should we keep do for nitrification...
TRANSCRIPT
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
SHOULD WE KEEP DO FOR NITRIFICATION CONTROL?
THE PROOF IS IN THE AMMONIUM ELECTRODES
Robert Lagrange1*, Sue Baert
2, Amanda Poole
3, Dave Green
3 and Nick Camin
4
1Lagrange Consulting, 4310 Royal Mustang Way, Snellville, Georgia, USA, 30039
(*correspondence: [email protected]) 2Wheaton Sanitary District, 1S640 Shaffner Road, Wheaton, Illinois, USA, 60189
3Baxter & Woodman Inc., 39 South LaSalle Street, Suite 816, Chicago, Illinois, USA, 60603
4Endress+Hauser Inc., 2350 Endress Place, Greenwood, Indiana, USA, 46143
KEYWORDS
Process Control, Optimization, Nitrification, Ammonium, Dissolved Oxygen, Energy Consumption,
Compliance, Instrumentation
ABSTRACT
Aeration often is the process that consumes the most energy in a wastewater plant. At the same time it
is an essential process to maintain compliance for BOD and Ammonia limits. It thus deserves a lot of
attention.
The use of dissolved oxygen measurement to control aeration is widely accepted. The literature has
many examples of excellent return on investment in wastewater plants that have implemented this
control. There are even theories that a concentration of 2 mg/l is the perfect value. But a DO sensor
only tells how much oxygen has not been used in the process and at times this measurement may not
bring the expected results. The effluent may end up out of compliance or too much energy can be
spent. Examples are available.
As one of the main objectives of the aeration tank is nitrification the measurement of the concentration
of ammonium or ammonia provides much better information than dissolved oxygen. Ion Selective
Electrodes (ISE) installed directly in the tank eliminate the need for sampling line and ensure an easier
integration. Their selectivity, accuracy and lower maintenance make them an attractive solution. As
demonstrated at Wheaton and Colorado Springs, additional energy savings and compliance are
possible when using either ammonia in a cascade loop with DO control or in direct control of the air
flow. Direct control either in feed-forward or feed-back provide faster and better response when spikes
are present.
The return on investment is very good even on smaller plants and compliance is achieved.
Dissolved oxygen concentration remains an important factor as it affects the quality of the sludge. The
control strategy has to maintain it within limits.
Lagrange, Baert, Poole, Green & Camin 2
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
INTRODUCTION
Many wastewater plants around the world are working hard to reduce their energy consumption and
the amount of nutrients discharged in their effluents.
As both carbon removal and nitrification consume oxygen it is important to insure that oxygen is
present in the right amount in the aeration tank. Dissolved Oxygen Instruments (DO) are typically used
for this application. But they are only an indication of the amount of free oxygen available at the
measuring point. The measurement of the amount of air sent to the tank provides the additional data to
determine the oxygen uptake rate.
In this paper the data from Wheaton Sanitary District (Illinois) provides the base for the discussion and
data from other sources will be added to confirm the findings: the installation of instruments for
automatic control is justified for small to large plants.
THE GOOD AND THE BAD OF DISSOLVED OXYGEN MEASUREMENT
The good
The literature abounds in examples of plants using DO to control the airflow to the aeration tank. The
return on investment is good even for small plants.
Eagle Lake Sewer Utility District in Wisconsin treats only 0.26 MGD and was able to justify the
installation of an optical DO instrument with the additional benefit of reduced maintenance cost
(Kohlmann, 2010).
As water and wastewater consume about 4% of the energy produced in the USA, power companies
have shown a big interest in promoting DO control associated with blowers with Variable Frequency
Drive (VFD). The Tennessee Valley Authority (TVA) sponsored demonstrations in real life at existing
wastewater plants. A result is shown in Figure 1.
Lagrange, Baert, Poole, Green & Camin 3
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
Figure 1 TVA demonstration
The Installation of DO sensors and VFD’s provided a 13% reduction in consumption and most
importantly a 39% reduction in peaks with the corresponding rate change..
