sis slides v1
TRANSCRIPT
-
8/10/2019 Sis Slides v1
1/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 1Slide 1
SAFETY INSTRUMENTED SYSTEMS &
EMERGENCY SHUTDOWN SYSTEMS
for Process Industriesusing IEC 61511 and IEC 61508
Unit 7: SIL Instrument Selection
Version for EQO26: 7 November 2012
Presented by Dave Macdonald,
EIT Cape Town South Africa
Contact E-mail: [email protected]
EIT Safety Instrumentation E-Learning
-
8/10/2019 Sis Slides v1
2/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 2
Introduction to Chapter 7: Practical selection ofsensors and actuators for safety duties
Impact on SIS Reliability,
Types of Sensors and Actuators
Failure modes and causes
Separation, redundancy, diversity, diagnostics
Device Selection Issues: What IEC 61511 requires + Common sense
Technologies: Safety certified instruments and fieldbus
-
8/10/2019 Sis Slides v1
3/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 3
Sensors and Actuators remain the most critical reliability items in an SIS
Separation, diversity and redundancy are critical issues.
Safety related instruments must have a proven record of performance.
IEC 61508 / 61511 have specific requirements
Logic solver intelligence and communications power will help to provide
diagnostic capabilities to assist field device reliability
Failure modes and common cause issues are potential problems for
intelligent instruments
-
8/10/2019 Sis Slides v1
4/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 4
Instrument practice for safety systems : well established
ISA S 84.01 Appendix B.obsolete standard but still relevant.
IEC 61511 specifics defined in clause 11.5 and 11.6 of part 1. Gruhn & Cheddie ISA Textbook; chapter 9
IEC 61511-1 Paragraph 11.5:
Requirements for selection of components and subsystems 11.5.2.1 Components and subsystems selected for use as part of a safety
instrumented system for SIL 1 to SIL 3 applications shall either be inaccordance with IEC 61508-2 and IEC 61508-3, as appropriate, or else theyshall be in accordance with 11.4 and 11.5.3 to 11.5.6, as appropriate
Certifiedcompliant toIEC 61508
Faulttolerance
Prior use
justification
-
8/10/2019 Sis Slides v1
5/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 5
Typical Reliability Table
Item Fail to
Danger Rate/ yr.
PFD avg(3 month proof test)
PFD avg
% of total
Input sensor loop 0.05 0.006 32
SIL 3 Logic Solver PLC 0.0005 3
Output Actuator loop
(Solenoid + valve)
0.1 0.0125 65
Totals 0.019 (SIL 1) 100
The field devices taken together contribute 97% of the PFD for this example.
The PFD figures for the field devices are affected by environmental conditions
and maintenance factors.
PES logic solvers benefit from auto-diagnostics.
Table 7.1
-
8/10/2019 Sis Slides v1
6/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 6
Bus connected safety certified instrumentsFoundation Field Bus
Profi-safe
ASI-Safety Bus
See Session 5
-
8/10/2019 Sis Slides v1
7/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 7
! " #
Good reliability and accuracy
Signal present at all timesimproved SFF Potential for diagnostics, easier to detect faults
Possible to compare signal with other parameters
Trending and alarming available Multiple set points
Competitive pricing
Rationalized spares
-
8/10/2019 Sis Slides v1
8/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 8
$
Components of the instrument
Process connection
Fouling /corrosion/process fluids/clogging
Wiring
Environmental: Process/Climate/Electrical
Specification/range/resolution.
Response time
Power supplies
Intrinsic safety barriers
Calibration/testing/ left on test/isolated.
-
8/10/2019 Sis Slides v1
9/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 9
$
SIS
Logic
Electrical Drive Trip
Interlocks
M
Process Valve Trip
380 v ac
power
SIS
Logic
Figure 7.4
-
8/10/2019 Sis Slides v1
10/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 10
Safety
Relay
K1
Relay
K1 Time
Delayed
Reset
Drive
controller
Stop Category 1
Safety Control Category 2
E-Stop
command
Power
%& & # '(
-
8/10/2019 Sis Slides v1
11/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 11
Components of the actuator, positioner, mechanical
failures of springs
Process connection/leaks. Mechanical distortion of
pipes causing stress in valve
Valve internal faults due to : Fouling or corrosion by
process fluids/jamming/sticking/leaking Wiring to solenoids
Pneumatics/ venting failures
Environmental. Physical impacts/fire/freezing oricing up.
Solenoid valves sticking or blocking
Potential Causes of Failures in Final Elements
-
8/10/2019 Sis Slides v1
12/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 12
) * $% "&
Sensor contacts closed during normal operation
Tx signals go to trip state upon failure (Normally < 4mA)
Broken wire = trip
Output contacts closed and energized for normal operation
Final trip valves go to trip (safe) position on air failure
Drives go to stop on trip or SIS signal failure
-
8/10/2019 Sis Slides v1
13/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 13
For an instrument to qualify for SIL target
Prior Use Build to IEC 61508 HW & SW
Smart tx
SIL 3 requires
assessement and a safety
manual
And PFD must satisfy SIL target
Certify to IEC 61508Analog or switch
or
Apply IEC 61511
limitations
SIL 1 or 2
-
8/10/2019 Sis Slides v1
14/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 14
# +
Do not share sensors because it:
Violates the principles of independence
Creates a high level of common cause failure
Does not create a separate layer of protection
Does not provide secure maintenance
-
8/10/2019 Sis Slides v1
15/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 15
Boiler Steam
Drum
LT1
Feed watersupply
LSL
SIS Logic Solver
Logic
Boiler
Trip
LIC
1
Figure 7.5Snap question: What is wrong with this safety tripdesign?
