S M A R T C H A R G I N G C O N T R O L L E R

Installation Manual

E N E R G Y M A N A G E R

Page 2: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

2

Safety Information

3

Manual for Maxem Home Energy Manager. Publication Date: November 1, 2016

Safety Information

Liability

• Installonlybyacertifiedelectrician.

• Completely follow the instructions.

• Usethisdevicewithpurposesitisdesignedfor,asdescribedinthismanual.

• Maxem works only after online activation.

• FailuretofollowtheabovewarningscanleadtoincorrectMaxeminstallation.

This can lead to overload of the power supply, damage to installations and

chargingstations,electricshocksorfire.

Cohere isnotresponsibleforthe installationofMaxemandforanydamagearisingfromincorrect implementation of the installation manual. Nor for damage resulting fromtypographical errors or misinterpretations of text or images.

AllinformationinthisdocumentisthecopyrightandintellectualpropertyofCohereEnergySolutionsB.V.Materialinthisdocumentmaynotbemodified,reproducedorcopied,inpartorinwhole,withouttheexplicitwrittenconsentofCohereEnergySolutionsB.V.Additionalinformation is available upon request.

MaxemisaregisteredtrademarkofCohereEnergySolutionsB.V.

S M A R T C H A R G I N G C O N T R O L L E RC H A R G E S M A R T E R

Installandusethisproductonlyaftercarefulreadingofthemanual.

Thisproductisdoubleinsulated.

Indooruseonly.

Productcontainselectronics.Donotthrowitinthehouseholdwaste.

ThisproductisdesignedforovervoltagecategoryIII.

ThisproductmeetsalltherequirementssetbytheEUfor

productsafety.

Productsymbolsstatements

©2016 COHERE ENERGY SOLUTIONS B.V.

Tip Warning

Symbolsinthisdocument

Questions or improvements

Ifyouseeanyerrorsordefects,ifyouhaveideasabouthowtoimprovethismanualortheMaxemsystem,[email protected].

Page 3: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Index

What is Maxem? 5

ProductSpecifications 6

Preparation 8

Feedingandfuseprotection 10

Installation Steps

01 - Mounting on the wall 11

02 - Connecting to power supply 12

03 - Connecting solar panels 12

Option 3.1 - Connecting current coils to solar panels 12

Option 3.2 - Connecting MID kWh-meter to solar panels 14

04 - Connecting charging station

Option 4.1 - Connecting KEBA charging station 15

Option 4.2 - Connecting ICU charging station 17

Option 4.3 - Connecting Tesla Wall Connector 18

Option 4.4 - Connecting EV-Box charging station 20

05 - Connecting Maxem 21

06 - Commissioning 22

07 - Telephone installation check 23

Annex 1 - Troubleshooting 24

Annex 2 - Setting MID kWh-meter 27

Annex 3 - Crimping RJ connectors 28

EC Declaration of Conformity 30

What is Maxem?

Fromthemeterbox,Maxemmeasurestheenergyuseinthehouseandtheenergy

generationofsolarpanels.Basedonthisinformation,itmanagestheloadingstation,

batteryorheatpumpsmartly.Thus,ithelpstheusertomakeeasierandcheaperuseof

sustainable energy.

4 5

Page 4: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

01-Voorbereidingenvooraf

Content of the box

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

MID kWh-meter extension

Maxemincludingmountingplate 6x Divisible current coil

L3L2L1

MX

2x Cable Splitter

RS485 cable

Network cablePower cable

4x Screws 3x20 2x RJ10 4P4C connector

Productspecifications

2x Tie-wrap

Specifications

Dimensions 184 mm (L) x 167 mm (W) x 55 mm (H)

Weight 700g

Working temperature 10°C to 35°C

Storage temperature 0°C to 60°C

Maximalhumidity 80%

Protection class II(doubleinsulated)

