shelter system multiple noise analysis and design in...
TRANSCRIPT
Shelter System Multiple Noise Analysis and Design in order to meet
MIL-STD-1474 Noise Limits Spec
Sockkyu LEE1; Ingi BAEK2; Sanghyun KIM3; Jeung LEE4; Jiho CHOI5
Mechanical Engineering R&D Lab, LIGNex1 Co., Ltd. , Korea
ABSTRACT
Shelter System is a control center for military purposes and is used for controlling reconnaissance system,
missile system, etc. The outside shape of the Shelter System is similar to a container carried by a cargo ship.
In the interior of the Shelter System there are several pieces of noise-producing electronic equipment such as
workstations, fans and air conditioners. As the internal operators of the Shelter System conduct several
specific missions over a long period of time in this noisy environment, one of the most important
specifications for the Shelter System is the internal noise level in the operator’s ear. In this paper, as
MIL-STD-1474 Noise Limits required by MIL-STD-1472 Human Engineering, it requires under 65 dB (a) or
75dB (a) noise level in the operator’s ear. So, to predict the at-ear position, we first measured the component
noise level at various locations - workstations, fans, air conditioners, etc. We then analyzed Multiple Noise
with measured data and related numerical formula considering position and modified factors. Also we
analyzed Multiple Noise with Actran, acoustic analysis software. So we suggested the design to meet Noise
Limits Spec. After the manufacture, we tested the noise level and compared it with the prediction.
Keywords: Multiple noise, Shelter System, Equipment noise, MIL-STD-1474 Noise Limits
1. INTRODUCTION
Shelter System is a control center for military purposes and is used for controlling reconnaissance
systems, missile systems, etc. The outside shape of the Shelter System is similar to a container carried
by a cargo ship. In the interior of the Shelter System there are several pieces of noise-producing
electronic equipment such as workstations, fans and air conditioners. The shape is shown in Fig. 1.
Figure 1 Shelter System
As the internal operators of the Shelter System conduct several specific missions over a long period
of time in this noisy environment, one of the most important specifications for the Shelter System is
the internal noise level in the operator’s ear. In this paper, it is assumed that the duty is 8 hours
1 [email protected] 2 [email protected] 3 [email protected] 4 [email protected] 5 [email protected]
INTER-NOISE 2016
6174
without hearing protection devices. So, the goal of noise limits is the range of Zone E, below Fig. 2.
Figure 2 Permissible noise exposure limits in MIL-STD-1472G(1)
Zone E, Maximum exposure without protection: For exposures of less than 8 hours, personnel
without hearing protection shall not be exposed to noise levels exceeding 84 dB(A). When personnel
remain for more than 8 hours in spaces with a high noise level, an Leq(24) of 80 dB(A) shall not to be
exceeded. Consequently, for at least a third of each 24 hours, the personnel shall be subject to an
environment with a noise level not exceeding 75 dB(A).(1)
As MIL-STD-1474D Noise Limits required by MIL-STD-1472G Human Engineering, it requires
under 65 dB (A) or 75dB (A) noise level in the operator’s ear because of category E or F as the
frequency of conversation. In the study, it is assumed that the goal noise limits is category E, 75dBA.
The noise limits in MIL-STD-1472D is shown in Tab.1 and 2.
Table 1 Steady-state noise categories in MIL-STD-1474D(2)
Category System Requirements
A No direct person-to-person voice communication required. Maximum design limit. Hearing
protection required.
B Electrically-aided communication via attenuating helmet or headset required. Noise levels are
hazardous to unprotected ears.
C No frequent direct person-to-person voice communication required. Occasional shouted
communication may be possible at a distance of 30 cm. Hearing protection required.
D
No frequent person-to-person voice communication required. Occasional shouted
communication may be possible at a distance of 60 cm. Levels in excess of Category D require
hearing protection.
E Occasional telephone or radio use or occasional communication at distances up to 1.50 m
required. (Equivalent to NC-70)
F Frequent telephone or radio use or frequent communication at distances up to 1.50 m required.
(Equivalent to NC-60).
Table 2 Steady-state noise limits (dBA) for personnel-occupied areas in MIL-STD-1474D(2)
Limit Category A B C D E F
A-Weighted Limit (dBA) 108 100 90 85 75 65
SIL-4 Limit 67 57
INTER-NOISE 2016
6175
2. NOISE SOURCE MEASUREMENT AND NOISE LEVEL ESTIMATION
2.1 Noise Source Measurement(10)
In order to estimate the noise at the ear position, we first measured the component noise level at
various locations - workstations, ventilator fans, air conditioners, etc.
