Foreword, Contents
General description
Function Description andUser Information
Communication Error Codes
Error Supplementary Codes
6DD1987-1AB0
General Diagnostics
SIMADYN D
Reference Manual
Siemens Aktiengesellschaft Order No. 6DD1987-1AB0
This Manual contains notices which you should observe to ensure your own personal safety, aswell as to protect the product and connected equipment. These notices are highlighted in theManual by a warning triangle and are marked as follows according to the level of danger:
_________________________________________________________________________
Dangerindicates that death, severe personal injury or substantial property damage will result if properprecautions are not taken._________________________________________________________________________
_________________________________________________________________________
Warningindicates that death, severe personal injury or substantial property damage can result if properprecautions are not taken._________________________________________________________________________
_________________________________________________________________________
Cautionindicates that minor personal injury or property damage can result if proper precautions are nottaken._________________________________________________________________________
_________________________________________________________________________
Notedraws your attention to particularly important information on the product, handling the product,or to a particular part of the documentation._________________________________________________________________________
Note the following:
_________________________________________________________________________
WarningThis device and its components may only be used for the applications described in the catalogor the technical description, and only in connection with devices or components from othermanufacturers which have been approved or recommended by Siemens._________________________________________________________________________
SIMATIC and SIMADYN D are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer totrademarks might infringe upon the rights of the trademark owners.
Safety Guidelines
!
!
!
Correct usage
!
Trademarks
Copyright SIEMENS AG 1997 All rights reserved Disclaimer of liability
The reproduction, transmission or use of this document or itscontents is not permitted without express written authority.Offenders will be liable for damages. All rights, including rightscreated by patent grant or registration or a utility model or design,are reserved.
Siemens AGDrives and Standard Products GroupASI 1 Variable-Speed Drives DivisionFrauenauracher Straße 8091056 Erlangen
We have checked the contents of this manual for agreement withthe hardware and software described. Since deviations cannot beprecluded entirely, we cannot guarantee full agreement. However,the data in this manual are reviewed regularly and any necessarycorrections included in subsequent editions. Suggestions forimprovement are welcomed.
Siemens AG 1997Technical data subject to change.
General diagnostics - SIMADYN D - Reference Manual iii6DD1987-1BA0 Edition 06.97
Foreword
NOTES • This Reference Manual is provided solely as a additionalinformation source and is not necessarily up-to-date.
• No guarantee can be made for the technical correctness of thismanual.
This Reference Manual will help you
• when troubleshooting the SIMADYN D control system, and
• serve as Reference Manual.
The individual diagnostic capabilities will be explained.
This manual is intended for engineers commissioning SIMADYN Dprograms. It is assumed that these persons are knowledgeable aboutinstrumentation and control.
This manual is valid for SIMADYN D Version 3.1 of D7-SYS.
Purpose of thisManual
Target group
Validity of thisManual
Foreword
iv General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 06.97
Comprehensive user documentation which is intended for selective use,is available to support personnel when configuring and programming aSIMADYN D control task. The following information together with Fig. 0-1 will help you select the user documentation which you actually require.
Symbol Significance
Reference Manual for selective use
The documentation introduces you to the methodology used.
The documentation is supplemented by an online help.
SIMADYN D
Simple to assemble and configure
SIMADYN DSystem software andD7-SYS configuringD7-SYS communication configuring
SIMADYN D
Online help
Online help
SIMADYN DBasis software for D7-SYS
CFC for SIMADYN D Continuous Function Chart
SIMADYN D
SIMADYN D
SIMADYN D
SIMADYN D
Hardware
Glossary and complete index
Help on events
Function block library
Online help1
1
Manual
1
Manual
Manual
Manual
Intro-duction
CompleteIndex
Reference Manual
Online help
Online help
Manuals can be individually ordered.1
? This subject is documented in an online help
?
Fig. 0-1 Overview of SIMADYN D documentation, Version V5.0
Overview of theSIMADYN Ddocumentation,Version V5.0
Foreword
General diagnostics - SIMADYN D - Reference Manual v6DD1987-1BA0 Edition 06.97
Introduction
Simply to assemble andconfigure
The Introduction provides an extremely simple entry into the methodologywhen assembling and programming the SIMADYN D control system. It isespecially conceived for first-time users of a control system.
System software andconfiguring D7-SYS
This Manual provides basic knowhow about the structure of the operatingsystem and an application program of a SIMADYN D CPU. It should beused to obtain an overview of the programming methodology, and as basisfor a user program design and configuration.
D7-SYS communicationconfiguring
This Manual provides you with basic knowhow about the SIMADYN Dcommunications capability and how to configure links to communicationpartners
Function block library This Reference Manual provides you with an overview of SIMADYN Dfunction blocks, such as closed-loop control-, communication blocks etc .
Basis software forD7-SYS
This Manual explains the essential use and the functions of the STEP 7automation software with a main focus on the SIMADYN D control system.For first users of SIMADYN D, the Manual provides an overview onconfiguring, programming and commissioning a SIMADYN D subrack.
When working with the basis software, you can access the context-sensitive online help which provides support when it comes to detailedquestions regarding software use.
CFC for SIMADYN DContinuous FunctionChart
The CFC language (Continuous Function Chart) allows you to graphicallyinterconnect blocks.
The following manuals are available: "CFC for S7, Continuous FunctionChart" and "CFC for SIMADYN D, Continuous Function Chart".
Further, when using the software, you can access the online help which cananswer detailed questions regarding the use of the editors/compilers.
Hardware The complete SIMADYN D hardware spectrum is described as reference inthis Manual.
Table 0-1 Information overview of the SIMADYN D Manuals, Version V5.0
This reference Manual is sub-divided as follows:
• resources for troubleshooting
• various error classes
• error codes
The "General diagnostics" Reference Manual consists of the followingdocuments:
Document Edition
1 General description 06.97
2 Function Description and User Information 06.97
3 Communication Error Codes 06.97
4 Error Supplementary Codes 06.97
Guide
Foreword
vi General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 06.97
The user section of this Manual does not contain any detailedinstructions with individual steps, but instead is intended to explain thebasic procedure. More detailed information on the software dialogs andtheir handling, are provided in the online help.
Please contact your local Siemens partner if you have questionsregarding the software which are neither addressed in the paperdocumentation nor in the online help. You can use a Hotline:
• Tel.: +49(9131) 98-5000
• Fax: +49(9131) 98-1603
• e-mail: [email protected]
If you have any questions or comments regarding this Manual, pleasecomplete the questionnaire at the end of the Manual and send it to theaddress below. Please let us know your personal opinion about theManual
We offer appropriate courses to make it easier for you to get to know theSIMADYN D automation system. Please contact the Central TrainingCenter in Erlangen:
• Tel.: +49(9131) 7-27689, -27972
• Fax: +49(9131) 7-28172
• Internet: http://www.atd.siemens.de/it-dl/training
• Intranet: http://training.erlm.siemens.de
Specialinformation
Additional support
General diagnostics - SIMADYN D - Reference Manual vii6DD1987-1BA0 Edition 10.97
Inhaltsverzeichnis
1 General description............................................................................................................. 1-1
1.1 The various resources for troubleshooting................................................................. 1-11.2 System error fields.................................................................................................... 1-3
2 Function description and user instructions ...................................................................... 2-1
2.1 Acknowledging errors................................................................................................ 2-12.2 The various SIMADYN D error classes ..................................................................... 2-1
2.2.1 Error in the INIT operating mode, 7-segment display "0" ................................ 2-12.2.2 Error in the RUN operating mode, 7-segment display "E", "C", "A" ................. 2-8
2.2.2.1 Error, task administrator "E" ......................................................... 2-82.2.2.2 Error communications "C" ............................................................ 2-92.2.2.3 User error "A"............................................................................. 2-102.2.2.4 Fatal system error "H" ................................................................ 2-10
2.3 Background processing........................................................................................... 2-142.3.1 Online test mode.......................................................................................... 2-142.3.2 Monitoring error, 7-segment display "b"........................................................ 2-14
3 Communication Error Codes.............................................................................................. 3-1
3.1 Overview .................................................................................................................. 3-13.2 Error Codes .............................................................................................................. 3-2
3.2.1 Data Interface Access Mechanisms ............................................................... 3-23.2.2 Data Interface Initialization Errors (IB Errors) ............................................... 3-183.2.3 Network ....................................................................................................... 3-183.2.4 Service ........................................................................................................ 3-31
3.2.4.1 Display....................................................................................... 3-323.2.4.2 Specific SS52 ............................................................................ 3-37
3.2.5 Process Data ............................................................................................... 3-383.2.6 Message System ......................................................................................... 3-413.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace)................................ 3-463.2.8 Time ............................................................................................................ 3-53
3.2.8.1 Device........................................................................................ 3-553.2.8.2 Download................................................................................... 3-58
3.2.9 Central Blocks for Links ............................................................................... 3-603.2.9.1 Coupling Memory Link................................................................ 3-603.2.9.2 Rack Link ................................................................................... 3-633.2.9.3 PN Local Link............................................................................. 3-683.2.9.4 Link DUST1................................................................................ 3-713.2.9.5 Link SINEC H1........................................................................... 3-713.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung ............... 3-753.2.9.7 EP Link ...................................................................................... 3-813.2.9.8 Link DUST7................................................................................ 3-843.2.9.9 Link DUST2................................................................................ 3-893.2.9.10 Link DUST3.............................................................................. 3-933.2.9.11 USS Link.................................................................................. 3-973.2.9.12 Rack Link Fiber Optic Cable................................................... 3-101
3.2.10 Gerätekopplung und Parameterbearbeitung auf T400.............................. 3-108
Inhaltsverzeichnis
viii General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
4 Error Supplementary Codes ............................................................................................... 4-1
4.1 Supplementary code "bsspvw_geme"....................................................................... 4-14.2 Supplementary code "bsspvw_info" .......................................................................... 4-24.3 Supplementary code "zbin_komdat" ......................................................................... 4-34.4 Supplementary code "zgsd_zini_nachtrag" ............................................................... 4-6
General diagnostics - SIMADYN D - Reference Manual 1-16DD1987-1BA0 Edition 10.97
1 General description
1.1 The various resources for troubleshooting
The following resources are available in the system for troubleshooting:
The 7-segment display on the CPU module is the first resource whichpermits rough troubleshooting. Depending on the error type, instead ofthe configured CPU number, a symbol is displayed which classifies theerror. The first error which was identified, is displayed, flashing. Afterbeing acknowledged with the red button on the CPU module, the errorcode of the next error which was identified, is then displayed. Thesequence in which these error codes are displayed depends on thepriority of the error.
The following can be displayed on the 7-segment display:
Initialization running (short numberscan also appear here)
<OFF> or <.> Processor crashed, no furtherdiagnostics possible. Replace thememory module or CPU module
.. CPU number, cyclic operation without system error
Monitoring error, cyclic operation; service possible; refer tothe Chapter "Monitoring errors
Communication errors, cyclic operation, service possible;refer to the Chapter "Communication errors"
Task administration error, cyclic operation; service possible;refer to Chapter "Task administration errors"
User error, generated by the USF function block, cyclicoperation; service possible; refer to the Chapter "User errors"
NOTE
At initialization orin the off status,operating modeINIT
In cyclic operationRUN operationmode
General description
1-2 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
Initialization error, no cyclic operation; service possible; referto Chapter "Initialization errors"
Non-maskable interrupt, no cyclic operation; service possible;refer to the Chapter "Fatal system errors"
(as running light). Error when loading the system software, nofurther diagnostics possible. The memory module could bedefective or data incorrectly loaded into it.
Stop mode, initiated by the user. Fast download
System error fields and exception buffers are memory areas in whichdetailed information on the errors which have occurred, can be saved.
Non-critical errors from the various software components (operatingsystem, communications,...) are saved in the system error fields.
The current system status is saved in the exception buffer when a fatalerror occurs, which results in standard processing being stopped.
These error fields are read-out, e. g. using CFC in the test mode.
In non-cyclicoperation, STOPoperation mode
NOTE
General description
General diagnostics - SIMADYN D - Reference Manual 1-36DD1987-1BA0 Edition 10.97
1.2 System error fields
In addition to the displayed symbols in the CPU 7-segment display,detailed error information is saved in the central RAM area of the CPUmodule. These data areas are designated system error fields.The system error fields, described here are called INIT_ERR andSYS_ERR.
Hardware-related error information is coded in the system error fieldINIT_ERR.
The various software components (operating system, communications,monitor, user, ...) enter their error information in the SYS_ERR systemerror field.
The first error field is used to identify which of the software componentswas the first to flag an error. It is possible to identify the first one from aseries of saved errors (which may subsequently initiate other errors).The first error field is a bit field in which each software component has anassigned bit. This is set to ’1’, if this component is the first to enter anerror.
The assignment of the bits can be seen from the following table:
First error field
Byte 1 Byte 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Always 0 User-generatederror code
Always0
Always0
Communi-cationserror
Hardwarefailure
(monitoringerror)
Taskadmini-stration
error
Always0
Fatalsystemerror
1) -> 0400H 0040H 0020H 0008H 0001H
Table 1.2-1 Assignment of the bits
1) These hexadecimal values are valid for the appropriate softwarecomponents, as a maximum of one bit can be set in the first error field
First error fieldSYS_ERR_ERST
General description
1-4 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
General diagnostics - SIMADYN D - Reference Manual 2-16DD1987-1BA0 Edition 10.97
2 Function description and user instructions
2.1 Acknowledging errors
If an error occurs, then this is indicated on the CPU 7-segment display.With the exception of fatal system errors (NMI) and communicationerrors, these errors can be acknowledged by depressing theacknowledge key. The highest-priority error message is always displayedfirst. After depressing the acknowledge button, the next highest priorityerror message is displayed. The appropriate symbol is displayed,flashing, to identify that the displayed error was the first one to occur. Ifthere are no more errors, the logical CPU module number is displayed.
2.2 The various SIMADYN D error classes
2.2.1 Error in the INIT operating mode, 7-segment display "0"
The errors of the INIT operating mode are saved in the FLAGH, FPNIB,PNINKO, KO_CBUS and KO_LBU elements of the SYS_ERR error fieldand in the INIT_ERR error field.For errors, which occur when the system is initialized, the user programdoesn’t run-up. However, the service utility can be used and can be usedfor diagnostics.Error diagnostics should start at that CPU module, which was the first todisplay an error message . If there is no CPU module which can beidentified as having been the first, then that CPU should be selected,which displays a , and which is to the furthest left in the subrack.
The significance of the error field contents is listed in the followingpages:However, if fatal system errors occur at initialization (e. g. non-maskableinterrupt NMI), initialization is aborted, and an appears in the7-segment display.
Fatal system errors can occur following an initialization error, forexample, if a function block addresses hardware, which wasn’t previouslycorrectly initialized. Thus, when fatal system errors occur during theinitialization phase, the error field should first be investigated forinitialization errors!
NOTE
Function description and user instructions
2-2 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
Initialization error FLAGH
Set bit Significance
0 Error when initializing the DRAM memory object
1 Error when initializing the SRAM memory object
2 Error at C BUS upload
3 Error at C BUS download
4 Error when creating the C BUS buffer system
5 Error when initializing the C bus buffer system
6 Error at L BUS upload
7 Error at L BUS download
8 Error when creating the C BUS buffer system
9 Error when creating the L bus buffer system
10 Error when initializing the task manager
11 RAM change is inhibited in the change memory
12 Änderungsspeicherinhalt kann nicht geladen werden; Speicherplatzmangel beim Service
13 Fehler bei der Initialisierung der Dollarsignale
14
15 CPU hat kein Anwenderprogramm
Bits 0-10, subsequent errors or system errors; the user cannotresolve these errors
Bit 11 can be an error due to an erroneous change memory,especially for test operation, can be resolved, if, in the changememorythe correct test byte ID AA (hexa) is entered in byte 0, anda 0 is entered in byte 2.
!ATTENTION The change memory entries are then lost!
Bit 13: siehe Diagnose der Dollarsignal Initialisierungsfehler
Bit15: Anwenderprogramm laden
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-36DD1987-1BA0 Edition 10.97
PN initialization- and PN-IB error FBNIB
Set bit Significance
8 Group display from the initialization blocks. (also refer to system error field INIT_ERR, )
9 When requesting a mirror register area in a KS, the slot number or location ID areinconsistent, or the memory object ID illegal
10 The requested mirror register area has already been set-up in the local RAM or in thecommunications buffer module
11 Number of CPU modules in the C/L bus directory > 1 with the ID, no C/L bus buffermodule
15 Group display when communications is initialized
Subsequent errors or system errors; they cannot be resolved bythe user
Error flags from the coordination associated with initializing a multi-processor system, is entered in the PNINKO element.
Bits are set for the various error statuses, if the delay time, defined in theoperating system, is not adequate for synchronization, i. e. theappropriate initialization stage must be aborted. Even bits (0,2,..)designate the bus master, uneven bits, the bus slaves. Bits 0-7 are usedfor the C-bus coordination, bits 8-15, for L-bus coordination.
Set bits for Synchronizing is canceled for the definedoperation
Master Slave
C bus L bus C bus L bus
0 8 1 9 Copying local information into the KS
2 10 Before re-loading the KS lists into the localRAM
3 11 3 11 Loading the mirror register into thecommunications buffer
4 12 5 13 Re-loading the KS information into the localRAM
6 14 7 15 Initialization- or final synchronization
6 14 6 14 FP initialization, possibly due to erroneoususer function blocks. Also refer to KO_CBUSand KO_LBUS
Subsequent errors or system errors-CPU, which caused theerror, can be identified from KO_CBUS and KO_LBUS
Coordination errorat PN InitializationPNINKO
Function description and user instructions
2-4 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
The CPU modules are marked in these error fields, which hadn’tsynchronized with the CPU being investigated. The type of synchronizingerror is defined in the PNINKO component. The non-synchronized CPUmodules are logged using a bit pattern
in the components KO_CBUS for the C bus" " " KO_LBUS " " L bus
and the appropriate bits ("PN No." - 1) set to 1, whereby the PN No. isthe logical CPU number (CPU No. = Bit No. + 1).
Example: SIMADYN D CPU 7 does not checkback via the C bus=> KO_CBUS = 0040.
If errors are identified in the initialization blocks during the initializationphase, then this is indicated in the group display of theSYS_ERR_FPNIB components of the system error field SYS_ERR, and,detailed information regarding the error is also saved in the system errorfield INIT_ERR. Only module errors are registered in the error fieldINIT_ERR, for those modules which are located from the CPU module,being investigated, up to the next CPU module, inserted to the right inthe subrack.
Monitoring errors, i. e., errors, which were first identified during normaloperation, are also logged in INIT_ERR.
The INIT_ERR system error field is 25 words long (50 bytes). A word isreserved for each module, whereby word- and slot number are clearlyassigned to one another (word 1 to word 24 correspond to slots 1 to 24).Each SIMADYN D CPU saves its own error information in word 0.
An error is displayed, if in one or several words of this field, a value isnot equal to 0.
The following messages are possible in word 0:
Error number(hexadecimal)
Significance
1XXX L bus interrupt is not received from the slave CPU
2XXX C bus interrupt was not received from the slave CPU
4XXX L bus KS cannot be accessed for slave CPU
8XXX C bus KS cannot be accessed for slave CPU
FXXX The length of the interrupt vector table in a CPU initialization block is inconsistent
Missing checkbacksignal from theC bus or L busKO_CBUS andKO_LBUS
Diagnosinginitialization errorswith the systemerror fieldINIT_ERR
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-56DD1987-1BA0 Edition 10.97
Measures:
Check the daisy chain jumpers and insert as configured
System error or subsequent error, cannot be resolved by the user
The error numbers, listed here, can be located in words 1-24 of errorfield INIT_ERR.
System errors or subsequent errors, cannot be resolved by theuser
Function description and user instructions
2-6 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
Error number(hexadecimal)
Significance
01XX PAD initialization
011X CPU module error
0111 Incorrect module codeIncorrect module, incorrect type or development statusMeasure: Insert the right CPU module type
012X Periphery initialization errorMeasure: Insert the correct module into the correct slot
0121 Invalid slot number transferred
0122 Incorrect module code
0124 No access to the module
0128 Invalid memory range size
014X Chip select error
0141 Address limits for chip select B interchanged
0142 Address limits for chip select C interchanged
0144 Invalid slot basis address
018X Warnings
0181 All chip select inhibited
0182 Chip select address exceeded
0184 Illegal mask for chip select A
02XX Memory initialization
0200 L-bus communications buffer cannot be accessed from KS-IBMeasure: Test the communications buffer module
0201 Not possible to access the C-bus communications buffer from KS-IBMeasure: Check the communications buffer
0202 Error during memory object initialization
0204 Communication resource list not available
04XX Requesting the mirror register
0401 Illegal memory object ID
0402 Non-configured memory used
0404 Not sufficient memory available
0408 Memory object inhibited
0410 Distribution mode illegal
08XX Special periphery, IB errors
0801 C-bus connection not available
0802 Synchronizing error (is signaled as monitoring error)
0804 Incorrect slot numberMeasure: Insert the module into the correct slot
0808 Incorrect configured special periphery
0810 Dual port RAM unable to be accessed
0820 L-bus connection not available
0840 Configuring error
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-76DD1987-1BA0 Edition 10.97
Error number(hexadecimal)
Significance
0FXX Monitoring error
0F1X Memory test error, can be signaled both as initialization error as well as monitoringerror
0F10 User memory errorMeasure: Progam a new memory module
0F11 RAM error: Defective address lineMeasure: Change the module
0F12 Memory module errorMeasure: Program a new memory module
0F14 RAM error: Data line defectiveMeasure: Change the module
0F18 Special periphery test error
0F1F Incorrect transfer parameter
0F2X Error when testing
0F20 Incorrect slot numberMeasure: Insert the module into the correct slot
0F21 Battery failureMeasure: Insert a battery or replace the battery
0F22 Module does not respondMeasure: Insert the correct module type
0F24 Fatal system error on another CPU moduleMeasure: Search for errors on other CPU modules
0F4X Overload, area X5Short-circuit or excessive current (not a brief overload condition).Measure: Check the periphery
0F41 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8
0F42 Overlaod, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18
0F8X Overload, area X6Short-circuit or excessive current (not a brief overload condition).Measure: Check the periphery
0F84 Overload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
0F88 Overload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
0FCX Overload, areas X5 and X6 simultaneouslyShort-circuit or excessive current (not a brief overload condition).Measure: Check the periphery
0FC5 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 andoverload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
0FC9 Overload, area X5, PINs 1, 2, 3, 4, 5, 6, 7, 8 andoverload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
0FC6 Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 andoverload, area X6, PINs 1, 2, 3, 4, 5, 6, 7, 8
0FCA Overload, area X5, PINs 11, 12, 13, 14, 15, 16, 17, 18 andoverload, area X6, PINs 11, 12, 13, 14, 15, 16, 17, 18
Function description and user instructions
2-8 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
2.2.2 Error in the RUN operating mode, 7-segment display "E", "C", "A"
Errors, occurring in normal operation, are saved in the DAT, COM_PM,COM_EXC, and ANW elements of the SYS_ERR error field.
2.2.2.1 Error, task administrator "E"
If a task administrator error occurs, the user program continues to run aswell as it can. For cycle errors, or inhibited tasks, low-priority tasks areeither not processed, or not on a regular basis.