Seal IP20

Working height 0 to 2,000 m

EMC EN 61326-1 (2013), EN 61000-3-2, 61000-3-3

Safety EN61010-1 (2010), EN61010-2-30 (2010)

Immunity EN 61326-1 (2013)

Overvoltage category 300V/CAT III

Input power 110 - 240V. 50/60Hz. Maximum 2,75W

Power coils Up to 50A

SETOK

1 2 3

MID kWh-meter P1 port

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Definitionsinput/outputportsandLEDindicators

Ethernet port to charging station

Ethernet port to Internet Router

Connection 230V power supply

Power coils solar panel

Available portCurrent measurement

Power coils main power supply

RS485 port 1

RS485 port 2

RS2RS1P1 CT3CT2CT1

6 7

Page 5: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Necessary tools

• Crossheadscrewdriver,sizesmall.

• Flatheadscrewdriver,sizemini<3mm.

• Flatheadscrewdriversizelarge.

• RJ45 (8P8C) crimping pliers.

• RJ10 (4P4C) crimping pliers.

• Cable Tester for UTP cables.

• A correct circuit breaker or earth leakage circuit breaker with proper fusing value. See

p.10todeterminefusing.

• Schukosocketsfor230VpowersupplyMaxem(ifnotalreadyavailable.

• UTP(CAT5orCAT6)datacableforconnectingchargingstationtoMaxem.

• RJ45 (8P8C) connectors for UTP cable.

• CableendsleevesforUTPcores(onlyforTeslaWallConnectororEV-Box).

Necessary materials

• FreespaceforMaxemwithconnectedwiringatthebottom.

• FreeSchuko230VsocketonPhase1(L1)forfeedingMaxemorfreespacetoplacea

new one.

• FreeEthernetportforInternetconnectedmodemorrouter.

• AnUTPcablemustbepulled (oralreadybeavailable) fromMaxem to the charging

station.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Wiring at the bottom

184mm

55,50mm

Environmental Requirements

20mm

70mm

20mm20mm

01-VoorbereidingenvoorafPreparation

WiredInternetaccess

MaxemmustbeconnectedtoawiredInternetconnection.Thefollowingisneeded:

• ModemorrouterconnectedtoInternet.

• A DHCP connection from the network to Maxem.

• MaxemshouldbeabletodoDNSrequests.

• MaxemmayalsobeplacedinaDMZ(demilitarizedzone)onaseparateVLAN.

Compatible with Maxem charging stations

ICU Compact

Tesla Wall Connector

ICU EVe mini KEBA P20/P30ICU EVe ICU Twin

EV-Box HomeEV-Box Business(G3 controller) (G3 controller)

8 9

Tesla Wall Connector itself does not measure current, for this a MID kWh-meter is needed. It can be supplied with Maxem.

Page 6: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Fusing charging station

Maxemisacontrolsystemthatregulatestheloadofthechargingstation.Therefore,itcan

be calculatedaccording to theNEN1010witha lowerequal time factor*.Maxemmakes

surethatthechargingstationislessloadedwhenthereismorechargeinthehouse.The

chargingstationcanthereforebefusedtoavaluehigherthannormal,butnothigherthan

thethresholdvalueofthemainpowersupplyterminal.

Power supply Charging station capacity Maximal fusing, charging station

3-phase 25A 3-phase 32A 3-phase 25A

3-phase 25A 3-phase 16A 3-phase 16A

3-phase 35A 3-phase 32A 3-phase 32A

1-phase 25A 1-phase 32A 1-phase 25A

1-fase 40A 1-fase 32A 1-fase 32A

*(NEN 1010:2015 722.311) The equal time factor is the ratio between the maximum simultaneous load of a

group of electrical devices or consumers within a certain period and the sum of their individual maximal loads

within the same period.

01-VoorbereidingenvoorafFeedingandfuseprotection

HangMaxem on a clean,moisture-free wall. Use the suppliedmounting plate and

screwsforthis.TakeintoaccountsufficientspacearoundtheMaxem.

