solution feb. 15. 2007 samsung electronics. 1. solution lineup 2. wired remote controller 3. 7-day...
TRANSCRIPT
Solution
Feb. 15. 2007
Samsung Electronics
1. Solution Lineup
2. Wired remote controller
3. 7-day scheduler
4. Interface module
5. Centralized control
6. Power distribution
7. DMS
8. S-Net 2 Plus
9. S-Net I
10. S-Net 3
11. S-Net mini
INDEXINDEX
3 / 84
Solution LineupSolution Lineup1.1.
System A/C Wired R/CI/MCentralizedA/C Control
GHP
ERV Domestic
BAC
FJM
Mini DVM
DVM
DVM Plus
DVM Plus II
MWR-TH01
MWR-BS00
MWR-WS00
MIM-B04A
MIM-B02
MIM-B13
MIM-B07
S-Net mini
MCM-B102
MIM-B12
MCM-A202
MCM-A100
S-Net mini
MIM-B06
MWR-BS00
MST-S1P
MIM-D00
MST-P3P
MST-P1W0
S-Net mini
4 / 84
Wired remote controllerWired remote controller2.2.
■ Features
FeaturesModel
Support COM 1 and COM 2 wiring RMC address assignment
Only support COM 2 wiring Support 2400 / 9600 bps Newly designed Sleep mode, Silent mode, Child lock Real time clock & 7-day schedule function Temperature sensor Service mode (Additional functions)
- Indoor unit option code setting function etc.
Image
MWR-TH01
MWR-WS00
5 / 84
■ Communication channel
N YInstall on COM 1 Install on COM 2
Dose the outdoorunit support thePLUS protocol?
Wired remote controllerWired remote controller2.2.
■ Connection units
COM 1 Wiring
■ Connection units
COM 2 Wiring
– Outdoor unit– Indoor units– Interface module (Key-tag, Lonworks, 485)– Wired remote controller– Power distribution unit
– Indoor units– Wired remote controller– 7-day scheduler
■ Old error display (Er XX) ■ Error code display (E XXX)
6 / 84
COM 2 wiring
COM 1 wiring12VDC for wiredRemote controller
■ Terminal block on the indoor unit
Wired remote controllerWired remote controller2.2.
7 / 84
■ COM 1 wiring of wired remote controller
Terminal Block
WhiteBlack
Red
Blue
12VDC Power Supply
Communication Line
Wired Remote Control
(MWR-TH01)
Wired remote controllerWired remote controller2.2.
Only CAC non-inverter model supports COM 1 wiring.
8 / 84
■ COM 1 wiring of wired remote controller
Wired remote controllerWired remote controller2.2.
Outdoor Unit
MWR-TH01
Main 0RMC 0 RMC 2RMC 1
Main 1 Main 2
RMC 1 RMC 2RMC 0
RMC AddressMain Address
Wired R/C Enable/DisableI/M Enable/Disable
Indoor Unit Option Setting
9 / 84
■ COM 2 wiring of wired remote controller
Terminal Block
White
Black
RedBlue
12VDC Power Supply
Communication Line(Non-polarity)
Wired Remote Control
(MWR-TH01 / WS00)
Wired remote controllerWired remote controller2.2.
10 / 84
■ Option switch setting (MWR-TH01)
SW No Off On Default
SW 1 Cooling only Cooling and heating On
SW 2 COM 2 Wiring (F3 / F4) COM 1 Wiring (F1 / F2) Off
SW 3 Celsius (C) display Fahrenheit (F) display Off
SW 4Wireless remote controller also available
Only wired remote controller can be used
Off
SW 5 Assign RMC (Group) address with wired remote controller Off
DS01
DS02DS03
Address switch
DS01 DS02
SW1 SW8SW5SW4
Wired remote controllerWired remote controller2.2.
SW 2 Off (COM 2) On (COM 1)
Address switch0 : Master Matches with Indoor
unit RMC addressOthers : Slave
11 / 84
Wired remote controllerWired remote controller2.2.
■ Assign RMC address (MWR-TH01 COM 2 wiring)
SW 5 ‘OFF’ – Set SW 5 of DS02 switch on the wired remote controller PCB to ‘OFF’.
– Press the ‘Mode’ button and ‘Fan speed’ button in front of the wired remote control simultaneously for more than 5 seconds.
– Adjust RMC address using “Up” and “Down” buttons.
Change confirm
Operation mode
– Press the “Operation” button to select the required group address. Then, the group address display flickers and changes.
– Press the button once to set the selected group address with the ‘beep’ sound.
– Wired remote controller LCD displays main address and RMC (Group) address and changes to the “Indoor unit group address setting mode”.
– Press the button again to quit the setting mode and enter the operation mode.
Enter ‘Group address setting
mode’
Change RMC
RMC change
12 / 84
■ Option switch setting (MWR-WS00)
SW No Off On Default
SW 1 Cooling and heating Cooling only Off
SW 2Wireless remote controller also available
Only wired remote controller can be used
Off
SW 3 Master Slave Off
SW 4 Celsius (C) display Fahrenheit (F) display Off
SW 5 Use indoor unit temperature sensorUse wired remote controller temperature sensor
Off
SW 6 -Use the average of indoor unit and wired remote controller temperature sensor
Off
SW 7 - - Off
SW 8 Service mode monitor Service mode setup Off
Wired remote controllerWired remote controller2.2.