More recent data shows that reduction in consumption of up to 50 to 60 % can be achieved and 80%
when new diffusers are used (Poole, 2011)
The bad
As we said earlier DO only shows the residual amount of oxygen available in the tank. It certainly does
not define the elimination of carbon nor does it tell precisely what is happening with nitrification or
denitrification.
The Hanover Area Regional WWTP (Pennsylvania) installed Ion Selective Electrodes instruments in
their oxidation ditch. For the initial period the data, Ammonium and Nitrate concentrations, were
recorded but not available to the operators. They had the information from a flowmeter, a DO and a
NADH (Fluorescence of nicotinamide adenine dinucleotide) to operate the plant. The surface aerators
had only 2 speeds. (Lagrange, 2009)
Figure 2 shows the location of those instruments at about 1/3rd
of the tank.
Lagrange, Baert, Poole, Green & Camin 4
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
Figure 2: Location of the instruments at Hanover
Figure 3 Hanover Data
Figure 3 shows the data for almost a week of operation. In the initial part the DO value does not
change while both the flow and the ammonium concentration (scaled 0 to 15 mg/l) change. As a result
the effluent was out of compliance. Then the aerator speed is finally adjusted between high and low to
follow the diurnal flow variations. The ammonium concentration is drastically reduced. Too much in
fact as at 1/3rd
of the ditch it is already below 2 mg/l. The plant was expecting to see some
denitrification taking place at low aerator speed (nitrate concentration scaled 5 to 25 mg/l). Again it is
not happening. The plant was using far too much energy.
Lagrange, Baert, Poole, Green & Camin 5
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
EXPERIENCE AT WHEATON SANITARY DISTRICT
The Wheaton Sanitary District is also looking at ways to maintain or improve the quality of its effluent
while reducing the consumption of energy. A new turbo blower was installed in 2011 to replace an
existing multistage centrifugal blower. Then a joint project was started with Baxter & Woodman to
find the best control strategy for that specific plant. Endress+Hauser Inc and WTW (now Xylem)
provided instrumentation assistance for the project.
The plant is designed to treat a dry weather flow of 8.9 million gallons per day (MGD), a design
maximum flow of 19.1 MGD and a peak wet weather flow of 45 MGD. The effluent is discharged in
Spring Brook with very low flow that dictates the willingness of the District to discharge effluents with
a quality well above their discharge permit.
The treatment consists of screens, sand, grease and fat removal, primary clarification, trickling filter,
aeration, secondary clarification, filtration and disinfection. The District has 5 aeration tanks in
parallel. Each equipped with one Air Flow measurement and one DO measurement. For the test one
Ion Selective Electrode (ISE) based measurement for ammonium was installed toward the start of tank
2 and another at the end of tank 3
Figure 4: Wheaton aeration showing the location of the instruments
Lagrange, Baert, Poole, Green & Camin 6
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
Step 1 Air Flow Control
After the installation of the new blower the first step was to maintain a constant air flow to each tank.
With this in place the DO concentration keeps changing reverse tracking the ammonium concentration
measured close to the inlet in tank 2 as expected. During that time the ammonium concentration in
tank 3, measured close to the end of the tank, remains constant around 0.4 mg/l very close to the limit
of detection of the instrument. This confirms that nitrification is complete. In the final effluent, after
some post aeration, the ammonia concentration is at a non detectable level in laboratory samples
(<0.05 mg/l)
Figure 5: Tank2 in airflow control mode
A 28% energy consumption saving was achieved, 10% of which can be attributed to the control itself
Step 2 DO Control
In that phase the control objective is to maintain a constant DO. With the correct DO set point there
should be enough air to keep the solids in suspension and prevent settling in the aeration tank.
Lagrange, Baert, Poole, Green & Camin 7
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
In that period, as can be seen in figure 6 there were some ammonium spikes the largest and with
highest rate of increase was on January 14. The control reacts well with that spike. As the DO
measurement is located toward the end of the tank, some 20 feet, the control had difficulty to keep up
with the fast change resulting in a very small blip on the effluent ammonium measurement. The change
is less than 0.2 mg/l increase.