01 - Mounting on the wall

Wiring at the bottom

70mm

20mm

20mm20mm

10 11

A.

230V power supply from Maxem

Maxem measures the power supply as follows:

• Amperage:divisiblecurrentcoilsmeasurethecurrentthroughthephasewires.

• Voltage: internal voltmeter in Maxem with the voltage from the 230V power supply.

For a correctmeasurement it is necessary to know fromwhich phaseMaxem is fed. In

MaxemitisstandardlyinstalledthatthesupplyisonPhase1(L1).

Page 7: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

02 - Connecting to power supply

ConnectthecablesplittertoMaxemportCT1,intendedforthemainpowersupply

terminal.

Option 3.1 - Connecting current coils to solar panels

Openthemeterboxusingintendedtools.

Click thesuppliedcurrentcoilsaround theL1phasewireof themainpowersupply

terminal. Connect this power supply coil to L1 of the cable splitter.

ConnectthecablesplittertoMaxemportCT2,intendedforthesolarpanels.

Turnoffthemainpowersupplyterminalofthefusebox.

03 - Connecting solar panels

RepeatthesestepsforL2andL3incaseofa3-phaseconnection.

ClickthesuppliedcurrentcoilsaroundtheL1phasewireofthesolarpanels.

ConnectthecurrentcoiltoL1ofthesuppliedcablesplitter.

RepeatthesestepsforL2andL3incaseofa3-phasesolarinverter.

Makesurethecurrentcoil(s)areconnectedintherightdirection.

See right page.

Makesurethecurrentcoil(s)areconnectedintherightdirection.

See right page.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

L3L2L1

MX

L3L2L1

MX

O.OFF O.OFF O.OFF O.OFF

Home

Grid / Solar

Home

Grid / Solar

Home

Grid / Solar

Grid / Solar

Home Grid / Solar

Home

O.OFF O.OFF O.OFF O.OFF

Home

Grid / Solar

Home

Grid / Solar

Home

Grid / Solar

Direction of currentMain power supply

terminal

L1 L2 L3 L1 L2 L3

CT1

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

CT2CT1 CT3CT2 CT3

L3L2L1

MX

Connect everything to the right phase!

Main connection Solar panels

12 13

A.

B.

C.

D.

E.

F.

A.

B.

C.

D.

E.

Direction of current

Solar panels

Page 8: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Option 4.1 - Connecting KEBA charging station

Install a circuit breaker or earth leakage circuit breaker at the maximal

power available. See p. 10.

Follow the installation instructions of the charging station. These

instructions can be found in the installationmanual of the charging

station.

Placea suitableUTP (CAT5orCAT6) cable from the charging station toMaxemand

clenchRJ45connectorsonbothsides.

ConnecttheUTPcabletotheEthernetportofthechargingstationandtheETHport

of Maxem.

It is advisable to test the network cable with the help of a cable tester.

04 - Connecting charging station

Connect the RS485 cable to the kWh-meter as follows:

• PortC:Greencore

• PortB:Whitecore

• PortA:Browncore

Place the kWh-meter on a DIN-rail in the installation cabinet.

Option 3.2 - Connecting MID kWh-meter to solar panels

Connect the RS485 cable to RS1 port on Maxem.

Connect this in such a way, that it measures the output of the solar inverter.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

RS1

SettheaddressingofthekWh-meteron001.Asaresult,Maxemcan

configureitself.SeeAnnex2howtosettheaddressing.

DSW1 - Power (paragraph above)DSW2-Addressing(paragraphbelow)

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Data activity on ETH portMaxem

Data activity on ETH portKeba P20 or P30

UTP cable with RJ45 connectors

14 15

A.

B.

C.

D.

SETOK

1 2 3

Distribution board

Solar panels

Dir

ectio

n of

cur

rent

Connecting RS485 cable to kWh-meter

A.