– After adding / removing indoor units or indoor unit PCB change, press the “Set” button and “Cancel” button simultaneously for 5 seconds.
13 / 84
Wired remote controllerWired remote controller2.2.
■ Service mode (MWR-WS00)
Menu Description
1 Monitoring and setting the indoor unit option code
2 Monitoring and setting the indoor unit RMC address
3 Monitoring the indoor unit cycle data
4 Setting the indoor unit temperature sensor compensation
5 Setting the fan RPM compensation
6 Setting the EEV step when the indoor unit is off in heating mode
7 Setting the filter time
8 Setting the heating capacity compensation
9 Checking the indoor unit centralized control switch setting
10 Checking the indoor unit drain pump switch setting
11 Checking the indoor unit electric heater switch setting
12 Checking the indoor unit hot water heater switch setting
13 Checking the number of connected indoor units (April. 2007)
14 Checking the program version of wired remote controller (April. 2007)
– If the option switch SW8 is set to ‘OFF’, the above service modes can be only monitored. Set the option switch SW8 to ‘ON’ to set the above service modes.
14 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-TH01
Address Switch 0
DIP Switch SW2 Off
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-WS00
DIP Switch SW3 Off
■ COM 2 basic wiring
Wired remote controllerWired remote controller2.2. Check List
15 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-TH01 (Master)
Address Switch 0
DIP Switch SW2 Off
MWR-TH01 (Slave)
Address Switch Except 0
DIP Switch SW2 Off
MWR-WS00 (Master)
DIP Switch SW3 Off
MWR-WS00 (Slave)
DIP Switch SW3 On
Max 2 Wired remote controller
■ 2 Wired remote controller wiring
Wired remote controllerWired remote controller2.2. Check List
16 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-TH01
Address Switch 0
DIP Switch SW2 Off
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-WS00
DIP Switch SW3 Off
Max 16 Indoor units
■ Group control using wired remote controller
Wired remote controllerWired remote controller2.2. Check List
17 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
Max 16 Indoor units
MWR-TH01 (Master)
Address Switch 0
DIP Switch SW2 Off
MWR-TH01 (Slave)
Address Switch Except 0
DIP Switch SW2 Off
MWR-WS00 (Master)
DIP Switch SW3 Off
MWR-WS00 (Slave)
DIP Switch SW3 On
Max 2 Wired remote controller
■ Group control using 2 wired remote controllers
Wired remote controllerWired remote controller2.2. Check List
18 / 84
■ Features
7-day scheduler7-day scheduler3.3.
FeaturesModel
Weekly schedule for 1 or 16 groups Can interface with wired remote controller
or centralized controller Can skip schedule on specified date
Image
MWR-BS00
With MWR-TH00 / MWR-TH01 With MCM-A201
– Connects to COM 2 wiring (F3 / F4)
– Connects to R1 / R2 communication port– Does not support individual group schedules– Controls all indoor units under centralized controller
19 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-TH01 (Master)
Address Switch 0
DIP Switch SW2 Off
MWR-BS00 (Slave)
SW 2 On : Disable the On/Off button on the wired remote controller
■ Wired remote controller / 7-day scheduler
7-day scheduler7-day scheduler3.3. Check List
20 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
Max 16 Indoor units
MWR-TH01 (Master)
Address Switch 0
DIP Switch SW2 Off
MWR-BS00 (Slave)
SW 2 On : Disable the On/Off button on the wired remote controller
■ Wired remote controller / 7-day scheduler (Group control)
7-day scheduler7-day scheduler3.3. Check List
21 / 84
Indoor Unit
RMC Address Anything OK
DIP Switch K1 Anything OK
MWR-TH01 (Master)
Address Switch 0
DIP Switch SW2 Off
MWR-BS00
SW 2 On : Disable the On/Off button on the wired remote controller
MWR-TH01 (Slave)
Address Switch Except 0
DIP Switch SW2 Off
■ 2 Wired remote controller / 7-day scheduler
7-day scheduler7-day scheduler3.3. Check List
22 / 84
Max 16 Interface modules
MCM-A201MIM-B04
Address 0
DIP Switch K1 On
Outdoor Unit
■ Centralized control using 7-day scheduler
7-day scheduler7-day scheduler3.3.
In case of mini-DVM & DVM Plus II, this combination is impossible .
Max 16 Interface modules
MWR-BS00
MCM-A100
MIM-B04
Address 0
DIP Switch K1 On
Outdoor Unit
Check List
23 / 84
■ Features
Interface moduleInterface module4.4.
FeaturesModel
485 communication interface module 2400 / 9600 bps auto detection BAC, DVM, FJM, DVM Plus series
485 communication interface module 2400 / 9600 bps auto detection Support earlier version include DVM Plus II
Image
MIM-B04A
MIM-B13
MIM-B02
MIM-B07
Key-tag interface module Be used in hotel where the A/C need
to turn off if vacant
Lonworks interface module BMS connection using Lonworks protocol
24 / 84
Interface moduleInterface module4.4.
■ Key-tag interface module (MIM-B02)
– BeBe widely used in hotels where the A/C needs to turn off if vacant.– CCan be used with the 485 interface module simultaneously only on selected outdoor units. (RVMH060GDM3, RVMH100GCM3, RVMR100GCM0)– From DVM Plus II Indoor units, MIM-B14 (External control interface module) has the Key-Tag function.