There was a 9% increase in energy consumption compared with the period with airflow control.
Figure 6 DO Control
Step 3 Ammonium Control
Figure 7 compares tank 2 in ammonium control with tank 3 in airflow control. The variations in DO
concentration are drastically reduced and in tank 3 the process remains under control with the big spike
Lagrange, Baert, Poole, Green & Camin 8
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
of ammonium on January 28/29. At the same time with the same wastewater in tank 3 the oxygen is
completely depleted and the nitrification is not complete.
The use of ammonium in feed-forward provides a better control, more stable process and insures that
the concentration of ammonia in the effluent remains at the low level desired by Wheaton.
Figure 7 Feed forward NH4 control
ISE A BETTER TOOL
When normalizing for changes in flow and BOD load the results favor ammonium control
• Step 2 consumes 5% more energy
• Step 3 consumes 6% less energy.
From Wheaton’s point of view achieving a stable process while maintaining their very low ammonia
discharge justified the investment to install one ISE instrument in the splitter box ahead of the 5
aerations tanks and modify the control strategy to feed-forward control. The decommissioning of the
Lagrange, Baert, Poole, Green & Camin 9
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
trickling filters will bring a higher nutrient load to the aeration tank allowing for a more efficient
control as the low limit on air flow from the blower will be prevented. As we can see in figure 7 there
is margin to reduce the energy consumption.
Colorado Springs Utilities
Colorado Springs Utilities (Lagrange, 2011; Camin, 2011) with a different set of problems took a
different approach. That plant faces very high daily ammonia peak while trying to run only their small
compressor. Designed for 20 MGD the actual flow was only 8 MGD at the time of the study, While on
DO control (those DO units were installed at construction time) the plant faced some high ammonia
concentration in the effluent or at other times low pH as nitrification consume alkalinity. The decision
was then made to install ISE measurement for both ammonium and nitrate as some denitrification was
implemented to increase alkalinity. The locations are described in figure 9.
Figure 8 Concentration of influent ammonia in green and power consumption at CSU
Lagrange, Baert, Poole, Green & Camin 10
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
Figure 9 Installation point for the instruments at CSU
To increase the speed of response of the control loop the air flow is directly controlled based on the
ammonium concentration. The control takes into account the DO concentration to maintain it within
high and low limits.
With that control strategy CSU was able to reduce the cost of energy while the flow increased as
shown in figure 10 for the months of November 2009 and November 2010.
Lagrange, Baert, Poole, Green & Camin 11
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
Figure 10 CSU flow and cost
The consumption of energy per MGD per pound of ammonia nitrified was reduced by 12% compared
with standard DO control. In the future the Ammonium sensor after the primary will be relocated to the
swing zone to combine feed-forward and feedback.
Others
The city of Peoria, Arizona, operated their Beardsley Road Water Reclamation Facility, a 4 MGD
plant, with a cascade control where the output of the Ammonium controller adjusts the set point of the
DO control loop. They were able to achieve a 3 months return on investment and improve the sludge
quality. (Dabkowski, 2011)
Rieger (2012) also demonstrated in three wastewater plants with average flows of 3.5, 10.5 and 54
MGD in Switzerland that the use of ammonium control provides benefits on other processes such as a
reduction in the consumption of chemicals for phosphorus removal as more volume can be used in
anaerobic phase.
Lagrange, Baert, Poole, Green & Camin 12
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
SUMMARY
Wheaton Utilities District decided to use a control strategy based on feed-forward based on ammonium
concentration as it provides them with the best results for their objectives. Colorado Springs used a
partial feedback and achieved excellent results. Peoria included the ISE in a cascade control for a high
return on investment.
Further reading is available. (Grievson, 2012)
We would like to leave the final comments to Leiv Rieger
“Ammonia controlled aeration in an activated sludge system leads to a significant reduction of the total
energy consumption in conjunction with decreased effluent concentrations of total nitrogen…..The
best solution will be the simplest concept that still yields a significant benefit in comparison with the
annual costs.”