B.

C.

D.

E.

RS1 port for MID kWh meter

Page 9: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

PutDSW1.3ON.Smartchargingwillbeactivated.

SettheDIPswitchesofDSW1onthemaximalavailablepower.Andleavetherestofthe

DIP switches on OFF.

Example 10A

DSW 1.6 OFF

DSW 1.7 OFF

DSW 1.8 OFF

10A

13A

16A

Maximal current strength

20A

25A

32A

Settings on DSW11 of 3-phase

See installation manual KEBA P20/P30 for more information

Option 4.2 - Connecting ICU charging station

Install a circuit breaker or earth leakage circuit breaker for each charging

station at the maximal power available. See p. 10.

Follow the installation instructions of the charging station. These

instructions can be found in the installationmanual of the charging

station.

Placea suitableUTP (CAT5orCAT6) cable from the charging station toMaxemand

clenchRJ45connectorsonbothsides.

ConnecttheUTPcabletotheEthernetportofthechargingstationandtheETHport

of Maxem.

It is possible to update the charging station firmware. This can be done via ICU Connect, as soon as the charging station is online. ICU or Cohere can assist you with this.

It is advisable to test the network cable with the help of a cable tester.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Data activity on ETH port Maxem

ETH port ICU UTP cable with RJ45 connectors

TakeoffthevoltageonKebaP20/P30(theDIPswitchsettingsonlybecomeactiveafter

a reset of the charging station).

16 17

A.

B.

C.

D.

E.

F.

G.

Page 10: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Rotary switch

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Set the Wall Connector as Slave by placing the rotary switch in F position.

CrimpthesuppliedRJ104P4CconnectoronMaxemsideonthedatacable.Twowires

mustbeconnected:

• Connect wire 1 (orange-white) to Pin 1

• Connect wire 2 (orange) to Pin 2

Connect the RJ10 4P4C connector to RS2 Maxem port.

ConnectthedatacabletotheIN(D+andD-)portoftheWallConnector

clamp block:

• Connectthewirefrompin1onD+

• Connect the wire from pin 2 to D-

RS2 port for Tesla Wall Connector

LED indications Tesla Wall Connector

RS2 Pin 1 Pin 2

LEDabovelightsupingreen:everythingisconnectedproperly

MiddleLEDisblinkingred:setasSlavebutnoconnectionwithMaxem

Lower LED burns 5 secs. green: correctly set as Slave at start

RJ10 4P4C

See installation manual Tesla Wall Connector for more information

Tab above

Option 4.3 - Connecting Tesla Wall Connector

Install a circuit breaker or earth leakage circuit breaker for each charging

station at the maximal power available. See p. 10.

Follow the installation instructions of the charging station. These

instructions can be found in the installationmanual of the charging

station.

Place a suitable UTP (CAT5 or CAT6) of the Wall Connector to Maxem. (To prevent

electromagneticinterferenceattheRS485connection,itisrecommendedtouseFTP

CAT6cableatdistancemorethan25m.Max:50m).

SETOK

1 2 3

Connect the RS485 cable to the kWh-meter as follows:

• PortC:Greencore

• PortB:Whitecore

• PortA:Browncore

Place the kW-meter on a DIN rail in the installation cabinet.

Distributionboard

Chargin station

Dir

ectio

n of

cur

rent

Connect it in such a way that it measures the consumption of the charging station.

Connection of RS485 cableto kWh-meter

SettheaddressingofthekWh-meterto002.Asaresult,Maxemcanconfigureitself.

SeeAnnex2howtosettheaddressing.

18 19

A.

B.

C.

D.

E.

F.

J.

I.

H.

G.

L.

Tesla Wall Connector does not measure kWh itself, therefore a MID kWh-meter is needed.

Cores for pull relief

Connect the RS485 cable to RS1 port on Maxem.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

RS1D.