If two indoor units are installed in the room
Wire according to the main address of the indoor unit.
If only one indoor unitis installed in the room
MIM-B14
25 / 84
■ Key-tag I/M Option switch setting (MIM-B02)
SW No Off On
SW 1 Normal close contact (B type) Normal open contact (A type)
SW 2 Address D4 (with 485 I/M) Address D0
SW 3 External control (On/Off control) Key-tag control (Off Control)
SW 4 Enable initial event control Disable initial event control
Interface moduleInterface module4.4.
– Only available in external control mode ( SW 3 Off )– This function is used for indoor units without breakout recovery function.
– If power reset occurs, an event signal is generated to recover operation status of indoor unit after checking the external contact status.– If the indoor units were ON before power reset, an event signal is generated to turn on the indoor units after power reset. If the indoor units OFF before power reset, they remain OFF after power reset.
Initial event control
26 / 84
Off Control
by contact status
ON
1 2 3 4
DS01
ON
1 2 3 4
DS01
Contact Status
Command
Indoor Operation
HIGH(SHORT)
LOW(OPEN)
Working Working Stop Stop
On event by other controller
OFF Command OFF Command
Contact Status
Command
Indoor Operation
HIGH(SHORT)
LOW(OPEN)
Working Working Stop Stop
On event by other controller
OFF Command
OFF Command
■ Key-tag interface function
Interface moduleInterface module4.4.
27 / 84
On/Off Control by contact status
Contact Status
Command
Indoor Operation
HIGH(SHORT)
LOW(OPEN)
ON Command
OFF Command
ON Command
Working
Stop Stop Working
Off event by other controller
Power In
Contact Status
Command
Indoor Operation
HIGH(SHORT) LOW(OPEN)
ON Command
OFF Command
ON Command
Working Stop Stop Working
Off event by other controller
Power In
ON
1 2 3 4
DS01
ON
1 2 3 4
DS01
■ Key-tag interface function
Interface moduleInterface module4.4.
28 / 84
Interface moduleInterface module4.4.
■ Key-tag interface module wiring
Outdoor Unit
Samsung Scope
Central monitoring panel
Key rack Room management system (RMS)Floor I/M
MIM-B02
DIP Switch K2 On
Indoor units
Main Address Manual
DIP Switch K2 Anything OK
Max 16 Indoor units
Check List
29 / 84
Samsung Scope
MIM-B02
DIP Switch K2 Off
Max 16 Indoor units
MIM-B04A
Address Anything OK
DIP Switch K1 On
MCM-A202
■ Key-tag interface module / Centralized controller
Central monitoring panel
Key rack Room management system (RMS)Floor I/M
Interface moduleInterface module4.4.
Indoor units
Main Address Manual
DIP Switch K2 Off
RVMH060GDM3, RVMH100GCM3, RVMR100GCM0
Check List
30 / 84
■ External control interface module
Interface moduleInterface module4.4.
MIM-B14
DB93-04159A External Control PBA
DB39-01263A Cable for timer input
DB39-01264A Cable for output
– Control indoor unit by “External contact signal”. (Switch, Timer etc.)– Display “Compressor operation and error status”.– Set DIP switch K11 to “Off” on the indoor unit’s PCS.
– Note 1. Operation is as same as last operation status. (At first , “Auto mode, Set temp. 24 , Auto airflow”)℃ 2. Impossible to connect with wall mounted Indoor units. (Vivace, Prestige, Premium)
Wire No. Description
1, 2 Error check
3, 4 Comp. operation Check
5, 6 Input signal
31 / 84
Interface moduleInterface module4.4.
DB39-01263A
CN83
Signal with power
ExternalSignal
External Signal
Operation
Relay
■ External control interface module (Direct connection)
PCB of duct type indoor unit
DIP S/W K11 : Off
Check List
32 / 84
Interface moduleInterface module4.4.
MIM-B14(DB93-04159A)
DB39-01263A
Off DelayTimer Relay
Power
PushButtonSwitch
Supplied by installer
External Signal
Operation
Timer setting
DB39-01264A
DIP S/W K11 : Off
CN83 CN81
■ External control interface module (Timer Delay)
Check List
33 / 84
■ Lonworks interface module (MIM-B07)
Interface moduleInterface module4.4.
MIM-B07 is used to manage DVM air conditioner with other devices using one of BMS open protocol Lonworks.
Function Item Description
Control
On/Off control Run or stop indoor unit
Operation mode Set operation mode (Auto / Cool / Heat / Fan mode)
Setting temperature Set target temperature (Cool : 18~30 C, Heat : 16~30 C)
Fan speed Set fan speed (Auto / Low / Mid / High)
Monitoring
Running status Monitor indoor unit running status (Run / Stop)
Operation mode Monitor operation mode (Auto / Cool / Heat / Fan mode)
Room temperature Monitor current room temperature
Error status Monitor error status (Error code)
34 / 84
■ Lonworks interface module (MIM-B07)
Interface moduleInterface module4.4.
