Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-420
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 2000 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-001
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 2000
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-420 Serial Number 27261-001
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 6000 11-18 11.1 11.0 11.1 Pass/Fail: Pass
Short Time 150 12000 .35-.50 .463 .462 .461 Tester Initials: cm
Instantaneous 100 8000 +/- 10% Amps7990 Amps7980 Amps8000
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 24 25 24 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 90 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-420
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 2000 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-002
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 2000
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-420 Serial Number 27261-002
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 6000 11-18 14.4 13.4 14.4 Pass/Fail: Pass
Short Time 150 12000 .35-.50 .461 .480 .482 Tester Initials: cm
Instantaneous 100 8000 +/- 10% Amps8710 Amps8480 Amps8370
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 25 26 26 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 100 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-420
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 2000 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-003
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 2000
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-420 Serial Number 27261-003
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 6000 11-18 12.4 11.3 11.9 Pass/Fail: Pass
Short Time 150 12000 .35-.50 .450 .451 .463 Tester Initials: cm
Instantaneous 100 8000 +/- 10% Amps7580 Amps7540 Amps8710
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 24 25 25 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 95 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-004
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-004
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 12.2 12.0 12.1 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .486 .471 .499 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps5137 Amps4838 Amps4736
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 30 30 31 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 95 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-005
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-005
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 11.8 11.4 11.2 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .480 .494 .475 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4615 Amps4610 Amps4636
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 33 32 31 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 95 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-006
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-006
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 13.3 13.4 13.6 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .490 .497 .482 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4810 Amps4910 Amps4859
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 31 29 30 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 95 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-007
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-007
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 12.7 12.4 12.5 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .474 .467 .493 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4812 Amps4725 Amps4635
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 30 29 29 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 100 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-008
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-008
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 12.5 12.1 12.8 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .488 .489 .485 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4612 Amps4547 Amps4531
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 32 37 33 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 90 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-009
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-009
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 11.2 11.2 11.3 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .499 .490 .498 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4812 Amps4760 Amps4750
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 34 35 32 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 90 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-010
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-010
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 12.5 13.2 13.4 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .48 .467 .471 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4788 Amps4712 Amps4675
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 35 33 35 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 90 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
Page 1 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Job Information
Customer Rubicon Minerals
Test Information
Test Location Gainesville, TX
Temperature (°F) 73 (°C) 22
Test Condition As Left
Product Condition ReconditionedHumidity (%) 33
Circuit Breaker Information
Manufacturer Westinghouse
Model DS-416
Mechanism Model # N/A
Rated Maximum Voltage 600 V
Continuous Amp Rating 1600 A
Type Air
Charge 120VAC
Close 120VAC
Trip 120VAC
Serial Number 27261-011
Wiring Diag. # 2a 6a
Operator Manual/Electric
Mount Draw Out
Trip Unit Information
Manufacturer Westinghouse
Type Static/Solid State
Model Amptector I A LSI
Curve Number 2
C. T. Rating 1200
Rating Plug N/A
Serial Number N/A
Primary Fuses N/A
PickupSettings Band
Long Time 1.0 4
Short Time 4 .5
Instant 4 N/A
Ground Fault N/A N/A
Control Voltage
X N/A
Y 120VAC
UV N/A
Comments:
N/A
.5
Band
4
Quality Control Signature
Page 2 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Results Summary
Customer Rubicon Minerals
Manufacturer Westinghouse
Model DS-416 Serial Number 27261-011
Mechanical Inspection Pass
Electrical Inspection Pass
Inspections
Visual Inspection Pass
Remarks/Recommendations
Tests Remarks/Recommendations
High Current Test Pass
Insulation Test Pass
Contact Resistance Test Pass
Min. Close and Trip Test Pass
Megger Control WiringP
Mechanical InterlocksP
Name PlateP
Blown Fuse IndicatorN/A
4th Wire GroundN/A
Anti-Pump FunctionP
Test StickerP
Indicating StickersP
Auxiliary SwitchesP
Operation CounterN/A
DocumentsY
Power Factor AttachedN/A
TTA AttachedN/A
Operation Counter ReadingN/A
Comments:
Tester Initials gd
P=Pass
F=Fail
Y=Yes
N=No
N/A=Not Applicable
I=Incomplete
Additional Tests, Inspections, and Documentation
Page 3 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
High Current Test Data
FunctionPercent
Pickup
Current
(Amps)Curve Specs.