RS1 port for MID kWh-meter

Page 11: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Option 4.4 - Connecting EV-Box charging station

Install a circuit breaker or earth leakage circuit breaker at the maximal

power available. See p. 10.

Follow the installation instructions of the charging station. These

instructions can be found in the installationmanual of the charging

station.

Place a suitable UTP (CAT5 or CAT6) of the EV-Box to Maxem. (To prevent electromagnetic

interferencewiththeRS485connection,itisrecommendedtouseFTPCAT6cableat

distancemorethan25m.Maximaldistanceis50m).

CrimpthesuppliedRJ104P4CconnectoronMaxemsideonthedatacable:

• Connect wire 1 (orange-white) to Pin 1

• Connect wire 2 (orange) to pin 2

• Connect two other wires for pull relief

Connect the RJ10 4P4C connector to Maxem RS2 port.

Connectthesetwocoresofthedatacabletothequadrupolecommunicationportof

EV-Boxmodem:

• Connect one wire (orange-white) to Port A

• Connect wire 2 (orange) to port B

• Theremainingportsdonothavetobeconnected

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

RS2 port for charging station

Scheme EV-Box controller

Pin 1Pin 2

ConnectMaxemwiththesuppliednetworkcabletothemodemorrouterconnected

to the Internet.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

Ethernet port to Internet Router

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

ConnectMaxemwith the included 230V feeding cable to a plug on themeter box.

MakesurethisplugisconnectedtoPhase1ofthepowersupply.Maxemmeasuresthe

voltage through the power supply. It is therefore important to know to which phase the

powersupplyisconnected.

CheckthatallcomponentsareconnectedtoMaxem.

20 21

12V/DC

ABGND

Tab above

A.

B.

C.

D.

E.

F.

A.

B.

C.

A

A

167

184

55.50

SECTION A-A

Client:

Rev. nr:

1:1Units:

1/2

CES-01 - Enclosure

MHVol. (mm³):

mm

Sheet:

Scale:

-

CohereDate:

Drawn:

File reference:Drawing name:

-Material:17-02-2016

Maxem 4 Assembly

A3

Stereo Design | Zamenhofstraat 150 - unit 336 | 1022AG | Amsterdam | Netherlands | T: +31 (0) 20 636 0671 | M: [email protected]

<0,2x45° or R<0,2

Ra 0,8 um

Default length tolerances: DIN 7168

±20'Default angle tol.:

Finish:

Default edges:

Roughness:

Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8Dim.: 0-6 7-30 31-120 121-400 401-1000

RS2

05 - Connecting Maxem

Cores for pull relief

Page 12: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

06 - Commissioning

22

Maxemrunsduringcommissioninganautoconfigurationprocesswhereallmeasuring

points,chargingstationsandotherdevicesarerecognizedandset.Followthefollowing

steps:

Putonthechargingstationorrestartittotakeoffthecurrenttemporarilyandputit

on again.

Connect the 230V power supply to Maxem or restart Maxem to pull the 230V supply

cabletemporarilyfromtheplugandplugitinagain.

23

TherearedifferentLEDsonMaxemwherebyyoucancheckwhethercomponentsareconnectedproperly.

RS2RS1P1 CT3CT2CT1

Maxem starts

LEDindicationsonMaxem

Installation OK Installation NOT YET OK

AutoconfigOKConnection web portal OK

AutoconfigNOTOKConnection webportal OK

AutoconfigOKConnection webportal NOT OK

Maxem back to factory settings, see chapter Troubleshooting

Communication OK There is a connection, but communication NOT OK

CentralLEDindicator

LEDindicatorsforinput/outputports

Noconnectiondetected

A.

B.

LED indication: blinks 3x

LED indication: blinks 4x

LED indication: blinks 2x

LED indication: blinks continuously

LED indication: lights continuously

After successful installation, Maxem sends a current limiting value to the charging station. In case of non-successful installation, this is not the case. This results in OVERLOAD OF THE POWER SUPPLY. Cohere should therefore always give OK for a successful installation.

