S M A R T C H A R G I N G C O N T R O L L E R
Installation Manual
E N E R G Y M A N A G E R
2
Safety Information
3
Manual for Maxem Home Energy Manager. Publication Date: November 1, 2016
Safety Information
Liability
• Installonlybyacertifiedelectrician.
• Completely follow the instructions.
• Usethisdevicewithpurposesitisdesignedfor,asdescribedinthismanual.
• Maxem works only after online activation.
• FailuretofollowtheabovewarningscanleadtoincorrectMaxeminstallation.
This can lead to overload of the power supply, damage to installations and
chargingstations,electricshocksorfire.
Cohere isnotresponsibleforthe installationofMaxemandforanydamagearisingfromincorrect implementation of the installation manual. Nor for damage resulting fromtypographical errors or misinterpretations of text or images.
AllinformationinthisdocumentisthecopyrightandintellectualpropertyofCohereEnergySolutionsB.V.Materialinthisdocumentmaynotbemodified,reproducedorcopied,inpartorinwhole,withouttheexplicitwrittenconsentofCohereEnergySolutionsB.V.Additionalinformation is available upon request.
MaxemisaregisteredtrademarkofCohereEnergySolutionsB.V.
S M A R T C H A R G I N G C O N T R O L L E RC H A R G E S M A R T E R
Installandusethisproductonlyaftercarefulreadingofthemanual.
Thisproductisdoubleinsulated.
Indooruseonly.
Productcontainselectronics.Donotthrowitinthehouseholdwaste.
ThisproductisdesignedforovervoltagecategoryIII.
ThisproductmeetsalltherequirementssetbytheEUfor
productsafety.
Productsymbolsstatements
©2016 COHERE ENERGY SOLUTIONS B.V.
Tip Warning
Symbolsinthisdocument
Questions or improvements
Ifyouseeanyerrorsordefects,ifyouhaveideasabouthowtoimprovethismanualortheMaxemsystem,[email protected].
Index
What is Maxem? 5
ProductSpecifications 6
Preparation 8
Feedingandfuseprotection 10
Installation Steps
01 - Mounting on the wall 11
02 - Connecting to power supply 12
03 - Connecting solar panels 12
Option 3.1 - Connecting current coils to solar panels 12
Option 3.2 - Connecting MID kWh-meter to solar panels 14
04 - Connecting charging station
Option 4.1 - Connecting KEBA charging station 15
Option 4.2 - Connecting ICU charging station 17
Option 4.3 - Connecting Tesla Wall Connector 18
Option 4.4 - Connecting EV-Box charging station 20
05 - Connecting Maxem 21
06 - Commissioning 22
07 - Telephone installation check 23
Annex 1 - Troubleshooting 24
Annex 2 - Setting MID kWh-meter 27
Annex 3 - Crimping RJ connectors 28
EC Declaration of Conformity 30
What is Maxem?
Fromthemeterbox,Maxemmeasurestheenergyuseinthehouseandtheenergy
generationofsolarpanels.Basedonthisinformation,itmanagestheloadingstation,
batteryorheatpumpsmartly.Thus,ithelpstheusertomakeeasierandcheaperuseof
sustainable energy.
4 5
01-Voorbereidingenvooraf
Content of the box
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
MID kWh-meter extension
Maxemincludingmountingplate 6x Divisible current coil
L3L2L1
MX
2x Cable Splitter
RS485 cable
Network cablePower cable
4x Screws 3x20 2x RJ10 4P4C connector
Productspecifications
2x Tie-wrap
Specifications
Dimensions 184 mm (L) x 167 mm (W) x 55 mm (H)
Weight 700g
Working temperature 10°C to 35°C
Storage temperature 0°C to 60°C
Maximalhumidity 80%
Protection class II(doubleinsulated)
Seal IP20
Working height 0 to 2,000 m
EMC EN 61326-1 (2013), EN 61000-3-2, 61000-3-3
Safety EN61010-1 (2010), EN61010-2-30 (2010)
Immunity EN 61326-1 (2013)
Overvoltage category 300V/CAT III
Input power 110 - 240V. 50/60Hz. Maximum 2,75W
Power coils Up to 50A
SETOK
1 2 3
MID kWh-meter P1 port
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Definitionsinput/outputportsandLEDindicators
Ethernet port to charging station
Ethernet port to Internet Router
Connection 230V power supply
Power coils solar panel
Available portCurrent measurement
Power coils main power supply
RS485 port 1
RS485 port 2
RS2RS1P1 CT3CT2CT1
6 7
Necessary tools
• Crossheadscrewdriver,sizesmall.
