SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

SINAMICS G120 with CU2xy-2 (from FW V4.4)

FAQ November 2012

Page 2: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

Question

2 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

This entry is from the Siemens Industry Online Support. The general terms of use (http://www.siemens.com/terms_of_use) apply. Clicking the link below directly displays the download page of this document. http://support.automation.siemens.com/WW/view/en/75277503 Caution The functions and solutions described in this article are predominantly confined to the realization of the automation task. Please also take into account that appropriate protective measures have to be taken with regard to industrial security when connecting your equipment to other parts of the plant, the company network or the Internet. Further information can be found under the content ID 50203404. http://support.automation.siemens.com/WW/view/en/50203404

Question SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Answer The instructions and notes listed in this document provide a detailed answer to this question.

Limitation This FAQ can be used for SINAMICS G120 with CU2xy-2. Only a limited number of FFB are available.

Page 3: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

Table of contents

SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)? Version 1, Item ID: 75277503 3

Table of contents 1 Introduction .................................................................................................... 4 2 Example 1: ON/OFF 1 using two NO contacts............................................... 5

Description of the terminals and signals for 2 digital inputs: ................ 5 Parameters for example 1 .................................................................. 5

3 Example 2: ON/OFF1 using one NO contact and one NC contact ................ 6

Description of the terminals and signals for 2 digital inputs: ................ 6 Parameters for example 2 .................................................................. 6

4 Example 3: ON/OFF 1 using a pushbutton (NO contact) .............................. 7

Description of the terminals and signals for 1 digital input: .................. 7 Parameters for example 3 .................................................................. 7

5 Example 4: ON clockwise, ON counter-clockwise, OFF1 using three NO contacts .................................................................................................... 9

Description of the terminals and signals for 3 digital inputs: ................ 9 Parameters for example 4 .................................................................. 9

6 Example 5: ON clockwise, ON counter-clockwise, OFF1 using two NO contacts and one NC contact (OFF1) .................................................... 11

Description of the terminals and signals for 3 digital inputs: .............. 11 Parameters for example 5 ................................................................ 11

Page 4: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

1 Introduction

4 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

1 Introduction Normally, the SINAMICS G120 expects a steady-state "ON/OFF" command (switch). For plants and systems, which must be switched on and off, controlled by pulses (e.g. a gate/door control, hoisting gear, conveyor belt), generally a relay interconnection is required. Using the free function blocks (FFB), it is possible to interconnect the ON/OFF commands so that the inverter can be controlled using a pushbutton. The following examples shown how "ON/OFF1" commands can be implemented using one or two digital inputs as well as also "ON clockwise", "ON counter-clockwise" and "OFF1" commands using three digital inputs. In this case, NO contacts are used for the "ON" commands, and NO contacts or NC contacts are used for "OFF1" commands. Example 1: ON/OFF1 using two NO contacts, 2 digital inputs Example 2: ON/OFF1 using one NO contact and one NC contact, 2 digital inputs Example 3: ON/OFF 1 using a pushbutton (NO contact), 1 digital input Example 4: ON clockwise, ON counter-clockwise, OFF1 using three NO contacts, 3 digital inputs Example 5: ON clockwise, ON counter-clockwise, OFF1 using two NO contacts and one NC contact (OFF1), 3 digital inputs

NOTE The script files can be used for fast parameter changes. You can find information under entry ID: 75163088

Page 5: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

2 Example 1: ON/OFF 1 using two NO contacts

SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)? Version 1, Item ID: 75277503 5

2 Example 1: ON/OFF 1 using two NO contacts

Description of the terminals and signals for 2 digital inputs: Terminal 5 (DI0), NO contact – "ON" command (r722.0) Terminal 6 (DI1), NO contact – "OFF1" command (r722.1)

Parameters for example 1 Table 2-1

Function Parameter Description Value Description Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

1 Fast commissioning

Macro selection p0015 Macro drive unit 12 Macro 12 1) 2)

Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

0 Ready

"ON/OFF1" command p0840.0 ON/OFF1 r20189.0 RSR 0 output Q Negative direction p1110.0 Inhibit/enable negative

direction 1 Inhibit negative direction

Sets the signal source for inverting the setpoint

p1113.0 Setpoint inversion 0 No setpoint inversion

Signal source RSR 0 p20188.0 RSR 0 input S "set" r722.0 Terminal 5 (DI0), ON signal Signal source RSR 0 p20188.1 RSR 0 input R "reset" r722.1 Terminal 6 (DI1), OFF1 signal Runtime group of the RSR 0 p20191 RSR 0 runtime group 1 Runtime group 1

1) Factory setting for CU240B-2, CU240E-2, CU240E-2 F, CU230P-2 BT, CU230P-2 CAN and CU230P-2 HVAC 2) As setpoint source, in macro 12, analog input AI0 is used as bipolar voltage input (-10 V ... +10 V). When required, the analog input can be reparameterized using parameter p0756 – and also the setpoint source can be reparameterized using parameter p1000. When using the analog inputs as setpoint source, the associated DIP switches must also be set. For the voltage input, DIP switch AI0/1 must be set to the "U" position. For the current input, DIP switch AI0/1 or AI2 (only for CU230P-2) must be set to the "I" position.

Page 6: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

3 Example 2: ON/OFF1 using one NO contact and one NC contact

6 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

3 Example 2: ON/OFF1 using one NO contact and one NC contact

Description of the terminals and signals for 2 digital inputs: Terminal 5 (DI0), NO contact – "ON" command (r722.0) Terminal 6 (DI1), NC contact – "OFF1" command (r722.1)

Parameters for example 2 Table 3-1

Function Parameter Description Value Description Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

1 Fast commissioning

Macro selection p0015 Macro drive unit 12 Macro 12 1) 2)

Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

0 Ready

"ON/OFF1" command p0840.0 ON/OFF1 r20189.0 RSR 0 output Q Negative direction p1110.0 Inhibit/enable negative

direction 1 Inhibit negative direction

Sets the signal source for inverting the setpoint

p1113.0 Setpoint inversion 0 No setpoint inversion

Signal source NOT 0 p20078 NOT 0 input I r722.1 Terminal 6 (DI1), OFF1 signal Runtime group of NOT 0 p20080 NOT 0 runtime group 1 Runtime group 1 Signal source RSR 0 p20188.0 RSR 0 input S "set" r722.0 Terminal 5 (DI0), ON signal Signal source RSR 0 p20188.1 RSR 0 input R "reset" r20079.0 NOT 0 inverted output Runtime group of the RSR 0 p20191 RSR 0 runtime group 2 Runtime group 2

1) Factory setting for CU240B-2, CU240E-2, CU240E-2 F, CU230P-2 BT, CU230P-2 CAN and CU230P-2 HVAC 2) As setpoint source, in macro 12, analog input AI0 is used as bipolar voltage input (-10 V ... +10 V). When required, the analog input can be reparameterized using parameter p0756 – and also the setpoint source can be reparameterized using parameter p1000. When using the analog inputs as setpoint source, the associated DIP switches must also be set. For the voltage input, DIP switch AI0/1 must be set to the "U" position. For the current input, DIP switch AI0/1 or AI2 (only for CU230P-2) must be set to the "I" position.

Page 7: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

4 Example 3: ON/OFF 1 using a pushbutton (NO contact)

SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)? Version 1, Item ID: 75277503 7

4 Example 3: ON/OFF 1 using a pushbutton (NO contact)

Description of the terminals and signals for 1 digital input: Terminal 5 (DI0), NO contact – "ON/OFF1" command (r722.0)

Parameters for example 3 Table 4-1

Function Parameter Description Value Description Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

1 Fast commissioning

Macro selection p0015 Macro drive unit 12 Macro 12 1) 2)

Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

0 Ready

"ON/OFF1" command p0840.0 ON/OFF1 r20189.0 RSR 0 output Q Signal source AND 0 p20030.0 AND 0 input 0 r20140.0 MFP 0 output Q Signal source AND 0 p20030.1 AND 0 input 1 r20190.0 RSR 0 inverted output QN Signal source AND 0 p20030.2 AND 0 input 2 1 Input permanently set Signal source AND 0 p20030.3 AND 0 input 3 1 Input permanently set Runtime group of AND 0 p20032 AND 0 runtime group 6 Runtime group 6 Signal source AND 1 p20034.0 AND 1 input 0 r20140.0 MFP 0 output Q Signal source AND 1 p20034.1 AND 1 input 1 r20189.0 RSR 0 output Q Signal source AND 1 p20034.2 AND 1 input 2 1 Input permanently set Signal source AND 1 p20034.3 AND 1 input 3 1 Input permanently set Runtime group of AND 1 p20036 AND 1 runtime group 6 Runtime group 6 Signal source MFP 0 p20138 MFP 0 input pulse I r722.0 Input signal for pulse generator MFP 0

= terminal 5 (DI0), ON/OFF1 signal Pulse duration MFP 0 p20139 MFP 0 pulse duration

in ms 200 Dependent on the system, e.g.

200ms. Can be adapted. Runtime group of the MFP 0

p20141 MFP 0 runtime group 5 Runtime group 5

Signal source RSR 0 p20188.0 RSR 0 input S "set" r20031.0 AND 0 output Q Signal source RSR 0 p20188.1 RSR 0 input R "reset" r20035.0 AND 1 output Q Runtime group of the RSR 0

p20191 RSR 0 runtime group 6 Runtime group 6

1) Factory setting for CU240B-2, CU240E-2, CU240E-2 F, CU230P-2 BT, CU230P-2 CAN and CU230P-2 HVAC 2) As setpoint source, in macro 12, analog input AI0 is used as bipolar voltage input (-10 V ... +10 V). When required, the analog input can be reparameterized using parameter p0756 – and also the setpoint source can be reparameterized using parameter p1000.

Page 8: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

4 Example 3: ON/OFF 1 using a pushbutton (NO contact)

8 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

When using the analog inputs as setpoint source, the associated DIP switches must also be set. For the voltage input, DIP switch AI0/1 must be set to the "U" position. For the current input, DIP switch AI0/1 or AI2 (only for CU230P-2) must be set to the "I" position.

Page 9: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

5 Example 4: ON clockwise, ON counter-clockwise, OFF1 using three NO contacts

SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)? Version 1, Item ID: 75277503 9

5 Example 4: ON clockwise, ON counter-clockwise, OFF1 using three NO contacts

Description of the terminals and signals for 3 digital inputs: Terminal 5 (DI0), NO contact – "ON clockwise" command (r722.0) Terminal 6 (DI1), NO contact – "ON clockwise" command (r722.1) Terminal 7 (DI2), NO contact – "OFF1" command (r722.2)

Parameters for example 4 Table 5-1

Function Parameter Description Value Description Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

1 Fast commissioning

Macro selection p0015 Macro drive unit 12 Macro 12 1) 2)

Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

0 Ready

"ON/OFF1" command p0840.0 ON/OFF1 r20047.0 OR 0 output Q Negative direction p1110.0 Inhibit/enable negative

direction 0 Enable negative direction

Sets the signal source for inverting the setpoint

p1113.0 Setpoint inversion r20194.0 RSR 1 output Q

Sets the signal source for acknowledging a fault

p2103.0 Fault acknowledgment r722.3 Terminal 8 (DI3), fault acknowledgment

Signal source OR 0 p20046.0 OR 0 input 0 r20189.0 RSR 0 output Q Signal source OR 0 p20046.1 OR 0 input 1 r20194.0 RSR 1 output Q Signal source OR 0 p20046.2 OR 0 input 2 0 Input permanently reset Signal source OR 0 p20046.3 OR 0 input 3 0 Input permanently reset Runtime group of OR 0 p20048 OR 0 runtime group 1 Runtime group 1 Signal source OR 1 p20050.0 OR 1 input 0 r722.1 Terminal 6 (DI1), ON counter-

clockwise signal Signal source OR 1 p20050.1 OR 1 input 1 r722.2 Terminal 7 (DI2), OFF1 signal Signal source OR 1 p20050.2 OR 1 input 2 0 Input permanently reset Signal source OR 1 p20050.3 OR 1 input 3 0 Input permanently reset Runtime group of OR 1 p20052 OR 1 runtime group 1 Runtime group 1 Signal source OR 2 p20054.0 OR 2 input 0 r722.0 Terminal 5 (DI0), ON clockwise

signal Signal source OR 2 p20054.1 OR 2 input 1 r722.2 Terminal 7 (DI2), OFF1 signal Signal source OR 2 p20054.2 OR 2 input 2 0 Input permanently reset Signal source OR 2 p20054.3 OR 2 input 3 0 Input permanently reset Runtime group of OR 2 p20056 OR 2 runtime group 1 Runtime group 1 Signal source RSR 0 p20188.0 RSR 0 input S "set" r722.0 Terminal 5 (DI0), ON clockwise

Page 10: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

5 Example 4: ON clockwise, ON counter-clockwise, OFF1 using three NO contacts

10 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

Function Parameter Description Value Description signal

Signal source RSR 0 p20188.1 RSR 0 input R "reset" r20051.0 OR 1 output Q Runtime group of the RSR 0 p20191 RSR 0 runtime group 2 Runtime group 2 Signal source RSR 1 p20193.0 RSR 1 input S "set" r722.1 Terminal 6 (DI1), ON counter-

clockwise signal Signal source RSR 1 p20193.1 RSR 1 input R "reset" r20055.0 OR 2 output Q Runtime group of the RSR 1 p20196 RSR 1 runtime group 2 Runtime group 2

1) Factory setting for CU240B-2, CU240E-2, CU240E-2 F, CU230P-2 BT, CU230P-2 CAN and CU230P-2 HVAC 2) As setpoint source, in macro 12, analog input AI0 is used as bipolar voltage input (-10 V ... +10 V). When required, the analog input can be reparameterized using parameter p0756 – and also the setpoint source can be reparameterized using parameter p1000. When using the analog inputs as setpoint source, the associated DIP switches must also be set. For the voltage input, DIP switch AI0/1 must be set to the "U" position. For the current input, DIP switch AI0/1 or AI2 (only for CU230P-2) must be set to the "I" position.