A. CallCohereinordertoactivateMaxem.Coherecontrolsthewholeworkofthe

deviceatadistanceandgives“OK”forasafeinstallation.

020 770 87 13

07 - Telephone installation check

Page 13: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

Maxemdoesnotconnecttotheonlinebackend

• ControlthatMaxemnetworkconnectionisactive.Ifthereisadataconnection,aLED

burnsorangeontheLANport,greenoritisoff.Ifthereisactivityontheconnection,

an orange LED is blinking.

• ControlifthereisanactiveInternetconnectionontheconnectedrouter.

• ControlwhethertheconnectedUTPcableiscorrectlyconnectedwiththehelpofa

cable tester.

• MakesurethataDHCPconnectioncanbemadetoMaxemfromthenetwork.

• MakesurethatMaxemcandoDNSrequeststhroughthenetworktoconnecttothe

backoffice.

• ItispossibletoplaceMaxeminaDMZ(demilitarizedzone)onaseparateVLAN.

• RestartMaxembyturningitoffandon.AnyproblemswiththeIPaddressingcanthus

befixed.

Autoconfigurationisnotsuccessful

• RS485connectedchargingstation:controlwhethertheRJ10(4P4C)connectoriswell

crimpedintotheRSportofMaxem.SeeAnnex3howtocrimpRJconnectorsthebest.

• EthernetConnectedchargingstation:MakesurethatgreenandblinkingorangeLED

in the charging station are on for an active connection with Maxem. If this is not the

case,thereisapossibleerrorintheinstalledUTPcable.

• Restartthechargingstationbyputtingthevoltageoffandonagain.

• Makesurethecorrectfirmwareisplacedonthechargingstationandthatis

compatible with Maxem. An employee of Cohere can help.

Thechargingstationisnotdetectedornotcorrectlydetected

• TurnoffMaxem.Waitfor10seconds.

• Then turn on Maxem. If there is a charging station, switch the group of the charging

stationoffandonagain.Theautoconfigurationwillrunagain.

24 25

Annex 1 - Troubleshooting

Thecardoesnotstartduringcharging

• Performarebootofthegroupofthechargingstationinthemeterbox(turnoffthe

group,waitfor10seconds,andthenturnonthegroupagain).Makesurethatthe

chargingcableisnotconnectedtothecar.

• An authorization problem for ICU charging stations may occur, which prevents the

chargingstationfromgivinga“permission”tostartachargingsession.Anemployee

of Cohere can help.

The measurements of the power supply are not logical

• Incasethesolarpanelsareavailable,turnoffthegroup.

• Makesurethepowersupply(socket)ofMaxemisconnectedtoL1.

• Makesurethateachcurrentcoilisconnectedtothephasecorrespondingtothe

labels of the cable splitter.

• Makesurethecurrentcoilsaredirectedcorrectly.Thearrowonthecurrentcoil

followsthecurrentdirectionofthenettothegroupsofthehouse.

• MakesurethecablesplitterisconnectedtoMaxemCT1port.

The measurements of the solar panels are not logical

• Makesurethepowersupply(socket)ofMaxemisconnectedtoL1.

• Makesurethateachcurrentcoilisconnectedtothephasecorrespondingtothe

labels of the cable splitter.

• Makesurethecurrentcoilsaredirectedcorrectly.Thearrowonthecurrentcoil

followsthecurrentdirectionofthesolarinvertertothegroupsofthehouse.

Page 14: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

26 27

Maxem can measure different devices through an external MID certified kWh-meter.

In order autoconfiguration could function properly, the kWh-meter must be set on the

correspondingaddress.Thisisdoneasfollows:

Device Addressing

Solar #1 001

Solar #2 011

Charging station #1 002

Charging station #2 012

Heat pump #1 004

Heat pump #2 014

Holdthebuttonfor2sec.toenterthemenu,ortogoupinthemenu.