• Flatheadscrewdriver,sizemini<3mm.
• Flatheadscrewdriversizelarge.
• RJ45 (8P8C) crimping pliers.
• RJ10 (4P4C) crimping pliers.
• Cable Tester for UTP cables.
• A correct circuit breaker or earth leakage circuit breaker with proper fusing value. See
p.10todeterminefusing.
• Schukosocketsfor230VpowersupplyMaxem(ifnotalreadyavailable.
• UTP(CAT5orCAT6)datacableforconnectingchargingstationtoMaxem.
• RJ45 (8P8C) connectors for UTP cable.
• CableendsleevesforUTPcores(onlyforTeslaWallConnectororEV-Box).
Necessary materials
• FreespaceforMaxemwithconnectedwiringatthebottom.
• FreeSchuko230VsocketonPhase1(L1)forfeedingMaxemorfreespacetoplacea
new one.
• FreeEthernetportforInternetconnectedmodemorrouter.
• AnUTPcablemustbepulled (oralreadybeavailable) fromMaxem to the charging
station.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Wiring at the bottom
184mm
55,50mm
Environmental Requirements
20mm
70mm
20mm20mm
01-VoorbereidingenvoorafPreparation
WiredInternetaccess
MaxemmustbeconnectedtoawiredInternetconnection.Thefollowingisneeded:
• ModemorrouterconnectedtoInternet.
• A DHCP connection from the network to Maxem.
• MaxemshouldbeabletodoDNSrequests.
• MaxemmayalsobeplacedinaDMZ(demilitarizedzone)onaseparateVLAN.
Compatible with Maxem charging stations
ICU Compact
Tesla Wall Connector
ICU EVe mini KEBA P20/P30ICU EVe ICU Twin
EV-Box HomeEV-Box Business(G3 controller) (G3 controller)
8 9
Tesla Wall Connector itself does not measure current, for this a MID kWh-meter is needed. It can be supplied with Maxem.
Fusing charging station
Maxemisacontrolsystemthatregulatestheloadofthechargingstation.Therefore,itcan
be calculatedaccording to theNEN1010witha lowerequal time factor*.Maxemmakes
surethatthechargingstationislessloadedwhenthereismorechargeinthehouse.The
chargingstationcanthereforebefusedtoavaluehigherthannormal,butnothigherthan
thethresholdvalueofthemainpowersupplyterminal.
Power supply Charging station capacity Maximal fusing, charging station
3-phase 25A 3-phase 32A 3-phase 25A
3-phase 25A 3-phase 16A 3-phase 16A
3-phase 35A 3-phase 32A 3-phase 32A
1-phase 25A 1-phase 32A 1-phase 25A
1-fase 40A 1-fase 32A 1-fase 32A
*(NEN 1010:2015 722.311) The equal time factor is the ratio between the maximum simultaneous load of a
group of electrical devices or consumers within a certain period and the sum of their individual maximal loads
within the same period.
01-VoorbereidingenvoorafFeedingandfuseprotection
HangMaxem on a clean,moisture-free wall. Use the suppliedmounting plate and
screwsforthis.TakeintoaccountsufficientspacearoundtheMaxem.
01 - Mounting on the wall
Wiring at the bottom
70mm
20mm
20mm20mm
10 11
A.
230V power supply from Maxem
Maxem measures the power supply as follows:
• Amperage:divisiblecurrentcoilsmeasurethecurrentthroughthephasewires.
• Voltage: internal voltmeter in Maxem with the voltage from the 230V power supply.
For a correctmeasurement it is necessary to know fromwhich phaseMaxem is fed. In
MaxemitisstandardlyinstalledthatthesupplyisonPhase1(L1).
02 - Connecting to power supply
ConnectthecablesplittertoMaxemportCT1,intendedforthemainpowersupply
terminal.
Option 3.1 - Connecting current coils to solar panels
Openthemeterboxusingintendedtools.
Click thesuppliedcurrentcoilsaround theL1phasewireof themainpowersupply
terminal. Connect this power supply coil to L1 of the cable splitter.
ConnectthecablesplittertoMaxemportCT2,intendedforthesolarpanels.
Turnoffthemainpowersupplyterminalofthefusebox.
