DOCUMENT SES-KS-SMARTS500-E-R4 HC Pellistor Sensor Low Power Combustible Flammable Gas Detection HC Pellistor Sensor Std. Power Combustible Flammable Gas Detection IR-HC Infrared Sensor Combustible Flammable Gas Detection OXY Electrochemical Cell Oxygen Gas Detection TX Electrochemical Cell Toxic Gas Detection S S M M A A R R T T S S - - 5 5 0 0 0 0 H H C C C C o o m m b b u u s s t t i i b b l l e e & & F F l l a a m m m m a a b b l l e e G G a a s s e e s s S S M M A A R R T T S S - - 5 5 0 0 0 0 T T X X T T o o x x i i c c G G a a s s e e s s S S M M A A R R T T S S - - 5 5 0 0 0 0 O O X X Y Y O O x x y y g g e e n n M M o o n n i i t t o o r r i i n n g g INSTRUCTION MANUAL Revision Card: Software HC V.05.1.4 Revision Card: Software TX V.05.1.4 Revision Card: Software OXY V.05.1.4 Revision Card: Hardware V.05.1.0

Upload: others

Post on 27-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

DOCUMENT SES-KS-SMARTS500-E-R4

HC Pellistor Sensor Low PowerCombustible Flammable Gas Detection

HC Pellistor Sensor Std. PowerCombustible Flammable Gas Detection

IR-HC Infrared Sensor Combustible Flammable Gas Detection

OXY Electrochemical CellOxygen Gas Detection

TX Electrochemical CellToxic Gas Detection

SSMMAARRTT SS--550000 HHCC CCoommbbuussttiibbllee && FFllaammmmaabbllee GGaasseess

SSMMAARRTT SS--550000 TTXX TTooxxiicc GGaasseess

SSMMAARRTT SS--550000 OOXXYY OOxxyyggeenn MMoonniittoorriinngg

INSTRUCTION MANUAL Revision Card: Software HC V.05.1.4 Revision Card: Software TX V.05.1.4 Revision Card: Software OXY V.05.1.4 Revision Card: Hardware V.05.1.0

Page 2: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 2 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

IINNSSTTRRUUCCTTIIOONN MMAANNUUAALL The information and technical data included in the present instruction manual are of exclusive property of SES ASA ENGINEERING S.r.L. Copy of this information or technical data or part of them cannot be reproduced without written authorisation of SES ASA ENGINEERING S.r.L. Any misused of this information will be persecuted by law. SES ASA ENGINEERING reserves the right to change or update this information any time it may be necessary without advanced notice

WWAARRRRAANNTTYY SES ASA ENGINEERING S.r.L. assures that all components, sub assembly and the final product is manufactured accordingly to certified quality system ISO 9001:2000 by DNV. All components are carefully controlled to be corresponding to the scope of their use and with MTBF as defined in our production specification. Should any defect arrives during operation, within the guarantee period, SES ASA ENGINEERING S.r.L. assures to replace or repair such defective parts ex works. Our product guarantee is 2 years of good operation or 3 years from shipment. If for any reasons a malfunction of the product due to a undetectable faults by factory quality control and FAT will cause damage, SES ASA ENGINEERING S.r.L. responsibility will be limited to the value of the product. Any malfunctions due to bad handling, incorrect installation or incorrect maintenance, will ipsofacto invalid the guarantee. SES ASA ENGINEERING S.r.L. reserves the right to check and verify any claim for any products or components returned as defective. For any dispute not solved amicable the competent court is MILANO, ITALY

Page 3: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 3 of 47

IINNDDEEXX

SECTION 1 - INTRODUCTION ................................................................................................................................4 1.1 GENERAL DESCRIPTION .............................................................................................................................4 1.2 DETECTOR ......................................................................................................................................................5 1.3 SENSOR ...........................................................................................................................................................6 1.4 REPLEACEMENT............................................................................................................................................7

SECTION 2 – TECHNICAL SPECIFICATIONS.....................................................................................................8 2.1 ELECTRICAL CHARACTERISTICS SMART S-500 HC COMBUSTIBLE & FLAMMABLE DETECTOR .........8 2.2 ELECTRICAL CHARACTERISTICS SMART S-500 TX TOXIC GASES DETECTOR ..................................8 2.3 ELECTRICAL CHARACTERISTICS SMART S-500 OXY OXYGEN DETECTOR........................................8 2.4 MECHANICAL CHARACTERISTICS ...........................................................................................................8 2.5 ELECTRICAL CHARACTERISTIC................................................................................................................9 2.6 OPERATIVE ENVIRONMENTAL CONDITIONS ......................................................................................10 2.7 FRONT PANEL & DIGITAL DISPLAY .........................................................................................................10

SECTION 3 - INSTALLATION................................................................................................................................11 3.1 CHECK OF SHIPMENT................................................................................................................................11 3.2 INSTALLATION - CONNECTIONS.............................................................................................................11

SECTION 4 - OPERATIVE ISTRUCTION ............................................................................................................12 4.1 BLOCK DIAGRAM SMART S-500 HC .......................................................................................................12 4.2 BLOCK DIAGRAM SMART S-500 TX / OXY ............................................................................................13 4.3 INPUT CONNECTION, POWER SUPPLY AND OUTPUT SIGNAL 0÷22MA ......................................14 4.4 OUTPUT RELE’ CONNECTION .................................................................................................................15 4.5 SENSING ELEMENT CONNECTIONS......................................................................................................17 4.6 SERIALE LINK RS-485 MODBUS CONNECTIONS COMMUNICATION PROTOCOL....................18 4.7 REMOTE CALIBRATION CONNECTIONS ...............................................................................................21 4.8 DIGITAL DISPLAY DATA – SEQUENCE ON THE DISPLAY AFTER POWER ON ............................22 4.9 OPERATIVE PARAMETERS CONFIGURATION.....................................................................................24 4.10 SMART S-500 HC OPERATION .................................................................................................................27

SECTION 5 – CALIBRATION PROCEDURES ....................................................................................................29 5.1 LOCAL CALIBRATION .................................................................................................................................29 5.2 REMOTE AUTOMATIC CALIBRATION .....................................................................................................30 5.3 CALIBRATION ERROR ................................................................................................................................31

SECTION 6 – MAINTENANCE...............................................................................................................................32 6.1 ELECTRONIC CIRCUITS OF SMART S-500 DETECTOR ....................................................................32 6.2 STORAGE.......................................................................................................................................................33

SECTION 7 – TROUBLE SHOOTING ...................................................................................................................34 7.1 TROUBLE SHOOTING .................................................................................................................................34 7.2 SYSTEM MESSAGES...................................................................................................................................34 7.3 SMART S-500 SERIES AVAILABLE ..........................................................................................................35 7.4 SPARE PARTS AND ACCESSORIES........................................................................................................36

SECTION 8 – LAYOUT ............................................................................................................................................37 8.1 DIMENSIONS - INTERCONNECTIONS SMART S-500 ..........................................................................37 8.2 DIMENSIONS - INTERCONNECTIONS S-500 (REMOTE) ....................................................................38

SECTION 9 – CERTIFICATE & ATTACCHED ...................................................................................................39 9.1 SAFETY INSTRUCTION ..............................................................................................................................39 9.2 EUROPEAN COMMUNITY CERTIFICATE TÜV .....................................................................................42 9.3 CE CONFORMITY DECLARATION ...........................................................................................................43 9.4 ATEX CERTIFICATE.....................................................................................................................................44

Page 4: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 4 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