• Lonworks Interface Module
• Model Code : MIM-B07
• CPU : Neuron 3150 Smart Transceiver
• Communication : RS485 to FTT-10A
FTT-10A 78Kbps
Free topology
• Service Pin : Auto-binding
• Power Input : DC 12V
• Size : 50mm x 80mm
• Parallel connection (4 units)
• Lonworks Interface Module
• Model Code : MIM-B07
• CPU : Neuron 3150 Smart Transceiver
• Communication : RS485 to FTT-10A
FTT-10A 78Kbps
Free topology
• Service Pin : Auto-binding
• Power Input : DC 12V
• Size : 50mm x 80mm
• Parallel connection (4 units)
Neuron Chip Transceiver
35 / 84
■ SNVT (Standard Network Variable Type) Configuration
Interface moduleInterface module4.4.
DVMIndoor[12]
nviFanSpeed
nviIndoorMode
nviSetTemp
nvoIndoorStatus
nvoRoomTemp
No NV Name Index NV Type Description
1 nviIndoorMode[12] 2~13 SNVT_hvac_mode On/Off & operation mode
2 nviSetTemp[12] 14~25 SNVT_temp_f Setting temperature
3 nviFanSpeed[12] 26~37 SNVT_Switch Fan speed
4 nvoIndoorStatus[12] 38~49 SNVT_hvac_Status On/Off, Mode, Error Monitoring
5 nvoRoomTemp[12] 50~61 SNVT_temp_f Current room temperature
36 / 84
■ SNVT (Standard Network Variable Type) Configuration
Interface moduleInterface module4.4.
SNVT_hvac_mode Operation
HVAC_OFF Stop
HVAC_AUTO Auto mode
HVAC_COOL Cooling mode
HVAC_HEAT Heating mode
HVAC_FAN_ONLY Fan mode
Value Operation
0 (Default) Auto
1 Low
2 Mid
3 High
nviIndoorMode nviFanSpeed
Field Type Description
mode Hvac_t Control mode
heat_output_primary Signed long Indoor unit address
fan_output Signed long Error code
in_alarm Unsigned short Error status (True / False)
nviIndoorStatus
37 / 84
– Function
1) “A” : Service Pin – Use Binding with other Lonworks I/M.
2) “B” : RS485 Comm. connector with DVM Outdoor and indoors.
3) “C” : Power connector (12VDC) from Outdoor units.
4) “D” : Terminal block for FTT-10A (Twisted Pair).
Display Status Action
Off Normal
Flickering Un-Configured Need re-commission
On Application Less Need program download
– Test using LED
1) D3(Service Pin LED) : Turn on when pushing service pin
2) D4 (Command Status LED) : Command receive on Network (0.2s)
3) D5 (RS485 Tx) : Flicking when data send on RS485 comm. Line (0.06s)
4) D6 (RS485 Rx) : Flicking when data receive on RS485 comm. Line (0.06s)
■ MIM-B07 Installation test
Interface moduleInterface module4.4.
A
C
D
B
D3
D4
D5D6
E
38 / 84
Outdoor Unit
Samsung Scope
MMI
Indoor units
Main Address Manual
DIP Switch K2 Off
Max 12 Indoor units
Lonworks Twisted PairLonworks
BMS SYSTEMBMS SYSTEM
Lon to TPC/IPRouter
Ethernet
Workstation Client 1 Client 2
PowerPower
EquipmentEquipment
EntranceEntrance
LightLight
MIM-B07
Address 0
■ Lonworks interface module wiring
Interface moduleInterface module4.4. Check List
39 / 84
Outdoor Unit
Samsung Scope
Indoor units
Main Address Manual
RMC Address Anything OK
DIP Switch K2 Off
Max 48 Indoor unitsMax 4 Lonworks interface modules
MIM-B07
Address 0
MIM-B07
Address 1
MIM-B07
Address 2
MIM-B07
Address 3
MMI
Lonworks Twisted PairLonworks
■ Lonworks I/M wiring (More than 12 indoor units)
Interface moduleInterface module4.4.
Power source : Install maximum 2 I/M from each outdoor module
Check List
40 / 84
■ Features
FeaturesModel
Use with 7-day scheduler BAC, DVM, FJM, DVM Plus series
High speed communication version Use with 7-day scheduler Support earlier version include DVM Plus II
Image
MCM-A201
Centralized controlCentralized control5.5.
MCM-A202
Used with centralized controller Group control up to 16 indoor groups Error display function
MCM-A100
41 / 84
■ Installing the centralized controller (MCM-A202)
Centralized controlCentralized control5.5.
NL
R1R2C1C2
220V AC Power input
485 Interface Module
Function ControllerSNET II+
FRONT VIEW
– LED On equivalent to interface module
address at tracking.– Green LED of PCB backside is flickering
when communication with interface
module. Red LED is flickering when
communication with DMS.– If “11” and “15” button press at the same
time for 5 seconds, centralized controller
is reset.
42 / 84
■ Option switch setting (MCM-A202)
SW No Off On
SW 3Group tracking
mode
Room tracking
mode
SW 4Communication
Speed 9600 bps
Communication
Speed 2400 bps
Centralized controlCentralized control5.5.
Control level SW 1 SW 2
0 Off Off
1 On Off
2 Off On
3 On On
Upper controller is set to “Room mode” & SW 3 is set to “Off”
Upper controller is set to “Group mode” & SW 3 is set to “On”
Upper controller is set to “2400 bps” & SW 4 is set to “Off”
Upper controller is set to “9600 bps” & SW 4 is set to “On”
Setting error display : Rotated flickering
43 / 84
■ Centralized control level
FeaturesLevel
No priority level. Wired and wireless remote controller can be used.