03 - Connecting solar panels
RepeatthesestepsforL2andL3incaseofa3-phaseconnection.
ClickthesuppliedcurrentcoilsaroundtheL1phasewireofthesolarpanels.
ConnectthecurrentcoiltoL1ofthesuppliedcablesplitter.
RepeatthesestepsforL2andL3incaseofa3-phasesolarinverter.
Makesurethecurrentcoil(s)areconnectedintherightdirection.
See right page.
Makesurethecurrentcoil(s)areconnectedintherightdirection.
See right page.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
L3L2L1
MX
L3L2L1
MX
O.OFF O.OFF O.OFF O.OFF
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar
Grid / Solar
Home Grid / Solar
Home
O.OFF O.OFF O.OFF O.OFF
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar
Direction of currentMain power supply
terminal
L1 L2 L3 L1 L2 L3
CT1
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
CT2CT1 CT3CT2 CT3
L3L2L1
MX
Connect everything to the right phase!
Main connection Solar panels
12 13
A.
B.
C.
D.
E.
F.
A.
B.
C.
D.
E.
Direction of current
Solar panels
Option 4.1 - Connecting KEBA charging station
Install a circuit breaker or earth leakage circuit breaker at the maximal
power available. See p. 10.
Follow the installation instructions of the charging station. These
instructions can be found in the installationmanual of the charging
station.
Placea suitableUTP (CAT5orCAT6) cable from the charging station toMaxemand
clenchRJ45connectorsonbothsides.
ConnecttheUTPcabletotheEthernetportofthechargingstationandtheETHport
of Maxem.
It is advisable to test the network cable with the help of a cable tester.
04 - Connecting charging station
Connect the RS485 cable to the kWh-meter as follows:
• PortC:Greencore
• PortB:Whitecore
• PortA:Browncore
Place the kWh-meter on a DIN-rail in the installation cabinet.
Option 3.2 - Connecting MID kWh-meter to solar panels
Connect the RS485 cable to RS1 port on Maxem.
Connect this in such a way, that it measures the output of the solar inverter.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
RS1
SettheaddressingofthekWh-meteron001.Asaresult,Maxemcan
configureitself.SeeAnnex2howtosettheaddressing.
DSW1 - Power (paragraph above)DSW2-Addressing(paragraphbelow)
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Data activity on ETH portMaxem
Data activity on ETH portKeba P20 or P30
UTP cable with RJ45 connectors
14 15
A.
B.
C.
D.
SETOK
1 2 3
Distribution board
Solar panels
Dir
ectio
n of
cur
rent
Connecting RS485 cable to kWh-meter
A.
B.
C.
D.
E.
RS1 port for MID kWh meter
PutDSW1.3ON.Smartchargingwillbeactivated.
SettheDIPswitchesofDSW1onthemaximalavailablepower.Andleavetherestofthe
DIP switches on OFF.
Example 10A
DSW 1.6 OFF
DSW 1.7 OFF
DSW 1.8 OFF
10A
13A
16A
Maximal current strength
20A
25A
32A
Settings on DSW11 of 3-phase
See installation manual KEBA P20/P30 for more information
Option 4.2 - Connecting ICU charging station
Install a circuit breaker or earth leakage circuit breaker for each charging
station at the maximal power available. See p. 10.
Follow the installation instructions of the charging station. These
instructions can be found in the installationmanual of the charging
station.
Placea suitableUTP (CAT5orCAT6) cable from the charging station toMaxemand
clenchRJ45connectorsonbothsides.
ConnecttheUTPcabletotheEthernetportofthechargingstationandtheETHport
of Maxem.
It is possible to update the charging station firmware. This can be done via ICU Connect, as soon as the charging station is online. ICU or Cohere can assist you with this.
It is advisable to test the network cable with the help of a cable tester.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Data activity on ETH port Maxem
ETH port ICU UTP cable with RJ45 connectors
TakeoffthevoltageonKebaP20/P30(theDIPswitchsettingsonlybecomeactiveafter
a reset of the charging station).
16 17
A.
B.
C.
D.
E.
F.
G.
Rotary switch
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Set the Wall Connector as Slave by placing the rotary switch in F position.
CrimpthesuppliedRJ104P4CconnectoronMaxemsideonthedatacable.Twowires
mustbeconnected:
• Connect wire 1 (orange-white) to Pin 1
• Connect wire 2 (orange) to Pin 2
Connect the RJ10 4P4C connector to RS2 Maxem port.