SECTION 1 - INTRODUCTION

1.1 GENERAL DESCRIPTION FUNCTIONALITY SMART S-500 is a State of the Art universal Combustible and Toxic Gas Detectors, a reliable, continuous monitoring device to protect people and your high value investments. SMART S-500 Gas Detector employs a powerful RISC Microprocessor which provides self diagnostic, serial line communications RS-485 for MODBUS protocol, One-Man calibration features firmware resident. SMART S-500 Gas Detector is suitable to be employed with almost all gas sensing elements / electrochemical cell available in the market. SMART S-500 Gas Detector employs a unique highly coupled Pellistor beads, or Electrochemical Cell, sensing elements supported by a plug-in cards. Sensors are field replaceable protected in a S.S.316 housing ATEX certified. The electronics enclosure is light alloy epoxy red painted ATEX certified. SMART S-500 technology has been developed to offer long life durable and strength device to protect your plant and to provides high reliability with easy and low cost maintenance. SMART S-500 HC transmitter represents a technological innovation in the combustible gas detection field. The electronics based on a microprocessor RISC, that visualizes on digital display 16 characters the gas concentration value, verify constantly power value of each single circuit any possible Fault as short circuit or Pellistor open. A Watch-Dog, circuit check the correct working of the analogue and digital logic sections. Any working anomaly are visualized on a digital display and by a fault relay, on terminal boards. SMART S-500 HC has a proportional output related to the concentration detected that can be interfaced directly to a PLC/DCS or to a generic system which receive 4÷20mA signal. (1÷22mA for calibration and diagnostic) It is possible to set the value of Warning and Alarm. The signals are visualized by the display with “Warning” and “Alarm”, along with “Fault”. These indications are available as free voltage contacts on the interface terminal board. In case of large leak of gas to be measured, the Over-range indication will be displayed.

The firmware has been made to guide the operator, helping him for a simple and accurate calibration and maintenance. One point of calibration, equal to about 50% of measure field, will be enough to obtain a correct calibration.

An exclusive mode of remote calibration (also via serial interface) is available and allows the SMART DETECTOR S-500 to receive an external command, when the Zero calibration starts and to control automatically the cylinder solenoid valve (open-close), with sample gas, for “Span” calibration. Through the serial line full duplex 485 standard RTU MODBUS, it is possible to set and adjust the analogue value corresponding to the gas concentration read by the sensors as well as all sensor functional parameters.

Page 5: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 5 of 47

1.2 DETECTOR To wire the sensor SMART S500 Terminals it is necessary to unscrew the Allen locking screw, remove the upper glass cap and repeat the operation for the central part of the explosion proof housing. Then take out the circuit leave it up making sure that interconnecting cable remain in its own position, then operate on terminals screws related to this connection. Also terminal screw must be pulling out in order to simplify the wiring connections. Particular attention must be used during operation of screwing up the central glass cap in order to avoid any damage. In order to follow state of the art related to explosion proof area rules it is necessary to lock all parts using the blocking screw above mentioned (See section 9.1). fig. 1 fig. 2

fig. 3

Page 6: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 6 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

1.3 SENSOR S-500 HC sensor has been designed with an innovative technology that permit to increase the reliability of detection, to reduce maintenance costs and fast sensor replacement in case of damages or fault. S 500 HC sensing element is made by two high temperature matched Pellistor beads. The beads are mounted on Teflon support to insulate them from external temperature change. The printed circuit with Pellistor beads is located in a S.S.316 INOX-316-L environmental resistant to aggressive agents. Sensor’s body is physically separated from electronics or terminal enclosure by an epoxy resin Flame Resistant. The sensor is made by two mechanical parts a sensor body base and sensor coverage separable on field, this permit the Pellistor beads replacement directly on the field without disconnecting power on electronics detector.

Page 7: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 7 of 47

1.4 REPLEACEMENT

S-500 SENSING ELEMENT Design represent a real cost of maintenance reduction, giving the possibility to substitute the sensing elements in few minutes. . The SMART S-500 Software permits to locally disconnect the sensor only, using a specific command from the keyboard , the sensor assembly can be open in classified area simply unscrewing the mechanical protection and substitute the sensing element mounted on the plug-in circuit. Most of other detection system in the market require the complete shut-off of the detector and replacement of the complete sensor and off site service condition, for the area involved.

Sensor Body Base

Sensor / Cell

Sensor Body Cover

Fixing Screw

With MagnetCalibration Tool

Base-500C.S.

Detail View Interchangeable Part

Front Internal Rear

C.S.Base-501

Front View Fixing Part

Page 8: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 8 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

SECTION 2 – TECHNICAL SPECIFICATIONS

2.1 ELECTRICAL CHARACTERISTICS SMART S-500 HC Combustible & Flammable Detector

Application : Explosive Gas Detection Operative ambient : Hazardous areas Warranty : 3 years of continuous operations

2.2 ELECTRICAL CHARACTERISTICS SMART S-500 TX Toxic Gases Detector Application : Toxic Gas Detection Operative ambient : Hazardous areas Warranty : 3 years of continuous operations

2.3 ELECTRICAL CHARACTERISTICS SMART S-500 OXY Oxygen Detector Application : Oxygen Gas Detection (Oxygen depletion) Operative ambient : Hazardous areas Warranty : 3 years of continuous operations

2.4 MECHANICAL CHARACTERISTICS • ELECTRONIC HOUSING

Material : Light alloy Color : SMART S-500 HC Red RAL 3000 Epoxy Paint

SMART S-500 TX Yellow RAL 1021 Epoxy Paint SMART S-500 OXY Blue RAL 5015 Epoxy Paint

Weight : 1,5 kg (including sensor body ) High : 160 mm Width : Ø 90 mm

• SENSOR BODY Material : S.S. AISI 316 High : 70 mm (Max) Width : Ø 40 mm Key : 41 mm exag. Splash guard : Ø 36 mm

Page 9: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 9 of 47

2.5 ELECTRICAL CHARACTERISTIC

• ELECTRONIC Power Supply Module : 24VDC nominal (20÷30VDC) Power Consumption : 3 W Max (in Alarm Condition) Analogue output Signal : 0÷22mA

o Start-Up 2mA (Wait Time 30÷300 minutes) ( SMART S-500 HC = 30m. SMART S-500 TX = 300m. SMART S-500 OXY = 120m.)

o Fault 1mA o Calibration 2mA (default)

(to set between 1mA and 2.5mA step 0.5mA) o 0-100% FS proportioning 4÷20mA o Over-range 22mA

• SENSOR for SMART S-500 HC Sensor type : Pellistor Twin Beads Detectable Gases : Hydrocarbons (Methane, Propane, Hydrogen…) Measuring Range : 0÷100% - L.E.L. (Low Explosion Limit) Long term drift : < ± 1 L.E.L. / Month Response time (T50) : 3 s Response time (T90) : 8 s Repeatability : ± 1% L.E.L. (referred to methane CH4) Precision : ± 2% L.E.L. (referred to methane CH4) Operative life : > 3 years

• SENSOR for SMART S-500 TX Sensor type : Electrochemical Cell Detectable Gases : Toxic (Ammonia, Carbon monoxide, Hydrogen Sulphide,

Sulphur Dioxide…) Measuring Range : Selection between 10÷1000ppm (part per million) Long term drift : < 10% / Month for NH3 Sensor < 2% / Month for H2S Sensor < 5% / Year for CO Sensor Response time (T90) : < 150 s for NH3 Sensor ≤ 30 s for H2S e CO Sensors Repeatability : 10% of Signal for NH3 Sensor

1 % of Signal for H2S e CO Sensors Precision : 0.5 ppm for NH3 e CO Sensors

0.1ppm for H2S Sensor Operative life : 1 Year in air free for NH3 Sensor 2 Year in air free for H2S Sensor 3 Year in air free for CO Sensor

• SENSOR for SMART S-500 OXY Sensor type : Electrochemical Cell Detectable Gases : Oxygen Measuring Range : 0÷30% Volume Long term drift : < 5% / Year Response time (T95) : ≤ 15 s Operative life : 2 Year in air free

Page 10: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 10 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

2.6 OPERATIVE ENVIRONMENTAL CONDITIONS Working Temperature HC -40°C ÷ +70°C (-40°F ÷ +158°F) MAX TX –OXY -20°C÷ +50°C ( -4°F ÷ +124°F) MAX Storage Temp. Electronics -40°C ÷ +85°C (-40°F ÷ +185°F) Storage Temp. Pellistor Beads -40°C ÷ +85°C (-40°F ÷ +185°F) Storage Temp. Electroch. Cell 0°C ÷ +20°C (+32°F ÷ +68°F) Humidity Ambient 0% ÷ 100% non condensing

2.7 FRONT PANEL & DIGITAL DISPLAY Note : Functions reed switches are activated through a Magnet Calibration Tool. Smart S-500 has been realized to satisfy international electromagnetic standard and also for noise emissions, so it will be not possible to actuate the reed switch using standard magnets. It is suggested to use magnets supplied by SES ASA ENGINEERING S.r.L. supplied along with the Smart S-500 detector.