Snap question: Draw a better arrangement
-
8/10/2019 Sis Slides v1
16/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 16
Boiler Steam
Drum
Separate Sensors for Control and Trip: Acceptable
LT1
Feed watersupply
LIC
1
SIS Logic Solver
Logic
Boiler
Trip
LT2
LSL
Figure 7.5 cont.
-
8/10/2019 Sis Slides v1
17/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 17
Boiler Damage
AND
OR
FW Fails
LT-1 Fails
high-No TripLIC causes
low level
Boiler Damage
AND
OR
FW Fails LT-1 Fails
high, LIC-1
causes low
level
0.2 / yr.
0.1 / yr.
LT-2 Fails high
Trip fails on
demand
PFD = 0.1/2 X 0.5
= 0.025
0.0075 / yr.
Low level and NO TRIP
Low level
0.3 / yr.
Trip fails on demand from
FW failure
FW Fails and
No Trip
0.105 / yr.
Low level and NO TRIP
PFD = 0.1/2 X 0.5
= 0.025
0.2 / yr.
0.005 / yr.
0.1 / yr.
Separate Sensor
Fault Tree Analysis for Boiler Low Level TripShared Sensor
Figure 7.6
-
8/10/2019 Sis Slides v1
18/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 18
& , $ & - , .-./
Sharing of sensor between SIS and BPCS only allowed
if safety integrity targets can be met. This would requiresensor diagnostics and is only likely to be possible for
SIL 1
Separate sensor is allowed to be copied to BPCS viaisolator
SIL 2, 3 and 4 normally require separate sensors with
redundancy
SIL 3 and 4 normally require separation and diverse
redundancy
-
8/10/2019 Sis Slides v1
19/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 19
& , $ & - , .-./
A single valve may be used for both BPCS and SIS but
is not recommended if valve failure places a demand onthe SIS.
Normally shared valve can only be used if: Diagnostic
coverage and reaction time are sufficient to meetsafety integrity requirements
Recommendations for a single valve application
SIL 2 and SIL 3 normally require identical or diverse
separation. Diversity not always desireble
-
8/10/2019 Sis Slides v1
20/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 20
!&& ', 0
SIS
BPCS
FY
FV
A/S
Check hazard demands due to valve
Positioner
Solenoid valve
direct acting,
direct mounted.
De-energise to
vent actuator.
Figure 7.7
-
8/10/2019 Sis Slides v1
21/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 21
& # '
0 - 0 1
Check hazard demands due to valve
SIS BPCS
A/S
FY
Figure 7.8
-
8/10/2019 Sis Slides v1
22/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 22
Do not confuse with proof testing
Compare trip transmitter value with relatedvariables. Not often practicable
Use safety transmitters if available
Use Smart transmitters with diagnostic alarm
but see next
-
8/10/2019 Sis Slides v1
23/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 23
Valve Diagnostics
Assurance that a trip valve will respond correctly when needed
Freedom of movement, full travel
Correct venting of actuator
Correct rate of response
Absence of sticking
Trip signals and solenoid all working
-
8/10/2019 Sis Slides v1
24/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 24
Methods for Valve Diagnostics
Online trip testing
Discrepancy alarm
Position feedback response testing
Partial closure testing manual or automatic
Smart positioners certified safety positioner
-
8/10/2019 Sis Slides v1
25/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 25
& 23
IEC 61508 places an upper limit on the SIL that can beclaimed for any safety function on the basis of the fault
tolerance of the subsystems that it uses.
Limit is a function ofthe hw fault tolerancethe safe failure fractionthe degree of confidence in the behaviour under fault
conditions
Details in IEC 61508 part 2
-
8/10/2019 Sis Slides v1
26/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 26
23 *&
IEC Defines two types of equipment for use in SafetySystems:
Type A: Simple Devices: Non PES. E.g Limit switch, levelfloat switch, analogue circuits.
Type B: Complex Devices: Including PES. E.G Smarttransmitters. Digital communications, processor based systems.
Fault tolerance rating of B is less than A except under certainconditions
-
8/10/2019 Sis Slides v1
27/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 27
IEC 61511-1 Table 6: Minimum hardware fault tolerance of
sensors, final elements and non PES logic
SIL Minimum HW Fault Tolerance
1 0
2 1
3 2
4 Special requirements: See IEC 61508
Alternatively tables 2 and 3 of IEC 61508 may be applied with an assessment
The following summarized conditions apply for SIL 1,2 and 3 :
Increase FT by 1 if instrument does not have fail safe characteristics
Decrease FT by 1 if instrument meets 4 conditions.
Predominately fail safe
Prior Use ( Proven in use)Limited device adjustment (process parameters only)
Password protected
-
8/10/2019 Sis Slides v1
28/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 28
4& 0 #, 4 5
-
8/10/2019 Sis Slides v1
29/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 29
4& 0 #, 4
-
8/10/2019 Sis Slides v1
30/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 30
4&
0#,4
-
8/10/2019 Sis Slides v1
31/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 31
Redundancy Options
Sensor or Actuator
Configuration.
Selection
1oo1 Use if both PFD and FT and nuisance triptargets are met.
1oo2 2 Sensors installed, 1 required to trip. PFD
value improved, nuisance trip rate doubled.
2oo3 3 Sensors installed, 2 required to trip. PFDimproved over 1oo1, nuisance trip ratedramatically reduced.
Table 7.4
-
8/10/2019 Sis Slides v1
32/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 32
Common Cause Failures in Sensors
Wrong specification
Hardware or circuit design errors
Environmental stress
Shared process connections
Wrong maintenance procedures
Incorrect calibrators
-
8/10/2019 Sis Slides v1
33/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 33
Be careful to analyze
for common causefaults
e.g Try to avoid this
PT
1B
PT
1A
SIS
Figure 7.10
-
8/10/2019 Sis Slides v1
34/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 34
Where measurement is
the problem use diverse
redundancy.
e.g. Steam or Ammoniaoverpressure protection
TT
01
PT
01
SIS
Figure 7.11
-
8/10/2019 Sis Slides v1
35/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 35
Requirements for Device to be Provenin-use
Evidence that the instrument is suitable for SIS
Consider manufacturers QA systems
PES devices need extra validation
Performance record in a similar profile
Adequate documentation
Volume of experience, > 1 yr exposure per case.