Scrolldownthroughmenuoradjustsettingvalue.

Presstogetintoamenuitemoracceptanadjustment.

Presstoadjustasetting.

Navigation through the menu of the ABB B23/B24 kWh-meter

IfyouseethisiconinthedisplayofthekWh-meter,thereisanactivedataconnectionwithMaxem.

Locationofthe‘addressing’functioninthemenustructure

SETOK

1 2 3

Addressingexample

Numberofdevices

Device type

StandardaddressingkWh-meter

Device Addressing

Solar 001

Charging station 002

Heat pump 004

Devices

Annex 2 – Installation kWh-meter

• Checkthemaximalchargingcapacityofthecar.Forexample,theTeslaModelSneeds

aduochargertocharge3x24A.AModelSwithasinglechargerchargesmaximum

3x16A.

• For KEBA charging stations: Check that the DIP switches are set correctly.

• ToolowfusingwasappliedatMaxemwhenconfiguring.AnemployeeofCoherecan

helptoadjustit.

Thecarischargedtooslowfortheavailablecapacity

Thecarischargedtoofastfortheavailablecapacity

• AtoohighfusingwasappliedatMaxemwhenconfiguring.AnemployeeofCoherecanhelptoadjustthis.

Page 15: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

234

1

TroubleshootingAnnex 3 – Crimping RJ-connectors

28 29

Materials

• Crimpingpliers(forRJ10and/orRJ45connectors)

• Scissors or pliers

• Sharp (Stanley) knife

• RJ10 or RJ45 connectors

Steps

Cutthecoresinastraightlinewithapairofpliersinordertohavethemallwiththe

same length.

Stripapproximately3cmoftheoutercoverwithasharp(Stanley)knife.Theindividual

coresshouldnotbedamaged.

A.

B.

InsertthecoresintotheRJ10orRJ45connector.Makesurethatthecoresareplacedin

thecorrectorder.FortheRJ10connectoritisrecommendedtoplace2additionalcores

for pull relief.

C.

Makesurethatthecoresareinserteddeepenoughintotheconnectorinordertohave

themfirmlyclamped.

D.

Placetheconnectorwiththeinsertedcableintothepliers.Clenchitinordertohave

thecoressecuredandexposed. Itmaybenecessary toclench thepliersfirmly two

times or more.

E.

Double-check that all cores are fully inserted. If this is not done correctly, the cable

will not work properly.1234

12345678

4P4C (RJ10)

Tab above

8P8C (RJ45)

Tab above

Connectiondiagrams

Cores for pull relief

Page 16: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

We,

Cohere Energy Solutions B.V.WillemdeZwijgerlaan3501055RDAmsterdam,theNetherlands

following the provision of the following EC Directives:• 2006/95/EC The Low Voltage Directive• 2004/108/EEC The Electromagnetic Compatibility Directive

Herebydeclarethattheproduct:MaxemEnergyManager4.0isinconformitywiththeapplicablerequirementsofthefollowingdocuments:

Emissions• EN 61326-1 (2013)• EN61000-3-2(2006)+A1(2009)+A2(2009)• EN 61000-3-3 (2008)

Immunity• EN 61326-1 (2013)

Safety• EN 61010-1 (2010),• EN 61010-2-030 (2010)• EN 61010-2-023

Signee Date Place Signature

Jan Willem HeinenCEO

1 August 2016 Amsterdam

30 31

TroubleshootingEC Declaration of Conformity

Page 17: SMART CHARGING CONTROLLER - · PDF fileDefault length tolerances: DIN 7168 ±20' Default angle tol.: Finish: Default edges: Roughness: Tol.: ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 Dim.: 0-6

C H A R G E S M A R T E RWillemdeZwijgerlaan350|1055RD|Amsterdam|TheNetherlands+31(0)207708713|[email protected]|www.cohere.eu