Page 11: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

6 Example 5: ON clockwise, ON counter-clockwise, OFF1 using two NO contacts and one NC contact (OFF1)

SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)? Version 1, Item ID: 75277503 11

6 Example 5: ON clockwise, ON counter-clockwise, OFF1 using two NO contacts and one NC contact (OFF1)

Description of the terminals and signals for 3 digital inputs: Terminal 5 (DI0), NO contact – "ON clockwise" command (r722.0) Terminal 6 (DI1), NO contact – "ON clockwise" command (r722.1) Terminal 7 (DI2), NC contact – "OFF1" command (r722.2)

Parameters for example 5 Table 6-1

Function Parameter Description Value Description Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

1 Fast commissioning

Macro selection p0015 Macro drive unit 12 Macro 12 1) 2)

Sets the parameter filter for commissioning a drive

p0010 Drive, commissioning parameter filter

0 Ready

"ON/OFF1" command p0840.0 ON/OFF1 r20047.0 OR 0 output Q Negative direction p1110.0 Inhibit/enable negative

direction 0 Enable negative direction

Sets the signal source for inverting the setpoint

p1113.0 Setpoint inversion r20194.0 RSR 1 output Q

Sets the signal source for acknowledging a fault

p2103.0 Fault acknowledgment r722.3 Terminal 8 (DI3), fault acknowledgment

Signal source OR 0 p20046.0 OR 0 input 0 r20189.0 RSR 0 output Q Signal source OR 0 p20046.1 OR 0 input 1 r20194.0 RSR 1 output Q Signal source OR 0 p20046.2 OR 0 input 2 0 Input permanently reset Signal source OR 0 p20046.3 OR 0 input 3 0 Input permanently reset Runtime group of OR 0 p20048 OR 0 runtime group 1 Runtime group 1 Signal source OR 1 p20050.0 OR 1 input 0 r722.1 Terminal 6 (DI1), ON counter-

clockwise signal Signal source OR 1 p20050.1 OR 1 input 1 r20079.0 NOT 0 inverted output Signal source OR 1 p20050.2 OR 1 input 2 0 Input permanently reset Signal source OR 1 p20050.3 OR 1 input 3 0 Input permanently reset Runtime group of OR 1 p20052 OR 1 runtime group 1 Runtime group 1 Signal source OR 2 p20054.0 OR 2 input 0 r722.0 Terminal 5 (DI0), ON clockwise

signal Signal source OR 2 p20054.1 OR 2 input 1 r20079.0 NOT 0 inverted output Signal source OR 2 p20054.2 OR 2 input 2 0 Input permanently reset Signal source OR 2 p20054.3 OR 2 input 3 0 Input permanently reset

Page 12: SINAMICS G120 with CU2xy-2 (from FW V4.4) FAQ y November 2012 · 2016. 8. 10. · FAQ y November 2012 . Question 2 SINAMICS G120 (CU2xy-2): ... The functions and solutions described

6 Example 5: ON clockwise, ON counter-clockwise, OFF1 using two NO contacts and one NC contact (OFF1)

12 SINAMICS G120 (CU2xy-2): Can I also use a pushbutton for control (without relay interconnection)?

Version 1, Item ID: 75277503

Function Parameter Description Value Description Runtime group of OR 2 p20056 OR 2 runtime group 1 Runtime group 1 Signal source NOT 0 p20078 NOT 0 input I r722.2 Terminal 7 (DI2), OFF1 signal Runtime group of NOT 0 p20080 NOT 0 runtime group 1 Runtime group 1 Signal source RSR 0 p20188.0 RSR 0 input S "set" r722.0 Terminal 5 (DI0), ON clockwise

signal Signal source RSR 0 p20188.1 RSR 0 input R "reset" r20051.0 OR 1 output Q Runtime group of the RSR 0 p20191 RSR 0 runtime group 2 Runtime group 2 Signal source RSR 1 p20193.0 RSR 1 input S "set" r722.1 Terminal 6 (DI1), ON counter-

clockwise signal Signal source RSR 1 p20193.1 RSR 1 input R "reset" r20055.0 OR 2 output Q Runtime group of the RSR 1 p20196 RSR 1 runtime group 2 Runtime group 2

1) Factory setting for CU240B-2, CU240E-2, CU240E-2 F, CU230P-2 BT, CU230P-2 CAN and CU230P-2 HVAC 2) As setpoint source, in macro 12, analog input AI0 is used as bipolar voltage input (-10 V ... +10 V). When required, the analog input can be reparameterized using parameter p0756 – and also the setpoint source can be reparameterized using parameter p1000. When using the analog inputs as setpoint source, the associated DIP switches must also be set. For the voltage input, DIP switch AI0/1 must be set to the "U" position. For the current input, DIP switch AI0/1 or AI2 (only for CU230P-2) must be set to the "I" position.