Function KeyScroll Down

Function KeyScroll Up

Function KeyEnter Data

Enable Function Menu Key

Display LCD 8x2with Backlight Screw Driver

with Magnet

Calibration Tool

Page 11: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 11 of 47

SECTION 3 - INSTALLATION

3.1 CHECK OF SHIPMENT All SMART S-500 Gas Detectors are carefully packed and delivered to the customer with utmost attention. All shipment are controlled and witness by our quality control service. As soon as received the good customer must inspect the packing and in case of damage, check the good and inform SES ASA ENGINEERING S.r.L. of any damage occurred during transportation. Please supply SES ASA ENGINEERING S.r.L. all data of order shipment model and serial number of the detector received.

3.2 INSTALLATION - CONNECTIONS SMART S-500 Gas Detector is built protected against magnetic interference, however the installation must be made away from any high current or intense magnetic field. Connection cable must be in accordance to section 4,2-4,3-4,4 and 4,5. The cable must be shielded with shield connected only to one end of the loop for example to the ground connection of controller or to PLC/DCS ground when 4÷20mA connections is made directly to the logic controller. Please make sure the ground is Zero voltage everywhere. Smart S-500 must be positioned taking into consideration many factors including but not limited to the gas density, flash point and as well as the sun and wind direction. The Smart S500 Gas Detector is designed and certified to be installed as one piece with integral sensor and electronics and digital display in one place. However according to the type of gas to be detected and the wind and sun influence, the SMART S500 Gas Detectors can be split into sensor unit and electronic and display unit to suit installation requirement. It is important that the installation and sensor position respect the specific gas condition and that the digital display be place at ergonometric position to be easy seen by the operator.

Internal Detail The SES ASA ENGINEERING S.r.L. is available to supply its qualified long time experienced, engineers to help designing the best type of gas detector to meet international standard to protect your specific plant requirement.

Page 12: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 12 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

SECTION 4 - OPERATIVE ISTRUCTION

4.1 BLOCK DIAGRAM SMART S-500 HC

PELLISTOR SENSOR

SUPERVISION OPEN LINE OR SHORT CIRCUIT

CURRENT CONTROLLER REGULATOR FOR PELLISTOR

AUTOMATIC ZERO CONTROL

AMPLIFIER

AUTOMATIC SPAN

CONTROL

ALOGICAL/DIGITAL CONVERTER

MICROPROCESSOR RISC E²prom + WD + ICSP

START/STOP

REED PUSH BUTTON

DISPLAY LCD

DRIVER SERIAL LINE

DIGITAL DRIVER

OPEN COLLECTOR OF REMOTE CALIBRATION

DIGITAL INPUT FOR REMOTE CALIBRATION

OPTOISOLATOR

WATCH DOG

SPST CONTACTS WARNING ALARM FAULT

ANALOG DRIVER

ANALOGICAL OUTPUT 0÷22mA

REFERENCE BEAD

MEASURING BEAD

POWER SUPPLY

AUXILIARY CARD FOR REMOTE CONTROL SES ASA PROTECTION (SEE DETAIL SECTION 8)

Page 13: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 13 of 47

4.2 BLOCK DIAGRAM SMART S-500 TX / OXY

ELECTROCHEMICAL CELL

BIAS VOLTAGE REGULATOR

AUTOMATIC ZERO CONTROL

AMPLIFIER

AUTOMATIC SPAN

CONTROL

ALOGICAL/DIGITAL CONVERTER

MICROPROCESSOR RISC E²prom + WD + ICSP

REED PUSH BUTTON

DISPLAY LCD

DRIVER SERIAL LINE

DIGITAL DRIVER

OPEN COLLECTOR OF REMOTE CALIBRATION

DIGITAL INPUT FOR REMOTE CALIBRATION

OPTOISOLATOR

WATCH DOG

SPST CONTACTS WARNING ALARM FAULT

ANALOG DRIVER

ANALOGICAL OUTPUT 0÷22mA

COUNTER

SENSING

POWER SUPPLY

AUXILIARY CARD FOR REMOTE CONTROL SES ASA PROTECTION (SEE DETAIL SECTION 8)

REFERENCE

POWER SUPPLY

Page 14: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 14 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

4.3 INPUT CONNECTION, POWER SUPPLY AND OUTPUT SIGNAL 0÷22mA

Terminal Board Remote Controller SMART S-500 HC / TX / OXY

The Detector Smart S500 HC /TX / OXY has an analog output signal 0÷22mA which can be connected to a non floating load of max 600Ω. The output signal can be connected directly to a supervised or control system such as Data Logger, DCS, SCADA, PLC, etc.. . The interconnecting cable between SMART S-500 and any controller must be made with correct wiring sizes as per following table. Cable recommended is shielded or shielded and armored types see Safety Instruction Section 9.1.

GROUND SHIELD INPUT 0÷22mA 0V +24V

Page 15: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 15 of 47

4.4 OUTPUT RELE’ CONNECTION

Terminal Board Remote Controller SMART S-500 HC / TX / OXY

On the interconnection terminal board J1 at the base of electronics, the following alarm relays contacts are connected: K1W Warning relay K2A Alarm relay K3F Fault relay .

Contact Rating 2A@30VDC. 0,5A@125/220VAC. The Alarm/Warning/Fault relays contacts as normally open N/O or normally close N/C can be selected through jumper on CS5 card

Fault detection input Alarm detection input Warning detection input

Page 16: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 16 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

JP5 CLOSE IN POSITION 1-2 K1W Contact of Warning Normally Open

JP5 CLOSE IN POSITION 2-3 K1W Contact of Warning Normally Close

JP6 CLOSE IN POSITION 1-2 K2A Contact of Alarm Normally Open

JP6 CLOSE IN POSITION 2-3 K2A Contact of Alarm Normally Close

JP7 CLOSE IN POSITION 1-2 K3F Contact of Fault Normally Open

JP7 CLOSE IN POSITION 2-3 K3F Contact of Fault Normally Close

Note: K3F Fault Relay during Normal Operation is normally energized. Will be de-energized in case of Fault. Ex: Detector powered without Fault, if JP7 is closed in position 1-2 the contact will be closed For the Warning and Alarm relay setting threshold see Section 4.9

Page 17: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 17 of 47

4.5 SENSING ELEMENT CONNECTIONS Be aware about wiring colors and right connections. (Normally this is made and connected in the factory)

Page 18: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 18 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

4.6 SERIALE LINK RS-485 MODBUS CONNECTIONS COMMUNICATION PROTOCOL

Interconnecting terminals board Remote Operating Station SMART S-500 HC /TX / OXY

Serial link is made RS 485 Full Duplex configured as follows:

Baud rate = 9600, Parity = N (none), Byte = 8, Stop Bit =1 The Standard protocol is MODBUS which SMART S-500 respond to the Master according to the following functions:

Function 3 (Read Registers) Function 4 (Read Analog Inputs) Function 6 (Preset Single Register)

NOTE: SMART S500 will respond only to its proper address (See section 4.9)

