SIPROTEC 7SA6 Distance Protection – secure investmentfor the future
2
The SIPROTEC® 7SA6 dis-
tance protection relay is a
universal device for protec-
tion, control and automa-
tion on the basis of the
SIPROTEC 4 system. Its
high level of flexibility
means it can be implement-
ed at all voltage levels. With
this device, you are ideally
equipped for the future: it
offers security of invest-
ment and also saves on op-
erating costs.
SIPROTEC 7SA6 Distance Protection – protecting, controlling and automatingat all voltage levels between 5 kV and 500 kV
This is facilitated by thefollowing features:• Tested protection modules
assure maximum safety• Uniform operator software
(DIGSI® 4) for all SIPROTECdevices saves on trainingcosts
• Clearly laid out measured-value display saves onexternal measuringinstruments
• DIGSI 4 start-up aids speedup commissioning
• Integrated control unitsaves space and money
• Flexible communicationmodules permit the use oftoday's and future protocolstandards and give yousecurity of investment
• Service interface fortelecommunication reducesmaintenance and operatingcosts
Optimum protection atall voltage levels between5 kV and 500 kV
As a universal protection de-vice, the SIPROTEC 7SA6 dis-tance protection relay can beimplemented at all voltagelevels. Proven and 100% type-tested function packages areavailable for various appli-cation areas in resonant-earthed, isolated-neutral orearthed-neutral systems.
The distance protection func-tion can be implemented withdifferent pickup methods thatare specifically tailored to thevarious operating conditions.You can choose between:• Overcurrent pickup• Voltage and current-
dependent pickup• Voltage, current and phase-
angle-dependent pickup• Impedance pickup
Each pickup method assuresa particularly high degree ofprotection selectivity, sinceimpedance measurement ispossible in up to 6 measuringloops simultaneously. Further-more, SIPROTEC 7SA6 offersmany more functions for com-prehensive feeder protectionand uncomplicated operation.
Automating a sub-station – simple, like inindustry
Even the basic variant of theSIPROTEC 7SA6 distance pro-tection relay includes extre-mely flexible programmablelogics. This permits:• Interlocking check for the
control unit / breaker• Additional protective circuits
to protection functions• Processing of measured
values with defined limitingvalues
With the aid of the CFC editor,familiar from the world ofSIMATIC industrial automati-on, the flexible opportunitiesoffered by the logic can beexploited to the full. With full-graphics interface support andwithout any programmingknowledge, the logic swit-ching elements can be selec-ted from a program library andconnected up on the PC. Aningenious consistency checkassures an error-free configu-ration result and reliable ope-ration.
3
A family of Devices – for any application– for any installation location
More than 30,000 digital
distance protection
devices are already in use
SIPROTEC 7SA6, the digitaldistance protection family wi-th control unit, is the logicalenhancement of the 7SA5 di-stance protection devices,thousands of which are in use.
More than 20 years of experi-ence in the development andproduction of digital protectionand control equipment havebeen incorporated into theconcept of the new family ofdevices. Powerful 32-bitmicroprocessor systemsenable us today to integratenumber-crunchingprotection algo-rithms and pre-cise controltechnology inone device.
Allfunctions areavailable in allenclosurevariants
Allfunctions areavailable in allenclosurevariants
4
Switchgear control fromremote of locally
The SIPROTEC 7SA6 distanceprotection relay enables thebreaker in the feeder to becontrolled directly, taking therespective interlocking condi-tions into account.
Particularly clear control ismade possible by those de-vices with a graphic displayfor displaying the feeder mim-ic diagram, colored controlkeys and 2 key switches. Thefeeder mimic diagram can beeasily designed and specificto the application with the aidof the PC program DIGSI 4.
Those devices with a 4-linedisplay also offer menu-drivencontrol. All device variants canbe integrated into the remote-control concepts of SCADAand protection systems. WithSIPROTEC 7SA6, control com-mands are executed reliablyand system faults cleared upquickly and selectively at alltimes.
DIGSI 4 – the uniform PCprogram for user-friendlyoperation of allSIPROTEC 4 devices
DIGSI stands for convenientand user-friendly parameteri-zation and operation of digitalprotection equipment.
• Each window contains theinformation that is reallynecessary – irrespective ofthe device you are in theprocess of configuring.
• Context-sensitive menusfor every situation offer youtailored functionality –there's no longer any needfor complex searchesthrough menu hierarchies.
• A matrix makes I/Oconfiguration transparent.You can set up connectionsright through to the controland protection system withjust a single click of themouse.Easy-to-use start-up aidsoffer safety and savemoney.
DIGSI 4 – easy to use
5
Retrofittable communicationmodules are available for allSIPROTEC 7SA6 distance pro-tection devices. This meansyou can and will be able tosatisfy today's and futurerequirements of differentcommunications protocols. Atthe same time, absolutely allSIPROTEC devices can beoperated via modem and/orstar coupler and communicatewith higher-level control andprotection systems such asSICAM.
