor PCB faulty
Trouble shooting: For 9K~24K:
Check if the wiring between main PCB and compressor connected well?
Correct the connection or replace the wires and
connectors.No
Check if the IPM installed correctly.Correct the installation, tighten the screws and apply silicon grease.
No
IPM continuity check. Check if the IPM terminal resistance values are uniform.
Yes
Replace the IPM board or replace the main PCB if the IPM board and main PCB are integrated together.
No
Check if the outdoor fan runs properly or the outdoor unit
ventilation is good.
Yes
NoPlease refer to the solution of 【Fan Speed Has Been Out Of Control】
malfunction
Yes
Check if the compressor resistance values are uniform . No Replace the compressor.
Yes
Replace the outdoor main PCB if the main PCB and IPM are separate.
Check the reactor or Inductance .Is it normal? No
Replace the reactor or Inductance
Yes
Yes
IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.
-
Digital tester Normal resistance value Digital tester Normal resistance value (+)Red (-)Black
∞ (Several MΩ)
(+)Red (-)Black
∞ (Several MΩ) P
N U
N U V V W W (+)Red
For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below:
Yes
Check whether the power voltage is normal.
Check whether the power voltage is normal.
Measure whether outdoor terminal voltage is normal?
Measure whether outdoor terminal voltage is normal?
Restart the unit when the power supply gets normal
Restart the unit when the power supply gets normalNo
Yes
No Reconnect it wellReconnect it well
Yes
Measure whether the voltage between L and N is normal?Measure whether the voltage between L and N is normal?
Yes
Measure whether input voltage of bridge rectifier is normal?
Measure whether input voltage of bridge rectifier is normal?
No
No
Check the wiring of power wires well or
correctly
Check the wiring of power wires well or
correctly
Reconnect it wellReconnect it wellCheck the wiring of L and N well or correctlyCheck the wiring of L and N well or correctly
Reconnect it wellReconnect it well Check the wiring of
bridge rectifier well or correctly
Check the wiring of bridge rectifier well or
correctly
No
Yes
Replace the PFC module(If has)Replace the PFC module(If has)
No
Measure whether the voltage between P and N is normal
refer to the Appendix 4?
Measure whether the voltage between P and N is normal
refer to the Appendix 4?Replace the bridge rectifierReplace the bridge rectifierNoCheck whether bridge
rectifier is normalCheck whether bridge
rectifier is normal
Check the wiring of reactor or inductance
Check the wiring of reactor or inductance Reconnect the wiring Reconnect the wiring No
Check whether reactor or inductance is normal
Check whether reactor or inductance is normal
Yes
Replace reactor or inductance
Replace reactor or inductanceNo
Check whether the connecting wire between main board and the
IPM board is connected tightly
Check whether the connecting wire between main board and the
IPM board is connected tightlyReconnect it wellReconnect it wellNo
Check if the outdoor unit ventilation is good
Check if the outdoor unit ventilation is good
Yes
Make the outdoor unit ventilate wellMake the outdoor unit ventilate well
Check whether the refrigerant system is okCheck whether the refrigerant system is ok
No
Check if the outdoor fan runs properly
Check if the outdoor fan runs properly
please refer to the solution of [fan speed has been out of control malfunction] . Find out the cause and have it solved.
please refer to the solution of [fan speed has been out of control malfunction] . Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is normal
Check the compress is normal
Yes
Replace the compressorReplace the compressorNo
Replace IPM board Replace IPM board
Replace the outdoor main PCB Replace the outdoor main PCB
No
Check whether the connecting wire of the compressor is
connected correctly or tightly
Check whether the connecting wire of the compressor is
connected correctly or tightlyReconnect it wellReconnect it wellNo
Yes
Yes
-
1.3.11 Low pressure protection diagnosis and solution(P6) Error Code P6
Malfunction decision conditions
When the pressure of system reach a certain value, the low pressure protector will switch off. After the pressure resume to normal ,the protection code will disappear.
Supposed causes ● Wiring mistake ● Pressure protector faulty ● Fan motor faulty ● PCB faulty ● System problems.