Phase A
(Seconds)
Phase B
(Seconds)
Phase C
(Seconds)
Long Time 300 3600 11-18 13.3 13.6 13.6 Pass/Fail: Pass
Short Time 150 7200 .35-.50 .498 .499 .500 Tester Initials: gd
Instantaneous 100 4800 +/- 10% Amps4610 Amps4810 Amps4615
Ground Fault N/A N/A N/A N/A N/A N/A
Comments:
Insulation Resistance Test
Comments:
Test
Voltage
Isolated
Bushing/s1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
A Phase
Closed
B Phase
Closed
C Phase
Closed
1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass
Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd
Contact Resistance Test
Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass
N/A 36 32 37 Tester Initials: gd
In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest
value recorded (ANSI/NETA MTS-2011 7.5.1.1).
Comments:
Minimum Close/Trip Voltage Test
Required Value Tested Value
Minimum Close Voltage 104VAC 95 Pass/Fail: Pass
Mininum Trip Voltage 104VAC 85 Tester Initials: gd
Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).
Comments:
Page 4 of 4
Low Voltage Circuit Breaker Test Report Rev. 14, 12-14
Job Number 27261 Date 12/16/14
Test Equipment
Manufacturer Model Serial Number Calibration Expires Used For
AVO/ETI PS-9160R 11412 03/03/15 High Current
AVO/ETI PS-9160R 11412 03/03/15 High Current
Fluke 1520 92470030 03/03/15 Insulation Resistance
Biddle 247001 49017 03/03/15 Contact Resistance
CBS Big Gray 148990 03/03/15 Min Trip/Close
Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level
! " # $ % ! & ' % ( )* + * , - . / 0 1 2 3 4 5 6 1 4 7 8 9 1 : : 7, ; < , - * = * * = - <> 7 8 ? 1 4 5 @ 3 / 8 7 1 4 A 3 3 .A 8 / 4 1 ? B *C , D D 9 * D D D 6E 6 1 4 * D D D - C F 1 = 5 6 . A G 6 8 8 * D D 6 1 3 4 * D - * D D * D -E 6 1 4 * D D D F 6 8 7 H H D G 6 8 8I A . B - - * D D < C F 1 = 5 6 . A G 6 8 8I A . B * - * D D < C F 1 = 5 6 . A G 6 8 8I A . B H - * D D < C F 1 = 5 6 . A G 6 8 8I A . B < - * D D < C F 1 = 5 6 . A G 6 8 8
< D D < D - < D D < D D 4 J 6 4 J 6 4 J 6 4 J 6 4 J 6 K D C F K D K D C - + ; C ; 4 J 6 4 J 6 4 J 6
L M
N O M M
P
* C F H * D D F D D D H + D D 4 J 6I A . B - - * D D 6 - D 6 - * K - * K - H *I A . B * - * D D 6 - D 6 - * D - * * - * ;I A . B H - * D D 6 - D 6 - * < - * - - - ;I A . B < - * D D 6 - D 6 - - H - - ; - * D
4 J 6
? Q
R S S T U V W X Y Z [ \ ] U ^ W [ V _ ` S [ a b ` W U c ` ^ ^ Z ` S S d e _ f \ [ U V f g _ U b W [ g [ _ ` W [ f ^ [ V ` h ` [ S ` a S U [ ^ W i U X ^ j [ ^ U U b [ ^ j k U \ ` b W ] U ^ W lm f b ] V n o p q r m s t q s u W i b f Z j i n o p q r m s t q v w