Wired and wireless remote controller are disabled when
the indoor unit is stopped by centralized controller.
0
Centralized controlCentralized control5.5.
1
The “All ON” button determines stand-by state. When the
“All ON” button is pressed, ON-state LED turns on without
turning on all the indoor units and the remote controllers
are allowed to use.
3
Remote controllers are disabled at all time2
44 / 84
■ Cooling / heating selection switch
Centralized controlCentralized control5.5.
– If set to “cool”, the indoor units will turn on to the cooling mode. However, this does not mean that heating mode is disabled.
– If set to “heat”, the indoor units will turn on to the heating mode.
MCM-C200
To prevent cooling/heating mode confusion error on the heatpump outdoor unit, MCM-C200 also can be used.
45 / 84
■ Installing the function controller (MCM-A100)
Centralized controlCentralized control5.5.
DC 12V Communication Line From Centralized Controller
C1 C2V2 V1
Front Rear
DC 12V
46 / 84
Indoor Unit
Main Address 0 (Manual)
RMC Address 0
DIP Switch K2 Off
Indoor Unit
Main Address 1 (Manual)
RMC Address 1
DIP Switch K2 Off
Indoor Unit
Main Address F (Manual)
RMC Address F
DIP Switch K2 Off
Max 16 Indoor units
Outdoor Unit
MIM-B04A
Address Anything OK
DIP Switch K1 On
※ Include DVM Plus less than 16 indoor units
■ Wiring (mini-DVM, DVM, DVM HR : Individual)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
47 / 84
From 17 to max 32 Indoor units
Outdoor Unit
MIM-B04A
Address Anything OK
DIP Switch K1 On
MIM-B04A
Address Anything OK
DIP Switch K1 Off
Indoor Unit
Main Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
RMC Address 0 1 2 3 4 5 6 7 8 9 A B C D E F
DIP S/W K2 Off
DIP S/W K10 On
Indoor Unit
Main Address 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
RMC Address 0 1 2 3 4 5 6 7 8 9 A B C D E F
DIP S/W K2 Off
DIP S/W K10 Off
■ Wiring (DVM Plus : Individual)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
48 / 84
Indoor Unit
Main (Ten) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
Main (One) 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
RMC (1) 0
RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F
DIP Switch K2 Off
Less than 16 Indoor units
Outdoor Unit
MIM-B13
Address Ch 1 Anything OK
Address Ch 2 Anything OK
Address Ch 3 Anything OKChannel 1
■ Wiring (DVM Plus II : Individual)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
49 / 84
Outdoor UnitMIM-B13
Address Ch 1 Anything OK
Address Ch 2 Anything OK
Address Ch 3 Anything OK
From 17 to max 32 Indoor units
Indoor Unit
Main (Ten) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
Main (One) 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
RMC (1) 0
RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F
DIP S/W K2 Off
Indoor Unit
Main (Ten) 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3
Main (One) 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
RMC (1) 1
RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F
DIP S/W K2 Off
Channel 1
Channel 2
■ Wiring (DVM Plus II : Individual)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
50 / 84
Outdoor Unit MIM-B13
Address Ch 1 Anything OK
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Indoor Unit
Main (Ten) 0 - 1 - 1 1 - 2 - 3 3 - 4 - 4
Main (One) 0 - 0 - 5 6 - 0 - 1 2 - 0 - 7
RMC (1) 0 1 2
RMC (2) 0 - A - F 0 - 4 - F 0 - 8 - F
DIP S/W K2 Off
From 33 to max 48 Indoor units
Channel 1
Channel 2
Channel 3
■ Wiring (DVM Plus II : Individual)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
51 / 84
Indoor Unit
Main Address 0 (Manual)
RMC Address 0
DIP Switch K2 Off
Indoor Unit
Main Address 1 (Manual)
RMC Address 0
DIP Switch K2 Off
Indoor Unit
Main Address F (Manual)
RMC Address F
DIP Switch K2 Off
Max 16 Indoor units and 16 Groups
Outdoor Unit
MIM-B04A
Address Anything OK
DIP S/W K1 On
■ Wiring (mini-DVM, DVM, DVM HR : Group)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
52 / 84
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Indoor Unit
Main Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
RMC Address 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7
DIP S/W K2 Off
DIP S/W K10 On
Indoor Unit
Main Address 16 1718
19
20
2122
23
24
25
2627
28
29 30 31
RMC Address 8 8 9 9 A A B B C C D D E E F F
DIP S/W K2 Off
DIP S/W K10 On
From 17 to max 32 Indoor units and less than 16 Groups
■ Wiring (DVM Plus : Group)
MIM-B04A
Address 1
DIP Switch K1 Off
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
53 / 84
Outdoor Unit
MIM-B13
Address Ch 1 Anything OK
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Indoor Unit
Main (Ten) 0 - 1 - 1 1 - 2 - 3 3 - 4 - 4
Main (One) 0 - 0 - 5 6 - 0 - 1 2 - 0 - 7
RMC (1) 0 1 2
RMC (2) 0 - A - F 0 - 4 - F 0 - 8 - F
DIP S/W K2 Off
Channel 1
Channel 2
Channel 3
Max 48 Groups
■ Wiring (DVM Plus II : Group)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
54 / 84
Max 32 Groups (without DVM Plus II)