Errors of the task administrator are recorded in the SYS_ERR_DATcomponents of the SYS_ERR system error field. This field is 5 byteslong, which are assigned to the existing tasks (bytes 0 - 4 for cyclic tasksT1 - T5).
A task, which was processed error-free, has the value 0 in "its" byte. Bitswhich have been set, have the following significance (several bits can besimultaneously set):
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Cycle errorwhich cannotbe resolved
(endless loop)
Internalerror
Softwarewatchdog
(only for T1)
No free buffer inthe C bus
communicationsbuffer
Not used No free buffer inthe L-bus
communicationsbuffer
No freelocal buffer
Cycle erroror taskback-up
System errors or subsequent errors, cannot be resolved by the user
Before a task is started, it is checked as to whether the task to be startedcan be completely executed within the task sampling time, or if it isalways in the ’continuous’ status. This means, it is flagged as the highest-priority task. If this is the case, the task start is bypassed, i. e. the task isnot processed for one cycle.
However, a cycle error is only flagged, when several task starts fail, i. e.not at the first failure. Thus, seldom failures, which do not negativelyinfluence program execution, are simply bypassed.
Cycle errors
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-96DD1987-1BA0 Edition 10.97
If several cycle errors occur one after the other then you can assumethat a task has a significant problem. The cause can be an endless loopwithin this task, or that practically no computation time is made availablefor this task over a longer time period (this computation time iscompletely used by higher-priority tasks), and can therefore not be fullycomputed.
Thus, in this case, processing is stopped (with an in the 7-segmentdisplay) and the diagnostics mode (communications utility service) isstarted.The user can resolve a cycle error, e. g. by increasing the sampling timeof the task involved or by reducing the configured function blocks in theparticular task.
Task "bottleneck" for a particular task is only registered, if the task is notflagged as being the highest-priority task; however it should be startedagain. Generally, the cause is a cycle error of a higher-priority task.The task start is evaluated just as for cycle errors, and generates thesame display bit. The same task-specific error information is used.For a task "bottleneck", using the PSL function block, the utilization ofthe individual tasks should be determined, and, if required, reduced byre-configuring the software (as for cycle errors).
This error is the result that the data sink no longer enables the databuffer. The task start is skipped.
A software watchdog occurs if the basic sampling time is not processedfour times consecutively (one after another). The basic cycle timer is re-initialized with the configured basic sampling time, and processingcontinued.If two software watchdogs occur one after the other, then instead of thebasic cycle timer being re-initialized, processing is aborted (with an inthe 7-segment display) and diagnostics operation (service communi-cations utility) started.
2.2.2.2 Error communications "C"
Communication errors are entered in the SYS_ERR_COM_PMcomponents of the SYS_ERR error field. Several entries are possible.The SYS_ERR_COM_EXC components specify which communicationerrors have been entered.
A communications error consists of an error number, a supplementary IDas well as the configured chart- and block name and an address tolocalize the function block to be entered.
Task "bottleneck"
No free local buffer
Software watchdog
Function description and user instructions
2-10 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
2.2.2.3 User error "A"
The user himself specifies the entries in the SYS_ERR_ANWcomponents of the SYS_ERR system error field. The USF function blockmakes the entry.
2.2.2.4 Fatal system error "H"
If a fatal system error occurs, processing (initialization or normaloperation) is interrupted, and the system goes into the stop mode. Theerror cause is available for diagnostic purposes.
Before investigating a fatal system error, the INIT_ERR and SYS_ERRsystem error fields should first be investigated. If errors are entered there(especially hardware (monitoring) errors), then this could be the cause ofa fatal system error.
A SAVE area is set-up in the upper area, in the local RAM of each CPUmodule. This area is not erased at re-initialization, if the status of theRAM copy is appropriate. An error buffer is set-up in this SAVE area,which includes the error protocol (error report) consisting of severalmessages.
The error buffer consists of an administration part and a ring buffer, inwhich the error messages are saved. The ring buffer is implemented asbuffer which can be overwritten, i. e. if the buffer is full with errormessages, then the new messages overwrite the oldest messages.
There are 2 different types of error messages. A long message is outputin the case of a non-maskable interrupt NMI. A short message for apower OFF.
The service communications utility is available, (even if it has not beenconfigured) to troubleshoot fatal system errors. It can be accessed viathe local diagnostics interface, after pressing the acknowledge button.Using the service utility, the error causes can be output in plain text.What is especially important is the error cause, specified under an IDcode and supplementary ID. If a function block is being calculated at theinstant that the system error occurs, then this is output. In addition, theresults of the last bus accesses are displayed; these are important, if abus access is the error cause. Further, all of the process registers aredisplayed for the system specialists to allow them to make a preciseerror analyses.
NOTE
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-116DD1987-1BA0 Edition 10.97
When a non-maskable interrupt occurs, this is considered as fatal errorand causes initialization or normal operation to be interrupted. All of themodules, inserted in the subracks, are no longer processed.
A large flashing is displayed on the CPU module display of thefaulted module, which caused this fatal error. A large is displayed assteady display on the other CPU modules which received an NMI asresult of the faulted module. The debug monitor can be activated bypressing the acknowledge button or setting the status value. Thesymbols output on the 7-segment display have the following significance:
Steady : CPU module was shutdown by another module.
Flashing : Fatal error on this CPU module (error cause).
NMI handling
Function description and user instructions
2-12 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
Example for an error protocol (error report) for fatal system errors
Information on the last crash:Time: 01.01.93 04:16:24.9294 h Crash instantID: #5 CPUSupplementary ID: 28 (unaligned instruction fetch) Crash causeEPC: 0x04C4F19A Crash adress andReturn jump address: 0x801201f8 adress of the last function call
Running task: T2Started levels: T2(NRM),T5(NRM),BACKGROUND The running and started tasks at theLast processed FB: FP-KRUMMS.AY0815 (Typ: ADD8F) crash instant as well as the processed (ALE: 0x80107D84 CODE: function block with information on
0x801201E0) the data- and code areas
Last L-bus access: Data on the system bus accesses.- Access type: q_read_2byte This data is especially interesting,- BUS address: 0xB0F25874 if an erraneous bus access is specified- Retries: 0 as the cause of the crash in the ID Last C-bus access: (NMI) and supplementary ID.- Access type: q_read_2byte- BUS address: 0xB4F400B4- Retries: 0
The processor status at the crash instant: Register dump of all process registerEPC : 0x04C4F19A BadVAddr: 0x04C4F19A Especially important:Status : 0xF000FC14 mdlo : 0x04C4F19A EPC (crash adress, as above) andfpc_csr : 0x00000F04 BadVAddr (bad virtual adress, adress
which was erroneously accessed(mainly for ID TLB and CPU))
CAUTION: The value of a0, a1 (and possibly a2)is not valid!
r00/0 : 0x00000000 r01/at: 0x00000000 r02/v0: 0x00000001 r03/v1: 0xB8803000r04/a0: 0x80064FC8 r05/a1: 0x80064F44 r06/a2: 0x0000000A r07/a3: 0x00000000r08/t0: 0x80064FC4 r09/t1: 0x80065048 r10/t2: 0x19999999 r11/t3: 0x00000000r12/t4: 0x04C4F19A r13/t5: 0x8007FE90 r14/t6: 0x00000000 r15/t7: 0x00000000r16/s0: 0x800650CC r17/s1: 0x8006511C r18/s2: 0x00000000 r19/s3: 0x8006548Cr20/s4: 0x8006548C r21/s5: 0x00000020 r22/s6: 0x800812E0 r23/s7: 0x80400000r24/t8: 0xFFFFFFFF r25/t9: 0x8007FE90 r26/k0: 0x00000210 r27/k1: 0x04C4F19Ar28/gp: 0x80088BA0 r29/sp: 0x80064EA8 r30/s8: 0x04C4F19A r31/ra: 0x801201f8
d00: +Denorm d02: +6.400000e+01 d04: +Denorm d06: +9.999000e-01d08: +4.687500e+01 d10: +Denorm d12: +Denorm d14:+2.660285e+154d16: +3.000001e+03 d18: +4.687500e+01 d20: QNaN d22:+8.329648e+298d24: -1.818767e-12 d26:-1.227518e+306 d28:-3.691391e+249 d30:-2.374690e-237
f00: +4.787490e+01 f02: +0.000000e+00 f04: +4.687500e+01 f06: +4.764729e+05f08: +0.000000e+00 f10: +Denorm f12: +4.787490e+01 f14: -1.960343e+37f16: +1.024000e+03 f18: +0.000000e+00 f20: -1.693935e+38 f22: QNaNf24: QNaN f26: QNaN f28: -6.835168e-27 f30: -4.550802e-04
------------------------ End of the diagnostics -----------------------
}
Function description and user instructions
General diagnostics - SIMADYN D - Reference Manual 2-136DD1987-1BA0 Edition 10.97
A fatal system error can have the following causes (ID codes). Asupplementary ID describes the error cause in more detail.
ID Supplementary ID code (precise description)
NMI a non-maskable interruptsecond bus clear for task-controlled accessbus clear for direct accesstimeout during L/C-bus arbitration/assignment(module missing/defective, daisy chain missing)ready internal from L/C bus (error on anotherCPU module)ready internal from the local expansion bus (LE bus)system bus controller overruntimeout when accessing the local peripheryspurious interrupt (an interrupt source cannot beidentified)direct access to the L/C bus (bypassing thedriver functions)
CPU exceptional status of the CPUinternal errorreserved Instructionunknown Syscallunaligned instruction fetch (jump to address whichcannot be divided by four)user access to kernel spaceunaligned load/store to coprozessor 0/2/3unaligned load/store to L-/C-bus address spacebreak 6/7 not in div/mul contextunknown break valuereserved exceptiontask running in endless loop
FPU FPU exception statusfpu fault at non-fpu instructionillegal fpu sub opcodeoperation on NaNsadd/sub/division of infinitiesmul of infinity and 0
TLB exception status of the TLBTLB modified exceptionTLB read/write miss (access to illegal address)UTLB miss (access to illegal address)
TIME basic cycle time failureOFF power down
power down/reset in the normal modepower down/reset in the stop mode (after anotherexception)
Causes of fatalerrors
Function description and user instructions
2-14 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
2.3 Background processing
If the CPU has no tasks to process during normal operation, it processesthe background task.
As background task, the following functions are simultaneously available:
− the online test mode and
− a service utility
The online test mode is normally processed in the background afterinitialization was successfully completed. However, if the acknowledgebutton is pressed at the end of initialization, then only the servicecommunications utility is activated.
Errors in the background processing are saved in the UEB element of theerror field SYS_ERR.
2.3.1 Online test mode
In the online test mode, for example, a battery test, a memory modulechecksum test etc. are executed. The memory module checksum routinedetermines the memory module checksum and compares it with thechecksum calculated by the programmer and that saved in the memorymodule. If a memory module checksum error is identified in the onlinetest mode, the user can remove the error by repeatedly generating thememory module. For battery test errors, he can replace the battery.
2.3.2 Monitoring error, 7-segment display "b"
The background processing errors are known as monitoring errors. Theyare registered during the online test mode, and in the normal mode by an"b" at the 7-segment display. Further, the error information is saved inthe system error fields. However, there are also errors, which areidentified during initialization, but, due to their low significance, areflagged as monitoring errors and normal mode is still permitted. If amonitor error is identified, then the appropriate bit of the slot number ofthe associated board is set in the SYS_ERR_UEB component of theSYS_ERR system error. Further, detailed information is saved in theappropriate word of the INIT_ERR system error, in the slot number of theassociated module.
General diagnostics - SIMADYN D - Reference Manual 3-16DD1987-1BA0 Edition 10.97
3 Communication Error Codes
3.1 Overview
The distribution with regard to the individual functionalities is as follows:
Number Range Functionality
Total Already Utilized
6000 - 60DF 6000 - 60BF Data Interface Access Mechanisms
60E0 - 60FF 60E0 - 60E3 Data Interface Initialization Errors
6100 - 61FF 6100 - 61AA Network Management
6200 - 6280 6200 - 6206 Service
6300 - 6380 6300 - 6333 Process Data
6400 - 6480 6400 - 6421 Message System
6500 - 6580 6500 - 654A Trace
6600 - 6680 6600 - 660B Time
6700 - 67FF 6700 - 6718 Devices
6800 - 68FF 6800 - 6810 Down Load
6900 - 6BFF 6900 - 6A6F Central Blocks for Links
6C00 - 6FFF Unassigned
7C00 - /CFF 7C00 - 7CB66 Gerätekopplung und Parameterbearbeitung auf T400
Communication Error Codes
3-2 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
3.2 Error Codes
The error codes are structured according to the same scheme as with the"Error Diagnostics Communication V3.2’’. The codes consists of:
F: Error CauseR: System ReactionA: Resolve ByEQ: Definition Location and Equate of the Error CodesEM: Module, that determines the ErrorAM: Module, that displays the ErrorAA: Display Type of the Error
The extended error codes EQ, EM and AM (not printed in bold) are of nosignificance for the designer. They are only supplementary informationfor the hotline or the development department of SIMADYN D.
3.2.1 Data Interface Access Mechanisms
The error codes designated with ①, have no equates in SDZ.SD, but areconverted as follows from the defined acknowledge value:
Error Code = SDZ_QUIT_xxx ) 6010 Hex.
The error codes designated with ② , have no equates in SDZ.SD, but areconverted as follows from the defined acknowledge value:
Error Code = SDZ_QUIT_xxx * 20 Hex ) 6060 Hex.
6100 Hex ErrorNumber in HexFormat
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-36DD1987-1BA0 Edition 10.97
F: No error detected.R: Error free function.A: Not necessary.EQ: SDZ_FRW_ZC_DATA_OK.EM: ZC.CSF.AM: Block invoking the function zc_start.AA: None.
F: (Only receiver) transmitter has not identified itself, i.e. thechannel is not yet in operation.R: Receive operation has not yet taken place.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_SEND_N_STARTKLAR.EM: ZCRD.CSF.AM: Block invoking the function zc_start.AA: Warning state.
F: (Only transmitter) receiver has not yet identified itself, i.e.channel not yet in operation.R: Transmit operation has not taken place.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_EMPF_N_STARTKLAREM: ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: Transmitter:Handshake / Select: User data length of the data to be transmitted is zero and channel is empty.Refresh / Multiple: User data length is zero and channel
is readyfor operation.Receiver:Not Select: User data length of the data to be received iszero and no acknowledge exists from the transmitter.Select: User data length of the data to be received is
zero.R: Transmit / Receive operation has not taken place.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_N_ATGEM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only transmit)Handshake/Select: User data buffer in the channel is
still full and noacknowledge exists from the receiver.Refresh: User data buffer is being read in the
channel.Multiple: Cannot occur.
R: Transmit operation has not taken place.A: Re-invoke function zc_start.EQ: SDZ_FRW_ZC_PUF_VOLLEM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
Not utilized.
6000 Hex
6001 Hex
6002 Hex
6003 Hex
6004 Hex
6005 Hex
Communication Error Codes
3-4 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: (Only select transmit): another transmitter has temporarilyoccupied the channel.R: Transmit operation has not taken place.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_SEND_KAN_BLOCKEM: ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
utilized.
F: Defined acknowledge was inserted into the channel.R: Acknowledge operation has taken place.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_QUIT_ABGESETZTEM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The acknowledge ‘‘Remote Link Partner Missing’’ was read fromthe channel.R: Line to link partner defective;
The link partner is missing.A: Check line;
Re-invoke the function zc_startEQ: SDZ_QUIT_KOP_PART_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only receiver) the acknowledge "Transmit Pause’’ was readfrom the channel.R: Transmitter temporarily does not carry out transmitoperations.A: Re-invoke the function zc_start.EQ: SDZ_QUIT_SEND_PAUSE _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only transmit) the acknowledge ‘‘Receive Pause’’ was readfrom the channel.R: Receiver temporarily does not carry out receiveoperation.A: Re-invoke the function zc_start.EQ: SDZ_QUIT_EMPF_PAUSE _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The acknowledge ‘‘Break’’ was read from the channel.R: The link partner has temporarily disconnected.A: Re-invoke the function zc_start.EQ: SDZ_QUIT_BREAK _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
6006 Hex
6007 Hex to 600FHex6010 Hex
6011 Hex
6012 Hex
6013 Hex
6014 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-56DD1987-1BA0 Edition 10.97
F: The acknowledge ‘‘NMC Off" was read from the channel.R: The corresponding NMC FB in the link has switched tothe ‘‘OFF’’ state.A: Investigate the NMC block that transmitted theacknowledge.EQ: SDZ_QUIT_NMC_AUS _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only SINEC L2 DP)The acknowledge ‘‘Station cannot be Controlled’’ was
readfrom the channel.
R: Bit 1 of the station diagnostics (byte 0 of slave station)was set.A: Check station.EQ: SDZ_QUIT_STAT_N_STEUER _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only SINEC L2 DP)The acknowledge ‘‘Station not on the SI NEC L2 DP Bus’’
was readfrom the channel.
R: Bit 0 of the station diagnostics (byte 0 of the slavestation) was set.A: Check if station is operational;
Check whether bus cable is connected.EQ: SDZ_QUIT_STAT_N_AM_BUS _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: (Only SINEC L2 DP)The acknowledge ‘‘Station Diagnostics Error’’ was read
from the channel.R: Two or several bits of the station diagnostics (byte 0 ofslave station) were set.A: Two or more of the above described errors
(SDZ_QUIT_BG_AUS_PORT_ERR,SDZ_QUIT_ADR_ERR_PARA_ERR,
SDZ_QUIT_STAT_N_STEUER,SDZ_QUIT_STAT_N_AM_BUS) have occurred.
EQ: SDZ_QUIT_STAT_DIAG_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Warning state.
6015 Hex
6016 Hex
6017 Hex
6018 Hex
Communication Error Codes
3-6 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: (Only SINEC-L2-DP)The acknowledge "Slave already configured by another
Master"was read from the channel.
R: Is "another Master" a PG --> temporary faultIs "another Master" a general DP-Master --> two Masters
configurethe same slave; hard fault
A: Is "another Master" a PG: When the PG releases theslave, then
Master can access slave againIs "another Master" a general DP-Master: check bus
configurationEQ: SDZ_QUIT_MASTER_LOCK _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "Transmission error: Parity, Framing orOverrun" was read from the channel.R: The received telegram will be discardedA: Check hardware layout;
i.e. terminating resistor, bus cable, bus connector, etc.EQ: SDZ_QUIT_POF_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "BCC error" was read from the channel.R: The received telegram will be discardedA: Check hardware layout;
i.e. terminating resistor, bus cable, bus connector, etc.EQ: SDZ_QUIT_BCC_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "DUST3: No connect (no DLE)" was read fromthe channel.R: Connect is repeatedA: Start-up link partner;
Check hardware layout;i.e. terminating resistance, bus cable, bus connector, etc.
EQ: SDZ_QUIT_KOP_NO_ACK _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "DUST3: receive character delay" was readfrom the channel.R: The received telegram will be discardedA: Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.EQ: SDZ_QUIT_EZVZ_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
6019 Hex
601A Hex
601B Hex
601C Hex
601D Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-76DD1987-1BA0 Edition 10.97
F: The acknowledge "DUST3: Invalid receive string, receivecharacter during
transmission" was read from the channel.R: The received telegram will be discardedA: Check hardware layout;
i.e. terminating resistance, bus cable, bus connector, etc.EQ: SDZ_QUIT_CHAR_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "DUST3: Invalid receive telegram type" wasread from the channel.R: The received telegram will be discardedA: Check SIMATIC S5 configuring with regard to thetransmit telegram typeEQ: SDZ_QUIT_TEL_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
F: The acknowledge "DUST3 / USS: Faulty or no reaction telegram"was
read from the channel.R: The received telegram will be discardedA: Start-up link partner;
Check hardware layout;i.e. terminating resistance, bus cable, bus connector, etc.
EQ: SDZ_QUIT_TEL_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Warning status
not utilized
F: The acknowledge index from the user is invalid.R: No transmit / receive acknowledge operation took place.A: Contact Siemens AG.EQ: SDZ_FRW_ZC_USER_QUIT_ERREM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_start.AA: Block dependent.
F: Memory assigning for ZCDAT structure temporarily not possible.Exact cause see chapter Error Supplementary Code
bsspvw_geme.R: ZCDAT structure has not been set, link initializationcannot be started.A: Re-invoke function zc_start.EQ: SDZ_FRW_ZC_N_ANMEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
601E Hex
601F Hex
6020 Hex
6021 Hex to 602EHex602F Hex
6030 Hex
Communication Error Codes
3-8 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The CIP entry for the link was found.R: ZCDAT structure has been set, link initialization can bestarted.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_CIP_ETG_OKEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The link in the CIP entry is enabled.R: Initialization of the link has begun.A: Re-invoke function zc_start.EQ: SDZ_FRW_ZC_KOP_FREI_OKEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The link in the CIP entry has not yet been enabled.R: Initialization of the link has not yet been started.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_KOP_N_FREIEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The DEXDO3 area is enabled.R: The DEXDO3 enable is set to ‘‘Free’’ in the interface.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_DEXDO_FREI_OKEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The DEXDO3 area has not yet been enabled.R: The DEXDO3 enable is set to ‘‘Disable’’ in the interface.A: Re-invoke the function zc_start.EQ: SDZ_ZC_FRW_ZC_DEXDO_N_FREIEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: Link enabled, channel initialization running.R: Channel registration or channel registration checks arestarted.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_KAN_INIT_STARTEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
reserved for debug purposes (within zc_start).
F: Channel initialization completed without error.R: Channel registration or channel registration check iscompleted,
channel is switched to transmit / receive operation.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_KAN_INIT_OKEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
6031 Hex
6032 Hex
6033 Hex
6034 Hex
6035 Hex
6036 Hex
6037 Hex to 603EHex603F Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-96DD1987-1BA0 Edition 10.97
F: Back plane bus access unsuccessful.R: Exception processing has started, a new initialization issubsequently implemented.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_EXCEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
not utilized.
F: (Multiple receiver) data inconsistent in intermediate buffer.R: Transmitter has overwritten the data in the channelbefore the receiver could read it.A: Re-invoke the function zc_start.EQ: SDZ_FRW_ZC_DATA_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Warning state.
F: The buffer status is faulty in the channel.R: The information in the channel management isinconsistent, further processing
of the channel is not possible.A: Contact Siemens AG.EQ: SDZ_FRW_ZC_PUF_ZUS_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The channel status in the channel is faulty.R: The information in the channel management isinconsistent, further processing
of the channel is not possible.A: Contact Siemens AG.EQ: SDZ_FRW_ZC_KAN_ZUS_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Refresh receiver) buffer semaphore is blocked.R: The information in the channel management isinconsistent, further processing of
the channel is not possible.A: Contact Siemens AG.EQ: SDZ_FRW_ZC_PUF_SEM_SPERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Entry in ZCVWL list not possible, since the ZCVWL list is alreadyfull.R: ZCDAT area was not set, link initialization cannot bestarted.A: Reduce the link partners on the processor board.EQ: SDZ_FRW_ZC_ZCVWL_VOLLEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
6040 Hex
6042 Hex to 604EHex604F Hex
6050 Hex
6051 Hex
6052 Hex
6053 Hex
Communication Error Codes
3-10 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Memory assigning for ZCDAT structure not possible,exact error cause see section Error Supplementary Codebsspvw_geme.