Shelter system, since a plurality of internal noise source generates noise at the same time,
becomes audible to the production of a composite noise form. Therefore, the noise of the noise
source measured, in consideration of the value and quantity, and calculates the equivalent noise level.
Then, reflecting the impact of the distance spaced apart to the point you want to know, and calculates
the final composite noise. So, at the first, noise source was measured as each condition and distance.
The Main noise source is shown in Tab. 3.
Table 3 Internal Main noise sources of Shelter
Units Cabinets
Ventilator Airduct #1 #2 #3
Workstation 5ea 2ea - - -
VME rack 2ea - - - -
UPS 1ea - - - -
Data recorder - 1ea - - -
Backbone S/W - 1ea - - -
Server unit - - 3ea - -
Data processor - - 4ea - -
Ventilator Fan - - - 3ea -
Air-conditioner - - - - 2ea
2.1.1 Workstation In order to measure the max noise level, we gave the simulated load to workstation. And also
we measured three cases-only a workstation, workstations built in cabinet opened door, workstations
built in cabinet closed door as below fig. 3. And the frequency domain noise level with NC line is
shown as below fig. 4 and fig. 5.(8) As fig. 5A, for high frequency noise, sound-absorbing material
will be applied on the door.(3,6)
Figure 3 Measurement results dB(A) (workstation)
INTER-NOISE 2016
6176
Figure 4 Measurement results with NC lines (workstation)
Figure 5 Measurement results with NC lines (workstation)
2.1.2 Ventilator It was measured to target the loaded ventilator in shelters basic backbone of similar size and
structure. In view of the adverse conditions, the noise in the Full RPM state of the ventilator was
measured. Measurements Case may operate only one Article ventilation fan, it was measured in a
state in which all doors were closed. The measurement results are shown as below fig.6. And the
frequency domain noise level with NC line is shown as below fig. 7.
INTER-NOISE 2016
6177
Figure 6 Measurement results dB(A) (ventilator)
Figure 7 Measurement results with NC lines (ventilator)
2.1.3 Air-conditioner The Air-conditioner is a 18,000 BTU/h-class military product. Similarly reflected in the
mechanical mounting conditions in the chamber wall, the noise was measured. The noise was
measured as air flow intensity "strong", "weak" mode. By applying the air duct outlet, the noise was
measured by a "strong" mode.
INTER-NOISE 2016
6178
Figure 8 Measurement results dB(A) (air-conditioner)
Figure 9 Measurement results with NC lines (air-conditioner)
2.2 Noise Level Estimation
The equivalent noise level will be calculated through related numerical formula considering
position with measure noise source data. Considering real effect, factors of formula will be modified
for estimation. Then, reflecting the impact of the distance spaced apart to the point you want to know,
and calculates the final composite noise.
2.2.1 Composite Noise Level Calculation Formula
Sound pressure level(SPL)
Sound pressure level(SPL) is a logarithmic measure of the effective pressure of a sound relative
to a reference value.(3) Sound pressure level, denoted Lp and measured in dB, is defined by (1)
INTER-NOISE 2016
6179
2
0
1010
P
PLogLp (1)
Multiple sources
The formula for the sum of the sound pressure levels of n incoherent radiating sources is
Inserting the formulas
In the formula for the sum of the sound pressure levels yields(3)
....log10...
log10
2
0
2
0
2
2
0
1102
0
222
21
10 dBp
p
p
p
p
pdB
p
pppL nn
(2)
,,...,2,1,10 102
0
nip
p dB
L
ii
(3)
.10...1010log10 10101010
21
dBL dB
L
dB
L
dB
L n
(4)
Distance
According to the inverse proportional law(5,9), when sound level Lp1 is measured at a distance
r1, the sound level Lp2 at the distance r2 is
2
12 1 10
2
10p p
rL L Log dB
r
(5)
2.2.2 Modified Factor for Noise Level Estimation Equations When comparing the noise measurement test results with the theoretical equation (eq.5) results
according to the distance, as Fig.10~Fig.11 below it shows a big difference in the slope. Thus, using
the coefficient of the slope difference between each measured value and the calculated value , it is
expressed as a modified theoretical calculation, as eq.6 and eq.12.