-
8/10/2019 Sis Slides v1
36/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 36
The approved safety instrument list
Each instrument that is suitable for SIS
Update and monitor the list regularly
Add instruments only when the data is adequate
Remove instruments from the list when they let you down
Adequate details: Include the process application
EIT E C SS U i 7 I S l i
-
8/10/2019 Sis Slides v1
37/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 37
Additional requirements for smart transmitters
and actuators:
Details in IEC 61511 11.5.4 for devices with
Fixed Programming Languages (FPLs)Extra for SIL 3
Formal assessmentlow probability of failure in planned
application.
Appropriate standards used in build
Consider manufacturers QA systems
Must have a safety manual
EIT E C t SS U it 7 I t t S l ti
-
8/10/2019 Sis Slides v1
38/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 38
6 ! 7 &
Smart
Transmitter
4-20 mA + FSK Data
Hart
Interface
DI
SIS Logic Solver
AI
Status Alarm
Hand Held
Programmer
Figure 7.12
FSK = Frequency Shift Keyed
EIT E C t SS U it 7 I t t S l ti
-
8/10/2019 Sis Slides v1
39/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 39
4& !
Figure 7.1
EIT: E Cert SS: Unit 7 Instrument Selection
-
8/10/2019 Sis Slides v1
40/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 40
+ !,
Internal diagnostics with high coverage factor
Very low PFDavg values. Saves on proof testing etc.
Certified for single use in SIL 2 (instead of dual channel)
Certified for dual redundant use in SIL 3 (instead of 1oo3)
End user verification is simplified
EIT: E Cert SS: Unit 7 Instrument Selection
-
8/10/2019 Sis Slides v1
41/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 41
& 8The safety manual presents all the essential information and set
up conditions that must be followed to allow the instrument to
be validated for any given application.
The manual also supplies the failure rates summary and
expected PFDavg
Compliance to safety manual requirements must be
demonstrated in the validation phase.
See examples of safety manuals and FMEDA reports
EIT: E-Cert SS: Unit 7 Instrument Selection
-
8/10/2019 Sis Slides v1
42/100
EIT: E-Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 42
& The safety certificate is issued by the testing body to clearly define what
products have been tested and what standards and limitations have been
applied in the evaluation.
The safety certificate is an essential document for the validation phase.
See examples of Safety Certificates: 3051C and Rex Radar
Testing Authorities include :TUV Rheinland
Exida.com
Any recognized testing body that can show competency in the SIS field.
Note : Exida specializes in certifying instruments claiming prior usequalification. Reports supply SFF and failure rate data with declaration of fault
tolerance requirements relevant to IEC 61511. See examples.
EIT: E-Cert SS: Unit 7 Instrument Selection
-
8/10/2019 Sis Slides v1
43/100
EIT: E Cert SS: Unit 7 Instrument Selection
www.eit.edu.au
Slide 43
$
Instruments must be well proven for safety with an assessment
report or Certified SIL capable to IEC 61508.
Intelligent instruments treated as PES
Separation, Redundancy, Diversity, Diagnostics
Diagnostic Coverage via Smarts or Logic Solver
Bus technology established and growing.
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
44/100
EIT EQO26: Unit 8 Reliability Analysis
www.eit.edu.au Slide 44
Slide 44
SAFETY INSTRUMENTED SYSTEMS &
EMERGENCY SHUTDOWN SYSTEMS
for Process Industriesusing IEC 61511 and IEC 61508
Unit 8: Reliability Analysis
Version for EQO26: 7 November 2012
Presented by Dave Macdonald,
EIT Cape Town South Africa
Contact E-mail: [email protected]
EIT Safety Instrumentation E-Learning
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
45/100
Q y y
www.eit.edu.au Slide 45
The task of measuring or evaluating the SIS design
for its overall safety integrity
Reasons and objectives
Resolving the SIS into reliability block diagrams
Identification of formulae
Trial calculation examples
Calculation software tools
Introduction to Chapter 8:
Reliability Analysis of the SIS
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
46/100
Q y y
www.eit.edu.au Slide 46
IEC 61511 requires reliability analysis be done for each SIF to
show that SIL target and RRF can be achieved. Why?
Because it tells everyone what RRF can be expected from each
individual safety function. It confirms the basis of the design and the chosen proof test
interval
Compares the calculated RRF for your design with the target toshow you can achieve the target.
To predict the accident rate: H events/yr = Demand Rate (D) x
PFDavg or H = D/ RRF
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
47/100
y y
www.eit.edu.au Slide 47
Terminology
RRF Risk Reduction Factor ( e.g. 200)
SIL Safety Integrity Level ( depends on RRF)
(SIL Tables)D Demand rate on Safety Function. ( How often the SIF is
demanded to respond to a hazard condition)
HHazardous event rate ( also called accident rate )
( e.g. 0.1/yr = 1 in 10 years)
PFDavg Average probability of failure on demand of the SIF
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
48/100
www.eit.edu.au Slide 48
Terminology
MTTFd Mean time to fail dangerously ( = 1/d)
MTTFs Mean time to fail safe (or spurious) ( = 1/s)
MTTRd Mean time to detect and repair a dangerous fault
Ti Time interval between proof tests
dd Failure rate for dangerous detectable faults
du Failure rate for dangerous undetectable faults (requiresproof testing)
sd Safe revealed failure rate ( causes spurious trip or loss ofaffected safety channel)
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
49/100
www.eit.edu.au Slide 49
Risk Reduction Factor and PFDavg
(PFDavg = average probability of failure on demand,)
PFDavg is a function of:
1. Failure rate per hour for undetected faults : du
2. Test interval: Ti
3. Redundancy (1oo1, 1oo2, 2oo3, etc)
Compare PFDavg with the target PFDavg for the SIL range we need.