R: ZCDAT area was not set, link initialization cannot bestarted.A: Reduce the RAM requirement in the application.EQ: SDZ_FRW_ZC_ZCDAT_VOLLEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only PN local link) the CIP entry cannot be accessed, since itpoints to another processor board.R: ZCDAT structure was set, but the link initialization cannotbe started.A: Board name at the communications port mustcorrespond to the nameof the processor board.EQ: SDZ_FRW_ZC_CIP_NAM_KENN_N_ADREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The CIP entry for the link does not exist.R: ZCDAT structure was set, but the link initialization cannotbe started.A: Check the configured name at the communications port.EQ: SDZ_FRW_ZC_CIP_NAM_N_KENNEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Unknown function return value of the function zbak_cip_suche.R: ZCDAT structure was set, but the link initialization cannotbe started.A: Contact Siemens AG.EQ: SDZ_FRW_ZC_CIP_SUCH_FRW_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
Not utilized.
F: Channel registration not possible since memory location inDEXDO3 interface is too small.R: Channel is not switched to the transmit / receiveoperation.A: Implement a memory reorganization (using CDVconnector at the corresponding central block) in order toremove possible channel corpses;
Reduce the link partners in the application.EQ: SDZ_FRW_ZC_MEM_KURZEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
6054 Hex
6055 Hex
6056 Hex
6057 Hex
6058 Hex
6059 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-116DD1987-1BA0 Edition 10.97
F: Channel with the desired channel names found but channelregistration check faulty because channel mode of thechannel and the user are different.R: Channel is not switched to the transmit / receiveoperation.A: Check the desired channel modes of the link partner.EQ: SDZ_FRW_ZC_KAN_MOD_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Channel with the desired channel names found but channelregistration check faulty because the user data structure ofthe channel and the user are different.R: Channel is not switched to the transmit / receiveoperation.A: Check the user data structures (connector types) of thelink partner.EQ: SDZ_FRW_ZC_DATA_STR_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Channel with the desired channel names found but channelregistration check faulty because the user data length of thechannel and the user are different.R: Channel is not switched to the transmit / receiveoperation.A: Check the desired user data lengths of the link partner.EQ: SDZ_FRW_ZC_DATA_LEN_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Channel with the desired channel names found but channelregistration check faulty because the utility type of thechannel and the user are different.R: Channel is not switched to the transmit / receiveoperation.A: Check the user types of the link partner.EQ: SDZ_FRW_ZC_DIENSTTYP_ERREM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Configuring error in the PROFIBUS DP (SS52)R: Channel is not released in the transmit/receive mode.A: Check the configuring; make sure that:
Mode = Refresh or (for receivers) MultipleUtility type = Process dataFirst character in the address stage 2 = "0" or "1"
EQ: SDZ_FRW_ZC_CSL2A_ERREM: ZCIN.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’, KFF
605A Hex
605B Hex
605C Hex
605D Hex
605E Hex
Communication Error Codes
3-12 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Internal error in the PROFIBUS DP (SS52)R: Channel is not released in the transmit/receive mode.A: Inform Siemens AG.EQ: SDZ_FRW_ZC_VARTYP_ERREM: ZCIN.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’, KFF
F: (Only receiver) the acknowledge ‘‘Incorrect Transmit Address’’was read from the channel.R: No connection to the link partner, because no remotepartner can be accessed under this transmit address.A: Check the transmit address of the link partner.EQ: SDZ_QUIT_SEND_ADR_ERR _EM: ZCRD.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only transmit) the acknowledge ‘‘Incorrect Receive Address’’was read from the channel.R: No connection to the link partner, since no remotepartner can be accessed under this receive address.A: Check the receive address of the link partner.EQ: SDZ_QUIT_EMPF_ADR_ERR _EM: ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only for networks)The acknowledge ‘‘Data Block False’’ was read from the
channel.R: The network could not connect to the last rack.A: Check that the utility types of the transmit and receiveblocks concur with one another;
Check that the desired data lengths of the transmit andreceive blocks concur with one another;
Check that the channel modes of the transmit andreceive blocks concur with one another;
Reduce the number of interface users for an endinterface on CSH11 or CS7 boards.EQ: SDZ_QUIT_TRANSIT_NDB_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge "No resources" was read by the channel.R: No connect to link partner, since no resources areavailable.A: CSH11: Check the buffer dimensioning in the NMLconfiguring and modify if necessary.
SS52: No helpEQ: SDZ_QUIT_N_RESOURCE _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Block dependant
605F Hex
6060 Hex
6061 Hex
6062 Hex
6063 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-136DD1987-1BA0 Edition 10.97
F: The acknowledge ‘‘Type Mis-Match’’ was read from the channel.R: No connection to the link partner, since the channel typedoes not match to the link partner.A: Check the channel type of the utility block:
Firmware is not permitted to synchronize itself as areceiver to the channel type multiple or as a transmitter to thechannel type select.EQ: SDZ_QUIT_TYP_MISMATCH _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge ‘Impermissible Utility Type’’ was read from the channel.
R: No connection to the link partner, since the utility type ofthe channel was faulty or not permitted by the link partner.A: Utilize a block, whose utility type is permitted by the linkpartner;
for SINEC L2 DP only the utility type process data ispermitted.EQ: SDZ_QUIT_ILLEGAL_DIENSTTYP _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge ‘‘CIP User Data Length does not match theAddress Stage 2’’ was read from the channel.R: No connection to the link partner, since the requiredlength of the user data and the address stage 2 areincompatible.A: Select another address stage;
Adapt the size of the data to be transmitted in theaddress stage.EQ: SDZ_QUIT_NDL_N_ADR2 _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge "Incorrect address stage 1" was read by the channel.
R: No connect to link partner, since the channel’s addressstage 1 does not match the link partner.A: Check the address stage 1 value range.EQ: SDZ_QUIT_ADR1_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Block dependant
6064 Hex
6065 Hex
6066 Hex
6067 Hex
Communication Error Codes
3-14 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The acknowledge "Incorrect address stage 2" was read by the channel.
R: No connect to link partner, since the channel’s addressstage 2 does not match the link partner.A: Check the address stage 2 value range.
USS: Check whether the station number has beenentered into thering buffer or whether a broadcast channel to adevice has been registered or whether an address stage 2is configuredEQ: SDZ_QUIT_ADR2_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Block dependant
F: The acknowledge ‘‘CIP User Data Length does not match theUser Data length of the VARANM Area’’ was read from thechannel.R: SW or HW error.A: Contact Siemens AG.EQ: SDZ_QUIT_NDL_N_VARANM _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge ‘‘Transmitter Already Registered’’ was readfrom the channel.
R: No connection to the link partner, since a transmitter isalready registered and a maximum of one is permitted.A: Remove a transmitter.EQ: SDZ_QUIT_SEND_ANM _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge ‘‘Receiver Already Registered’’ was read fromthe channel.R: No connection to the link partner, since a receiver isalready registered and a maximum of one is permitted.A: Remove a receiver.EQ: SDZ_QUIT_EMPF_ANM _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge ‘‘Invalid Data Format in VARANM Area’’ wasread from the channel.R: No connection to the link partner, since the data formatto be transmitted is not permitted.A: Check permissible data formats according to the table.EQ: SDZ_QUIT_DATA_FORMAT _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
6068 Hex
6069 Hex
606A Hex
606B Hex
606C Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-156DD1987-1BA0 Edition 10.97
F: The acknowledge ‘‘VARANM Area too Large’’ was read from the channel.
R: SW or HW error.A: Contact Siemens AG.EQ: SDZ_QUIT_VARANM_LEN_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only SINEC L2 DP)ET200U: The acknowledge ‘‘Board Pulled’’ was
read from the channel.ET200K: The acknowledge ‘‘Port Faulty’’ was read
from the channel.R: Bit 3 of the station diagnostics (byte 0 of the slavestation) was set.A: Check allocated station.EQ: SDZ_QUIT_BG_AUS_PORT_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only SINEC L2 DP)ET200U: The acknowledge ‘‘Incorrect Address ID’’
was read from the channel.ET200K: The acknowledge ‘‘Parameter Fault’’
was read from the channel.R: Bit 2 of the station diagnostics (byte 0 of the slavestation) was set.A: Check station parameters.EQ: SDZ_QUIT_ADR_ERR_PARA_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: (Only SINEC-L2-DP)The acknowledge "Configuring error: Station type does
not match IM318B" was read from the channel.R: No data exchange takes place via this channel with thecorresponding
Slave-Station.A: COM ET200: Check configuration of this station.EQ: SDZ_QUIT_PARA_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’
KFF (6070, pointer to configured name,Suppl. info dependent upon message generating block)
606D Hex
606E Hex
606F Hex
6070 Hex
Communication Error Codes
3-16 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The acknowledge "maximum number of channel connectsreached,
no further channels possible" was read from the channel.R: No data exchange takes place via this channel with thecorresponding
link partner.A: Reduce number of transmit / receive function blocksEQ: SDZ_QUIT_MAX_CHANNEL _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’
KFF (6071, pointer to configured name,Suppl. info dependent upon message generating block)
F: The acknowledge "incorrect mode (mode of operation)" was readfrom the channel.R: No data exchange takes place via this channel with thecorresponding
link partner.A: Check mode (mode of operation: Refresh, Handshake,Select, Multiple)EQ: SDZ_QUIT_MODE_ERR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’
KFF (6072, pointer to configured name,Suppl. info dependent upon message generating block)
F: (Only SINEC-L2-DP)Channel’s user data length does not match the COM
ET200 configuring.R: No data exchange to the corresponding link partner takesplace via this channel.A: SIMADYN D : Match the amount of data to betransmitted;
COM ET200: modify configuration.EQ: SDZ_QUIT_NDL_N_AWI _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Block dependant
F: (Only SINEC-L2-DP)Channel does not match COM ET200 configuring
(Address Stage1, Station Number)R: No data exchange to the corresponding link partner takesplace via this channel.A: Match the address stage1 and station number in COMET200.EQ: SDZ_QUIT_N_STAT_ADR1 _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: Block dependant
6071 Hex
6072 Hex
6073 Hex
6074 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-176DD1987-1BA0 Edition 10.97
F: (Only SINEC L2 DP)The acknowledge ‘‘No AWI Data Configured for the
Channel’’ was read from the channel.R: No connection to the link partner, since the AWI dataarea does not exist in the link partner.A: SIMADYN D: Remove transmit / receive FB;
COM ET200: Configure input / output bytes for station.EQ: SDZ_QUIT_NO_AWI_DATA _EM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: The acknowledge "Receive telegram is larger than the availableuser data buffer" was read from the channel.
R: No data exchange takes place via this channel with thecorresponding
link partner.A: Check configuring;
ensure that the maximum transmit data length does notexceed the receive data length.
EQ: SDZ_QUIT_NDL_ZUKL _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’
KFF (6076, pointer to configured name,Suppl. info dependent upon message generating block)
F: User data length too large for the link.R: No data exchange to the corresponding link partner takesplace via this channel.A: Reduce the amount of user dataEQ: SDZ_QUIT_NDL_ZUGR _EM: ZCRD.CSF, ZCWR.CSFAM: Block that invokes the function zc_startAA: 7-Seg ’C’
KFF (6077, pointer to configured name,Additional information dependant upon message
generating block)not utilized.
F: Unknown acknowledge value detected by the channelmanagement.R: SW or HW error.A: Contact Siemens AG.EQ: SDZ.SDEM: ZCRD.CSF, ZCWR.CSFAM: Block invoking the function zc_start.AA: Block dependent.
F: Unknown status flag in the ZCDAT structure.R: The channel is disabled.A: Contact Siemens AG.EQ: SDZ.SDEM: ZCIN.CSFAM: Block invoking the function zc_start.AA: Block dependent.
6075 Hex
6076 Hex
6077 Hex
6078 Hex to 60BEHex60BE Hex
60BF Hex
Communication Error Codes
3-18 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
3.2.2 Data Interface Initialization Errors (IB Errors)
F: The IB could not create the PN local KDR list.Exact cause of error, see section Error Supplementary
Code bsspvw_info.R: Processor board is not initialized.A: Contact Siemens AG.EQ: ZG_ERR_NUM_KDR_LIST_N_EINEM: ZG.CSFAM: ZG.CSFAA: 7-Seg. ‘I’.
F: The IB could not create the PN local ZCVWL list.Exact cause of error, see section Error Supplementary
Code bsspvw_info.R: Processor board is not initialized.A: Contact Siemens AG.EQ: ZG_ERR_NUM_ZCVWL_LIST_N_EINEM: ZG.CSFAM: ZG.CSFAA: 7-Seg. ‘I’.
F: The IB could not create the PN local ZINI list.Exact cause of error, see section Error Supplementary
Code bsspvw_info.R: Processor board is not initialized.A: Contact Siemens AG.EQ: ZG_ERR_NUM_ZINI_LIST_N_EINEM: ZG.CSFAM: ZG.CSFAA: 7-Seg. ‘I’.
F: The IB could not create the PN local list.Exact cause of error, see section Error Supplementary
Code bsspvw_info.R: Processor board is not initialized.A: Contact Siemens AG.EQ: ZG_ERR_NUM_CIP16K_LIST_N_EINEM: ZG.CSFAM: ZG.CSFAA: 7-Seg. ‘I’.
3.2.3 Network
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the @NMC initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NMC_ZUGR_KDREM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
60E0 Hex
60E1 Hex
60E2 Hex
60E3 Hex
6100 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-196DD1987-1BA0 Edition 10.97
F: Faulty operating status.R: Abort the @NMC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NMC_BZS_ERREM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: Initialization error.R: Abort the @NMC initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NMC_INIEM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: General @NMC group error.R: Abort the @NMC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NMC_INT_ERREM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: Channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: Abort the @NMC normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NMC_DREI_APFELEM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: No longer sufficient RAM memory available .Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @NMC normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NMC_NO_MEMEM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: Error in function zbin_komdat.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the @NMC normal mode.A: See section Error Supplementary Code zbin_komdat.EQ: ZF_ERR_NUM_NMC_ZBIN_KOMDATEM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
F: Invoking the sub-task not successful.R: Abort the @NMC initialization.A: Check the configured sampling time.EQ: ZF_ERR_NUM_NMC_INI_SUB_TASKEM: _NMC.CSFAM: _NMC.CSFAA: 7-Seg. ‘C’; YTS.
6101 Hex
6102 Hex
6103 Hex
6104 Hex
6105 Hex
6106 Hex
6107 Hex
Communication Error Codes
3-20 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
not utilized.
F: No @NMC configured or correctly initialized.R: Abort the NRI initialization.A: Correct @NMC configuring.EQ: ZF_ERR_NUM_NRI_N_NMCEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ’C’; YTS
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the NRI initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NRI_N_KDREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ’C’; YTS.
F: Faulty ISA connector.R: Abort the NRI initialization.A: Correctly configured the ISA connector.EQ: ZF_ERR_NUM_NRI_ISA_ERREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for NMC-NRI element not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_ELEMEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for NMC-NRI buffer not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_MEM_NMC_NRI_BUFEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for NRI-NMC buffer not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_MEM_NRI_NMC_BUFEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
6108 Hex to 611EHex6120 Hex
6121 Hex
6122 Hex
6123 Hex
6124 Hex
6125 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-216DD1987-1BA0 Edition 10.97
F: RAM memory assigning for RIL not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_MEM_RILEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS
F: Unknown operating status.R: Abort the NRI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NRI_BZS_ERREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ’C’; YTS
F: Configured data interface not found.R: Abort the NRI normal mode.A: Correctly configure the CTS connector.EQ: ZF_ERR_NUM_NRI_N_CIPEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ’C’; YTS.
F: Channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NRI normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NRI_KAN_ERREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: Error during channel search interface channel Read.R: Abort the NRI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NRI_N_IK1_SUCHEEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS
F: Error during channel search interface channel Write.R: Abort the NRI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NRI_N_IK2_SUCHEEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for VARANM area IKR not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_VARANM_IKREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
6126 Hex
6127 Hex
6128 Hex
6129 Hex
612A Hex
612C Hex
612E Hex
Communication Error Codes
3-22 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: RAM memory assigning for KOMDAT area IKR not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_KOMDAT_IKWEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
not utilized.
F: RAM memory assigning for VARANM area IKW not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_VARANM_IKWEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for KOMDAT area IKW not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_KOMDAT_IKWEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning for intermediate buffer IKW notpossible.
Exact cause see section Error Supplementary Codebsspvw_geme.R: Abort the NRI normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NRI_N_ZW_IKWEM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
not utilized.
F: The function zbak_kop_typ could not find the ZINI list;or the function zbak_kop_typ could not find the desired
CIP entry in the ZINI lists;or the function return value of the function zbak_kop_typ
is unknown.R: Abort the NRI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NRI_ZBAK_KOP_TYP_FRW_ERREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
612F Hex
6130 Hex
6131 Hex
6132 Hex
6133 Hex
6134 Hex to 6135Hex6136 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-236DD1987-1BA0 Edition 10.97
F: The link type is not supported.R: Abort the NRI normal mode.A: Configure NRI-FB on a board, that has networkcapability.EQ: ZF_ERR_NUM_NRI_KOP_TYP_ERREM: NRI.CSFAM: NRI.CSFAA: 7-Seg. ‘C’; YTS.
not utilized.
F: No @NMC initialized.R: Abort the NSI initialization.A: Correctly configure @NMC.EQ: ZF_ERR_NUM_NSI_N_NMCEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: No NTC initialized.R: Abort the NSI initialization.A: Correctly configure NTC.EQ: ZF_ERR_NUM_NSI_N_NTCEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: No NET list exists.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the NSI initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NSI_N_NETEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: Faulty operating state.R: Abort the NSI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NSI_N_DEFEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: Faulty return value of the zc_start function.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NSI normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NSI_ZCEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
not utilized.
6137 Hex
6138 Hex to 613FHex6140 Hex
6141 Hex
6142 Hex
6143 Hex
6144 Hex
6145 Hex
Communication Error Codes
3-24 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: No global list KDR exists.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the NSI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NSI_N_KDREM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ’C’; YTS
not utilized.
F: No back-up list exists.R: Abort the NSI initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NSI_BCK_LISTEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: RAM memory assigning not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NSI initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NSI_N_RAMEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS.
F: Error in function zbin_komdat.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the NSI initialization.A: See section Error Supplementary Code zbin_komdat.EQ: ZF_ERR_NUM_NSI_ZBINEM: NSI.CSFAM: NSI.CSFAA: 7-Seg. ‘C’; YTS
not utilized.
F: Faulty return value for the function zc_start.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NSL normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NSL_N_DEFEM: NSL.CSFAM: NSL.CSFAA: 7-Seg. ’C’; YTS.
6146 Hex
6147 Hex
6148 Hex
6149 Hex
614A Hex
614B Hex to 6161Hex6162 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-256DD1987-1BA0 Edition 10.97
F: Channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NSL normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NSL_ZCEM: NSL.CSFAM: NSL.CSFAA: 7-Seg. ‘C’; YTS.
F: Faulty operating status.R: Abort the NSL normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NSL_BZSEM: NSL.CSFAM: NSL.CSFAA: 7-Seg. ’C’; YTS
not utilized.
F: Insufficient RAM memory available.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NSL initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NSL_N_RAMEM: NSL.CSFAM: NSL.CSFAA: 7-Seg. ‘C’; YTS.
F: Error in the function zbin_komdat.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the NSL initialization.A: See section Error Supplementary Code zbin_komdat.EQ: ZF_ERR_NUM_NSL_ZBINEM: NSL.CSFAM: NSL.CSFAA: 7-Seg. ’C’; YTS.
not utilized.
F: No function block NTD correctly initialized.R: Abort the NTC normal mode.A: Correctly configure function block NTD.EQ: ZF_ERR_NUM_NTC_NO_NTDEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: No data interface for processing received from @NMC.R: Abort the NTC normal mode.A: This function block does not need to be configured.EQ: ZF_ERR_NUM_NTC_GOT_NO_CIPEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
6163 Hex
6164 Hex
6165 Hex to6166Hex6167 Hex
6168 Hex
6169 Hex to 617FHex6180 Hex
6181 Hex
Communication Error Codes
3-26 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The @NMC is not (no longer) active.R: Abort the NTC normal mode.A: Analyze the @NMC error message.EQ: ZF_ERR_NUM_NTC_NMC_OFFEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Faulty operating status.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_BZS_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Error while accessing the global list KDR.R: Abort the NTC initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_ZUGR_KDREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS
F: Multiple configuring NTC.R: Abort the NTC initialization.A: The function block NTC does not need to be configured.EQ: ZF_ERR_NUM_NTC_MEHRFACHPROJEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
not utilized.
F: Insufficient RAM memory available.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NTC normal mode.A: Create available RAM memory.EQ: ZF_ERR_NUM_NTC_NO_MEMEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Insufficient memory available on MM11.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NTC initialization.A: Create available memory.EQ: ZF_ERR_NUM_NTC_NO_NET_MEMEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Unknown channel mode.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_KANALMODUS_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
6182 Hex
6183 Hex
6184 Hex
6185 Hex
6186 Hex
6187 Hex
6188 Hex
6189 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-276DD1987-1BA0 Edition 10.97
F: Unknown channel status.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_KAN_STATUSEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: An invalid value is to be written into a status byte.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_KAN_FLAGS_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Invalid transit ID read from the channel.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_TRANSIT_KENNUNG_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Invalid transit direction of the channel determined.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_TRANSIT_RICHTUNG_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: Channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NTC normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NTC_DREI_APFELEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: The function znak_transit_kennung could not find a channel withthe
desired register number;or the return value of the function znak_transit_kennung
is unknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KENNUNG_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
618A Hex
618B Hex
618C Hex
618D Hex
618E Hex
618F Hex
Communication Error Codes
3-28 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The function znei_transit_kennung could not find a channelwith the desired register number;or the function znei_transit_kennung determined that the
semaphorefor the transit ID in the channel is disabled;or the return value of the function znei_transit_kennung
is unknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZNEI_TRANSIT_KENNUNG_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: The function znak_prk_aktiv determined that the desired link isnot a rack link;
or the return value of the function znak_prk_aktiv isunknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_ZNAK_PRK_AKTIV_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: Unknown return value of the function znei_kanal_komdat.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZNEI_KANAL_KOMDAT_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Unknown return value of the function znak_dexdo_zugriff.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZNAK_DEXDO_ZUGRIFF_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: The function znak_varanm_laenge could not find a channel withthe desired registered number;
or the return value of the function znak_varanm_laengeis unknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZNAK_VARANM_LAENGE_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
6190 Hex
6191 Hex
6192 Hex
6193 Hex
6194 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-296DD1987-1BA0 Edition 10.97
F: Unknown return value of the function znak_transit_kanal.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_ZNAK_TRANSIT_KANAL_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: Faulty return value of the function zc_start.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NTC normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NTC_ZC_START_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Internal error.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_INT_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: Several transmitters / receivers for the same handshake / refreshchannel.
R: Abort the NTC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTC_KAN_HR_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ‘C’; YTS.