Workstation
Modified Equation for a workstation only (eq.6).
2
12 1 10
2
0.4 10p p
rL L X Log dB
r
(6)
Modified Equation for a workstation built in cabinet (eq.7)
2
12 1 10
2
0.4 10p p
rL L X Log dB
r
(7)
Modified Equation for two or three workstations built in cabinet (eq.8)
INTER-NOISE 2016
6180
2
12 1 10
2
0.5 10p p
rL L X Log dB
r
(8)
Figure 10 Noise Correction results (workstation)
Ventilator fan
2
12 1 10
2
0.2 10p p
rL L X Log dB
r
(9)
Figure 11 Noise Correction results(ventilator, air-conditioner)
Air-conditioner
Modified Equation for “strong” mode air-conditioner (eq.10)
2
12 1 10
2
0.4 10p p
rL L X Log dB
r
(10)
Modified Equation for “weak” mode air-conditioner (eq.11)
INTER-NOISE 2016
6181
2
12 1 10
2
0.35 10p p
rL L X Log dB
r
(11)
Modified Equation for “strong” mode air-conditioner applying the air duct outlet (eq.12)
2
12 1 10
2
0.35 10p p
rL L X Log dB
r
(12)
2.2.3 Consideration of Measured Results and Final Modified Factor As Fig.3, a workstation, a rack-type equipment, is measured at about 70 dBA at the front.
However, when attached to the cabinet assembly, it is measured at about 65.2 dBA due to the side
sound absorbing, when the front door applied, it is measured at about 51.4 dBA due to the front
sound absorbing material. As Fig.3B, when attached to the cabinet assembly, the workstations are
measured at similar dBA whether the number of workstation is two or three.
In Fig.3,Fig.6, Fig.8, it shows a large variation between measurements and numerical calculations
as the distance. Numerical calculations estimate the sound energy is assumed to be established in the
form of spherical wave from spreading to an open space with no reflective effect. But because of
states which the equipment is installed, the actual noise source is spread to go to unidirection from a
equipment location, it is estimated as a result, an acoustic reflection effect in the closed reflected
space. Also, the goal of the noise source measurement is to finally predict the noise in the enclosed
space of a shelter system. So, it was measured in three cases such as open area, closed area, anechoic
chamber. As a result, as shown in Fig.10, Fig.11, the result of measurement in a certain work area
(open area), such as workstations and the result of measurement in anechoic chamber, such as
air-conditioner was in a tendency to be corrected to 0.4~0.5 about distance attenuation slope factor,
in case of ventilator(enclosed space, at basic shelter), the result of measurement was in a tendency to
be corrected to 0.2 about distance attenuation slope factor. Because this noise measurement is the
purpose of calculating the composite noise within a certain closed space, for a conservative review, it
sets the attenuation slope factor as 2 for estimation. By utilizing Eq.4, Eq.9, the results of calculated
composite noise is shown in tab.4.(4,7)
Table 4 Multiple noise of cabinets (with door/airduct) [Unit ; dB(A)]
Units Cabinets
Ventilator Airduct #1 #2 #3
Workstation 51.8 51.8 - - -
VME rack 52.0 - - - -
UPS 45.0 - - - -
Data recorder - 45.0 - - -
Backbone S/W - 52.0 - - -
Server unit - - 52.0 - -
Data processor - - 45.0 - -
Ventilator Fan - - - 68.0 -
Air-conditioner - - - - 65.5
Multiple noise(Front) 60.4 56.9 57.8 72.8 68.5
Total multiple noise(1m) 70.5
Total multiple noise(2m) 69.3
INTER-NOISE 2016
6182
When illustrated reflecting properties of the noise in the Tab.4, it is shown in Fig.12.
Figure 12 Multiple noise Estimation (Table.4)
2.2.4 Actran Analysis and design modification For multiple noise analysis, an analysis model was constructed with Actran S/W as shown in
Fig13.
Considering only the reflection effect, in order to estimate the complex noise, noise sources were
assumed to be point source. And air damping was properly considered.
Figure 13 Actran Analysis Model
Figure 14 Actran Analysis Results
INTER-NOISE 2016
6183
As shown in Fig.14, between the cabinet and the walls, the ventilator fan noise is spread by the
gap. There was a gap which would spread ventilator fan noise through. So it is suggested
modifying the design, and block the noise.