Outdoor UnitMIM-B04A
Address 0
DIP Switch K1 On
Indoor Units
DIP Switch K2 OffMax 16 Interface modules
Indoor Units
DIP Switch K2 Off
DIP Switch K10 On
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 Off
Indoor Units
DIP Switch K2 Off
DIP Switch K10 Off
Max 16 Interface modules
■ Wiring (Combination : Group)
MIM-B04A
Address 1
DIP Switch K1 On
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
55 / 84
Outdoor Unit MIM-B13
Address Ch 1 1
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Channel 2
Max 48 Groups (with DVM Plus II)
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Indoor Units
DIP Switch K2 Off
Max 16 Interface modules
Max 16 Interface modules
Indoor Units
RMC (1) 0 1 2
DIP Switch K2 Off
Max 16 Interface modulesChannel 3
■ Wiring (Combination : Group)
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
56 / 84
Outdoor UnitMIM-B13
Address Ch 1
1
Address Ch 2
Anything OK
Address Ch 3
Anything OK
Channel 1
Channel 2
Max 16 Interface modules
Max 16 Interface modules
Channel 3
MIM-B04A
Address Anything OK
DIP S/W K1 On
Indoor Units
DIP S/W K2 Off Off
DIP S/W K10 On Off
Outdoor Unit
MIM-B04A
Address 0
DIP S/W K1 OffMax 16 Interface modules
Max 16 Interface modules
Indoor Units
RMC (1) 0 1 2
DIP Switch K2 Off
■ Wiring (Combination : Group) with DVM Plus & DVM Plus II
Centralized controlCentralized control5.5.
MCM-A202
SW 3 Off
Check List
57 / 84
Outdoor Unit
MIM-B13
Address Ch 1 0
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Max 16 Interface modules
MCM-A100
MIM-B04A
Address 1
DIP S/W K1 On
Outdoor Unit
■ Wiring (Function controller / Centralized controller)
Centralized controlCentralized control5.5.
MCM-A202
Address Same wit F.C
SW 3 Off
SW 4 On
Check List
58 / 84
■ Features
FeaturesModel
PDU (Power distribution unit) Can connect maximum 48 indoor units Alarm of measuring failure Total / Individual power consumption display
Image
Power distributionPower distribution6.6.
MCM-B102
PDIM (Power distribution interface module) Can connect maximum 32 PDU
MIM-B06
When one outdoor unit is used several households for common use like studio apartment / arcade etc, display and management of accumulated power consumption of each household air conditioner.
Total demand capacity of indoor unitsTotal power consumption x
Demand capacity of Room ARoom A’s electric power consumption
=
59 / 84
■ PDU Specification
Power distributionPower distribution6.6.
Model code MCM-B102
Power supply 1 Phase 220VAC, 50/60Hz
Power meter makerRS485 type
Omni System
Korea Micronics
LS Industrial Systems
Hansuk Tech
Pulse type Anything
Power meter communication type RS485 or Pulse type
Remote measuring company
Omni System
Korea Micronics
LS Industrial Systems
Total power consumption display Power Consumption of one Outdoor unit
Power consumption of each indoor unit Maximum 48 Indoor units
Search Auto / Manual Search Function
Operation temperature -40 C ~ 80 C
Dimension 131 Width x 196 Height x 56.5 Depth
60 / 84
Outdoor Unit
Indoor units
Main Address Manual
RMC Address Anything OK
Max 48 Indoor units
MCM-B102
Address Anything OK
Power meter
■ Wiring (PDU)
Power distributionPower distribution6.6. Check List
61 / 84
Outdoor Unit
Indoor units
Main Address Manual
RMC Address Anything OKMCM-B102
Address 0
Indoor units
Main Address Manual
RMC Address Anything OKMCM-B102
Address 1 Samsung Scope
Max 32 PDU
Max 16 PDIM
Remote measuring
MIM-B06
Address 0
MIM-B06
Address 1
■ Wiring (PDU / PDIM)
Power distributionPower distribution6.6. Check List
In case of DVM Plus & DVM Plus II, remote measuring is impossible .
62 / 84
DMSDMS7.7.
FeaturesModel
DMS (Data management server) Lower level : System A/C data storage server Upper level : Gateway for multi connection
Image
MIM-D00
SIM for power distribution on DMS level Can connect maximum 8 power metersMIM-B12
■ Features
– Embedded web server, Operation without PC– 16 Centralized controller and 256 indoor unit group/individually control – Error and operation status reports to the upper level controller– Edit and save yearly / weekly schedules– Power distribution function (Save 62 days worth of power distribution data)– Support multi user and compatible with multiple controllers (S-Net i, S-Net 3)– Connectable 8 SIM (MIM-B12) and 64 power meters– Current time back up for 24 hours when the power is cut off
63 / 84
DMSDMS7.7.
■ Menu architecture
Menu architecture
Control & Monitor Features Monitoring System environment
Control & Monitoring Control Periodical power use Tracking
Error history Power distribution Run time ratio Rename
Peak power control Power use per IU User management
Daily run time
Peak control status
■ DMS connectable devices
No Product Model Note
1 Indoor / Outdoor BAC, DVM, DVM Plus, DVM Plus II
2 Interface module MIM-B04A / MIM-B13 Don’t use MIM-B04
3 Centralized controller MCM-A202 Don’t use MCM-A200 / 201
4 SIM MIM-B12 Power distribution
64 / 84
DMSDMS7.7.