RRF =1
PFDavg
-
8/10/2019 Sis Slides v1
50/100
EIT EQO26: Unit 8 Reliability Analysis
F il i f U t t d SIF
-
8/10/2019 Sis Slides v1
51/100
www.eit.edu.au Slide 51
Mission time
State of Process
Operating
safely
Operating but
not protected
Hazardous condition
occurs (Demand)
Reportable
accidentoccurs
1 yr 2 yr
Unrevealed Dangerous fault
occurs
Failure scenario for an Untested SIF
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
52/100
www.eit.edu.au Slide 52
Mission time
StateofProcess
Operating
safely
Operating but not
protected
Hazardous condition
Occurs (Demand)
Accident
prevented
0.5 yr 1 yr
Proof test reveals
fault
Fault
repaired
Low Demand Mode: Proof Tested SIF repaired before demand
Unrevealed Dangerous
fault occurs
Proof test
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
53/100
www.eit.edu.au Slide 53
Mission time
Stateo
fProcess
Operating
safely
Operating but not
protected
0.5 yr 1 yr
Demand occursbefore next proof
test
Failure (to respond)
on Demand
Low Demand Mode: Proof tested SIF but failure on demand
Unrevealed Dangerous
fault occurs
Reportable
accident
occurs
Proof test
EIT EQO26: Unit 8 Reliability Analysis
Di ti + P f T t d SIF
-
8/10/2019 Sis Slides v1
54/100
www.eit.edu.au Slide 54
Mission time
State of Process
Detectable Dangerous
fault occurs
Operating safely
1 yr 2 yr
Diagnostic test
reveals fault
Proof test forundetected
faults
Diagnostic + Proof Tested SIF
Accident
prevented
Diagnostic test
typically100
times/day
PFDavg = MTTD&R x Fail danger rate
Fault
detected &
repaired
EIT EQO26: Unit 8 Reliability Analysis
0 8 6 8
-
8/10/2019 Sis Slides v1
55/100
www.eit.edu.au Slide 55
0# 8 6 8
Low demand mode applies when the demand on the SIS is equal toor less than once per year. ( IEC 61511) . Alternatively no more thantwo demands per proof test interval.
Low demand calculations use PFDavg. Hazard event rate H = D x PFDavg
High demand mode applies when the demand on the SIS is morethan once per year. ( IEC 61511) . Alternatively more than twodemands per proof test interval.
High demand mode calculations use PFH probability of dangerousfailure per hour.
Hazard event rate H = PFH
96 :# ;
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
56/100
www.eit.edu.au Slide 56
Low Demand Mode Application
Pressure relief
trip (SIS)
Pressure surge
once per year(D)
Accident occurs if
dangerous fault
undetected before the
surge occurs
Accident rate H = D x PFDavg
Provided Test interval is shorter than 1 year or
diagnostics detect faults quickly
Example: If PFDavg = 0.05 and D= 1 : H = 0.05/yr
EIT EQO26: Unit 8 Reliability Analysis
Hi h d d M d A li i
-
8/10/2019 Sis Slides v1
57/100
www.eit.edu.au Slide 57
High demand Mode Application
Electronic
Braking Controls
(SIS)
Brake applied
100 times per
day
Accident occurs as
soon as brake circuit
fails
Accident rate = Probability of failure/hr of the EBC
= Failure rate per hour of the SIS
Example: If PFH = 0.0001/hr H = 0.0001/hr of service
If machine used for 5000 hrs /yr accident rate = 0.5/yr.
EIT EQO26: Unit 8 Reliability Analysis
D i I i f T PFD i L D d M d
-
8/10/2019 Sis Slides v1
58/100
www.eit.edu.au Slide 58
Design Iteration for Target PFD in Low Demand Mode
Set Target PFD
Evaluate Solution PFD
Revise Design
No
Yes
Proceed to Detail Design
Acceptable
SRS defines the Risk Reduction Factor
PFD = 1/RRF
Calculated PFD < Target PFD?
EIT EQO26: Unit 8 Reliability Analysis
El t d t i th SIS d l
-
8/10/2019 Sis Slides v1
59/100
www.eit.edu.au Slide 59
Elements and terms in the SIS model
(SIS)Hazard
Demand Rate D
Protective System
H HazardEvent Rate
PFD avg. = H/D = 1/(Risk Reduction Factor)
SIL3
SIL2
SIL1
Sensor Logic ActuatorD H
PFD1 PFD2 PFD3
Overall PFD = PFD1 + PFD2 + PFD3
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
60/100
www.eit.edu.au Slide 60
Single Channel Basic calculation of PFD
If the fail to danger rate is d and proof test interval is Ti
PFDavg = du x Ti/2 (failure rate/yr x mean time to detect )
Example Fail to danger rate = 0.05 per year, Ti = 1 year
PFDavg = 0.05 x = 0.025. ( SIL 1)
How is this formula obtained ?
du
EIT EQO26: Unit 8 Reliability Analysis
6
-
8/10/2019 Sis Slides v1
61/100
www.eit.edu.au Slide 61
6
-
8/10/2019 Sis Slides v1
62/100
www.eit.edu.auSlide 62
8 ! =. &
,
Time t
p(t)
Probability of
being failed when
demand occurs.
1
0
=
Ti 2Ti
Proof test action
Average
value
EIT EQO26: Unit 8 Reliability Analysis
-
8/10/2019 Sis Slides v1
63/100
www.eit.edu.auSlide 63
$ 8
Overt Failures
Spurious Trip Rate
S = 1/MTBFsp
Loss of Production
Detectable
by Self
Diagnostics
Undetectable
except by manual
proof testing
Trips plant unless
2oo3 or 2oo2 voting
Covert Failures
Dangerous Failure Rate
D = 1/MTTFD
D
DUDD
DU = (1 C) DDD = C D
S + DD
C= Coverage
EIT EQO26: Unit 8 Reliability Analysis
Example: Find the Safe and Dangerous Failure Modes
SIS Hi h L l T i
-
8/10/2019 Sis Slides v1
64/100
www.eit.edu.auSlide 64
LTLT
11
PSVPSVPSVPSV
LCLC
11
I/PI/PI/PI/P
FCFC
FluidFluid
FeedFeedFCFC
Logic SolverLogic Solver
LTLT
22
ASAS
SIS High Level TripSIS High Level Trip
Fail Modes/yr Device sp du dd
Bottom Blocked : 0.1 . Top leaks 0.2 LE connection
Runs low: 0.05. Runs high : 0.02 LT electronics
Breaks: 0.01 Shorts across LT: 0.1 Cable
Lost power: 0.02 Power
Totals for sensor sub system:
Assume out of range detection provided (forcing a trip)
EIT EQO26: Unit 8 Reliability Analysis
1oo1 SIS Formulae
-
8/10/2019 Sis Slides v1
65/100
www.eit.edu.auSlide 65
Single Channel SIS Fail Rates
Overt Failures
Spurious Trip Rate
S = 1/MTBFsp
Loss of Production
Detectable by
Self
Diagnostics
Detectable by
manual proof
testing
Trips plant unless
2oo3 or 2oo2 voting
Covert Failures
Dangerous Failure Rate
D = 1/MTTFD
D
DU = (1 C) DS + DD
C= Coverage
DD = C D
PFD1 = DD x (MTTR) PFD2 = DU x (Ti/2)SP Trip Rate = s + DD
EIT EQO26: Unit 8 Reliability Analysis
1oo2 SIS Formulae
-
8/10/2019 Sis Slides v1
66/100
www.eit.edu.auSlide 66
Single Channel SIS Fail Rates
Overt Failures
Spurious Trip Rate
S = 1/MTBFsp
Loss of Production
Detectable by
Self
Diagnostics
Detectable by
manual proof
testing
Trips plant unless
2oo3 or 2oo2 voting
Covert Failures
Dangerous Failure Rate
D = 1/MTTFD
D
DU = (1 C) D
C= Coverage
DD = C D
SP Trip Rate = 2 ( s + DD) PFD2 =((D U .Ti)2)/3PFD1 =2(DD)
2( MTTR)2
EIT EQO26: Unit 8 Reliability Analysis
Formula sets
-
8/10/2019 Sis Slides v1
67/100
www.eit.edu.auSlide 67
Single Channel SIS Fail Rates
Overt Failures
Spurious Trip Rate
S = 1/MTBFsp
Loss of Production
Detectable by
Self
Diagnostics
Detectable by
manual proof
testing
Trips plant unless
2oo3 or 2oo2 voting
Covert Failures
Dangerous Failure Rate
D = 1/MTTFDD
DU = (1 C) DS + DD
C= Coverage
DD = C D
Formula set 2
in Fig 8.6
Formula set 3
in Fig 8.6
Formula set 1
in Fig 8.6
EIT EQO26: Unit 8 Reliability Analysis
Multi-channel Formula Sets for PFD and s (excludingd f il )
Figure 8.6
-
8/10/2019 Sis Slides v1
68/100
www.eit.edu.auSlide 68
Overt Failures
Spurious Trip Rate
s = 1/MTBFsp
By SelfDiagnostics
By ManualProof testing
s1oo1
2s1oo2
2(s)2(MTTR)2oo2
D U (Ti/2)D D (MTTR)
((D U .Ti)2)/32(DD)
2( MTTR)2
D U .Ti2 D D (MTTR)
6(D D)2 (MTTR)22oo3 6(s)2(MTTR)
Detectable
Spurious trip rate PFD due to diagnostics
(if detected but not tripped)
common mode failures )
Covert Failures
Dangerous Failure Rate
d = 1/MTTF
PFD due to proof test
Detectable
Formula set 1 Formula set 2 Formula set 3
D D = DC. D D U = (1-DC) DVoting
((D U .Ti)2)
EIT EQO26: Unit 8 Reliability Analysis
Sources of Reliability Data
-
8/10/2019 Sis Slides v1
69/100
www.eit.edu.auSlide 69
Sintef: http://www.sintefbok.no/Product.aspx?sectionId=65&productId=559&categoryId=10
http://www.sintef.no/Projectweb/PDS-Main-Page/PDS-Handbooks/
Also see:
1. exida.com Reliability Handbook
2. Manufacturers Safety manuals for
specific SIL certified instruments
3. Faradip 3 Database4. exida.com: Safety Automation
Equipment List ..Functional Safety
Assessment Reports
http://www.exida.com/index.php/resour
ces/sael/
EIT EQO26: Unit 8 Reliability Analysis
Dual Channel Basic calculation of PFD
-
8/10/2019 Sis Slides v1
70/100
www.eit.edu.auSlide 70
If the fail to danger rate is du and proof test interval is Ti.
