Sharing of RI
Non-Compliant Cases
1/<Total>
![Page 2: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/2.jpg)
Case 1
Proposed 6 blocks of 17-storey
condominium with basement (total 378
units) and communal facilities
![Page 3: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/3.jpg)
Non-Compliant 1
Breeching inlet between ME building and block T1
not located on external wall of building – SS575
Clause 2.3
3/<Total>
![Page 4: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/4.jpg)
Dry rising
main
breeching
inlets not
house in a
glass-fronted
box – Clause
2.3.2.4 SS575
Non-Compliant 2
![Page 5: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/5.jpg)
Emergency door
release not installed in
the direction of escape
at FFL – Clause
2.3.9(h)(iv)(2)
Non-Compliant 3
![Page 6: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/6.jpg)
Proposed development of a 7-storey nursing
home with lower first storey carpark
Case 2
![Page 7: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/7.jpg)
Non-Compliant 1
Bath room located along the naturally-
ventilated internal corridor was not
compartmented with 0.5-hour fire rated doors
and fitted with automatic self-closing device -
Clause 2.9.3(a)
![Page 8: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/8.jpg)
![Page 9: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/9.jpg)
Non-Compliant 2
Fire Command Centre provided with 1hr fire-
rated door instead of 2hrs - Table 6.4A
![Page 10: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/10.jpg)
![Page 11: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/11.jpg)
Non-Compliance 3
Internal corridor at the staff dormitory floor is not
cross-ventilated & ventilation opening is more
than 12m – Clause 2.9.3(c),(d) & (e)
![Page 12: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/12.jpg)
![Page 13: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/13.jpg)
Condominium housing development
comprising 4 blocks (E1, E2, E3, & F) of 3
storey flats and 6 blocks (A, B, C, D, G & H) of
5 storey flats (total 393 units) with basement
carparks and communal facilities
Case 3
![Page 14: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/14.jpg)
CB’s labels to all fire-rated doors not
provided – Clause 8 SS332
Non-Compliant 1
![Page 15: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/15.jpg)
Hydrant not readily accessible and clear of
obstruction – Clause 2.1.2(f) SS575
Non-Compliant 2
![Page 16: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/16.jpg)
Dry rising main breeching inlets not house in a glass-fronted box –Clause 2.3.2.4 SS575
Non-Compliant 3
![Page 17: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/17.jpg)
DR piping
passing through
basement
carpark not
protected –
Clause 2.2.3.1
SS575
Non-Compliant 4
![Page 18: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/18.jpg)
Fire engine
turning facilities
not readily
accessible
(obstructed by
pond, trees and
plants) – Clause
4.2.2(d)(ix)
Non-Compliant 5
![Page 19: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/19.jpg)
Hydrant not installed in accordance to the approved
plan (unit 01-56, H – 9-9)
Non-Compliant 6
![Page 20: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/20.jpg)
Services other
than sprinkler
piping mounted
above the fire
hydrant
pipework –
Clause 4.4.3(b)
Non-Compliant 7
![Page 21: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/21.jpg)
Proposed residential development comprising
of 2 blocks of 22-storey apartments, 3 blocks of
20-storey apartments and 8 units of strata
landed houses (total: 495 units) with one shop,
common basements carparks, landscape deck
& communal facilities
Case 4
![Page 22: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/22.jpg)
Insufficient distance for the
fire engine turning facility
between Blk 21 & 23 and in-
between strata landed
houses. The distance
measured at site is 18.5m &
18m respectively, not
meeting the 20m
requirement for the fire
engine turning facility. –
Cl.4.2.2(d)(v)
Non-Compliant 1
![Page 23: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/23.jpg)
![Page 24: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/24.jpg)
Insufficient hosereel coverage for the function
room at B1. Short of 7m hosereel coverage
when nearest hosereel was fully extended from
the nearest block 21. – Cl.6.2.8(a)
Non-Compliant 2
![Page 25: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/25.jpg)
![Page 26: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/26.jpg)
Distance between fire engine access road and
entrance of exit staircase at B2 exceeded 18m
for Blk 27 & 29. (19m & 28m) - Cl.4.2.2(a)(iii)
Non-Compliant 3
![Page 27: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/27.jpg)
28m
![Page 28: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/28.jpg)
>18m
![Page 29: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/29.jpg)
Unprotected opening within external exit staircase between Blk 21 & 23 – Cl 2.3.3
Non-Compliant 4
![Page 30: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/30.jpg)
Exit discharge not directly to external at exit staircases at 4 blocks – Cl 2.3.3
Non-Compliant 5
![Page 31: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/31.jpg)
Deadendexceeded46m. Site –52m – Cl4.2.2(d)(v)
Non-Compliant 6
![Page 32: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/32.jpg)
Blk
25
Hose reel not adjacent to exit staircase. –SS575 Cl 6.2.2.1
Non-Compliant 7
![Page 33: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/33.jpg)
Blk
23
![Page 34: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/34.jpg)
Case 5
Proposed erection of 4 storey single-user warehouse and ancillary office
![Page 35: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/35.jpg)
Non-Compliant 1
Dotted rectangle markings for PWD holding point on the floor not provided. – Cl 3.2.7 (d) Appendix 20
![Page 36: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/36.jpg)
Non-Compliant 2
Smoke-stop lobby and fire-fighting lobby not ventilated by permanent fixed ventilation openings in the external wall of the lobby. – Cl 2.2.13 (b)
![Page 37: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/37.jpg)
Non-Compliant 3Smoke vents not permanent open type in the warehouse at 2nd and 3rd storey. – Appendix 4 Cl 6.2
![Page 38: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/38.jpg)
Non-Compliant 4Smoke-stop lobby shall be located not more than 9m from an air-well or external recessed space of minimum clear area 93m² and minimum width of 6m. (site – 14.7m). - Cl 2.2.13 (b)
![Page 39: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/39.jpg)
Fire doors not
provided to
MDF room at
1st storey and
service shafts
on all floors. –
Table 6.4A
Non-Compliant 5
![Page 40: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/40.jpg)
Non-Compliant 6
Fire rated door for FCC not provided with 2hr rating (site -1hr rating). – Cl 6.4A
![Page 41: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/41.jpg)
Case 6
Proposed additions and alterations to existingunit at 3rd storey and attic
![Page 42: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/42.jpg)
One-way travel distance at
3rd Storey (including attic).