■ DI (Digital input) / DO (Digital output)
② ① ④ ③ ⑤ ⑥
1 DI – 1 External contact signal control
2 DI - 2 External contact signal control
3 DO – 1
Outputs 12V if at least one indoor unit is running.
(External circuit may be built for display using the
12V output) Equivalent to the ‘A/C Running’ LED
on the DMS external display.
4 DO - 2
Outputs 12V if there is an error on the indoor or
outdoor unit or if communication error occurs.
(External circuit may be built for display using the
12V output) Equivalent to the ‘Error’ LED on the
DMS external display.
5 LAN LAN connection port
6 COM Communication port to centralized controller / SIM
65 / 84
DMSDMS7.7.
■ DI (Digital input) External contact control
PatternDIP Switch
Control details1 2
Pattern 1 Off Off No response to the external contact signal control. (Factory setting)
Pattern 2 On Off – Used for emergency cases such fire.– When there is an input ON signal on DI-1, turns off all the indoor
units, and disables the use of all the remote controllers.– During an emergency stop, the DMS will ignore any request from
the higher level controllers.– The schedules and the peak power control will not operate as well.– The indoor units are restored to the previous operation status,
when the input signal changes to OFF. (The DI-2 is not used)
Fire Sensor
66 / 84
DMSDMS7.7.
■ DI (Digital input) External contact control
PatternDIP Switch
Control details1 2
Pattern 3 Off On – Changes the on/off status of all the indoor units depending on the
ON/OFF status of the DI-1 input.– Enables/disables the remote controllers depending on the
ON/OFF status of the DI-2 input. (ON: enable/ OFF: disable)– The schedules and the peak power control will run regardless of
pattern 3.
Pattern 4 On On – Turns on all the indoor units when there is a pulse input on DI-0.– Turns off all the indoor units when there is a pulse input on DI-1.– Turns off all the indoor units when there is a pulse input on DI-1,
DI-2. (The pulse width is valid only for 0.5~1.0 sec.)– The schedules and the peak power control will run regardless of
pattern 4.
67 / 84
DMSDMS7.7.
■ DI (Digital input) External contact control
No Pattern Control details
1 Power (Red) Power display.
2 CPU Alive (Yellow)Flickers every second in normal operation.
3 Linked (Green) Internet cable connection status display.
4 Active (Green) Flickers during data transmit & receive.
5 RS485 Tx (Green)Flickers during data transmission from theDMS to the centralized controller.
6 RS485 Rx (Green)Flickers during data transmission from thecentralized controller to the DMS.
7 DI-1 Status (Green)Lights on when using the DI-1 externalcontact signal control.
8 DI-2 Status (Green)Lights on when using the DI-2 externalcontact signal control.
9 A/C Running (Green)Lights on if at least one indoor unit connected to the DMS is running.
10 Error (Green)Lights on if there is an error on at leastone indoor or outdoor unit.
68 / 84
MIM-D00
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 OnMax 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
Outdoor Unit
Max 256 indoor unitsMax 16 Centralized controllers
Web browser
DMSDMS7.7.
■ Wiring
MCM-A202
Address 0
SW 4 Off
MCM-A202
Address 1
SW 4 Off
Check List
69 / 84
■ Wiring with SIM
MIM-D00
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 OnMax 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
Outdoor Unit
Max 256 indoor unitsMax 16 Centralized controllersMax 8 SIM
Web browser
Max 8 Power metersMIM-B12
Address 0
DMSDMS7.7.
MCM-A202
Address 0
SW 4 Off
Check List
70 / 84
S-Net 2 PlusS-Net 2 Plus8.8.
FeaturesModel
System A/C control PC software using RS-232C communication. Individual / Group / Zone control. Weekly / Daily / Timely scheduling. Maximum 256 groups, 4096 indoor units control. Enable / disable individual use of remote controllers. Peak power control (Korea domestic only)
MST-S1P
■ Features
PC–Converter Comm. Status Display LED
Converter–485 Comm. State Display LED
Power LED
RS232 Cable Connection Connector
RS485 Communication Connector
Converter Power Input Connector
MIM-C00
485 / 232Converter
Centralized controllers CANNOT be used in individual control.
71 / 84
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
MCM-C202
Address 0
MCM-C202
Address 1
MIM-C00
Max 4096 indoor unitsMax 256 indoor groupsMax 16 Centralized controllers
MST-S1P
S-Net 2 PlusS-Net 2 Plus8.8.
■ Wiring
Check List
Less than 32 indoor units with DVM Plus 2
72 / 84
S-Net iS-Net i9.9.
FeaturesModel
DMS based system A/C control. Color LCD touch panel web pad. (Windows CE) Connect maximum 4 DMS, Control 256 indoor units.MST-P1W0
■ Features
Centralized controllers CANNOT be used in room tracking mode.
Image
– Individual / Group / Multi / Whole control.– Schedule management.– Group management. (Logical, not physical group by switch setting)– Monitoring of connection structure, error log, detailed cycle information.– Power management (Peak power control )– Upper / Lower temperature limit, remote control, peak circulation, priority
of indoor unit setup function.