F: The function zcei_kan_nam_loesch could not find a channel withthe desired registered number;
or the return value of the function zcei_kan_nam_loeschis unknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZCEI_KAN_NAM_LOESCH_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
F: The function zcak_kanal_nummer_bestimmen could not find achannel with the desired registered number; or the returnvalue of the function zcak_kanal_nr_bestimmen is unknown.R: Abort the NTC normal mode.A: Contact Siemens AG.EQ:
ZF_ERR_NUM_NTC_ZCAK_KAN_NR_BEST_FRW_ERREM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’; YTS.
6195 Hex
6196 Hex
6197 Hex
6198 Hex
6199 Hex
619A Hex
Communication Error Codes
3-30 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
not utilized.
F: No function block NTC active.R: Abort the NTD initialization.A: Correctly configure the function block NTC.EQ: ZF_ERR_NUM_NTD_NO_NTCEM: NTD.CSFAM: NTD.CSFAA: 7-Seg. ’C’; YTS.
F: Faulty return value of the function zc_start.Exact cause see section Data Interface Access
Mechanisms.R: Abort the NTD normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_NTD_KAN_ERREM: NTD.CSFAM: NTD.CSFAA: 7-Seg. ’C’; YTS.
F: Too little RAM memory.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the NTD initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_NTD_N_MEMEM: NTD.CSFAM: NTD.CSFAA: 7-Seg. ‘C’; YTS.
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the NTD initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTD_N_KDREM: NTD.CSFAM: NTD.CSFAA: 7-Seg. ‘C’; YTS.
not utilized.
F: Copy relationship failed (whilst reading the source channel).R: Copy relationship is no longer processed. The blockremains enabled.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTD_STS_ERR_QUELLEEM: NTD.CSFAM: NTD.CSFAA: YTS.
F: Copy relationship failed (whilst writing to the destinationchannel).R: Copy relationship is no longer processed. The blockremains enabled.A: Contact Siemens AG.EQ: ZF_ERR_NUM_NTD_STS_ERR_ZIELEM: NTD.CSFAM: NTD.CSFAA: YTS.
619B Hex to 619FHex61A0 Hex
61A1 Hex
61A2 Hex
61A3 Hex
614A Hex to 61A7Hex61A8 Hex
61A9 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-316DD1987-1BA0 Edition 10.97
F: Incorrect function return value.R: NTD is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_NTD_N_CIPEM: NTD.CSFAM: NTD.CSFAA: 7-Seg. ’C’
F: Too many data interfaces (CIP).R: NTC is disabledA: Reduce the number of data interfaces (fewerMM11/MM4 or CS11/CS21)EQ: ZF_ERR_NUM_NTC_CIP_ANZEM: NTC.CSFAM: NTC.CSFAA: 7-Seg. ’C’
3.2.4 Service
F: General initialization error.Exact cause see section Error Supplementary Code
zbin_komdat and bsspvw_geme.R: Abort the initialization, SER block not operating.A: Contact Siemens AG.EQ: Z_ERR_NUM_SER_INIT_ERREM: zdsest.csfAM: zdsest.csfAA: 7-Seg. ‘C’; YTS.
F: Initialization errors: insufficient RAM memory available.Exact cause see section Error Supplementary Code
zbin_komdat and bsspvw_geme.R: Abort the initialization, SER block not operating.A: Create available RAM memory.EQ: Z_ERR_NUM_SER_INIT_NO_MEMEM: zdsest.csfAM: zdsest.csfAA: 7-Seg. ’C’; YTS.
F: Initialization error: request channel cannot be initialized.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the initialization, SER block not operating.A: Check specifications at the CTS and US connectors.EQ: Z_ERR_NUM_SER_INIT_KOMDAT_RDEM: zdsest.csfAM: zdsest.csfAA: 7-Seg. ’C’; YTS.
F: Initialization error: reply channel cannot be initialized.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the initialization, SER block not operating.A: Check specifications at the CTS and US connectors.EQ: Z_ERR_NUM_SER_INIT_KOMDAT_WREM: zdsest.csfAM: zdsest.csfAA: 7-Seg. ’C’; YTS.
61AA Hex
61AB Hex
6200 Hex
6201 Hex
6202 Hex
6203 Hex
Communication Error Codes
3-32 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Initialization error: sub-task not created.R: SER block cannot operate.A: Check configured sampling times.EQ: Z_ERR_NUM_SER_INIT_SUB_TASKEM: zdsest.csfAM: zdsest.csfAA: 7-Seg. ’C’; YTS.
F: Request channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: SER block is disabled.A: See section Data Interface Access Mechanisms.EQ: Z_ERR_NUM_SER_KAN_ERR_RDEM: zdsekrd.csfAM: zdsekrd.csfAA: 7-Seg. ‘C’; YTS.
F: Reply channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: SER block is disabled.A: See section Data Interface Access Mechanisms.EQ: Z_ERR_NUM_SER_KAN_ERR_WREM: zdsekwr.csfAM: zdsekwr.csfAA: 7-Seg. ‘C’; YTS.
3.2.4.1 Display
F: Configuring FB type @DIS0R, connector DIS:Multiple configuring of display system with the same
name.R: Block is disabled.A: Enter correct specification at connector DIS.EQ: Z_ERR_NUM_DIS_MEHRFACHEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring FB type @DIS0R: Invalid sampling time.R: Block is disabled.A: Configure @DIS0R with valid sampling time (30ms <= t<= 300ms)EQ: Z_ERR_NUM_DIS_ABTASTZEITEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring FB type @DIS0R or DISxy, connector ST1 and ST2:No display station specified.
R: Block is disabled.A: Specification at connector ST1 or ST2 not equal to zero.EQ: Z_ERR_NUM_DIS_NOSTATIONEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
6204 Hex
6205 Hex
6206 Hex
6281 Hex
6282 Hex
6283 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-336DD1987-1BA0 Edition 10.97
F: Configuring @DIS0T or DISxy, connector DIS:Associated central block @DIS0R or @DIS0T is not
configured.R: Block is disabled.A: Configure block type @DIS0R and @DIS0T with thesame specification at connector DIS.EQ: Z_ERR_NUM_DIS_NO_ZBEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring @DIS0T or DISxy, connector DIS:Associated central block @DIS0R is not configured.
R: Block is disabled.A: Configure block type @DIS0R with the samespecification at connector DIS.EQ: Z_ERR_NUM_DIS_NO_DISEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring @DIS0T or DISxy:Sampling time does not match the associated @DIS0R.
R: Block is disabled.A: Configure block with the same sampling time [email protected]: Z_ERR_NUM_DIS_AKT_AUFGABEEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring DISA4, connector Y or DISS4, connector X:Type switching to V4 is not permitted.
R: Block is disabled.A: Set different connector type.EQ: Z_ERR_NUM_DIS_V4EM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Configuring DISxy, connector ST1 and ST2:Configured stations are not all initialized by the central
block @DIS0R.R: Block is disabled.A: Only specify those stations at ST1, ST2, that are alsospecified at @DIS0R.EQ: Z_ERR_NUM_DIS_STA_NOZBEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
6284 Hex
6285 Hex
6286 Hex
6287 Hex
6288 Hex
Communication Error Codes
3-34 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Configuring DISx, connector KEY:Process data number is already defined (for a display
station).R: Block is disabled.A: Select other process data number or check specificationat ST1, ST2.EQ: Z_ERR_NUM_DIS_PZD_DOPEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address ofthe display station)
F: Configuring DIS1x, connector KEY:Binary value number is already defined (for a display
station).R: Block is disabled.A: Select other binary value number or check specificationat ST1, ST2.EQ: Z_ERR_NUM_DIS_BIN_DOPEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = Station address ofthe display station)
F: Configuring DISxy, connector KEY: Invalid value configured.R: Block is disabled.A: Configure valid value (review block description).EQ: Z_ERR_NUM_DIS_KEYEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Internal: Error during memory create.Precise cause: review section Error suppl. code
bsspvw_geme.R: Block is disabled.A: Reduce the RAM requirements in the application.EQ: Z_ERR_NUM_DIS_GEMEEM: ZDDI.CSF, function BSSPVW_GEMEAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW ofBSSPVW_GEME)
F: Internal: Error during Save-memory create for setpoint.Precise cause: review section Error suppl. code
bsspvw_geme.R: Block is disabled.A: Reduce the SAVE requirements in the application.EQ: Z_ERR_NUM_DIS_GEMESAVEM: ZDDI.CSF, function BSSPVW_GEMEAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW ofBSSPVW_GEME)
6289 Hex
628A Hex
628B Hex
6290 Hex
6291 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-356DD1987-1BA0 Edition 10.97
F: Internal: Error during SAVE-pointer create for setpoint.R: Block is disabled.A: Reduce the SAVE requirements in the application.EQ: Z_ERR_NUM_DIS_SAVPUFEM: ZDDI.CSF, function BSSAVPUF_GEMEAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Internal: KDR list not foundR: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_KDREM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Internal: Error during sampling time calculationR: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_AMPI_TNEM: ZDDI.CSF, function AMPI_TNAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI_TN)
F: Internal: Error during receive channel initialization.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_KOMDAT_EMPFEM: ZDDI.CSF, function ZBIN_KOMDATAM: ZDDI.CSFAA: YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl.code = FRW of ZBIN_KOMDAT)
F: Internal: Error during transmit channel initialization.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_KOMDAT_SENDEM: ZDDI.CSF, function ZBIN_KOMDATAM: ZDDI.CSFAA: YTS, YAC = Station address; 7-Seg. ’C’, KFF (Suppl.code = FRW of ZBIN_KOMDAT)
F: Internal: Implementation error.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_IMPLEMEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Internal: Implementation errorR: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_FORMATEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
6292 Hex
6293 Hex
6294 Hex
6295 Hex
6296 Hex
6297 Hex
6298 Hex
Communication Error Codes
3-36 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Internal: (P32) Error during connector description fetch.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_BESCHREM: ZDDI.CSF, function AMPI/AFPIAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF (Suppl. code = FRW of AMPI/AFPIfunction)
F: Internal: (P16) Segment pointer fetch unsuccessful.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_BSBI_SEGEM: ZDDI.CSF, function BSBI_SEGAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Internal: (P16) Dimension text fetch unsuccessful.R: Block is disabled.A: Inform Siemens AG.EQ: Z_ERR_NUM_DIS_BSBI_DIMEM: ZDDI.CSF, function BSBI_DIMAM: ZDDI.CSFAA: YTS; 7-Seg. ’C’, KFF
F: Dialog unit: Incorrect request ID in the telegram.R: Transmit an error telegram to the dialog unit.A: Check dialog unit.EQ: Z_ERR_NUM_DIS_AUFKENNEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS, YAC = Station address;
Error telegram: Error class, (Error number = Request ID)F: Dialog unit: Incorrect telegram length.
R: Transmit an error telegram to the dialog unit.A: Check dialog unit.EQ: Z_ERR_NUM_DIS_AUFLGEEM: ZDDI.CSFAM: ZDDI.CSFAA: YTS, YAC = Station address;
Error telegram: Error class, (Error number = Telegramlength)
F: Dialog unit: Incorrect process data number requested.R: Transmit an error telegram to the dialog unit.A: Check dialog unit.EQ: Z_ERR_NUM_DIS_PZDNREM: ZDDI.CSFAM: ZDDI.CSFAA: YTS, YAC = Station address;
Error telegram: Error class, (Error number = PZDnumber)
6299 Hex
629A Hex
629B Hex
62A0 Hex
62A1 Hex
62A2 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-376DD1987-1BA0 Edition 10.97
F: Dialog unit: Incorrect binary value number requested.R: Transmit an error telegram to the dialog unit.A: Check dialog unit.EQ: Z_ERR_NUM_DIS_BINNREM: ZDDI.CSFAM: ZDDI.CSFAA: YTS, YAC = Station address;
Error telegram: Error class, (Error number = BINnumber)
3.2.4.2 Specific SS52
F: FB-DIAL2A: Impermissible specification at connector ST1 orST2.R: Block disables.A: Correct specification: 3<=ST1<=ST2<=123.EQ: Z_ERR_NUM_DPDIAG_ST1_ST8_NZUGEM: DIAL2A.CSFAM: DIAL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-DIAL2A: Too little memory (RAM) available.R: Block disables.A: Reduce configuring.EQ: Z_ERR_NUM_DPDIAG_N_SLAVE_LI
Z_ERR_NUM_DPDIAG_N_ZWI_PUZ_ERR_NUM_DPDIAG_N_VARANM_BER
EM: DIAL2A.CSFAM: DIAL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-@SYL2A: Impermissible specification at connector SEL.R: Block disables.A: Correct specification at connector SEL: 1<=SEL<=8.EQ: Z_ERR_NUM_DPSYNC_SEL_NZUGEM: @SYL2A.CSFAM: @SYL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-@SYL2A: Impermissible specification at connector CNX.R: Block disables.A: Correct specification at connector CNX: CNX>0.EQ: Z_ERR_NUM_DPSYNC_UNTERS_NZUGEM: @SYL2A.CSFAM: @SYL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-@SYL2A: Impermissible specification at connector CTS:Board does not exist or not a CS7.
R: Block disables.A: Correct specification at connector CTS.EQ: Z_ERR_NUM_DPSYNC_CIP3_NVHEM: @SYL2A.CSFAM: @SYL2A.CSFAA: 7-Seg ’C’, KFF
62A3 Hex
62A4 Hex
62A5 Hex62A6 Hex62A7 Hex
62A8 Hex
62A9 Hex
62AA Hex
Communication Error Codes
3-38 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: FB-@SYL2A: Impermissible specification at connector CTS:Only CS7/SS52 permitted with FB-@CSL2A.
R: Block disables.A: Correct specification at connector CTS.EQ: Z_ERR_NUM_DPSYNC_KOP_NZUGEM: @SYL2A.CSFAM: @SYL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-@SYL2A: Impermissible multiple configuring.R: Block disables.A: Remove block.EQ: Z_ERR_NUM_DPSYNC_FB_MEHRFACHEM: @SYL2A.CSFAM: @SYL2A.CSFAA: 7-Seg ’C’, KFF
F: FB-@SYL2A: Waiting for SS52 firmware.R: Wait.A: SS52 installed?EQ: Z_ERR_NUM_DPSYNC_SS52_WAITEM: @SYL2A.CSFAM: @SYL2A.CSFAA: Warning
3.2.5 Process Data
see section Data Interface Access Mechanisms.
F: RAM memory assigning for VARANM area not possible.Exact error cause see section Error Supplementary Codebsspvw_geme.
R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: Z_FRW_ZDPD_N_MEM_VARANMEM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,ZDPD.CSFAM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,CCC4.CSF, CDC4.CSFAA: 7-Seg. ‘C’; YEV.
F: Fehler bei Auswertung der Adreßparameter (Eingang AT, AR).Genaue Fehlerursache siehe Abschnitt Fehlerzusatzcodezbin_kombat.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: Z_FRW_ZDPD_INIT_KOMDAT_ERREM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,ZDPD.CSFAM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,CCC4.CSF, CDC4.CSFAA: 7-Seg. `C'; YEV.
62AB Hex
62AC Hex
62AD Hex
6000 Hex to 60BFHex6310 Hex
6311 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-396DD1987-1BA0 Edition 10.97
F: Specification at the MOD connector faulty.R: Block reverts to the dead status.A: Correct the specification at the MOD connector, only theH, R, S or M letters are permissible.EQ: Z_FRW_ZDPD_INIT_KOMDAT_ERREM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,ZDPD.CSFAM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,CCC4.CSF, CDC4.CSFAA: 7-Seg. ‘C’; YEV.
utilized for internal purposes.
F: Unknown function return value of the function zc_start.R: Block reverts to the dead status.A: Contact Siemens AG.EQ: Z_FRW_ZDPD_UNDEFEM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,CCC4.CSF, CDC4.CSFAM: _CRV.CSF, CRV.CSF, _CTV.CSF, CTV.CSF,CCC4.CSF, CDC4.CSFAA: 7-Seg. ‘C’; YEV.
F: RAM memory assigning for reference list not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CTV_N_MEM_REF_LISTEEM: _CTV.CSF, CTV.CSFAM: _CTV.CSF, CTV.CSFAA: 7-Seg. ‘C’; YEV.
F: RAM memory assigning for reference list not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CRV_N_MEM_REF_LISTEEM: _CRV.CSF, CRV.CSFAM: _CRV.CSF, CRV.CSFAA: 7-Seg. ‘C’; YEV.
F: Reference list no found; no virtual connection configured.R: Block reverts to the dead status.A: Check the virtual connection at the AT connector.EQ: ZF_ERR_NUM_CTV_N_REF_LISTEEM: _CTV.CSF, CTV.CSFAM: _CTV.CSF, CTV.CSFAA: 7-Seg. ‘C’; YEV.
F: Reference list no found; no virtual connection configured.R: Block reverts to the dead status.A: Check the virtual connection at the AR connector.EQ: ZF_ERR_NUM_CRV_N_REF_LISTEEM: _CRV.CSF, CRV.CSFAM: _CRV.CSF, CRV.CSFAA: 7-Seg. ‘C’; YEV.
utilized for internal purposes.
6312 Hex
6313 Hex to 631EHex631F Hex
6320 Hex
6321 Hex
6322 Hex
6323 Hex
6324 Hex to 631FHex
Communication Error Codes
3-40 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: RAM memory assigning for intermediate buffer not possible.Exact error cause of error see section Error
Supplementary Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CTV_N_MEM_ZWEM: _CTV.CSF, CTV.CSFAM: _CTV.CSF, CTV.CSFAA: 7-Seg. ‘C’; YEV.
F: RAM memory assigning for intermediate buffer not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CRV_N_MEM_ZWEM: _CRV.CSF, CRV.CSFAM: _CRV.CSF, CRV.CSFAA: 7-Seg. ‘C’; YEV.
F: RAM memory assigning for intermediate buffer not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CCC4_N_MEM_ZWEM: CCC4.CSFAM: CCC4.CSFAA: 7-Seg. ‘C’; YEV.
F: RAM memory assigning for intermediate buffer not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Block reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CDC4_N_MEM_ZWEM: CDC4.CSFAM: CDC4.CSFAA: 7-Seg. ‘C’; YEV.
F: unknown connector type during evaluation of the return valuefrom function zbak_kon_typ_wandelR: Block reverts to the neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_CRV_CTV_KON_N_KENNEM: ZBAK.CSFAM: _CRV.CSF, _CTV.CSF, CRV.CSF, CTV.CSFAA: 7-Seg. ’C’;
KFF (6334,pointer to configured name,0)
6330 Hex
6331 Hex
6332 Hex
6333 Hex
6334 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-416DD1987-1BA0 Edition 10.97
3.2.6 Message System
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the MSI initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSI_N_KDREM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ‘C’;
F: No central block @MSC configured.R: Abort the MSI initialization.A: Configure central block @MSC.EQ: ZF_ERR_NUM_MSI_N_MSCEM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ’C’;
F: RAM memory assigning not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the MSI initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_MSI_N_MEMEM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ’C’;
F: KOMDAT area cannot be initialized.Exact cause see section Error Supplementary Code
zbin_komdat.R: Abort the MSI initialization.A: See section Error Supplementary Code zbin_komdat.EQ: ZF_ERR_NUM_MSI_KOMDAT_INITEM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ’C’;
F: Channel continuously faulty.Exact cause see section Data Interface Access
Mechanisms.R: Abort the MSI normal mode.A: See section Data Interface Access Mechanisms.EQ: ZF_ERR_NUM_MSI_KAN_ERREM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ’C’;
F: Faulty operating status.R: Abort the MSI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSI_BZS_ERREM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ‘C’;
6400 Hex
6401 Hex
6402 Hex
6403 Hex
6404 Hex
6405 Hex
Communication Error Codes
3-42 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Faulty message format.R: Abort the MSI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSI_MF_ERREM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ‘C’;
F: Unknown return value of the function zc_start.R: Abort the MSI normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSI_ZC_START_FRW_ERREM: MSI.CSFAM: MSI.CSFAA: 7-Seg. ‘C’;
F: @MSC configured in incorrect sampling time.R: Abort the @MSC initialization.A: @MSC must be configured with the correct samplingtime.EQ: ZF_ERR_NUM_MSC_TN_ERREM: _MSC.CSFAM: @MSCAA: 7-Seg. ’C’;
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the @MSC initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSC_N_KDREM: _MSC.CSFAM: @MSCAA: 7-Seg. ’C’;
F: Multiple configuring of the @MSC.R: Abort the @MSC initialization.A: @MSC may only be configured once per rack.EQ: ZF_ERR_NUM_MSC_MEHR_PROJEM: _MSC.CSFAM: @MSCAA: 7-Seg. ‘C’;
F: Global list of the SAVE area not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the @MSC initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSC_N_SAVEEM: _MSC.CSFAM: @MSCAA: 7-Seg. ‘C’;
6406 Hex
6407 Hex
6408 Hex
6409 Hex
640A Hex
640B Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-436DD1987-1BA0 Edition 10.97
F: Too little memory available in the SAVE area.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @MSC initialization.A: Create available SAVE memory.EQ: ZF_ERR_NUM_MSC_N_MEM_SAVEEM: _MSC.CSFAM: @MSCAA: 7-Seg. ‘C’;
F: Too little memory for the message sequencing buffer.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @MSC initialization.A: Create available memory.EQ: ZF_ERR_NUM_MSC_N_MEM_MFPEM: _MSC.CSFAM: @MSCAA: 7-Seg. ’C’;
F: Connector SAV of the @MSC can’t be changed online.R: Abort the @MSC initialization.A: Set connector SAV to initial value.
Changes only in the configuring.EQ: ZF_ERR_NUM_MSC_INV_PROJEM: _MSC.CSFAM: @MSCAA: 7-Seg. ’C’;
F: No memory for the entry description system error.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @MSC initialization.A: Create available SAVE memory.EQ: ZF_ERR_NUM_MSC_N_MEM_EB_CEM: _MSC.CSFAM: _MSC.CSFAA: 7-Seg. ’C’;
not utilized.
F: No memory in RAM area for static intermediate buffer.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @MSC initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_MSC_N_KOM_ERROREM: _MSC.CSFAM: _MSC.CSFAA: 7-Seg. ’C’;
F: No message evaluation blocks configured.R: Abort the @MSC normal mode.A: Configure function blocks MSI.EQ: ZF_ERR_NUM_MSC_N_MAEM: _MSC.CSFAM: _MSC.CSFAA: 7-Seg. ’C’;
640C Hex
640D Hex
640E Hex
640F Hex
6410 Hex
6411 Hex
6412 Hex
Communication Error Codes
3-44 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Faulty operating status communication error evaluation.R: Abort the @MSC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSC_MZC_ERREM: _MSC.CSFAM: _MSC.CSFAA: 7-Seg. ’C’;
F: Faulty operating status.R: Abort the @MSC normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_MSC_BZS_ERREM: _MSC.CSFAM: _MSC.CSFAA: 7-Seg. ’C’;
F: Global list KDR not found.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the ME initialization.A: Contact Siemens AG.EQ: ZF_ERR_NUM_ME_N_KDREM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
F: No central block @MSC available.R: Abort the ME initialization.A: Configure central block @MSC.EQ: ZF_ERR_NUM_ME_N_MSCEM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
6413 Hex
6414 Hex
6415 Hex
6416 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-456DD1987-1BA0 Edition 10.97
F: Too little SAVE memory area for pointer.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the ME initialization.A: Create available SAVE memory.EQ: ZF_ERR_NUM_ME_N_MEM_SAVEEM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
F: Too little SAVE memory for insertion description.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the ME initialization.A: Create available SAVE memory.EQ: ZF_ERR_NUM_ME_N_MEM_FBEM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
F: Too little RAM memory for the static intermediate buffer.Exact cause see section Error Supplementary Code
bsspvw_info.R: Abort the ME initialization.A: Create available RAM memory.EQ: ZF_ERR_NUM_ME_N_MEM_SPEM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
not utilized.
