site reference details site specific notes

19
PENNANT HILLS PARK 339 BRITANNIA ST ADDRESS: 311207 339 BRITANNIA STREET PENNANT HILLS NSW 2120 ORDER DO NOT SCALE F 1 E D 2 3 C B A 1 2 3 C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved. 4 5 DWG NO. DRAWN CHKD AMENDMENT DATE EXAM APPD ISS 6 NO. SHT A3 F E D 4 5 C B 6 A Cad file: N110386.dwg MOBILE NETWORK SITE 311207 PENNANT HILLS PARK 339 BRITANNIA ST N110386 DC DRAWING INDEX AND DOCUMENT CONTROL - SHEET 1 OF 2 339 BRITANNIA STREET, PENNANT HILLS, NSW 2120 NODE MANAGER ADDRESS ID: 06/02/18 DRAWING STATUS SHEET NO. 2 SITE ACCESS AND LOCALITY PLAN S1 S3 WEST ELEVATION DRAWING NUMBER DRAWING DESCRIPTION ISSUE NO. SITE EARTHING PLAN G4 2 EQUIPMENT LAYOUT E1 S0 N110386 SITE SPECIFIC NOTES - SHEET 1 OF 2 ELECTRICAL SPECIFICATION E0 1 AC POWER - CONNECTION E2 DC POWER LINE DIAGRAM E4 N110386 N110386 N110386 N110386 N110386 N110386 N110386 ISSUE DATE CANCELLED PRELIMINARY CONSTRUCTION AS BUILT FOR STRUCTURAL DESIGN CERTIFICATION Z1 N110386 06/02/18 06/02/18 06/02/18 06/02/18 06/02/18 06/02/18 06/02/18 06/02/18 P P P P P P P P P Z1-1 N110386 08/2016 P PROJECT NO. NA16917.01 Level 1, 29 Christie Street, St. Leonards NSW 2065 T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au REFERENCE ONLY 2 SITE LAYOUT S1-1 N110386 06/02/18 P S3-1 ANTENNA CONFIGURATION TABLE 2 N110386 06/02/18 P PATHFINDER CHANNEL RACK LAYOUT E5 N110386 06/02/18 P 06/02/18 S0-1 N110386 SITE SPECIFIC NOTES - SHEET 2 OF 2 1 P 2 ANTENNA LAYOUT S1-2 N110386 06/02/18 P NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1 1 1 1 1 1 1 1 1 SITE TENURE PLAN G1 N110386 SITE DETAIL SURVEY G2 N110386 06/02/18 06/02/18 P P 1 1 GEOTECHNICAL REPORT REF: 16/2209 SHELTER FOOTING DETAILS - SHEET 1 OF 2 T3 1 N110386 06/02/18 P The copyright and ownership of the drawings is to be assigned to Telstra Telstra Networks Wireless program Delivery Template - 017866P02 issue 11.4 XX /XX/ 2015 SHELTER FOOTING DETAILS - SHEET 2 OF 2 T3-1 1 N110386 06/02/18 P

Upload: others

Post on 03-Apr-2022

36 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

PENNANT HILLS PARK 339 BRITANNIA STADDRESS:

311207339 BRITANNIA STREETPENNANT HILLSNSW 2120

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 DC

DRAWING INDEX AND DOCUMENT CONTROL - SHEET 1 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

NODE MANAGER ADDRESS ID:

06/02/18

DRAWING STATUS

SHEE

T NO

.

2SITE ACCESS AND LOCALITY PLAN S1

S3WEST ELEVATION

DRAWINGNUMBER

DRAWINGDESCRIPTION

ISSU

E NO

.

SITE EARTHING PLAN G4

2

EQUIPMENT LAYOUT E1

S0N110386SITE SPECIFIC NOTES - SHEET 1 OF 2

ELECTRICAL SPECIFICATION E0

1

AC POWER - CONNECTION E2

DC POWER LINE DIAGRAM E4

N110386

N110386

N110386

N110386

N110386

N110386

N110386

ISSUEDATE

CANC

ELLE

D

PREL

IMIN

ARY

CONS

TRUC

TION

AS B

UILT

FOR

STRUCTURAL DESIGN CERTIFICATION Z1N110386

06/02/18

06/02/18

06/02/18

06/02/18

06/02/18

06/02/18

06/02/18

06/02/18

P

P

P

PPPP

P

P

Z1-1N110386 08/2016 PPROJECT NO. NA16917.01

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

REFE

RENC

E ONL

Y

2SITE LAYOUT S1-1N110386 06/02/18 P

S3-1ANTENNA CONFIGURATION TABLE 2N110386 06/02/18 P

PATHFINDER CHANNEL RACK LAYOUT E5N110386 06/02/18 P

06/02/18S0-1N110386SITE SPECIFIC NOTES - SHEET 2 OF 2 1 P

2ANTENNA LAYOUT S1-2N110386 06/02/18 P

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

1

1

1

1

1

1

1

1

SITE TENURE PLAN G1N110386

SITE DETAIL SURVEY G2N110386

06/02/18

06/02/18PP

1

1

GEOTECHNICAL REPORT REF: 16/2209

SHELTER FOOTING DETAILS - SHEET 1 OF 2 T3 1N110386 06/02/18 P

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

SHELTER FOOTING DETAILS - SHEET 2 OF 2 T3-1 1N110386 06/02/18 P

Page 2: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 DC-1

DRAWING INDEX AND DOCUMENT CONTROL - SHEET 2 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

PENNANT HILLS PARK 339 BRITANNIA STADDRESS: 339 BRITANNIA STREET

PENNANT HILLSNSW 2120

NODE MANAGER ADDRESS ID:

DRAWING STATUS

SHEE

T NO

.

DRAWINGNUMBER

DRAWINGDESCRIPTION

ISSU

E NO

.

ISSUEDATE

CANC

ELLE

D

PREL

IMIN

ARY

CONS

TRUC

TION

AS B

UILT

FOR

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

REFE

RENC

E ONL

Y

311207

REFERENCE DRAWINGS:

P017866P05 1STANDARD CONSTRUCTION NOTES 2 19/11/10

017866P123 1 1 30/06/08EQUIPMENT ALARM CONFIGURATION P

P017866P160ELECTRICAL SPECIFICATION 1 3 07/12/12

FEEDER EARTHING DETAILS 11 2017866P201 13/05/15 P

PDETAILS & CONNECTIONS GALVANISED STEEL BASED SYSTEM 1 2017866P201 14/04/15

P5 1017866P201 11/05/11TYPICAL ENHANCEMENT COMPOUND INSTALLATIONTO EARTH ELECTRODE & EARTH STRAP

P017866P16 1STANDARD FENCING 5 23/09/11

P017866P18 1STANDARD FENCING - GATES 5 23/09/11

PTEL-MK40BF-D1 A001 2 08/12/17

PTEL-MK40BF-D1 A002 2 08/12/17

PTEL-MK40BF-D1 A101 2 08/12/17

PTEL-MK40BF-D1 A102 1 06/10/17

P- BRJ10594-1-1 12/10/1740m MONOPOLE - PENNANT HILLS PARK 339 BRITANNIA ST311207 - GENERAL ARRANGEMENTANTENNA MOUNTS P- BRJ10594-2-AM1 12/10/17

P- BRJ10594-3-1 12/10/1740m MONOPOLE - PENNANT HILLS PARK 339 BRITANNIA ST311207 - BORED PIER FOUNDATION

P- BRJ10594-4-SD3 12/10/17SAFETY IN DESIGN RISK ANALYSISSTRUCTURE FOUNDATION

P- BRJ10594-3-FC1 12/10/17STANDARD FOUNDATION NOTES SHEET 1 OF 1

P- BRJ10594-4-SD1 12/10/17SAFETY IN DESIGN RISK ANALYSISANTENNA SUPPORT STRUCTURE

BASE PLATE GROUTING P- BRJ10594-2-BG1 12/10/17

P- CRJ10594-2-MP1 14/02/13STANDARD LAPPED MONOPOLE ERECTIONNOTES SHEET 1 OF 1

REFLECTED CEILING PLAN(3.15m x 2.38m SHELTER)EXTERNAL ELEVATIONS(3.15m x 2.38m SHELTER)INTERNAL ELEVATIONS(3.15m x 2.38m SHELTER)

P017866P134 11 1 14/08/14RRU POWER AND EARTHING SP22-HC POWER SYSTEM& DC-DC CONVERTERS - THREE PHASE SITES

30 2017866P203 31/08/12 PLIGHT POLE & SHELTER

1 1017866P205 08/06/12 PSTEEL POLE EARTHING DETAIL

1017866P140 2 20/12/12UNDERGROUND CONDUIT AND DRAWING PIT DETAILS P

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

P19 2017866P201 05/12/13MOBILE NETWORK SITE EARTHING STANDARDSSTAINLESS STEEL EARTH BAR DETAILS

P20 1017866P201 17/02/12MOBILE NETWORK SITE EARTHING STANDARDSICS SHELTER INTERNAL FEB DETAIL RRU & NON RRU SITES

FLOOR PLAN(3.15m x 2.38m SHELTER)