73 / 84
■ Menu architecture
Menu architecture
Control Schedule Group management Monitoring
Individual control
(Group control)
Schedule list
(Add / Edit / Delete)
(Apply / Stop)
(Make / Edit / Delete) Connection status
Error log
Multi control Detailed information
(Only room tracking)Whole control
System environment System setting
Tracking Date / Time
DMS IP setup Brightness control
Change password Volume control
Time synchronization IP setup
Stylus adjustment
S-Net iS-Net i9.9.
74 / 84
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
S-Net iS-Net i9.9.
■ Wiring
Max 256 indoor unitsMax 16 Centralized controllers
MIM-D00
MST-P1W0
Max 4 DMS
MCM-A202
Address 0
SW 4 Off
MCM-A202
Address 1
SW 4 Off
Check List
75 / 84
FeaturesModel
DMS based system A/C control PC software through LAN. Version comparison and auto update. Various statistical analysis using database management and reporting. Data backup and recover with DMS. Support remote access. (Multi PCs can connect to a single DMS) Connect maximum 16 DMS and 4096 indoor units control.
MST-P3P
■ Features
S-Net 3S-Net 310.10.
– User classification (General, Manager, Installer)– Individual / Group / Multi / Whole control, setup and monitoring.– Schedule management.– Group management. (Management structure, Installation structure)– Power management (Power distribution, Peak power control )– Statistical analysis and reporting (Device list, Event log, Operation ratio,
Power consumption, Demand control etc)
76 / 84
■ Menu architecture
Menu architecture
Control & Monitoring Schedule management Power demand control Usage analysis
Indoor Make schedule Demand list Time & power usage
Outdoor Schedule list Demand history Power report
DMS Daily schedule Indoor classification Power management
Management structure Setup exception day Setup target demand Setup power section
Installation structure
System management Toolbar
Environment Log out
Setup DMS Full screen
Event log Edit structure
Device list renewal Device list
Backup & recover Whole indoor stop
S-Net 3S-Net 310.10.
77 / 84
S-Net 3S-Net 310.10.
MIM-D00
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
■ Wiring
Max 256 indoor unitsMax 16 Centralized controllers
Max 16 DMS
S-Net 3
MCM-A202
Address 0
SW 4 Off
MCM-A202
Address 1
SW 4 Off
Check List
78 / 84
S-Net 3S-Net 310.10.
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
Max 256 indoor unitsMax 16 Centralized controllersMax 8 SIM
MIM-D00
Max 8 Power metersMIM-B12
Address 0
Max 16 DMS
■ Wiring with SIM
S-Net 3
MCM-A202
Address 0
SW 4 Off
Check List
79 / 84
FeaturesModel
Free connection control device. (With DMS, interface module, centralized controller) 7 inch wide touch screen LCD. Connect USB keyboard. Maximum 256 indoor units individual / group control.
S-Net mini
■ Features
S-Net miniS-Net mini11.11.
Image
Control targetInterface module / Centralized controller
(Basic Function)DMS
Function
– Tracking– Individual / Zone control– Schedule / Zone management– Status monitoring– Installation structure– Access control (Touch lock)
– Basic function– Error log– Peak power management– Demand control– Power distribution
Function (TBD)
80 / 84
S-Net mini
Outdoor UnitMIM-B13
Address Ch 1 0
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
■ Wiring (Connection with interface module)
S-Net miniS-Net mini11.11.
81 / 84
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
Max 256 indoor unitsMax 16 Centralized controllers
S-Net mini
■ Wiring (Connection with centralized controller)
S-Net miniS-Net mini11.11.
MCM-A202
Address 0
SW 4 Off
MCM-A202
Address 1
SW 4 Off
82 / 84
MIM-B13
Address Ch 1 2
Address Ch 2 Anything OK
Address Ch 3 Anything OK
Channel 1
Outdoor Unit
MIM-B04A
Address 0
DIP Switch K1 On
Max 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
■ Wiring (Connection with DMS)
Max 256 indoor unitsMax 16 Centralized controllers
MIM-D00
Max 4 DMS
S-Net mini
S-Net miniS-Net mini11.11.
MCM-A202
Address 0
SW 4 Off
MCM-A202
Address 1
SW 4 Off
83 / 84
Channel 1
MIM-B04A
Address 0
DIP Switch K1 OnMax 16 Interface modules
MIM-B04A
Address 1
DIP Switch K1 On
Outdoor Unit
MCM-C00
S-Net 1
MIM-B04A
Address 2
DIP Switch K1 On
S-Net 1 series (Freeware)S-Net 1 series (Freeware)12.12.
■ S-Net 1 Wiring
Outdoor Unit
Outdoor Unit
Check List
84 / 84
Anything OKAddress Ch 2
MIM-B13
Anything OKAddress Ch 3
2Address Ch 1
Channel 1
Outdoor Unit
MIM-B04A
OnDIP Switch K1
0Address
Max 16 Interface modules
MIM-B04A
OnDIP Switch K1
1Address
Outdoor Unit
Outdoor Unit
0Address
MCM-C202
MCM-C00
S-Net 1 Plus
S-Net 1 series (Freeware)S-Net 1 series (Freeware)12.12.
■ S-Net 1 Plus Wiring
Check List