LIST OF ACRONYMS:
ISE ................. Ion Selective Electrode
DO .................. Dissolved Oxygen
NADH ........... nicotinamide adenine dinucleotide (fluorescence of)
CSU................ Colorado Springs Utilities
MGD .............. Million Gallons per Day
Lagrange, Baert, Poole, Green & Camin 13
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
REFERENCES
Camin & al. Ammonia Based Aeration Control Workshop 105 WEFTEC 2011
Dabkowski & al. Ammonia Based Aeration Control Workshop 105 WEFTEC 2011
Kohlmann. Saving costs by continuous monitoring of D.O. in plant Application Note Endress+Hauser
Inc. 2010
Grievson Aeration Control in wastewater activated sludge plants using mixed liquor, organic loading
and ammonia analysis Water Industry Process Automation & Control Group, March 2012
https://www.onlinefilefolder.com/2s7lVnXAEb7zZW
Lagrange & al. The revival of the Ion Selective Electrode Applications in Wastewater Plants ISA Expo
2009
Lagrange & al. A change in control strategy reduces power consumption at Colorado Springs Utilities
Energy & Water 2011
Poole & al. Aeration System Automation: Control Strategies to Maximize Energy Savings at Low
Capital Cost WaterCon 2012
Rieger & al. Improving Nutrient Removal While Reducing Energy Use at Three Swiss WWTPs Using
Advanced Control Water Environment Research, Volume 84, 2012
Lagrange, Baert, Poole, Green & Camin 14
Presented at the 2012 ISA Water / Wastewater and Automatic Controls Symposium
Holiday Inn Castle Resort, Orlando, Florida, USA – Aug 7-9, 2012 – www.isawwsymposium.org
About the Authors:
Robert Lagrange, PhD is a Doctor in Physics from the University of Grenoble, France. After 11 years
with Endress+Hauser as Business Manager Water and Wastewater Robert is now working part time as
a consultant. Robert presented multiple times at the ISA WWACS and is a member of WEF and
AWWA instrumentation and control committees
Sue Baert, B.Sc. is the Plant Superintendent at the Wheaton Sanitary District where she started as a
chemist became the Lab Manager and wrote the Quality Assurance Project Plan for the stream water
quality project, collected, analyzed and submitted the data. She has a degree in Biology/Chemistry
from the UW-Lacrosse. Sue is involved with the DuPage Salt Creek watershed group as Vice-
President. She is an active member of WEF through the local MA Central States Water Environment
Association (CSWEA). She was President of the Illinois section of Central States for a one year term,
and then Illinois Trustee to the Executive staff for two years. In all, her career in the water/wastewater
section has spanned over 22 years.
Amanda Poole, M.Eng. is an environmental engineer at Baxter & Woodman, where she focuses on
energy reduction and generation measures at wastewater treatment plants. Amanda has been involved
in numerous wastewater treatment plant energy audits and aeration energy reduction projects
throughout the Chicago area. Amanda received her B.S. and M.S. in Environmental Engineering from
the University of Illinois in Urbana – Champaign. She has been working in the water/wastewater sector
for the past 3 years and awaits her P.E. licensure in December 2012. She is an active member of the
Central States Water Environment Association.
David Green, AAS EET joined Baxter & Woodman in 2008 as a Senior Systems Integrator. Dave’s
passion for automation and innovation led him to become the Automation Technical Director. He
brings over 16 years of experience designing and providing unique solutions to Automated Systems
Integration projects. He has quickly become a technical leader in the organization, and has a hunger
for learning new technology and finding the best solutions for automation problems.
Nick Camin, BSEE, MBA has worked in the instrumentation field for over thirteen years specializing
in environmental industry applications for over ten of them. Nick is a graduate of Purdue University
with a bachelor of sciences degree in electrical engineering and he also holds a master of business
administration degree from Indiana Wesleyan University. With Endress+Hauser he has held the
positions of application engineer, project manager, municipal business manager, regional sales
manager and currently he is marketing manager for the environmental industry. Nick is a member of
WEF and AWWA instrumentation and control committees.