6417 Hex
6418 Hex
6419 Hex
641A Hex to 641FHex
Communication Error Codes
3-46 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Faulty operating status.R: Abort the ME normal mode.A: Contact Siemens AG.EQ: ZF_ERR_NUM_ME_BZS_ERREM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAM: MES.CSF, MES2.CSF, MES4.CSF, MES16.CSF,MED.CSF, MED2.CSF, MED4.CSF,
MED16.CSF, MEDF.CSF, MESV2.CSF, MEDV2.CSF,MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
F: Faulty return value of a zdms function.R: Abort the block.A: Contact Siemens AG.EQ: ZF_ERR_NUM_ZDMS_FRW_ERREM: _MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF,MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF,
MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF,MEDV2.CSF, MESV4.CSF, MEDV4.CSFAM: _MSC.CSF, MSI.CSF, MES.CSF, MES2.CSF,MES4.CSF, MES16.CSF, MED.CSF, MED2.CSF,
MED4.CSF, MED16.CSF, MEDF.CSF, MESV2.CSF,MEDV2.CSF, MESV4.CSF, MEDV4.CSFAA: 7-Seg. ’C’;
3.2.7 Trace (Equipment Trace, Simple Trace, Analog Trace)
F: RAM memory assigning for reference list not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the block initialization.A: Restrict the memory area to the local RAM;
Reduce configured value of the NTV connector.EQ: Z_ERR_NUM_TC_INI_NO_RAM_1EM: ZDTR.CSFAM: @TCI , @TCPAA: 7-Seg. ’C’; YTS
F: RAM memory assigning for the trace buffer not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the control block initialization.A: Restrict the memory area to the local RAM;
Reduce configured value of the TBL connector.EQ: Z_ERR_NUM_TC_INI_NO_RAM_2EM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
6420 Hex
6421 Hex
6500 Hex
6501 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-476DD1987-1BA0 Edition 10.97
F: SAVE memory assigning for reference list not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the control block initialization.A: Restrict the memory area to the local SAVE area;
Reduce configured value of the NTV connector.EQ: Z_ERR_NUM_TC_INI_NO_SAVE_1EM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: SAVE memory assigning for the trace buffer not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the @ control block initialization.A: Restrict the memory area to the local SAVE area;
Reduce configured value of the TBL connector.EQ: Z_ERR_NUM_TC_INI_NO_SAVE_2EM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: RAM memory assigning for channel VARANM area not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the control block initialization.A: Restrict the memory area to the local RAM.EQ: Z_ERR_NUM_TC_INI_NO_RAM_3EM: ZDTR.CSF, _TCI.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: RAM memory assigning for channel buffer area not possible.Exact cause see section Error Supplementary Code
bsspvw_geme.R: Abort the control block initialization.A: Restrict the memory area to the local RAM.
Reduce configured value of the NTV connector.EQ: Z_ERR_NUM_TC_INI_NO_RAM_4EM: ZDTR.CSF, _TCI.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
is not utilized.F: Configured value at TBL connector is equal to zero.
R: Abort the control block initialization.A: Configure value not equal to zero at the TBL connector.EQ: Z_ERR_NUM_TC_INI_BAD_TBLEM: ZDTR.CSF, TRCC2.CSFAM: @TCI, @TCP, TRCC2AA: 7-Seg. ’C’; YTS.
F: TRC ID at the control block multiply exists.R: Abort the control block initialization.A: Select new unique TRC ID.EQ: Z_ERR_NUM_TC_INI_TC_DUPEM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
6502 Hex
6503 Hex
6504 Hex
6505 Hex
6506 Hex6507 Hex
6508 Hex
Communication Error Codes
3-48 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Global KDR list not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: Abort the control block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_NO_KDREM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: Global KOMM_ERROR list not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: Abort the control block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_NO_KOMEM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ‘C’; YTS.
F: KOMDAT area of the request channel was not correctlyinitialized.
Exact cause of error see section Error SupplementaryCode zbin_komdat.R: Abort the control block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_NO_KDB_1EM: ZDTR.CSFAM: @TCI.CSFAA: 7-Seg. ‘C’; YTS.
F: KOMDAT area of the reply channel was not correctly initialized.Exact cause of error see section Error Supplementary
Code zbin_komdat.R: Abort the control block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_NO_KDB_2EM: TCI.CSF, ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: SAVE area full.R: Abort the control block initialization.A: Restrict the memory area in the local SAVE area.EQ: Z_ERR_NUM_TC_INI_NO_SAVE_3EM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS
F: List of the SAVE area not available.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: Abort the control block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_NO_SAVE_4EM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
is not utilized.
6509 Hex
650A Hex
650B Hex
650C Hex
650D Hex
650E Hex
650F Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-496DD1987-1BA0 Edition 10.97
F: Error during channel access to request channel.Exact cause of error see section Data Interface Access
Mechanisms.R: @TCI reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_ZP_CHA_INEM: _TCI.CSFAM: @TCIAA: 7-Seg. ’C’; YTS.
F: Error during channel access to reply channel.Exact cause of error see section Data Interface Access
Mechanisms.R: @TCI reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_ZP_CHA_OUTEM: ZDTR.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: No acquisition block has been initialized.R: Acquisition block reverts to the dead status.A: Configure acquisition block with corresponding TRC ID.EQ: Z_ERR_NUM_TC_ZP_NO_TRIEM: _TCI.CSF, _TCP.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
F: Unknown connector format to be recorded.R: Block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_BAD_FORMATEM: TRCC2.CSFAM: TRCC2AA: 7-Seg. ’C’; YTS.
are not utilized.
F: Global KDR list does not exist.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: Abort the acquisition block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TR_INI_NO_KDREM: ZDTR.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
is not utilized.F: Multiple configuring of the same acquisition block in the same
task.R: Abort the acquisition block initialization.A: Re-configure.EQ: Z_ERR_NUM_TR_INI_NO_TCIEM: ZDTR.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ‘C’; YTS.
6510 Hex
6511 Hex
6512 Hex
6513 Hex
6514 Hex to 651FHex6520 Hex
6521 Hex6522 Hex
Communication Error Codes
3-50 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: List of the SAVE area does not exist.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: Abort the acquisition block initialization.A: Contact Siemens AG.EQ: Z_ERR_NUM_TR_INI_NO_SAVE_1EM: ZDTR.CSF, TRCC2.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: SAVE area full.R: Abort the acquisition block initialization.A: Reduce memory requirements in the local SAVE area.EQ: Z_ERR_NUM_TR_INI_NO_SAVE_2EM: ZDTR.CSF, TRCC2AM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: SAVE memory assigning for reference list body not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Abort the acquisition block initialization.A: Reduce memory requirements in the local SAVE area.EQ: Z_ERR_NUM_TR_INI_NO_SAVE_3EM: ZDTR.CSF, TRCC2.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: SAVE memory assigning for trace value list not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Abort the acquisition block initialization.A: Reduce memory requirements in the local SAVE area;
Reduce configured value at the NTV connector of thecorresponding @TCI.EQ: Z_ERR_NUM_TR_INI_SAVE_4EM: ZDTR.CSF, TRCC2.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: RAM memory assigning for reference list body not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Abort the acquisition block initialization.A: Reduce memory requirements in the local RAM area.EQ: Z_ERR_NUM_TR_INI_NO_RAM_1EM: ZDTR.CSF, TRCC.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
6523 Hex
6524 Hex
6525 Hex
6526 Hex
6527 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-516DD1987-1BA0 Edition 10.97
F: RAM memory assigning for trace value list not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: Abort the acquisition block initialization.A: Reduce memory requirements in the local RAM area;
Reduce configured value at the NTV connector of thecorresponding @TCI.EQ: Z_ERR_NUM_TR_INI_NO_RAM_2EM: ZDTR.CSF, TRCC.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: No control block with corresponding TRC ID initialized.R: Abort the acquisition block initialization.A: Configure control block with corresponding TRC ID.EQ: Z_ERR_NUM_TR_INI_UNKWN_TRCEM: ZDTR.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
F: Connector ID not uniquely selected.R: Abort the acquisition block initialization.A: Utilize unique connector ID at the acquisition block.EQ: Z_ERR_NUM_TR_INI_DUP_CIDEM: TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSFAM: TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
are not utilized.
F: Unknown block status for control block.R: Control block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_ZP_BAD_BZSEM: _TCI.CSF, _TCP.CSF, TRCC2.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPF, TRCC2AA: 7-Seg. ’C’; YTS.
F: Ring buffer size too small.R: Control block reverts to the dead status.A: Enlarge trace buffer / configure fewer acquisition blocks.EQ: Z_ERR_NUM_TR_ZP_SM_UMPUFEM: _TCP.CSFAM: @TCPAA: 7-Seg. ’C’; YTS.
F: Sampling time for the control block cannot be determined.R: Control block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TC_INI_BAD_TIMEEM: _TCI.CSF, _TCP.CSFAM: @TCI, @TCPAA: 7-Seg. ’C’; YTS.
6528 Hex
6529 Hex
652A Hex
652B Hex to 653FHex6540 Hex
6541 Hex
6542 Hex
Communication Error Codes
3-52 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Sampling time for the acquisition block cannot be determined.R: Acquisition block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TR_INI_BAD_TIMEEM: _TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF,TRPF.CSFAM: @TRI , TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
F: Unknown block status for acquisition block.R: Acquisition block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TR_ZP_BAD_BZS_EM: _TRI.CSF, TRP1.CSF, TRP2.CSF, TRP4.CSF,TRPF.CSFAM: @TRI, TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
F: Information function of the operating system could not beinvoked.R: Acquisition block reverts to the dead status.A: Contact Siemens AG.EQ: Z_ERR_NUM_TR_INI_BAD_AFPIEM: TRP1.CSF, TRP2.CSF, TRP4.CSF, TRPF.CSFAM: TRP1, TRP2, TRP4, TRPFAA: 7-Seg. ’C’; YTS.
F: Invalid value at the HIA of TRHIR: TRHI reverts to the dead status.A: Configure a value between 0 and 10 at the connectorHIA of the TRHI.EQ: Z_ERR_NUM_TR_INI_PARAM_ANZEM: TRHI.CSFAM: TRHIAA: 7-Seg. ’C’; YTS.
F: TRHI block multiply configured.R: TRHI reverts to the dead status.A: Configure only one TRHI per trace system.EQ: Z_ERR_NUM_TR_INI_MEHREM: TRHI.CSFAM: TRHIAA: 7-Seg. ’C’; YTS.
F: Channel length at the group telegram has been configured toosmall.R: @TCP reverts to the dead status.A: Select a larger connector CHA of the @TCP. Theminimum number is located at the supplement of thecommunication error message.EQ: Z_ERR_NUM_TC_ZP_CHAEM: _TCP.CSFAM: @TCPAA: 7-Seg. ’C’; YTS.
6543 Hex
6544 Hex
6545 Hex
6546 Hex
6547 Hex
6548 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-536DD1987-1BA0 Edition 10.97
F: Too many acquisition blocks at the group telegram output.R: @TCP reverts to the dead status.A: Configure fewer than 256 acquisition blocks
(TRP1,TRP2,TRP4,TRPF).EQ: Z_ERR_NUM_TC_TRP_ANZEM: _TCP.CSFAM: @TCPAA: 7-Seg. ’C’; YTS.
F: Length of the output channel is less than 200 bytes.R: Block reverts to the dead status.A: Set the output channel size (connector CHA) to at least200.EQ: Z_ERR_NUM_CHA_OUT_LENEM: ZDTR.CSFAM: @TCP, @TCIAA: 7-Seg. ’C’; YTS.
not utilized.
3.2.8 Time
F: The board name at the TM connector refers to a board that doesnot exist in the rack or cannot function as a time source.R: RTCM reverts to the dead status.A: Enter the name of a board that can act as a time source:
- Master Processor Board,- CSH11,- MM3,- SS5,- CS21.
EQ: ZF_ERR_NUM_RTCM_SZQ_N_VALIDEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
not utilized.F: Unknown operating status of the RTCM block.
R: RTCM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_RTCM_BZS_ERREM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: Memory assigning for the local structures not possible.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: RTCM reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_RTCM_N_MEMEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
6549 Hex
654A Hex
654B Hex to 657FHex
6600 Hex
6601 Hex6602 Hex
6603 Hex
Communication Error Codes
3-54 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Several RTCM blocks were configured in the same rack.R: RTCM reverts to the dead status.A: Remove one of the configured RTCM blocks.EQ: ZF_ERR_NUM_RTCM_MEHR_PROJEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: A SS5 import board (at the TM connector) and a SS5 exportboard
(at the TTM connector) are simultaneously configured.R: RTCM reverts to the dead status.A: Another clock source must be configured at the TMconnector;
The name of the SS5 export board at the TTM connectormust be removed.EQ: ZF_ERR_NUM_RTCM_CSL2F_PROJEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: PN local KDR list not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: RTCM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_RTCM_N_KDREM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS
not utilized.F: The rack has no CBUS connection.
R: RTCM reverts to the dead status.A: Utilize rack with CBUS connection (i.e. SR8).EQ: ZF_ERR_NUM_RTCM_N_CBUSEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: RTCM block was configured with an impermissible sampling time(not between 128 ms and 512 ms).
R: RTCM reverts to the dead status.A: Configure the sampling time between 128 ms and 512ms.EQ: ZF_ERR_NUM_RTCM_ABTASTZEIT_ERREM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: The RTCM block is configured on a board that is not a master.R: RTCM reverts to the dead status.A: Configure RTCM block on a processor board (processor1) installed to the left.EQ: ZF_ERR_NUM_RTCM_N_MASTEREM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
6604 Hex
6605 Hex
6606 Hex
6607 Hex6608 Hex
6609 Hex
660A Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-556DD1987-1BA0 Edition 10.97
F: The clock specification at the connectors XYR, XMO, XDA, XHRand / or XMI are invalid.R: RTCM reverts to the dead status.A: Check specifications at the connectors XYR, XMO, XDA,XHR and XMI Permissible values are:
00 v XYR v 9901 v XMO v 1201 v XDA v 3100 v XHR v 2300 v XMI v 59
EQ: ZF_ERR_NUM_RTCM_STELL_N_VALIDEM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
F: Access to link memory unsuccessful.R: RTCM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_RTCM_BUS_ZUGR_ERREM: RTCM.CSFAM: RTCM.CSFAA: 7-Seg. ’C’; YTS.
3.2.8.1 Device
F: Incorrect assignments UP connectorR: @DPH reverts to a neutral stateA: Check specification at connector UP. Permissible values:1-3EQ: ZF_ERR_NUM_DPH_UPEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: Invalid combination UP and PHL connectorR: @DPH reverts to a neutral stateA: Check specifications at the UP and PHL connectors.Invalid combination:
PHL = 0 ( 3 word PIV interface )UP = 1 ( SINEC-L2-DP protocol )
EQ: ZF_ERR_NUM_DPH_UP_PHLEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: KDR list not foundR: @DPH reverts to a neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_DPH_NO_KDREM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRW ofSDB_FUNC_BSSPVW_INFO)
660B Hex
660C Hex
6700 Hex
6701 Hex
6702 Hex
Communication Error Codes
3-56 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Multiple configuring of central blocksR: @DPH reverts to a neutral stateA: Connector value PHS must differ on local processor foreach @DPH block.EQ: ZF_ERR_NUM_DPH_MEHR_PROJEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: No memory availableR: @DPH reverts to a neutral stateA: Reduce memory requirementEQ: ZF_ERR_NUM_DPH_NO_MEMEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRW ofSDB_FUNC_BSSPVW_GEME)
F: No parameter block DPI configuredR: @DPH reverts to a neutral stateA: Configure at least one block DPI with the sameconnector value PHSEQ: ZF_ERR_NUM_DPH_NO_DPIEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: Internal errorR: @DPH reverts to a neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_DPH_DPI_AKEM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: Internal errorR: @DPH reverts to a neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_DPH_INT_ERREM: _DPH.CSFAM: _DPH.CSFAA: 7-Seg. ’C’; YTS, KFF
F: KDR list not foundR: DPI reverts to a neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_DPI_NO_KDREM: DPI.CSFAM: DPI.CSFAA: 7-Seg. ’C’; YTS, KFF (Suppl. code = FRWSBD_FUNC_BSSPVW_INFO)
F: No central block @DPH configuredR: DPI reverts to a neutral stateA: Configure central block @DPH with the same connectorspecification PHSEQ: ZF_ERR_NUM_DPI_NO_DPHEM: DPI.CSFAM: DPI.CSFAA: 7-Seg. ’C’; YTS, KFF
6703 Hex
6704 Hex
6705 Hex
6706 Hex
6707 Hex
6710 Hex
6711 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-576DD1987-1BA0 Edition 10.97
F: Faulty cascade sequencingR: DPI reverts to a neutral stateA: A request was transferred from several parameter blocksDPI to the same central block. Check the cascadeconfiguring !EQ: ZF_ERR_NUM_DPI_IC_ERREM: DPI.CSFAM: DPI.CSFAA: 7-Seg. ’C’; YTS, KFF
F: Internal errorR: DPI reverts to a neutral stateA: Inform Siemens AG.EQ: ZF_ERR_NUM_DPI_INT_ERREM: DPI.CSFAM: DPI.CSFAA: 7-Seg. ’C’; YTS, KFF
F: Incorrect parameter ID at the PR connectorR: DPI does not generate requestA: Specify correct value at the connector PR. Permissiblevalues: 0-11EQ: ZF_ERR_NUM_DPI_REQ_PR_ERREM: DPI.CSFAM: DPI.CSFAA: QS1; YTS
F: Incorrect parameter number at the PN connectorR: DPI does not generate request.A: Specify correct value at the connector PN. Permissiblevalues: 0-2047EQ: ZF_ERR_NUM_DPI_REQ_PN_ERREM: DPI.CSFAM: DPI.CSFAA: QS1; YTS
F: Incorrect parameter index at the PI connectorR: DPI does not generate requestA: Specify correct value at the connector PI. Permissiblevalues: 0-254EQ: ZF_ERR_NUM_DPI_REQ_PI_ERREM: DPI.CSFAM: DPI.CSFAA: QS1; YTS
F: Double word request with PIV interface length of 3 words at the connector PR
R: DPI does not generate requestA: Configure correct word request at connector PREQ: ZF_ERR_NUM_DPI_PR_4_BYTE_ERREM: DPI.CSFAM: DPI.CSFAA: QS1; YTS
6712 Hex
6713 Hex
6714 Hex
6715 Hex
6716 Hex
6717 Hex
Communication Error Codes
3-58 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: No reply from the device within the TIME-OUT periodR: DPI has not received replyA: Increase TIME-OUT period (connector RCM) at thecentral block @DPH, check communication with the device.EQ: ZF_ERR_NUM_DPI_RES_TIME_OUT_ERREM: DPI.CSFAM: DPI.CSFAA: QS2; YTS
3.2.8.2 Download
F: Internal status error 1.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_BZSEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Internal status error 2.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ATG_STATEEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Internal status error 3.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ANT_STATEEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Internal status error 4.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_KON_STATEEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Internal status error 5.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_KOP_STATEEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Too little memory.R: Block LPN disables.A: Reduce application’s RAM requirements.EQ: ZF_ERR_NUM_LPN_NO_MEMEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
6718 Hex
6800 Hex
6801 Hex
6802 Hex
6803 Hex
6804 Hex
6805 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-596DD1987-1BA0 Edition 10.97
F: Multiple configuring of the block LPN.R: Block LPN disables.A: Only configure one LPN-FB per processor board.EQ: ZF_ERR_NUM_LPN_MULTEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: KDR list not foundR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_NO_KDREM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Job request channel continually faulty.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ATG_KANEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Job request initialization faultyR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ATG_KOMDAT_INITEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Job request initialization faulty.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ATG_KAN_INITEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Reply channel continually faulty.R: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ANT_KANEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Reply channel initialization faultyR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ANT_KOMDAT_INITEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
6806 Hex
6807 Hex
6808 Hex
6809 Hex
680A Hex
680B Hex
680C Hex
Communication Error Codes
3-60 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Reply channel initialization faultyR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_ANT_KAN_INITEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Unknown card typeR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_CARD_TYPE_ERREM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Internal card programming errorR: Block LPN disables.A: Inform Siemens AG..EQ: ZF_ERR_NUM_LPN_BSFC_FRW_ERREM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
F: Sub-task initialization not possibleR: Block LPN disables.A: Configure LPN-FB in a different sampling time.EQ: ZF_ERR_NUM_LPN_INI_SUB_TASKEM: LPN.CSFAM: LPN.CSFAA: QTS; YTS
3.2.9 Central Blocks for Links
3.2.9.1 Coupling Memory Link
F: Several @CMM blocks were configured with the same coupling memory board names.
R: @CMM reverts to the dead status.A: Remove one of the configured @CMM blocks.EQ: ZF_ERR_NUM_CMM_MEHR_PROJEM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_CIP_FREI_FRW_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
680D Hex
680E Hex
680F Hex
6810 Hex
6900 Hex
6901 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-616DD1987-1BA0 Edition 10.97
F: The CIP entry for the @CMM block cannot be accessed.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CMM block does not exist.R: @CMM reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CMM_NAM_N_KENNEM: ZBAK.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_SUCH_FRW_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_REOR_FRW_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CMM block.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_BZS_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for the warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CMM reverts to the dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CMM_SAVE_ZU_KURZEM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_SAVE_N_KENNEM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
6902 Hex
6903 Hex
6904 Hex
6905 Hex
6906 Hex
6907 Hex
6908 Hex
Communication Error Codes
3-62 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: @CMM block was configured in an impermissible sampling time(not between 32 ms and 255 ms).
R: @CMM reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CMM_ABTASTZEIT_ERREM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CMM reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CMM_EXC_ZU_KURZEM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the reorganization structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CMM reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CMM_REORG_ZU_KURZEM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_FB_INIT_FRW_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Link type in CIP entry is not set to ‘‘Coupling Memory Link’’.R: @CMM reverts to the dead status.A: Check the configured name at the CTS connector;
Check that the configured block type corresponds to@CMMEQ: ZF_ERR_NUM_CMM_KOP_TYP_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_ANM_FRW_ERREM: _CMM.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
6909 Hex
690A Hex
690B Hex
690C Hex
690D Hex
690E Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-636DD1987-1BA0 Edition 10.97
F: Unknown registered status determined in DEXDO3 management section.