PFDavg = (du xTi)2/3
Example: If fail to danger rate = 0.05 per year, Ti = 1 year
PFDavg = (0.05 x 1)2/ 3 = 0.00083 ( SIL 3)
But this ignores common cause and is unrealistic
du
du
Note: dd omitted for clarity
EIT EQO26: Unit 8 Reliability Analysis
Beta Factor: Common Cause Failures in redundant SISchannels
-
8/10/2019 Sis Slides v1
71/100
www.eit.edu.auSlide 71
channels
(1-) d
(1-) d
(1-) d
d
Unit Failures Common CauseFailures
Example:2oo3 sensor withcommon causefailures
EIT EQO26: Unit 8 Reliability Analysis
Formulae Sets with Common Cause Factor included
-
8/10/2019 Sis Slides v1
72/100
www.eit.edu.auSlide 72
EIT EQO26: Unit 8 Reliability Analysis
Dual Channel Basic calculation of PFD inc Common Cause 5%
N t dd itt d f l it
-
8/10/2019 Sis Slides v1
73/100
www.eit.edu.auSlide 73
If the fail to danger rate is d and proof test interval is Ti.
PFDavg = ((1-) du xTi)2/3 + du xTi/2
Example Fail to danger rate = 0.05 per year, Ti = 1 year Beta = 5%
PFDavg = (0.95 x 0.05 x 1)2/ 3 + (0.05 x 0.05 x ) = 0.002 ( SIL 2)
du(1-) du
(1-) du
Note: dd omitted for clarity
EIT EQO26: Unit 8 Reliability Analysis
2oo3 Channel Basic calculation of PFD inc Common Cause 5%
-
8/10/2019 Sis Slides v1
74/100
www.eit.edu.auSlide 74
If the fail to danger rate is d and proof test interval is Ti.
PFDavg = ((1-) du xTi)2 + du xTi/2
Example Fail to danger rate = 0.05 per year, Ti = 1 year Beta = 5%
PFDavg = (0.95 x 0.05 x 1)2 + (0.05 x 0.05 x ) = 0.0035 ( SIL 2)
d(1-) d
(1-) d
(1-) d
EIT EQO26: Unit 8 Reliability Analysis
Formulae Sets with Common Cause Factor included
-
8/10/2019 Sis Slides v1
75/100
www.eit.edu.auSlide 75
EIT EQO26: Unit 8 Reliability Analysis
! $
-
8/10/2019 Sis Slides v1
76/100
www.eit.edu.auSlide 76
7: 4&
Formula for calculating PFDavg for 1oo1
PFDavg = (DU xTi/2) + (DD x MTTR)
Failures per year
Parameter Value Notes
DU 0.0500 Dangerous undetected failure rate for one channel
DD 0.1000 Dangerous detected failure rate for one channel
Ti in yrs 1.0000 Proof test interval
MTTR in yrs 0.0027 Mean time to detect and repair a detectable fault
(DU xTi/2) 2.50E-02 Undetected portion
(DD x MTTR) 2.74E-04 Detected portion
PFD for 1oo1 subsystem 2.53E-02 SIL Table: SIL 1
EIT EQO26: Unit 8 Reliability Analysis
! $
-
8/10/2019 Sis Slides v1
77/100
www.eit.edu.auSlide 77
7: 4&
Formula for calculating PFDavg for 1oo1
PFDavg = (DU xTi/2) + (DD x MTTR)
Failures per hour
Parameter Value Notes
DU 5.71E-06 Dangerous undetected failure rate for one channel
DD 1.14 E-05 Dangerous detected failure rate for one channel
Ti in hrs 8760 Proof test interval
MTTR in hrs 24 Mean time to detect and repair a detectable fault
(DU xTi/2) 2.50E-02 Undetected portion
(DD x MTTR) 2.74E-04 Detected portion
PFD for 1oo1 subsystem 2.53E-02 SIL Table: SIL 1
EIT EQO26: Unit 8 Reliability Analysis
$ ! $
(1(1 )) dd
-
8/10/2019 Sis Slides v1
78/100
www.eit.edu.auSlide 78
7: 4& -Formula for calculating PFDavg for 1oo2
PFDavg = (1/3)*((1-)DU xTi)2 + 2((1-)DD x MTTR)2 +(DU xTi/2)+(DD)x MTTR
Failures per year
Parameter Value Notes
DU 5.71E-06 Dangerous undetected failure rate for one channel
DD 1.14 E-05 Dangerous detected failure rate for one channel
0.1000 Common cause factor for dangerous and safe failuresTi in hrs 8760 Proof test interval
MTTR in hrs 24 Mean time to detect and repair a detectable fault
(1/3)*((1-)DU xTi)2 6.75E-04 Undetected Voting portion
2((1-)DD2 x MTTR2) 1.18E-07 Detected voting portion
(DU xTi/2) 2.50E-03 Undetected Common portion
(DD)x MTTR 2.70E-05 Detected common portion
PFD for 1oo2 subsystem 3.20E-03
dd
(1(1--)) dd
(1(1--)) dd
Safecalc: D = 1.71% safe =0 C=66%
EIT EQO26: Unit 8 Reliability Analysis
$ ! $
dd(1(1--)) dd
-
8/10/2019 Sis Slides v1
79/100
www.eit.edu.auSlide 79
7: 4& -1
Formula for calculating PFDavg for 2oo3
PFDavg = ((1-)DU xTi)2 + 6((1-)DD x MTTR)2 +(DU xTi/2)+(DD)x MTTR
Failures per yearParameter Value Notes
DU 5.71E-06 Dangerous undetected failure rate for one channel
DD 1.14 E-05 Dangerous detected failure rate for one channel
0.1000 Common cause factor for dangerous and safe failures
Ti in hrs 8760 Proof test interval
MTTR in hrs 24 Mean time to detect and repair a detectable fault
(1-)DU xTi)2 2.03E-03 Undetected Voting portion
6((1-)DD x MTTR)2 3.54E-07 Detected voting portion
(DU xTi/2) 2.50E-03 Undetected Common portion
(DD)x MTTR 2.70E-05 Detected common portion
PFD for 2oo3 subsystem 4.55E-03
dd
(( ))
(1(1--)) dd
(1(1--)) dd