ConnectthedatacabletotheIN(D+andD-)portoftheWallConnector
clamp block:
• Connectthewirefrompin1onD+
• Connect the wire from pin 2 to D-
RS2 port for Tesla Wall Connector
LED indications Tesla Wall Connector
RS2 Pin 1 Pin 2
LEDabovelightsupingreen:everythingisconnectedproperly
MiddleLEDisblinkingred:setasSlavebutnoconnectionwithMaxem
Lower LED burns 5 secs. green: correctly set as Slave at start
RJ10 4P4C
See installation manual Tesla Wall Connector for more information
Tab above
Option 4.3 - Connecting Tesla Wall Connector
Install a circuit breaker or earth leakage circuit breaker for each charging
station at the maximal power available. See p. 10.
Follow the installation instructions of the charging station. These
instructions can be found in the installationmanual of the charging
station.
Place a suitable UTP (CAT5 or CAT6) of the Wall Connector to Maxem. (To prevent
electromagneticinterferenceattheRS485connection,itisrecommendedtouseFTP
CAT6cableatdistancemorethan25m.Max:50m).
SETOK
1 2 3
Connect the RS485 cable to the kWh-meter as follows:
• PortC:Greencore
• PortB:Whitecore
• PortA:Browncore
Place the kW-meter on a DIN rail in the installation cabinet.
Distributionboard
Chargin station
Dir
ectio
n of
cur
rent
Connect it in such a way that it measures the consumption of the charging station.
Connection of RS485 cableto kWh-meter
SettheaddressingofthekWh-meterto002.Asaresult,Maxemcanconfigureitself.
SeeAnnex2howtosettheaddressing.
18 19
A.
B.
C.
D.
E.
F.
J.
I.
H.
G.
L.
Tesla Wall Connector does not measure kWh itself, therefore a MID kWh-meter is needed.
Cores for pull relief
Connect the RS485 cable to RS1 port on Maxem.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
RS1D.
RS1 port for MID kWh-meter
Option 4.4 - Connecting EV-Box charging station
Install a circuit breaker or earth leakage circuit breaker at the maximal
power available. See p. 10.
Follow the installation instructions of the charging station. These
instructions can be found in the installationmanual of the charging
station.
Place a suitable UTP (CAT5 or CAT6) of the EV-Box to Maxem. (To prevent electromagnetic
interferencewiththeRS485connection,itisrecommendedtouseFTPCAT6cableat
distancemorethan25m.Maximaldistanceis50m).
CrimpthesuppliedRJ104P4CconnectoronMaxemsideonthedatacable:
• Connect wire 1 (orange-white) to Pin 1
• Connect wire 2 (orange) to pin 2
• Connect two other wires for pull relief
Connect the RJ10 4P4C connector to Maxem RS2 port.
Connectthesetwocoresofthedatacabletothequadrupolecommunicationportof
EV-Boxmodem:
• Connect one wire (orange-white) to Port A
• Connect wire 2 (orange) to port B
• Theremainingportsdonothavetobeconnected
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
RS2 port for charging station
Scheme EV-Box controller
Pin 1Pin 2
ConnectMaxemwiththesuppliednetworkcabletothemodemorrouterconnected
to the Internet.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
Ethernet port to Internet Router
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
ConnectMaxemwith the included 230V feeding cable to a plug on themeter box.
MakesurethisplugisconnectedtoPhase1ofthepowersupply.Maxemmeasuresthe
voltage through the power supply. It is therefore important to know to which phase the
powersupplyisconnected.
CheckthatallcomponentsareconnectedtoMaxem.
20 21
12V/DC
ABGND
Tab above
A.
B.
C.
D.
E.
F.
A.
B.
C.
A
A
167
184
55.50
SECTION A-A
Client:
Rev. nr:
1:1Units:
1/2
CES-01 - Enclosure
MHVol. (mm³):
mm
Sheet:
Scale:
-
CohereDate:
Drawn:
File reference:Drawing name:
-Material:17-02-2016
Maxem 4 Assembly
A3
Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]
<0,2x45° or R<0,2
Ra 0,8 um
Default length tolerances: DIN 7168
±20'Default angle tol.:
Finish:
Default edges:
Roughness:
Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000
RS2
05 - Connecting Maxem
Cores for pull relief
06 - Commissioning
22
Maxemrunsduringcommissioninganautoconfigurationprocesswhereallmeasuring
points,chargingstationsandotherdevicesarerecognizedandset.Followthefollowing
steps:
Putonthechargingstationorrestartittotakeoffthecurrenttemporarilyandputit
on again.