RS485FD / RS232 CONVERTER TX+ TX- RX+ RX-

RS-232

RS-485

Page 19: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 19 of 47

• PARAMETERS FOR FUNCTION 3: READ REGISTER Address Function Start

Register Start Register

Nr. Of Registers

Nr. Of Registers

CRC CRC

Hi Lo Hi Lo Lo Hi

SMART S 500 format response: Address Function ByteCount Status 1Hi Status 1Lo CRC Lo CRC Hi

CALL : Address address sent to SMART S-500

Function function requested Start. Register start register (2 bytes = 00 01) Nr. Of Registers number register to be transferred(2 bytes = 00 01) CRC cyclic redundancy check (2 bytes)

REPLY: Address address received from SMART S-500 HC

Function function to which responds ByteCount byte number after ByteCount and before CRC (=02) Status 1 status of SMART S-500, see following table

Bit alarm = 1 Alarm condition Bit warning = 1 Pre-alarm condition Bit fault = 1 Fault condition Bit in-calib. = 1 Calibration condition Bit sens-short = 1 Pellistor short circuit (only HC Version) Bit sens-open = 1 Pellistor circuit open (only HC & OXY) Bit over range = 1 Over-range Bit req-calib. = 1 SMART S-500 HC / TX / OXY need calibration Bit start-up = 1 The sensor in warm up condition (at start up) Bit in-menu = 1 smart keyboard actives Bit cal-error = 1 fault calibration signal Bit key-lock = 1 keyboard blocked Bit vana-fail = 1 analogical power supply fault Bit n.u. bit non utilized Bit n.u. bit non utilized Bit ck-path = 1 it is a “toggle”, bit it changes its own value (0-1) each

transmission in order to permit to verify the correct working of the logic and data transmission.

BIT 7 6 5 4 3 2 1 0 Status 1 Lo REQ-CALIB. OVERRANGE SENS-OPEN SENS-SHORT IN-CALIB. FAULT WARNING ALARM Status 1 Hi CK-PATH N.U. N.U. VANA-FAIL KEY-LOCK CAL-ERROR IN-MENU START-UP

Page 20: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 20 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

• PARAMETERS FOR FUNCTION 4: ANALOG INPUTS READING Standard MODBUS format for function 4 call: Address Function Start

Input Start Input

Nr. Of Inputs

Nr. Of inputs

CRC CRC

Hi Lo Hi Lo Lo Hi SMART S500 standard format response: Address Function Byte Count Value-H Value-L CRC CRC

Hi Lo Lo Hi

CALL : Address SMART S-500 HC /TX / OXY address Function function requested Start. Input start input (2 bytes = 00 01) Nr. Of Inputs inputs to be transferred (2 bytes = 00 01) CRC cyclic redundancy check (2 bytes)

REPLY : Address SMART S-500 HC /TX / OXY address

Function function to which respond ByteCount byte number after ByteCount and before CRC (=02) Value-H analog value – byte high (= 00) Value-L analog value – byte low (= 00÷103 %LEL

/ ppm / %Vol.) • PARAMETER FOR FUNCTION 6: PRESET SINGLE REGISTER

Standard MODBUS function 6 call : Address Function Reg.Nr. Reg.Nr. Data Data CRC CRC

Hi Lo Hi Lo Lo Hi

SMART S-500 format response : Address Function Reg.Nr. Reg.Nr. Data Data CRC CRC

Hi Lo Hi Lo Lo Hi

CALL : Address SMART S-500 HC /TX / OXY address Function function requested Reg.Nr. register number to be set (= 00 01) Data value for register (= 00 01→Calibration start) Data value for register(= 00 08→keyboard lock, Toggle

bit) CRC cyclic redundancy check (2 bytes) RESPONSE Address SMART S-500 HC /TX / OXY address

Function function to which respond Reg.Nr. number of register set (= 00 01) Data value for the register (= 00 01→Calibration start) Data Value for the register (= 00 08→keyboard lock,

Toggle bit) CRC cyclic redundancy check (2 bytes) NOTA: The reply is equal to what of the call.

Page 21: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 21 of 47

4.7 REMOTE CALIBRATION CONNECTIONS SMART S-500 HC /TX / OXY Interconnecting terminal board Switch for remote calibration +V -V

Solenoid relay

Recommended Fast - Diode

Calibration Kit

Cylinder with 50% Full Scale Concentration Pressure Reducer Solenoid Valve 24VDC Flow Meter 1 liter Max. (Advise ¼ Liter) Teflon Tube Flex Splash Guard and Adapter Calibration (same product)

Page 22: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 22 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

4.8 DIGITAL DISPLAY DATA – SEQUENCE ON THE DISPLAY AFTER POWER ON When powered the SMART S-500 digital displays will shows, the following sequences:

SES ASA ENGINEERING

↓ Either Or Or

SMART SMART SMART S-500 HC S-500 TX S-500 OXY

S-500.54 S-500.XX S-500.13 V.05.1.4 V.05.1.4 V.05.1.4

POWER UP PLEASE

↓ The display sequence guide the operator to follow the preparation routine including self diagnostic and warm up of the Pellistor beads to reach stabilized temperature. The first diagnostic time is about 60 seconds to allow zero calibration with indication display.

ZERO IN PROGRESS

At the end of Automatic “Zero” Calibration procedure the program will inhibit all output functions for 30 minutes for HC version, 300 minutes for TX version 120 minutes for OXY version. During the warm up and stabilizing time, the display will shows the name of the gas for which the detector has been configured, the output current will be 2mA Start-up signal and the serial link communication MODBUS will indicate Start Up. The display will show “0” value blinking until the duration of warm up time:

Either Or Or

METHANE AMMONIA OXYGEN 0 % LEL 0.0 ppm 00.0 %V

Type of gas to be detected gas concentration value detected flashing

POWER UP WAIT

Page 23: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 23 of 47

During the warm up time if apply the special SES magnet tool on one of four reed switch near the display read Keyboard Locked and it is possible to know the time required to complete the warm up time.

- 58 Min WAIT:KEYBOARD NOT AVAILABLE NOW

Minutes remaining of stand-by displaying scroll message NOTE: The SMART S500 HC has 8+8 liquid digital characters displayed on two lines therefore when the letter of the messages is longer that 8 characters it is cycled displayed on each line. After completing the warm up condition, all the output will be activated. The output current will be set at 4mA as zero gas condition and reset variable start-up in MODBUS. The display will show the name of the gas to be indicated and - 0% L.E.L. - 0.0 ppm - 20.9% Vol. - will stop to blink remaining fixed. This means the stand by time is over.

Either Or Or METHANE AMMONIA OXYGEN 0 % LEL 0.0 ppm 20.9 %V

Type of gas to be Detected Concentration detected

fixed

Now it is possible to set SMART S-500 working parameter and then to calibrate the system. Note: Wait time change from 30÷300 minutes in function of instrument and gas to detect.

Page 24: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 24 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

4.9 OPERATIVE PARAMETERS CONFIGURATION All parameters modified will be memorized in E2prom on board, therefore any modification

will be permanent stored with “ENTER” reed activation 4.9.0 FUNCTION SET UP

Place the magnet on the Menu symbol on the right of display start the procedure, function set up will shown for one minute.

FUNCTION SET UP

4.9.1 SET-UP WARNING

Place the magnet on the “ENTER” symbol to set Warning / low set point alarm. The display will show the message for one second the message:

SET-UP WARNING

And then will show the message: Either Or Or

SET-UP SET-UP SET-UP W=20 LEL W=25 ppm W=19 %

Place magnet on the increase or decrease symbol to set the low alarm value . After the warning relay K1W will be activated when the set point value will be

reached.