Page 3: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

DENOTES TELSTRA ANTENNA SECTOR AS SHOWN ON SHEET S1-2X

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S0

SITE SPECIFIC NOTES - SHEET 1 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

SERVICES LEGEND

ABOVE GROUND ELECTRICAL SUPPLY

WATER SUPPLY

OPTIC FIBRE ABOVE GROUND

SEWER LINE

T T T

BELOW GROUND ELECTRICAL SUPPLY

HV HV HIGH VOLTAGE ELECTRICAL SUPPLY

SW STORM WATER

BELOW GROUND FEEDER CABLES

GAS SUPPLY

OPTIC FIBRE BELOW GROUNDT T T

ABOVE GROUND FEEDER CABLES

AX

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

SITE SPECIFIC NOTESEQUIPMENT SHELTERTYPE: PROPOSED TELSTRA ICS Mk 4.0 (BF OPTION)EQUIPMENT SHELTER (3150 L x 2380 W x 3000 H)COLOUR: BRUNSWICK GREENFEEDER ENTRY WINDOW: FRONT RIGHT SIDEAIR CONDITIONING CAGE: YESREFERENCE DRAWING: SHEETS E1, T3 & T3-1, DRG.TEL-MK40BF-D1 SHEETS A001, A002, A101 & A102

STRUCTURETYPE: PROPOSED TELSTRA 40m ROAM HIGHSTEEL MONOPOLECOLOUR: GALVANISED FINISHFEEDER ENTRY WINDOW: REAR RIGHT SIDEREFERENCE DRAWING: RJ10594-1 SHEET 1,RJ10594-2 SHEETS BG1 & MP1, RJ10594-3SHEETS 1 & FC1, RJ10594-4 SHEET SD3

HEADFRAMETYPE: PROPOSED TELSTRA COLLARMOUNTED HEADFRAMEMODEL NO.: TO SUIT POLE TYPECOLOUR: GALVANISED FINISHREFERENCE DRAWING: RJ10594-1SHEET 1 & RJ10594-2 SHEET AM1

ANTENNA ACCESSTELSTRA: ELEVATED WORK PLATFORMOTHERS: ELEVATED WORK PLATFORM

ANTENNA MOUNTSTYPE: PROPOSED TELSTRA STEEL MOUNTSCOLOUR: GALVANISED FINISHREFERENCE DRAWING: RJ10594-1 SHEET 1& RJ10594-2 SHEETS AM1

POWER SUPPLYEXISTING TELSTRA POWER SUPPLY (3 PHASE/ 50 AMP).EXISTING METERS AND EQUIPMENT TO BE RELOCATEDBY L2 ASP. REFER TO SHEETS E0 & E2.DIAL 1100 BEFORE YOU DIG.

SITE ACCESSVIA 339 BRITANNIA STREET, PENNANT HILLS, NSW 2120REFER TO SHEET S1SITE S.A.C. TO ADVISE C.D.C. LOCATION DETAILS

SITE SIGNAGEALL EME SIGNAGE IS REFERENCED ONSHEETS S1-1, S1-2 & S3.REFER TO DOCUMENT 005486 FOR DETAILS.

PROPERTY SIGNAGESPECIFY PROPERTY SIGNAGE AS PER DOCUMENT017866A12. PROPERTY SIGN INCLUDES RFNSA SITENUMBER. SITE NAME: BRANDED SITE IDENTIFICATIONREGULAR (BSr). TELSTRA S/I NUMBER 187/00929.JABAC PART NUMBER TEMS929-M.

GENERAL NOTES1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS SPECIFIED OTHERWISE.

2. BIRD PROOFING CABLES AND ALL ACCESS POINTS ON THE STRUCTURE MUST BE BIRD PROOFED IN ACCORDANCE WITH THE METHODS SPECIFIED IN DOCUMENT NO. 003615 EXTERNAL PLANT STANDARDS FOR MOBILE BASE STATIONS, SECTION 6.3.3.

3. SERVICES, WHERE SHOWN ARE INDICATIVELY ONLY. LOCATION OF ALL RELEVANT EXISTING SERVICES SHALL BE IDENTIFIED AND CONFIRMED PRIOR TO COMMENCING WORK. THE CONTRACTOR TO LIAISE WITH RELEVANT AUTHORITIES FOR DIRECTIONS AND PERMITS REQUIRED. DIAL BEFORE YOU DIG 1100.

4. FEEDER CONNECTION DETAILS, ELECTRICAL AND MECHANICAL TILTS ARE TO BE OBTAINED FROM CANRAD REPORTS.

5. CONSTRUCTORS ARE TO BE AWARE OF TELSTRA DOCUMENT 007338-C8-11 AND IN PARTICULAR CLAUSE 7.3 & 10.3 WHICH DESCRIBES REQUIREMENTS PERSONNEL MUST UNDERTAKE IN RESPECT TO ASBESTOS MANAGEMENT AT TELSTRA FACILITIES.

ENVIRONMENTAL ISSUESREFER TO ENVIRONMENTAL RISK ASSESSMENTCHECKLIST 018422F10. THIS SITE IS IN ADESIGNATED BUSH FIRE PRONE AREA, LOWRISK - BAL< 29.

GPS RECEIVER SYSTEM

SURGE ARRESTOR DEVICE PART NO.: NGC90145GPS RECEIVE UNIT PART NO.: NCD90141/1

GPS ANTENNA INC. BRACKET PART NO.: KRE1012082/1

ACTIVE SPLITTER 1 x 4 PART NO.: KRY1011946/1SIGNAL CABLE 2m PART NO.: RPM1136127/2000RF JUMPER 1.5m -N(m) TO SMA(m) TYPE: TSR951357/1500

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET S0-1

SITE DESIGN BRIEF WCDMA850 / LTE700 / LTE1800 NA16917.01 ISSUE 02 DATED 25/09/2017

SITE REFERENCE DETAILSSITE CODESITE NAMEOCCUPIER

PENNANT HILLS PARK

339 BRITANNIA ST

TELSTRA 311207

PENNANT HILLS PARK -OOPTUS S1118

PENNANT HILLS PARK -O JS9497

PENNANT HILLS PARKVODAFONE 227573

RFNSA SITE NUMBER - 2120008STRUCTURE OWNER - TELSTRA

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

OPTUS VODAFONEJOINT VENTURE

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

Page 4: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S0-1

SITE SPECIFIC NOTES - SHEET 2 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

EQUIPMENT NOTES - PROJECT NO. NA16917.01ITEM EQUIPMENT EQUIPMENT DETAILS EXISTING PROPOSED TOTAL REFERENCE DWG

1

2

3

4

5

6

7

8

9

10

11

12

13

SHEET E50 1 1

KAELUS COMBINER (LTE700) DBC0086F1V2-1 TO BE INSTALLED IN 45RU PATHFINDER RACK 0 3 3 SHEET E5

ERICSSON GPS ANTENNA KRE 101 2082/1 OMNI Ø68 x 96mm 0 1 1 -

- - - -UW 7096 MCEQUIPMENT ROOM KEY NO.

7/8" HYBRID CABLES 95m (LTE1800) 0 3 3 -

0 2 2 SHEET E5530 x 600 x 2200mm (W,D,H)45RU PATHFINDER RACK

KAELUS FILTER UNITS DDF0035F1V2 TO BE INSTALLED IN 45RU PATHFINDER RACK 0 3 3 SHEET E5

DUW-31 CARD (WCDMA850) TO BE INSTALLED IN RBS6202 0 11

14

15

16

- - - -N/ASECURITY COMPOUND GATE KEY NO

17

18

19

SHEET E5

ERICSSON SITE INTEGRATION UNIT (SIU) 482 x 350 x 45mm (W,D,H) SUPPORT TYPE 45RU PATHFINDER RACK 0 11 SHEET E5

ELTEK SP22-HC (PSU) 600 x 600 x 2200mm (W,D,H)

ELTEK SP22-HC RECTIFIERS FP2 HE, 2kW

SHEETS E1 & E40 1 1

0 SHEET E4

0 4 SHEET E4

ERICSSON RBS6202 (LTE700 / LTE1800) 500 x 525 x 568mm (W,D,H) SUPPORT TYPE 45RU PATHFINDER RACK

ELTEK SP22-HC BATTERIES FXH190-12S BATTERY RESERVE CAPACITY 7 HRS

20

21

22

ELTEK SURGE PROTECTION DEVICE (SPD 12.3 WAY) 350 x 150 x 350mm (W,D,H) WALL MOUNTED 0 1 1 SHEET E1

ERICSSON RRUS-32 B3 (LTE1800) 470 x 187 x 518mm (W,D,H) NATURAL COLOUR 0 3 3 SHEETS S1-2 & S3

SAMSUNG RRU JUNCTION BOX 80 x 133 x 510mm (W,D,H) NATURAL COLOUR 0 3 3 SHEETS S1-2 & S3

R503 DIGITAL UNIT TO BE INSTALLED IN RBS6202 0 11 SHEET E5RUS-02 (B28) 1 x 100W, LTE700 TO BE INSTALLED IN RBS6202 0 66 SHEET E5RUS-02 (B5) 1 x 100W, WCDMA850 TO BE INSTALLED IN RBS6202 0 33 SHEET E5