R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CMM_ANM_STATUS_ERREM: ZP.CSFAM: _CMM.CSFAA: 7-Seg. ’C’
3.2.9.2 Rack Link
F: Several @CS11 blocks were configured with the same CS11board names.R: @CS11 reverts to the dead status.A: Remove one of the configured @CS11 blocksEQ: ZF_ERR_NUM_CS11_MEHR_PROJEM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_CIP_FREI_FRW_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CS11 block cannot be accessed.R: @CMM reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CS11 block does not exist.R: @CS11 reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CS11_NAM_N_KENNEM: ZBAK.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_SUCH_FRW_ERREM: ._CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
690F Hex
6910 Hex
6911 Hex
6912 Hex
6913 Hex
6914 Hex
Communication Error Codes
3-64 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_REOR_FRW_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CS11 blocks.R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_BZS_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for the warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS11 reverts to the dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CS11_SAVE_ZU_KURZEM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_SAVE_N_KENNEM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: @CS11 block was configured in a impermissible sampling time(not between 32 ms and 255 ms).
R: @CS11 reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CS11_ABTASTZEIT_ERREM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Memory assignment not possible for the exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS11 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CS11_EXC_ZU_KURZEM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
6915 Hex
6916 Hex
6917 Hex
6918 Hex
6919 Hex
691A Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-656DD1987-1BA0 Edition 10.97
F: Memory assigning not possible for the reorganization structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS11 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CS11_REORG_ZU_KURZEM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_FB_INIT_FRW_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Link type or sub-link type is not set to "CS11 rack link".R: @CS11 reverts to the neutral stateA: Check the configured name at the CTS connector;
The configured name at the CTS connector mustcorrespond to a CS11 boardEQ: ZF_ERR_NUM_CS11_KOP_TYP_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_ANM_FRW_ERREM: _CS11.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: Unknown registered status detected in DEXDO3 managementsection.R: @CS11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS11_ANM_STATUS_ERREM: ZP.CSFAM: _CS11.CSFAA: 7-Seg. ’C’
F: The configured name of the @CS21 block corresponds toanother in the link.R: @CS21 reverts to the dead status.A: Check, whether the name at the CTS connectorcorresponds to another CS21 block;
Check, whether the @CS21 block has been multiplyconfigured on the same CS21 board.EQ: ZF_ERR_NUM_CS21_MEHR_PROJEM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
691B Hex
691C Hex
691D Hex
691E Hex
691F Hex
6920 Hex
Communication Error Codes
3-66 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The CIP entry for the @CS21 block cannot be accessed.R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CS21 block does not exist.R: @CS21 reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CS21_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_CIP_SUCH_FRW_ERREM: ._CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
not utilized.F: There are already three registered @CS21 blocks in the link.
R: @CS21 reverts to the dead status.A: Power down rack and power up again after 10 seconds;
Check whether more than three CS21 boards exist onthe link;
Check whether the @CS21 block has been multiplyconfigured on the same CS21 board.EQ: ZF_ERR_NUM_CS21_SCHON_DREI_CS21EM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: The configured CS11 board does not exist.R: @CS21 reverts to the dead status.A: Check the configured CS11 name at the MTS connector.EQ: ZF_ERR_NUM_CS21_CS11_N_KENNEM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _cs21_anmeldung.R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_ANM_FRW_ERREM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CS21 block.R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_BZS_ERREM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
6921 Hex
6922 Hex
6923 Hex
6924 Hex6925 Hex
6926 Hex
6927 Hex
6928 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-676DD1987-1BA0 Edition 10.97
F: SAVE memory assigning not possible for the warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_gemeR: @CS21 reverts to the dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CS21_SAVE_ZU_KURZEM: ZP.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_infoR: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_SAVE_N_KENNEM: ZP.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: @CS21 block was configured in an impermissible sampling time(not between 32 ms and 255 ms).
R: @CS21 reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CS21_ABTASTZEIT_ERREM: ZP.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS21 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CS21_EXC_ZU_KURZEM: ZP.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS21 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CS21_REORG_ZU_KURZEM: ZP.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_FB_INIT_FRW_ERREM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
not utilized.
6929 Hex
692A Hex
692B Hex
692C Hex
692D Hex
692E Hex
692F Hex to 6931Hex
Communication Error Codes
3-68 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Link type or sub-link type is not set to "CS11 rack link".R: @CS21 reverts to the neutral stateA: Check the configured name at the CTS connector;
The configured name at the CTS connector mustcorrespond to a CS21 boardEQ: ZF_ERR_NUM_CS21_KOP_TYP_ERREM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
F: The software version on the processor board is not compatiblewith the version in the CS11 rack.
R: @CS21 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CS21_VERSION_ERREM: _CS21.CSFAM: _CS21.CSFAA: 7-Seg. ’C’
not utilized.
3.2.9.3 PN Local Link
F: The @CPN block was multiply configured on the same processorboard.
R: @CPN reverts to the dead status.A: Remove one of the configured @CPN blocks.EQ: ZF_ERR_NUM_CPN_MEHR_PROJEM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_CIP_FREI_FRW_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CPN block cannot be accessed,since it is pointing to another processor board.
R: @CPN reverts to the dead status.A: Board name at the CTS connector must correspond to
the name of the processor board.EQ: ZF_ERR_NUM_CPN_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CPN block does not exist.R: @CPN reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CPN_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
6932 Hex
6933 Hex
6934 Hex to 693FHex
6940 Hex
6941 Hex
6942 Hex
6943 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-696DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zbak_cip_suche.R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_CIP_SUCH_FRW_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_REOR_FRW_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CPN block.R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_BZS_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CPN reverts to dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CPN_SAVE_ZU_KURZEM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_info.R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_SAVE_N_KENNEM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: @CPN block was configured in an impermissible sampling time(not between 32 ms and 255 ms)
R: @CPN reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CPN_ABTASTZEIT_ERREM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
6944 Hex
6945 Hex
6946 Hex
6947 Hex
6948 Hex
6949 Hex
Communication Error Codes
3-70 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Memory assigning not possible for exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS21 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CPN_EXC_ZU_KURZEM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS21 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CPN_REORG_ZU_KURZEM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CPN reverts to the dead status.A: Contact Siemens AGEQ: ZF_ERR_NUM_CPN_FB_INIT_FRW_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Link type is not set to ‘‘PN Local Link’’.R: @CS21 reverts to the dead statusA: Check the configured name at the CTS connector;
Check that the configured block type corresponds [email protected]: ZF_ERR_NUM_CPN_KOP_TYP_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_ANM_FRW_ERREM: _CPN.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in the DEXDO3 management section.
R: @CPN reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CPN_ANM_STATUS_ERREM: ZP.CSFAM: _CPN.CSFAA: 7-Seg. ’C’
694A Hex
694B Hex
694C Hex
694D Hex
694E Hex
694F Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-716DD1987-1BA0 Edition 10.97
3.2.9.4 Link DUST1
F: Specification at the TWU connector faulty.R: @CSD01 reverts to the dead status.A: Set specifications at the TWU connector to only decimalvalues be tween 0 and 1000.EQ: ZF_ERR_NUM_CSD1_TWU_ERREM: _CSD01.CSFAM: _CSD01.CSFAA: 7-Seg. ’C’
F: Specification at the BDR connector faulty.R: @CSD01 reverts to the dead status.A: The specification at the BDR connector can only
correspond to one of the following baud rates:300, 600, 1200, 2400, 4800, 9600, 19200
EQ: ZF_ERR_NUM_CSD1_BDR_ERREM: _CSD01.CSFAM: _CSD01.CSFAA: 7-Seg. ’C’
not utilized.
3.2.9.5 Link SINEC H1
F: Several @CSH11 blocks were configured with the same CSH11board names.R: @CSH11 reverts to the dead status.A: Remove one of the configured @CSH11 blocks.EQ: ZF_ERR_NUM_CSH1_MEHR_PROJEM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_CIP_FREI_FRW_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSH11 block cannot be accessed.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSH11 block does not exist.R: @CSH11 reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CSH1_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
6965 Hex
6966 Hex
6969 Hex to 6996Hex
6970 Hex
6971 Hex
6972 Hex
6973 Hex
Communication Error Codes
3-72 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return values of the function zbak_cip_suche.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_CIP_SUCH_FRW_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return values of the function zp_dexdo_reorganization.
R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_REOR_FRW_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CSH11 block.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_BZS_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CSH11 reverts to dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CSH1_SAVE_ZU_KURZEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_infoR: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_SAVE_N_KENNEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: @CSH11 block was configured in an impermissible samplingtime
(not between 32 ms and 255 ms)R: @CSH11 reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CSH1_ABTASTZEIT_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
6974 Hex
6975 Hex
6976 Hex
6977 Hex
6978 Hex
6979 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-736DD1987-1BA0 Edition 10.97
F: Memory assigning not possible for the exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CSH11 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSH1_EXC_ZU_KURZEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CS21 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSH1_REORG_ZU_KURZEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_FB_INIT_FRW_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Link type not set to ‘‘CSH11 Link’’.R: @CSH11 reverts to the dead status.A: Check the configured name at the CTS connector;
Check that the block type corresponds to @CSH11.EQ: ZF_ERR_NUM_CSH1_KOP_TYP_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_ANM_FRW_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_ANM_STATUS_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
697A Hex
697B Hex
697C Hex
697D Hex
697E Hex
697F Hex
Communication Error Codes
3-74 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: CSH11 firmware has detected an unrepairable error.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_INI_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: CSH11 firmware has reverted to an error status.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_TOTEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown status of the CSH11 firmware.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_ZUS_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_FIRM_ZYK_FRW_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Length of the specified address at the MAA connector is false.R: @CSH11 reverts to the dead status.A: Specification at the MAA connector must be exactly 12characters long.EQ: ZF_ERR_NUM_CSH1_STRING_LEN_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Specification at the MMA connector faulty.R: @CSH11 reverts to the dead status.A: The address at the MAA connector must correspond to ahexa decimal number, i.e. only numbers 0, 1, 2, 3, 4, 5, 6, 7, 8,9 and letters a, b, c, d, e, f are permitted.EQ: ZF_ERR_NUM_CSH1_STRING_ERREM: _CSH11.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the firmware structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CSH11 reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSH1_N_MEMEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
6980 Hex
6981 Hex
6982 Hex
6983 Hex
6984 Hex
6985 Hex
6986 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-756DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function _csh11_init.R: @CSH11 reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSH1_INI_FRW_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function_csh11_firmware_init.R: @CSH11 reverts to the dead status.A: Contact Siemens AGEQ: ZF_ERR_NUM_CSH1_FIR_INIT_FRW_ERREM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
not utilized.
3.2.9.6 Allgemeine Zentral-Funktionsbaustein-Fehlerkennung
F: Several communications central blocks were configuredwith the same CS7 board names or interface name.
R: @CSxyz reverts to the dead status.A: Remove one of the configured @CSxyz blocksEQ: ZF_ERR_NUM_CL2F_MEHR_PROJEM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown return function of the function zp_cip_freigabe.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_CIP_FREI_FRW_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSxyz block cannot be accessed.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSxyz block does not exist.R: @CSxyz reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CL2F_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
6987 Hex
6988 Hex
6989 Hex to 698FHex
6990 Hex
6991 Hex
6992 Hex
6993 Hex
Communication Error Codes
3-76 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zbak_cip_suche.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_CIP_SUCH_FRW_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_REOR_FRW_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CSxyz block.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_BZS_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CSxyz reverts to dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CSH1_SAVE_ZU_KURZEM: ZP.CSFAM: _CSH11.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error Supplementary
Code bsspvw_infoR: @CSxyz reverts to the dead status.A: Contact Siemens AGEQ: ZF_ERR_NUM_CL2F_SAVE_N_KENNEM: ZP.CSFAM: _CSxyz.CSF
F: @CSxyz block was configured in an impermissible samplingtime
(not between 32 ms and 255 ms)R: @CSxyz reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CL2F_ABTASTZEIT_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
6994 Hex
6995 Hex
6996 Hex
6997 Hex
6998 Hex
6999 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-776DD1987-1BA0 Edition 10.97
F: Memory assigning not possible for the exception structure.R: @CSxyz reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CL2F_EXC_ZU_KURZEM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the reorganization structure.R: @CSxyz reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CL2F_REORG_ZU_KURZEM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown function return value for the function zp_fb_init.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_FB_INIT_FRW_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Link type is not set to ‘‘CSL2x Link’’.R: @CSxyz reverts to the dead status.A: Check the configure name at the CTS connector;
Check that the block type corresponds to @CSxyz.EQ: ZF_ERR_NUM_CL2F_KOP_TYP_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown function return value for the function zp_anmelde_ueberwachung.
R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_ANM_FRW_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_ANM_STATUS_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: CSL2x firmware has detected an unrepairable error.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_INIT_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
699A Hex
699B Hex
699C Hex
699D Hex
699E Hex
699F Hex
69A0 Hex
Communication Error Codes
3-78 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: CSL2x firmware has reverted to an error status or SS5x moduleinsert is missing.R: @CSxyz reverts to the dead status.A: SS5x module in the CS7 board;
Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_TOTEM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown status of the CSL2x firmware.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_ZUS_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_FIRM_ZYK_FRW_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Station address false at the MAA connector.R: @CSxyz reverts to the dead status.A: The specification at the MAA connector must correspondto a
number between 1 and 126. (@CSL2A: between 1 and123)EQ: ZF_ERR_NUM_CL2F_STAT_ADR_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
not utilized.F: Memory assigning not possible for the firmware structure.
Exact cause of error see section Error SupplementaryCode bsspvw_gemeR: @CSxyz reverts to the dead status.A: Reduce the RAM requirement of the application.EQ: ZF_ERR_NUM_CL2F_N_MEMEM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _csl2f_init.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_INIT_FRW_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
69A1 Hex
69A2 Hex
69A3 Hex
69A4 Hex
69A5 Hex69A6 Hex
69A7 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-796DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function_csl2f_firmware_init.R: @CSxyz reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CL2F_FIR_INIT_FRW_ERREM: ZP.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Specification of the BDR connector faulty.R: @CSxyz reverts to the dead status.A: The coded baud rate at the BDR connector mustcorrespond to
a number between 0 and 5 (@CSL2A: between 0 and 8).EQ: ZF_ERR_NUM_CL2F_BDR_ERREM: _CSxyz.CSFAM: _CSxyz.CSFAA: 7-Seg. ’C’
F: Specification of the AST connector faulty.R: @CSL2L reverts to the dead status.A: The value at the BDR connector must correspond to
a number between 0 and 126.EQ: ZF_ERR_NUM_CL2L_AST_ERREM: _CSL2L.CSFAM: _CSL2L.CSFAA: 7-Seg. ’C’
F: Projektierungsfehler Eingang LTTR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Eingang LTT korrigierenEQ: ZF_ERR_NUM_STD_KON_LTTEM: _peer.csfAM: _peer.csfF: Projektierungsfehler Eingang LTRR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Eingang LTR korrigierenEQ: ZF_ERR_NUM_STD_KON_LTREM: _peer.csfAM: _peer.csfF: Projektierungsfehler Anschluss CTSR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Anschluss CTS korrigieren (X01, X02 beachten)EQ: ZF_ERR_NUM_STD_KON_CTSEM: _peer.csf, _uss_s/mAM: _peer.csf, _uss_s/mF: Fehler bei Kommunikationsinitialisierung („ZINI-Eintrag“)R: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Siemens AG benachrichtigenEQ: ZF_ERR_NUM_STD_FRW_ZINIEM: diverseAM: diverse
Zusatzcode: Rückgabewert der Funktion zg_zini_Nachtrag
69A8 Hex
69A9 Hex
69AA Hex
69AB Hex
69AC Hex
69AD Hex
69AE Hex
Communication Error Codes
3-80 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Fehler bei SpeicherbeschaffungR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Projektierung verkleinernEQ: ZF_ERR_NUM_STD_FRW_GEMEEM: diverseAM: diverse
Zusatzcode: Rückgabewert der Funktion bsspvw_gemeF: Schnitstelle X01/X02 ist belegtR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Nur eine Kopplung pro Schnittstelle projektierenEQ: ZF_ERR_NUM_STD_SST_BELEGTEM: _peer.csf, _uss_s/mAM: _peer.csf, _uss_s/mF: Projektierungsfehler Eingang BDRR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Eingang BDR korrigierenEQ: ZF_ERR_NUM_STD_KON_BDREM: _peer.csf, _uss_s/mAM: _peer.csf, _uss_s/mF: Projektierungsfehler Eingang MAAR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Eingang MAA korrigierenEQ: ZF_ERR_NUM_STD_KON_MAAEM: _uss_sAM: _uss_sF: Projektierungsfehler Eingang PZDR: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Eingang PZD korrigierenEQ: ZF_ERR_NUM_STD_KON_PZDEM: _uss_sAM: _uss_sF: Schnitstelle X01 nicht für USS freigegebenR: USS wird nicht gestartet, es läuft Service auf X01A: Schalter S1/8 auf T400 auf ON stellenEQ: ZF_ERR_NUM_STD_SST_SPERR_X01EM: _uss_s/mAM: _uss_s/mF: Zwei USS-Kopplungen auf T400R: Baustein schaltet sich ab, Eintrag ins KommunikationsfehlerfeldA: Nur eine USS-Kopplung auf T400 projektierenEQ: ZF_ERR_NUM_STD_USS_DOPPELTEM: _uss_s/mAM: _uss_s/mF: Empfangene Telegrammlänge passt nicht zur projektierten
LängeR: Telegramm wird verworfenA: Telegrammlänge des Kommunikationspartners mit projektierter
Länge abgleichen(USS-Slave: Eingänge PAR, PZD; USS-Master: Anzahl virtueller
Verbindungen)EQ: ZF_ERR_NUM_STD_TEL_LEN_EMPFEM: _uss_s/mAM: _uss_s/m
69AF Hex
69B0 Hex
69B1 Hex
69B2 Hex
69B3 Hex
69B4 Hex
69B5 Hex
69B6 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-816DD1987-1BA0 Edition 10.97
3.2.9.7 EP Link
F: Several @CEP22 resp. @CEP blocks have been configured withthe same EP22 board name.R: @CEP22 resp. @CEP reverts to the dead status.A: Remove one of the configured @CEP22 resp. @CEPblocks.EQ: ZF_ERR_NUM_EP22_MEHR_PROJEM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_CIP_FREI_FRW_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CEP22 resp. @CEP block cannot be accessed.
R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CEP22 resp. @CEP block does notexist.R: @CEP22 resp. @CEP reverts to the dead status.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_EP22_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_CIP_SUCH_FRW_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_REOR_FRW_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
69D0 Hex
69D1 Hex
69D2 Hex
69D3 Hex
69D4 Hex
69D5 Hex
Communication Error Codes
3-82 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown operating status of the @CEP22 resp. @CEP block.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_BZS_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for the warm start flag.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CEP22 resp. @CEP reverts to the dead status.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_EP22_SAVE_ZU_KURZEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: SAVE are not found.Exact cause of error see section Error Supplementary
Code bsspvw_infoR: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_SAVE_N_KENNEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: @CEP22 resp. @CEP block was configured in an impermissible sampling time (not between 32 ms and 255 ms).
R: @CEP22 resp. @CEP reverts to the dead status.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_EP22_ABTASTZEIT_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the exception structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CEP22 resp. @CEP reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_EP22_EXC_ZU_KURZEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for the reorganization structure.Exact cause of error see section Error Supplementary
Code sspvw_geme.R: @CEP22 resp. @CEP reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_EP22_REORG_ZU_KURZEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
69D6 Hex
69D7 Hex
69D8 Hex
69D9 Hex
69DA Hex
69DB Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-836DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_fb_init.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_FB_INIT_FRW_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Link type in the CIP entry is not set to ‘‘Coupling Memory Link’’.R: @CEP22 resp. @CEP reverts to the dead status.A: Check the configured name at the CTS connector;
Check that the configured block type corresponds to@CEP22 resp. @CEP.EQ: ZF_ERR_NUM_EP22_KOP_TYP_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_ANM_FRW_ERREM: _CEP22.CSF resp. _CEP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_ANM_STATUS_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: CEP22 firmware has detected an unrepairable error.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_INIT_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: CEP22 firmware has reverted to an error status.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_TOTEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown status of the CEP22 firmware.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_ZUS_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
69DC Hex
69DD Hex
69DE Hex
69DF Hex
69E0 Hex
69E1 Hex
69E2 Hex
Communication Error Codes
3-84 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_FIRM_ZYK_FRW_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
not utilized.
F: Memory assigning not possible for the firmware structure.Exact cause of error see section Error Supplementary
Code bsspvw_geme.R: @CEP22 resp. @CEP reverts to the dead status.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_EP22_N_MEMEM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _CEP22_init resp. _CEP_init.
R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_INIT_FRW_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function_CEP22_firmware_init.R: @CEP22 resp. @CEP reverts to the dead status.A: Contact Siemens AG.EQ: ZF_ERR_NUM_EP22_FIR_INIT_FRW_ERREM: ZP.CSFAM: _CEP22.CSF resp. _CEP.CSFAA: 7-Seg. ’C’
not utilized.
3.2.9.8 Link DUST7
F: Several communication central blocks were configured with thesame
CS7 board names or interface names.R: @CSD07 reverts to the dead state.A: Remove one of the configured @CSD07 blocks;
Correct the interface specification of one @CSD07block.EQ: ZF_ERR_NUM_CSD7_MEHR_PROJEM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
69E3 Hex
69E4 Hex to 69E5Hex69E6 Hex
69E7 Hex
69E8 Hex
69E9 Hex to 69EFHex
69F0 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-856DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_cip_freigabe.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_CIP_FREI_FRW_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD07 block is not accessible.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD07 block does not exist.R: @CSD07 reverts to the dead state.A: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CSD7_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_CIP_SUCH_FRW_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_REOR_FRW_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown operating status of the @CSD07 block.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_BZS_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flagExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD07 reverts to the dead state.A: Reduce the SAVE requirement in the applicationEQ: ZF_ERR_NUM_CSD7_SAVE_ZU_KURZEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
69F1 Hex
69F2 Hex
69F3 Hex
69F4 Hex
69F5 Hex
69F6 Hex
69F7 Hex
Communication Error Codes
3-86 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: SAVE area not found.Exact cause of error see section Error supplementary
code bsspvw_info.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_SAVE_N_KENNEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: @CSD07 block configured in impermissible sampling time (not between 32ms and 255ms)
R: @CSD07 reverts to the dead state.A: Configure the sampling time between 32ms and 255msEQ: ZF_ERR_NUM_CSD7_ABTASTZEIT_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for exception structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD07 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD7_EXC_ZU_KURZEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD07 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD7_REORG_ZU_KURZEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_fb_init.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_FB_INIT_FRW_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Link type is not set to "DUST1" or "CS7".R: @CSD07 reverts to the dead state.A: Check the configured name at CTS connector;
Check that block type corresponds to @CSD07EQ: ZF_ERR_NUM_CSD7_KOP_TYP_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
69F8 Hex
69F9 Hex
69FA Hex
69FB Hex
69FC Hex
69FD Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-876DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_ANM_FRW_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_ANM_STATUS_ERREM: ZP.CSFAM: @CSD07AA: 7-Seg. ’C’
F: DUST1 firmware has detected an unrepairable error.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_DUST_INIT_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: DUST1 firmware has reverted to an error status or SS4 adapter module missing.