x y z | ~ z z ~ ~ ~ ~ ~ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « § ¦ ¬ ® ¯ ¡ ° ¥ £ ¤ ¥ ¦ ¥ ± ± ± ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² · ª ª ¥ § ¸ ³ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² · ª ª ¥ § ¥ § © ± µ ¶ § ² · ª ª ¥ ¬ · ¡ ¤ £ £ ± ¹ ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ± ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ³ ± µ ¶ § ² · ª ª ¥ § ¸ µ ¶ § ² · ª ª ¥ ³ © ½ § ¾ ± ± £ µ ¶ § ² · ª ª ¥ ¹ ³ ¹ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¹ ¾ ¡ ª « ¿ § ¥ ¯ ¨ ¢ ³ ¹ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¾ À ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± § ² ² ± ± µ ¶ § ² · ª ª ¥ © ½ § ¾ ¹ § ² ¥ ¡ § ¨ ¥ ª ¥ § ¥ ª ¡ ¿ À ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ¹ ¹ ³ ³ µ ¶ § ² · ª ª ¥ ¯ ¨ ¢ ¹ ¹ µ ¶ § ² · ª ª ¥ ¯ ¨ ¢ ¹ ¬ ® ¯ ¡ ° ¥ £ ¤ ¥ ¦ ¥ Â § ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ Á ¼ ± ± ¡ º £ ¤ ¥ ¦ ¥ Â ¯ ± © ¾ Ã ² · ¬ ¥ Ã ² · ¶ ¥ ¡ ² ¬ £ ¦ ¹ § ¥ § ² ² ± ± Á Á ± µ ¶ ¾ Ã º « ¥ Ã « ¥ ¿ ° ¤ ³ ± ¬ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¶ Ä Å ±
! " # $ % ! & ' % ( )* + * , - . / 0 1 2 3 4 5 6 1 4 7 8 9 1 : : 7, ; < , - * = * * = - <> 7 8 ? 1 4 5 @ 3 / 8 7 1 4 A 3 3 .A 8 / 4 1 ? B *C , D D 9 * D D D 6E 6 1 4 * D D D - C F 1 = 5 6 . A G 6 8 8 * D D 6 1 3 4 * D - * D D * D -E 6 1 4 * D D D F 6 8 7 H H D G 6 8 8I A . B - - * D D < C F 1 = 5 6 . A G 6 8 8I A . B * - * D D < C F 1 = 5 6 . A G 6 8 8I A . B H - * D D < C F 1 = 5 6 . A G 6 8 8I A . B < - * D D < C F 1 = 5 6 . A G 6 8 8
< D D < D - < D D < D D 4 J 6 4 J 6 4 J 6 4 J 6 4 J 6 K D C F K D K D C - + ; C ; 4 J 6 4 J 6 4 J 6
L M
N O M M
P
* C F H * D D F D D D H + D D 4 J 6I A . B - - * D D 6 - D 6 - * K - * K - H *I A . B * - * D D 6 - D 6 - * D - * * - * ;I A . B H - * D D 6 - D 6 - * < - * - - - ;I A . B < - * D D 6 - D 6 - - H - - ; - * D
4 J 6
? Q
R S S T U V W X Y Z [ \ ] U ^ W [ V _ ` S [ a b ` W U c ` ^ ^ Z ` S S d e _ f \ [ U V f g _ U b W [ g [ _ ` W [ f ^ [ V ` h ` [ S ` a S U [ ^ W i U X ^ j [ ^ U U b [ ^ j k U \ ` b W ] U ^ W lm f b ] V n o p q r m s t q s u W i b f Z j i n o p q r m s t q v w
x y z | ~ z z ~ ~ ~ ~ ~ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « § ¦ ¬ ® ¯ ¡ ° ¥ £ ¤ ¥ ¦ ¥ ± ± ± ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² · ª ª ¥ § ¸ ³ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² · ª ª ¥ § ¥ § © ± µ ¶ § ² · ª ª ¥ ¬ · ¡ ¤ £ £ ± ¹ ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ± ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ³ ± µ ¶ § ² · ª ª ¥ § ¸ µ ¶ § ² · ª ª ¥ ³ © ½ § ¾ ± ± £ µ ¶ § ² · ª ª ¥ ¹ ³ ¹ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¹ ¾ ¡ ª « ¿ § ¥ ¯ ¨ ¢ ³ ¹ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¾ À ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± § ² ² ± ± µ ¶ § ² · ª ª ¥ © ½ § ¾ ¹ § ² ¥ ¡ § ¨ ¥ ª ¥ § ¥ ª ¡ ¿ À ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ¹ ¹ ³ ³ µ ¶ § ² · ª ª ¥ ¯ ¨ ¢ ¹ ¹ µ ¶ § ² · ª ª ¥ ¯ ¨ ¢ ¹ ¬ ® ¯ ¡ ° ¥ £ ¤ ¥ ¦ ¥ Â § ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ Á ¼ ± ± ¡ º £ ¤ ¥ ¦ ¥ Â ¯ ± © ¾ Ã ² · ¬ ¥ Ã ² · ¶ ¥ ¡ ² ¬ £ ¦ ¹ § ¥ § ² ² ± ± Á Á ± µ ¶ ¾ Ã º « ¥ Ã « ¥ ¿ ° ¤ ³ ± ¬ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¶ Ä Å ±