Open communicationstandards
Communication by IEC proto-col and PROFIBUS: the inter-national, standardized inter-face defined in IEC 60870-5-103 has proven itself as anopen communications stand-ard for connecting protectionequipment from different ven-dors. Alternatively, other formsof fieldbus interfacing, viaPROFIBUS or other protocols,are also available withSIPROTEC 4 – widely imple-mented standards, particularlyin the fields of control andprotection systems and auto-mation engineering.
Measurement and testingfunctions
Integrated in the SIPROTEC7SA6 distance protection relayare a large number of meas-urement and testing functionsfor commissioning and opera-tional measurements.
In addition to the usual meas-ured values taken for operatingcurrents, voltages and power,the equipment now also offersmin./max. values, demand val-ues and energy metering.
Siemens AGPower Transmission and Distribution GroupProtection and Substation ControlSystems DivisionP.O. Box 4806D-90026 Nuremberg
www.ev.siemens.dePower
to the
Siemens Aktiengesellschaft Subject to change without prior notice Order No. E50001-U321-A153-X-7600Printed in GermanyDispo-Stelle 0620061D6254 Ra/Sö 101671 03005.
Performance Characteristics of the 7SA6 distance protection family
Measured values
Measured values • Extensive choice of operat. measuredvalues, measuring accuracy <1%
• Energy metering• Energy metering with meter-pulse
processing• Min./max. values• Demand values
Function ANSI no.Protection functions
Thermal overload 49 • Prewarning stage and tripping stageprotection • Measured valuesCircuit-breaker failure protection 50BF • 2-stages with short reset times
Control
Control function • Number of controllable switchingdevices dependent only onthe number of inputs and outputsavailable
• Extensive choice of all commonsingle and double commands/alarms
• Interlocking by means of freelyprogrammable logic
Feeder control display • Freely programmableProgrammable keys • 4 function keys
• Control keysProgrammable logic
• All common logic functions withCFC software via PC
• Processing of interlock andprotection signals
Additional functions
Automatic reclosing 79 • Up to 8 reclosing cyclesWith/without action timecontrol
• ADT (= adaptive dead time control)
• RDT (= reduced dead timecontrol)
• DLC (= dead line check)Synchrocheck 25 • Measurement of ∆U, ∆f, ∆ϕTripping circuit 74TC • Optional with 1 or 2 inputsmonitoring • 1 or 3 tripping circuitsLock-out 86 • Reclosing after final tripping
only after special resetcommand
Fault recording • Analog channels, customer-specific choice of digital channels
Communication
Communication • 1 IRIG-B time-sync. input• 1 RS232/RS485 serial interface,
at rear, electrically isolated• 2 serial interfaces, at rear,
electricalor optical, variablewith plug-in communicationmodules
• 1 RS232 serial interface, at front
Protection functions
Trip mode • 3-pole only• 1-/3-pole
Distance protection 21, 21N • 6-loop measurementDistance-protection • Overcurrent I>pickup method • Undervoltage/overcurrent U/I
• Undervoltage/overcurrent/angle U/I/ϕ
• Impedance ZTeleprotection schemes 85–21 • Permissive trip PUTT, POTTfor distance protection • Blocking, Unblocking
• Reverse interlocking• Pilot wire comparison
via DC loop• Multi-end applications
Remote intertripping • Direct breaker intertrippingvia binary input DUTT
Weak infeed 27WI • Echoprotection • Tripping on carrier reception
and U<Fault locator FL • Optionally with load-current
compensation• Fault location display on device
via DIGSI, via system interface,via 20 mA analog output, BCD
Parallel-line – • For distance measurementcompensation for and fault locatoroverhead linesPower-swing 68 • Blocking the distance protectiondetection 68T • Tripping on loss of
synchronismDirectional earth-fault 50N • Definite-time overcurrentprotection for earthed- 51N • Inverse time overcurrent, varioussystem starpoints 67N characteristics
• U0 inverse• Direction determination with U0, IY, U2-I2• 4-stages
Teleprotection schemes 85–67N • Directional comparisonfor directional earth- • Blocking, Unblockingfault protection • Multi-end applicationsEarth-fault protection • Earth-fault direction withfor resonant-earthed/ wattmetric measurement principleisolated-neutral system • Measured earth-fault valuesstarpoints • Transient-earth-fault meas. principle
with supplementary device 7SN60Overcurrent-time 50, 51 • As emergency function for failureprotection 50N, 51N of measuring-circuit voltage or
running in parallel with dist. protect.• Definite-time overcurrent• Inverse time, various characteristics
Voltage protection 27, 59 • Phase/positive-sequenceovervoltage U>
• Phase/positve-sequenceundervoltage U<
• Negative-sequence overvoltage U2>• Zero-sequence overvoltage 3U0>