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis Model Example
-
8/10/2019 Sis Slides v1
80/100
www.eit.edu.auSlide 80
Proof
Testing
Auto
Diagnostics
Proof
Testing
Sensor Logic ActuatorD H
d1=0.2 d2=0.02 d3=0.1Failure Rates:
5yrs 50yrs 10yrs
0.01 0.005 0.01
Overall PFD avg. = 0.025
Qualifies for SIL 1 (E-1 to E-2)
= 2.5 E-2
Apply
Testing or
Diagnostics
or MTTF
PFD averages:
Apply
calculation
+ +
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Step 1
-
8/10/2019 Sis Slides v1
81/100
www.eit.edu.auSlide 81
(SIS)Hazard
Demand Rate D
Protective System
H HazardEvent Rate
Sensor Logic ActuatorD H
SIL 2 SIL 1 SIL 1
SIL 1
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Step 2, identify channels in each stage
-
8/10/2019 Sis Slides v1
82/100
www.eit.edu.auSlide 82
Sensor Logic ActuatorD H
Sensor
Logic
ActuatorD H
Sensor ActuatorD H
Example:Dual channel sensors and actuators, single channel logic
1oo2D
1oo1D
1oo2
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Step 3, expand details for each single channel
-
8/10/2019 Sis Slides v1
83/100
www.eit.edu.au Slide 83
Sensor
Logic
Sensor
1oo2D
1oo1D
Process
ConnectionTransmitter
Cable and
Power
Expand detail of sensor sub system and apply fail rates for each item
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis:Step 4: Decide du, dd and s for the elements
-
8/10/2019 Sis Slides v1
84/100
www.eit.edu.au Slide 84
Step 5: Enter the values to table and totalize
Process
ConnectionTransmitter
Cable and
Power
DU1 DU2 DU3DD1 DD2 DD3
SD1 SD2 SD3
SubsystemElement Device SD/hr SU/hr DD/hr DU/hr
1 Process connection 1.14E-05 0.00E+00 5.71E-06 3.42E-06
2 Transmitter 1.14E-05 0.00E+00 5.71E-06 5.71E-07
3 Cable and Power 1.14E-05 0.00E+00 5.71E-06 3.42E-06
4
5
Subsystem totals 3.42E-05 0.00E+00 1.71E-05 7.42E-06
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Step 6, find the PFDavg for the 1oo2 subsystem
-
8/10/2019 Sis Slides v1
85/100
www.eit.edu.au Slide 85
= common cause failure fraction
1oo2 Failures common toCh1 and Ch2 sensors
Logic
1oo1 d
Redundant section:
PFDavg =
2((1-).dd)2 . (MTTR)2
+ ((1-) .du .Ti)2)/3
Common cause section
PFDavg =
.dd (MTTR)+ .du . Ti/2)
+
(1-) d
(1-) d
=PFDavg
Break out the common cause failure fraction for the redundant channels and calculatePFD for each portion and add them together
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Step 7, repeat steps 3 to 6 for each stage
-
8/10/2019 Sis Slides v1
86/100
www.eit.edu.au Slide 86
Sensor
Logic
Actuator
Sensor Actuator
Example: Dual channel sensors and actuators, single channel logic
1oo2
1oo1
1oo2
PFDavgfor sensors
+ PFDavg forlogic solver
+ PFDavgfor actuators
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Example
E l D l h l d i l h l l i 1
-
8/10/2019 Sis Slides v1
87/100
www.eit.edu.au Slide 87
Example: Dual channel sensors and actuators, single channel logic. 1yr test
.045
0.05
.09
.045 .09
1oo2
1oo1D
1oo2
Dual Sensors PFD
= .00075 +.00125
= .002
Logic solver PFD
= .00013 +.00125
= .00138
Dual Actuators PFD
= .005 + .0027
= .0077
.0025 .01
SIS PFD = .002 + .0014 +.0077
= . 0111 or 1.11 E-2 = SIL 1
= 5% = 10%C = 95%
DU = 0.05 DU = 0.0025
DD = 0.0475
DU = 0.1
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Example using the EIT Calculator
Data Input Table for Sensor Subsystem Fil EIT GP SIL C l l t l
-
8/10/2019 Sis Slides v1
88/100
www.eit.edu.au Slide 88
Data Input Table for Sensor SubsystemProof Test Interval in Hrs (Ti) 8760
Common cause factor (B)% 5%
Mean Time To Test & Repair (Hrs) (MTTR) 24
Subsystem
ElementDevice SD/hr SU/hr DD/hr DU/hr
1 Sensor all components 1.14E-05 0.00E+00 0.00E+00 5.71E-06
2
3
4
5
Subsystem totals 1.14E-05 0.00E+00 0.00E+00 5.71E-06
Calculation results for Sensing
Safe Failure Fraction 66.7%
Diagnostic coverage 0.0%
PFDavg for 1001 2.50E-02
PFDavg for 1002 2.00E-03
PFDavg for 20033.51E-03
File name: EIT GP SIL Calculator .xls
EIT EQO26: Unit 8 Reliability Analysis
IEC Table of PFDs relevant to Figure 8.16
-
8/10/2019 Sis Slides v1
89/100
www.eit.edu.au Slide 89
-
8/10/2019 Sis Slides v1
90/100
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Example Calculation for Spurious Trip
E l D l h l d t t i l h l l i
-
8/10/2019 Sis Slides v1
91/100
www.eit.edu.au Slide 91
Example:Dual channel sensors and actuators, single channel logic
Sensor MTTF = 5 years, 75% safe failure fraction. C=0%, = 10%, Ti = 0.5 yrs, MTTR = 8hrsLogic MTTF = 10 years, 50% safe failure fraction. C= 95%, = 10%, Ti = 1 yrauto diagnostics test interval = 2 secs, MTTR = 24hrs