4.9.2 SET-UP ALARM

Place the magnet on the “ENTER” symbol to set Alarm / high set point alarm. The display will show the message for one second the message:

SET-UP ALARM

And then will show the message: Either Or Or

SET-UP SET-UP SET-UP A=40 LEL A=35 ppm A=15 %

Place magnet on the increase or decrease symbol to set the high alarm value. After the alarm relay K2A will be activated when the set point value will be reached.

Page 25: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 25 of 47

4.9.3 SET-UP GAS TYPE

Place the magnet again an “ENTER” symbol to select the 3rd parameter, type of gas you want to use for the detector (only HC version). The display will show type of gas. The display will show for one second the message:

SET-UP GAS TYPE

And then will show the message:

Either Or Or SET-UP SET-UP SET-UP

METHANE AMMONIA OXYGEN

Place magnet on the increase or decrease symbol to select the type of gas. HC = METHANE, PROPANE, HYDROGEN, N-PENTHANE, BENZENE TX = AMMONIA, CARBON MONOXIDE, HYDROGEN SULPHIDE,

SULPHUR DIOXIDE OXY = OXYGEN See Section 7.3 for gas detector guide.

4.9.4 SET-UP RS-485

Place the magnet on “ENTER” symbol to select the serial link communication. The display will show SET-UP RS485. The display will show for one second the message:

SET-UP RS-485

Place the magnet on increase or decrease symbols to select the address from 1÷64.

SET-UP ADD= 1

4.9.5 SET-UP CURRENT SIGNAL FOR CALIBRATION

Place the magnet on “ENTER” symbol to set up the calibration output current The display will show for one second the scroll message:

SET-UP CURRENT SIGNAL FOR CALIBRATION 2.0mA

Place the magnet on increase or decrease symbols till you set the reading of 2mA. (from 1mA to 2,5mA step 0.5mA)

Page 26: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 26 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

4.9.6 SET-UP FULL SCALE VALUE

Place the magnet on “ENTER” symbol to select the Full Scale parameter. This function is not available for HC and OXY version. Is available only for TX version and only if the value read is “0.0” (zero) ppm. The display will show for one second the message:

SET-UP FS VALUE

And then will show the message: SET-UP FS= 50

Place the magnet on increase or decrease symbols till you set the reading of preferred. From 1ppm to 50ppm step 1ppm, over step 50ppm up to 1000ppm)

4.9.7 SET-UP SENSOR SHUTDOWN

Place the magnet on “ENTER” symbol to set up sensor shut-down. This procedure it is necessary only when the Sensor must be replaced. The display will show the message:

SENSOR SHUTDOWN

To sensor shut-down place the magnet on decrease symbol. During this phase the output current (4÷20mA) force out to 1mA and the fault relay will be activate.

The power supply to the Sensor will be OFF

The display will show the message.

SENSOR OFF

This condition will remains active permanently. The sensor connection can be restored by placing the magnet on increase symbol (see section 6.2), only after have mounted the sensor completely the and fixing the screw. SMART S500 HC will be activated restarting from initial phase with a stabilization time for 30÷300 minutes before the normal working operation will start.

It is suggested to turn off the power to SMART S-500 for all maintenance operations.

Place again the magnet on “ENTER” , to terminate set up procedure without sensor power off.

Page 27: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 27 of 47

4.9.8 DISPLAY PELLISTOR VOLTAGE (Only smart S-500 HC)

To see Pellistor voltage place the magnet on “MENU” to enter in function set-up: FUNCTION

SET UP

Place the magnet on decrease symbol until you read on display the Pellistor Voltage pre set at 2,00 V depending on the type of beads used display will stay for 30 seconds.

V SENSOR 2,00 V

Note: This value will be between 1,90V and 2,10V with sensor in air free of gas. Control this value after replacement of new Sensing Element

4.9.9 DISPLAY OF RESIDENT FIRMWARE VERSION

Place the magnet on “ENTER” symbol to obtain the firmware version resident in microprocessor. The display will show for 5 seconds. :

S-500.XX V.0x.1.x

XX = SMART S-500 selected or requested at purchase.

4.10 SMART S-500 HC OPERATION During the normal operation the digital display will show the concentration value of gas present in the ambient. In status of normal condition the relay output of Warning and Alarm will be off (de energized), meanwhile the Fault relay will be maintained on (energized). When the Warning concentration will be reach the set point value the digital display will visualize the following messages in sequence:

Either Or Or WARNING WARNING WARNING 20%LEL W=25 ppm W=19 %

Followed Followed METHANE AMMONIA OXYGEN 20%LEL W=25 ppm W=19 %

The Warning relay K1W will actuate and, on the serial line, will be available the related information (Warning status, analogical , etc.). When the Alarm concentration will be reach the set point value the digital display will visualize the following messages in sequence: Either Or Or

ALARM ALARM ALARM 40%LEL A=35 ppm A=18 %

Followed Followed METHANE AMMONIA OXYGEN 40%LEL A=35 ppm A=18 %

Page 28: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 28 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

The alarm relay K2A will be activated and on the serial line will be available all related information (status of Warning, Alarm, analogical value, etc.). In case the gas concentration will Over range (over 100% LEL) the digital display will visualize the following messages in sequence:

ALARM OVER

ALARM RANGE

For HC and TX versions the Warning relay K1W and Alarm K2A will remain activated and on serial line will be available the related information (status of Warning, Alarm, Over range, analogical value, etc.). For OXY version only on serial line the information will be available for Over-range and analogue value. In this situation for HC version when the detector will reached Over range the power supply to the Pellistor sensor will be removed in order to protect its integrity, and each 30 seconds the sensor will be powered to verify the gas concentration value in the ambient, if the Over-range condition continues, the Pellistor will be turned off again and again. When the concentration value result lower than the full scale, the Pellistor will remain powered normally and the display will show the alarm condition and relative measure of value concentration. Available data on serial line will be adjourned consequently. When the concentration value will go down alarm condition the relative relay K2A will be deactivated and the display will show the pre-alarm condition and the relative measure of value concentration. When the ambient gas concentration decreases, down pre-alarm the relay K1W will be deactivated and the display will show the measure of value concentration. When any fault arrives to the system, the relay K3F will be deactivated and the output current will be 1mA. The display will show these messages:

FAULT: SENSOR CANNOT INITIALIZE

Either Or

FAULT FAULT SENSOR OPEN CIRCUIT SENSOR SHORT CIRCUIT

Or Or Or FAULT FAULT NEGATIVE -15V +15V DRIFT

See detail to reset Fault at Section 7 Diagnostic.

Page 29: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 29 of 47

SECTION 5 – CALIBRATION PROCEDURES

5.1 LOCAL CALIBRATION Caution: If you don’t have know gas concentration or not enough gas , don’t try to start calibration.

Place the magnet on “MENU” symbol the display will show: FUNCTION

SET UP

Place the magnet on decrease symbol until you read FUNCTION CALIBRATION. The display will show the following scroll message:

FUNCTION CALIBRATION

• Verify to be in free air from HC or toxic gases. • Prepare calibration kit with Nitrogen for OXY version.

Place the magnet on “ENTER” symbol this will confirm start calibration . In calibration condition the output current will be set at 2mA and all output function will be inhibited. The MODBUS on the serial line (IN-CALIB.) first function will be activated. Caution: If you don’t have know gas concentration or not enough place the magnet on “MENU” symbol two (2) time to exit of procedures. If you continue the display will show the following message describe the concentration calibration value, modify through increase or decrease symbols till you set the concentration calibrating gas that will used (written on the bottle in % L.E.L. or in ppm ):

• This function is not available for OXY version. TEST GAS

C = 50.0

Place the magnet on “ENTER” symbol this will proceed with calibration . • Apply nitrogen with flow of ¼ or ½ litre/minute (OXY version).

The instrument will make the Zero value calibration visualizing the following message: For HC & TX For OXY

ZERO IN PLEASE NITROGEN PROGRESS APPLY

When “ZERO” calibration is terminated, the following message will be visualized: ZERO

OK • Remove Nitrogen of Sensor (OXY version).