3. COMPARISON OF ESTIMATION AND REAL RESULTS
As shown in Fig.15, Fig.16, measurements which were measured at pre-production and post
-production system in a similar position were compared. In the closed door case as Fig.15, it is
assumed that high frequency noise was decreased because of sound-absorbing material on the door.
Figure 15 Comparison of Before Measurement results with After (workstation)
Figure 16 Comparison of Before Measurement results with After (ventilator fan , air-conditioner)
Because of the noise characteristics change before and after manufacture, there are different
results. But for a conservative prediction method, it is meaningful to use the formula method and
Actran S/W.
As shown in Tab.5, The maximum value of analysis and experimental data have similar results,
within the range of 5%.
INTER-NOISE 2016
6184
Table 5 Comparison of analysis and test results
CASE POSITION(dBA)
#1 #2 #3 #4
Estimation results with formula 60.0 60.0 62.0 69.3
Estimation results with Actran S/W 65.5 67.0 66.8 67.7
Real results after manufacture 67.5 66.8 67.1 66.8
4. CONCLUSIONS
In this paper, we used the same or similar equipment to measure the noise source for estimation at
pre-manufacture, the actual multiple noise was predicted by noise-related formula applied modified
coefficient. The formula considered the reflection effect and was properly predicted.
Also we used the Actran S/W to analyze the multiple noise and we suggested the design to meet
Noise Limits Spec.
After manufacture, we measured real multiple noise at the ear’s position, and we compared the
analysis and test results. So, the maximum value of analysis and experimental data have similar
results, within the range of 5%.
REFERENCES
1. Departments and Agencies of the Department of Defense., 2012, “MIL-STD-1472G HUMAN
ENGINEERING”, p.151 ~ p.152.
2. Departments and Agencies of the Department of Defense., 1997, “MIL-STD-1474D NOISE LIMITS”,
p.12 ~ p.17
3. Hong, S. M., 1995, “HANDBOOK OF NOISE AND VIBRATION”, p.8 ~ p64
4. Yong-woon Choi, Jeong-seo Koo, Won-hee You and Hyo-in Koh, 2010, “A Study on the Increase of
Transmission Loss of Metro Train”, Transactions of the Korean Society for Noise and Vibration
Engineering, Vol. 20, No. 3, p257 ~ p262
5. Jin-Kyun Oh, Hye-Na Park and Jang-Ryul Sohn, 2009, “Development of the Noise Prediction Program
to apply in Construction Site”, Transactions of the Korean Society for Noise and Vibration Engineering,
Vol. 19, No. 4, p409 ~ p417
6. Daejoon Kang, W. S. Lee, J. W. Lee, J. K. Hong and Y. H. Jo, 2006, “Characteristics of Absorption
Performance of Sound Absorptive Materials according to Test Conditions”, Transactions of the Korean
Society for Noise and Vibration Engineering, Vol. 16, No. 7, p683 ~ p689
7. Seungki Hong, Jaehwan Kim, Kyutae Kim and Soogab Lee, 2007, “A Laboratory Study on Low
Frequency Noise Assessment based on Noise Acceptability Limit”, Transactions of the Korean Society
for Noise and Vibration Engineering, Vol. 17, No. 8, p736 ~ p740
8. Daejoon Kang, Jinhoi Gu and Jaewon Lee, 2009, “Sound Power Level of Electric Home Appliances
according to Measurement Method”, Transactions of the Korean Society for Noise and Vibration
Engineering, Vol. 19, No. 4, p335 ~ p346
9. Jin-Kyun Oh, Hye-Na Park and Jang-Ryul Sohn, 2009, “Development of the Noise Prediction Program
to apply in Construction Site”, Transactions of the Korean Society for Noise and Vibration Engineering,
Vol. 19, No. 4, p409 ~ p417
10. Daejoon Kang, Jinhoi Gu and Jaewon Lee, 2010, “Characteristics of Industrial Machinery Noise”,
Transactions of the Korean Society for Noise and Vibration Engineering, Vol. 20, No. 2, p160 ~ p165
11. Sang-Hyun Kim, Byung-Ho Lee, Sock-Kyu Lee, Jeung Lee and Dong-Suk Kang, 2015, “Multiple noise
analysis of the inside equipments in shelter system”, Transactions of the Korean Society for Noise and
Vibration Engineering, Vol. 25, No. 4, p255 ~ p265
INTER-NOISE 2016
6185