Actuator MTTF = 2 years, 80 % safe failure fraction. C= 0%, = 10%, Ti = 0.25 yrs, MTTR =24hrs
Sensor: single channel s = 1/5 x .75 = .15/yrLogic: single channel s = 1/10 x .5 = .05 dd = (C xd ) =95% x 0.05 = .0475/yrActuator: single channel s = 1/2 x .8 = .4/yr
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Example Calculation for Spurious TripExample :Dual channel sensors and actuators, single channel logic
Spurious Trip for 1oo1
-
8/10/2019 Sis Slides v1
92/100
www.eit.edu.au Slide 92
Spurious Trip for 1oo1
ST = S + DD Logic solver 1oo1
Parameter Sensor Logic Actuator Notes
S 0.05 Fail safe rate
DD 0.0475 DD rate added due to 95 coveragTotal for 1oo1 subsystem 0.0975 Spurious trip rate per yr
Spurious Trip for 1oo2
ST = 2x(1-B) (S + DD) +B(S + DD) Actuators: 1oo2
Parameter Sensor Logic Actuator Notes
S 0.15 0 0.4 Fail safe rate
DD 0 0 0 DD rate added due to S
Beta 0.1 0 0.1
2x(1-B) (S + DD) 0.27 0 0.72
B(S + DD) 0.015 0 0.04 Common portion
Total for 1oo2 subsystem 0.285 0 0.76 Spurious trip rate per yr
Overall Spurious Trip Rate
1.1425 per yr
EIT EQO26: Unit 8 Reliability Analysis
SIS Analysis: Example, Spurious Trip Rate
E l D l h l d i l h l l i
-
8/10/2019 Sis Slides v1
93/100
www.eit.edu.au Slide 93
Example: Dual channel sensors and actuators, single channel logic
.05
.36
.0135.36
1oo2
1oo1
1oo2
Dual Sensors Spurious
= .28 trips per yr
Logic solver
.097 trips per
yr
Dual Actuators PFD
= (2x .36) + (1x.04)
= .76 trips per yr
.04
Spurious trip rate = ..28 + .097 +.76
= 1.14 trips per year
..0135
.015
EIT EQO26: Unit 8 Reliability Analysis
Reducing Spurious Trip RateDesign Version B
-
8/10/2019 Sis Slides v1
94/100
www.eit.edu.au Slide 94
.135
.135
.015
.135
2oo3
2oo3 Sensors Spurious
= 6x s2 (MTTR)+ s= (6 x .1352x 8/8760) + .015
= .0001 + .015. 015 trips per yr
.15
1oo2
Dual Sensors Spurious
= 2 x .15= .30 trips per yr
.15
From 0.3 per year to 0.015/yr
If 1 trip costs AUD 50 000 the annual saving is
What? .
Design Version A
EIT EQO26: Unit 8 Reliability Analysis
Outcomes of a Reliability Study
-
8/10/2019 Sis Slides v1
95/100
www.eit.edu.au Slide 95
Show whether or not the SIS will satisfy the SIL target
Overall SIS Probability of Failure on Demand (PFDavg)
PFDavgs for each section of the SIS
Show benefits of redundancy or voting schemes
Decide the proof testing intervals
Predict the accident rate
EIT EQO26: Unit 8 Reliability Analysis
Conclusions on Analysis Models
-
8/10/2019 Sis Slides v1
96/100
www.eit.edu.au Slide 96
Models help to visualise SIS performance
Software speeds up analysis
IEC 61508 part 6 - methods and tables
Fault tree analysis for detailed systems
EIT EQO26: Unit 8 Reliability Analysis
&& 0# 8 6 8
9 :# ;
-
8/10/2019 Sis Slides v1
97/100
www.eit.edu.au Slide 97
9 :# ; Low demand mode applies when the demand on the SIS is equal to
or less than once per year. ( IEC 61511) . Alternatively no more thantwo demands per proof test interval.
Low demand calculations use PFDavg. Hazard event rate H = D x PFDavg
High demand mode applies when the demand on the SIS is more
than once per year. ( IEC 61511) . Alternatively more than twodemands per proof test interval.
High demand mode calculations use PFH ( same as failure to dangerrate)
Hazard event rate H = PFH
EIT EQO26: Unit 8 Reliability Analysis
PSHPump
-
8/10/2019 Sis Slides v1
98/100
www.eit.edu.au Slide 98
6 0#
PFDavg = 0.05 x = 0.025. and
PFH = 0.05 /8760 = 5.7E-06/hr
Suppose the demand rate D is once per year and the overpressure event rate= H/yr
In low demand mode calculation H = D x PFDavg so H = 1 x 0.025 = 0.025/yr
In high demand mode calculation H = PFH so H = 5.7E-06/hr = 0.05/yr
SISPower
pd = 0.05 and Ti = 1/yr:
Hp safety Trip
EIT EQO26: Unit 8 Reliability Analysis
6 0#PSHPump
-
8/10/2019 Sis Slides v1
99/100
www.eit.edu.au Slide 99
6 0#
PFDavg = 0.05 x = 0.025. and
PFH = 0.05 /8760 = 5.7E-06/hr
Suppose the demand rate D is once per day ( 365/yr)
And the overpressure event rate = H/yr
In low demand mode: H = D x PFDavg so H = 365 x 0.025 = 9.1/yr
In high demand mode :H = PFH so H = 5.7E-06/hr = 0.05/yr
SIS
Power
pd = 0.05 and Ti = 1/yr:
EIT EQO26: Unit 8 Reliability Analysis
#
-
8/10/2019 Sis Slides v1
100/100
www.eit.edu.au Slide 100
SIS has failures at
PFD = 0.01
PFH = 0.02/yr (2.28 E-06/hr)
Demand on SIS H = hazardous event
D = 0.1/yr ..H = /yr ?
D = 1.0/yr ..H = /yr ?
D = 10.0/yr ..H = /yr ?
D = 100 /yr ..H = /yr ?