Connect the 230V power supply to Maxem or restart Maxem to pull the 230V supply
cabletemporarilyfromtheplugandplugitinagain.
23
TherearedifferentLEDsonMaxemwherebyyoucancheckwhethercomponentsareconnectedproperly.
RS2RS1P1 CT3CT2CT1
Maxem starts
LEDindicationsonMaxem
Installation OK Installation NOT YET OK
AutoconfigOKConnection web portal OK
AutoconfigNOTOKConnection webportal OK
AutoconfigOKConnection webportal NOT OK
Maxem back to factory settings, see chapter Troubleshooting
Communication OK There is a connection, but communication NOT OK
CentralLEDindicator
LEDindicatorsforinput/outputports
Noconnectiondetected
A.
B.
LED indication: blinks 3x
LED indication: blinks 4x
LED indication: blinks 2x
LED indication: blinks continuously
LED indication: lights continuously
After successful installation, Maxem sends a current limiting value to the charging station. In case of non-successful installation, this is not the case. This results in OVERLOAD OF THE POWER SUPPLY. Cohere should therefore always give OK for a successful installation.
A. CallCohereinordertoactivateMaxem.Coherecontrolsthewholeworkofthe
deviceatadistanceandgives“OK”forasafeinstallation.
020 770 87 13
07 - Telephone installation check
Maxemdoesnotconnecttotheonlinebackend
• ControlthatMaxemnetworkconnectionisactive.Ifthereisadataconnection,aLED
burnsorangeontheLANport,greenoritisoff.Ifthereisactivityontheconnection,
an orange LED is blinking.
• ControlifthereisanactiveInternetconnectionontheconnectedrouter.
• ControlwhethertheconnectedUTPcableiscorrectlyconnectedwiththehelpofa
cable tester.
• MakesurethataDHCPconnectioncanbemadetoMaxemfromthenetwork.
• MakesurethatMaxemcandoDNSrequeststhroughthenetworktoconnecttothe
backoffice.
• ItispossibletoplaceMaxeminaDMZ(demilitarizedzone)onaseparateVLAN.
• RestartMaxembyturningitoffandon.AnyproblemswiththeIPaddressingcanthus
befixed.
Autoconfigurationisnotsuccessful
• RS485connectedchargingstation:controlwhethertheRJ10(4P4C)connectoriswell
crimpedintotheRSportofMaxem.SeeAnnex3howtocrimpRJconnectorsthebest.
• EthernetConnectedchargingstation:MakesurethatgreenandblinkingorangeLED
in the charging station are on for an active connection with Maxem. If this is not the
case,thereisapossibleerrorintheinstalledUTPcable.
• Restartthechargingstationbyputtingthevoltageoffandonagain.
• Makesurethecorrectfirmwareisplacedonthechargingstationandthatis
compatible with Maxem. An employee of Cohere can help.
Thechargingstationisnotdetectedornotcorrectlydetected
• TurnoffMaxem.Waitfor10seconds.
• Then turn on Maxem. If there is a charging station, switch the group of the charging
stationoffandonagain.Theautoconfigurationwillrunagain.
24 25
Annex 1 - Troubleshooting
Thecardoesnotstartduringcharging
• Performarebootofthegroupofthechargingstationinthemeterbox(turnoffthe
group,waitfor10seconds,andthenturnonthegroupagain).Makesurethatthe
chargingcableisnotconnectedtothecar.
• An authorization problem for ICU charging stations may occur, which prevents the
chargingstationfromgivinga“permission”tostartachargingsession.Anemployee
of Cohere can help.
The measurements of the power supply are not logical
• Incasethesolarpanelsareavailable,turnoffthegroup.
• Makesurethepowersupply(socket)ofMaxemisconnectedtoL1.
• Makesurethateachcurrentcoilisconnectedtothephasecorrespondingtothe
labels of the cable splitter.
• Makesurethecurrentcoilsaredirectedcorrectly.Thearrowonthecurrentcoil
followsthecurrentdirectionofthenettothegroupsofthehouse.
• MakesurethecablesplitterisconnectedtoMaxemCT1port.