After zero has been verified or adjusted the procedure will go to “SPAN” calibration. The display will show:

For HC, TX OXY For HC, TX For OXY PLEASE TEST OXYGEN APPLY GAS 20.9 %V

Use the calibration kit device supplied by SES ASA ENGINEERING S.r.L., 0,5BAR cylinder with calibrating gas 50% L.E.L or 50% of Full Scale for ppm Toxic Gas with flow meter and

Page 30: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 30 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

valve to adjust the flow at ¼ or ½ liter/minute of selected gas. As soon as the concentration is passing 35% L.E.L. / ppm the digital display will show:

• Verify to be in free air for OXY version, or apply Oxygen at 20,9% vol.

SPAN IN PROGRESS

To complete the “SPAN” phase, the display will show the message of calibration completed, followed by the message that invite to remove the sample gas.

• The OXY version will show only the message CALIBRATION COMPLETE and then will exit automatically from this procedure.

CALIBRATION

COMPLETE PLEASE REMOVE

TEST GAS When the gas concentration will go down 30% of FS value, the message of calibration completed will be alternative to the message of waiting to return to zero value.

CALIBRATION COMPLETE

When the Zero value of the instrument will return to normal operative functions, actuating the output relay, setting the value of output current and showing the value of concentration detected.

5.2 REMOTE AUTOMATIC CALIBRATION The calibration procedure can be started remotely (when the remote calibration system as described in sez.4.7 is connected.) the calibration gas solenoid valve can be energized in two ways

• By the closing (to 0 VDC) of the input IC-0V on the connector J2 (on CS5) of the terminal board of the instrument.

• Through the setting of MODBUS variable (IN_CALIB.) through serial communication line RS-485 to actuate the remote Solenoid valve.

When actuated this function will be start the same sequence of calibration described in the previous section at paragraph 5.1. When Span Calibration starts, will be activated the open collector output (OC-0V on the connector J2 of the instrument terminal board), that through a relay will energize the solenoid valve mounted on the sample gas cylinder. This output, when SPAN will terminate, will be automatically deactivated. Note: The OXY version will activate the open collector output (OC-0V) during “ZERO” phase calibration.

WAIT FOR VALUE RETURN TO ZERO

Page 31: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 31 of 47

5.3 CALIBRATION ERROR During Zero calibration procedure if the sensor is not placed in clean free air, and in case of Oxy model is not in presence of Nitrogen, this generates a Zero calibration failure and the display will shows:

CALIBRATION ERROR

PLEASE REMOVE TEST GAS

During Span calibration will appear the same message if the gas applied is not the correct one or gas is not applied within 60 seconds. A new message will be displayed as: WARNING: In case calibration error will be displayed a new calibration should start in order to correctly calibrate the sensor. The Oxygen Detector can be calibrate also in Warning-Alarm conditions (see par 5.1) but the previous condition will be deleted, therefore the relays will be in OFF condition along Modbus signals, and the current signal will be 2mA (or other setting). The display will show :

CAUTION: THIS OPERATION DELETE ALM WARN SIGNALS

PROCEED? Y=ENTER

To proceed to have access at all menu, apply the magnet on “ENTER” for remain in

actual condition (go back) apply the magnet on “MENU” or wait 30 seconds.

HC Pellistor Sensor

TX-OXY Electrochemical Cells

SENSOR MUST BE CALIBRATED

Page 32: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 32 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

SECTION 6 – MAINTENANCE GENERAL NOTES SMART S-500 HC Combustible Gas Detector which has been correctly installed it needs anyway to be periodically checked. SES ASA ENGINEERING S.r.L. suggest to make the operation check each 3 months. The whole system must be tested almost one time per year. The check must include at least the following : 1. Verify that connection cables are right and right screwed on the terminal board. 2. Verify that the complete system responds always to installation requirements. 3. Verify the functionality of the module simulating the malfunction and alarm conditions,

putting the system in safe condition. 4. Supply a sniff of gas to check that the synthesized flame proof disk is not stacked

6.1 ELECTRONIC CIRCUITS OF SMART S-500 DETECTOR

CS1 - CPU and Display Circuit board ⇒

CS2 - Analog Pellistor Control Circuit board ⇒

CS3 - Power Supply Circuit board ⇒

CS4 - Output Circuit board ⇒

CS5 - Terminal Circuit Board ⇒

Page 33: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 33 of 47

SENSING ELEMENT REPLACEMENT

To replace the Sensing Element make the following operations:

1) Disconnect Sensor power supply following section 4.9.0 and 4.9.7 (Sensor Power Off)

2) Unscrew Allen Safety Screw (D) until Sensor Body Cover (B) can be removed, using the Allen Screwdriver (C) supplied, extract Sensor (Sensing Element) (A) by hand.

3) Now Insert the New Sensing Element taking care about the 3 pin position connections (A) this operation is simplify from the evidence “INSERT ↑” on Sensor Body Base to insert in coincidence of writing on Sensor.

4) Screwing the Sensor Body Cover (B) 5) Block the Sensor Body Cover (B) with the Allen Safety Screw (D) 6) Reconnect Power Supply to the Sensor following Section 4.9.7 (placing the

magnet on increase symbol) 7) Make the SMART S-500 calibration at the end of stabilizing phase of the Sensor

(Section 5.1)

6.2 STORAGE SMART S-500 does not need particular care for what concern the storage temperature. (Section.2.4)

Sensor Body Base

Sensor / Cell

Sensor Body Cover

Allen Safety Screw

A

B

Splash Guard &Calibration Adapter

D

Internal Detail Sensor

Magnet

C Allen Screwdriver

Page 34: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 34 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

SECTION 7 – TROUBLE SHOOTING

7.1 TROUBLE SHOOTING The following information are supplied as guide line to solve the most common problems. In case of malfunction, the repair of the sensor must be made only by SES ASA ENGINEERING S.r.L.. or authorized personnel or dealer. Any repair or misuse made by non qualified personnel will invalid the guarantee.

FAULT DISPLAY VISUALIZED

POSSIBILE CAUSE REMEDY

NEGATIVE DRIFT

Sensor out of calibration Sensor Element damaged

Calibrate the SMART S-500 HC Replace sensor Element

SENSOR OPEN CIRCUIT SENSOR CIRCUIT NOT CONNECTED

Sensor Element disconnected (HC / OXY Versions) Sensor broken

Check the internal wiring between sensor and printed circuit Replace the Sensor Element

SENSOR SHORT CIRCUIT SENSOR CIRCUIT SHORT

Wiring of sensor element in short circuit Sensor broken

Check the internal wiring between sensor and printed circuit. Replace sensor element

CALIBRATION ERROR

Time calibration expired Sensor element damaged

Calibrate SMART S-500 Replace Sensor element

SENSOR MUST BE CALIBRATED

Sensor out of calibration Pellistor sensor element damaged

Calibrate SMART S-500 Replace Sensor element

CANNOT INITIALIZE SENSOR

Sensor element damaged Replace Sensor element

+15V OUT Fault on power supply card Replace the electronic circuit CS3

-15V OUT Fault on power supply card Replace the electronic circuit CS3

7.2 SYSTEM MESSAGES SYSTEM MESSAGGE

SHOWN BY THE DISPLAY

CAUSE REMEDY

KEYBOARD LOCKED

Keyboard Locked by MODBUS through communication serial RS485

Enable keyboard resetting the toggle bit KEY-LOCK (See Section 4.7)

What indicated can be considered as suggestion in case of fault. Occasionally the fault can arise due to peculiar circumstances and so it become difficult to fix it. In case in which the problem remain also after all instruction made switch off the sensor following section 4.9.0 and 4.9.7 and start again. If the problem remain, contact SES ASA ENGINEERING representative or the factory service at +39-02-61037 ext.223 or 204 or send a E-mail to Missis Bianca Molena, [email protected].