Trouble shooting:
Whether the wiring between the low pressure protector and main control board is connected well or
correctly
Whether the wiring between the low pressure protector and main control board is connected well or
correctly
Method: Disconnect the plug. Measure the
resistance of the low pressure protector. If the
protector is normal the value is o
Method: Disconnect the plug. Measure the
resistance of the low pressure protector. If the
protector is normal the value is o
Yes
Yes
Connect it wellConnect it well
Replace outdoor main boardReplace outdoor main board
No
Replace low pressure protectorReplace low pressure protectorNo
Whether the low pressure protector
is broken
Whether the low pressure protector
is broken
Check whether the outdoor ambient temperature is too
low
Check whether the outdoor ambient temperature is too
low
No
Stop the unit Stop the unit Yes
Open fully valve core of high pressure valve
Open fully valve core of high pressure valveNo
Check whether valve core of high pressure valve is
opened
Check whether valve core of high pressure valve is
opened
Check if the indoor fan runs properly in cooling mode
Check if the indoor fan runs properly in cooling mode
please refer to the solution of [fan speed has been out of control
malfunction]. Find out the cause and have it solved.
please refer to the solution of [fan speed has been out of control
malfunction]. Find out the cause and have it solved.
No
Yes
Yes
No
Check whether the refrigerant system is ok
Check whether the refrigerant system is ok
Refrigerant is not enough add the refrigerant
Refrigerant is not enough add the refrigerant
No
-
Main parts check 1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Temperature sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(TP) sensor. Measure the resistance value of each winding by using the multi-meter.
-
Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (°C--K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm -20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
-
Appendix 2 Temperature Sensor Resistance Value Table for TP (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.717
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849
12 54 99.69 52 126 18.26 92 198 4.703
13 55 95.05 53 127 17.58 93 199 4.562
14 57 90.66 54 129 16.94 94 201 4.426
15 59 86.49 55 131 16.32 95 203 4.294
16 61 82.54 56 133 15.73 96 205 4.167
17 63 78.79 57 135 15.16 97 207 4.045
18 64 75.24 58 136 14.62 98 208 3.927
19 66 71.86 59 138 14.09 99 210 3.812
-
Appendix 3:
ΔT(℉) =9ΔT(℃)
5 °C °F °C °F °C °F °C °F °C °F
-5 23 21 69.8 51 123.8 82 179.6 113 235.4 -4 24.8 22 71.6 52 125.6 83 181.4 114 237.2 -3 26.6 23 73.4 53 127.4 84 183.2 115 239 -2 28.4 24 75.2 54 129.2 85 185 116 240.8 -1 30.2 25 77 55 131 86 186.8 117 242.6 0 32 25.5 77.9 56 132.8 87 188.6 118 244.4
0.5 32.9 26 78.8 57 134.6 88 190.4 119 246.2 1 33.8 27 80.6 58 136.4 89 192.2 120 248
1.5 34.7 28 82.4 59 138.2 90 194 121 249.8 2 35.6 29 84.2 60 140 91 195.8 122 251.6
2.5 36.5 30 86 61 141.8 92 197.6 123 253.4 3 37.4 31 87.8 62 143.6 93 199.4 124 255.2
3.5 38.3 32 89.6 63 145.4 94 201.2 125 257 4 39.2 33 91.4 64 147.2 95 203 126 258.8
4.5 40.1 34 93.2 65 149 96 204.8 127 260.6 5 41 35 95 66 150.8 97 206.6 128 262.4 6 42.8 36 96.8 67 152.6 98 208.4 129 264.2 7 44.6 37 98.6 68 154.4 99 210.2 130 266 8 46.4 38 100.4 69 156.2 100 212 131 267.8 9 48.2 39 102.2 70 158 101 213.8 132 269.6
10 50 40 104 71 159.8 102 215.6 133 271.4 11 51.8 41 105.8 72 161.6 103 217.4 134 273.2 12 53.6 42 107.6 73 163.4 104 219.2 135 275 13 55.4 43 109.4 74 165.2 105 221 136 276.8 14 57.2 44 111.2 75 167 106 222.8 137 278.6 15 59 45 113 76 168.8 107 224.6 138 280.4 16 60.8 46 114.8 77 170.6 108 226.4 139 282.2 17 62.6 47 116.6 78 172.4 109 228.2 140 284 18 64.4 48 118.4 79 174.2 110 230 141 285.8 19 66.2 49 120.2 80 176 111 231.8 142 287.6 20 68 50 122 81 177.8 112 233.6 143 289.4