The measurements of the solar panels are not logical
• Makesurethepowersupply(socket)ofMaxemisconnectedtoL1.
• Makesurethateachcurrentcoilisconnectedtothephasecorrespondingtothe
labels of the cable splitter.
• Makesurethecurrentcoilsaredirectedcorrectly.Thearrowonthecurrentcoil
followsthecurrentdirectionofthesolarinvertertothegroupsofthehouse.
26 27
Maxem can measure different devices through an external MID certified kWh-meter.
In order autoconfiguration could function properly, the kWh-meter must be set on the
correspondingaddress.Thisisdoneasfollows:
Device Addressing
Solar #1 001
Solar #2 011
Charging station #1 002
Charging station #2 012
Heat pump #1 004
Heat pump #2 014
Holdthebuttonfor2sec.toenterthemenu,ortogoupinthemenu.
Scrolldownthroughmenuoradjustsettingvalue.
Presstogetintoamenuitemoracceptanadjustment.
Presstoadjustasetting.
Navigation through the menu of the ABB B23/B24 kWh-meter
IfyouseethisiconinthedisplayofthekWh-meter,thereisanactivedataconnectionwithMaxem.
Locationofthe‘addressing’functioninthemenustructure
SETOK
1 2 3
Addressingexample
Numberofdevices
Device type
StandardaddressingkWh-meter
Device Addressing
Solar 001
Charging station 002
Heat pump 004
Devices
Annex 2 – Installation kWh-meter
• Checkthemaximalchargingcapacityofthecar.Forexample,theTeslaModelSneeds
aduochargertocharge3x24A.AModelSwithasinglechargerchargesmaximum
3x16A.
• For KEBA charging stations: Check that the DIP switches are set correctly.
• ToolowfusingwasappliedatMaxemwhenconfiguring.AnemployeeofCoherecan
helptoadjustit.
Thecarischargedtooslowfortheavailablecapacity
Thecarischargedtoofastfortheavailablecapacity
• AtoohighfusingwasappliedatMaxemwhenconfiguring.AnemployeeofCoherecanhelptoadjustthis.
234
1
TroubleshootingAnnex 3 – Crimping RJ-connectors
28 29
Materials
• Crimpingpliers(forRJ10and/orRJ45connectors)
• Scissors or pliers
• Sharp (Stanley) knife
• RJ10 or RJ45 connectors
Steps
Cutthecoresinastraightlinewithapairofpliersinordertohavethemallwiththe
same length.
Stripapproximately3cmoftheoutercoverwithasharp(Stanley)knife.Theindividual
coresshouldnotbedamaged.
A.
B.
InsertthecoresintotheRJ10orRJ45connector.Makesurethatthecoresareplacedin
thecorrectorder.FortheRJ10connectoritisrecommendedtoplace2additionalcores
for pull relief.
C.
Makesurethatthecoresareinserteddeepenoughintotheconnectorinordertohave
themfirmlyclamped.
D.
Placetheconnectorwiththeinsertedcableintothepliers.Clenchitinordertohave
thecoressecuredandexposed. Itmaybenecessary toclench thepliersfirmly two
times or more.
E.
Double-check that all cores are fully inserted. If this is not done correctly, the cable
will not work properly.1234
12345678
4P4C (RJ10)
Tab above
8P8C (RJ45)
Tab above
Connectiondiagrams
Cores for pull relief
We,
Cohere Energy Solutions B.V.WillemdeZwijgerlaan3501055RDAmsterdam,theNetherlands
following the provision of the following EC Directives:• 2006/95/EC The Low Voltage Directive• 2004/108/EEC The Electromagnetic Compatibility Directive
Herebydeclarethattheproduct:MaxemEnergyManager4.0isinconformitywiththeapplicablerequirementsofthefollowingdocuments:
Emissions• EN 61326-1 (2013)• EN61000-3-2(2006)+A1(2009)+A2(2009)• EN 61000-3-3 (2008)
Immunity• EN 61326-1 (2013)
Safety• EN 61010-1 (2010),• EN 61010-2-030 (2010)• EN 61010-2-023
Signee Date Place Signature
Jan Willem HeinenCEO
1 August 2016 Amsterdam
30 31
TroubleshootingEC Declaration of Conformity
C H A R G E S M A R T E RWillemdeZwijgerlaan350|1055RD|Amsterdam|TheNetherlands+31(0)207708713|[email protected]|www.cohere.eu