Page 35: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 35 of 47

7.3 SMART S-500 SERIES AVAILABLE

SMART S-500.54 HC 100% L.E.L. (Low Power) ⇒ code 135012 Detector for hydrocarbons with Pellistor Sensor at 2V@175mA

SMART S-500.90 IR INFRARED HC 100% L.E.L. ⇒ code 135312 Detector for hydrocarbons with Infrared Sensor

SMART S-500.01 TX CO 100ppm ⇒ code 135034 Detector for Carbon Monoxide with E. Cell.

SMART S-500.02 TX H2S 20÷50 ppm ⇒ code 135093 Detector for Hydrogen Sulphide with E. Cell.

SMART S-500.04 TX SO2 20ppm ⇒ code 135015 Detector for Sulphur Dioxide with E. Cell.

SMART S-500.06 TX NO 20ppm ⇒ code 135047 Detector for Nitrogen Oxide with E. Cell.

SMART S-500.07 TX NO2 100ppm ⇒ code 135043 Detector for Nitrogen Dioxide with E. Cell.

SMART S-500.10 TX HCN 100ppm ⇒ code 135065 Detector for Hydrogen Cyanide with E. Cell.

SMART S-500.12 TX NH3 50÷200ppm ⇒ code 135052 Detector for Ammonia with E. Cell.

SMART S-500.13 OXY O2 11÷21% Vol. ⇒ code 135053 Detector for Oxygen depletion with E. Cell.

S-500 SERIES AVAILABLE S-500.57 HC 100% L.E.L. (Low Power) ⇒ code 135310

With Pellistor Sensor 2V@175mA for hydrocarbons S-500.56 HC 100% L.E.L. (Std. Power) ⇒ code 135037

With Pellistor Sensor 2V@300mA for hydrocarbons

The SES ASA ENGINEERING S.r.L. is available to supply its qualified long time experienced, engineers to help designing the best type of gas detector to meet international standard to protect your specific plant requirement to type of Gas to detect.

Page 36: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 36 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

7.4 SPARE PARTS AND ACCESSORIES Pellistor Sensor Low Power 2V@175mA HC ⇒ code 112400 Pellistor Sensor Std. Power 2V@300mA HC ⇒ code 112401 Infrared Sensor IR-HC ⇒ code 112402 Electrochemical Cell Sensor CO 100ppm ⇒ code 112403 Electrochemical Cell Sensor H2S 20÷50ppm ⇒ code 112405 Electrochemical Cell Sensor SO2 20ppm ⇒ code 112406 Electrochemical Cell Sensor NO 20ppm ⇒ code 112408 Electrochemical Cell Sensor NO2 100ppm ⇒ code 112409 Electrochemical Cell Sensor HCN 100ppm ⇒ code 112411 Electrochemical Cell Sensor NH3 50÷200ppm ⇒ code 112414 Electrochemical Cell Sensor OXY O211÷21% V. ⇒ code 112415 Splash Guard (adapter for calibration) ⇒ code 136100 Cable Gland ¾” ATEX (for armoured cable) ⇒ code 029055 Junction Box ATEX for remote S-500 Red ⇒ code 112320 Junction Box ATEX for remote S-500 Yellow ⇒ code 112309 Junction Box ATEX for remote S-500 Blue ⇒ code 112312 1810GC Card Controller (SMART S-500 HC) ⇒ code 034600 1810GC Card Controller (S-500 HC) ⇒ code 034624 1810GX Card Controller (SMART S-500 TX) ⇒ code 034625 1810GO Card Controller (SMART S-500 OXY) ⇒ code 034800 2402 Card Controller (SMART S-500 HC) ⇒ code 034561 2403 Card Controller (S-500) ⇒ code 034619 2404 Card Controller (SMART S-500 TX) ⇒ code 034562 2407 Card Controller (SMART S-500 OXY) ⇒ code 034563 Calibration Kit for Bottle 1 L. Use-Waste ⇒ code 107502

Pressure Reducer/Flow Meter, 5mt. tube, Splash Guard (adapter for calibration) Calibration Kit for Cylinder 5 L. ⇒ code 107503

Pressure Reducer/Flow Meter, 5mt. tube, Splash Guard (adapter for calibration) Bottle 1 liter (Use-Waste)

CH4 Methane 50% L.E.L. ⇒ code 113501 C3H8 Propane 50% L.E.L. ⇒ code 113502 H2 Hydrogen 50% L.E.L. ⇒ code 113504 C5H12n-Phentane 50% L.E.L. ⇒ code 113507 CO Carbon Monoxide 50 ppm ⇒ code 113508 N Nitrogen T (99,995%) ⇒ code 113710

Cylinder 5 liter empty (STD. valve) ⇒ code Cylinder 5 liter empty (INOX valve)* ⇒ code Cylinder 5 liters Recharged (cylinder not included)

CH4 Methane 50% L.E.L. ⇒ code 113521 C3H8 Propane 50% L.E.L. ⇒ code 113522 *NH3 Ammonia 25 ppm ⇒ code 113510 *NH3 Ammonia 50 ppm ⇒ code 113511 *H2S Hydrogen Sulphide 10 ppm ⇒ code 113512 *H2S Hydrogen Sulphide 25 ppm ⇒ code 113513 SO2 Sulphur Dioxide 10 ppm ⇒ code 113514 NO Nitrogen Oxide 10 ppm ⇒ code 113515 NO2 Nitrogen Dioxide 50 ppm ⇒ code 113516 *HCN Hydrogen Cyanide 50 ppm ⇒ code 113517

Other type of Gas available to request. * Required INOX Valve.

Page 37: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 37 of 47

SECTION 8 – LAYOUT

8.1 DIMENSIONS - INTERCONNECTIONS SMART S-500

SENSOR S-500

0v

24d

22d28z30z

+24Vdc

RED CABLE LINE SIGNALWHITE CABLE LINE +24Vdc

GROUND

SAFETY AREAHAZARDOUS AREA

Cable+ Shield

must be isolated

SHIELDthis side

from ground

CABINET

+24Vdc

0v

8z

28z

32z

2z 4z8d

28d

32d

2d 4d

Ch1 Ch2

1 2

Internal

43

W R B S

BLACK CABLE LINE 0V.

Power Supply Card

Power Supply Card

tube TEFLON 5mm (internal)

CYLINDER

KNOW GAS

CONCENTRATION

SMART S-500

1 Channel1810 GC (HC 4÷20mA)

CONTROL CARD

2 Channels

2402 (HC 4÷20mA)

LOGIC CONTROL CARD

CALIBRATION KIT

WITH CYLINDER

FLOW-METER0,5 LITRE MINUTE max

GAS-PRESSURE GAUGE0,5 BAR max

CYLINDER VALVE

View

FrontView

70mm

108mm

100mm

80mm

80mm

100mm

2 Hole8mm

Front Rear

Fixed PartFront View

Interchangeable Part View

Front Internal

Base-500C.S.

C.S.Base-501

MountingBracket

FIRST COMBUSTIBLE SENSORWITH FIELD REPLACEMENT ELEMENT

FIELD

2402% L.E.L.

SEL

TESTSET

INH

% L.E.L.

TX

RX

WD

H

H

M

ALARM

FAULTREADY

WARN

ALARM

FAULT

READY

WARN

1810GC

FAULTREADYWARNALARM

INHIBIT

INHSET

SPAN ZERO

% L.E.L.

2404ppm

SEL

TESTSET

INH

ppm

TX

RX

WD

H

H

M

ALARM

FAULTREADY

WARN

ALARM

FAULT

READY

WARN

1810GX

FAULTREADYWARNALARM

INHIBIT

INHSET

SPAN ZERO

ppm

1810GO

FAULTREADYWARNALARM

INHIBIT

INHSET

SPAN ZERO

% O²

2407% O²

SEL

TESTSET

INH

% O²

TX

RX

WD

H

H

M

ALARM

FAULTREADY

WARN

ALARM

FAULT

READY

WARN

1810 GX (TX 4÷20mA)1810 GO (OXY 4÷20mA)

2404 (TX 4÷20mA)

2407 (OXY 4÷20mA)

Page 38: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 38 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

8.2 DIMENSIONS - INTERCONNECTIONS S-500 (REMOTE) NOTE: In case of use same remote verify the junction box fixing parts.

Advisable to make 4 holes to adapt at every models SMART S-500, S-500.