More than 13m to exit.
Non-Compliant 1
>13m
(about 14.5m)
![Page 43: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/43.jpg)
Staircase was
not protected
with fire-rated
wall and door
at 3rd Storey.
Non-Compliant 2
![Page 44: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/44.jpg)
Hosereel (at 3rd Storey)
was obstructing the
staircase leading to
attic storey.
Non-Compliant 3
![Page 45: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/45.jpg)
Case 7
Proposed change of use to KTV and additionsand alterations of existing internal layout tounit #02-01
![Page 46: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/46.jpg)
46/<Total>
![Page 47: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/47.jpg)
47/<Total>
![Page 48: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/48.jpg)
48/<Total>
![Page 49: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/49.jpg)
49/<Total>
Occupant passing through the spaces or
rooms occupied by other occupants or
tenants. - Clause 2.2.12(b)
Non-Compliant 1
![Page 50: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/50.jpg)
Case 8
Proposed erection of a 4-storey nursing homewith roof terrace and sub-basement car park
![Page 51: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/51.jpg)
FAP not accessible from fire engine accessway at 4th
storey and obstructed by companion suites unit. – Clause 4.2.3
51/<Total>
Non-Compliant 1
![Page 52: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/52.jpg)
Breeching inlets (sprinkler and dry rising main) not located
within 18m (site about 25m), not visible from the fire
engine access ways & not on external wall of building. -
Clause 4.3 & SS575 2.3.1.2
52/<Total>
Non-Compliant 2
![Page 53: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/53.jpg)
Staircases ST 02 landing width/depth that serve patient accommodation not comply (site measurement is 2.74m and 1.695m). – Table 2.5.1(a)(viii)(2)
53/<Total>
Non-Compliant 3
![Page 54: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/54.jpg)
Exit door opening into exit staircase (ST 02) impeded the egress of occupants when door swing outwards.(site measure is 890mm clearance) – Clause 2.3.9 (d)(i)
54/<Total>
Non-Compliant 4
![Page 55: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/55.jpg)
2nd, 3rd & 4th storey - Remoteness of 2 exit staircases is grossly under 1/3 maximum diagonal of the building footprint. (require 1/3D = 19.6m, provision = 8.5m). –Clause 1.2.60(a)
55/<Total>
Non-Compliant 5
![Page 56: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/56.jpg)
56/<Total>
![Page 57: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/57.jpg)
2nd, 3rd & 4th storey - 1-way travel distance exceeded from most remote point at Gridline E/27 and A/1 – Clause 1.2.60 (d)
57/<Total>
Non-Compliant 6
![Page 58: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/58.jpg)
58/<Total>
![Page 59: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/59.jpg)
Fresh air duct supply to the lobby (PL01 and PL 02) between area of refuge 1a not drawn directly from external of building and located inside the building. –Clause 7.1.4
59/<Total>
Non-Compliant 7
![Page 60: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/60.jpg)
60/<Total>
![Page 61: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/61.jpg)
FAD passing through this lobby not installed with fire damper (GL G to O+/14 to 15). – Clause 7.1.1(e)
61/<Total>
Non-Compliant 8
![Page 62: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/62.jpg)
Proposed new erection of 12 storey international school with multi-storey carpark and swimming pool
62/<Total>
Case 9
![Page 63: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/63.jpg)
No provision of e-lights in the whole block of MSCP – Clause 8.1.3
63/<Total>
Non-Compliant 1
![Page 64: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/64.jpg)
DR breeching inlet for DR 3-9 not installed on external wall of building. – SS575 Clause 2.3.1.2
64/<Total>
Non-Compliant 2
![Page 65: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/65.jpg)
Door (staircases/ FFL/ corridor) for re-entry floor locked with electro-magnetic device and not provided with emergency door release on both sides of entry.
Door to all exit access door not installed with electro-magnetic device.
Clause 2.3.9 (k)
65/<Total>
Non-Compliant 3
![Page 66: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/66.jpg)
No testing of e-lights carried out in the whole block of MSCP. – RI Regulation 1st Schedule Part 2
66/<Total>
Non-Compliant 4
![Page 67: Sharing of RI Non-Compliant Cases - SCDF](https://reader031.vdocuments.us/reader031/viewer/2022012100/6169d86c11a7b741a34c0255/html5/thumbnails/67.jpg)