R: @CSD07 reverts to the dead state.A: Install SS4 module in CS7 board;A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_DUST_TOTEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown status of the DUST1 firmware.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_ZUS_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_FIRMWARE_ZYK_FRW_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
69FE Hex
69FF Hex
6A00 Hex
6A01 Hex
6A02 Hex
6A03 Hex
Communication Error Codes
3-88 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Memory assigning not possible for firmware structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD07 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD7_N_MEMEM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Specification at SPB connector faulty.R: @CSD07 reverts to the dead state.A: Specification at TWU connector can only be in range 0,1 or 2 .EQ: ZF_ERR_NUM_CSD7_SPB_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Specification at PAR connector faulty.R: @CSD07 reverts to the dead state.A: Specification at BDR connector can only be in range 0, 1or 2 .EQ: ZF_ERR_NUM_CSD7_PAR_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Specification at BDR connector faulty.R: @CSD07 reverts to the dead state.A: Specification at BDR connector can only correspond toone of the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200EQ: ZF_ERR_NUM_CSD7_BDR_ERREM: _CSD07.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _CSD7_init.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_INIT_FRW_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function_CSD7_firmware_init.R: @CSD07 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD7_FIR_INIT_FRW_ERREM: ZP.CSFAM: _CSD07.CSFAA: 7-Seg. ’C’
not utilized
6A04 Hex
6A05 Hex
6A06 Hex
6A07 Hex
6A08 Hex
6A09 Hex
6A0A Hex to 6A0FHex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-896DD1987-1BA0 Edition 10.97
3.2.9.9 Link DUST2
F: Several communication central blocks were configured with thesame
CS7 board names or interface names.R: @CSD02 reverts to the dead state.A: Remove one of the configured @CSD02 blocks;
Correct the interface specification of one @CSD02 blockEQ: ZF_ERR_NUM_CSD2_MEHR_PROJEM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_CIP_FREI_FRW_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD02 block is not accessible.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD02 block does not exist.R: @CSD02 reverts to the dead state.A: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CSD2_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_CIP_SUCH_FRW_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_REOR_FRW_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
6A10 Hex
6A11 Hex
6A12 Hex
6A13 Hex
6A14 Hex
6A15 Hex
Communication Error Codes
3-90 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown operating status of the @CSD02 block.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_BZS_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flagExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD02 reverts to the dead state.A: Reduce the SAVE requirement in the applicationEQ: ZF_ERR_NUM_CSD2_SAVE_ZU_KURZEM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error supplementary
code bsspvw_info.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_SAVE_N_KENNEM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: @CSD02 block configured in impermissible sampling time (not between 32ms and 255ms)
R: @CSD02 reverts to the dead state.A: Configure the sampling time between 32ms and 255msEQ: ZF_ERR_NUM_CSD2_ABTASTZEIT_ERREM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for exception structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD02 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD2_EXC_ZU_KURZEM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD02 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD2_REORG_ZU_KURZEM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
6A16 Hex
6A17 Hex
6A18 Hex
6A19 Hex
6A1A Hex
6A1B Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-916DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_fb_init.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_FB_INIT_FRW_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Link type is not set to "DUST1" or "CS7".R: @CSD02 reverts to the dead state.A: Check the configured name at CTS connector;
Check that block type corresponds to @CSD02EQ: ZF_ERR_NUM_CSD2_KOP_TYP_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_ANM_FRW_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_ANM_STATUS_ERREM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: DUST1 firmware has detected an unrepairable error.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_DUST_INIT_ERREM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: DUST1 firmware has reverted to an error status or SS4 adapter module missing.
R: @CSD02 reverts to the dead state.A: Install SS4 module in CS7 board;A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_DUST_TOTEM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown status of the DUST1 firmware.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_ZUS_ERREM: ZP.CSF,_CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
6A1C Hex
6A1D Hex
6A1E Hex
6A1F Hex
6A20 Hex
6A21 Hex
6A22 Hex
Communication Error Codes
3-92 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_FIRMWARE_ZYK_FRW_ERREM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for firmware structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD02 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD2_N_MEMEM: ZP.CSF,AM: _CSD02.CSFAA: 7-Seg. ’C’
F: Specification at PAR connector faulty.R: @CSD02 reverts to the dead state.A: Specification at TWU connector can only be in range 0to 1 .EQ: ZF_ERR_NUM_CSD2_TWU_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Specification at BDR connector faulty.R: @CSD02 reverts to the dead state.A: Specification at BDR connector can only correspond toone of the following baud rates:
300, 600, 1200, 2400, 4800, 9600, 19200EQ: ZF_ERR_NUM_CSD2_BDR_ERREM: _CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _csd2_init.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: Z_ERR_NUM_CSD2_INIT_FRW_ERREM: ZP.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
F: Unknown function return value of thefunction_csd2_firmware_init.R: @CSD02 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD2_FIR_INIT_FRW_ERREM: ZP.CSF,_CSD02.CSFAM: _CSD02.CSFAA: 7-Seg. ’C’
not utilized
6A23 Hex
6A24 Hex
6A25 Hex
6A26 Hex
6A27 Hex
6A28 Hex
6A29 Hex to 6A2FHex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-936DD1987-1BA0 Edition 10.97
3.2.9.10 Link DUST3
F: Several communication central blocks were configured with thesame
CS7 board names or interface names.R: @CSD03 reverts to the dead state.A: Remove one of the configured @CSD03 blocks;
Correct the interface specification of one @CSD03 blockEQ: ZF_ERR_NUM_CSD3_MEHR_PROJEM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_CIP_FREI_FRW_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD03 block is not accessible.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSD03 block does not exist.R: @CSD03 reverts to the dead state.A: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CSD3_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_CIP_SUCH_FRW_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_REOR_FRW_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
6A30 Hex
6A31 Hex
6A32 Hex
6A33 Hex
6A34 Hex
6A35 Hex
Communication Error Codes
3-94 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown operating status of the @CSD03 block.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_BZS_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flagExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD03 reverts to the dead state.A: Reduce the SAVE requirement in the applicationEQ: ZF_ERR_NUM_CSD3_SAVE_ZU_KURZEM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: SAVE area not found.Exact cause of error see section Error supplementary
code bsspvw_info.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_SAVE_N_KENNEM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: @CSD03 block configured in impermissible sampling time (not between 32ms and 255ms)
R: @CSD03 reverts to the dead state.A: Configure the sampling time between 32ms and 255msEQ: ZF_ERR_NUM_CSD3_ABTASTZEIT_ERREM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for exception structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD03 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD3_EXC_ZU_KURZEM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD03 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD3_REORG_ZU_KURZEM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
6A36 Hex
6A37 Hex
6A38 Hex
6A39 Hex
6A3A Hex
6A3B Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-956DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function zp_fb_init.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_FB_INIT_FRW_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Link type is not set to "DUST1" or "CS7".R: @CSD03 reverts to the dead state.A: Check the configured name at CTS connector;
Check that block type corresponds to @CSD03EQ: ZF_ERR_NUM_CSD3_KOP_TYP_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_anmelde_ueberwachung.
R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_ANM_FRW_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_ANM_STATUS_ERREM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: DUST1 firmware has detected an unrepairable error.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_DUST_INIT_ERREM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: DUST1 firmware has reverted to an error status or SS4 adapter module missing.
R: @CSD03 reverts to the dead state.A: Install SS4 module in CS7 board;A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_DUST_TOTEM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: UInknown status of the DUST1 firmware.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_ZUS_ERREM: ZP.CSF,_CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
6A3C Hex
6A3D Hex
6A3E Hex
6A3F Hex
6A40 Hex
6A41 Hex
6A42 Hex
Communication Error Codes
3-96 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_FIRMWARE_ZYK_FRW_ERREM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for firmware structureExact cause of error see section Error supplementary
code bsspvw_geme.R: @CSD03 reverts to the dead state.A: Reduce the RAM requirement in the applicationEQ: ZF_ERR_NUM_CSD3_N_MEMEM: ZP.CSF,AM: _CSD03.CSFAA: 7-Seg. ’C’
F: Specification at BCC connector faulty.R: @CSD03 reverts to the dead state.A: Specification at BCC connector can only be in range 0 to1 .EQ: ZF_ERR_NUM_CSD3_TWU_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Specification at BDR connector faulty.R: @CSD03 reverts to the dead state.A: Specification at BDR connector can only correspond to
one of the following baud rates:300, 600, 1200, 2400, 4800, 9600, 19200
EQ: ZF_ERR_NUM_CSD3_BDR_ERREM: _CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _csd3_init.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_INIT_FRW_ERREM: ZP.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function_csd3_firmware_init.R: @CSD03 reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSD3_FIR_INIT_FRW_ERREM: ZP.CSF,_CSD03.CSFAM: _CSD03.CSFAA: 7-Seg. ’C’
not utilized.
6A43 Hex
6A44 Hex
6A45 Hex
6A46 Hex
6A47 Hex
6A48 Hex
6A49 Hex to 6A4FHex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-976DD1987-1BA0 Edition 10.97
3.2.9.11 USS Link
F: Several communication central blocks were configured with thesame
CS7 board names or interface names.R: @CSU reverts to the dead stateA: Remove one of the configured @CSU blocks;
correct the interface specification of one @CSU block.EQ: ZF_ERR_NUM_CSU_MEHR_PROJEM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_cip_freigabe.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_CIP_FREI_FRW_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSU block is not accessible.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: The CIP entry for the @CSU block does not exist.R: @CSU reverts to the dead state.A: Check the configured name at the CTS connector.EQ: ZF_ERR_NUM_CSU_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zbak_cip_suche.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_CIP_SUCH_FRW_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function zp_dexdo_reorganization.
R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_DEX_REOR_FRW_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
6A50 Hex
6A51 Hex
6A52 Hex
6A53 Hex
6A54 Hex
6A55 Hex
Communication Error Codes
3-98 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown operating status of the @CSU block.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_BZS_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: SAVE memory assigning not possible for warm start flagexact cause of error see section Error supplementary
code bsspvw_geme.R: @CSU reverts to the dead state.A: Reduce the SAVE requirement in the application.EQ: ZF_ERR_NUM_CSU_SAVE_ZU_KURZEM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: SAVE area not found.exact cause of error see section Error supplementary
code bsspvw_info.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_SAVE_N_KENNEM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: @CSU block was configured in impermissible sampling time(not between 32ms and 255ms).
R: @CSU reverts to the dead state.A: Configure the sampling time between 32 ms and 255 ms.EQ: ZF_ERR_NUM_CSU_ABTASTZEIT_ERREM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for exception structureexact cause of error see section Error supplementary
code bsspvw_geme.R: @CSU reverts to the dead state.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSU_EXC_ZU_KURZEM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for reorganization structureexact cause of error see section Error supplementary
code bsspvw_geme.R: @CSU reverts to the dead state.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSU_REORG_ZU_KURZEM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
6A56 Hex
6A57 Hex
6A58 Hex
6A59 Hex
6A5A Hex
6A5B Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-996DD1987-1BA0 Edition 10.97
F: unknown function return value of the function zp_fb_init.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_FB_INIT_FRW_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: lLnk type is not set to "USS" or "CS7".R: @CSU reverts to the dead state.A: Check the configured name at CTS connector;
Check that block type corresponds to @CSU.EQ: ZF_ERR_NUM_CSU_KOP_TYP_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the functionzp_anmelde_ueberwachung.
R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_ANM_FRW_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown register status detected in DEXDO3 managementsection.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_ANM_STATUS_ERREM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: USS firmware has detected an unrepairable error.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_DUST_INIT_ERREM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: USS firmware has reverted to an error status or SS4 adaptermodule missing.R: @CSU reverts to the dead state.A: Install SS4 module in CS7 board;A: Contact Siemens AGEQ: ZF_ERR_NUM_CSU_TOTEM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown status of the USS firmware.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_ZUS_ERREM: ZP.CSF,_CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
6A5C Hex
6A5D Hex
6A5E Hex
6A5F Hex
6A60 Hex
6A61 Hex
6A62 Hex
Communication Error Codes
3-100 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value of the functionzp_firmware_zyklisch.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_FIRM_ZYK_FRW_ERREM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Memory assigning not possible for firmware structureexact cause of error see section Error supplementary
code bsspvw_geme.R: @CSU reverts to the dead state.A: Reduce the RAM requirement in the application.EQ: ZF_ERR_NUM_CSU_N_MEMEM: ZP.CSF,AM: _CSU.CSFAA: 7-Seg. ’C’
F: Specification at PPT connector faulty.R: @CSU reverts to the dead stateA: Specification at PPT connector can only be in range 0 to32767.EQ: ZF_ERR_NUM_CSU_PPT_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Specification at HCT connector faulty.R: @CSU reverts to the dead state.A: Specification at HCT connector can only be in range 0 to32767.EQ: ZF_ERR_NUM_CSU_HCT_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Specification at BDR connector faulty.R: @CSU reverts to the dead state.A: Specification at BDR connector can only correspond
to one of the following baud rates:300, 600, 1200, 2400, 4800, 9600, 19200,38400
EQ: ZF_ERR_NUM_CSU_BDR_ERREM: _CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
F: Unknown function return value of the function _csu_init.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_INIT_FRW_ERREM: ZP.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
6A63 Hex
6A64 Hex
6A65 Hex
6A66 Hex
6A67 Hex
6A68 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1016DD1987-1BA0 Edition 10.97
F: Unknown function return value of the function_csu_firmware_init.R: @CSU reverts to the dead state.A: Contact Siemens AG.EQ: ZF_ERR_NUM_CSU_FIR_INIT_FRW_ERREM: ZP.CSF,_CSU.CSFAM: _CSU.CSFAA: 7-Seg. ’C’
not utilized.
3.2.9.12 Rack Link Fiber Optic Cable
F: Several @CS1 blocks were configured withthe same CS11/12/13/14 board names.
R: @CS1 is disabledA: Reconfigure;
only one @CS1 central block permittedEQ: ZF_ERR_NUM_CS1_MEHR_PROJEM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A90, pointer to configured name, 0)F: Unknown function return value from the function
zp_cip_freigabe.R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_CIP_FREI_FRW_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A91, pointer to configured name,function return value of the function zp_cip_freigabe)
F: The CIP entry for the @CS1 block cannot be accessed.R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A92, pointer to configured name, 0)F: The CIP entry for the @CS1 block does not exist.
R: @CS1 is disabledA: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CS1_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A93, pointer to configured name, 0)
6A69 Hex
6A6A Hex to 6A6FHex
6A90 Hex
6A91 Hex
6A92 Hex
6A93 Hex
Communication Error Codes
3-102 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value from the functionzbak_cip_suche.R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_CIP_SUCH_FRW_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A94, pointer to configured name,function return value of the function zbak_cip_suche)
F: Unknown function return value from the function zp_dexdo_reorganisation.
R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_DEX_REOR_FRW_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A95, pointer to configured name,function return value of the function
zp_dexdo_reorganisation)F: Unknown operating status of the @CS1 block.
R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_BZS_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A96, pointer to configured name, not defined)F: SAVE-memory create for warm start flag not possible
Precise cause of error, review section Error suppl. codebsspvw_gemeR: @CS1 is disabledA: Reduce the SAVE requirements in the applicationEQ: ZF_ERR_NUM_CS1_SAVE_ZU_KURZEM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A97, pointer to configured name, not defined)F: SAVE area not found.
Precise cause of error, review section Error suppl. codebsspvw_infoR: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_SAVE_N_KENNEM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A98, pointer to configured name, not defined)
6A94 Hex
6A95 Hex
6A96 Hex
6A97 Hex
6A98 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1036DD1987-1BA0 Edition 10.97
F: @CS1 block was configured in an invalid sampling time(not between 32ms and 255ms).
R: @CS1 is disabledA: Configure the sampling time between 32ms and 255msEQ: ZF_ERR_NUM_CS1_ABTASTZEIT_ERREM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’’
KFF (6A99, pointer to configured name, not defined)F: Memory create for exception structure not possible
Precise cause of error, review section Error suppl. codebsspvw_gemeR: @CS1 is disabledA: Reduce the RAM requirements in the applicationEQ: ZF_ERR_NUM_CS1_EXC_ZU_KURZEM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9A, pointer to configured name, not defined)F: Memory create for reorganization structure not possible
Precise cause of error, review section Error suppl. codebsspvw_gemeR: @CS1 is disabledA: Reduce the RAM requirements in the applicationEQ: ZF_ERR_NUM_CS1_REORG_ZU_KURZEM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9B, pointer to configured name, not defined)F: Unknown function return value from the function zp_fb_init.
R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_FB_INIT_FRW_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9C, pointer to configured name,function return value of the function
zp_dexdo_reorganisation)F: Link type not set to "CS11/12/13/14 Rack Link".
R: @CS1 is disabledA: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CS1_KOP_TYP_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9D, pointer to configured name, 0)
6A99 Hex
6A9A Hex
6A9B Hex
6A9C Hex
6A9D Hex
Communication Error Codes
3-104 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Unknown function return value from the function zp_anmelde_ueberwachung.
R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_ANM_FRW_ERREM: _CS1.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9E, pointer to configured name,function return value of the function
zp_anmelde_ueberwachung)F: Unknown connect status in DEXDO3 management area.
R: @CS1 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS1_ANM_STATUS_ERREM: ZP.CSFAM: _CS1.CSFAA: 7-Seg. ’C’
KFF (6A9F, pointer to configured name, 0)F: The configured name of the @CS2 block matches another in the
link.R: @CS2 is disabledA: Reconfigure;
only one @CS2 central block permitted.EQ: ZF_ERR_NUM_CS2_MEHR_PROJEM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA0, pointer to configured name, 0)F: The CIP entry for the @CS2 block cannot be accessed.
R: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_CIP_NAM_KEN_N_ADEM: ZBAK.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA1, pointer to configured name, 0)F: The CIP entry for the @CS2 block does not exist.
R: @CS2 is disabledA: Check the configured name at the CTS connectorEQ: ZF_ERR_NUM_CS2_CIP_NAM_N_KENNEM: ZBAK.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA2, pointer to configured name, 0)F: Unknown function return value from the function
zbak_cip_suche.R: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_CIP_SUCH_FRW_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA3, pointer to configured name,function return value of the function zbak_cip_suche)
6A9E Hex
6A9F Hex
6AA0 Hex
6AA1 Hex
6AA2 Hex
6AA3 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1056DD1987-1BA0 Edition 10.97
not utilizedF: Eight @CS2 blocks already connected in the link.
R: @CS2 is disabledA: Power down rack and after 10 sec. power up again
Check whether more than eight CS2 boards exist in thelink or whether the @CS2 block is multiply configured on thesame CS21/22 boardEQ: ZF_ERR_NUM_CS2_SCHON_ACHT_CS22EM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA5, pointer to configured name, 0)F: The configured CS11/12/13/14 board does not exist.
R: @CS2 is disabledA: Check the configured CS11/12/13/14 name at the MTSconnectorEQ: ZF_ERR_NUM_CS2_CS1_N_KENNEM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’’
KFF (6AA6, pointer to configured name, 0)F: Unknown function return value from the function
_cs2_anmeldung.R: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_ANM_FRW_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA7, pointer to configured name,function return value of the function _cs2_anmeldung)
F: Unknown operating status of the @CS2 block.R: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_BZS_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA8, pointer to configured name, faultyoperating status)
F: SAVE-memory create for warm start flag not possiblePrecise cause of error, review section Error suppl. code
bsspvw_gemeR: @CS2 is disabledA: Reduce the SAVE requirements in the applicationEQ: ZF_ERR_NUM_CS2_SAVE_ZU_KURZEM: ZP.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AA9, pointer to configured name, not defined)
6AA4 Hex6AA5 Hex
6AA6 Hex
6AA7 Hex
6AA8 Hex
6AA9 Hex
Communication Error Codes
3-106 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: SAVE area not found.Precise cause of error, review section Error suppl. code
bsspvw_infoR: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_SAVE_N_KENNEM: ZP.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AAA, pointer to configured name, not defined)F: @CS2 block was configured in an invalid sampling time
(not between 32ms and 255ms) or the sampling time ofthe @CS1 does not fit.R: @CS2 is disabledA: Configure the sampling time between 32ms and 255msor
check the sampling time of the @CS1EQ: ZF_ERR_NUM_CS2_ABTASTZEIT_ERREM: ZP.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AAB, pointer to configured name, 0)F: Memory create for exception structure not possible
Precise cause of error, review section Error suppl. codebsspvw_gemeR: @CS2 is disabledA: Reduce the RAM requirements in the applicationEQ: ZF_ERR_NUM_CS2_EXC_ZU_KURZEM: ZP.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AAC, pointer to configured name, not defined)F: Memory create for reorganization structure not possible
Precise cause of error, review section Error suppl. codebsspvw_gemeR: @CS2 is disabledA: Reduce the RAM requirements in the applicationEQ: ZF_ERR_NUM_CS2_REORG_ZU_KURZEM: ZP.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AAD, pointer to configured name, not defined)F: Unknown function return value from the function zp_fb_init.
R: @CS2 is disabledA: Inform Siemens AG.EQ: ZF_ERR_NUM_CS2_FB_INIT_FRW_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’’
KFF (6AAE, pointer to configured name,function return value of the function zp_fb_init)
not utilized
6AAA Hex
6AAB Hex
6AAC Hex
6AAD Hex
6AAE Hex
6AAF Hex to 6AB0Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1076DD1987-1BA0 Edition 10.97
F: Link type not set to "CS22 Rack Link in the expandedaddress area" or "CS22 Rack Link in the special
peripherals area".R: @CS2 is disabledA: Check the configured name at the CTS connectorotherwise
inform Siemens AG.EQ: ZF_ERR_NUM_CS2_KOP_TYP_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AB1, pointer to configured name, 0)F: Three @CS2 blocks already connected in the link.
R: @CS2 is disabledA: Power down rack and after 10 sec. power up again
Check whether more than three CS21 boards exist in thelink or
whether the @CS2 block is multiply configured on thesame CS21 boardEQ: ZF_ERR_NUM_CS2_SCHON_DREI_CS21EM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AB2, pointer to configured name, 0)F: The software version on the processor board is not compatible
with theversion in the CS11/12/13/14 rack.
R: @CS2 is disabledA: Check the versions in all the connected racks, otherwise
inform Siemens AG.EQ: ZF_ERR_NUM_CS2_VERSION_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AB3, pointer to configured name, 0)F: Memory size of the CS22 and the CS12/13/14 do not match
R: @CS2 is disabledA: Check the EMA connectors on the CS12/13/14-IB orCS22-IB, otherwise inform Siemens AG.EQ: ZF_ERR_NUM_CS2_MEM_SIZE_ERREM: _CS2.CSFAM: _CS2.CSFAA: 7-Seg. ’C’
KFF (6AB4, pointer to configured name, 0)
6AB1 Hex
6AB2 Hex
6AB3 Hex
6AB4 Hex
Communication Error Codes
3-108 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
3.2.10 Gerätekopplung und Parameterbearbeitung auf T400
F: Parameternummer ist nicht vorhandenR: Auftrag wird nicht ausgeführtA: Parameternummer überprüfenEQ: ZF4_GER_ERR_PRP_NO_PARA_NREM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 0
F: PEN-Eingang erlaubt keine Änderung der ParameterR: Parameter wird nicht geändertA: FB-@DRIVE, Eingang PEN auf 1 setzenEQ: ZF4_GER_ERR_PRP_NO_PENEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 1
F: MIN- / MAX-Grenze ueberschrittenR: Parameter wird nicht geändertA: Wert für Parameterauftrag so ändern, daß er innerhalb der
Grenzwerte liegt. Oder Grenzwerte ändern, falls Grenzwerteüber PLIM-Bausteine festgelegt wurden, und RESET der T400.