KAELUS TOWER MOUNTED AMPLIFIER LTE700 TMA2094F01V2-1 0 3 3 SHEETS S1-2 & S3

SAMSUNG HCC OPTICAL FIBRE PATCH PANEL 425 x 350 x 44mm (W,D,H) SUPPORT TYPE 45RU PATHFINDER RACK 0 11 SHEET E5

RFS LCF114-50JA 95m (WCDMA850 & LTE700) 0 12 12 -23

24

25

0 11 SHEET E5

ELTEK 48/48V DC CONVERTER FP2 HE, 1.35kW SHEET E40

4

24 24

4 4

DUS-41 (LTE700 / LTE1800) TO BE INSTALLED IN RBS6202

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET S0

SHEET E50 1 1ERICSSON RBS6202 (WCDMA850) 500 x 525 x 568mm (W,D,H) SUPPORT TYPE 45RU PATHFINDER RACK

26

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

0 1 1 -SPLIT SYSTEM, 6.3kWAIR CONDITIONING27

ELTEK BATTERY EXTENSION RACK 600 x 600 x 2200mm (W,D,H) SHEETS E1 & E40 1 1

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

Page 5: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

T

T

T

T

T

T

The copyright and ownership of the drawings is to be assigned to Telstra

PART OF LOT 1 ON DP 883213PARISH OF SOUTH COLAHCOUNTY OF CUMBERLAND

PROPERTY DESCRIPTION

RFNSA SITE No. 2120008

SITE ACCESS SCALE 1:1500

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S1

SITE ACCESS AND LOCALITY PLAN339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TN

SITE STRUCTURE CO-ORDINATES (GDA94)GPS READING ACCURACY: ± 0.1m

CENTRE OF POLE

LONGITUDE

LATITUDE GDA 94-33.743023

GDA 94151.078303

LOCALITY PLANNOT TO SCALE

COPYRIGHT C WHEREIS REGISTERED TRADEMARK OF SENSIS PTY LTD.R

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 UM SS PRELIMINARY - 30064156W20SSMC - WCDMA850 / LTE700 / LTE1800 KS IT 17.05.17 1

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEETS S1-1 & S1-2

BRITANNIA STREET

EXISTING AUSGRIDPOLE #80743

EXISTING OPTUS POLE WITHPANEL & M/W ANTENNAS

EXISTING OPTUS POLE WITHPANEL ANTENNAS

EXISTING BUILDING(TYP.)

PROPOSED TELSTRAINSTALLATION. REFER TOSHEET S1-1 FOR SITE LAYOUT

EXISTING TREES (TYP.)

BRITANNIA STREET

BRITANNIA STREET

EXISTING FIBRE OPTIC ROUTE(TO BE CONFIRMED BY TELSTRA)EXISTING U/G OPTUS SUBMAINS. REFERTO SHEETS E0 & E2 FOR DETAILS

EXISTING LIGHT POLE WITH EXISTINGTELSTRA PANEL ANTENNAS (6 OFF).DECOMMISSION & RECOVER ALLTELSTRA EQUIPMENT AND MOUNTINGSTEELWORK. LEAVE TIMBER POLE &FLOODLIGHTS IN PLACE

EXISTING 1m HIGH FENCEAROUND LIGHT ATHLETIC FIELD

EXISTING OPTUS EQUIPMENT SHELTEREXISTING TELSTRA EQUIPMENT SHELTER & ITS FOUNDATIONTO BE DECOMMISSIONED & RECOVERED. GROUND SURFACETO BE MADE GOOD. FENCE TO REMAIN IN PLACE

EXISTING AUSGRID PADMOUNTED TRANSFORMER

PROPOSED TELSTRA EQUIPMENT SHELTER TYPE ICS Mk 4.0(BF OPTION) (3150 L x 2380 W x 3000 H) COLOURED'BRUNSWICK GREEN' TO ACCOMMODATE PROPOSEDTELSTRA EQUIPMENT ON CONCRETE PAD FOOTING. REFERTO SHEET E1 FOR EQUIPMENT DETAILS & TELSTRA STD DRG017866P45 AND NOTE 6 IN SHEET S1-1 FOR SHELTERFOOTING DETAILS

SCALE 1:15000 30m 60m30m

LOT 1DP 883213

ERNHOLMES

OVAL

NOTES:1. ALL FEEDER ACCESS POINTS ON THE STRUCTURE MUST BEBIRD PROOFED AS PER EXTERNAL PLANT POLICY 003615.2. FOR SITE SPECIFIC NOTES REFER TO SHEETS S0 & S0-1.3. CLEAR ALL VEGETATION WITHIN THE COMPOUND TOMINIMISE SNAKE ACTIVITY.

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

PROPOSED TELSTRA U/GSUBMAINS. INDICATIVEROUTE ONLY (APPROX. 50m).REFER TO SHEETS E0 & E2FOR DETAILS

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 2

EXISTING AUSGRID PILLAR

PROPOSED SHARED FREESTANDING MAINSWITCHBOARD / METERENCLOSURE. INDICATIVEONLY. REFER TO SHEETS E0& E2 FOR DETAILS

AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
AutoCAD SHX Text
/
Page 6: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

T

T

T

T

T

T

The copyright and ownership of the drawings is to be assigned to Telstra

SITE LAYOUTSCALE 1:200

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S1-1

SITE LAYOUT339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TN

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

0 10m2m SCALE 1:2002m 4m 6m 8m

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEETS S1 & S1-2

PROPOSED SIGN SECUREDTO TELSTRA SHELTER DOOR

PROPOSED TELSTRA 40m HIGH ROAM STEELMONOPOLE. REFER TO ROAM DRAWINGRJ10594-1-1 FOR MONOPOLE DETAILS

REFER TO SHEET S1-2 FORANTENNA LAYOUT

EXISTING BOUNDARY FENCE

1.5m AGL#6

PROPOSED TELSTRA GPS ANTENNA (1 OFF A7)MOUNTED ON PROPOSED ANTENNA BRACKETMOUNT NEAR FEEDER WINDOW ON SHELTER ROOF

EXISTING FIBRE OPTIC ROUTETO BE CONFIRMED BY TELSTRA

EXISTING 1m HIGH FENCEAROUND ATHLETIC FIELD

EXISTING LIGHT POLE TO BEREMOVED (AFTER INSTALLATIONOF TELSTRA MONOPOLE)

PROPOSED TELSTRA Ø100 U/G CONDUITS (12 OFF) TOACCOMMODATE PROPOSED TELSTRA FEEDERS (15 OFF)

PROPOSED TELSTRA DRAW PITS (4 OFF). REFER TOTELSTRA STD DRG 017866P140 FOR DETAILS

PROPOSED TELSTRA EQUIPMENT SHELTER TYPE ICS Mk 4.0 (BFOPTION) (3150 L x 2380 W x 3000 H) COLOURED 'BRUNSWICK GREEN'TO ACCOMMODATE PROPOSED TELSTRA EQUIPMENT ON PADFOOTING WITH CONCRETE BASEFRAME. REFER TO SHEET E1 FOREQUIPMENT LAYOUT DETAILS & NOTE 6 FOR SHELTER FOOTINGDETAILS

PROPOSED TELSTRA U/G FIBRE ROUTE (TBC)

EXISTING PARKING AREA2530

ERNHOLMES

OVAL

NA16917.01 UM SS PRELIMINARY - 30064156W20SSMC - WCDMA850 / LTE700 / LTE1800 KS IT 17.05.17 1

NOTES:1. ALL FEEDER ACCESS POINTS ON THE STRUCTURE MUST BE BIRDPROOFED AS PER EXTERNAL PLANT POLICY 003615.2. FOR SITE SPECIFIC NOTES REFER TO SHEETS S0 & S0-1.3. FOR EME SIGNS NOTED THUS #X REFER TO 005486 FOR DETAILS.4. #6 EME SIGN TO BE SECURED 1.5m AGL TO MONOPOLE.5. #13 EME SIGN TO BE SECURED TO TELSTRA SHELTER DOOR.6. REFER TO SHEETS T3 & T3-1 FOR SHELTER PAD FOOTING DETAILS.7. CLEAR ALL VEGETATION WITHIN THE COMPOUND TO MINIMISE SNAKEACTIVITY.

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

PROPOSED MONOPOLE FOUNDATION. REFERTO DRG RJ10594-3 SHEET 1 FOR DETAILS

5000

6417

PROPOSED STEEL BOLLARDS (4 OFF).REFER TO SHEETS T3 & T3-1 FOR DETAILS

#13

EXISTING TREES (TYP.)