SENSOR S-500

RED CABLE LINE SIGNALWHITE CABLE LINE +

GROUND

HAZARDOUS AREA

Cable+ Shield

must be isolated

SHIELDthis side

from ground

1 2

Internal

43

W R B S

BLACK CABLE LINE 0V.

tube TEFLON 5mm (internal)

CYLINDER

KNOW GAS

CONCENTRATION

S-500

CALIBRATION KIT

WITH CYLINDER

FLOW-METER0,5 LITRE MINUTE max

GAS-PRESSURE GAUGE0,5 BAR max

CYLINDER VALVE

View

FrontView

70mm

100mm

100mm

MountingBracket

FIELD

108mm

80 mm

80mm

2 Hole8mm

Front Rear

Fixed PartFront View

Interchangeable Part View

Front Internal

Base-500C.S.

C.S.Base-501

FIRST COMBUSTIBLE SENSORWITH FIELD REPLACEMENT ELEMENT

must be isolated

SHIELDthis side

from ground

1 2

Internal

43

W R B S

SMART S-500

View

FrontView

108mm

100mm

80mm

80mm

100mm

2 Hole8mm

MountingBracket

To Controller(Section 8.1)

Page 39: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 39 of 47

SECTION 9 – CERTIFICATE & ATTACCHED

9.1 SAFETY INSTRUCTION Safety Instructions nr. SES-OS-201 of 03.03.2004

GAS Detectors S-500, SMART S-500 HC, SMART S-500 IR,

SMART S-500 TX, SMART S-500 OXY SCOPE These safety instructions are referred to the installation, use and maintenance of S-500, SMART S-500 HC, SMART S-500 IR, SMART S-500 OXY SMART S-500 TX Gas Detectors and their use in classified areas with potential presence of explosive atmosphere. The equipment indicated in these instructions are conforms to 94/9/CE (ATEX) standard and certified for use in classified area conform to:

II 2 G EEx d IIC T6 The indication in these safety instructions must be followed in addition to the instructions information given in the operating and maintenance manual. GENERALITY These Series have been designed to detect Explosives and Toxic gases in dangerous areas such as Platforms, chemical and Petrochemical plants. The SMART S-500 Series can be connected directly to a power supply of 24VDC (30VDC Max.), and to interface systems standard 4÷20mA, while the S-500 Series sensor without short circuit can be connected to cards with current 450mA Max. and power of 5VDC Max. INSTALLATION

• Suitability of instrument to site installation In case in which the sensor is used in areas with explosion danger, it is necessary to verify that the identified type of sensor is suitable to the classified area and to the flammable products present in the plant as well as to the aggressive environment if any. The essential requisition of safety against explosion hazard in classified area are per European rules 94/9/CE of march 23rd 1994 (for what concern the instruments)and 1999/92/CE of December 16th 1999 (for what concern installations). Criteria for area classification against explosion risk are given by EN60079-10 rules. Technical requisition of the electrical installation in classified area are given by EN60079-14 rules. On the label, more than functionality data, are indicated also notified bodies authorized for certification.

Page 40: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SMART S-500 The Right Choice for Reliable Gas Monitoring SES-ASA ENGINEERING

Page 40 of 47 SMART S-500 Instruction Manual SES-KS-SMARTS500-E Rev.4

• Summary of label data related to safety in classified area

II 2 G Equipment for installation with presence of gas or vapors of category 2 suitable for zone 1 and with redundancy for zone 2.

EEx d Explosion Proof equipment

II C Equipment suitable for gas group IIC

T6 Equipment Class temperature (max. surface temperature)

CE European Marking conform to applicable rules

Marking conform to 94/9/CE directives and to relative technical rules.

CESI 04 ATEX 078 Name of the Laboratory issuing CE type certificate; 04 = year of certificate issuing ; 078 = certificate number .

N° 0035 Number of Authorized and Notified Center that make quality control of manufacturing system

A. T. -20°C ÷ +40°C -4°F ÷ +104°F Ambient Temperature referred to type of certificate

Note: a) Equipment certified for group IIC are suitable for class IIA and IIB; b) Equipment with class temperature T6 can be suitable also for classes with higher

temperature (T5, T4, T3, T2, T1);

• Advices for installation The detector must be fixed with sensor body locking It is not permitted to modify or prick the detector housing To fix use holes already made in the housing box or fixing plate. It is forbidden to open the sensor housing in classified areas under power Cable entry

Accessories used for cable entry or closing cap of any eventual hole not used, must be ATEX certified in accordance to EN50014 and EN50018

rules with marking II 2 G EEx d IIC Ground connection

The sensor housing must be connected through a ground terminal having unscrewing and un slacken device with ground voltage controlled.

Page 41: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

Instruction Manual SES-KS-SMARTS500-E Rev. 4 SMART S-500 Page 41 of 47

• Electrical Connections It is strongly suggested to use 2-3-4 shielded wires cable or armored cable. The

maximum resistance of sensor loop connection to Pellistor (Table 1) is of 50 Ohm, meanwhile the connection from the electronic to a transmitter is of 600 Ohm (Table 2).

. Table 1 (Pellistor sensor ) Table 2 (transmitter)

mm2 AWG Meter Feet Mm2 AWG Meter Feet 2.5 14 2320 7600 2.5 14 1372 4500 1.5 16 1460 4800 1.5 16 685 2250 1 18 910 3000 1.0 18 488 1600

VERIFICATION AND MAINTENANCE Verification and maintenance of certified equipment must be made as per criteria indicated in European Standard EN60079-17.

REPAIR In case of malfunction or damage, it is suggested to send the equipment to SES ASA ENGINEERING S.r.L. that will provide the repair under guarantee conditions. In the case in which the repair will not be made by the manufacturer or manufacturer authorized dealer, they must be made anyway as per criteria indicated in IEC 79-19 rules and in repair center having all necessary equipment and tools for correct repair and verification with adequate technical know-how related to protection.

Page 42: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

9.2 CERTIFICATE TÜV

Page 43: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING SMART S-500 The Right Choice for Reliable Gas Monitoring

9.3 CE CONFORMITY DECLARATION

SES ASA ENGINEERING S.r.L. Via Carolina Romani 8/10

20091 BRESSO (MI) ITALY

Attesta Sotto la Propria Esclusiva Responsabilità Che Attest Under His Responsibility That

PRODOTTO SERIE : SMART S-500 PRODUCT SERIES : SMART S-500

MODELLO : SMART S-500.** *** MODEL : SMART S-500.** ***

Questa Dichiarazione è Conforme Alle Seguenti Direttive e Norme: This Declaration Is In Accordance

With Following Directives: 94/9/CE ATEX

EN50014-EN50018 Con marcatura

With mark

II 2 G EEx d IIC T6

Certificato di esame CE del tipo EC Type Examination Certificate

N° CESI 04 ATEX 078

In Rappresentanza Legale Del Costruttore In Legal Representation of Manufacturer

SES ASA ENGINEERING S.r.L.

Page 44: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

9.4 ATEX CERTIFICATE

Page 45: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art
Page 46: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

NOTE:

Page 47: SMART S-500 HC Combustible & Flammable Gases SMART S-500 TX Toxic …ses-enser.com/users/files/products_asa/SES-KS-SMARTS500... · 2018-02-19 · SMART S-500 is a State of the Art

SES-ASA ENGINEERING S.r.L. ENGINEERING & MANUFACTURING