Slovak University of Technology Faculty of Material Science and Technology in Trnava. Software of Programmable Controllers. 2007. Programmable controller KRGN 90. 8 - loop controller HW configurable I/O signal more than 40 pre-programmed functions operator panel operator interface - PowerPoint PPT PresentationTRANSCRIPT
Software of Programmable Controllers
Slovak University of TechnologyFaculty of Material Science and Technology in Trnava
2007
Programmable controller KRGN 90 8 - loop controller HW configurable I/O signal more than 40 pre-programmed functions operator panel
operator interface engineering functions
4 displays to monitor a controlled processes communication protocol...
KRGN 90 - operator interface
Displays
DATA - VALUE Set Point PROCESS OUTPUT ALARMS
KRGN 90 - operator interface
Keys
Set Point MAN, AUTO, CAS Man Reset PP, II, DD ACK
KRGN 90 - eng. functions
Displays Object - step - function - data - value
AI configuration CONF / AUX - ANAL
Loop configuration CONF / AUX - LOOP
INS - RPL - DEL
Analogue input configuration
CONF - ANAL- AInn FNC 01 - Q1, Q2, Q3, Q4...
AUX - ANAL - Ainn DFIL, ISCL, ISCH IALL, IALH, ISFL, ISFH, SAFE
ANAL - Ainn AI type assignment to the physical AInn
Loop configuration CONF - LOOP- l
FNC 10, FNC 20, FNC 55
AUX - LOOP - l SCAN, OLIL, OLIH, OGRL, OGRH LSCL, LSCH, GRAD PALL, PALH, DALL, DALH DINL, DINH, GAPL, GAPH...
LOOP ON / OFF
Loop program structure Controller KRGN 90 has 8 LOOPs
Loop has 20 program STEPs maximum
Program step consists one function FNCnn
Function has questions Q1,Q2, Q3,...
FNC 01 - AI processing
Purpose: The unified analogue signal transformation to digital representation in e.u. and primary input variable processing.
Q1 – a type of current unified input signal
Q2 – linearisation type
Q3 – binary output for technological alarm signalisation
Q4 – safety alarm signalisation
FNC 10 - step signal specification
An value assignment to the real and logical part of program step output, where the function FNC 10 is configured.
Q1 – real part of the program step value
Q2 – logical part of the program step specification
FNC 20 - PID function
The ideal paralel type of a PID algorithm as a sum of the proportional, integral and derivative part of a control action.
Q1– the type of the set point processing when a loop is switched from MAN to AUTO mode.
Q2 – control action direction
Q3 – loop mode after controller restart
FNC 20 - PID functionFNC 20 continued:
Q4 – type of the derivative part of control action
Q5 – binary variable address for process variable alarm
Q6 – binary vaariable address for deviation alarm
Q7 – control action computation type
FNC 21 – Set Point computation for cascade loop
A computation of the set point for a slave loop in cascade mode.
A set point of the cascade loop is computed according the expression
ZHCAS = RATIO*INPUT+BIAS
Q1 – signal source specification
FNC 22 – Auto RATIO
On line computation of the slave loop RATIO for a bumpless switching the AUTO mode to the CAS one
INP
BIASZHCASRATIO
Q1 – signal source specification
FNC 23 – Auto BIAS
On line computation of the slave loop BIAS for a bumpless switching the AUTO mode to the CAS one
Q1 – signal source specification
INPUT*RATIOZHCASBIAS
FNC 24 - SP computation for slave loop
A set point computation for a cascade loop, when the limits of this set point are given.
Q1 – loop number
LSCLLSCH*n
DOUT1n
ZHCASn
ZHCAS
FNC 30- arithmetic operations
Arithmetic operations: sum, difference, multiplication and division.
Q1 – the second operand
Q2 – type of arithmetic operation
Q3 – order of operands
FNC 50 – Dynamic signal compensation
Dynamic compensation of a signal by the block LEAD/LAG of 1st order.
Q1 – lead time constant in the interval 0 to 99999 sec.
Q2 – lag time constant in the interval 0.5 to 99999 sec.
isT1dsT1
F(s)
FNC 51 – Dead Time Block
A delay of a main value signal at a specified time.
Q1 – time delay in the interval 0.5 to 99999 sec.
sDeF(s)
FNC 55 – D/A conversion
A conversion of a control action value to the corresponding analogue unified signal.
Q1 – type of analogue current unified signal
Q2 – signal specification
Auxiliary parameters for AI
DFIL – the time constant of 1st. order digital filter
ISCL – input scale lower
ISCH – input scale upper
IALL – lower limit for technological alarm
IALH – upper limit for technological alarm
Auxiliary parameters for AI
ISFL – input safety lower value
ISFL – input safety lower value SAFE - safety/ default value of input signal
Auxiliary parameters for LOOP
SCAN – program loop execution scan period
OLIL – lower limit of control action
OLIH – upper limit of control action
OGRL – maximum rate of valve closing rate during one scan period
OGRH – maximum rate of valve opening rate during one scan period
Auxiliary parameters for LOOP continued
GRAD – maximum rate of set point change during one
scan period
LSCL – lower limit of set point
LSCH – upper limit of set point
PALL – lower limit of process variable alarm
PALH – upper limit of process variable alarm
DALL – lower limit of deviation alarm
DALH – upper limit of deviation alarm
Auxiliary parameters for LOOP continued
DINL – deviation lower limit indicated on the bargraph
DINH – deviation upper limit indicated on the bargraph
GAPL – lower hysteresis band for control action execution
GAPH – upper hysteresis band for control action execution