-
Appendix 4
1. Normal voltage of P and N
208-240V(1-phase,3-phase) 380-420V(3-phase) In standby
around 310VDC around 530VDC In operation
With passive PFC module
With partial active PFC
module
With fully active PFC module /
>200VDC >310VDC >370VDC >450VDC
-
2. Compressor checking Measure the resistance value of each winding by using the tester.
Position Resistance Value
ASN98D22UFZ ASM135D23UFZ ATF235D22UMT ATF250D22UMT Blue - Red
1.57Ω
1.75 Ω
0.75 Ω
0.75 Ω
Blue - Black
Red - Blue
-
3. Fan Motor Measure the resistance value of each winding by using the tester.
Model YKT-32-6-202L
YKT-32-6-3L
YKT-48-6-206
YKT-63-6-200L
Brand Tongde Welling Welling Welling Black –
Red Main
Ω 86 213 152 88.5
Blue –Black
AUX
Ω 64 156 142 138
-
4. Pressure On Service Port Cooling chart:
°F(°C) ODT IDT 75
(23.89) 85
(29.44) 95
(35) 105
(40.56) 115
(46.11) BAR 70/59 8.2 7.8 8.1 8.6 10.1 BAR 75/63 8.6 8.3 8.7 9.1 10.7 BAR 80/67 9.3 8.9 9.1 9.6 11.2
°F(°C) ODT IDT
75 (23.89)
85 (29.44)
95 (35)
105 (40.56)
115 (46.11)
PSI 70/59 119 113 117 125 147 PSI 75/63 124 120 126 132 155 PSI 80/67 135 129 132 140 162
°F(°C) ODT IDT
75 (23.89)
85 (29.44)
95 (35)
105 (40.56)
115 (46.11)
MPA 70/59 0.82 0.78 0.81 0.86 1.01 MPA 75/63 0.86 0.83 0.87 0.91 1.07 MPA 80/67 0.93 0.89 0.91 0.96 1.12
0,0
2,0
4,0
6,0
8,0
10,0
12,0
75 (23.89) 85 (29.44) 95 (35) 105 (40.56) 115 (46.11)
70/59
75/63
80/67
-
Heating Chart: °F (°C)
ODT IDT
57/53 (13.89/11.67)
47/43 (8.33/6.11)
37/33 (2.78/0.56)
27/23 (-2.78/-5)
17/13 (-8.33/-10.56)
BAR 55 30.3 28.5 25.3 22.8 20.8 BAR 65 32.5 30.0 26.6 25.4 23.3 BAR 75 33.8 31.5 27.8 26.3 24.9
°F (°C)
ODT IDT
57/53 (13.89/11.67)
47/43 (8.33/6.11)
37/33 (2.78/0.56)
27/23 (-2.78/-5)
17/13 (-8.33/-10.56)
PSI 55 439 413 367 330 302 PSI 65 471 435 386 368 339 PSI 75 489 457 403 381 362
°F (°C)
ODT IDT
57/53 (13.89/11.67)
47/43 (8.33/6.11)
37/33 (2.78/0.56)
27/23 (-2.78/-5)
17/13 (-8.33/-10.56)
MPA 55 3.03 2.85 2.53 2.28 2.08 MPA 65 3.25 3.00 2.66 2.54 2.33 MPA 75 3.38 3.15 2.78 2.63 2.49
2. Disassembly Instructions Note: This part is for reference, the photos may have slight difference with your machine.
2.1 Indoor unit
No. Parts name Procedures Remarks
0,0
5,0
10,0
15,0
20,0
25,0
30,0
35,0
40,0
57/53 (13.89/11.67)
47/43 (8.33/6.11)
37/33 (2.78/0.56)
27/23(-2.78/-5)
17/13(-8.33/-10.56)
55
65
75
-
1 Front panel How to remove the front panel.
1) Pull the below side of
the panel toward you and
remove screw of the cover.
2) Release the connector of
the display ass’y.
3) Release the two clips and
then remove the panel.
4) Remove the filter and the
horizontal louver.
5) Remove the three screws
and then remove the panel
ass’y.
①1 screw
②
⑤
-
2 Electrical parts
How to remove the electrical
parts.
1) Remove the front
panel from procedure 1.
2) Pull out the room temp.
sensor (T1). Remove the two
screws for the ground
connection.
3) Remove the fixing screw.
4) Pull out the coil temp.
sensor.
5) From the side direction,
open the electronic control box
cover fixing by clips. Pull out
the fan motor connector and
swing motor connector. Then
remove the electronic control
box.
②
③
④
⑤
1.1 Indoor Unit Error Display1.2 Outdoor unit error display(TBD)1.3 Diagnosis and Solution2. Disassembly Instructions2.1 Indoor unit