EQ: ZF4_GER_ERR_PRP_OFF_LIMITEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 2
F: Keine gueltiger Parameterauftrag, Auftragsnummer undParameternummer konnten nicht aus der Parameter ID bestimmtwerden.
R: Auftrag wird nicht bearbeitetA: Parameter ID überprüfen und gültige Parameter ID angebenEQ: ZF4_GER_ERR_PRP_NO_PARA_IDEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 3
F: Ungueltiger DatentypR: Auftrag wird nicht ausgeführtA: Gültigen Datentyp für Parameterauftrag verwendenEQ: ZF4_GER_ERR_PRP_ILLEGAL_DATA_TYPEEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 5
F: Parameter auf einem Ausgang ist nicht änderbarR: Auftrag wird nicht ausgeführtA: Parameter auf einen Eingang projektierenEQ: ZF4_GER_ERR_PRP_NO_INPUTEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert 18
7C00 Hex
7C01 Hex
7C02 Hex
7C03 Hex
7C05 Hex
7C12 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1096DD1987-1BA0 Edition 10.97
F: Schreibschutz der Speicherkarte ist eingelegtR: Abspeichern in das EEPROM ist nicht möglich.A: Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PRP_SAVE_PROTECTEM: zf4ger.csfAM _drive.csf, YTx,
Fehlernummer wird als zusätzlicher Parameterrückgabewert beider Auftragsantwort mit zurückgesendet.
F: Kanalzustand ist AUS aufgrund Baugruppen-KonfigurationR: Keine weitere BearbeitungA: Überprüfen, ob die Baugruppen richtig gesteckt sindEQ: ZF4_GER_ERR_PRP_KAN_ZUS_OFFEM: zf4ger.csfAM: _drive.csf, YTx
F: Funktionsbaustein ist mehrfach projektiertR: Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltetA: Funktionsbaustein nur einmal projektierenEQ: ZF4_GER_ERR_MEHRFACHEM: _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csfAM: _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
F: Abtastzeit nicht 10 .. 200msR: Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltetA: Abtastzeit ändern, so daß sie zwischen 10 ms und 200 ms liegt.EQ: ZF4_GER_ERR_ABTASTZEITEM: _drive.csfAM: _drive.csf, YT1
F: Fehler bei der SpeicherbeschaffungR: Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltetA: Siemens AG benachrichtigenEQ: ZF4_GER_ERR_GEMEEM: _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csfAM: _drive.csf, cbconf.csf, ptrans.csf, tfaw.csf, rfaw.csf
Zusatzinformation im Kommunikationsfehlerfeld: Rückgabewertder Funktion bsspvw_geme
F: ungueltiges Request-Buffer-Status-ByteR: Paramterkanal wird nicht bearbeitet.A: Hardware überprüfen, Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PRP_RQU_BUFFEREM: zf4ger.csfAM: _drive.csf, YT1
7C66 Hex
7C70 Hex
7C72 Hex
7C7A Hex
7C7B Hex
7C7E Hex
Communication Error Codes
3-110 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: kein Zugriff auf Reply-Buffer möglichR: Paramterkanal wird nicht bearbeitet.A: Hardware überprüfen, Siemens AG benachrichtigen.EQ: ZF4_GER_ERR_PRP_RPL_NO_ACCEM: zf4ger.csfAM: _drive.csf, YTx
F: ungueltiges Reply-Buffer-Status-ByteR: Paramterkanal wird nicht bearbeitet.A: Hardware überprüfen, Siemens AG benachrichtigen.EQ: ZF4_GER_ERR_PRP_RPL_BUFFEREM: zf4ger.csfAM: _drive.csf, YTx
F: Vorheriger Speicherauftrag noch in Arbeit.R: Auftrag wird nicht ausgeführt.A: Auftrag wiederholen.EQ: ZF4_GER_ERR_PRP_SAVE_BUSYEM: zf4ger.csfAM: _drive.csf, Ytx
Fehlernummer wird als zusätzlicher Parameterrückgabewert beider Auftragsantwort mit zurückgesendet.
F: Kanalkennung fehlerhaftR: Paramterkanal wird nicht bearbeitet.A: Hardware überprüfen, Siemens AG benachrichtigen.EQ: ZF4_GER_ERR_PRP_NO_KAN_KNGEM: zf4ger.csfAM: _drive.csf, YTx
F: Parameterfunktion nicht implementiert, ParameterAuftragsnumer ist ungültig oder Parameterauftrag kann auf derT400 nicht bearbeitet werden.
R: Paramterauftrag wird nicht ausgeführt.A: Gültigen Parameterauftrag projektieren.EQ: ZF4_GER_ERR_PRP_NO_PKWEM: zf4ger.csfAM: _drive.csf, YTx, Parameterrückgabewert
F: Fehler bei der Übertragung neuer Konfigurationsdaten zumComboard
R: kein Datenaustausch zum Comboard.A: An Baseboard oder FB CBCONF andere Konfigurationsdaten für
Comboard einstellen und diese zum Comboard übertragen.EQ: ZF4_GER_ERR_CBCONFEM: _drive.csfAM: _drive.csf, cbconf.csf, YTS
7C7F Hex
7C80 Hex
7C81 Hex
7C83 Hex
7C84 Hex
7C8D Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1116DD1987-1BA0 Edition 10.97
F: Falsche Baugruppe rechtsR: Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltetA: Anderen Baugruppe rechts verwendenEQ: ZF4_GER_ERR_KOPP_REM: _drive.csfAM: _drive.csf, YT1
F: Parametertabelle ist nicht vorhandenR: Eintrag ins Kommunikationsfehlerfeld, Baustein wird
abgeschaltetA: Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PRP_PTABEM: _drive.csfAM: _drive.csf, YT1
F: Request-Buffer-Channel-Control is OFFR: Parameterkanal wird nicht bearbeitetA: Kommunikationpartner überprüfen.EQ: ZF4_GER_ERR_PRP_RQU_CC_OFFEM: zf4ger.csfAM: _drive.csf, YTx
F: kein Zugriff auf Request-Buffer möglichR: Parameterkanal wird nicht bearbeitetA: Kommunikationpartner überprüfen.EQ: ZF4_GER_ERR_PRP_RQU_NO_ACCEM: zf4ger.csfAM: _drive.csf, YTx
F: Reply-Buffer-Channel-Control is OFFR: Parameterkanal wird nicht bearbeitetA: Kommunikationpartner überprüfen.EQ: ZF4_GER_ERR_PRP_RPL_CC_OFFEM: zf4ger.csfAM: _drive.csf, YTx
F: Auf Parameterantwort vom anderen Board warten.R: Auf Parameterantwort vom anderen Board warten.A: Überprüfen, ob anderes Board korrekt arbeitet.EQ: ZF4_GER_ERR_PRP_RPL_WAITEM: zf4ger.csfAM: _drive.csf, YT5
F: Timeout beim Warten auf Parameterantwort vom anderen BoardR: Parameterantwort „Auftrag konnte nicht ausgeführt werden“ mit
Zusatzinformation „Timeout beim Warten auf Quittung vomanderen Board“ wird gesendet
A: Überprüfen, ob anderes Board korrekt arbeitet.EQ: ZF4_GER_ERR_PRP_RPL_WAITOUTEM: zf4ger.csfAM: _drive.csf, YT5
7C8F Hex
7C92 Hex
7C93 Hex
7C94 Hex
7C95 Hex
7C97 Hex
7C98 Hex
Communication Error Codes
3-112 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Speicherkarte ist nicht „SIMADYN D konform“R: Parameterauftrag wurde nicht ausgeführtA: Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PRP_SAVE_NONCOMPEM: zf4ger.csfAM: _drive.csf, YTx, als Parameterrückgabewert
F: Speicherkarte wurde beim letzten Schreibvorgang defekt. Alleweiteren Versuch zu schreiben sind zwecklos
R: Parameterauftrag wurde nicht ausgeführtA: Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PRP_SAVE_DEFECTEM: zf4ger.csfAM: _drive.csf, YTx, als Parameterrückgabewert
F: Speicherplatz im EEPROM ist nicht ausreichendR: Parameterauftrag wurde nicht ausgeführtA: keineEQ: ZF4_GER_ERR_PRP_SAVE_NO_SPACEEM: zf4ger.csfAM: _drive.csf, YTx, als Parameterrückgabewert
F: Konvertierung von Float auf I4 hat fehlgeschlagen, Float-Zahlwar zu groß
R: Parameterauftrag wird nicht ausgeführt.A: kleinere Float-Zahlen im Parameterauftrag versenden,
Parameterkanal verwenden, über den Float-Zahlen versendetwerden können (siehe PCF-/PTF-Eingang am FB @Drive)
EQ: ZF4_GER_ERR_PRP_NO_KONV_NFI4EM: zf4ger.csfAM: _drive.csf, Ytx
Fehlernummer wird als zusätzlicher Parameterrückgabewert beider Auftragsantwort mit zurückgesendet.
F: Zentralbaustein FB-@Drive fehltR: Eintrag ins Kommunikationsfehlerfeld, Abschaltung des
suchenden BausteinsA: FB @Drive projektierenEQ: ZF4_GER_ERR_N_DRIVEEM: zf4ger.csf, pname.csf, ptrans.csf, cbconf.csf, tfaw.csf, rfaw.csfAM: pname.csf, plim.csf, plim_i.csf, plim_d.csf, ptrans.csf,
cbconf.csf, tfaw.csf, rfaw.csfYTS-Ausgänge
F: Kanal fehlerhaftR: Kommunikation wird abgebrochenA: Board überprüfen, Siemens AG benachrichtigenEQ: ZF4_GER_ERR_PKZ_BREAKEM: zf4ger.csf, ptrans.csfAM: tfaw.csf, ptrans.csf -- YTS-Ausgänge
7C9C Hex
7C9D Hex
7C9E Hex
7CA1 Hex
7CA6 Hex
7CA7 Hex
Communication Error Codes
General diagnostics - SIMADYN D - Reference Manual 3-1136DD1987-1BA0 Edition 10.97
F: Parameter zur projektierten Nummer ist einBeobachtungsparamter (Ausgang)
R: Grenzwerte werden nicht in die Parametertabelle eingetragen,Eintrag in das Fehlerfeld
A: Parameter an einem Eingang projektierenEQ: ZF4_PLIM_ERR_NO_WRITEEM: zf4ger.csfAM: plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang
F: Parameter zur projektierten Nummer ist nicht vorhandenR: Grenzweret können nicht in die Parametertabelle eingetragen
werden, Eintrag in das FehlerfeldA: Vorhandene Parameternummer projektierenEQ: ZF4_PLIM_ERR_NO_PARAM_NREM: zf4ger.csfAM: plim.csf, plim_i.csf , plim_d.csf -- YTS- Ausgang
F: Datentypen sind nicht identischR: Grenzwerte für Parameternummer werden nicht aktiv, Eintrag in
das FehlerfeldA: Richtigen PLIM-Baustein verwendenEQ: ZF4_PLIM_ERR_NO_DATA_TYPEEM: plim.csf, plim_i.csf, plim_d.csfAM: plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das
Fehlerfeld
F: Fehler bei der Bestimmung der Skalierungsfaktoren der MIN- /MAX-Eingänge
R: Grenzwerte werden nicht aktivA: Siemens AG benachrichtigenEQ: ZF4_PLIM_ERR_MINMAXEM: plim.csfAM: plim.csf -- YTS- Ausgang
Eintrag in das Fehlerfeld, Zusatz: Funktionsrückgabewert derFunktion sda_func_afpi_suche_fbk_nr odersda_func_afpi_fbk_kbs
F: Minimum ist größer als MaximumR: Grenzwerte werden nicht aktivA: Eingänge MIN, MAX korrigierenEQ: ZF4_PLIM_ERR_MINMAXEM: plim.csf, plim_i.csf, plim_d.csfAM: plim.csf, plim_i.csf, plim_d.csf -- YTS- Ausgang, Eintrag in das
Fehlerfeld
7CAB Hex
7CAC Hex
7CAD Hex
7CAE Hex
7CAF Hex
Communication Error Codes
3-114 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: T400 ist nicht als Techboard projektiertR: Abschaltung des Bausteins und Eintrag in das
KommunikationsfehlerfeldA: T400 am FB @DRIVE als Techboard projektieren (Eingang
BBF=0)EQ: ZF4_PTRANS_ERR_NO_T400EM: ptrans.csfAM: ptrans.csf- YTx-Konnektoren
F: Funktionsbaustein kann wg. Hardwarekonfiguration nichtverwendet werden
R: Funktionsbaustein schaltet sich ab.A: Baustein nur projektieren, wenn Konfiguration dies zulässtEQ: ZF4_GER_ERR_FB_FE_KOPPZUSEM: cbconf.csf, tfaw.csf, rfaw.csfAM: cbconf.csf, tfaw.csf, rfaw.csf -- YTx-Ausgänge
F: Initialisierung des Funktionsbausteins läuftR: (temporärer Zustand)A: wartenEQ: ZF4_GER_ERR_FB_INIEM: cbconf.csf, tfaw.csf, rfaw.csfAM: cbconf.csf, tfaw.csf, rfaw.csf - YTx-Ausgänge
F: keine Kommunikation mit KommunikationspartnerR: Es findet keine Übertragung der Fehler und Warnungen statt.A: Kommunikationspartner überprüfen, Siemens AG
benachrichtigenEQ: ZF4_GER_ERR_FAW_N_COMEM: tfaw.csf, rfaw.csfAM: tfaw.csf, rfaw - YTx-Konnektoren
F: kein Zugriff auf Kanal möglichR: Es findet keine Übertragung der Fehler und Warnungen statt.A: Kommunikationspartner überprüfen, Siemens AG
benachrichtigenEQ: ZF4_GER_ERR_FAW_N_CHANNEL_ACCESSEM: tfaw.csf, rfawAM: tfaw.csf, rfaw.csf - YTx-Konnektoren
7CB0 Hex
7CB3 Hex
7CB4 Hex
7CB5 Hex
7CB6 Hex
Fehler! Datei kann nicht geöffnet werden. - Fehler! Datei kann nicht geöffnet werden. - Fehler! Datei kann nicht geöffnetwerden. 4-1Fehler! Datei kann nicht geöffnet werden. Fehler! Datei kann nicht geöffnet werden.
4 Error Supplementary Codes
This chapter describes the error supplementary codes to the individualerror codes. Which supplementary codes exist for which error codes isindicated in the description of the corresponding error codes. An errorsupplementary code does not automatically exist for each error code.
4.1 Supplementary code "bsspvw_geme"
F: Memory object ID impermissible.(permissible memory object ID’s are PN local RAM, slots 1...24,PN local SAVE area, L bus coupling memory and C bus couplingmemory).
R: Required memory was not set.A: Contact Siemens AG .EQ: SDB_FRW_BSSPVW_GEME_SOK_UNZEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
F: Memory object ID points to a memory object that does not exist in the rack.
R: Required memory was not set.A: Contact Siemens AG .EQ: SDB_FRW_BSSPVW_GEME_SOK_NEXISTEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
F: The free memory space on the memory object is not sufficient.R: Required memory was not set.A: Free up memory space on the memory object by reconfiguring.EQ: SDB_FRW_BSSPVW_GEME_SP_ZUKLEINEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
F: The memory object is currently blocked by another user.R: Required memory was not set.A: Wait state.EQ: SDB_FRW_BSSPVW_GEME_SO_KZUGREM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
01 Hex
02 Hex
03 Hex
04 Hex
Error Supplementary Codes
4-2 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: Required memory distribution is impermissible.(permissible memory distribution is either word wise or paragraphwise).
R: Required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_GEME_SOM_UNZEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
F: System bus access errorR: Required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_GEME_BUSEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
F: RAM drive access error.R: Required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_GEME_RAMEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_geme.AA: Block dependent.
4.2 Supplementary code "bsspvw_info"
F: Memory object ID impermissible.(permissible memory object ID’s are PN local RAM, slots 1...24, PN local SAVE area, L bus coupling memory and C bus couplingmemory.)
R: The address of the required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_INFO_SOK_UNZEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_info.AA: Block dependent.
F: Memory object ID points to a memory object that does not exist in the rack.
R: Required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_INFO_SOK_NEXISTEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_info.AA: Block dependent.
05 Hex
06 Hex
07 Hex
01 Hex
02 Hex
Error Supplementary Codes
General diagnostics - SIMADYN D - Reference Manual 4-36DD1987-1BA0 Edition 10.97
F: The required list does not exist.R: The address of the required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_INFO_SON_NEXISTEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_info.AA: Block dependent.
F: System bus access errorR: The address of the required memory was not set.A: Contact Siemens AG.EQ: SDB_FRW_BSSPVW_INFO_BUSEM: BSSPVW.CSFAM: Block that invokes the function bsspvw_info.AA: Block dependent.
4.3 Supplementary code "zbin_komdat"
F: Memory assigning for KOMDAT structure temporarily not possible. Exact cause of error see section Error supplementary code bsspvw_geme.
R: KOMDAT area is not set.A: Repeat the function invocationEQ: Z_FRW_ZBIN_N_ANMEM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Memory assigning for KOMDAT structure not possibleexact cause of error see section Error supplementary codebsspvw_geme.
R: KOMDAT area is not set.A: Reduce the RAM requirement in the applicationEQ: Z_FRW_ZBIN_GEME_AUFRUF_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Transmit/receive ID in transfer structure of the function incorrect.R: KOMDAT area is not set.A: The value in transmit / receive ID must correspond to the ENUMtype
z_kenn_valEQ: Z_ZBIN_DIR_KENN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
03 Hex
04 Hex
31 Hex
32 Hex
33 Hex
Error Supplementary Codes
4-4 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
F: The number of components (separated by a dot) of the configuring specification is larger than 6.
R: KOMDAT area is not set.A: The specification at AT / AR / US connector may only have a
maximum of 6 components.EQ: Z_ZBIN_TEIL_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: The configuring specifications consist of more than 3 components but is not identifiable as a destination specification.
R: KOMDAT area is not set.A: When no destination is configured at AT / AR /US connector,
then the specification may consist of a maximum of three components (channel name, address stage 1, address stage 2;when a destination is configured at AT / AR / US connector, then the specification of the destination rack name must start with an "@").
EQ: Z_ZBIN_ZIEL_N_KENNEM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Configured destination specification is incorrect.R: KOMDAT area is not set.A: Only configure a "@" at AT / AR / US connector.EQ: Z_ZBIN_ZIEL_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Configured channel name is too long.R: KOMDAT area is not set.A: Channel name first sub?specification at AT / AR / US connector)
may be a maximum of 8 characters long.EQ: Z_ZBIN_KAN_NAM_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Configured address stage 1 is too long.R: KOMDAT area is not set.A: Address stage 1 (second sub?specification at AT / AR / US
connector) may be a maximum of 14 characters long.EQ: Z_ZBIN_ADR_STUF1_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
34 Hex
35 Hex
36 Hex
37 Hex
38 Hex
Error Supplementary Codes
General diagnostics - SIMADYN D - Reference Manual 4-56DD1987-1BA0 Edition 10.97
F: Configured address stage 2 is too long.R: KOMDAT area is not set.A: Address stage 2 (third sub?specification at AT / AR / US
connector) may be a maximum of 20 characters long.EQ: Z_ZBIN_ADR_STUF2_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: The configured destination specification is located in the incorrect section of the string.
R: KOMDAT area is not set.A: The "@" is only permitted to be at start of the second or third last
sub?specification at the AT / AR / US connector.EQ: Z_ZBIN_STRING_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdatAA: Block dependent.
F: Configured destination rack is too long.R: KOMDAT area is not set.A: Destination rack name (first sub?specification after the "@" at
the AT / AR / US connector) must be up to 6 characters long.EQ: Z_ZBIN_ZBGT_NAM_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Configured destination board name length is incorrect.R: KOMDAT area is not set.A: Destination board name (second sub?specification after the "@"
at the AT / AR / US connector) must be exactly 6 characters long.
EQ: Z_ZBIN_ZBG_NAM_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
F: Configured destination interface length is incorrect.R: KOMDAT area is not set.A: Destination board name (third sub?specification after the "@" at
the AT / AR / US connector) must be exactly 3 characters long.EQ: Z_ZBIN_ZSS_LEN_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdatAA: Block dependent.
F: Configured destination interface is incorrect.R: KOMDAT area is not set.A: Only the following interface specifications are permitted: "X01",
"X02", "X03".EQ: Z_ZBIN_ZSS_NAM_ERREM: ZBIN.CSFAM: Block that invokes the function zbin_komdat.AA: Block dependent.
39 Hex
3A Hex
3B Hex
3C Hex
3D Hex
3E Hex
Error Supplementary Codes
4-6 General diagnostics - SIMADYN D - Reference Manual6DD1987-1BA0 Edition 10.97
4.4 Supplementary code "zgsd_zini_nachtrag"
F: ZINI list is already fullR: Data interface cannot be initialized.A: Reduce the number of data interfacesEQ: SDZ_FRW_ZG_ZINI_ZU_KURZEM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
F: Incorrect bus accessR: Data interface cannot be initialized.A: Check hardware or inform Siemens AG.EQ: SDZ_FRW_ZG_BUS_ACC_ERREM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
F: ZINI list is already fullR: Data interface cannot be initialized.A: Reduce the number of data interfacesEQ: SDZ_FRW_ZG_ZINI_VOLLEM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
F: Impermissible board nameR: Data interface cannot be initialized.A: Check CTS connectorEQ: SDZ_FRW_ZG_BG_NAM_ERREM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
F: ZINI list not foundR: Data interface cannot be initialized.A: Inform Siemens AG.EQ: SDZ_FRW_ZG_ZINI_N_FOUNDEM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
F: Slot cannot be foundR: Data interface cannot be initialized.A: Inform Siemens AG.EQ: SDZ_FRW_ZG_NO_STPL_NREM: ZGSD.CSFAM: Block that invokes the function zgsd_zini_nachtragAA: Block dependent
02 Hex
03 Hex
04 Hex
05 Hex
07 Hex
08 Hex
Basissoftware for D7-SYS - SIMADYN D - Manual 16DD1987-1BA2 Edition 01.99
To
Siemens AG
A&D LD R
Frauenauracher Straße 80
91056 Erlangen
From
Your Name:
Your Function
Your Company:
Street:
City:
Telephone:
Please indicate your particular industrial sector:
o Automobile industry o Pharmaceutical industry
o Chemical industry o Plastic processing
o Electrical industry o Paper industry
o Foodstuff industry o Textile industry
o Process control o Transport
o Machine construction o Others _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
o Petrochemical
"
2 Basissoftware for D7-SYS - SIMADYN D - Manual6DD1987-1BA2 Edition 01.99
Recommendations and comments on the User Documentation
Your comments and recommendations help us to improve the quality andusefulness of our documentation. Please complete this form at the nextconvenient opportunity and return it to Siemens.
Please give us your own personal opinion to the following questions, valuesfrom1 = good to 5 = poor.
1. Do the contents of the documentation fulfill your requirements?
2. Can you easily find the information you require?
3. Is the text easy to understand?
4. Do we go into enough technical details for your requirements?
5. How do you evaluate the quality of the diagrams and tables?
6.
7.
8.
If you come across any problems, please let us know in the space below: