siemnes palicaion de ct y tp

Upload: rodolfoordiguez70

Post on 02-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    1/27

    Power Transmission and Distribution

    Author

    Page 241 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Basics of

    Current and Voltage Transformers

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    2/27

    Power Transmission and Distribution

    Author

    Page 242 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    2

    1

    12

    N

    N= II

    R1jX1 jX2 R2I1 I2

    Zb

    S2P2 Ideal CT

    S1P1 Im

    N1 N2 ZmU

    2

    Equivalent current transformer circuit

    X1 = Primary leakage reactance

    R1 = Primary winding resistance

    X2 = Secondary leakage reactanceZ0 = Magnetizing impedance

    R2 = Secondary winding resistance

    Zb = Secondary load

    Note: Normally the leakage fluxes X1 and X2 can be neglected

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    3/27

    Power Transmission and Distribution

    Author

    Page 243 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    jX2

    i2 ZBi1

    1 : N2

    R2

    RB

    i'1= i1 i21

    N2

    LW

    L2

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    4/27

    Power Transmission and Distribution

    Author

    Page 244 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    N1

    I1

    I2

    N2

    Zb

    I2

    I1

    Im

    . N1N2

    Current transformer:Phase displacement () and current ratio error ()

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    5/27

    Power Transmission and Distribution

    Author

    Page 245 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    CT classes to IEC 60044-1: 5P or 10P

    Specification: 300/1 A 5P10, 30 VA

    5% accuracyat I= n x In Accuracy

    limit factor ALF

    Rated burden

    (nominal power) PNBRatio In -Prim / In -Sek.

    BBPiP

    NBPiPALFALF+

    +='

    Actual accuracy limit factor

    in operation is higher as the CT

    is normally underburdened :

    Operating ALF: ALF

    Dimension criterium:

    TFK

    n

    I

    SCIALF max'

    KTF (over-dimensioning factor) considers the single sided CT over-magnetising due to the d.c.

    component in short circuit current ISC.

    KTF values required in practice depend on relay type and design.

    Recommendations are provided by manufacturers (see Application Guides)

    RCT

    5 Ohm

    CT2

    .seci RIP =

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    6/27

    Power Transmission and Distribution

    Author

    Page 246 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    UKN

    10 %

    50 %

    U2

    Im

    Definition of the CT knee-point voltage

    IEC 60044-1 Class PX

    formerly

    British Standard BS3938:

    Class X

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    7/27

    Power Transmission and Distribution

    Author

    Page 247 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Accuracy classCurrent error

    at nominal

    current (In)

    Angle errorat rated current

    In

    Total error at n x In

    (rated accuracy limit)

    5P

    10P

    1 %

    5%

    60 minutes 5 %

    10 %

    IEC 60044-1 specifies the following classes:

    Current transformer, Standard for steady-state performance

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    8/27

    Power Transmission and Distribution

    Author

    Page 248 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformers, Standard for transient performance

    IEC 60044-6 specifies four classes:

    Class

    Ratio error Angle error

    Maximum error at

    rated accuracy limit

    TPX(closed iron core)

    TPYwith anti-remanence

    air gap

    TPZlinear core

    30 min

    30 min

    180 18 min

    0,5 %

    1,0 %

    1,0 %

    %10

    only)current(a.c.

    %10

    %10

    Error at rated current

    TPSclosed iron core

    Special version for high impedance protection

    (Knee point voltage, internal secondary resistance)

    Remanence

    no limit

    < 10 %

    negligible

    No limit

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    9/27

    Power Transmission and Distribution

    Author

    Page 249 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformer saturation

    Steady-state saturation with AC current

    Transient saturation with offset current

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    10/27

    Power Transmission and Distribution

    Author

    Page 250 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    S

    ISC

    Im

    DC flux non-saturated

    AC flux

    Magnetising current

    Short circuit current

    Transient CT saturation due to DC component

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    11/27

    Power Transmission and Distribution

    Author

    Page 251 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Pprimary current

    TN

    B

    total flux

    a.c. flux

    transientd.c. flux

    BMax

    B~

    t

    t

    d.c. component

    B~

    )(

    1 TSt

    TN

    t

    SN

    SN

    ~

    += ee

    TT

    TT

    B

    B

    TNTS

    TS

    S

    NS

    Max1

    ~

    +=T

    TT

    B

    B

    N

    S

    NS

    SN

    MaxBnT

    Tl

    TT

    TTt =

    tan

    1

    Bi

    W

    S

    =

    +=

    RR

    LT

    [ ]

    [ ]ms10900

    min

    S

    =TFor 50 Hz:

    Course of CT-flux during off-set short-circuit current

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    12/27

    Power Transmission and Distribution

    Author

    Page 252 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    CT transient over-dimensioning factor KTF

    KTF

    TS [ms]

    50 100 150 200

    10

    2

    0

    3

    0

    4

    0

    5

    0

    6

    0

    100

    250

    500

    1000

    5000

    (KTF 1+TN)

    Closed iron core

    Linear core

    TN = network time constant

    (short-circuit time constant)

    TS = CT secondary time constantTN [ms]

    NS

    S

    TT

    T

    S

    N

    STF

    1

    += TT

    TK

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    13/27

    Power Transmission and Distribution

    Author

    Page 253 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthorTp

    +=N

    M

    TFT

    t-

    e-1N1 TK'

    N

    NNTF 11

    R

    XTK +=+=

    0 20 40 60 80 100

    5

    10

    15

    40 ms

    50 ms

    30 ms

    10 ms

    20 ms

    tM

    Ktd

    [ ms]

    Mt

    14

    6

    CT with closed iron core,

    Over-dimensioning factor KTF

    for specified time to saturation (tM

    )

    :tM

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    14/27

    Power Transmission and Distribution

    Author

    Page 254 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    0 20 40 60 80 1000

    20

    40

    60

    80

    100

    120

    140

    160

    180

    0 20 40 60 80 1000

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4

    KTF

    TN in ms

    10 ms

    8 ms

    6 ms

    4 ms

    2 ms

    2 ms

    6 ms4 ms

    8 ms

    10 ms

    tM

    tM

    (tM,TN)(el. degree)

    CT over-dimensioning factor KTF (tM,TN)

    in the case of short time to saturation (tM)

    TN in ms

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    15/27

    Power Transmission and Distribution

    Author

    Page 255 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformer

    magnetising and de-magnetising

    P

    BBMax

    m

    BR

    t m

    BMax

    BR

    B

    t

    ( ) TSt

    RMax.R

    += eBBBB

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    16/27

    Power Transmission and Distribution

    Author

    Page 256 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformer

    Course of flux in the case of non-successful auto-reclosure

    tF1 tDT tF2

    tF1 = duration of 1st fault

    tDT dead time

    tF2 =duration of 2nd fault

    B

    t

    Bmax

    ++

    +

    +=

    S

    F2

    N

    F2

    SN

    SNS

    F2DT

    S

    F1

    N

    F1

    SN

    SN Tt

    Tt

    (

    1Ttt

    Tt

    Tt

    (

    1~

    maxee

    TT

    TTeee

    TT

    TT

    B

    B

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    17/27

    Power Transmission and Distribution

    Author

    Page 257 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformer

    magnetising curve and point of remanence

    BI II III

    H = imw

    I: closed iron core (TPX)

    II: core with anti-remanence air-gaps (TPY)

    III: Linearised core (TPZ)

    up to 80%

    < 10%

    negligible

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    18/27

    Power Transmission and Distribution

    Author

    Page 258 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Current transformers TPX und TPY

    Course of the flux with non-successful auto-reclosure

    tF1 tDT tF2 t

    BR

    BR

    closed iron core (TPX)

    core with anti-

    remanence air-gaps (TPY)

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    19/27

    Power Transmission and Distribution

    Author

    Page 259 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Standards of voltage transformers

    Class

    designation

    5P

    3P

    Voltage error FU Angle error

    Permissible error at 0.05 UN and 1.0 UN

    3.0 %

    6.0 %

    120 minutes

    240 minutes

    Class

    designation at 1.0 UN at 1.0UN

    0.1

    0.2

    0.5

    1

    3

    0.1

    0.2

    0.5

    1

    3

    10

    5

    20

    30

    Not determined

    Permissible voltage error in % Permissible angle error in minutes

    VT classes to IEC 60044-2

    VT classes for measurement IEC 60044-2

    All 3P and 5P protection CTs must

    additionally comply with one of the

    below VT metering classes!

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    20/27

    Power Transmission and Distribution

    Author

    Page 260 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Capacitive voltage transformer,

    Equivalent circuit

    ZBLF CF

    RF 100 V

    3

    20 kV

    3

    400 kV

    3

    C1= 5 nF

    C2= 95 nF

    R'BLF CF

    RFLTRT

    CT

    CE= C1+ C2

    RE

    LO

    U*1= UP C1

    C1+ C2U*2

    L'B

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    21/27

    Power Transmission and Distribution

    Author

    Page 261 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Legend:

    UP(t) Primary voltage

    US(t) Secondary voltage

    (1) Fault inception

    (2) Aperiodic damping of US(t)

    (3) Periodic damping of US(t)

    Time

    Tsin ms

    Ratio

    Classes

    3PT1

    6PT1

    3PT2

    6PT2

    3PT3

    6PT3

    10 --- 25 4

    20 10 10 2

    40 10 2 2

    60 10 0.6 2

    90 10 0.2 2

    %100U2

    )t(U

    s

    s

    t

    Measured voltage transients after fault at

    voltage maximum and zero-crossing

    (Example)

    Recommendations to IEC 60044-5

    Transient performance of CVTs,

    Recommendations acc. to IEC 60044-5

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    22/27

    Power Transmission and Distribution

    Author

    Page 262 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    BCT

    BNCT

    B

    BNiALF

    i RR

    RR

    PP

    PPALFALF'

    +

    +=

    +

    +=

    rated CT burden: PBNinternal burden of the CT: Pi=RiI2N

    2

    Actual connected burden : PB= RBI2N2

    RB=Rl+RR= burden resistance

    Rl= resistance of connecting cables

    RR= burden resistance of the relayBNCT

    BCT

    BNi

    BALF'i

    RR

    RR

    PP

    PPALF'ALF

    +

    +=

    +

    +=

    N

    KOD

    I

    IK' ALF No saturation

    for the total

    short-circuit duration:N

    N

    N

    ~

    Max

    TF 11R

    XT

    B

    BK' +=+==

    +=

    S

    M

    N

    M

    SN

    SN

    T

    t

    T

    t

    (

    1 eeTT

    TTTFK ''

    No saturation for

    the specified time tM:mTFODKKK

    Re

    100

    Remanence%1

    1K mRe

    =

    with

    CT dimensioning

    Theory:

    Practice:

    TFKODK =

    Remanence only considered in extra high voltage systems (EHV)

    KTF-values acc. to relay manufacturers guides

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    23/27

    Power Transmission and Distribution

    Author

    Page 263 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    Practical CT requirements

    Transient over-dimensioning factors KTF

    (AR not considered)

    5KTF

    Distance

    7SA6 and 7SA522 30ms)Tif1(2K NTF >setting/ IN, at least 207SJ56

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    24/27

    Power Transmission and Distribution

    Author

    Page 264 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    CT dimensioning for

    Example differential protection (1)

    1. Calculation of fault currents

    Net

    IL IL IT

    F1 F2 F3 F4

    7UT617SD61

    Impedances related to 20 kV:

    [ ]

    0.13

    3000

    220

    MVA''SCS

    2kV2NU

    N Z:Net ==

    =

    [ ][ ]

    1.2100

    %12

    40

    220

    100

    %

    MVAT-NP

    2kV2NU

    T Z:Transf. ==

    = Tu

    [ ] [ ] 3,20,48/km'LzkmlL Z:Line ===

    Impedances related to 110 kV:

    [ ]

    4.03

    3000

    2110

    MVA''SCS

    2kV2NU

    N Z:Net ==

    =

    110 kV, 3 GVA

    110/20 kV

    40 MVA

    uT=12%OH-line:

    l = 8 km,zL= 0,4 /km

    300/1A 1200/1A 200/1A 200/1A

    [ ][ ]

    36.3100

    %12

    40

    2110

    100

    %

    MVAT-NP

    2kV2NU

    T Z:Transf. ==

    = Tu

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    25/27

    Power Transmission and Distribution

    Author

    Page 265 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    F1 kA17.34.03

    3110kV/1.1

    NZ

    3/NU1.1F1I =

    =

    =

    kA1.7336.34.03

    3110kV/1,1

    TZNZ

    3/NU1.1F2I =

    +

    =

    +

    = kA2.83.21.20.13

    320kV/1,1

    LZTZNZ

    3/NU1.1F4I =

    ++=

    ++=F2

    Dimensioning of the 110 kV CTs for the transformer differential protection:

    Manufacturer recommends for relay 7UT61: 1) Saturation free time 4ms for internal faults2) Over-dimensioning factor KTF 1,2

    for through flowing currents (external faults)The saturation free time of 3 ms

    corresponds to KTF 0,75See diagram, page 59

    Criterion 1) therefore reads:

    43300

    173000,75

    NI

    F1ITFKALF' == 7

    300

    17301,2

    NI

    F2ITFKALF' ==

    For criterion 2) we get:

    kA9.551.20.13

    320kV/1.1

    ZZ

    3/U1.1I

    TN

    NF3 =

    +

    =

    +

    =F3

    F4

    The 110 kV CTs must be dimensioned according to criterion 1).

    CT dimensioning for

    Example differential protection (2)

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    26/27

    Power Transmission and Distribution

    Author

    Page 266 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    CT dimensioning for

    Example differential protection (3)

    We try to use a CT type: 300/1, 10 VA, 5P?, internal burden 2 VA.

    1.1643102

    5.22' =+

    +=

    +

    + ALF

    ratedP

    iP

    operationPiPALF

    Specification of the CTs at the 20 kV side of the transformer:

    Chosen, with a security margin : 300 /1 A, 5P20, 10 VA, R2 2 Ohm (Pi 2VA)

    It is good relaying practice to choose the same dimensioning as for the CTs on the 110 kV side:

    1200/1, 10 VA, 5P20, R2 2 Ohm (Pi 2VA)

    Dimensioning of the 20 kV CTs for line protection:

    For relay 7SD61, it is required: 1) Saturation free time 3ms for internal faults

    2) Over-dimensioning factor KTF 1.2for through flowing currents (external faults)

    24200

    95500.5

    NI

    F3ITFKALF' == 8.16==

    200

    28001.2

    I

    IKALF'

    N

    F4TF

    The 20 kV line CTs

    must be dimensioned

    according to criterion 1).

    (Connected burden estimated to about 2.5 VA)

    The saturation free time of 3 ms corresponds

    to KTF 0.5See diagram, page 59

    Criterion 1) therefore reads: For criterion 2) we get:

  • 8/11/2019 Siemnes Palicaion de Ct y Tp

    27/27

    Power Transmission and Distribution

    Author

    Page 267 2007-08

    Copyright Siemens AG 2007. All rights reserved.

    PTD SE PTIAuthor

    For the 20 kV line we have considered the CT type: 200/5 A, 5 VA, 5P?, internal burden ca. 1 VA

    8245111' =++=

    ++ ALF

    ratedPiPoperationPiPALF

    Specification of line CTs:

    We choose the next higher standard accuracy limit factor ALF=10 :

    Herewith, we can specify: CT Type TPX, 200/5 A, 5 VA, 5P10, R2 0.04 Ohm ( Pi 1 VA)

    (Connected burden about 1 VA)

    CT dimensioning for

    Example differential protection (4)