142

142.2

142.4

141.8141.6141.4

141.2

141

142

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 2

5000

3500

560

PROPOSED TELSTRA U/G SUBMAINS.INDICATIVE ROUTE ONLY (APPROX. 50m).REFER TO SHEETS E0 & E2 FOR DETAILS

560

925

925

Page 7: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

The copyright and ownership of the drawings is to be assigned to Telstra

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S1-2

ANTENNA LAYOUT339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TN

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEETS S1 & S1-1

PROPOSED TELSTRA LTE700 PANEL ANTENNAS(3 OFF A4, A5 & A6)

PROPOSED TELSTRA WCDMA850 / LTE1800 PANELANTENNAS (3 OFF A1, A2 & A3)

PROPOSED TELSTRA LTE700 TMA'S (3 OFF)ATTACHED BEHIND PROPOSED TELSTRAPANEL ANTENNAS (A4, A5 & A6)

PROPOSED TELSTRA LTE1800 RRU'S (3 OFF)WITH JUNCTION BOXES (3 OFF) BELOW

1A1 A4

2

3

A2 A5

A6A3

1

2

3# 2 BEHIND EACH

PANEL ANTENNA

PROPOSED TELSTRA COLLAR MOUNTS (TYP.).REFER TO DRG. RJ10594-2-AM1 FOR DETAILS

PROPOSED TELSTRA 40m HIGHROAM STEEL MONOPOLE

# 2 BEHIND EACHPANEL ANTENNA

ANTENNA LAYOUT AT EL 38.7mSCALE 1:25

0 1000500 SCALE 1:25500

ANTENNA LAYOUT AT EL 35.7mSCALE 1:25

RRU LAYOUT AT EL 32.5mSCALE 1:25

NA16917.01 UM SS PRELIMINARY - 30064156W20SSMC - WCDMA850 / LTE700 / LTE1800 KS IT 17.05.17 1

NOTES:1. FOR SITE SPECIFIC NOTES REFER TO SHEETS S0 & S0-1.2. FOR EME SIGNS NOTED THUS #X REFER TO 005486 FOR DETAILS.3. #2 EME SIGN SECURED BEHIND EACH PANEL ANTENNA.4. SPARE MOUNTING POLES ON HEADFRAME ARE NOT TO BE INSTALLED.FABRICATE PANNING BASE PLATE TO SUIT 8 TIP FERRULES ON 520 PCD.

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 2

Page 8: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

T

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S3

WEST ELEVATION339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

WEST ELEVATIONSCALE 1:150

The copyright and ownership of the drawings is to be assigned to Telstra

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

SCALE 1:1500 3m 6m3m

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET S3-1

E.L. 0.0mGROUND LEVEL(R.L. 143.0m AHD)

E.L. 3.1m (±100mm) R.L. 146.1m AHDBASE OF PROPOSED TELSTRA GPS ANTENNAS (1 OFF A7)

PROPOSED SIGN SECURED TOTELSTRA SHELTER DOOR (BEHIND)

PROPOSED TELSTRA 40m HIGHSTEEL MONOPOLE. REFER TO DRGRJ10594-1 SHEET 1 FOR DETAILS

#13

EXISTING BOUNDARY FENCE

1.5m AGL #6

PROPOSED TELSTRA U/G SUBMAINS. INDICATIVEROUTE ONLY (APPROX. 50m). REFER TO SHEETS E0 &E2 FOR DETAILS

PROPOSED TELSTRA GPS ANTENNA (1 OFF A7)MOUNTED ON PROPOSED ANTENNA BRACKETMOUNT NEAR FEEDER WINDOW ON SHELTER ROOF

EXISTING TREES (TYP.)

EXISTING 1m HIGH FENCEAROUND ATHLETIC FIELD(BEHIND)

EXISTING LIGHT POLE TO BE REMOVED(AFTER INSTALLATION OF TELSTRAMONOPOLE). REFER TO NOTE 8

PROPOSED TELSTRA Ø100 U/G CONDUITS (12 OFF) TOACCOMMODATE PROPOSED TELSTRA FEEDERS (15 OFF)

PROPOSED TELSTRA DRAW PITS(4 OFF). REFER TO TELSTRA STDDRG 017866P140 FOR DETAILS

PROPOSED TELSTRA EQUIPMENT SHELTER TYPE ICSMk 4.0 (BF OPTION) (3150 L x 2380 W x 3000 H)COLOURED 'BRUNSWICK GREEN' TO ACCOMMODATEPROPOSED TELSTRA EQUIPMENT ON PAD FOOTINGWITH CONCRETE BASEFRAME. REFER TO SHEET E1FOR EQUIPMENT LAYOUT DETAILS & NOTE 9 FORSHELTER FOOTING DETAILS

PROPOSED TELSTRA U/G FIBRE ROUTE

DO NOT

1

SCALE

2

ORDER

E

D

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

AMENDMENT

3

DRAWN CHKD

4

EXAM APPD

DWGNO.

5

ISSDATE

NO.SHT

A3V6

F

E

D

C

B

A

1 2

C

B

3 4 5

A

6

Cad file: N110386.dwg

E.L. 40.0m (±100mm) R.L. 183.0m AHDOVERALL HEIGHT

# 2 BEHIND EACHPANEL ANTENNA

PROPOSED TELSTRA JUNCTIONBOXES (3 OFF)

PROPOSED TELSTRA LTE700 TMA'S (3 OFF)ATTACHED BEHIND PROPOSED TELSTRAPANEL ANTENNAS (A4, A5 & A6)

PROPOSED TELSTRA FEEDERCABLES (12 OFF) & HYBRIDCABLES (3 OFF) TO RUNINTERNALLY TO MONOPOLE

E.L. 38.7m (±100mm) R.L. 181.7m AHDC/L PROPOSED TELSTRA WCDMA850 / LTE1800

E.L. 32.5m (±100mm) R.L. 175.5m AHDC/L PROPOSED TELSTRA LTE1800 RRU'S (3 OFF)

E.L. 25.0m (±100mm) R.L. 168.0m AHDC/L EXISTING RELOCATED FLOOD LIGHTS

PANEL ANTENNAS (3 OFF A1, A2 & A3)

E.L. 35.7m (±100mm) R.L. 178.7m AHDC/L PROPOSED TELSTRA LTE700 PANEL ANTENNAS(3 OFF A4, A5 & A6)

EXISTING AUSGRID POLE #80743

PROPOSED MONOPOLE FOUNDATION. REFERTO DRG RJ10594-3 SHEET 1 FOR DETAILS

EXISTING BENCH

TOP OF MONOPOLE

NA16917.01 UM SS PRELIMINARY - 30064156W20SSMC - WCDMA850 / LTE700 / LTE1800 KS IT 17.05.17 1

NOTES:1. ALL FEEDER ACCESS POINTS ON THE STRUCTURE MUST BE BIRDPROOFED AS PER EXTERNAL PLANT POLICY 003615.2. FOR SITE SPECIFIC NOTES REFER TO SHEETS S0 & S0-1.3. FOR EME SIGNS NOTED THUS #X REFER TO 005486 FOR DETAILS.4. #2 EME SIGN SECURED BEHIND EACH PANEL ANTENNA.5. #6 EME SIGN TO BE SECURED 1.5m AGL TO MONOPOLE.6. #13 EME SIGN TO BE SECURED TO TELSTRA SHELTER DOOR.7. STRUCTURAL ADEQUACY OF PROPOSED TELSTRA MONOPOLE,MONOPOLE FOOTING, BASEPLATE WITH CONNECTIONS, PANELANTENNA MOUNTING STEELWORK, RRU MOUNTS AND FLOODLIGHTSUPPORT TO SUPPORT TELSTRA EQUIPMENT HAS BEEN CONFIRMEDAND CERTIFIED BY ROAM. REFER TO CERTIFICATE RJ10594-CER-1DATED 13/10/2017 FOR DETAILS.8. FOUNDATION HOLE TO BE BACKFILLED WITH SELECTED FILL IN200mm LAYERS. COMPACT FILL TO 95% MAX. DRY DENSITY. MAKEGROUND SURFACE GOOD.9. REFER TO SHEETS T3 & T3-1 FOR SHELTER PAD FOOTING DETAILS.

FOR CONSTRUCTION

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

REFER TO DRG RJ10594-1-1 FORFLOODLIGHT MOUNTING DETAILS

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 2

Page 9: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 S3-1

ANTENNA CONFIGURATION TABLE339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET S3

TELSTRA MOBILES ANTENNA CONFIGURATION TABLEANTENNA

NoANTENNA TYPE &SIZE H x W x D

ANTENNAHEIGHT

C/L A.G.L.

PHYSICALANTENNA

BEARING (°T)

ANTENNAACTION

REQUIRED

SECTOR NO.& TECHNOLOGY

A1 38.7m 110°INSTALL

S1: LTE1800S1: LTE1800

S1: WCDMA850S1: WCDMA850

S1: LTE1800S1: LTE1800ARGUS RVVPX310. 11B - T2 PANEL

2533 x 350 x 208

A2 38.7m 210°INSTALL

S2: LTE1800S2: LTE1800

S2: WCDMA850S2: WCDMA850

S2: LTE1800S2: LTE1800

A3 38.7m 330°INSTALL

S3: LTE1800S3: LTE1800

S3: WCDMA850S3: WCDMA850

S3: LTE1800S3: LTE1800

A4 35.7m 110°INSTALL

SPARESPARE

S1: LTE700S1: LTE700

SPARESPARE

A5 35.7m 210°INSTALL

SPARESPARE

S2: LTE700S2: LTE700

SPARESPARE

A6 35.7m 330°INSTALL

SPARESPARE

S3: LTE700S3: LTE700

SPARESPARE

ARGUS RVVPX310. 11B - T2 PANEL2533 x 350 x 208

ARGUS RVVPX310. 11B - T2 PANEL2533 x 350 x 208

ARGUS RVVPX310. 11B - T2 PANEL2533 x 350 x 208

ARGUS RVVPX310. 11B - T2 PANEL2533 x 350 x 208

ARGUS RVVPX310. 11B - T2 PANEL2533 x 350 x 208

0°ERICSSON GPSKRE 101 2082/1 OMNI Ø68 x 96 INSTALLA7 -

BASE OFGPS3.1m

NA16917.01 UM SS PRELIMINARY - 30064156W20SSMC - WCDMA850 / LTE700 / LTE1800 KS IT 17.05.17 1

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 2

Page 10: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTIONORDER

DO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 G1

SITE TENURE PLAN339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TN

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

1123 DP822285

1DP883213

1DP604119

R 45012 FOR PUBLIC RECREATION

BRIT

ANNI

A S

TREE

T

CECIL

AV

KURRAJONG ST

SEEDIAGRAM

(A)

(B) (A) RIGHT OF WAY 6 WIDE & VAR.(B) EASEMENT FOR ELECTRICAL PURPOSES 2 WIDE(C) EXCLUSIVE USE AREA

(B)

(A)

99°57'5

189°

57' 3

.5

279°57'5

9°57

' 3.5

258°27'50"

19.15348°27'50"

101.875(27.73) TO ANGLE

WORKSAREA17.5m² 348°27'50"

101.875

LEASE AREA PLANSCALE 1:1:200

0 10m2m SCALE 1:2002m 4m 6m 8m

SITE TENURE PLANSCALE 1:8000

0 400m8m SCALE 1:800080m 160m 240m 320m

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

PART OF LOT 1 ON DP 883213PARISH OF SOUTH COLAHCOUNTY OF CUMBERLAND

PROPERTY DESCRIPTION

SITE STRUCTURE CO-ORDINATES (GDA94)GPS READING ACCURACY: ± 0.1m

CENTRE OF POLE

LONGITUDE

LATITUDE GDA 94-33.743023

GDA 94151.078303

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

(C)

(C)

Page 11: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTIONORDER

DO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 G2

SITE DETAIL SURVEY339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TN

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

CONCRETE

PATH

WIRE MESH FENCE

WIRE MESH FENCE

PLAYINGFIELD

5.0

EXISTINGLIGHT POLELIGHT RL 159.03

PROPOSEDPOLE

CARPARK

SERVICEPOLEPOWER

POLE

ELTRANSFORMER

ELBOX

PITS

PITS

FIREHYD

FIREHYD

BM ON CONCRETERL 142.44

TOP OF BANK

141

142

PIT

3.5

5.0

189°

57'

3.5

5.0

TOP OF BANK

EXCLUSIVEUSE AREA

TELSTRASHELTER

PEGRL 142.35

PEGRL 142.39

PEGRL 142.10

PEGRL 142.28

BM on CONCRETERL 142.44

N 6264626.52E 322004.49

N 6264625.66E 322009.42

258°27'50"

19.15

348°27'50"

101.871

(27.73)

146°18'25"

275.685 TO SSM81017

BRITANNIA STREET

1DP 883213

"PENNANT HILLS PARK"

142

142.2

142.4

141.8

141.6

141.4141.2

99°57'

3.5

279°57'

258°27'50"

19.15

348°27'50"

WORKS AREA17.5m²

EASEMENT

FOR ELECTRICITYRIGHT OF WAY

143.0

x 142.58

x 141.67

x 142.49

TOPx 147.61

TREESTO HT 21m

SSM 81017

SITE DETAIL SURVEYSCALE 1:250

SCALE 1:2500 10m5m 5m

LEASE PLANSCALE 1:100

0 1m 2m 3m 4m 5m1m SCALE 1:100

TELSTRA WORKS AREA

THE SITE OWNER MUST BE CONTACTED FOR THIS INFORMATION.SERVICES ON PRIVATE PROPERTY MAY NOT BE ON PUBLIC RECORD.

"DIAL BEFORE YOU DIG" CALL 1100.IF SERVICES ARE DAMAGED. MINIMISE THIS RISK BY CONTACTING

PERSONS EXCAVATING THIS SITE MAY BE HELD FINANCIALLY RESPONSIBLE

THIS IS FOR PLANNING PURPOSES ONLY.ONLY VISIBLE SERVICES ARE DEPICTED ON THIS PLAN.

WARNING E:M.G.A.

INFO

RMAT

ION

CO-O

RDIN

ATE

AHD RL.ZONE N:

G.D.A. LATITUDE (S)LONGITUDE (E)PROPOSED

POLE143.0

-33.743023°151.078303°

563219906264678

COORDINATE SOURCE: L.P.I.Surveyed ±0.05m

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

6417

9°57

'

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

Page 12: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

SITE EARTHING PLAN - SCHEMATICSCALE 1:150 FOR CONSTRUCTION

FEB TO EARTH ELECTRODE

EARTHINGINSTALLATION SCHEDULEITEM DESCRIPTION

SEB TO EARTH ELECTRODE

EQUIPOTENTIAL CONDUCTOR

SEB TO SHELTER CHASSIS

POLE TO EARTH ELECTRODE STRAP

POLE TO EARTH ELECTRODE CONDUCTOR

ALL METALWORK TO THEEQUIPOTENTIAL CONDUCTOR

B

C

D

J

K

L

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 G4

SITE EARTHING PLAN339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

A

TN

LEGEND:19/1.53mm EQUIPOTENTIAL CONDUCTOR,GREEN/YELLOW (35mm²)

50 x 3mm HOT DIPPED GALVANISED STEELTAPE LAID 500mm BELOW GROUND LEVEL

FEEDER EARTH BARFEB

SERVICE EARTH BAR (1600mm AFL)SEB

EARTHING ELECTRODE IN INSPECTION TYPEP2 PIT. DETAILS AS SHOWN ON TELSTRASTANDARD DRGS 017866P201, SHEET 5

EARTHING BOND

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NOTES:1. USE EARTH ENHANCING MATERIAL (BENTONITE OR GYPSUMSLURRY) DUE TO UNFAVOURABLE GEOLOGICAL SITE CONDITIONS.2. 2.88m LENGTH S/S ELECTRODES (7 OFF).3. REFER ALSO TELSTRA STANDARD DRAWING 017866P203SHEET 30 FOR DETAILS.

K

J

J

J

J

D

B

B

C

L

PROPOSED SEBPROPOSED FEB

A

D

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

Page 13: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTIONORDER

DO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 E0

ELECTRICAL SPECIFICATION339 BRITANNIA STREET, PENNANT HILLS, NSW 2120

TELSTRA ELECTRICAL AND EARTHING SPECIFICATION:1.GENERALELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THISSPECIFICATION, SHEET E2, TELSTRA CIVIL DESIGN MANUAL, TELSTRAEARTHING MANUAL, AS/NZS 3000, AS/NZS3008, AS/NZS3015, AS/NZS3017,AS/NZS1768 ALL OTHER RELEVANT AUSTRALIAN STANDARDS, NSWSERVICE AND INSTALLATION RULES, LATEST EDITION WITH AMENDMENTSAT TIME OF CONSTRUCTION IS TO APPLY.UNDERGROUND CABLING IS TO BE INSTALLED IN uPVC HEAVY DUTY RIGIDCONDUIT. THE CABLE ROUTE SHALL BE AS SHOWN ON SHEET S1. WHERECABLE TURNS ARE REQUIRED, THE RADIUS OF ANY BENDS SHALL NOT BELESS THAN THE MINIMUM BENDING RADIUS OF THE CABLE.ALL CONDUIT SHALL BE INSTALLED AS A CATEGORY A WIRING SYSTEM ASDEFINED BY AS3000 AND SHALL HAVE MINIMUM COVER OF 500mm UNLESSNOTED OTHERWISE.ALL CABLE LENGTHS SHOWN ARE APPROXIMATE ONLY AND SHOULD BEVERIFIED ON SITE. THESE CABLE LENGTHS ARE NOT TO BE RELIED UPONFOR ORDERING OR ESTIMATION PURPOSES.CONTRACTOR SHALL MAKE THEMSELVES AWARE OF ALL SERVICESPRESENT ON SITE, ALL SITE CONDITIONS AND SAFETY REQUIREMENTSPRIOR TO COMMENCING WORK ON SITE.SITE SHUTDOWN WILL BE REQUIRED TO CARRY OUT THESE PROPOSEDWORKS. SITE SHUTDOWN TIME IS TO BE KEPT TO MINIMUM. CONTRACTORIS TO LIAISE WITH ALL AFFECTED PARTIES AND SHALL PROVIDE ANALTERNATIVE SUPPLY (MOBILE GENERATOR) IF REQUIRED.

2. POINT OF SUPPLYEXISTING PILLAR.

3. CONSUMERS MAINSPROVIDE AND INSTALL 25mm² 4 x 1C XLPE Cu CONSUMERS MAINS IN 50mmuPVC HEAVY DUTY CONDUIT FROM THE POINT OF SUPPLY TO THESHARED MAIN SWITCHBOARD/ METER ENCLOSURE.

4. MAIN SWITCH BOARD/METERINGCONTRACTOR SHALL PROVIDE AND INSTALL PROPOSED FREE STANDINGTELSTRA WEATHERPROOF (IP 23 RATED MIN) MAIN SWITCHBOARD/METERENCLOSURE SUITABLE FOR TWO CONSUMERS. THE PROPOSED MAINSWITCHBOARD/METER ENCLOSURE SHALL HOUSE:· PROPOSED SERVICE AND METER PROTECTION FUSES· PROPOSED TELSTRA 50A TP TYPE C MCB MAIN SWITCH· PROPOSED OPTUS 50A TP TYPE C MCB MAIN SWITCH· RELOCATED THREE PHASE (TP) TELSTRA METER· RELOCATED OPTUS METER.INSTALL M.E.N. AND ELECTRODE AT THIS LOCATION.THE CONTRACTOR SHALL LIAISE WITH AUSGRID FOR ALL METERINGREQUIREMENTS BEFORE THE INSTALLATION BEGINS.

5. SUB MAINSEXISTING 95mm² 4 x 1C XLPE Cu OPTUS U/G MAINS IS TO BE REROUTED TOTHE PROPOSED SHARED MAIN SWITCHBOARD/METER ENCLOSURE.USE EXISTING CABLE ROUTES/INSTALLATION METHODS WHERE POSSIBLEINSTALL PROPOSED AS REQUIRED. USE CABLE REDUCING LUGS ATTERMINATIONS.PROVIDE AND INSTALL 25mm² 4C+E XLPE Cu SUBMAINS IN 50mm DIA HDuPVC CONDUIT FROM TELSTRA MAIN SWITCH TO 50A TP LOAD BREAKISOLATOR IN ISOLATION ENCLOSURE AT THE PROPOSED TELSTRASHELTER.

6. GENERATOR SUPPLYCONTRACTOR IS TO ENSURE THAT ALL EQUIPMENT AND WIRINGCOMPLIES WITH AS/NZ3010 FOR ALTERNATE GENERATOR SUPPLY.CORRECT SWITCHING OF AUXILIARY (PORTABLE GENERATOR) SUPPLYNEUTRAL SHELTER CHANGEOVER SWITCH VIA THE INLET SOCKET WILLNEED TO BE CONFIGURED IN ACCORDANCE WITH AS3010.

7. AIR CONDITIONING HEAT LOADTHE PROPOSED WORKS WILL RESULT IN A TOTAL SHELTER HEAT LOAD OF4.05kW.PROVIDE AND INSTALL 6.3kW SPLIT SYSTEM TYPE A/C UNIT (1 OFF).

8. DC POWER SYSTEMTHE PROPOSED WORKS WILL RESULT IN A TOTAL SHELTER DC LOAD OF120 AMPS.INSTALL PROPOSED ELTEK SP22-HC POWER SYSTEM AT SUITE GD/1/01WITH 4 OFF FP2 2kW HE RECTIFIER MODULES, 4 OFF DC/DC CONVERTERSAND 4 OFF FXH190-12S BATTERY STRINGS.INSTALL PROPOSED ELTEK BATTERY EXTENSION RACK AT SUITE GD/1/02WITH 2 OFF FXH190-12S BATTERY STRING.BATTERY RESERVE TIME IS 7 HOURS AT 120 AMPS DC LOAD. REFER ALSOTO SHEET E4.

9. RBSINSTALL PROPOSED 2 x 45RU PATHFINDER RACKS AT GD/2/3 AND GD/2/4.PROPOSED PATHFINDER RACKS SHALL BE EQUIPPED WITH:· 1 x RBS6202 LTE700/1800· 6 x RUS02 B28· 1 x DUS-41· 1 x R503· 1 x SIU· 3 x FIBRE CABLE TRAY· 1 x FIBRE PATCH PANEL· 3 x DBC0086F1V2-1 COMBINERS LTE700· 2 x GPS RX· 1 x GPS SPLITTER

· 1 x RBS6202 WCDMA850· 3 x RUS02 B5· 1 x DUW-31· 3 x DDF0035F1V2 FILTERS WCDMA850REFER TO SHEET E5 FOR FINAL RACK CONFIGURATIONS.

10. RRU INSTALLATIONPROPOSED RRUS (3 OFF) ARE TO BE INSTALLED AS SHOWN ON SHEET S3.REFER TO SHEET S0 FOR TYPE AND HYBRID CABLE DETAILS.PROPOSED 12.3 WAY SPD BOX (1 OFF) IS TO BE INSTALLED AS SHOWN ONSHEET E1.THE PROPOSED RRUS (3 OFF) SHALL BE SUPPLIED FROM THE PROPOSEDSP22-HC DC POWER SYSTEM.REFER TO TELSTRA STANDARD DRAWING 017866P134 SHEET 11 FORFURTHER DETAILS.

11. EARTHING SYSTEMALL EARTHING AND BONDING IS TO BE IN ACCORDANCE WITH THETELSTRA EARTHING MANUAL 017866A07, 017866P203 SHEET 30,017866P205 SHEET 1 AND SHEET G4. LATEST EDITION WITH AMENDMENTSAT TIME OF CONSTRUCTION IS TO APPLY.

12. FEEDER EARTH BAR (FEB)PROVIDE PROPOSED FEB INSIDE THE TELSTRA SHELTER, DIRECTLYBELOW THE INTERNAL SEB/SPC BAR. FEB IS TO BE CONNECTED TOCLOSEST EARTH ELECTRODE USING STRANDED 35mm² Cu G/Y PVCINSULATED CABLE. REFER TO TELSTRA STANDARD DRAWINGS 017866P201SHEETS 19 & 20.

13. LTE700 GPS SYSTEMPROVIDE AND INSTALL GPS ANTENNA FOR LTE700 MOUNTED ON THEPROPOSED GPS MOUNT.

14. FLOODLIGHTINGEXISTING FLOODLIGHTING IS TO BE RELOCATED TO PROPOSED TELSTRAMONOPOLE. REFER ALSO SHEET S3. REUSE EXISTING CIRCUITS. EXTENDOR REPLACE EXISTING CABLING AS REQUIRED.

Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET E1

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

Page 14: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTIONORDER

DO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 E1

EQUIPMENT LAYOUT339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET E0LIGHT SWITCH

PROPOSED EQUIPMENT

EXISTING EQUIPMENT

RESERVED EQUIPMENTCEILING HEIGHT 2700-2750

PROPOSED TELSTRA NATIONAL ICS Mk 4.0EQUIPMENT SHELTER - EQUIPMENT LAYOUT WIND REGION A

SUITE 2RE

LIEF

LOUV

RE(A

BOVE

DOO

R)

ISOLATIONENCLOSURE WITHGENERATORRECEPTACLE BELOW

SCALE 1:20

MISCELLANEOUS RACKRBS6202LTE700 /LTE1800

SUITE 1GD/1/04

ELTEKSP22-HC

DISTRIBUTION & CONTROLBOARD ATTACHED TO METALPLATE HANGING FROM CEILING SP

LIT S

YSTE

M IN

DOOR

UNI

T

NOTES:1. FOR SITE SPECIFIC NOTES REFER TO SHEETS S0, S0-1 & E0.2. REFER TO ICS DRAWINGS IN CADLINK NATIONAL DATABASE.3. MITS POSITIONS IN FORMAT XX/X/XX WHERE SHELTER ONGROUND PREFIX GD/1/01 AND SHELTER ON ROOFTOP PREFIXRT/1/01. REFERENCE SP000511 NUMBERING, LABELLING ANDDATA ENTRY REQUIREMENTS OF NETWORK INVENTORY.

LEGEND

RBS6202WCDMA850

PROPOSED TELSTRA GPSANTENNA (1 OFF A7) MOUNTED ON PROPOSEDANTENNA BRACKET ON SHELTER ROOF

PROPOSED GPS SURGEARRESTOR DEVICE NGC90145 TOBE WALL MOUNTED

PROPOSED RBS6202 (2 OFF), WITH RUS-02 (B5) (3 OFF), RUS-02 (B28) (6 OFF), DUS-41 (1 OFF),DUW-31 (1 OFF), R503 (1 OFF), COMBINERS (3 OFF), FILTERS (3 OFF) & SIU (1 OFF) IN THEPROPOSED 45RU PATHFINDER RACKS. REFER TO SHEET E5 FOR DETAILS

ELTEK SP22BATTERY

EXTENSION RACK

REFER TO SHEETS E0 AND E4 FORRECTIFIERS AND BATTERY QUANTITIES

RELOCATE TRANSMISSIONEQUIPMENT TO MISC RACK

SPARE

2380

2180

100

100

940

900 (

CLEA

R OP

ENIN

G)

640

600

2950

3150

35

100100

180305

505 600

SPARE

GD/1/01 GD/1/02 GD/1/03

SPAREGD/2/02 GD/2/03 GD/2/04

GD/2/05

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

3050

PROPOSED 6.3kW SPLIT SYSTEM AIR CONDITIONER

PROPOSED 12.3 WAY SPD

660

7811

0078

1100

PROPOSED TELSTRA 6.3kW A/C OUTDOORUNIT (1 OFF)

50

Page 15: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTIONORDER

DO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 E2

AC POWER - CONNECTION339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

BY AUSGRID

BY TELSTRA CONTRACTOR

EARTH BARNEUTRAL BAR

EMERGENCYGENERATORRECEPTACLE

SINGLE LINE DIAGRAM

EXISTING AUSGRID PILLAR

4 x 1C 25mm² Cu XLPE / PVC(APPROX. 5m)

kWhT

50A

PROPOSED TELSTRAEQUIPMENT SHELTER

PROPOSED SHARED FREESTANDING MAIN SWITCHBOARD /METER ENCLOSURE

kWhT

CIRCUIT BREAKER 50A

GENERATOR INLET SOCKET

LEGEND:

T = TELSTRAPOLYPHASE METER

FUSE

DISTRIBUTION BOARD

MAINS GEN.

OFF MANUAL CHANGEOVERSWITCHMAINS GEN.

M.E.N LINK

THREE PHASE

MAINS GEN.

OFF

MAINS GEN.

NOT TO SCALE

kWhO

50A

TO EXISTING OPTUSCOMPOUND ISOLATIONENCLOSURE

O = OPTUS

ISOLATOR

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

EXISTING AUSGRID POLE#80743

50A

25mm2 4C + E XLPE Cu(APPROX. 50m)

Page 16: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 E4

DC POWER LINE DIAGRAM339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

FOR CONSTRUCTIONFOR CONSTRUCTION

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

AC MAIN SWITCHBOARD

COMMON

ELTEK SP22-HC CONVERTER 48/48 POWER SYSTEM - (274/80040)

L1-1

EQUIP RACKS

TO MISC RACKTO MOBILE

L2-1

L3-1

NOTE

2

175A ANDERSONCONNECTOR

32A

G/Y1 x 35mm²

1 x 10mm²

32A

32A

1 x 10mm²

1 x 10mm²

EARTH BAR

SERVICEEARTH

ELECTRODE

S.P.C

G/Y1 x 16mm²

G/Y1 x 35mm²G/Y1 x 35mm²

G/Y

1 x 35

mm²

G/Y

1 x 35

mm²

S.E.B

C120

-48V/2000W

-48V/2000WRECTIFIER 3

RECTIFIER 4

RECTIFIER 5

RECTIFIER 6

RECTIFIER 7

RECTIFIER 8

RECTIFIER 9

RECTIFIER 2

RECTIFIER 1

(274/09423)FLATPACK 2

MODULE ELTEK

SUBRACKRECTIFIER

BATTERYSTRING 1

150A

MONOBLOCK 4MONOBLOCK 3MONOBLOCK 2MONOBLOCK 1

1 x 25

mm²

1 x 25

mm²

BATTERY MONOBLOCKS - FXH190-12S

B1

-48V/2000W

SMARTPACKCONTROLLER

INTERFACEALARM

ALARM RELAYOUTPUTS

(242100.118 274/00810)(SUBRACK 2)

HE RECTIFIERPLUG-IN

MCB

RACK EARTH

LIGHTNINGPROTECTION

SYSTEM

N

E

NOTE 8NOTE 7

EARTH BONDING TERMINAL

RECTIFIER 10

RECTIFIER 11

CABLE TRAYG/Y1 x 35mm²

BATTERYSTRING 1

(SUBRACK 9)

BATTERYSTRING 2

(SUBRACK 8)

BATTERYSTRING 3

(SUBRACK 7)

BATTERYSTRING 4

(SUBRACK 6)

SMART PACK 2CONTROLLER &

CONVERTERDISTRIBUTION(SUBRACK 3)

RECTIFIERSUBRACK

(SUBRACK 2)

DISTRIBUTION(SUBRACK 1)

DC-DCCONVERTERS(SUBRACK 4)BATTERY CBs(SUBRACK 5)

11

7

8

4

5

6

1

2

3

7

4

3

8

5

2

1

6

BANK

9

10

LVD

125A

F1

125A

F2

125A

F3

125A

F4

125A

F5

125A

F6

32A

F7

32A

F8

32A

F9

32A

F10

F11

20A

F12

10A

F13

6A

F14

6A

F15

4A

F16

4A

F17

150A

F18/19

150A

F20/21

F22

F23

DISTRIBUTION(SUBRACK 1)

1 x 35mm² PROPOSED RBS6202 LTE700 / LTE1800

SPARE

SPARE

1 x 35mm² PROPOSED RBS6202 WCDMA850

PROPOSED SHELTER ENVIRO. CONTROL (PLC)

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

1 x 2.5mm² PROPOSED LTE SIU

SPARE

VACANT

VACANT

DC/DC DISTRIBUTION(SUBRACK 4)

F24125A

F25125A

F26125A

F27125A

PROPOSED 12.3 WAY SPD FEED A

SPARE

SPARE

FEBISOLATED EARTH

1 x 35mm²

PROPOSED 12.3 WAY SPD FEED B1 x 35mm²

20A

1 x 2.5mm²

SPARE

1 x 2.5mm²

DC-DC CONVERTER SUBRACK 4 (1ST SHELF)

DC-DC CONVERTER SUBRACK 4 (2ND SHELF)

BATTERYSTRING 5

(SUBRACK 4)

BATTERYSTRING 6

(SUBRACK 3)

BATTERYSTRING 7

(SUBRACK 2)

GD/1/01

BATTERYSTRING 8

(SUBRACK 1)

ELTEK SP22-HCGD/1/02

ELTEK BATTERY EXTENSION RACK

-48V/2000W

BATTERYSTRING 2

150A

1 x 25

mm²

1 x 25

mm²

B2

BATTERYSTRING 3

150A

1 x 25

mm²

1 x 25

mm²

B3

BATTERYSTRING 4

150A

1 x 25

mm²

1 x 25

mm²

B4

NOTE: LOW VOLTAGE BATTERY DISCONNECTNOT ALWAYS FITTED

BATTERYSTRING 5

1 x 25

mm²

1 x 25

mm²

MONOBLOCK 8MONOBLOCK 7MONOBLOCK 6MONOBLOCK 5

150A

B5

SPARE

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NOTES:1. EARTHING AND A.C. WIRING IAW AS3000, AS3015, & OTHER RELEVANTDOCUMENTATION.2. REFER TO MANUFACTURERS HAND BOOK FOR AC CONNECTIONS.3. PANEL NUMBERING IN THE SUBRACK NUMBERED AS ENTERED INSTRUCTURE BUILDER/MITS.4. CELLS TO BE NUMBERED FROM 1 AT THE POSITIVE END OF STRING.5. BATTERY STRINGS TO BE NUMBERED AS SHOWN ABOVE.6. BATTERY EXTENSION RACK (274/01053) TO BE INSTALLED AS REQUIRED.7. REFER MANUFACTURER'S HANDBOOK FOR INPUT BREAKER SIZE.MINIMUM 32A, RECOMMENDED 50A Th/Mag E.G. MGC60H OR Hy/mAG C2E.G. CBI QF OR QY.8. REFER MANUFACTURER'S HANDBOOK FOR CABLE SIZE. MINIMUM 6mm²,RECOMMENDED 10mm².

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

1 x 25

mm²

1 x 25

mm²

150A

B6

BATTERYSTRING 6

Page 17: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

NOTES:1. FOR SITE SPECIFIC NOTES REFER TO SHEETS S02. INDICATIVE 45RU PATHFINDER RACK SHOWN FOR LAYOUT PURPOSES ONLY.3. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS SPECIFIED OTHERWISE.4. REFER TO DOCUMENT CIN0005 LTE700 SITE ENGINEERING GUIDELINES FORFURTHER INFORMATION.

DO NOT

1

SCALE

2

ORDER

E

D

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

AMENDMENT

3

DRAWN CHKD

4

EXAM APPD

DWGNO.

5

ISSDATE

NO.SHT

A3V6

F

E

D

C

B

A

1 2

C

B

3 4 5

A

6

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 E5

PATHFINDER CHANNEL RACK LAYOUT339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

FOR CONSTRUCTIONSIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

ELEVATIONSCALE 1:10

BASE (150mm)

530

45RU 19 INCH RACK (187/01629)

GD/2/04

SIU-02 UNIT

FIBRE MANAGEMENT 1

GPS

SPLIT

TER

GPS

Rx

23

12

FIBRE STORAGE TRAY

EARTH BAR

RBS6202LTE700 / LTE1800

DUS-

41

FUTURE DU ADAPTOR

BASE (150mm)

530

2200

45RU 19 INCH RACK (187/01629)

GD/2/03

FUTURE RBS

RBS6202WCDMA850

LTE7

00 C

OMBI

NER

3-WAY FILTER MOUNT

FUTURE RBS6601

R503

DIG

ITAL

UNI

T

FUTURE SIU-02 UNIT

FUTURE RBS 6601

FUTURE FIBRE MANAGEMENT

12

FUTURE PATCH PANEL

RUS0

2 B5

EARTH BAR

FUTURE DU ADAPTOR

FUTURE CABLE GUIDE

DUW

-31

CABLE GUIDE

FIBRE PATCH PANELFU

TURE

RU

RUS0

2 B5

WCD

MA85

0 IM

FILT

ER

FUTURE FIBRE MANAGEMENT

FUTURE FIBRE MANAGEMENT

FUTU

RECO

MBIN

ERRU

S02 B

28

RUS0

2 B28

FIBRE MANAGEMENT 2

FIBRE MANAGEMENT 3

LTE7

00 C

OMBI

NER

LTE7

00 C

OMBI

NER

RUS0

2 B28

RUS0

2 B28

RUS0

2 B28

RUS0

2 B28

FUTU

RE R

U

RUS0

2 B5

FUTU

RE R

U

WCD

MA85

0 IM

FILT

ER

WCD

MA85

0 IM

FILT

ER

1

PROPOSED TELSTRA GPSANTENNA SPLITTERLOCATION (1 OFF)

PROPOSED TELSTRA GPSANTENNA RECEIVER UNITS(2 OFF) (TYP.)

37

27

2200

3-WAY FILTER MOUNT 3-WAY FILTER MOUNT

3-WAY FILTER MOUNT

2 FUTU

RE IM

FILT

ER

FUTU

RE IM

FILT

ER

FUTU

RE IM

FILT

ER

FUTU

RECO

MBIN

ER

FUTU

RECO

MBIN

ER

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 VC JB 06.02.18 1

Page 18: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 T3

SHELTER FOOTING DETAILS - SHEET 1 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOX

FOR CONSTRUCTION

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

SHELTER PLANSCALE 1:25

TN 5000

1951890

3500

300

2500

PROPOSED TELSTRA EQUIPMENT SHELTER TYPEICS Mk 4.0 (3150 L x 2380 W x 3000 H) ON PADFOOTING WITH CONCRETE BASEFRAME

PROPOSED TELSTRA SHELTER PAD FOOTING(5m x 3.5m) WITH 300 x 650 EDGE BEAM

PROPOSED TELSTRA Ø165.1 x 5.0 CHSBOLLARDS (4 OFF)

PROPOSED TELSTRA FLOORGLAND (Ø150 PENETRATION -4 OFF)

PROPOSED TELSTRA 6.3kW A/COUTDOOR UNITS (2 OFF)

730730

200

200

NOTES:1. FOR STANDARD CONSTRUCTION NOTES REFER TO TELSTRASTANDARD DRAWING 017866P05.2. CONCRETE COMPRESSIVE STRENGTH TO BE f'c = 32MPa AT 28 DAYS.3. COVER TO BE 75 TYPICAL.4. SAFE WORKING PRACTICE TO BE CARRIED OUT IN ACCORDANCE WITHAS2159 AND STATE AND LOCAL REGULATIONS.5. BACKFILL TO BE GRANULAR, FREE OF ORGANIC MATERIAL ANDCOMPACTED TO AT LEAST 95% MAXIMUM DRY DENSITY.6. REFERENCE TO BE GEOTECHNICAL REPORT BY STSGEOENVIRONMENTAL PTY LTD (REPORT NO: 16/2209) DATED AUGUST2016 FOR SOIL CONDITIONS.7. LOCATION OF UNDERGROUND SERVICES TO BE CHECKED ON SITEBEFORE EXCAVATION.8. GEOTECHNICAL CONDITION TO BE CONFIRMED ON SITE BEFOREPOURING CONCRETE FOR FOOTING BY RPEQ GEOTECHNICAL ENGINEER.9. TOP FILL SOIL NEEDS TO BE REMOVED PRIOR TO CONSTRUCTION.

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET T3-1

630630

300

C HOLD-DOWN BOLTL C HOLD-DOWN BOLTL

C HO

LD-D

OWN

BOLT

LC

HOLD

-DOW

NBO

LTL

PROPOSED TELSTRA SHELTERHOLD-DOWN BRACKET

PROPOSED TELSTRA BASE PLATE.REFER TO SHEET T3-1 FOR DETAILS

70

150

195

300TYP.

Page 19: SITE REFERENCE DETAILS SITE SPECIFIC NOTES

ORDERDO NOTSCALE

F

1

E

D

2 3

C

B

A

1 2 3

C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved.

4 5

DWGNO.

DRAWN CHKD AMENDMENT DATEEXAM APPD ISS

6NO.SHT

A3

F

E

D

4 5

C

B

6

A

Cad file: N110386.dwg

MOBILE NETWORK SITE 311207PENNANT HILLS PARK 339 BRITANNIA ST

N110386 T3-1

SHELTER FOOTING DETAILS - SHEET 2 OF 2339 BRITANNIA STREET, PENNANT HILLS, NSW 2120Level 1, 29 Christie Street, St. Leonards NSW 2065

T +61 2 9478 9999 | F +61 2 9478 9900 | www.servicestream.com.au

SIGNATURE

COMPLETED AS PER DESIGNALTERATIONS IN RED

DATENAME (PRINT)

COMPLIANCE BOXFOR CONSTRUCTION

The copyright and ownership of the drawings is to be assigned to Telstra

Telst

ra N

etwor

ks W

ireles

s pro

gram

Deli

very

Temp

late -

0178

66P0

2 iss

ue 11

.4 X

X /X

X/ 20

15

NA16917.01 AD SS FC- 30069054W0001SSMC - WCDMA850 / LTE700 / LTE1800 KS MD 06.02.18 1

SHELTER FOOTING DETAILSSCALE 1:25

PROPOSED TELSTRA EQUIPMENTSHELTER TYPE ICS Mk 4.0 (3150 L x2380 W x 3000 H) ON PAD FOOTINGWITH CONCRETE BASEFRAME

PROPOSED TELSTRA SHELTER PAD FOOTING(5m x 3.5m) WITH 300mm x 650mm EDGE BEAM

PROPOSED TELSTRA Ø165.1 x5.0 CHS BOLLARDS (4 OFF)

PROPOSED TELSTRA 6.3kWA/C OUTDOOR UNITS (2 OFF)

25 NON SHRINK GROUT

FILL WITH CONCRETE f'c=25 MPaROUNDED FINISH ON TOP

PAINT WITH REFLECTIVEYELLOW COLOUR

50mm THICK (MIN) BLINDING SAND COMPACTED TO LEVEL FINISH

GROUNDLEVEL

3mm THK POLYTHENE MEMBRANE TYP.

200 THK CONCRETE

R10 AT NOMINAL500 CTRS3L12TM (TYP.)

600

50

300 100

200

650

100

TYP.

1000

3625

100

NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET T3

NOTES:1. FOR STANDARD CONSTRUCTION NOTES REFER TO TELSTRASTANDARD DRAWING 017866P05.2. REFER TO NOTES IN SHEET T3.

Ø18 HOLES

4590

6065

HOLD-DOWN BRACKET DETAILSCALE 1:5

100 x 10 EA HOLD-DOWNBRACKET HOT DIPGALVANISED TO AS4180

Ø22 HOLES

PROPOSED TELSTRA FLOOR GLAND (Ø150 PENETRATION - 4 OFF)

E.L. 0.0mGROUND LEVEL

PROPOSED TELSTRA EQUIPMENTSHELTER CONCRETE BASEFRAME

SHELTER HOLD-DOWN BRACKET.REFER TO DETAIL

M16 S/S THREADED ROD 125EMBEDMENT WITH HILTI HVU FOILCAPSULE. PROVIDE 45° SPLAY ATEND OF ROD TO ALLOW FORCAPSULE MIXING (TYP.)

SHELTER LIFTER TO BE REMOVEDAFTER SHELTER LOCATED ONSITE. REUSE EXISTING M20FERRULE TO ATTACH HOLDDOWN BRACKET (4 OFF)

SL92 MESH TOP AND BOTTOM (TRIMWIRES AROUND CONDUITS) TYP.SHELTER CONCRETE BASE

REFER TO HOLD-DOWN DETAIL

HOLD-DOWN DETAILSCALE 1:25

125

BOLLARD PLATE DETAILSSCALE 1:10

25030 190 30

300

5020

050

16 PL4 HOLES Ø18 FOR4 M16 BOLTS

250 x 300 x 15 THK BASE PLATE C/W4 x Ø18 HOLES. REFER TO BOLLARDPLATE DETAILS

M16 S/S THREADED ROD 125EMBEDMENT WITH HILTI HVU FOILCAPSULE. PROVIDE 45° SPLAY ATEND OF ROD TO ALLOW FORCAPSULE MIXING (TYP.)

PROPOSED TELSTRAØ165.1 x 5.0 CHSBOLLARDS (4 OFF)

5000